Centum VP
Centum VP
Centum VP
IM 33M05D10-40E
IM 33M05D10-40E
3rd Edition
Introduction
This operation manual is written for plant operators who use the CENTUM VP to perform
operation and monitoring.
This manual comprises the following chapters. Listed below are their brief explanations:
• Starting up HIS
This chapter explains how to start up HIS and the structure of operation and monitoring
windows.
Media No. IM 33M05D10-40E (DVD) 3rd Edition : Oct. 2010 (YK) IM 33M05D10-40E 3rd Edition : Oct.22,2010-00
All Rights Reserved Copyright © 2008, Yokogawa Electric Corporation
ii
CENTUM VP
Engineering
Guidance
CENTUM Data
Fieldbus APCS
Access Library
Documentation Documentation
IM 33M05F10-40E
Hardware
User's manual
Installation Only available in electronic document
CENTUM VP
Relationship between manuals
Installation that must be read in order
IM 33M01A20-40E Relationship to a referred manual
Reference manual
Safety Precautions
n Safety, Protection, and Modification of the Product
• In order to protect the system controlled by the product and the product itself and ensure
safe operation, observe the safety precautions described in this user’s manual. We assume
no liability for safety if users fail to observe these instructions when operating the product.
• If this instrument is used in a manner not specified in this user’s manual, the protection
provided by this instrument may be impaired.
• If any protection or safety circuit is required for the system controlled by the product or for
the product itself, prepare it separately.
• Be sure to use the spare parts approved by Yokogawa Electric Corporation (hereafter
simply referred to as YOKOGAWA) when replacing parts or consumables.
• Modification of the product is strictly prohibited.
• The following symbols are used in the product and user’s manual to indicate that there are
precautions for safety:
Indicates that caution is required for operation. This symbol is placed on the product to refer
the user to the user’s manual in order to protect the operator and the equipment. In the
user’s manuals you will find precautions to avoid physical injury or death of the operator,
including electrical shocks.
Identifies a protective grounding terminal. Before using the product, ground the terminal.
Identifies a functional grounding terminal. Before using the product, ground the terminal.
Indicates an AC supply.
Indicates a DC supply.
n Notes on Software
• YOKOGAWA makes no warranties, either expressed or implied, with respect to the
software’s merchantability or suitability for any particular purpose, except as specified in the
terms of warranty.
• This product may be used on a machine only. If you need to use the product on another
machine, you must purchase another product.
• It is strictly prohibited to reproduce the product except for the purpose of backup.
• Store the DVD-ROM (the original medium) in a safe place.
• It is strictly prohibited to perform any reverse-engineering operation, such as reverse
compilation or reverse assembling on the product.
• No part of the product may be transferred, converted or sublet for use by any third party,
without prior written consent from YOKOGAWA.
Documentation Conventions
n Typographical Conventions
The following typographical conventions are used throughout the user’s manuals:
“▼” Mark
This symbol indicates the description for an item for which you should make a setting in the
product’s engineering window.
While operating an engineering window, the help information for the selected item can be
accessed from “Builder Definition Items” in the Help menu.
Listing more than one definition item after this symbol implies that the paragraph on the page
describes more than one definition item.
Example:
▼ Tag Name, Station Name
“Δ” Mark
Indicates a space between character strings that must be entered.
Example:
. ALΔPIC010Δ-SC
“...” Mark
Indicates that the previous command or argument may be repeated.
Example:
Imax (arg1, arg2, ...)
n Symbol Marks
Throughout this user’s manual, you will find several different types of symbols are used to identify
different sections of text. This section describes these icons.
CAUTION
Identifies instructions that must be observed in order to avoid physical injury and electric
shock or death of the operator.
WARNING
Identifies instructions that must be observed in order to prevent the software or hardware
from being damaged or the system from becoming faulty.
IMPORTANT
Identifies important information required to understand operations or functions.
TIP
Identifies additional information.
SEE
ALSO
n Drawing Conventions
Some drawings may be partially emphasized, simplified, or omitted, for the convenience of
description.
Some screen images depicted in the user’s manual may have different display positions or
character types (e.g., the upper / lower case). Also note that some of the images contained in this
user’s manual are display examples.
n Trademark Acknowledgments
• CENTUM and Vnet/IP are registered trademarks of YOKOGAWA.
• Microsoft, Windows, Windows Vista, Visual Basic, Visual C++ and Visual Studio are either
registered trademarks or trademarks of Microsoft Corporation in the United States and/or
other countries.
• Adobe, Acrobat and Acrobat Reader are either registered trademarks or trademarks of
Adobe Systems Incorporated in the United States and/or other countries.
• Ethernet is a registered trademark of XEROX Corporation.
• Java is a registered trademark of Sun Microsystems,Inc.
• MELSEC is a registered trademark of Mitsubishi Electric Corporation.
• Modicon and Modbus are registered trademarks of Schneider Electric SA.
• Memocon-SC is a registered trademark of Yaskawa Electric Corporation.
• PLC is a registered trademark of Rockwell Automation, Inc.
• SYSMAC is a registered trademark of OMRON Corporation.
• SIEMENS and SIMATIC are registered trademarks of Siemens Industrial Automation Ltd.
• FOUNDATION in FOUNDATION fieldbus is a registered trademark of Fieldbus Foundation.
• SmartPlant is a registered trademark of Intergraph Corporation.
• HART is a registered trademark of the HART Communication Foundation.
• All other company and product names mentioned in this user’s manual are trademarks or
registered trademarks of their respective companies.
• We do not use TM or ® mark to indicate those trademarks or registered trademarks in this
user’s manual.
• We do not use logos and logo marks in this manual.
CENTUM VP
HIS Operation
IM 33M05D10-40E 3rd Edition
CONTENTS
1. Using the Basic Features of HIS.............................................................. 1-1
1.1 Starting up HIS and Confirming the Security Setting.................................... 1-2
1.2 Structure and Types of Operation And Monitoring Windows....................... 1-5
1.3 Using System Message Banner....................................................................... 1-9
1.4 Using Browser Bar........................................................................................... 1-10
2. Using Graphic Views................................................................................. 2-1
2.1 Calling Graphic Views....................................................................................... 2-2
2.2 Using Graphic View........................................................................................... 2-4
3. Useful Features of HIS.............................................................................. 3-1
3.1 Operation Panel Mode....................................................................................... 3-2
3.2 Switching to Operation and Monitoring Windows while operating
general-purpose Windows Applications......................................................... 3-4
3.3 Using Short Cut Keys........................................................................................ 3-5
3.4 Multiple-Monitor................................................................................................. 3-9
4. Operating the Instrument Faceplate....................................................... 4-1
4.1 Entering Data...................................................................................................... 4-2
4.2 Changing the Block Mode................................................................................. 4-6
4.3 Operation Mark on Instrument Faceplate....................................................... 4-8
4.4 Tight Shut and Full Open................................................................................ 4-10
5. Viewing and Confirming Messages........................................................ 5-1
5.1 Confirming Generated Messages.................................................................... 5-2
5.2 Message Search................................................................................................. 5-9
5.3 Messages On Help Window............................................................................ 5-15
5.4 Confirming Messages in CAMS for HIS........................................................ 5-18
6. Reading the Trend of Process Data......................................................... 6-1
6.1 Confirming Data in the Trend View.................................................................. 6-2
6.2 Changing the Assignment of Trend Data Being Displayed........................... 6-4
6.3 Creating/Displaying Trend Reference Patterns . ........................................... 6-8
7. Outputting Screen Images....................................................................... 7-1
7.1 Outputting the Screen Image of Currently Displayed Windows ................. 7-2
7.2 Outputting the Previously Output Screen Images Again.............................. 7-6
8. When a System Error Occurred............................................................... 8-1
TIP
If one of the following settings has been made, the HIS starts up automatically after the computer is turned on.
• The [Auto Logon] option is selected in the HIS Utility dialog box.
• In Windows authentication mode, the [Enable HIS Type Single Sign On] option is selected in the HIS
Utilities dialog box.
SEE
ALSO For information about the Windows authentication mode and CENTUM authentication mode, see the following:
E1, ”Human Interface Station” of “Reference (IM 33M01A30-40E)”
In the case of the operation key When the engineering key is inserted.
Changes between The key can be
the ON, OFF positions. switched to any position.
010001E.ai
TIP
By the setting on HIS Utilities, you can prevent the privilege level from being changed even if the mode switching
key is used to change the privilege level. You can confirm whether the mode switching key is disabled or not by
checking the HIS Utilities setting.
SEE
ALSO • For more information about the privilege level, see the following:
F3.3, “Privilege Level” of “Reference (IM 33M01A30-40E)”
• For more information about the privilege level when CAMS for HIS is enabled, see the following:
E12.8, “HIS Actions when CAMS for HIS is Enabled” of “Reference (IM 33M01A30-40E)”
TESTUSER
010002E.ai
SEE
ALSO For the details of System Message Banner, see the following:
“1.3, Using System Message Banner”
User-In
User Information
User ENGUSER (Default ENG User)
Group DEFGRP (Default User Group ALL)
Since 2004/10/28 16:52
Password
Shut Down
010003E.ai
2. Enter the user name and password and click the [User-In] button.
The user is switched and the operation right is also switched accordingly.
SEE
ALSO For more information about User-In dialog box, see the following:
“ User-In and User-Out” in E2.5.1, “Components of System Message Banner” of “Reference (IM
33M01A30-40E)”
Container window
Bin
Frame
Recycle
View
Browser bar
010101E.ai
System Message Banner: Shows the latest three messages that are not yet acknowledged.
It also provides the buttons to call up the alarm-related views or
windows as well as the buttons for switching the users, printing
the screen images, and other functions.
Browser bar: Lists the names of views and windows, and tag information of
CENTUM VP. It also provides the buttons to call them up.
Container window: A window that contains frames and views.
Frame: Placed in a container window and shows a set of views that are
combined for a specific purpose.
View: The contents shown in a frame.
Graphic View
Trend View
Tuning View
Trend Point View
Faceplate View
Custom Faceplate View
*3
Operator Guide View Operator Guide Individual Acknowledgement *3
*2
Process Alarm View Process Alarm Individual Acknowledgement *2
010102E.ai
010103E.ai
SEE
ALSO For more information about various HIS windows, see the following:
E2.3, “System Windows and User-Defined Windows” of “Reference (IM 33M01A30-40E)”
SEE
ALSO For the details of the System Message Banner, see the following:
E2.5, “System Message Banner” in “Reference (IM 33M01A30-40E)”
Browser Bar contains the following five tool boxes. Click the tabs in the left most strip to switch
the tool boxes.
Comment
Address /USER
Favorite
favorite-1
P MYPJT1
.SH
GR0002
favorite-2
TG0216
CG0001
Search
010301E.ai
Default Stabio;Ingotmtn
Call View
SYS HELP ?
Window Control
Builder
Window History
Window History
Function Name Command .
O LI201 -SC O LI201 -SC
CG0001 O CG0001 -SL
GR0002 O GR0002 -SL
CG0001 O CG0001-SL
O FIC100FF -SC O FIC100FF -S
GR0001 O GR0001 -SL
GR0001 O GR0001 -SL
OV0001 O OV0001 -SL
NAME
OV0001 O OV0001 -SL
CG0001 O CG0001 -SM
O FIC100FF TUN -SM O FIC100FF TU
FIC002 O FIC002 TUN
FIC002 O FIC002 -SC
System Status Overview O .SO -SL
FIC001 O FIC001 -SC
Station Status Display O .SF FCS0102
010302E.ai
SEE
ALSO For the details of Graphic Builder, see the following:
F12. “Graphic Builder” of “Reference (IM 33M01A30-40E)”
Vapor 3 4
Distillation Column Condenser
36.2 % 40.8 M3/H
2D
1 2
SYS-OV
1LIC100 1FIC101
Reflux Drum
Dist TR
Dynamic
Reboiler
Instruments Bottom
31.7 M3/H
25.9 %
Extraction
Compressor okay 1FIC300
1LIC300
ALRM
Ready
020001E.ai
Tool Button
View Operation
Call View
SYS HELP ?
NAME Overview
Graphic view
Window Control
Builder
020101E.ai
Name Input
Window Name Input
GRAPHIC 1 Call
NAME
020102E.ai
2. Press the Call button. The graphic view you requested (GRAPHIC 1 in the above example)
appears.
SEE
ALSO For how to call up other windows from the Name Input Tool Box, see the following:
“n Calling up Windows by Entering Names” in E2.7.1, “Directly Calling up Operation and Monitoring
Windows” in “Reference (IM 33M01A30-40E)”
020201E.ai
Faceplate Assignment
1. FIC100 9. AIC100
3. FI102 11.
4. FI103 12.
5. FI104 13.
6. TIC100 14.
7. TIC200 15.
8. TIC300 16.
OK Cancel
020202E.ai
2. Enter a new tag names to the corresponding faceplates, then click [OK] button. The
faceplates will indicate the newly changed function blocks.
SEE
ALSO For more information about generic name set of graphics, see the following:
F12.16, “Creating reusable graphic views using generic names” of Reference (IM 33M01A30-40E)
020203E.ai
Comment
Comment
OK Cancel
020204E.ai
3. Choose a generic name set from the pull-down list, and then click [OK].
The data displayed on the graphic view will be changed to a different data set.
020205E.ai
020206E.ai
SEE
ALSO For more information about operation panel mode, see the following:
E2.2, “Operation Screen Mode” of “Reference (IM 33M01A30-40E)”
IMPORTANT
The selected operation panel mode will become effective after logoff.
1. In the Tool Button Tool Box in the Browser Bar, click the button to show System Status
Overview view.
Tool Button
View Operation
Call View
SYS HELP ?
Window Control
Builder
030101E.ai
030102E.ai
File
Equalize Function Keys Operation Mark Multimedia Browser Bar Trend Long-Term
External Recorder OPC REPORT Process Management Multiple-Monitor
Station Printer Buzzer Display Window Switching Alarm Preset Menu
Operation Screen Mode (HIS should be restarted.) Status Display without Scaling
030103E.ai
Tool Button
View Operation
Call View
SYS HELP ?
NAME Overview
Window Control
Builder
Circulate
030201E.ai
2. The Operation and Monitoring Window at the back is moved to the front.
System Message Banner System Message Banner
Browser Bar
Browser Bar
030202E.ai
Figure Circulate
SEE
ALSO For details of short cut keys, see the following:
E2.12, “Shortcut Keys for Operation and Monitoring Windows” in “Reference (IM 33M01A30-40E)”
SEE
ALSO For details of function keys, see the following:
E13.2, “Function Keys” in “Reference (IM 33M01A30-40E)”
Tool Button
View Operation
Call View
SYS HELP ?
Window Control
Builder
030301E.ai
030302E.ai
File
Preset Menu Equalize Function Keys Operation Mark Multimedia Long-Term
OPC REPORT Process Management Multiple-Monitor
Station Printer Buzzer Display Window Switching Navigator Alarm
Project : MYPJT1
Station Name : HIS0164
Type : PC (PC)
Address : 01-64
Comment :
OS : Windows Vista (6.0.6000:)
OPKB Revision : 0.0
Port :
030303E.ai
4 Restart HIS.
The setting you made in the step 3 becomes valid.
3.4 Multiple-Monitor
The function known as Multiple-Monitor connects up to four monitors to one Human
Interface Station (HIS), and displays windows for the operation and monitoring on each
monitor. In this way up to four monitors can be handled as one large, logical desktop area
(virtual desktop area).
The Multiple Monitors feature of Windows is utilized to form the multiple-monitoring
scheme of HIS. Therefore, the operating environment in the general-purpose personal
computer should be either Windows XP or Windows Vista that supports the multiple
monitors. And the package for the multiple monitoring (LHS4600) should be installed in
the PC too.
n Overview of Multiple-Monitor
An overview of Multiple-Monitor is as follows:
• Up to four monitors can be connected to one HIS. A display card compatible with the
Multiple Monitors feature of Windows is used for connection.
• The monitors can be stacked (vertical orientation) or placed side-by-side (lateral
orientation).
• One monitor is designated as the main monitor and the others are the sub monitors.
• Multiple full-size operation and monitoring windows can be displayed at the same time.
• The secondary dialog that is called up from an operation and monitoring window is
displayed on the monitor where the calling window is being displayed.
• System Message Banner is displayed on each monitor, showing the same information.
• Browser Bar is displayed on each monitor. Each Browser Bar can be operated
independently.
• A display destination monitor can be designated when calling up an operation and
monitoring window.
The following display operations can be performed on a Multiple-Monitor HIS:
• Windows can be called up on a specified monitor.
• Windows on a specified monitor can be erased.
• The Print Screen can be executed for a specified monitor.
• Windows can be transferred between the specified two monitors (shift and exchange).
• The mouse cursor can be freely moved across the monitors.
• Operation and monitoring windows can be moved across the monitors by dragging with
mouse.
n Installing monitors
The multiple monitors can be stacked vertically or placed side-by-side, as shown below. You
need to setup in the Windows Display Properties on how you install the multiple monitors.
030401E.ai
SEE
ALSO For details of the Multimonitoring, see the following:
E14. “Multiple-Monitor” in “Reference (IM 33M01A30-40E)”
SEE
ALSO For details of instrument faceplate, see the following:
E6. “Instrument Faceplate” in “Reference (IM 33M01A30-40E)”
CMP mark
Tag name FIC100
Comment
Tag comment Reactor conduit Instrument mark
display area
vapor pressure
Tag mark Block status
S
Status T
Block mode
display area AUT IMAN
Alarm ON/OFF status
NR CAL AOF
Alarm status PV M3/H
70.0 Engineering unit
Parameter Data item name SV Data
display area 98.0
MV Calibration status
Open/close mark 100.0
OPN
Instrument faceplate scale
100.0 high limit
Index Setpoint value pointer
Manipulated output 80.0
value pointer
60.0
Instrument
display area Manipulated
output value limit bar 40.0
AUT
NR
PV M3/H
70.0
SV M3/H
50.0
MV %
65.1
100.0
Button to call
0.0
data entry dialog box
040101E.ai
FIC001 TankA
MV = 65.1% ITEM
DATA =
2. Enter data in the data entry area, and press the [RETURN] key.
If the setting exceeds the high limit or low limit, a reconfirmation window will appear.
3. Confirm the data value.
MV = 65.1% ITEM
DATA =
040103E.ai
FIC001
040104E.ai
2. In the Data Item Change dialog box, click the new data item and click the [OK] button.
FIC001
ITEM OK
MV
P Cancel
PH
PL
PMV
Click
Mouse
040105E.ai
The item name displayed in the Data Entry dialog box will be changed.
Changes from [MV] to [PH]
DATA = DATA =
040106E.ai
In the above example, the display will change from [MV] to [PH], and changing the value of data
item PH becomes possible.
AUT
NR
PV M3/H
70.0
SV M3/H
50.0
MV %
65.1
100.0
0.0
Mouse
040107E.ai
INC button
MV = 65.1
DEC button
040108E.ai
TIP
• The manipulated output value can be changed in the MAN mode, while the set point value can be changed
in the AUT mode.
• The operable pointer is shown in red. In MAN mode, if you click the set point value pointer (in yellow), it
turns red and operable.
2. Click the INC button or DEC button to change the data value.
TIP
If the setting exceeds the high limit or low limit, a reconfirmation dialog box will appear.
AUT
NR
PV M3/H
Click 70.0
SV M3/H
50.0
MV %
65.1
Mouse
100.0
0.0
040201E.ai
FIC001
2. In the Block Mode Change Operation dialog box, click the mode button to be changed. For
the blocks with SEMI mode, clicking on the CAS button changes the mode to SEMI.
Clicking any of the buttons will call a dialog box to confirm the operation.
3. Perform confirmation operation.
MAN
NR
Click
PV MAN M3/H
AUT 70.0
SV CAS M3/H
mouse 100.0
MV %
100.0
OPN
100.0
040203E.ai
2. Select a block mode on the menu. Then a dialog box will be displayed for confirmation.
3. Confirm.
SEE
ALSO For details of operation marks, see the following:
F3.5, “Operation Mark” in “Reference (IM 33M01A30-40E)”
040301E.ai
FIC100
A system intake flowrate
None
Setting
Inspection
Operation prohibited
Running
OPMARK04
OPMARK05
OPMARK06
OPMARK07
OPMARK08
OPMARK09
OPMARK10
OPMARK11
OPMARK12
OPMARK13
OPMARK14
OPMARK15
OK Cancel
040302E.ai
3. Check [Setting], and then select an operation mark from the list. For removing an operation
mark, [None] should be checked instead of [Setting].
4. Click [OK].
The selected operation mark is set to the instrument faceplate of the function block.
Tool Button
View Operation
Call View
SYS HELP ?
Window Control
Builder
040303E.ai
IMPORTANT
• If the output destination of the manipulated value (MV) of a function block having the ‘Tight
shut/Full open’ feature is a Fieldbus Faceplate block, set the ‘Tight shut/Full open’ to “No” in
the Function Block Detail Builder.
• In the Function Block Detail Builder, the setting items “Output Value for Tight-shut (Ms)” and
“Output Value for Full-open (Mf)” are named assuming the ‘valves with reverse actions”
where the valves close tightly if the manipulated value (MV) is 0 %. For the valves that close
tightly if the manipulated value (MV) is 100 %, the setting item “Output Value for Tight-shut
(Ms)” is a value for setting the actual output value to a value less than 0 % if the manipulated
value (MV) is 0 %. Take note that the setting item “Output Value for Full-open (Mf)” is a value
for setting the actual output value to a value more than 100 % if the manipulated value (MV)
is 100 %.
SEE
ALSO For using Consolidated Alarm Management Software (CAMS for HIS), see the following:
E12. “Consolidated Alarm Management Software” in “Reference (IM 33M01A30-40E)”
TIP
When CAMS for HIS is enabled and the [Display Total Number of Alarms] check box in the Alarm tab of
the HIS Setup window is selected, the total number of process alarms are displayed under the number of
unacknowledged process alarm messages.
l Acknowledging messages
1. If beeps are output, look at the flashing button in the System Message Banner to check
which type of message is generated.
2. Click the Message Display area in the System Message Banner. Or click the flashing button.
A message window appears.
1 08/18 04:18:33 PM
Reactor, high temperature!
2 08/18 04:18:14 PM SBP201: MSG002
Reactor operation condition error!
Pressure and temperature exceed the specified values.
PIC100 11 kPa Specified valus 3.5 kPa
TIC200 125 DEG Specified valus 120.0 DEG
3 08/18 03:17:40 PM
Transfer process starts. SBP200: MSG001
4 08/18 03:17:05 PM
Enter the setpoint.
5 08/18 02:16:18 PM
Raw material charge is completed.
050102E.ai
Move condition =
TIP
In the case of an operator guide message or system alarm message, clicking on the delete button after
acknowledging operation will delete the message.
l Tag Report
1. In the Tool Button Tool Box in the Browser Bar, click the button to display Process Report
View.
Tool Button
View Operation
Call View
SYS HELP ?
CAMS
Window History
Function Name Comman
Block:01 Group:02
System Alarm Message
Process Alarm
System Status Overview
GR0001
PID001
OV0001
CG0001
FIC100
050104E.ai
050105E.ai
Tag Name Tag Comment Alarm Current Value Mode Operation Mark System Tag Name
FIC300 Discharge line A NR 80.0M3/H MAN .BL0158S010101
TIC100 Charge tank NR 20.0DEGC MAN IMAN Maint .BL0159S010101
LIC200 Discharge tank NR 36.0L/H MAN .BL0160S010101
PI150 Reactor NR 25.0PA AUT .BL0161S010101
MC100 Wash valve 1 NR 0.0% MAN .BL0162S010101
SIO220 Flowrate valve NR 1 MAN .BL0163S010101
LSW111 Agitator NR .BL0164S010101
SW330 Discharge line .BL0165S010101
01ST0002 NR 2 AUT .BL0166S010101
LC001 Transfer 1 NR MAN .BL0167S010101
LC002 Transfer 2 NR MAN .BL0168S010101
LIC001 NR 0.0% MAN .BL0169S010101
LIC002 NR 0.0% MAN .BL0170S010101
AN0001 Tank level error ALM 1 Maint .AN0001S010101
AN0002 Pump A fail NR 0 .AN0002S010101
AN0003 Tank A temp HI NR 0 .AN0003S010101
AN0004 Tank B temp LO NR 0 .AN0004S010101
AN0005 Tank A level HH NR 0 .AN0005S010101
AN0010 Tank B level HI NR 0 .AN0010S010101
AN11 Tank C level LO NR 0 .AN0011S010101
MORE "TAG" DEFAULT "I/O" FCS0101 %SW
050106E.ai
The dialog box consists of multiple tabs; only the conditions in the selected tab are applied.
Click the above button again may refresh the displayed tag report.
3. Click the following button can open the Tag Search dialog box for setting conditions.
050107E.ai
050108E.ai
Tool Button
View Operation
Call View
SYS HELP ?
CAMS
Window History
Function Name Comman
Block:01 Group:02
System Alarm Message
Process Alarm
System Status Overview
GR0001
PID001
OV0001
CG0001
FIC100
050109E.ai
050110E.ai
The I/O report view displays the I/O points and their state according to the conditions set in
the I/O Search dialog box.
FCS0101
1234567890 1234567890 1234567890 1234567890 1234567890
AN0000 . . 1. 1. 1. 11 11. 111. . . . . 111. 11. 1. 11. . . 1. . . . . . . 11. . . . .
AN0050 . 11111. 1. . 1. . 1. . . 1. . . . 1. . 1. 11. . . . . . 1. . 11 . . 11. . . . . .
AN0100 . 1. 111. 11. . 1. . . 1. 1. . 11. . . . . 111 . 1. 1. 1. . . 1 . . . . . 1. 1. .
AN0150 . . 1. 11. 1. . 1. 1111. . . 1 . . . . . 111. . . . . . . 11. 1. 1. 1111. . . 1
AN0200 . 111. . 1111 11. . . 1. . . 1 . . 11. . . . 11 11. 1. 1. . 1. . 111. 1. . . 1
050111E.ai
Click the above button again may refresh the displayed I/O report.
3. Click the following button can open the I/O Search dialog box for setting conditions.
050112E.ai
OK Cancel
050113E.ai
SEE
ALSO For using Consolidated Alarm Management Software (CAMS for HIS), see the following:
E12. “Consolidated Alarm Management Software” in “Reference (IM 33M01A30-40E)”
1.0
m3/s
1 10/28 10:18:15 FIC005 Flowrate 5 NR 33.0M3/H NR
2 10/28 10:18:15 FIC005 Flowrate 5 LO 33.0M3/H NR
3 10/28 10:17:05 FIC004 Flowrate 4 DV+ 50.0M3/H DV+
4 10/28 10:16:45 FIC003 Flowrate 3 HH 12.0M3/H HH
050201E.ai
Filter
Range
All
Tag Name
Batch ID
Type
All
Annunciator Only
OK Cancel
050202E.ai
2. In the Filter dialog box, specify the range and type of the alarm to be searched for, then click
the [OK] button.
With a horizontal split, a view can be displayed into two frames. The filtered messages are
displayed in the top frame while the whole messages are displayed in the bottom frame.
An example of the process alarm window split is shown as follows:
1.0
m3/s
050208E.ai
102.3
82.3
62.3
FIC001.PV
42.3
22.3
Click
Mouse
050203E.ai
2. Click the button to display the process alarm view in the System Message Banner.
Process alarm view
050204E.ai
1.0
m3/s
1 10/28 01:18:30 PM FIC001 Tank Flowrate 1 NR 50.1M3/H NR
2 10/28 01:18:30 PM FIC001 Tank Flowrate 1 LO 72.1M3/H NR
3 10/28 10:17:45 AM FIC001 Tank Flowrate 1 LO 72.1M3/H NR
050205E.ai
Tool Button
View Operation
Call View
SYS HELP ?
NAME Overview
Historical message report window
Window Control
Builder
050206E.ai
STOP
050207E.ai
HELP
050302E.ai
.HW Help
050303E.ai
Tool Button
View Operation
Help window
Call View
SYS HELP ?
NAME Overview
Window Control
Builder
050304E.ai
Help window with the help messages for the faceplate or the window is displayed.
.HW Help
050305E.ai
3. In the Search key area in the Help window, choose a search key from the list.
The following search keys are available:
• View or Window Name
• Tag Name
• Message Number
• Help Number
4. Enter an alphanumeric string to the field at right-hand side of the search key, and then click
[Display] button.
The detailed help message matches the above condition will be displayed.
050401E.ai
050402E.ai
SEE
ALSO For details of setting up CAMS for HIS, see the following:
E12. “Consolidated Alarm Management Software” in Reference (IM 33M01A30-40E)
F24. “CAMS for HIS Builder” in Reference (IM 33M01A30-40E)
Operator Guide
System Alarm
Process Alarm
050403E.ai
Tool Button
View Operation
Call View
SYS HELP ?
NAME Overview
Builder
050406E.ai
Name Input
Window Name Input
Call
NAME
050404E.ai
Tool Button
View Operation
Call View
SYS HELP ?
NAME Overview
Historical Report
Window Control
Builder
050405E.ai
SEE
ALSO For the features of CAMS for HIS, see the following:
E12. “Consolidated Alarm Management Software” in Reference (IM 33M01A30-40E)
SEE
ALSO For the steps to call the trend view, see the following:
E5, “Trend Recording” in Reference(IM33M01A30-40E)
The trend view displays the acquired data in a graph or the present values in numeric
values.
102.3
82.3
62.3
FIC001.PV
42.3
22.3
060101E.ai
102.3
82.3
62.3
FC01.PV
42.3
22.3
2.3
16:22 16:23 16:24 16:25 16:26 16:27
060102E.ai
When a batch trend is displayed, if a reference pattern is assigned to the displayed trend
pen the reference pattern will be displayed too.
060201E.ai
Pen Assignment
Set Upper/
Block Collected Lower Limit Lower Display
1 FIC100.PV
Initialize
OK Cancel
060202E.ai
2. Set the data to be acquired and high/low limits in the Pen Assignment dialog box. If high/low
limits are not specified, the trend graph to be displayed will use the values defined via the
trend gathering pen assignment builder.
3. To display desired data in the trend view, mark off the corresponding check box under
[Display].
4. Click the [OK] button.
The trends checked in the pen assignment dialog box will be displayed.
060203E.ai
A dialog box will appear, showing a list of files in which trend data are saved.
Open
Desktop
Administrator
Computer
File name: TG0101.trf Open
060204E.ai
Overview
View Trend Plant
TR003
GROUP01
TAG001.PV
TAG002.PV
TAG003.PV
TAG004.SV
TR002
NAME
GROUP01
Drag and drop
TR003
TR004
TRTANK Tank A
1
2
Comment
102.3
Address /USER
82.3
Favorite
favorite-1 62.3
FIC001.PV
P MYPJT1 42.3
.SH
22.3
GR0002
favorite-2 2.3
Gathering 00:12:00
13:34
100%
13:36 13:38 13:40 13:42 13:44
TG0216
CG0001 □ ●
Tag Name
1 FIC001. PV
Tag Comment
Inlet flow
Value
72.1
Unit
M3/h
Upper
100.0
Lower
0.0
□ ● 2 FIC002. PV Outlet flow 53.3 M3/h 100.0 0.0
□ ● 3 LIC100. PV Level 3.8 M 100.0 0.0
Search □
□
●
●
4
5
TIC100. PV
TIC200. PV
Temp A
Temp B
25.7
14.1
DEGC
DEGC
100.0
100.0
0.0
0.0
□ ● 6
□ ● 7
□ ● 8
060205E .ai
Pen is assigned, and the data in the folder is shown in the Trend graph view.
TIP
Pens are assigned from the top (1) to the bottom (8). The highest number of available pen is assigned. If the
maximum 8 pens are already assigned, an assignment error is raised. In this case, delete some of the existing
unneeded pen assignments before adding a new pen assignment.
060301E.ai
Save As
Folders
060302E.ai
2. Specify the name and the location of the file in which to save trend data, and then click the
[Save] button.
Input Comment
1 FIC100.PV Distillation A
2 FI101.PV Inlet A
3 FI102.PV Outlet A
4 FIC200.PV Distillation B
5 FI201.PV Inlet B
OK Cancel
060303E.ai
3. If you want to change the pen comments to be displayed in the trend view, enter new
comments.
4. Click the [OK] button.
060304E.ai
Pen Assignment
OK Cancel
060305E.ai
2. Click the [Specify File] button in the Pen Assignment dialog box.
A dialog box will appear; select a file in which the trend reference pattern is saved.
Open
Folders
Open Cancel
060306 E.ai
060307E.ai
TIP
In Windows authentication mode, you cannot output the screen image if you have entered as OFFUSER.
070101E.ai
2. The image of the view or window in which the button was clicked will be output to the printer.
In the example shown below, clicking on the button in the graphic view outputs the image of
the graphic view only. Images of other view or window will not be output.
Only this graphic view is output.
FCS0101 Batch Manager Ready 2008/03/03 14:35
? FCS0101 RIGHT Control
Copy
0 17 0 FCS0101 RIGHT Manual Reset Start TESTUSER
FIC002
Vapor 3 4 FIC002
My Computer Distillation Column Condenser 2D
View Operation
1 2
36.2 % 40.8 M3/H
SYS-OV
1LIC100 1FIC101
Reflux Drum
Start
070103E.ai
FIC002
Vapor 3 4 FIC002
My Computer Distillation Column Condenser 2D
View Operation
1 2
36.2 % 40.8 M3/H
SYS-OV
1LIC100 1FIC101
Reflux Drum
Start
Tool Button
View Operation
Call View
SYS HELP ?
Window Control
Builder
070105E.ai
Figure Opening the System Staus Overview View
FCS
IOM
APCS0110 GSGW0111
070106E.ai
File
Preset Menu Equalize Function Keys Operation Mark Multimedia Long-Term
OPC REPORT Process Management Multiple-Monitor
Station Printer Buzzer Display Window Switching Navigator Alarm
Message and Report
Hardcopy
070107E.ai
3. Mark off the check box next to [Output to File] in the printer tab strip.
4. Click the button to output the screen image(s) to the printer. The screen image(s) will be
output to a file as well as to the printer.
The file will be output in bitmap (.bmp) format. When recalling the screen image, the image
window can be used to open the file.
Tool Button
View Operation
Call View
SYS HELP ?
NAME Overview
Image window
Window Control
Builder
070201E.ai
FIC002
Vapor 3 4 FIC002
My Computer Distillation Column Condenser 2D
View Operation
1 2
36.2 % 40.8 M3/H
SYS-OV
1LIC100 1FIC101
Reflux Drum
Ready 7
NUM
Sheet1 Sheet2 Sheet3
Command 100% - +
070203E.ai
Open
070204E.ai
070205E.ai
Printer EM-930C OK
070206E.ai
SEE
ALSO • For more information about setting the alarm tones, see the following:
E4.3.3, “Buzzer Tab” in Reference (IM 33M01A30-40E)
• For using Consolidated Alarm Management Software (CAMS for HIS), see the following:
E12. “Consolidated Alarm Management Software” in Reference (IM 33M01A30-40E)
1. Click the Message Display area or the flashing button in the System Message Banner.
2. If you want to view the detailed information on the message, click the message and click the
[HELP] button.
The detailed information on the message appears in the HELP window.
SEE
ALSO For the details of system alarm messages, see the following:
Operating Messages (IM 33M05D20-40E)
HELP
080002E .ai
FCS
IOM
Fail
FCS0101 FCS0102 FCS0103 FCS0104 FCS0105 FCS0106
Ready
080004E.ai
SEE
ALSO • For the steps to call the system status overview view, see the following:
“n Outputting the Screen Image to a File” in 7.1, “Outputting the Screen Image of Currently Displayed
Windows”
• For the details of System Status Overview, see the following:
E4.1, “System Staus Overview” in Reference (IM 33M01A30-40E)
Fail
Fail
Both sides Left side Right side
CPU Fail CPU Fail CPU Fail
080005E.ai
Communication error
080006E.ai
080007J.ai
CENTUM VP
HIS Operation
IM 33M05D10-40E 3rd Edition
INDEX
B S
Block Mode............................................................ 4-6 Screen Image......................................................... 7-1
Browser Bar.........................................................1-10 Security.................................................................. 1-3
Short Cut Key......................................................... 3-5
C System Message Banner...................................... 1-9
CAMS for HIS.......................................................5-18 System Status Overview View............................... 8-3
Circulate function................................................... 3-4
T
F Tight Shut.............................................................4-10
Filter Dialog Box..................................................... 5-9 Trend View............................................................. 6-2
Full Open..............................................................4-10
G
Graphic View.......................................................... 2-1
H
Help Window........................................................5-15
HIS......................................................................... 1-1
I
Instrument Faceplate............................................. 4-1
M
Message................................................................ 5-1
Multiple-Monitor..................................................... 3-9
O
Operation And Monitoring Windows...................... 1-5
Operation Mark...................................................... 4-8
Operation Panel Mode........................................... 3-2
Revision Information
Title : CENTUM VP HIS Operation
Manual No. : IM 33M05D10-40E