PEFS Maintenance Manual V2.2
PEFS Maintenance Manual V2.2
Maintenance Manual
(Part Number 61432)
(CSIRO ActivFire Listing Number: afp-2118)
PEFS Maintenance Manual 2
PRE-FACE
Document History
This manual is an uncontrolled document. Chubb Fire Safety reserves the right to alter this manual at any
time in accordance with our policy of continuous development. Chubb Fire Safety welcomes feed back
regarding this manual and associated equipment. For further information or feedback, contact Chubb Fire
Safety on 1300 369 309.
GENERAL INFORMATION
Contents
PRE-FACE ...........................................................................................................................................................2
Document History...........................................................................................................................................2
GENERAL INFORMATION .......................................................................................................................................3
Contents .........................................................................................................................................................3
About this manual ……………………………………………………………………………………………………4
Warranty ………………………………………………………………………………………………………………4
Intended use..…………………………………………………………………………………………………………5
Introduction …………………………………………………………………………………………………………...5
Recommended tool list...................................................................................................................................6
MAINTENANCE SCHEDULE ....................................................................................................................................7
Daily................................................................................................................................................................9
6 Monthly......................................................................................................................................................11
Yearly ...........................................................................................................................................................15
5 yearly.………………………………………………………………………………………………………………23
MAINTENANCE REPORT ......................................................................................................................................24
SPARE PARTS ....................................................................................................................................................25
Cylinders & Cylinder Assemblies .................................................................................................................25
Discharge Components................................................................................................................................31
Detection & Actuation Components .............................................................................................................37
Monitoring & Control Components ...............................................................................................................50
VS CONTROL SYSTEM OPERATION & FAULT FINDING..........................................................................................55
Chubb Fire Safety Limited (“Chubb”) assumes no responsibility for the application of any systems other than
those addressed in this manual. The technical data contained herein is limited strictly for informational
purposes only. All information contained in this manual is based on the latest product information available
at the time of preparation and Chubb reserves the right to make changes at any time without notice. Chubb
believes this data to be accurate, but it is published and presented without any guarantee or warranty.
Chubb disclaims any liability for any use that may be made by the data and information contained herein by
any party.
PEFS systems are to be designed, installed, commissioned, inspected, maintained, and tested only by
qualified, trained personnel.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by
any means, electronic, mechanical, photocopying, or otherwise without the prior approval of Chubb Fire
Safety.
IMPORTANT
Please note this manual contains warnings and cautions against some specific service methods which could
cause personal injury. It must be understood that these warnings cannot cover all ways in which service
might be done. Anyone using service procedures whether or not recommended by Chubb Fire Safety must
satisfy himself thoroughly that neither personal safety nor equipment safety will be jeopardised. All
information contained in this manual is based on the latest product information available at the time of
preparation. Chubb Fire Safety reserves the right to make changes at any time without notice.
Warranty
Chubb warrants to the original system purchaser (“Customer”) that each new PEFS system is free from
defects in material and workmanship under normal use for a period of twelve (12) months from the date of
commissioning. This warranty does not cover damage resulting from a party’s negligence, fault, misuse,
neglect or incorrect use of the product, abuse or fair wear and tear. In addition, the warranty does not cover
work required to be done to repair a defect or damaged caused by vandalism, fire, water, damage, power
surge or other circumstance outside of Chubb’s control. This warranty is conditional upon documented
evidence of proper maintenance, performed in accordance with the PEFS Owner’s Manual and Maintenance
Manual by qualified and trained personnel, using replacement parts that conform to original design
specifications. This warranty will be voided upon modification of the (i) installed and commissioned PEFS
system; (ii) use, condition and environment of the Customer’s equipment. Chubb will have no liability for any
statements, representations, guarantees, conditions or warranties not expressly stated in writing by Chubb.
Nothing in this warranty excludes, restricts or modifies the application of the provisions of any statute
(including the Trade Practices Act 1974 (Cth)) where to do so would contravene that statute or cause any
part of this warranty to be void.
Where Chubb breaches its obligations under this warranty, Chubb agrees at its sole discretion to elect to re-
supply the PEFS system again or to the replacement or repair of the PEFS system. To the extent
permitted by law the aggregate liability of Chubb to the Customer whether in contract, tort (including
negligence) or otherwise, will be limited to the value of the payment received by Chubb from the purchaser
in respect of the purchase of PEFS.
Notwithstanding anything else in this document, Chubb will not be liable for:
(a) any indirect, consequential or special or economic loss, cost, liability, damage or expense howsoever
arising; or
(b) loss of profit, loss of use, loss of income, loss of rental or other benefit, loss of production, loss of actual
or potential business opportunity or loss of reputation.
Intended use
The PEFS system is a fire suppression system, installed as part of a fire risk reduction strategy, as defined
in the PEFS Risk Assessment. As such, it is designed to suppress a fire occurring in the specified risk area
only.
Introduction
Mining, Off-Road, Forestry and Construction equipment operating in harsh outdoor environments can be
subjected at any time to the threat of fire, which may spread rapidly through the equipment endangering life
and resulting in damage to major capital equipment and loss of production. The installation of a fire
detection and suppression system is essential to minimise the risk to both operator and equipment.
PEFS is a Pre-Engineered Foam Spray system designed specifically to cope with the harsh operating
conditions experienced by mobile and transportable equipment. PEFS systems consist of pressurised
cylinders containing foam solution, actuation devices to initiate discharge and a discharge network
containing nozzles to direct the foam spray on the hazard. PEFS systems may be configured for both
manual and automatic operation.
PEFS systems offer impressive fire suppression capabilities through the combination of FOAM discharged in
the form of a finely atomized SPRAY. Strategically positioned nozzles direct the high velocity foam spray
and provide “three dimensional” fire fighting properties, allowing the system to suppress pressure fires such
as might occur from a ruptured fuel or hydraulic line. The small droplets of foam are extremely efficient at
absorbing large amounts of heat and turn to steam which further enhances the three dimensional fire
fighting properties of the PEFS system. Once discharged, the foam is also effective in suppressing spill or
pool fires which may result from the collection or leakage of fuel. The resulting foam blanket provides post
fire securement.
Australian Standard AS5062 Fire Protection of Mobile and Transportable Equipment details the
requirements for fire protection systems used in these applications. Chubb’s PEFS system has been tested
and approved by CSIRO and, when installed and commissioned in accordance with the requirements of this
manual, complies with AS 5062.
Glossary of terms
Description
Tape measure 25mm
Portable tube bender (suit 6.0mm & 12.7mm OD tube)
Flaring tool – 45° 1/8” – 3/4" tube sizes
Angle grinder 100 mm
Drill (Heavy duty) - 12.7 mm chuck
Socket set - metric 4mm – 19mm, A/F 3/16” – 15/16”
Spanner Set - metric 7mm – 22mm, A/F 1/4" – 1”
Files - Round and Flat (medium bastard) 250mm
Hand / Drill type deburring tool 2-14mm
Hex Wrench set (Allen keys) Metric & Imperial
Portable drop saw and spare discs
Ultra Bi Hacp Cobalt 12Dx32Tx10mm Tap
Hacksaw and spare blades
Stanley knife and spare blades
Pressurising unit with lockable chuck
Nitrogen cylinder c/w regulator
15 metre extension lead (10 amp)
Thread tape M6x1.0 (x2), M8x1.25 & M10x1.5
Shifters 250mm & 450mm
Tee handle wrenches 5mm
Screwdriver set 13 Piece
Hammer - Ball Pein
Side cutters 250mm
Funnel and measuring jug
Deutsch connector crimping tool.
Multimeter
Cable Stripper
Crimp Pliers (Automotive lug type)
Drill Set 1mm – 13mm x 0.5mm (high speed)
Holesaw set
Step ladder
Digital scales
Pliers (combination) 225mm
Multigrips 250mm
Cable cutters
Cutting compound
Loctite 567 hydraulic thread sealant
Molykote 111 lubricant
Thread tape
Assortment of high tensile bolts, nuts and Nylok type nuts
Assortment of flat and spring washers
Nitrogen cylinders and regulator
Pressure packs of Zinc based primer
Assortment of electrical lug connectors.
Assortment of Deutsch connectors. (3, 4 & 12 Pin)
Assortment of cable glands
Assortment of screws (self taping)
Radox fire retardant cable twin and 4 core .75mm
Portable Welder (VRD Inverter)
Welding Rods
Welding safety equipment
Grinding face shield
MAINTENANCE SCHEDULE
The following maintenance schedule is a guide and sets out minimum requirements only. In all cases, local
conditions where the system is fitted should be taken into consideration when setting maintenance
frequencies. For example, in harsh environments the yearly service may need to be carried out every 6
months.
The daily inspection items should be completed by the operator prior to equipment start-up or shift change.
6 Monthly Yearly
1 Nozzles - clean 9 9
Daily
System Pressure
Check the reading on the pressure indicator located on the cylinder valve. The pressure should be 1350kPa
as indicated in the green segment of the indicator.
On LOP systems, check the reading on the pressure indicator located on the manual LOP actuators. The
pressure should show 1350kPa in the green segment of the indicator.
If system is low on pressure, the source of the leak should be identified and rectified prior to re-pressurising
the system. If the system pressure shows 0 kPa, it is likely the system has been discharged and will need to
be refilled.
Manual Actuators
Check that all actuators are secure, clean, undamaged, clearly visible and accessible.
LOP Systems
Check that the pull pins are in place on all LOP manual actuators.
ROP Systems
Check that the pull pins are in place on all ROP manual actuators. Check that the pull pin is in place on all
ROP cylinder valves.
If a pull pin is not in place, check the cylinder pressure to ensure that the system has not been activated.
If the system has been activated, all the CO2 Cartridge should need to be inspected and replaced if
necessary.
VS Control Systems
Check that the pull pins are in place on all VS Control System manual
release units.
If a pull pin is not in place, check the cylinder pressure to ensure that the
system has not been activated
a. Inspect the VS display panel and check that only the green
POWER LED is illuminated
b. Press and hold the “TEST” button and confirm that:
• All LED’s on the display illuminate.
• Audible alarm sounds.
c. Release the “TEST” button and check that only the green
POWER LED is illuminated.
Six Monthly
The following items are required to be completed in addition to the daily service items.
Distribution System
• Check that all nozzle seals are in place and are clean.
• Check that nozzles are correctly aimed and aligned.
• Check that all discharge hose, tubes and fittings are undamaged and secure.
Actuation System
• Check that all pneumatic actuation hoses, tubes and fittings are undamaged and secure.
• Check that all electrical actuation wiring and connections are undamaged and secure.
Note: Care must be taken when inspecting LOP actuation detection tubing, hose and fittings. Loosening
of any connections may cause the PEFS system to discharge.
Detection System
• Check that all pneumatic detection hoses, tubes and fittings are undamaged and secure.
• Check that all electrical detection wiring, LHD (Linear Heat Detection) cable and connections are
undamaged and secure.
Instruction Labels
• Check that all manual release, system warning and instruction and cylinder labels are in place,
visible and legible.
WARNING: The cylinder is a pressure vessel. Do not remove any parts from the cylinder unless
the cylinder is depressurised first.
To safely depressurise the cylinders the following procedure should be followed: New LOP picture
needed
2
Manual Actuators
• Check that all manual actuators are secure, clean, undamaged and accessible.
• Test the operation of each actuator.
LOP Systems
• Remove the cover from each LOP actuator and check that the SureSpray nozzle seal is in tact.
Note: Care must be taken when inspecting LOP actuation detection tubing, hose and fittings. Loosening
of any connections may cause the PEFS system to discharge.
ROP Systems
Check the contents of the CO2 cartridge fitted in each ROP manual actuator.
CO2 Cartridge
VS Control Systems
1. Check that all electrical manual release units incorporated into the VS control system are accessible
and in good condition.
2. For those systems using solenoid activation, remove the solenoid coil from the solenoid valve and place
the coil on a spare solenoid valve or valve stem.
3. Remove the back cover from the VS display panel and move the Maintenance Isolate DIP switch
(switch 7) to the ON position. Confirm the ISOLATED LED on the VS display panel is illuminated.
System Reset
DIP Switches
The isolate switch isolates the actuation, auxiliary alarm and shutdown outputs from the VS control
module. All VS control module inputs remain enabled along with the audible alarm unit output, fault
output and VS display panel LED’s. In this state the ISOLATED LED on the VS display will remain
illuminated and the audible alarm unit will beep once per minute. This switch allows testing of manual
release and detection inputs as well as fault conditions without causing discharge of the PEFS system,
initiating equipment shutdown or auxiliary alarm outputs.
4. With the system isolated, operate each electrical manual release incorporated in the VS control system
and confirm the ALARM LED on the VS display panel illuminates and audible alarm unit operates.
5. Reset the VS control system after operating each manual release by pressing and holding the RESET
button (located on the display panel circuit board) for 2 seconds.
6. After all manual release units have been tested return the Maintenance Isolate DIP switch to the OFF
position and confirm the ISOLATED LED on the VS display panel is extinguished.
7. One final test should be completed without the system being isolated to ensure the solenoid coil is
energised by the VS control system when in alarm. Operate one of the electric manual releases and
confirm that the solenoid coil is energised.
Note: As the coil is only energised by the control system for 30 seconds, it may be necessary to
have two people complete this task.
8. Reset the VS control system by pressing and holding the RESET button (located on the display panel
circuit board) for 2 seconds.
10. Re-fit the solenoid coil to the solenoid valve on the PEFS system.
Battery Condition
The VS control system monitors the usage of the internal battery during operation. A visual indication of the
remaining battery capacity can be obtained by following the procedure below.
RS232
connection
Battery reset
To replace the internal battery it is necessary to remove the circuit board from the control module housing.
7. Confirm the battery life has been reset by pressing and holding the “fault” and “battery life reset”
push buttons on the circuit board. All LED’s should illuminate. More detailed battery usage
information can be obtained using the control module’s RS232 interface and “get battery info”
command.
NOTE: As the internal battery is used to energize the actuation output, it is critical that the battery
life monitor only be reset when installing a new battery pack.
PEFS Maintenance Manual, version 2.1, September 2007
© Copyright 2007 Chubb Fire Safety Limited
PEFS Maintenance Manual 15
Yearly
VS Control System – Function Test
1. For those systems using solenoid activation, remove the solenoid coil from the solenoid valve and place
the coil on a spare solenoid valve or valve stem.
2. Operate a manual release unit.
3. Confirm the ALARM LED and amber SHUTDOWN LED on the VS display panel is illuminated and the
audible alarm unit sounds.
4. Confirm the solenoid coil is energised by checking for a magnetic field.
Note: As the coil is only energised by the control system for 30 seconds, it may be necessary to
have two people complete this task.
5. Reset the VS control system by removing the back cover from the VS display panel and pressing the
RESET button (located on the display panel circuit board) for 2 seconds.
6. Confirm the ALARM and SHUTDOWN LED’s on the display are extinguished.
7. Repeat Steps 3 to 6 by introducing a short circuit on the detection circuit.
8. Refit the back cover on the display panel.
9. Check all actuation wiring supports and connections are secure.
In conjunction with the test detailed above, complete the following items to confirm the correct operation of
the VS control system.
Equipment Shutdown
Record the time delay between the VS control system registering an alarm and the shutdown output being
energised. Confirm the equipment shutdown operates and interfaces correctly. Confirm this time matches
that specified on the commissioning documentation for the system.
Shutdown Delay
Confirm the DELAY button becomes enabled during the final ten seconds of the shutdown delay period and
record the shut delay extension period. Confirm this time matches that specified on the commissioning
documentation for the system.
Discharge delay
Record the time delay between the VS control system registering an alarm and the solenoid output being
energised. Confirm this time matches that specified on the commissioning documentation for the system.
Detection mode
Confirm the detection mode setting (single circuit or dual circuit) of the VS control system is correct.
Auxiliary outputs
Test and confirm the correct operation of any auxiliary alarm and fault indicators fitted to the auxiliary alarm
and auxiliary fault outputs.
Test and confirm the correct operation of the cylinder low pressure switch input by disconnecting the
electrical connector on the pressure switch. Confirm the FAULT LED on the VS display panel and audible
fault alarm unit operates.
Test and confirm the correct operation of the cylinder low pressure switch input by disconnecting the
electrical connector on the pressure switch. Confirm the DISCHARGED, FIRE and SHUTDOWN LED’s
illuminate and the audible alarm sounds.
At the completion of function testing, replace the internal battery with a new unit and reset the battery life
counter as detailed in the previous section.
NOTE: Detailed information on the configuration and operation of the VS control system can be
found at the end of this manual.
1. Discharge the PEFS system using one of the available actuation or detection options.
2. Confirm all nozzle seals release and nozzles discharge.
3. Check that the nozzle discharge patterns cover the fire hazard area as specified in the commissioning
documentation.
4. Confirm the DISCHARGED LED on the VS display panel illuminates.
5. Record the Effective Discharge Time (EDT) and compare it to the EDT recorded during commissioning.
6. Check that all alarms, actuation and shutdown functions operate as intended.
7. Service PEFS cylinder valves.
8. Refill and Pressurise system.
9. Reset the VS control system by pressing the RESET button on the display panel printed circuit board
and refit the back cover to the display panel.
WARNING: The cylinder is a pressure vessel. Do not remove any parts from the cylinder prior to
depressurising the cylinder.
6
2
7
4
3 8
4 7
12 8
2
9
3
1
10
11
Prior to replacing any LOP detection tubing ensure the system is depressurised by depressurising the PEFS
cylinders using the schrader valve fitted to the cylinder valve fill port.
NOTE: Do not loosen any hose connections or fittings in the LOP actuation system while the system is
pressurised. This will cause the system to discharge.
After having depressurised the PEFS cylinders, replace each length of LOP detection tubing leak test the
detection network and re-pressurise the system to 1,350 kPa.
ROP Systems
Replace the wick in each Pyrotube detector using the procedure detailed below. Alternatively, each
Pyrotube detector can be completely replaced if it is not possible to remove the wick from the installed
Pyrotube detectors.
1
2
WARNING: Pyrotube Wick is a flammable item. Treat its disposal with caution.
Pyrotube Wick should be destroyed only by competent personnel. Do not place in rubbish bins or with
commercial waste for disposal until Pyrotube Wick has been rendered safe by completing the procedure
below.
1. Ensure that a portable Dry Chemical Fire Extinguisher is positioned close by.
2. Unwind the wick on a non-flammable surface in an outdoor area away from any flammable items.
3. Cut thread connector from one end
4. Light the cut end of the wick. The wick will burn progressively along its entire length at approximately 5
seconds per metre.
Notice: Water will not extinguish burning wick. Pyrotube Wicks do not require oxygen to burn.
PEFS Maintenance Manual, version 2.1, September 2007
© Copyright 2007 Chubb Fire Safety Limited
PEFS Maintenance Manual 20
NOTE: Do not loosen any hose connections or fittings in the LOP actuation system while the system is
pressurised. This will cause the system to discharge.
After having depressurised the PEFS cylinders, service each LOP actuator as follows.
ROP Systems
3
1
3
2
4 3
1
4
1. Remove actuation hose/fitting from check valve fitted to the ROP cylinder valve (1).
2. Fit a plug to the actuation hose/fitting removed from the check valve.
3. One section at a time, connect a source of nitrogen or compressed air to the end of each actuation
network section (3).
4. Remove the actuation hose from each check valve (4) in the manifold block (other than the section
being tested).
5. Pressurise the section being tested to 1,350kPa and inspect for leaks. Leak test all connections and
check valves with liquid leak detection solution (allow to sit for at least 5 minutes).
6. Repeat steps 3 – 6 until section of the ROP actuation and detection system has been tested.
7. Release pressure in actuation network and re-instate all actuation hose connections to their original
state.
PEFS Maintenance Manual, version 2.1, September 2007
© Copyright 2007 Chubb Fire Safety Limited
PEFS Maintenance Manual 21
Pressurising
LOP Systems
LOP systems are pressurised using the schrader valve fitted on any of the manual LOP actuators.
NOTE: Do not pressurise LOP systems using the schrader valve on the filler port assembly (1) of the PEFS
cylinders. This will cause the cylinder to discharge.
Note: LOP systems may also be pressurised from using a “recharging point” fitted anywhere in the LOP
actuation network and following steps 3 – 7 detailed above.
PEFS Maintenance Manual, version 2.1, September 2007
© Copyright 2007 Chubb Fire Safety Limited
PEFS Maintenance Manual 22
ROP Systems
ROP cylinders can be pressurised using the schader valve fitted to either the filler port Assembly (1) or the
cylinder valve.
5 Yearly
PEFS cylinders must be hydrotested every five years at a licensed test station. Following hydrotesting of
each cylinder complete the following service items:
1. Install burst disk to cylinder. Apply Loctite 567 thread sealant to threads prior to installation.
2. Check o-rings on fill tube and filler plug assembly (1) are clean. Replace damaged o-rings.
3. Install fill tube and filler plug assembly to cylinder.
4. Check cylinder valve neck o-ring is clean. Replace o-ring if damaged. Lubricate o-ring with Molykote
111.
5. Fit syphon tube to cylinder valve
6. Fit cylinder valve and syphon tube to cylinder.
7. Install new label to cylinder or clean existing label.
8. Install cylinder to cylinder bracket.
9. Install and connect pressure switches.
10. Connect discharge hose to cylinder valve.
11. Connect actuation hoses to cylinder valve.
12. Refill and pressurise cylinder.
MAINTENANCE REPORT
Inspection and Maintenance Report for PEFS Pre-Engineered Foam Spray Systems
Work Order Number: Date:
Client Information
Customer Name: Contact Name:
Customer Address:
Telephone: Mobile: Fax:
Equipment Information
Equipment Type: Equipment Make:
Equipment Model: Equipment Serial No.:
Equipment Location:
AFFF System
Operating Mode: LOP ROP
Cylinder Size: Qty: Serial Numbers: Manufacture Date:
Qty Nozzles: Qty Manual Actuators: Fire Alarm Panel: Standard Shutdown None
Service
THIS INSPECTION IS TO BE CONDUCTED IN ACCORDANCE WITH PEFS MAINTENANCE & PARTS LIST MANUAL (P/N: 61416)
Item Service 6 Mnth 12 Mnth Defect Report
9 Cylinders – Check
11 Labels – Check
16 Cylinders – Inspect
SPARE PARTS
Cylinders
PEFS cylinders are manufactured from 304 stainless steel to the requirements of AS3509. PEFS cylinders
have a fill ratio of 80% of their water capacity and are pressurised to 1,350kPa.
H
H
H
H
Cylinder Assemblies
Two types of cylinder assemblies (Rise of Pressure [ROP] and Loss of Pressure [LOP]) are available for use
in PEFS systems depending upon the detection and actuation mode selected.
CYLINDER VALVE
118554
CYLINDER VALVE
110269
New LOP picture
needed
O’RING
107656
FILLER PLUG
ASSY
23100
FILL TUBE
SIPHON TUBE
ASSY
CYLINDER
BURST DISC
112255
Cylinder Sub-assemblies
Cylinder sub-sssemblies come with burst disk, fill tube and filler plug assembly
Cylinder Sub-Assembly
Cylinder Size
Part Number
C23 109508
C30 109510
C45 109511
C65 109512
C106 111045
Fill Tubes
Cylinder assemblies are fitted with a fill tube to assist in the correct filling of cylinders. The cylinders are
filled to the correct volume when the foam solution level reaches the bottom of the fill tube. Each cylinder
size has a different length fill tube.
Siphon Tubes
PEFS cylinder assemblies are fitted with flexible siphon tubes to allow the cylinders to be mounted either
vertically or horizontally. The siphon tubes are manufactured from reinforced flexible hose with brass end
fittings.
Foam Concentrate
Only Chubb 3% AFFF foam concentrate (20 litre drum part number 86280) is to be used for filling PEFS
systems. Tables 3 & 4 detail the correct fill quantities for each size PEFS cylinder. PEFS systems are
suitable for use in suppression of class A (ordinary combustible) and class B (flammable liquid) fires.
The ROP valve consists of a chrome plated brass body and incorporates an integral manual and pneumatic
actuator.
SOCKET HEAD
SCREW
110265
SPRING
WASHER
103194 CAM
110249
GRUB SCREW
CHECK VALVE 110264
103222
PULL PIN
104657 MANUAL ACTUATOR BODY
110245
SPRING PLUG
110255 118551
(Port for 127379 200kPa Fire
Alarm/Discharge Pressure
Switch)
CAP
40503 PLUG
118551
(Port for 127361 900kPa
SCHRADER VALVE Cylinder Low Pressure Switch)
94001
PRESURE
INDICATOR VALVE BODY
103850 110243
PLUG
VALVE STEM 103604
ASSEMBLY
110263
SPRING
110273
The LOP valve consists of a stainless steel valve body with brass piston.
SOCKET HEAD
SCREW
SCHRADER VALVE 118537
94001
SPRING
CAP WASHER
40503 118538
NIPPLE
128817
CAP O’RING
XXXXX 90022
PISTON
118534
O’RING BS211
118548
O’RING BS005
103856
CHECK VALVE
118536
O’RING BS208
118549
RETAINER
PLUG 118535
118551
(Port for 127361 900kPa Cylinder
Low Pressure Switch)
PLUG
118551
(Spare port for 127379
200kPa Fire Alarm/Discharge
Pressure Switch)
PRESURE
INDICATOR
103850 BODY
118532
Cylinder Brackets
PEFS cylinder brackets are manufactured from welded carbon steel and painted black.
Figure 7 – C45 & C65 cylinder bracket Figure 8 – C106 cylinder bracket
(part number 128737) (part number 128738)
DISCHARGE COMPONENTS
Stainless Steel Tube
½”’ Stainless Steel tube should be used in the fire hazard areas to supply the PEFS discharge nozzles. The
tube is 12.7mm outside diameter x 0.9mm wall thickness annealed seamless type 304 or 316 stainless steel
tubing (part number 112108 for 2m lengths).
Discharge Hose
All hose used in PEFS discharge systems must be flame resistant to U.S.MSHA 2G requirements. Use of
hose in fire risk areas should be kept to a minimum and avoided if possible. In areas where discharge hose
may be subjected to abrasion or impact, hose protection spiral guards should be used.
SureSpray discharge nozzles are non-aspirated, solid cone, spray nozzles with a 1/4” BSP inlet thread.
Surespray nozzles are of all brass construction and comprise 4 parts, including a brass foil seal.
1 1. nozzle body
4 2. pintle
3. foil seal
4. foil retaining cap
3 2
Upon system discharge, the foil seal is designed to rupture and the support pintle will be displaced from the
nozzle outlet allowing the nozzle to discharge foam solution. Replacement of the foil and pintle is required
following discharge.
NOTE: As the foils are very thin, care must be taken to ensure that only a single foil is installed when
servicing SureSpray nozzles.
PEFS Maintenance Manual, version 2.1, September 2007
© Copyright 2007 Chubb Fire Safety Limited
PEFS Maintenance Manual 32
Two types of SureSpray nozzles, BM17N and BM16W, are available. The BM17N has a narrow discharge
pattern and is suitable for applications where the nozzle is mounted up to 1,000mm from the target, whilst
the BM16W has a wider discharge pattern for close range applications where the nozzle is mounted less
than 450mm from the target.
Nozzle Kits
A range of standard nozzle discharge configurations are available in the form of nozzle kits.
Nozzle kit single straight (part number 115371) Nozzle kit single end 90° (part number 115151)
ELBOW
SOCKET 112138
112143
Nozzle kit single straight 90°(part number 115152) Nozzle kit double straight 90° (part number 115153)
TEE
112132
TEE
112132
ELBOW
112139
ELBOW
119336
TEE
REDUCING 112183
BUSH
112144
SOCKET
112143
SOCKET ELBOW
112143 TEE 114632
112183
The hose and tube fittings supplied by Chubb meet minimum levels of quality and corrosion resistance.
Fittings from non-approved suppliers may not offer the same levels of quality and corrosion resistance and
could result in blockage of hose or tubing due to corrosion.
Cap/Nut 112145 3/4” JIC Nut & Sleeve to suit 1/2” Tube
128748 3/4” JIC (m) x 3/4” JIC (f)swv x 3/4” JIC (m)
115151
112108
Nozzle Assy.
Single, Tee
115150
114609
Tee
118100
Hose
112129
Nipple
The Pyrocord has an installed life of 1 year and must be replaced annually as part of the regular
maintenance routine.
Table 11 – Pyrotube (Pyrotubes are supplied with JIC flared fittings without the Pyrocord.)
Pyrocord
Pyrocord (part number 93501) is supplied separately to the Pyrotube Assemblies and needs to be cut to size
and inserted into the Pyrotube Assemblies at the time of installation.
Pyrotube Filter
A Pyrotube filter must be fitted in each Pyrotube detection circuit to prevent debris from the burnt Pyrocord
element fouling other actuation system components. The filter is to be fitted at the junction of the Pyrotube
detector and the connecting tube or hose directing pressure to the pneumatic actuator on the cylinder valve.
The Pyrotube Filters have a 230µm mesh element that may be removed for cleaning or replacement.
7/16” JIC
Male Flare
ROP manual actuators are manufactured from stainless steel and contain a CO2 cartridge. When the strike
button on the actuator is struck, the CO2 cartridge is pierced and the pressure released is used to operate
the cylinder valve’s pneumatic actuator.
BOLT
SPRING WASHER 91314
94234
ORING
90011 NUT
O’RING 92327
90222
CO2 CARTRIDGE ORING
16004 94814
BUTTON
26172
SLEEVE
26170 BODY
26171
PISTON
26173 LABEL
(NOT SHOWN)
66517
BRACKET
76818
Figure 15 – Remote manual ROP actuator (part number ES9106-B Surface/Flush Mounted)
(Bracket 76818 removed for flush mount application)
Check Valve
The check valve comes with 1/4” tube JIC flare and 1/4” NPT male thread designed to fit into actuation
manifold blocks.
LOP detection tubing has an installed life of 1 year and must therefore be replaced annually as part of the
regular maintenance routine.
LOP Detection Tubing must be securely mounted using pipe clips with a synthetic sheathed surface to avoid
chafing. The distance between support clips should be 500mm or less. The LOP Detection Tubing has a
minimum internal bend radius of 50mm.
The manual LOP actuator is suitable for internal and external vehicle mounting. Manual LOP actuators are
manufactured from red powder coated stainless steel housing and incorporates a pressure gauge. It is
designed for mounting on a vertical surface, using 4 x M6 fasteners.
NOTE: Care must be taken when fitting manual LOP actuators to a LOP Detection System. These
actuators must be fitted before pressurising the cylinder.
Listed below are fittings required to assemble most configurations of LOP and ROP detection and actuation
networks.
Hose Fittings 9344220357 1/4” Hose x 7/16” JIC (f)swv Field Attachable
Support
119226 LOP Tubing internal support spigots
Spigots
128753 7/16” JIC (f) x 7/16” JIC (m) x 7/16” JIC (m)
Tee
128749 7/16” JIC (m) x 7/16” JIC (f) x 7/16” JIC (m)
Elbow
114568 45° 7/16” JIC (m & f) swv
Nipple
112148 1/4” NPT x 7/16” JIC
128817 1/8” NPT x 7/16” JIC
Table 15 – fittings common to both ROP & LOP detection & actuation systems
Actuator location and instruction signs are required to be located adjacent to each manual action point.
Figure 18 – Manual actuator location label - self adhesive, 150mm x 70mm (Part number 66133)
Figure 19 – Manual actuator instruction sign - PVC, 75mm x 200mm (Part number 66509)
Linear heat detection (LHD) cable may be used to automatically activate both ROP and LOP PEFS systems.
LHD cable is non-resettable. Once the insulation has melted, the melted section must be replaced. Either
the entire length of cable or just the melted section can be replaced.
Electric Actuation
Electric actuation of both ROP and LOP PEFS systems is achieved using a 12V DC10W solenoid operated
valve. The solenoid valve is connected VS Control System and when energised will initiate discharge of the
PEFS cylinders.
EARTH
1 2
NEUTRAL ACTIVE
ACTUATION ACTUATION
SOURCE SOURCE
ROP and LOP solenoid valve assemblies are available, complete with the necessary fittings required to fit
them. The LOP solenoid valve assembly may be fitted anywhere in the LOP actuation network and includes
a SureSpray nozzle fitted to the solenoid valve outlet to prevent blockage of the valve outlet by
contaminants. Care should be taken to direct the outlet of the solenoid valve so that its discharge does not
cause a hazard to personnel.
The ROP solenoid valve assembly is to be fitted to the check valve located on the pneumatic actuator body
of the ROP cylinder valve. A suitable length hose must be assembled to connect the inlet of the solenoid
valve to the cylinder filler valve port (see figure 25).
LOP actuation
network
Connect to
hose from
cylinder filler
port
Connect to
check valve on
pneumatic
actuator body
128756
Hose
128817
Nipple
Manual CO2 Actuator
ES9106-B
118551
Plug
128762
Manifold Block
Filter
Check Valve
119568
128760
103222
128817
Plug
Nipple
Pyrotube Assy
& Wick
Coupling
117811
ES9014-E ROP
solenoid valve
assy.
Check valves
103222
ROP solenoid
valve assy
ES9014-E ROP actuation hose
Tee 128749
Coupling 128763
Spigot 119226
Hose Nipple
Coupling 9344220356 112148
9344220357
Plug
118551
PEFS Maintenance Manual
Figure 27 – Typical LOP combined solenoid and pneumatic detection & actuation arrangement
LOP Solenoid valve Assy. ES9014-D
Note: may be located at any point in
the LOP actuation network
PEFS Maintenance Manual 48
Check valve
103222
Check valves
103222
Figure 28 - multiple ROP cylinder - combined solenoid and pneumatic actuation arrangement
Hose and tubing used on PEFS actuation and discharge systems must be properly supported and a range of
supports for use with hose and stainless steel tubing are detailed in table 16. Any bolts or welding used for
installation must be in accordance with the customers or vehicle manufactures specifications.
Nozzle Bracket 104592 Size: 76x51x5 angle, 50mm width, Zinc plated
The pressure switches have a 1/8”NPT connection, are configurable for NO or NC, and are provided with a
IP65 rated Deutsch DTM series connector.
The pressure switches are connected directly to the cylinder valve as shown on figure 29.
VS Control System
The VS Control System comprises a control module, a remote display panel and audible alarm unit. The
display panel provides visual indication of system status, alarms, and faults and also allows manual
extension of the equipment shutdown delay.
VS Display Panel
VS Control Module
The control module comprises an IP67 rated enclosure and IP69 rated Deutsch DT series connectors.
Battery Pack
The audible alarm unit is IP65 rated and comprises buzzer, c/w end of line components required for the
supervision of the buzzer circuit, fitted in a metal enclosure.
The manual release unit consists of an IP65 rated metal enclosure with a glanded cable entry. It
incorporates a switch fitted with a series and a parallel EOL resistor to allow it to be monitored for both open
and short circuit faults.
The EOL resistor is used to terminate LHD cable detection circuits. The EOL allows the VS control system
to monitor the integrity of the detection circuit. The EOL resistor is inside a brass housing fitted with metal
cable gland.
Jiffy splice cable connectors are used to join field wiring (e.g. radox cable to LHD cable). The connectors
are IP65 rated and are suitable for use with Deutsch connector pins and sockets. Where Jiffy Splice
connectors are used to join to separate lengths of radox cable, the connectors must only be installed outside
the fire hazard area.
Two strips of 3M dual lock tape are used to mount the VS display panel.
The connector kit is used to terminate and connect field cabling, and
that from the VS display panel, to the VS control module.
The VS control module includes an RS232 connection to allow interrogation and download of event history.
Firmware updates can also been uploaded using the RS232 connection.
Fault Conditions
Audible and visual fault indications, consisting of illumination of Fault LED and sounding of the buzzer once
every 10 seconds, will be generated by any of the following conditions:
• Open circuit on either detection circuit input
• Open or short circuit on manual discharge input
• Open or short circuit on actuation circuit
• Open or short circuit on the buzzer circuit
• Open circuit on cylinder low pressure switch input (default configuration)
• Primary power supply failure
• Internal battery power supply failure
• A communications fault between the control box and display panel
• Real Time Clock not set
• Real Time Clock battery failure
• Shutdown over-ride DIP switch activated
When the control system is in a fault condition, the fault output relay will also be energized to allow auxiliary
remote fault indications. Faults within the VS control system can be displayed using either the VS control
module circuit board FAULT LED’s or alternatively using the LED’s on the VS display panel. A total of 14
fault conditions can be displayed and these are split into 2 sets of 7 faults. Each set of (7) faults is displayed
at a 2 seconds intervals. The fault set being displayed is indicated by the status of Green fault LED on the
controller (or the green Power LED on the display panel, when using the display panel to display active fault
conditions).
To facilitate fault finding, a set of eight (1 x green, 7 x amber) fault indicating LED’s are provided on the
circuit board inside the VS control module. To view the fault indicators, hold down the pushbutton located
next to the fault LED’s. The fault conditions indicated by these LED’s are shown in table 17.
In its normal operating mode, the VS display panel will indicate a primary power supply fault by illuminating
the amber “Power” LED whilst all other faults are indicated as a common fault by illuminating the amber
“fault” LED.
However, to improve fault finding, the LED’s on the display unit can temporarily be set to show individual
active system faults by holding down both the ‘DELAY’ and ‘TEST’ buttons on the keypad. Faults are shown
one at a time and at a 2 seconds intervals. The fault conditions indicated by the LED’s are shown in table
18.
Event Log
The VS control system incorporates a Real Time Clock (RTC) which allows up to 65 fault, alarm, shutdown,
isolation and other maintenance events to be date and time stamped and stored in system non-volatile
memory for later retrieval and analysis.
A RTC fault occurs when the system detects an incorrect date setting. This could indicate that the time and
date haven’t been set correctly or that the RTC battery (small battery on the VS control module PCB) is
faulty. The RTC fault is latching and to clear it, the system must be reset.
To diagnose the cause of the RTC fault it is necessary to utilize the RS232 interface and the Terminal
program installed on a laptop computer; follow the instructions below:
a. Use the ‘T’ command to check the current time and date.
b. If the time and date is incorrect, use the ‘ST’ command to set the current time and date.
c. Verify that the time and date are now correct by again using the ‘T’ command.
d. Isolate the primary and internal battery power by unplugging the power connector from the
control module.
e. Wait 10 seconds
f. Plug in the power connector to the control module and wait for the system to initialize.
NOTE: if the RTC has defaulted to the date of “01/01/00” it is necessary to replace the RTC battery and
then follow the steps detailed above.
Fire Alarm
Audible and visual fire alarm indications, consisting of illumination and latching of the Alarm LED and
sounding of the buzzer once per second will be initiated by any of the following conditions:
• System Discharge, via open circuit on discharge pressure switch input (default configuration)
caused by either:
o Manually initiated system discharge.
o Automatically initiated system discharge by either Pyrotube or LOP detection tubing.
When in an alarm condition, the auxiliary alarm output relay will be energised and equipment shutdown
sequence commenced. If the alarm condition was initiated by operation of either electrical manual release
input or fire detection input(s) the actuation output will also be energised. The actuation output is not
energised in the case of pneumatic (LOP or Pyrotube detection) operation or manual mechanical operation
of the PEFS system.
System Discharge
The default (and recommended) discharge configuration for the VS control system is for immediate
discharge when a fire alarm condition is detected. Immediate discharge gives the suppression system the
best chance of suppressing the fire in its early stages. In special circumstances, however, delaying the
discharge of the suppression system may be desirable. To cater for such circumstances, (such as operator
safety) a discharge delay timer is provided with selectable delay periods of 0, 15, 30 and 60 seconds.
When the PEFS system cylinders are actuated, a pressure switch in the discharge network is used to
confirm that agent has been released from the cylinders by illuminating and latching the Discharged LED.
Operation of the discharge pressure switch provides the following functions:
• In the case of manual (mechanical) or automatic pneumatic (ROP or LOP detection) actuation of the
cylinders:
o Operates the fire alarm visual and audible indications and initiates equipment shutdown.
o Confirms that the cylinders have discharged.
Equipment Shutdown
A shutdown time delay is incorporated in the VS control system to allow the equipment operator to
safely bring the equipment to rest before the shutdown is activated. The shutdown time delay
countdown is initiated by:
Once the equipment shutdown countdown is initiated the following functions occur:
If the Delay push button is pressed before the countdown period expires the following functions will
occur:
• The shutdown period will be extended by a selectable delay extension period (0, 5, 10, 15, 20, 30,
40 – 180 in 20 second intervals, 210 and 240 seconds). The default shutdown delay extension
period is 30 seconds.
• The Amber shutdown LED will change back from flashing to continuous indication.
• The extended delay period will commence counting down.
NOTE: The PEFS VS control system is configured to allow only one time delay extension period to
the equipment shutdown. However, the initial and extended delay periods can be
independently set to different values. Both delay periods should be kept as short as safely
possible.
Once the shutdown period has expired the following functions will occur:
System Reset
A system reset button is mounted on the circuit board in both the VS display panel and VS control box. The
system reset will reboot the VS control system and clear all outputs (alarm, shutdown etc). To reset the
system hold down the either reset button for 2 seconds.
A system reset can also be activated using the “TEST”, “DELAY” and “DIM” push buttons on the VS display
panel. To prevent accidental operation, the ‘delay’ push button must be pressed prior to the other two
buttons:
g. Press and hold the ‘DELAY’ button
h. Press and hold the ‘TEST’ and ‘DIM’ buttons
i. Wait 1 seconds
j. Release all three buttons