Ieee C37.99-2012
Ieee C37.99-2012
Ieee C37.99-2012
Sponsoredط٧ the
Power System Relaying Committee
IEEE
IEEE Std 57.991-2012
New York,
USA
٧٧
3 Park Avenue
100 6-5997 (Revision of
,EEE Std 37.99-2000)
8 March 2013
,EEE std 37.99111-2012
(Revision of
IEEE Std 037.99-2000)
Sponsor
IEEE 15 a registered trademark أ1 U.S. Patent & Trademark Office, owned by The Institute اهElectrical ل Electronics
Engineers. Incorporated.
ﻋﻌﻜﺎprohibits discrimination, harassment and bullying. For 1110 information. Visit http.fwww.ieee.org/webaboutusV1atis/oohcies/p9-26.html.
٧٥part اهthis publication may be reproduced in any form, 11 21 electronic retneval system هotherwise, without the prior written permission
of the publisher.
٢0٤٤٤ a n d Disclaimer 0 اI iabilit) Concerning ،he Use 0٤ 1٤٤٤ Documents: IFEF Standard، ؟documents are developed
within the IEEE Societies 21 ل٤ ﻋﺎStandards Coordinating Committees ٥ اdie ﺗﺎﺗﺎﺗﺎاStandards Association (IEEE-SA)
Standards Hoard, اطﺗﺎاdevelops its standards through a consensus development process, approved by the American National
Standards Institute, ١ hich brings together volunteer's representing varied viewpoints and interests 10 achieve the final product.
Volunteers are not necessarily members 0٤ the Institute and serve without compensation, ١Vhile اﺗﺎ ﺗﺎاadministers the process
and establishes rules 10 promote fairness 1 the consensus development process, IEEE does 110 اindependently evaluate, lest, or
verify the accuracy of any o f the information 0٣ the soundness of any judgments contained 1٦ its standards.
Use of an IEEE Standard 15 wholly voluntary. IEEE disclaims liability for any personal injury', property or other damage, of
any nature whatsoever, whether special' indirect, consequential, 0 compensaloiy, directly 0 indirectly resulting 11011 the
publication, 11 ع0 اor reliance upon any IEEE Standard document.
اﺗﺎااdoes 0 اwarrant or represent the accuracy or content 0 اthe material contained 1 its standards, and expressly disclaims
any express 0٣ implied warranty, including any implied warranty 0 اmerchantability 0٣ fitness for 3 specific purpose, 0٣ that
the use of the material contained 11 15 اstandards 15٤٤ن
1 1101 patent infringement. ﺗﺎﺗﺎﺗﺎاStandards documents are supplied "٨5
IS."
The existence of an IEEE Standard docs 110 اimply that there are no other ١٧3٧5 10 produce, test, measure, purchase, market, or
provide other goods and services related 10 the scope 01٦ عIEEE standard. Furthermore, the viewpoint expressed al the lime 4
standard 15 approved and issued 18 subject 10 change 10011 about through developments 11 the state o f the 311and comments
received 1101٦15•٣5 0 اthe standard. Every1' اﺗﺎﺗﺎاstandard 15 subjected 10 review al least every ten years. ١Vhen a document is
more than ٤٤11 years old 3 لhas 110 اundergone a revision process. It 15 reasonable 10 conclude that 15 اcontents, although still 0٤
some value, ل0 not wholly ٤٤11٤٤1 the present stale of die art. Users are cautioned 10 ٤11٤ 10 determine that they have the
latest edition of any IEEF. standard.
ا1 publishing 3 لmaking its standards available, ﺗﺎﺗﺎﺗﺎا15 not suggesting or rendering professional or other services 10٣ or 01
behalf 0 اany person 0٣ entity. ١٢0٣ 15 IEEE undertaking 10 perform any duty owed by any other person 0٣ entity 10 another.
Any person utilizing any ﺗﺎﺗﺎ ﺗﺎاStandards document, should rely 0001 his 0 her own independent judgment 111 the exercise 0٤
reasonable ٤2٣ عin any given circumstances or. as appropriate, seek the advice 04 اcompetent professional 11 determining the
appropriateness 0٤4 given اﺗﺎﺗﺎاstandard.
Translations: 11٦ ﺗﺎﺗﺎ ﺗﺎا عconsensus development process involves the review of documents 11 English only. ا1 the event that
an IEEE standard 15 translated, only the English version published ٧ IEEE should be considered the approved اﺗﺎﺗﺎاstandard.
Official Staten cnls ٨ statement, written or oral, that is not processed 11 accordance with the IFEE-SA Standards Hoard
Operations Manual shall 0 اbe considered the official 001110٦ of (FEE or any of its committees 2 لshall not be considered 10
be, nor عrelied upon 35. 2 formal 00511101 ٦ ٥ IEEE. ٨1 lectures, symposia, seminars, 0 educational courses, an individual
presenting information on ﺗﺎﺗﺎطﺎstandards shall 14 اا عclear that his 0٣ her views should be considered the personal views 0ا
11 اindividual rather 101 the fonnal 00511011 of IEEE.
Cnmmenis 011 Standards: Comments for revision 0 اIEEE Standards documents are welcome from any interested party,
2221 ل155 0٤ membership affiliation with IEEE. However. IEEE does not provide consulting information 0 advice pertaining
10 IEEE Standards documents. Suggestions ٤0٣ changes 11 documents should ع1٦1٦ ع0٣٦ 0٤ 2 proposed change 0٤ text,
together with appropriate 5up00rtng comments. Smce ﺗﺎﺗﺎﺗﺎاstandards represent 4 consensus 0 concerned interests. It 15
important 10 ensure that any responses 10 comments and questions also receive the concurrence of a balance 0٤ interests. For
this reason, ﺗﺎﺗﺎﺗﺎا0 لthe memlxrs of its societies and Standards Coordinating Committees are 0 اable 10 provide an instant
1250005 ع10 comments or questions except 1 those cases where the matter 1105 previously been addressed. Any person 110
would like 10 participate in evaluating comments 0٣ revisions 10 1 IFFF standard 15 welcome 10 join the relevant 11
working group 3 اhttp: /5tandards.ieee.org.dcvelop/wg/.
Photocopies: Authorization 10 photocop) portions of any individual standard for internal 0٣ personal use 15 granted طfhe
Institute 0٤ Electrical and Electronics Engineers. Inc., provided that the appropriate fee 15 021 ل10 Copyright Clearance Center.
10 arrange for payment of licensing fee, please contact Copyright Clearance Center, Customer Service, 222 Rosewood Drive,
Danvers, MA 01923 USA: +1 978 750 8400 Permission 10 photocopy 0011105 of any individual standard 10 educational
classroom use ٤11also be obtained through the Copyright Clearance ،'enter.
Nice ٤٥ users
Users 0 ا1 ﺗﺎﺗﺎﺗﺎStandards documents should consult ااهapplicable laws and regulations. Compliance with
ﻋﺎprovisions o f any IEEE Standards document does 00 اimply compliance 10 any applicable regulatory
requirements. I m p l e m e n t s o f the standard are responsible for observing 0٣ referring 10 the applicable
regulatory requirements. IEEE does not. by the publication o f its standards, intend 10 urge action that 15 not
11 compliance with applicable laws. 011 لthese documents 1113٧ 00 ا0 عconstrued as doing 50.
Copyrights
1٦15 document 15 copyrighted by the 1ﺗﺎﺗﺎ ﺗﺎ. 1٤ 15 made available ٤0٣ a wide variety 0 0 ا00 ﻋﺎاطand
private uses. 'These include 0ا use. by reference, in laws and regulations, and use 11 private self-
regulation, standardization, and the 00110100 0٤ engineering practices and methods. By making 115
document available for use and adoption by ﻋﺎاطﺎauthorities and private users. عIEEE 0025 10٤ waive
any rights 11 copyright ٤0 this document.
Errata
Errata, 1٤ any, 10٣ this 2110 all other standards can be accessed at 1 10110111 URL:
http:.-//st2ndards.ieee.org tmdstdserrataindex.html■ Users are encouraged 10 check this URL 10٣ errata
periodically.
Attention 15 called 10 the possibility that implementation 0٤ this standard may require ﻻ5 عo f subject matter
covered ط٧ patent rights. By publication of this standard, 00 0051110115 taken by the IEEE with respect 10
the existence or validity o f any patent rights 11 connection therewith. 112 patent holder or 02٤٤0٤ applicant
35 filed 2 statement 0٤ assurance via 211 Accepted Letter 0٤ Assurance, then the statement 15 listed 0 the
E E E - S A ٧2051٤ عhttp://standards.ieee.org about sasbpatconVpatents.html. letters o f Assurance may
indicate whether the Submitter 15 w i l l i n g 0 unwilling 10 grant licenses under patent rights without
compensation or under reasonable rates, w ith reasonable terms and conditions that 3٣ عdemonstrably free o f
any unfair discrimination 10 applicants desiring 10 obtain 5 اﻋﻼlicenses.
Essential Patent Claims may exist 10[ which a Letter o f Assurance has not been received. 11٦ ﺗﺎﺗﺎﺗﺎا عis not
2500151 01 ع10 identifying Essential Patent (1311115 10 which 3 license may عrequired, 10 conducting
inquiries 1110 ﻋطﺎlegal validity or scope ٥ اPatents Claims, or determining whether any licensing terms or
conditions provided 11 connection with submission 0 ا3 Letter 0 اAssurance, 1 اany, or 11 any licensing
agreeiuents 3٣ عreasonable or non-discriminatory. LJsers 0 اthis standard 3٣ عexpressly advised that
determination o f the validity 0 ا31 اpatent rights. 00 لthe risk o f infringement o f such rights. 15 entirely
٧ عobtained from the ! ﺗﺎﺗﺎ ﺗﺎStandards Association.
their o w n responsibility. Further information 1113
٨1 the time this guide was submitted 10 the IEEE-SA Standards Board 10٣ approval, ﻋﺎProtection 0 اShunt
Capacitor Banks Working Group had the following membership:
*Corresponding Members
The following members of the individual balloting committee voted 01 ا15 gutde, Balloters 1113٧ have
voted 10٣ approval, disapproval, or abstention.
*Member Emeritus
Dun 15511ح
IEEE Stundurds Progrum Munuger* Document Development
Erin Spiewak
IEEE s tundurds Progrunt Muttuger,Technical progrunt Development
1115 introduction 15 not part of IEEE 5ل (2012-37.99, IEEE (3111 ﻋلfor 1 عProtection of Shun! Capacitor Banks,
IEEE Std 37.99-2012 incorporates significant additions and ٤1211225 since the last 121510٦ 11 2000. These
additions include the theory 0 اunbalance 0101221101 methods, impedance measurement techniques, and
settings examples 25 Annex ﺗﺎ. Detailed discussion 011 grounding has now 02211 reduced 10 address concerns
related 10 protection, and the reader has been directed 10 ret٠er to IEEE Std 1036ا١ا-2010 ‘دor more details,
11١15 guide was e ised ط٧ the shunt capacitor bank protection revision 011102 group of the substations
protection subcommittee ٥٤ 1١ ع1٥٧٤٣ Systems Relaying Committee 0 اthe ﺗﺎﺗﺎ ﺗﺎا
Power and Energy
Society.
2٠ Normative references.............................................. 2
3 دDefinitions ......................................... 3
Annex 10 (informative) Inrush current and frequency during capacitor bank switching .............................. 118
IMPORTANT ٧01٤٤: IEEE Standards documents ٤٤2 219 intended to ensure safety, health, or
environmental protection, 9 2/٤٤٤٤٤ against ,٤٤2٤/٤٤2/٤٤2 1٤٤ 9 ء/7999 other devices 9 ء121 9٤ .
linplementers 9/ IEEE Standards documents are responsible for determining and complying with ا
appropriate safety, security, environmental, health, and interference protection practices and all
applicable laws and regulations*
This IEEE document is made available for use subject to important notices and legal disclaimers*
These notices and disclaimers appear in all publications containing this document and may
be found under the heading Important Notice" or "Important Notices and Disclaimers
Concerning ٤٤٤ Documents*" They can also %2 obtained on request from ٤٤٤ or viewed م
httn://standards٠ieee٠org/lPR/disclaimers٠html٠
!.Overview
1.1 Scope
This guide applies 10 the protection 0٤ shunt power capacitor banks 211 لt i t e r capacitor 2115. Included are
guidelines (0٣ reliable applications 0 اprotection methods intended for use 11 many shunt capacitor
applications and designs. The guide does not include ﻋﺎprotection o f pole-mounted capacitor banks 00
distribution circuits or capacitors connected to the terminals 0 اrotating machines.
1.2 Purpose
1115 guide has been prepared 10 assist protection engineers 1111٦ عapplication 0٤ relays and other devices for
the 01012101 0 اshunt capacitor banks used 11 substations. I t covers methods 0 اprotection for many
commonly used shunt capacitor bank configurations including the latest protection techniques.
Additionally, this guide covers the protection 0٤ filter capacitor banks and large eMra-highvoltage (ElIV)
shunt capacitor banks.
2. Normative references
The 101101100 referenced document 15 indispensable for 1 عapplication 0 اthis document (i٠e., 1 اmust be
understood and used. 50 each referenced document 15 2110011 text and 15 relationship ٤0 15 document 15
20131024). 10٣ dated references, only the edition cited applies. For undated references, the latest edition 0ا
the referenced document (including any amendments 0٣ corrigenda) applies.
٨51 ث37 .06. American National Standard ٨ High-Voltage Circuit Breakers Rated 01 3 Symmetrical
Current Basis- Preferred Ratings and Related Required Capabilities.؛
! ﺗﺎﺗﺎ ﺗﺎStd 469 ٦ ﺗﺎﺗﺎﺗﺎاRecommended Practice for Voice-Frequency Electrical-Noise Tests 0٤ Distribution
Transformers.
! ﺗﺎﺗﺎ ﺗﺎStd 52 5٨. IEEE Cuide for the Design and Installation 0٤ Cable Systems in Substations.
! ﺗﺎﺗﺎ ﺗﺎStd 103 6٨ا. !EEE Cuide for Application 0 اShunt Power Capacitors.
!EEE Std C37.012™, ﺗﺎﺗﺎﺗﺎاApplication Cuide 10٣ Capacitance Current Switching 10٣ ٨ High-Voltage
Circuit Breakers.
!EEE Std C37.O41. ! ﺗﺎﺗﺎ ﺗﺎStandard Rating Structure ٤0٣ ٨ High-Voltage Circuit Breakers.
!EEE Std C 3 7 . 2 ’ . ﺗﺎﺗﺎ ﺗﺎاStandard 10٣ Electrical Power 5٧51٤1٦ Device Function Numbers. Acronyms, and
Contact Designations.
!EEE Std C37.4X’. ﺗﺎﺗﺎ ﺗﺎاCuide 10٣ the Application. (Operation, and Maintenance of High-Voltage Fuses,
Distribution Enclosed Single-Pole Air Switches. Fuse Disconnecting Switches, and Accessories.
! ﺗﺎﺗﺎ ﺗﺎ51ل 37.66٨ا. IEEE Standard Requirements 10 Oil-Filled Capacitor Switches ٤0٣ ٨ Systems ( ا٤٧
٤0 38٤٤٧).
! ﺗﺎﺗﺎ ﺗﺎStd 37.90.1. ﺗﺎﺗﺎﺗﺎاStandard for Surge Withstand Capability (swe) Tests 10٣ Relays and Relay
Systems Associated w ith Electric Power Apparatus.
! ﺗﺎﺗﺎ ﺗﺎ51 لC57. !3.3’. ! ﺗﺎﺗﺎﺗﺎCuide for f o u n d i n g 0٤ Instrument Transformer Secondary Circuits 20 لCases.
! ﺗﺎﺗﺎ ﺗﺎStd C57.16™, !EEE Standard Requirements. 1211111110102. and 1 ع5ا 00 ع10٣ Dry-Type Air-Core
Series-Connected Reactors.
! ﺗﺎﺗﺎ ﺗﺎStd C62.2™, ! ﺗﺎﺗﺎ ﺗﺎCuide for the Application 0٤ Capped Sihcon-Carbide Surge Arresters 10
Alternating Current Systems.
ا ٨5ا0010 ا1221105 : ﻋراavailable 10 the American National Standards Institute (http://www.ansi.0rg/).
٠١IEEE publications are available 10 11 عInstitute 0٤ Electrical and Electronics Engineers (httD./Zstandards 1ece.org/).
ا rhe IEEE standards 0 products referred 10 11 115 clause are trademarks of The Institute 0٤ Electrical and Electronics Engineers, Inc
2
Copyright © 2013 IEEE. ااه 19ا8 reserved.
IEEE Sid C37 99-2012
ﻋﻌﻌﺎGuide for ا Protection of Shunt Capacitor Banks
1 اﺗﺎتStd C62.22™, !EEE Guide for the ٨ 100112211011 0٤ M e t a l - O d e Surge Arresters for Alternating-
Current Systems.
3. Definitions
Eor the 011100505 0٤ 1115 document, the 10110٦٢10 terms and definitions apply. 111 عIEEE 5/0,1/045
Dictionary Online 5110111 لhe consulted for terms not defined in this claused
capacitor bank: ٨1 assembly at one location of capacitors) 31 ااه لnecessary accessories (such 35
witching equipment, protective equipment, controls, etc.) required ٤0٣ 3 complete operating installation.
capacitor control: The device required 10 operate ع switching device(s) automatically 10 energize and
deenergize shunt power capacitor banks,
capacitor element (0 element): The basic component 0٤ a capacitor 111٤ consisting 0٤ two electrodes
separated by a dielectric.
capacitor inrush current (or inrush current): The transient charging cun-ent that flows 11 3 capacitor
when a capacitor 15 initially connected ٤0 a voltage source.
capacitor line fuse (capacitor 20 0 مfuse): ٨ fiise applied ٤0 disconnect a faulted phase 0٤ a capacitor
bank from a power system,
capacitor outrush current (or outrush current): The transient discharge current that flows when 2٦
energized capacitor bank 15 initially connected 10 2٦ external 51011circuit.
capacitor unit (capacitor, power capacitor): ٨11 assembly 0٤ dielectric 211 لelectrodes 11 a container
(case), w ith terminals brought out, that 15 intended ٤0 introduce capacitance 1110 311 electric pow er circuit.
discharge device: ٨1 internal or external device intentionally connected in shunt w ith the terminals of a
capacitor for the purpose of reducing the trapped voltage after the capacitor 15 disconnected 1101٦ an
energized line,
externally fused 2021٤0 021 ٤: ٨ capacitor bank 1ﻻ fiises external 10 the (power) capacitor units,
filter capacitor: (202 1101(5) utilized w ith inductors and or resistors 10٣ controlling harmonic voltages and
currents 11 the power system,
fixed capacitor bank: ٨ capacitor bank not designed for automatic or frequent 511 ن11112
.
fused capacitor: ٨ capacitor having fuses mounted 011 its terminals, inside 2 terminal enclosure, 0 inside
the capacitor case, for ﻋﺎpurpose of disconnecting a failed capacitor element, unit, or group.
fuseless capacitor 0211: ٨ capacitor bank w ithout any 10505. internal 0 external, which 15 constructed 0٤
(parallel) strings of series-connected capacitor units.
individual capacitor ٤52: ٨ frise applied 10 disconnect an individual faulted capacitor unit from its 020.
internal ٤05 ع0٤ 2 capacitor: ٨ frjse connected inside 3 capacitor unit. 11 series with 31 element 0٣ a group
of elements,
internally fused capacitor (unit): ٨ capacitor unit that includes internal ftjses.
kilovar (1000 vars): The practical unit o f reactive po١١er equal ٤0 the product 0 اthe root-mean-square
(1٨15) voltage 11 kilovolts ( k V ) , the 115 current in amperes (٨). and the sine of the angle between them.
phase-over-phase: ٨ capacitor bank construction 0110٦ عstructure, w i t h the individual phases (0٣ 1225 10
delta connected capacitor banks) 0 ا1 ﻋﺎcapacitor bank installed above each other 211 لinsulated 110111each
other.
٨ي
m
د خ ل
ﻟل.
in :
111 L -)HHHHHHHHHI-
HHHHHHHHHHH
HHHHHHHHHHh
111 ٠
111
111
111 ;
111
٦١٦٦١
scries٠(clement)iconncctcd capacitor (unit): ٨ capacitor unit with the 21211125 اconnected 11 series with
each other between the line terminals, with one 0٣ more such series 5٣11125 within a capacitor unit
(Figure )ا.
switched capacitor (switched capacitor 4111٤): ٨ 202110٣ bank designed 10٣ controlled operation a n d o r
frequent switching.
thyristor-controlled reactor (TCR): ٨ reactor whose effective value 15 changed by controlling ﻋﺎ110١ 0ا
current by phase-controlling ﻋﺎاtum-on signal 10 the thyristors.
thyristor-svvitchcd capacitor (TSC): ٨ capacitor switched 0 and 0اا by thyristor control action.
4. B a s i c considerations
Protection 0٤ shunt capacitor banks requires 211 understanding 0٤ ﻋﻠﺎterminology (see Figure 2).
capabilities, and limitations of the individual capacitor units and associated electrical equipment. Four types
0٤ capacitor units and their respective connections may affect the relay function selection for the protection
scheme:
Figure 2 shows the basic terminology 31 examples of wye-connected 005 (grounded 0٣ ungrounded)
w ith these tour types of capacitor units.
Clause 2 shows the applicable standards 10٣ the associated electrical equipment 10٣ the individual capacitor
units, individual capacitor-unit 1S2S, bank switching devices, power 1S2S, voltage- or current-sensing
devices, surge arresters, and reactors.
"Internal Discharge
Device
ﺑﯾﻲ.
-م=ن
—ﺑﻲ
٦ اك Rushing
ﺳﯾب
دﻧﻣﺳﮫ
n
+ ب Elemem
. ٠
ﻣﺎط
ﻣﺎن
ﻣﺎن
ﻟﯨﻣوو
م —اﺑط١ذر
، —اب٩ﻛو
ة
ه اﻧب
اك
اﻧب.
ان
-ا،
ب
*
TI m m ٢٣
ا ﻟﻼ ﻟﻼ ﻟل
؛٠
ًطﻔﺎsee note (bl
Physical Connection ا
اااداCa،١acilor Units
in 01 ) عiroup
آ4
+ 1
ﻟﺞ ﻟﺞ ﻟﺞ ﻟﺞ ﻟﺞ
+ ب
Physical Connection
ه ﻟﺞ
ol. Senes String
-ﻟﻣﺻﺻﮫ
ال٢٢ ■
TTT *ﻟﺟﻠﺣﻠﺟﻠﺞ
ﻟﺞ ﻟﺞ أك ﻟﺞ ﻟﺞ
ﻟﻠم ٢٢٩٦
+
٦٧1٦٤1٦ protecting capacitor banks, 1115 important 10 realize the capabilities 0 اcapacitor units 50 that the
protection system can be applied 10 guard the capacitor units against system-induced events 211 upon
failures 0٤ some units 11 the bank. IEEE Std 1۴١ specifies the standard ratings 0 اthe capacitors designed
0٣ shunt connection to ac transmission and distribution systems.* IEEE 5 ﻻ1036™ gives application
guidelines for these capacitors. ٨5 per IEEE Std 18. the following 15 specified:
2) Capacitors 3٣ عintended 10 be operated 3 ا0٣ below their rated voltage. Capacitors shall be
capable 0٤ continuous operation under the contingency system and bank conditions provided
٦0 ٦ ع0١٦ عfollowing limitations 3٣ عexceeded:
1) ا100 % o f rated 115 voltage
2) 120% 0 rated peak voltage (i.e., peak voltage not exceeding 1.2 2 times (1 عrated
115 01132. including harmonics, but excluding transients)
b) 11 عcapacitance 0 4 unit shall not vary' more than -0% 10 410% o f the nominal value 025 لon
rated kvar, voltage, and frequency, measured at 25 ٥c uniform case 311 لinternal temperature.
c) Capacitor units mounted i n multiple ٣05 311 لtiers should be designed for continuous operation
for a maximum 4 اaverage ambient air temperature 0 ا40 ٥c during the hottest day. Capacitors
shall عcapable o f both continuous operation and switching operations at a minimum ambient
temperature of-40٥c.
)ل Capacitor units rated above 600 ٧ shall have an internal discharge device 10 reduce the residual
voltage 10 50 V 0٣ less in 5 min. Capacitor units 3٣ عavailable 111a variety 0 اvoltage ratings
(216٧10 24 940 V 0 and 51205 (2.5 kvar 10 about 800 kvar). Capacitor units designed for special
applications can exceed these ratings (see IEEE Std 18). See IEEE 51 ل1036 l o r capacitor short-
time overvoltage capability.
Depending 011the application, any 0٤ the four types o f capacitor units (i.e.٠ externally fused, internally
hised, fuscless, and unfused) may be suitable 10٣ ا capacitor bank design.
Externally fused shunt capacitor banks 3٣ عconfigured using one 0٣ more series groups o f parallel connected
capacitor units per phase. A n individual fuse, externally mounted between the capacitor unit and the
capacitor bank fuse bus, typically protects each capacitor unit. Figure 2(2) illustrates a typical capacitor
bank utilizing externally fused capacitor units. The capacitor unit can be designed for 3 relatively high
voltage because the external fuse 15 capable o f interrupting a high-voltage fault. اlowever, the kilovar rating
of the individual capacitor unit may عsmaller because a minimum number 0 اparallel units 15 required 10
311٥١٩٧ the bank to remain 11 service with one unit out.
11 general, banks employing internally fused capacitor units 3٣ عconfigured w i t h fewer capacitor units 1٦
parallel and more series 0101105 0 اunits 1131 3٣ عused 1٦ banks employing externally fused capacitor units.
Figure 2) illustrates 3 ٤٧101 اعcapacitor 000 utilizing internally fused capacitor 10101٤5.11٦ عcapacitor units
normally have 2 large kvar rating, and 3 complete unit 15 not expected 10 fail due to operation 0٤ 10595 0٦
failed internal elements.
A n internal 05 ع15 connected i n series w i t h each capacitor element. Each internally fijsed capacitor unit 15
constructed ٢٧1 اa large number o f elements connected 11 parallel 10 form 3 group and w i t h only a few
210005 connected 11 series. This construction 15 the opposite o f that found in externally fused capacitors,
which normally 2111010٧ a large number 0 اseries groups made up of parallel connected elements, w i t h
correspondingly fewer elements connected 111parallel per series group. With internally fiised capacitors,
١121 2 capacitor element fails, the current through 115 individual fusible link w i l l be considerably higher
than the normal current. 1015 higher current w i l l b l o w the fusible link, thereby isolating the failed element.
Fuseless shunt capacitor banks 3٣ عnormally used for applications where ﻋﺎfailure (short circuiting) 0٤ 0٦ع
capacitor element w i l l not cause excessive voltage 01 the remaining elements 11 that string. This 15 usually
at 0٣ above 34.5 ٤٧. The capacitor units 2٣ عnormally designed with ٤0 bushings with the elements
insulated from the case. 111 capacitor 11115 are connected 111series strings between 025 عand neutral (0٣
between line terminals for delta-connecled 0٣ single-phase installations). The protection is based 011 the
capacitor element’s failing 111a shorted mode. 11١ discharge energy is small because 110 capacitor units are
connected directly 1٦ parallel. Figure 2(c) illustrates a typical capacitor 031 utilizing fuseless capacitor
units.
The unfused shunt capacitor approach uses 3 series parallel connection of the capacitor units, similar to
externally or internally fused capacitor banks. This type 0 اcapacitor 0311 has not 0221 ١videly used. Some
users have removed fuses from externally fused capacitor banks because of excessive nuisance operations
and have ended ﻣﻠﺎ1 ااan unfused capacitor 0311. 11١ عunfused approach may 0 عuseful 01٦1banks below
34.5 ٦٧ (where series strings 3٣ 110 اpractical) or 01 higher voltage capacitor banks with modest parallel
energy. 1115 design may 1101require as many 303110٣ units 11 parallel 35 311externally fused bank because
ﻋﺎvoltage 011the fuse during operation 15 00 اa consideration. Figure 2( )لillustrates a 101 اﻟﻊcapacitor
bank utilizing unfused capacitor units.
A n externally fused shunt capacitor bank 0 ا2 01٧21512 عand voltage ٣311112 may be made ﻣﻠﺎo f a number 0ا
series 2111 parallel groups. ﻟﺎ5 ع0 اcapacitors with the highest 005510 ﻋﺎvoltage rating ااأresult 11 3
capacitor bank with 1 يfewest number o f series groups. 1115 airangement generally provides the simplest
rack structure and the greatest sensitivity 10٣ unbalance detection schemes. The available unbalance signal
level decreases significantly as the number 0 اseries groups o f 202110٣5 15 increased 0٣ as the number 0ا
capacitor units 11٦ parallel per series group 15 increased.
1٦١ عnumber 0 اcapacitor units in parallel per series group 15 governed by both 2 minimum 21 ل2 maximum
limitation.
he minimum number o f capacitor units per group 15 determined by the overvoltage considerations upon
150ا2ا101 0 اone capacitor unit 11 the group 21 لhas sufficient overcurrent through 2 ا05 ع011 2 faulted
capacitor unit 10 blow the fuse 11 3 reasonably 511011time (50 that the unbalance protection does 00 اrequire
a long time delay). Hie general rule 15 that isolation of one capacitor unit 11 3 group should 00٤ cause
voltage unbalance sufficient ٤0 place more than ا109% of rated voltage on the remaining capacitors i n the
group. 1٦ عvalue 0 ا ا%10 15 the maximum continuous overvoltage capability 0٤ capacitor units as per
IEEE Std 18.
The maximum number 0 اcapacitor units that 1113٧ be placed 111parallel per series group 15 governed ﻟﻂa
different consideration. ١Vhen 3 capacitor unit fails* other capacitors 11 the same parallel group ٧1 ااcontain
some amount o f charge. This charge w i l l drain off as 3 high-trequency transient current that flows through
the failed capacitor unit and 115 fuse. The fuse holder 21 لthe failed capacitor unit should withstand this
discharge transient safely until the fuse blows,
0٣ 3 large number 01 parallel externally fused capacitors* 10 minimize the probability 01 failure 0 اthe
expulsion fuse holder 0٣ rupture of the capacitor case* 0٣ both* ت٨1٨ (1 اrecommends that the total
energy stored 111 3 parallel connected group o f capacitors should 110٤ exceed 15 000 لfor all-film dielectric
capacitor units (10 000 اfor older all-paper 0٣ paper-film dielectric capacitor 00115) at maximum peak
voltage (rated voltage X 1٠1 X ٧2). F o r b ) 112 applications* N E M A C P I recommends هtotal parallel kilovar
limit 014650 ٤٧3٣ 10٣ all-film dielectric capacitor units (3100 kvar 10٣ older capacitor units). A l l - f i l m
dielectric capacitor 003115 have been applied up 10 9600 kvar 11 parallel with expulsion fuses (Mendis ال اع.
[01017). Consult عcapacitor and fuse manufacturer before exceeding the 4650 kvar limit 10 assist 11
ensuring that the total available discharge energy (including energy from capacitors 11 a parallel ٧ and or
111parallel banks) does 10 اexceed the discharge energy capability o f the fuse 0٣ the faulted capacitor.
113 capacitor bank having the minimum number 0٤ series 010005 has more 111314650 ٤٧3٣ per series group*
then capacitors o f a lower voltage rating requiring more series 010005 and fewer units 11 parallel per 0roup
may 0 عa suitable solution. اlowever, this arran0ement w i l l reduce ﻋﺎsensitivity o f the unbalance detection
scheme. The bank may have ٤0 ع٢٤110 ﻟﻊ110111 service for 3 reduced number 0 اisolated capacitor units
because the voltage 21055 the remaining units exceeds ا10 % o f their rated voltage. Splitting the bank 1110
two 522110115. 35 3 ‘٠double-wye٠١١may be 3 preferred arrangement 311 لmay permit 3 better unbalance
detection scheme. 11٦ 3 d uble-wye” arrangement* the failure 0 اfewer capacitor units w i l l also result i n 1ع
removal 0 اthe bank. The use 0 اcurrent-limiting fuses 11 3 single wye configuration 001 ل0 عanother
option.
A n internally fused shunt capacitor bank 0 ا3 0121 512 عand voltage rating may be made up 0 ا3 number 0ا
series and parallel groups.
Use 0٤ capacitors with 1٦ عhighest 0055101 عkilovar rating ٧1 ااresult 11٦ 3 capacitor bank with the fewest
number o f capacitor units. 115 arrangement generally provides the simplest rack structure and permits اا
largest number 0 اelement failures before unbalance tripping 15 required.
11 15 usually desirable 10 have al least 10 units 11 parallel 11 each series group. 11 the event 0 ا3 large
number 0٤ internal ftise operations 11 0٦ عcapacitor unit* the other capacitor helps 2 ﻣﻊthe terminal voltage
0٤ the affected capacitor dow n.
The maximum number 0٤ capacitor 01115 that 1٦٦3٧ 0 عplaced 11 parallel per series group 15 governed 0 the
parallel energy capability of 1 عinternal 10525. Placing 100 many capacitor units 11 parallel can jeopardize
the operation 0٤ the 0525. ٦he manufacturer 0 اthe capacitor units typically recommends the maximum
number 0٤ capacitor units 10 be connected directly 1٦ parallel.
1٤a proposed capacitor 00 having the minimum number 0٤ 52٣125 2101105 has 100 1٦٦٩1٦ capacitor units 1٦
parade!, then it 1113٧ be possible to reduce عparallel energy 0٧ changing the number of series 2101105 0٣
by rearranging the bank 11٤0 multiple wyes.
٨ fuseless capacitor bank 15 arranged with individual capacitor units in series (called 2 "series 51٣102))
connected between the phase terminals and the ground 0٣ neutral. 11٦ عsum of the individual capacitor unit
rated voltages 11 a string should equal 0٣ exceed the normal phase-to-ground 0٣ phase-to-neutral voltage 0ا
the capacitor bank. The desired three-phase kvar 0 اthe capacitor bank 15 accomplished by adding series
strings 0 اcapacitor units 11 parallel.
Fuseless banks are usually used at a higher 5٧5٤٤1٦1 voltage (3٤ 0٣ above 34.5 kV). Capacitor units are
connected in series strings. 1١ عcapacitor units usually have two bushings and may have additional
insulation between the capacitor elements and the case. Each string usually has more 1131 10 elements 11
series 10 assist 11٦ ensuring that 1 عremaining elements do not exceed ا%10 0 اthe nominal rating 1131
element 111 the 511112 shorts.
٨11 unfused bank would have a series, parallel arrangement. 1٤23ا٧ unbalance functions are normally set 10
trip the bank when ا١ عvoltage 01 remaining capacitor units exceeds ا%10 0 اrated voltage or the
overvoltage on remaining eletnenls in a faulted capacitor unit 15 high enough that cascading failure 01
5٧52111 transient overvoltage 15 likely. 011 smaller 00115. tripping may 0 عbased 01٦ the failure of a single
element. (For small banks.٤ا١ عprobability of element failure may 0 عsmall given the small total number 0ا
elements.)
٤0 an externally fused 0211* 0٤ 3 given size, 05 ع0 اa larger individual capacitorunit *ilovar rating
decreases the number 0 parallel capacitor units per group and increases the overvoltage change due 10
isolation of a single capacitor. Failure 0 اadditional capacitors 15 likely 10 occur 11٦ the same parallel group
as the first failure because these remaining capacitor units have the highest voltage stress. However, if tw o
capacitors اااin different parallel 010005. then the overvoltage percentage 15 1255 than that of the ٤٧0
capacitors failing 1٦ the same parallel group.
٨1٦ internally fitsed bank ٤21٦ connect the capacitor elements inside the capacitor unit in various series and
parallel configurations 10 minimize the overvoltage 51٣255 01٦ the remaining internal elements and
unaffected cai0acitor units when fuses operate. When a puncture 0٣ a short-circuit occurs 11٦ a capacitor
element, the current through the fuse increases 11٦ proportion 10 the number 0 اelements connected 1٦
parallel. 1115 1٦٣245 15 sufficient 10 melt the fuse within a very short time. 1٦ عcapacitor units are
designed with a !arge enough number 0٤ elements 11 parallel 50 that the operation 0 one 105 ع0005 110٤
result 11 ٤00 much increase 11 voltage 01 the remaining parallel 2121112015. Further failures 0٤ elements
causes overvoltage 01 the health)’ units, and unbalance protection should ultimately operate when
overvoltage exceeds design level.
Fuseless bank design depends 01 the capacitor elements being connected 11 series, and the expected 111ﻻ٣ع
mode o f the capacitor element w i l l عa 511011circuit. 1٦ عnumber 0٤ capacitor elements 11 series increases
with 1 عincrease 11 the nominal voltage rating 0 اthe capacitor bank, i f an element shorts, then the
remaining 202110٣ elements w i l l عsubject 10 overvoltage. The voltage increase 011each element w i l l be
approximately equal 10٤/(٤-1). where E 15 1 عoriginal number of capacitor elements 11 the string. ٦he
continuous 21 لovervoltage capability' o f the elements 15 equal 10 the capability o f the capacitor unit divided
ﻟﺄطthe number o f elements in series w ithin the capacitor unit.
11١ عunfused capacitor bank has 0 fuses. Unbalance protection should be applied 50 that follow ing failures,
1 عresulting voltage 01٦ the remaining healthy capacitor units 0005 00٤ exceed ا%10 0٤ their rating or the
recommended level specified by the manufacturer.
5. B a n k c o n n e c t i o n s
51 common capacitor bank connections are shown 11 Figure 3. The optimum connection depends 01 ﻋﺎا
best utilization 0اا ا1 عavailable voltage ratings 0 اcapacitor units, fusing, 311 لprotective claying. These
connections can عused for externally fused capacitor bank design, internally fused capacitor bank design,
fuseless capacitor bank design ( i f enough elements 3٣ عconnected 11 series for a protection scheme 10ﻋﻂ
applied), 311ل110 ا15 لcapacitor bank design. ٧irtually all 5005101101banks 3٣ عwye connected. Distribution
capacitor banks, however, may be wye or 02113 connected. Some banks 105 ع311I I configuration 01 each 0ا
1 عphases with a current transformer 11 ﻋﺎconnecting branch 10 detect the unbalance.
٦
12) %) (c)
()ل
دب٩ ” د
٠u|i(k٠h;i
٠6)٠إ٢0ه1ﻟﻠﺎ٩ﻳﺬ
1 ﻟﺎا- ungruumkd ٨٤٤
راا- ungHHKMkd 1٤س٨٠ ٦ل١ اا- tnaiir.il-s 111 or
٦11ﻻاا1
K'l - ا اﻟﺎ اااا٨٤
أا1٠،٦ml‘igiim٠،١ni
)ا
5.1 G r o u n d e d wye-connected b a n k s
Grounded ١٧ عcapacitor 0215. composed o f series- and parallel-connected capacitor 001ا5 per phase, 1٦3٧
require overvoltage/ unbalance protection. Figure 2 510١٧5 typical bank arrangements.
Grounded capacitor banks provide a low-impedance path to ground for lightning surge currents and give
some protection from surge voltages. Some banks 1٦3٧ be operated without surge arresters, taking
advantage of the capability o f the capacitors to 35010 the surge.
Grounded capacitor 005 3150 provide 3 lowtmpedance path 10 ground for triplen harmonic currents.
These harmonic currents may cause communication facility interference, 1٤ such circuits parallel power
lines. Additionally, an open phase 11 the vicinity o f the capacitor bank produces zero sequence currents that
may cause capacitor bank ground relay operations. Harmonic resonance may also ع3 problem because
capacitor banks are 1 many cases part o f a resonant loop, resulting i n magnification 0٤ specific harmonic
components.
١Vhen the neutral 15 grounded, recovery voltages encountered during switching are reduced: however,
careful consideration should عgiven 10 the effect 0 اinrush current 01 current transformer ((1) circuits
(see 10,6.1). communication circuits and bank protective relay performance (52 ا1.3).311 لthe 111211010ا
system grounding (see 6.1).
There 15 10 overvoltage across the remaining capacitor units 11 3 failed, externally ftised capacitor unit 15
isolated with 3 fijse: therefore, unbalance relay protection 15 not required. The individual external capacitor
fuses should be capable 0 اinterrupting the 5٧5٤٤1٦٦ available fault current.
Internally fttsed and unfttsed capacitor 0205 should have unbalance protection to 20 1 لexcessive element
overvoltages and 10 trip the hank for severe unbalance conditions.
Internally 1sed capacitor units should ﻋﻂarranged 11 the bank design 50 that the energy 11 the parallel
group does 0٤ exceed the interrupting capability of the internal 10525. Relatively small banks can ﻋﻂ
designed with internally fused capacitor units 2 لstill use large capacitor units for a simple design.
The fuseless design 15 not usually applied ا0٣ 55٧5٤٤11 voltages 1255 than about 34.5 ٤٧. 1٦ عreason 15 that
there 5100111 ﻋﻂmore than 10 elements 11 series so that the 2 does not 2٦ عto ﻋﻂremoved from service
for the failure of one element because the voltage across the remaining elements would increase ط٧ 2 factor
0 اabout £ / ( £ - 1)٠ where ٤ 15 the number o f elements 1٦ the string.
large capacitor banks may 0 ع5ام1 ا1110 ٤0 wy e 52210115.10 maintain the parallel energy o f a series group
w ithin the limits of capacitor units 0٣ fuses. The characteristics o f the grounded double ٧ عare similar to a
grounded single ١٧ ع021 *. The two neutrals should عdirectly connected with a single connection 10
ground.
The double ١٧ عdesign allows a secure 3 لfaster protection with a simple uncompensated relay because
any system 2210 sequence unbalance affects both ٧٧25 equally, but a failed capacitor unit ااا0 عdetected
11 عneutral unbalance. Time coordination may 0 عrequired to allow’ a fuse 10 blow 1٦ or 01 3 failed
capacitor unit. I f 1٤ is a fuseless design, the time delay 311 be set short because 110 fuse coordination 15
required.
11 fuseless capacitor banks, double ١٧٧ عdesigns w i t h voltage differential schemes also may mitigate
nuisance alarms 0٣ trips caused by the unequal variation 0 اcapacitance ﻋﻠﺎل10 solar radiation.
5.2 U n g r o u n d e d wye— c o n n e c t e d b a n k s
Ungrounded wye 0215 00 not permit zero sequence currents, third harmonic currents, 0٣ large capacitor
discharge currents during 5٧5٤٤1٦ ground faults. (Phase-ophase faults may still occur and w i l l result i n
large discharge currents.) 1٦١ عneutral point 0 اthe bank, however, 50011 عinsulated 10٣ full ا1٦ عvoltage
because i t is momentarily at phase potential when the bank 15 switched 0٣ when one capacitor unit fails 1113
21 configured with 2 single 21000 0ل ا115 0٣ during close-in system ground fault.
٤0٣ systems with line-to-neutral voltages corresponding 10 available capacitor ratings, wye-connected
capacitor banks with 3 single series group per phase may be used. The capacitor bank neutral 1٦3 be
ungrounded 10 avoid ﻳﺎاneed for power fttses 10 interrupt the system short-circuit fault current 0٣ 10
minimize the fiow o f triplen hamionics, w hich can cause telephone interference. This design requires that
single-bushing capacitor units 0 ع1110112 لon 211insulated rack. I f two-bushing capacitor units are used
with a grounded rack, then 2 fault 10 the case 1 ع اا4 system line-to-ground fault. High 5٧5٤٤111fault
currents 13 lead 10 case rupture. ت0٣ externally fused capacitor 03105. the 10525 511011 ﻻhe selected 10
interrupt the available phase-to ground short-circuit current, 1٤lower rated 11ses 3٣ عused, then a fault 10 the
capacitor case may not he cleared by the capacitor-unit 105 عand will require that the fault be cleared by٤ا٦ع
capacitor bank overcurrent protective devices. Ungrounded wye capacitor 0215 usually 00 110 اrequire
current-limiting capacitor-unit fuses because current through a faulted capacitor unit 15 limited to 1.73 times
normal phase current. However, caution needs to be exercised when re-fusing a bank 0٤ 115 type because
faulted capacitors 11 different phases could result 11 a phase-to-phase system fault,
٦٧٧ عbanks w ith multiple series groups 113٧ also 0 عungrounded. Such a bank 0005 not provide 2 path 10
ground ا0٣ a surge voltage and provides 10 path 10 ground for third harmonic currents. 11١ عentire bank,
including the neutral should be insulated 10٣ ااﻻline 01122.
When a capacitor 00* 022011105100 large 10٣ ﻋﺎ4650 kvar per group maximum for expulsion 1055 and 15
large enough 10 meet the minimum units per group requirement as outlined in 4.3. the bank may be split
1110 two wye sections. Whenﻻ٦ ع10 neutrals are ungrounded, ﻋﺎbank has the same characteristics as the
ungrounded single-wye bank outlined in 5.2.2. These two neutrals may 0 tied together through a current
transformer 0٣ 2 voltage transformer 10 facilitate certain protection methods. ٨5 for any ungrounded wye
bank, the اھﺎ اﻻعinstrument transformers should 0 عinsulated from ground for ااﻻIme-to-ground voltage.
Delta-connected banks 3٣ عgenerally used 01ا٧ at distribution voltages and 3٣ عtypically configured ٧11 اa
single series group 0 اcapacitors because banks 3٣ عsmall, rated at line-to-line voltage. Delta-connected
banks require a two-bushing capacitor 0٣ single-bushing units with insulated racks. Delta-connected banks
3٣ عfrequently used at 2400 ٧ because capacitor units for wye connection at 2400 ٧ are 110 اreadily
available.
٦٧1٦ only 0٦ عseries group 0 اunits, 00 overvoltage occurs 221055 the remaining capacitor units from the
isolation of 3 faulted capacitor unit. Therefore, unbalance detection 15 00٤ required 10٣ protection اﻻطmay
be used 10 detect the outage of units within the 031. No zero-sequence or third harmonic currents can flow
1110 2 delta-connected capacitor bank.
Where 0٦ عseries group 0 اcapacitors 15 used, the individual capacitor fuses should 0 عcapable of
interrupting the system short-circuit phase-to-phase fault curtent. 1115 design may necessitate current-
limiting fases.
If internally fused capacitor units 3٣ عused, then unbalance detection 15 required 10 detect a capacitor w ith
failed elements. There 15100 visible indication 0 اa blown fuse. 10 0٣ more senes groups are normally
required 11 each capacitor unit 10 enable the internal fuses 10 interrupt the fault current.
Static var compensators usually use the della connection for the thyristor-switched capacitor (15(5) 10
simplify the controls 21 لoptimize the use 0 اthe thyristor valve.
5.4 H configuration
Some larger banks use 21 11 configuration 11 each phase with 3 current transformer connected between the
1٧0 1205 10 compare the cutrent 00٧٧11each leg. ٨5 long as ااهthe capacitors are normal, 110 current ٧1اا
flow through the current transformer. I f 2 capacitor fitse operates, then some current 1 ااflow- through 1٦ع
current transformer. 1115 bridge connection can be ٧٤٣٧ sensitive. This arrangement 15 used 01 large banks
١11 اmany capacitor units i n parallel.
6. other considerations
The performance 0٤ the protection method can 0 عinfluenced لthe ل251211 0 اthe capacitor bank.
Therefore, protection consideration begins 11 ﻻbank design (52 ع4.3). 111general, shunt capacitor 00*
design requirements necessitate an increase 11 minimum 001* 512 ع١1 اsystem voltage. The higher the
system voltage, the larger the bank investment 0 [ ل15 o f costly damage, i f protection does 110 اoperate
correctly. Although capacitors having large 110٧3٣ ratings may reduce the overall cost of the bank, they
may also reduce the choice o f different capacitor connections 0٣ combinations.
١Vith grounded ١٧ عcapacitor banks, high-frequency, high-magnitude transient currents 1٦3 flow from the
capacitor bank neutral 1010 the substation ground. Voltages induced by these ground currents may cause
malfunction 0٣ damage 10 protection systems 0٣ other equipment, even 11 parts 0٤ the substation 110 اdirectly
related 10 the capacitor installation.
— Discharge 0٤ the capacitor bank 110111 ١ عpeak 0٤ the operating voltage 1110 3 nearby line-to-
01000 لfault
— Line-to-ground fault 111the capacitor bank (large discharges may occur 35 scries groups arc
shorted out)
1125 high-frequency ground mat transient currents are 21 important consideration 1٦ the design o f the
ground mat 1٦ substations that include grounded wye capacitor 211*5. 1٦ عuse 0 102111 52 اﻻgrounding can
ﻣﺎﻋﺎkeep the high-frequency transient currents out o f 03115 o f the substation not directly connected w ith the
capacitor. ١ here there are multiple capacitor banks 2 اthe same voltage 11 2 substation, the use o f single
point grounding w i l l reduce the ground mat currents between capacitor 205 associated with capacitor
switching. The subject o f capacitor bank grounding, including peninsula grounding 2 لsingle point
grounding, 15 discussed more fully 11 ﺗﺎﺗﺎ ﺗﺎاStd 1036.
These high-frequency ground currents 3٣ عalso 31 important consideration 111 the shielding and protection o f
relaying circuits associated with a capacitor bank. 11125 considerations are discussed 11 10.6. l o r
instrument transformer secondary grounding considerations, refer 10 ﺗﺎﺗﺎ ﺗﺎاStd (57.13.31٨.
The application 0 اlarge shunt capacitor banks w ith sw itched parallel 005 11 high-voltage transmission
5٧5٤٤115 involves 3 number 0٤ considerations, one 0 اwhich 15 grounding. It 15 generally recommended that
the neutral of capacitor banks be grounded only in systems that are effectively grounded. 11 the event 0 ا3
phase-to-ground fault, a grounded capacitor hank neutral 11 an otherwise ungrounded 5٧5٤٤1٦٦ may lead to
10 اtransient overvoltages 11 the 5٧5٤٤1٦ 21 لcapacitor hank 35 3 result of restriking of the arcing fault ٤0
ground. One main advantage associated with 021113 اgrounding 15 less severity of the transient recovery
voltage (TRV) across the first pole of the sw itch 10 clear, interrupting the charging current of the capacitor
0211. The recovery voltage across the fjrst 001 ع10 open consists of trapped charges 01 the capacitors and
the variation in the 60 Hz voltage 0 اthe 5٧5٤٤1. Due 10 system parameters and capacitor hank size, ٤ع
recovery’ voltage can be approximately 10 times the normal peak voltage when 1 عbank 15 grounded. 01
211 ungrounded bank, ٤ا١ عmagnitude 0٤ the first peak of the recovery voltage can عas high as three times
the peak 5٧5٤211 line-to-ground voltage when the bank 15 switched. Because recovery’ voltage 15 4 critical
factor 111 determining the capability’ 0٤4 switching device 10 switch capacitive reactive power, it may 0ع
desirable (11 terms 0 اswitch performance) 10 ground the neutral 0 اshunt capacitor banks.
IEEE 5 ل (37.04١ and ANSI (37.06-2000 recommend that both the shunt capacitor bank and 1 ع5٧512111
0 grounded at voltage levels 01121 ٤٧ and above. Many capacitor banks of higher voltage are installed
ungrounded, but the circuit breaker manufacturer should be consulted 10٣ the application of a breaker 1ا
these conditions 3٣ ع00٤ met. ١٧hile 11131٦٧ shunt capacitor banks are directly connected 10 2 high-voltage
substation bus, sw itched capacitor banks may 0 عconnected 10 tertiaries 0 اpower transformers that are
connected 10 the line or possibly 10 the bus. Grounding 1١ عneutral 01 a wye-connected capacitor bank
should 0 عdone only 01 an effectively grounded system. For instance, the delta tertiary 0٤ the auto
transformer represents 31 isolated network: grounding the neutral 0 اthe capacitor 01* connected 10 the
tertiary winding 11135 this side 0 اthe transformer capacitively grounded. 02٧0114205 may 0ع
experienced during lineto-ground faults for certain ratios 010/1. depending 011 5٧5٤٤1٦. transformer, and
capacitor 03* 031311121215.1 اthe neutral 1510 0 عgrounded 01 3 system that 15 not effectively grounded,
then the application should 0 عthoroughly analyzed for proper application 0٤ surge arresters, bank
configuration, bank sw Itching devices, and so on.
The protection 0٤ shunt capacitor 0215 involves both bank and 551٤1٦ protection schemes. Bank
protection schemes 3٣ عprovided 10٣ faults ٢٢ 111 the capacitor bank itself. Bank protection 1113٧ include
112105 such 35 3 means ٤0 disconnect a faulted capacitor unit or capacitor element(s), a means to initiate
tripping 0٤ the bank 11 case 0 اfaults that may lead ٤0 a catastrophic failure, and alarms 10 indicate
unbalance within the اط
5٧5٤٤1٦ protection schemes 3٣ عprovided ٤0 protect the capacitor 31 11011stresses that may عcaused ط5
the system and ٤0 protect the substation and system 110111 stresses that 1113 be caused ط٧ the 002131010٤ the
capacitor bank. 515٤2111 protection may include 1٤٤1115 such 35 a means 10 limit overvoltage and excessive
transient overcurrents and 10 disconnect the bank 11 the event 0 3 major fault within the capacitor
installation or 0111 عsubstation bus 10 which the capacitor bank 15 connected. System protection may also
include alarms and/or 3 method 10 disconnect ا1 عentire shunt capacitor bank 111 order 10 prevent farther
damage 10 the capacitors due ٤0 abnormal system conditions.
Table اlists various bank and system protection schemes typically applied to shunt capacitor banks. Each
condition listed 5110111 ع لconsidered w hen providing protection for 2 shunt capacitor bank.
System outage. Undervoltage relays. Capacitor banks ( w hich may be) energized
through 3 transformer w ithout 102 ل01 the
transformer may need 10 عsw itched 01٤
before reenergizing the system.
Transmission line tripping (a) Transfer tripping o f the Capacitor 210*5 directly connected to 1
(10٤ capacitor banks capacitor bank sw itch transmission ا1 نw i t h 110 connected load may
connected 10 1 transmission () Undervoltage relays. need 10 ﻋﻂdisconnected 1101 the line before
line segment). closing the line.
Breaker failure. Breaker failure relays. Local 0 remote breakers should have
capacitor sw itching capability i f they tripاا١ع
bank w ithout parallel load during breaker
1411 ع[رconditions.
11 externally fused capacitor banks, several capacitor element breakdowns may occur before ا ﻋﺎا15ع
removes the entire unit. The external fuse w i l l operate when 3 capacitor ﻻ1111becomes (essentially) short-
circuited, isolating the faulted unit. Unbalance protection 15 typically designed 10 remove the 000 10111
sen ice when ااresulting overvoltage becomes excessive 01 the remaining healthy capacitor units.
Internally fused capacitors have individual 303110٣ elements within 4 capacitor unit that are disconnected
w hen an element breakdow n occurs. The risk o f successive faults is minimized because the fuse اازأisolate
the faulty element within a few cycles. Unbalance protection 15 typically designed 10 remove ا bank from
sen ice when the resulting overvoltage becomes excessive 01 the remaining healthy capacitor elements 0٣
units.
For useless or unfused capacitor banks, 3 failed element 15 short-circuited by the weld 13 اnaturally occurs
at the 0011 اo f failure. Unbalance protection 15 typically 405101 ﻟﻊ10 remove the bank 101 senice ٧111 ﻋﺎ
resulting ovenoltage becomes excessive 01 ﻋﺎremaining healthy capacitor elements 0٣ units.
The fuse selection should provide sufficient safety margins 10 assist 11 ensuring the availability 0 اthe
capacitor banks. The fuses should be selected 10 isolate dielectric breakdown quickly and interrupt the
parallel energy at 11 fault location.
302110٣ fusing requires the careful protection considerations given 11 7.1.2 and 7.1.3 10٣ externally and
internally fused capacitor banks.
ﺗﺎﺗﺎ ﺗﺎا51 لC37.48™ covers in detail the application guidelines for high-voltage external capacitor 10525.
The 2100٣٤٧ stored 1٦ the healthy capacitors 0 ا0 ع5٣125 group 0 اparallel-connected capacitors ااا
discharge 1110 the failed capacitor unit o f that group and 1ا5 115 ع. 1٦ عfuse should عable 10 interrupt the
energy supplied by 1 عparallel group 0 اcapacitor units w hen they 2٣ عcharged 10 their 023 اvoltage.
I f the capacitor bank design has 21٦ available dischatge energy higher 1٦3٦ the 2022 110٣ units 0٣ expulsion
fuses can w ithstand, then cutrent-limiting fuses 1 ا31 adequate energy' rating should عconsidered.
When ungrounded wye capacitor banks 3٣ عsupplied 1٦ 2٦ enclosure, current-limiting fuses 0٣ appropriately
designed expulsion fuses having exhaust control devices and intended 10٣ use 111511enclosures should be
1052. ٨٣ عproducts t o m 105 5 without exhaust control 11٦3 cause 0rther evolution 0 ا.2 fault 111510 عthe
confined enclosure. ٨150 note that the 1155 may have 10 interrupt the 111 5٧5121 fi٠ault current and must ﻋط
appropriately rated. Even ungrounded capacitor hanks could have 2 fi٠ault ٤0 ground. 10ت٣ example, 0٦
enclosed single-group ungrounded ١٧ ع02115 13 اare designed ١vith 10 hushing units, the fitrst hushing 15
05 ل10٣ ٤١ عphase connection, the second hushing 15 used 10٣ the neutral connection, and the case 15
connected 10 ground. 1115 arrangement requires the capacitor fiises to interrupt system fault current 11 the
event ot, 3 failure of, the unit insulation near the phase hushing. ا1 applications having high short-circuit
current, current-limiting 0S2S may 0 عrecommended to reduce the energy during 2 t'ault.
NEMA CPI suggests 2 parallel energy limit 0٤ 15 ( ا4650 kvar) t٠or all-film dielectric capacitors.
Expulsion 0525 are frequently applied ١vith higher parallel energy (to 30 kJ) (Mendis et al. 13101). 11115
higher energy application 15 acceptable if٠the total available discharge energy of’ the hank does not exceed
the discharge energy rating of the fuse 0+ ﻻ1 عcapability of the faulted capacitor unit.
10 determine proper 052 selection, the capacitor unit case rupture curve should be available from the
manufacturer. 35 عrupture curves are different for different capacitor unit constructions 311 لdesigns.
The total clearing curve 0٤ the fuse 0٣ fuse link 15 then compared 10 the case rupture curve: adequate
01012110 15 assured 11 total clearing curve of the use 1510 the left of and below the rupture curve of the
capacitor unit.
Other important considerations for external ا05ع selection 31 لoperation include the following:
— Fuses should ع designed and rated 10٣ the externally (used capacitor bank application.
— Fuses should provide for ا1ا ع35ا isolation 0 ا3 faulted capacitor unit.
— Voltage interruption capability, 0 اthe 0se should ع coordinated with the voltage withstand
capability 0 اthe capacitor unit.
— Fuses should handle ا٦ع transient 11011ل5 اand outrush current vvithout inappropriately operating.
— Fuses should 0 عdesigned ا0٣ ﻋﺎا current loadability requirements, including harmonics 311ل
adequate alovance factors.
— Fuses should ع designed lor ﻋﺎ inductive 30 لcapacitive current interruption capability.
— Fuse characteristics should coordinate between the different shunt bank protection schemes and
the characteristics 0٤ the 11525 (that 15. expulsion, current limiting, or a combination 0٤ both).
11١ عoptimum performance of 31 internally fused capacitor bank relies 0111٦ عdesign 211 لselection of fitses.
Adequate fuse 010213101should 0 عassured 1٦ case 0 اcapacitor element breakdown. Element fuses in
internally fused capacitor 205 have current-limiting properties that 3٣ عmainly dependent 01٦ the available
fault current, the discharge energy ( اح1 ) from the elements connected 11 parallel with the faulty' element,
and the voltage across the faulted element at the instant 0 اfailure.
The fuses should properly isolate the faulted element after fuse operation. Fuses should be designed ١vith 3
sufficient oveioltage-interrupiing capability 10 assist 11 ensuring reliable and safe operation under extreme
transient element ovei-voltage conditions, considering both the system transient overvoltage and the
unbalance within the capacitor unit resulting from previously blown 0525. Fuse selection typically
considers the following:
— Inrush and outrush currents ٥٧٤٣ the life 0 اthe capacitor units
The fastest appropriate element '؛use that meets ﻋﺎpreceding requirements should ﻋﻂselected. The
remaining fuses in a ﻟﻌﺎا ﻟﺎﺷﺎcapacitor unit should he capable of safely interrupting subsequent internal
element failures.
Unbalance protection normally provides the primary protection for capacitor elements 0[ unit failures, rack
faults within 3 capacitor bank, and other abnormalities that ,nay damage capacitor units 31 لor fuses, Such
faults may cause substantial damage 11 a small fraction of a second. The unbalance protection should ha٧٤
minimum intentional delay 11 order 10 11111111112اا ع1 عamount of damage 10 اا1 ع0310 in the event of rack
faults.
Capacitor unbalance protection 15 provided 11 many different ways, depending 01 the capacitor bank
arrangement. The variety of unbalance protection schemes that are 05 ﻟﻊfor internally fused, externally
fused, fuscless, 0٣ unfused shunt capacitor 0315 15 illustrated 11 the figures 0 اClause 8 along ١vith
examples 0 اthe required settings calculations.
Unbalance protection normally senses changes associated with capacitor clement 0٣ ﻟﺎ11failure andiOr 15ع
operation. It 15 not generally sensitive enough 10 detect 3 defective connection. Defective connections 1113٧
deteriorate until 3 fault occurs within the capacitor bank, causing the unbalance م10122110110 operate. ٨
defective connection within 3 capacitor unit (usually a rare occurrence) may result 11 3 pressure buildup
3 لcapacitor unit rupture before the operation 0 اthe unbalance protection. 1 عunbalance protection
therefore should operate quickly because of the possibility 0 ا13 عfault after case rapture.
With 3 shunt capacitor bank constructed 50 that ﻋﺎindividual phases are well separated 00 separate
structures, an arc-over w ithin the capacitor bank ١ اااbegin as an arc over 0 اa single series group. Such 2
fault produces very' little phase overcurrent. If an unbalance relay protection scheme fails 10 operate, more
and more series groups 0 the same 035 ع31 become atTected until ١ عbank overcurrent ٣213٧5 trip the
bank 0٣ fuses clear. 1٦15 fault 15 accompanied ط٧ heavy damage to the bank, including many blown fuses
and ruptured capacitor units. Instantaneous overcurrent relays 3٣ عusually 110 اeffective 10٣ rack faults
because 0٤ their required high setting.
1٦ عmost effective protection 10٣ an arc-over within the capacitor 21* 15 provided by 3 15 اunbalance
relay. ٨ 5011 time delay for the unbalance relays minimizes the damage caused by 1 *عfaults. Intentional
delays as short 25 0.05 5 have been used. This short unbalance time delay, however, should 0 ٤ ع1255than
the maximum clearing time of the capacitorunit 0٣ element fuse.
٨11 unusually 101٦2 unbalance time delay may be required 10 coordinate with the power 5٧51٤1٦ adjacent
protection schemes, unless the unbalance relay scheme 15 a 1٧ ﻋﻢthat does not respond 10 (0٣ uses
compensation for) system unbalance (10٣ example, 22٣0 sequence voltage).
'1 he setting 01 the unbalance trip relay should ﻋﻂ5٤٦511 عenough ا0 010 اعthe capacitor units or elements
from continuous overvoltages that result 1101٦1 individual unit 0٣ element failure 2 لresultant fuse
operation. When 5 اع011this basis, the resultant sensitivity 15 typically adequate 10 detect the initial rack
fault, assuming the initial fault is across 0٦ عseries section 010 عphase.
Although the unbalance trip relay 15 ﻋﺎmost effective protection 10٣ 3٣ عdetection 0 ا2 5٤115 section, the
neutral voltage 1٧0 ع0٤ unbalance relay [for instance, see figure 21( ])طshould not be relied 011 for rack fault
protection 011capacitor banks where all three 0355 3٣ عnot well separated. For example, consider 31
ungrounded single ١٧ عcapacitor bank with ٤٧0 series groups per phase, where 3 ااthree phases are
installed 01 a single steel structure. The individual phases are stacked over each other 50 that the initial
fault may occur 25 a midrack phase-to-phase fault, as sho١vn 1٦ Figure 4. 1115 fault 0025 not cause 2٦
unbalance 0٤ the neutral voltage (0٣ neutral cun-ent, if grounded); therefore, a neutral unbalance relay does
00٤ respond. ٦he initial fault may spread until 1٤ becomes severe enough 10 operate the overcunent relays.
However, there may 0 عconsiderable damage involving ااthree phases before the bank trips. Methods for
protecting a midrack phase-to-phase arcing fault include the 10110٦٢102:
— Using 3 fixed time overcurrcnt relay set typically 3 اabout 1.35 times normal 035 عcurrent and
using a short time delay (typically 0.1 5). The ovcrcurrcnt relay should have 3 fast dropout time.
— ﻻ51112a current unbalance or negative sequence current relay. Negative sequence relays 35 a
backup protection can be 5 اع10 be 1110٣ sensitive than phase overcurrent relays, but tripping
should be delayed 10 coordinate with the other 12135 11 the system. ٨ setting 0٤ 10% 0٤ the
rated capacitor current, taking 11110 consideration the maximum system voltage unbalance and
the maximum capacitance variation together with 3 time delay setting 0 ا15 10 25 cycles, may
provide adequate coordination for faults external 10 the bank. However, it 1113٧1101 prevent
031112225 due 10 arcing faults within the bank structure.
10٣ wye-wye banks, the unbalance protection will operate ٤0٣ this type 0 اfault, provided the correct groups
are bonded 0 عrack (see 8.3.2).
Arcing ع
Parallelع000ع110ام م
capacitor units
System protection may help reduce stresses and minimize damage 10 capacitors 01 the occurrence of the
following events:
— Other considerations (such 35 1055 of voltage transformer fuse, breaker failure protection, and
surge arrester protection)
External 3٣٤ 110 w ithout the prompt operation of the unbalance protection may cause case ruptures 0٣ other
damage 10 capacitor units 3 لmay blow fuses. It may ﻋطdesirable 10 provide the capacitor 00* with
redundant unbalance protection and or phase or negative sequence current protection 10 minimize damage.
The ovcrcurrcnt protection 15 not normally sensitive 10 arcing within 3 capacitor 031 and, 1 ا1 اsenses 3
disturbance, 15 normally 100 slow.
he capacitor bank and other equipment 11 the vicinity 1113 ﻋط لsubjected 10 overvoltages resulting 1011
abnormal system operating conditions. If the system voltage exceeds اcapacitor or equipment capability
w ith اcapacitor 00 01 line, then the bank should be removed w ith minimum time delay. (Removing the
capacitor bank from the 5٧5٤٤1٦٦ lowers the 5٧51211 voltage 11 the vicinity 0 اthe capacitor, reducing the
overvoltage 01 other 5٧51211 elements.)
In some cases, inverse time overvoltage relays may عrequired 10 protect 1 عcapacitor units from severe
5٧5٤٤11 overvoltage conditions. 11 ا15 case, a suitable overvoltage relay provided with adequate protection
algorithms should be used and set according 10 the capabilities provided by ﺗﺎﺗﺎ ﺗﺎا51 ل1036 0٣ the capacitor
manufacturer. ا٤ the capacitors 3٣ عexposed 10 overvoltages 25 a result 0 ا3 combined fundamental and
harmonic content, then the manufacturer should be asked 10 provide the 023* voltage 5٣255 levels 35 a
function 0 اtime and temperature. Modem all-film capacitors are affected by crest voltage: therefore, 023*
overvoltage measuring relays are recommended for اا15 application.
For very large EI1٧ capacitor banks, 1 ا15 advisable to install three-phase overvoltage relays (59 ا8) ٤0
monitor the ﻻط5 voltage. 11٦ ع59 B relays 11 Figure 8 may ا٣1 م1 عbank quickly 10٣ extreme overvoltage
conditions. 10 avoid nuisance tripping ﻻل٣100transient overvoltage conditions, 11 some cases, tripping 15
delayed ط2 timer. Because this tripping 15 not due to 3 fault within the capacitor 00*. the capacitor bank
15 not 10ل out. typically, the capacitor bank is locked out when bank protection operates 10٣ 21 internal
fault and 15 not locked out 1٤ trip occurred not due to a fault within a bank. 1115 facilitates ٤٤٧1٤ 0٤ ا1٦
causes of bank protection operation: 111 addition, interaction 1 ﻻthe automatic voltage regulators (AVRs)
or other ط0 controllers can ﻋطreviewed 05 well.
800* overvoltage protection relays 025 لon phase currents have been used 11 ا٦ عindustry' instead 0ا
conventional overvoltage relays saving ع ﻋﺎ05 اof installation of voltage transformers. 11١15 application 15
possible by recognizing dtat ﻋﺎvoltage !'across 3 capacitance c 15 tied with the current . ،lowing through
عcapacitance, as 111 Equation (1):
()=ل40ا (I)
1٦ عrelay estimates the instantaneous value 0 ا1 عvoltage based 01٦ Equation (1) and therefore incorporates
the impact of hamionics 2 لother signal distortions. It then applies the voltage replica 10 2 standard
operating overvoltage characteristic 25 per ﺗﺎﺗﺎﺗﺎاStd 1036. The relay designers exercise ٤3٣ ع10 2551511٦
ensuring that the 00212101 of integrating 3 signal 15 stable 0٧٣ long periods 0٤ time and does not yield 10
drifts 11٦ the voltage replica signal. The current-based overvoltage protection can also عconsidered 2
backup function 10٣ the 1055 of potential conditions.
Temperature variations 111 the actual capacitance would cause some accuracy errors 111 this protection
function as it uses 1 ﻋﺎnominal value 0٤ the capacitance per Equation (1). Also, undetected capacitor 1111٤
failures 21٤٣ the value 0٤ the actual capacitance 21 لthe function either underprotects 0٣ overprotects the
hank using the 101111 اهvalue of the capacitance when deriving 1 عvoltage replica signal,
Each time 2 large grounded ١٧ عcapacitor hank 15 energized, momentary capacitor inrush currents 11 01ع
phase and 11 the neutral may approach the ground fault trip level. Where a parallel hank 15 already
energized, the 1112211110 ﻋﻞand frequency of this inrush current 15 much higher than the inrush to an isolated
capacitor bank 211 لcan he 01 the order of thousands of amperes (Abdulrahim اه اع. 1311). Spurious relay
operations, relay failures, current transformer failures, charged substation fences, and ground mat problems
may result. Where inrush currents are excessive, certain measures have 10 ﻋﻂtaken, such as usage 0ا
current-limiting devices, switching devices with preinsertion resistors, and preinsertion inductors, 211ل
proper grounding of parallel bank as described 111 IEEE 51 ل1036.
Protecting the capacitor bank against 3 major fault, such 25 a line-Oline fault 0٣ a line-to-ground fault,
generally requires external 01012 ن1101 . such as power fuses, circuit breakers, 0٣ circuit switchers with
associated relay circuits. For best protection, the relays should 0 عset as 10٧ and fast as possible, with only
enough delay 10 avoid tripping 011 external system disturbances.
Tin eovercurrent relays can be applied with the desirable minimum pickup 0 ا%135 0 اnominal phase
current 10٣ grounded ١٧ عbanks 0٣ 125% 10٣ ungrounded banks. Instantaneous relays, if used, should 0 عset
high 10 override inrush or outrush transients.
Time overcurrent functions 11 modem relays with fundamental frequency band-pass filters 3٣ عnot 1131
susceptible 10 inrush or outrush currents. Successful operation may 0 عobtained by setting instantaneous
relays at 3 10٧٤٣ value compared w ith relays without band-pass filters: typically, three 10 four 1111105 the
capacitor rated current (0٣ ١0٧٤٣) 15 sufficient 10 override back-to-back bank switching.
11 some large capacitor banks, redundant overcurrent devices may protect 10٣ short circuits within the
capacitor bank. Figure 8 illustrates 10 5ع15 0 اthree-phase overcurrent relays (50/51) with short-time
overcurrent 311 لinstantaneous functions. ٨ low, burden 10٣ 11115 neutral overcurrent ٣213٧ 5 IN reduces high
voltages 221055 current transformer secondaries caused ﻟﺎطhigh-frequency outrush currents 1101٦٦ the bank
during 311 external fault.
For ineffectively grounded systems with ungrounded capacitor banks, the neutral overcurrent relay 511
should عset sensitively 10 detect and 10 provide fast clearing 10٣ ground faults of low' magnitudes not
detected by phase overcurrent relays.
For effectively grounded systems with grounded ٧ عcapacitor banks, the high-frequency outrush current
11010 31 external ground fault will not normally operate the 5 IN ground relay. The unbalanced capacitor
0311* load current caused by the external ground fault may be sufficient 10 cause the ٣2 ا3 10 pick up and
٤٣110 the capacitor bank 1٤the 51٦115 set 100 low,,10 prevent this inadvertent tripping, the trip 0٤ the 5 IN
relay is normally set above the capacitor phase current.
Figure 8 illustrates one unbalance protection scheme in use 01٦ large single-wye grounded EHV capacitor
banks. Other schemes are also 111 use for different 00 arrangements (10٣ example, midpoint 1005.
11-0110225. and wye-wye). Refer 10 Cause 8 for unbalance protection schemes.
Major 001 faults as ااع35 problems w ith capacitor elements can be detected 05 changes 11 the directly
measured impedance of the capacitor bank.
With reference 10 Figure 5. 31 impedance protection function can 0 عused 10 monitor the apparent
impedance between the hus and the ground (-ز٤). T e (1 can عlocated at the high potential 0٣ 2105 ع٤0
the bank neutral. The CT location 0005 not change sensitivity ٤0٣ detecting internal problems ١١ith capacitor
units. Response 10 major bank faults 15 not affected either by the (1 location because of the ١'ery small
restraint ٣221011111 the operating impedance characteristic.
١٠
م
خ(ا ٤1
When monitoring each string individually (52 عFigure 6). the impedance function retains maximum
sensitivity because 2 failure 0 ا2 capacitor unit generates 2 larger percentage change in the measured
impedance as compared ١١ith monitoring the apparent impedance of all parallel strings [Figure 7(2)1. One
can consider a solution 0٤ monitoring just two 0٣ three strings with 2 single impedance function 25 3
compromise between sensitivity and ا number of 15 and amount 0 اrelay equipment required
[Figure 7().
11011 this perspecti١e, locating (15 at the bank neutral can be beneficial. When using multiple current
measurements 10 monitor each string individually and placing them 10 5٣ 10 the grounded neutral 0ﻋﺎا ا
bank, the voltage insulation le١'el of the required (15 can عlo١ver
The apparent impedance is affected ٧ (1, 01130 عtransformer (٧1). 21 لrelay accuracies. Given the high
sensitivity 0٤ the method. ﻋﺎcomplete protection system measurement 1311 15 often calibrated 0٦
energizing the bank ال11100initial commissioning or 211٤٣ major bank repair, ١١hich 15 similar 10 ﻋﺎ
unbalance protection methods. 115 process involves selectingاا1 عactually measured nominal impedance as
ﻋﺎاrelay setting rather 1113111ا5 ١'alue calculated based 011 the nameplate data.
د
Figure 6 —For maximum sensitivity, ٤٤2 impedance method s h o u l d monitor each
capacitor string individually
اد (اأ٠
-'-.I'، ٦ p٣ A
٠,٠ ﺳﺪ4 Hmm ■
ا....,* MM ا-ﻣﺤﻄﺢ
ílmx-n
ا-ﻟﻮ
I H و
Figure 7—Monitoring ااstrings with one impedance element (2) reduces sensitivity:
هcompromise between sensitivity and amount ٥٤ protection equipment is required (%)
11٦ عcapacitance 0٤ the capacitors 15 a 1011011 0٤ temperature. Thus, the impedance 0٤ the capacitor 15 a
fimction 0٤ temperature. Particularly with larger capacitor banks that require very 52115111٧ عalarm and trip
settings, the relay impedance settings for unbalance might be of the same order of magnitude as the change
111 impedance caused by temperature variations. For 11125 عapplications, the relay needs 10 compensate for
the changes 11٦ impedance as 2 function of capacitor temperature. 11 estimating the capacitor temperature,
the effect of sun-loading 011 the capacitors may need to عconsidered. Also, there 15 4 small change in
capacitance due 10 the temperature rise 111 the capacitor following energization.
111 some cases, it may ع necessary’10 trip a shunt capacitor bank if the supply bus voltage 15 lost. Two
conditions 131 may 112 ل10 ﻋﻂconsidered arc 05 follows:
Undervoltage relay, device 271311 Figure 8. will detect loss of 5٧512111 voltage 21 لtrip the capacitor 20*ط
after a sufficient time delay. This delay prevents 111001112 0٤ ا1 عbank for system faults external 10 the 211.
The undervoltage relay should be 5ع1 50 that the relay will 00 اoperate for voltages that require 1 عcapacitor
bank 10 remain 111 service. Because this tripping, 11 عsystem overvoltage tripping, 15 2150 not due 10 a fault
1111 the capacitor bank, the bank 15 00 اlocked out.
ﻟﺑﺑب
ًأﻛﺗﺎ ٦٦٦٦١
To IlL
DmaeM ا
٩1٨
«<دع٦
r
٩٦ ■71.r ■
٢٠p،i٠،١c
٩k(K
Legend♦:
52 ٠ Breaker
505ا ٠ Ovcrcurreni relay
،ﻋﺛﺞ:
>طﺋﻲ 5ااا - Neutral overeurrent relay
59B - Buv overvoltage relay
27 11 - Bus unde٣١ ullage relay
٩7٦ - Voltage differemial relay
59 ﻟﺎل- اداسunbalance ،ا٥
l ٢٩
أ ع
Many protective functions used 01 large capacitor banks 3٣ عsensitive 10 loss 0 اvoltage. ٤0٣ اا15 reason,
primary* fuses may 110 اbe installed 01 voltage transformers used for this purpose. In addition, ا٦ عcircuit
supplying the potential for the protective relays should عbrought directly from the voltage transformer 10
the relay panel with 10 other connected loads. This arrangement prevents cable voltage drops, especially
from varying loads, from affecting the sensitive unbalance 0101221011 relays.
When other 045 0٣ standards require primary fuses 10 0 عinstalled, the fuse 002131101should not cause
incorrect operation of protection function, which can عachieved ٧ 50021510٦ 0٤ ﻋﺎloss-of-potential
logic. ٨ voltage transformer with an 001 primary circuit may have high impedance between 1 عsecondary*
terminals, affecting relay operation.
Secondary* fuses usually do not present 3 problem because they 3٣ عsized 10 protect 1 عع20( ﻋﺎusually 30 ٨)
2 لthe unbalance protection has typically enough time delay not 10 operate before the fuses blow, which
then can عblocked ﻟﺎطloss٠of-potential logic.
If the capacitor sw itching device is 2 circuit breaker 0٣ a circuit sw itcher, then a breaker failure protection
scheme 1٦٦٩٧ 0 عincorporated 10 provide 2 local backup protection if the sw itching device fails. If the device
does fail, then the capacitor bank 15 isolated 1011 the systemط٧ tripping the adjacent breakers connected 10
the bank after a breaker failure lime delay. 1٦ some cases, remote transfer tripping may 0 عnecessary. 1115
important 10 verify the capacitance switching capahihties of these adjacent devices 10٣ proper operation 0٤
the breaker failure scheme.
The local breaker failure detection logic 15 initiated by auxiliary relays. Standard breaker failure schemes
either have an overcurrent supervision logic 10 start 3 timer 0٣ have the output 0٤ the timer supervised by
overcurrent logic. ٦hese overcurrent elements are set 10 operate 10٣ ااtypes of capacitor faults. (Some
currents can 0 عless than the nominal rated current.) ٨ phase overcurrent setting 0ا%500 0 اthe capacitor
bank normal rated current 15 generally considered adequate 10٣ both grounded and ungrounded banks.
Eightning and switching transient overvoltages may ﻋط0111101 1 لby using standard overvoltage protection
equipment, such 25 surge arresters. ٨ capacitor bank generally 2050105 overvoltages because it acts
temporarily 25 3 short circuit for step voltage changes. Overvoltages around capacitor banks 3٣ عgreatly
reduced, اﻻطcomplete 01012101115 not assured. The overvoltage on 2 bank depends 01 the length of line
between the shunt capacitor bank, the 00111at which the transient voltage 15 generated, and the surge
duration as w ell 35 the rating and location of any surge arresters that may 0 عconnected 01 nearby station
buses (IEEE Surge Protective Device Committee 1881).
8. Unbalance relaying m e t h o d s
8.1 Introduction
Unbalance 010122101 utilizes the unbalance that occurs 11٦ 3 normally balanced capacitor bank 10 detect 2٦
abnormality and initiate appropriate action. Te most important 102 10٦ 1510 remove the bank promptly
1101٦service 10٣ any fault 1113٤ may result 111 farther damage. ٨1 external fault 11 3 capacitor 30* 15 likely
to cause extensive damage (ع35ع2ل1112failure) and may create a safety hazard 1٤ the bank 15 not tripped
quickly. ٨1٦ external fault 11 a capacitor 21* 15 3 fault w thin the zone 0٤ protection 0٤ the unbalance
relaying, but external 10 a capacitor unit, for instance, across 31 insulator supporting a fase rail 0٣ frai11e.
3) Trip اا1 عban* promptly 131 unbalance indicates the possible presence of external arcing or a
cascading fault within ﻋﺎاcapacitor ban*.
)ط Provide early unbalance alarm 51213(ا5) 10 indicate de operation 0 ا1525 or failure of capacitor
elements.
c) Trip the bank for unbalances that are large enough 10 indicate that continuing 0001411011may
result 1٦ the following:
3) Undesirable Itlter operation (for capacitor banks that are a part of a harmonic filter)
Functions a) and c) are frequently combined by setting 11٦ عtrip level based 01٦ function c) and with a very
short timing based 011function 3).
Failure 10 provide adequate unbalance protection may lead 10 0٦ عor more of' the following situations:
— Excessive damage 10 ﻋﺎcapacitor bank 5 ﻟﺎas ع35 عrupture and undesirable discharge of
dielectric liquid and/or fire
— Outage o f the capacitor 20* and 1055 or limited volt/var control capability
Unbalance protection 5٧51٤1٦5 1٦٦3٧ not operate fast enough 10 avoid catastrophic failure ﻋﻠﺎل10 high system
short-circuit currents within capacitor units. Single series group grounded wye capacitor banks 0٣ capacitor
00105 with grounded 003٤110٣ unit cases may have system short-circuit current 10٣ 2 single fault within 3
capacitor unit. Conventional overcurrent protection should always compliment unbalance 0101221101
systems 10 provide fast fault clearing for high short-circuit cutrents. External fusing 113 ل2150 0 عdesirable
10 avoid major damage 0 these banks.
Most installations w i l l require 31٦ individual engineering analysis 10 determine the most appropriate
01012110٦ scheme. Bank design, ﻟﺎ5 عcoordination, and selection of a sensing device w i l l directly afTect
sensitivity and the delay time requirements o f the 010121101 scheme.
Unbalance protection normally senses changes associated w i th capacitor element 0٣ unit failure and or fuse
operation. Defective connections may deteriorate until 3 fault occurs within 1 عcapacitor bank, causing the
unbalance protection 10 operate. ٨ defective connection w ithin a capacitor unit (usually 3 rare occurrence)
may result 11 3 pressure buildup and capacitor unit rupture before the operation o f the unbalance protection.
The unbalance 0101221101should operate quickly for the external arcing after case rupture.
Unbalance protection methods detect 01001٤1115 w ith capacitor units using the presumed symmetry 11 the
impedances of the protected bank. 111other words, 10 provide increased sensitivity, they 3٣ عbased on the
known relationships among the many possible current or 01132 measurements taken around the bank.
Instead o f monitoring the impedance directly, these methods respond 10 unbalances 11 the measured signals
caused by the changes 11 the impedances.
This subclause derives and explains the basic unbalance 0101221101methods 10 demonstrate their
applicability 10 various bank configurations, limitations, and susceptibility’ 10 transients. Standing
unbalance 51011315 0ا1 ع10 capacitor tolerances, temperature drifts, and instrumentation errors 3٣ عdiscussed,
311 لthe 1112110 ل5 0٤ eliminating or reducing the 5101001100 unbalance 3٣ عoutlined.
Consider 2 capacitor 01* 11 figure 9. 1115 assumed that a 1310 voltage measurement 15 provided 10 facilitate
3 ٧01130 divider principle 35 1 عbasis for this unbalance protection method.
٤19 ل٣2 — وDerivation ٥٢٤ا2 phase voltage differential unbalance protection method
11٦ عfollowing relations 11 Equation (2) 10 ﻻtrue for each phase of the bank:
٢TA?٠rV ٠ X2
ل'دب|'د (2)
where
ًا and 2 3٣ عthe capacitive reactance values above 3 لbelow ا ﻋﺎ3 مpoint 111اا1 عsame
phase
*TAP and I bis 3٣ع11 عvoltages corresponding 10 the same 005
TAP* ء BUS, 30ل //.V 3٣ عthe fundamental frequency 011050٣5
Xl
r B us x t +x 2 (3)
٤=-ج
11٦ عbalance Equation (2) 3ل Equation (3) can be rewritten 35 11 Equation (4):
1 ٦٦ع 20٢ع signal stays 22٣0 as long 25 1٦ عbank does 0ا change and 05ﻻ the original value 0٤ k.
where I I stands 10٣ the magnitude o f the signal, typically including some amount o f filtering as per design
013 given relay that implements the method.
Equation (5) constitutes 3 voltage differential function because it responds 10 a vectorial difference o f ٤٧0
voltages. The same result is obtained for 3 grounded bank even اأa difference 111magnitude 0 ا٤٧0
components /٢٨1» and ، x K h l s 15 calculated because the voltage across the capacitor 15 due 10 the same
current fiow ing through the bank. K n o w n methods 311 عapplied 10 balance the sensitivity 311 the security
0اا ا15 protection function. 111addition 10 3 pickup threshold. 3 definite or inverse٠time delay can عused. 0٣
a form 0 اrestraint 35 3 countermeasure 10 errors 111 the 10 involved voltages.
The ،'-value 15 a relay selling selected 10 zero-out the operating signal under normal 300٤110٣ bank
conditions. 11115 311 be done based 01 the nameplate data 0٣ measurements 0 اthe bank impedances while
follow ing Equation (3).
Alternatively, the ،'-value can be set using actual measurements performed by 1 عrelay itself, typically
during commissioning 0 اthe 031 اprotection system. 1٦ عlatter alternative 15 110٧1 as self-setting 0٣
،'-setting and stems from Equation (5). The ،'-value set automatically based 0٦ the acttjal measurements 15
as 11 Equation (6):
Often, protective relays supporting the concept 0 اself-setting perform a series o f measurements based 01
Equation (6). average the results, check 10٣ consistency, and require the commissioning engineer 10 approve
the derived ،'-value. In the case o f the 035 عvoltage differential function, per-phase ،'-values are used.
٦٧1٦٤1٦the protected bank experiences 3 failure 0٣ drifts out 0٤ tolerance, due 10 temperature. 10[ example,
the actual value 0 اthe ،' factor (٨٨٤٣) 15 different compared with the set value (511). Erom Equation (4). we
obtain Equation (7):
Inserting Equation (7) 11110 Equation (5) gives the value of the operating signal resulting 110111bank failures,
imprecise setting, 0٣ impedance drifts, as 11٦ Equation (8):
1٦ Other words, 1 عvoltage differential function responds 10 the unbalance 1113115 proportional 10 the
difference between the actual and set values 0 اthe k factor, and ﻋﺎاvoltage applied 10 the 0311.
Equation (8) allows analyzing both the sensitivity 0 اthe function and its security under measurement errors
0٣ impedance drifts.
Equation (8) yields 01 2113 protection function. By analyzing the vectorial position 0ﻋﺎا operating signal
with respect 10 the bus voltage (in-phase 0٣ out-of-phase), the relay ع31 detect whether ﻋﺎا،’-value
increased or decreased 35 a result 0٤ the bank failure 00 لdetermine w hether ﻋﺎfailure occurred above or
below the tap 00111. 11٦ addition, the voltage differential function is 3 perphase function and can 0111001
the affected phase. 11115 rttdimentary, yet effective, fault location can speed up troubleshooting and repairs
of the bank.
11٦ عphase voltage differential method can be applied 10 ungrounded banks 0٣ banks grounded ٧13
impedance, 05110 the following operating signal 11 Equation (9) derived from Equation (2):
11 other words, ungrounded banks requite the voltage differential method 10 measure 1 عneutral point
voltage and apply i t 11٦ the operating signal with the factor of ( I - ) 10 correct 10٣ it.
Note that the operating principle o f the phase voltage differential 15 013 differential kind, meaning two
voltages are compared w ith 3 scaling factor being a real number (imag(،’) - 0). 11115 means that the voltage
differential unbalance method 15 not susceptible 10 transients and high-frequency components—these
components appear 11 both 0٤ the compared voltages and cancel mutually as 10112 35 the two voltages 3٣ع
measured by instrument transformers having similar frequency characteristics 3 ل3٣ عfiltered by the [213
using similar filters.
٨150 note that 1115 method does 10 ا1113 عany assumptions 35 10 the internal connections o f the impedances
constituting the bank phases. Therefore, ااapplies 10 both the w e- and H -connected bank configurations.
1115 subclause presented the typical scenario ١11 اthe 13 مand bus voltages compared through the voltage
divider 0111101. Other variants are possible, such 35 comparing 10 1310 voltages o f 1٧0 315 connected
10 the same bus voltage.
٧٠
V»
٧٤
٨ -] /٦١
TTT
٦
The 10110 1102 relation 11 Equation (11) holds true 35 10112 35 1 عbank 15 ungrounded:
/,+/*+/ =0 (11)
/اه'ام7،=ﻫﻞ (12)
ح+ف+ح-1٧*(ل+*+*)=0 (13)
١Vhen the 0010 15 perfectly balanced, the three phase impedances are equal, and Equation (13) simplifies 10
Equation (14):
31 م-3*0-1٧ (14)
Thus, ا٦ عzero-sequence voltage 3ا ا٦ﻻط ع5 equals ا٦ عneutral-point voltage of the symmetrical bank. 11١15
simply reflects 10 alternative ١vays 0 اderiving اا1 عzero-sequence voltage: ط٧ summing the three ﻻط5
voltages and by measuring the neutral point voltage of a symmetrical wye-connected load.
Equation ( 14) can now ﻋﻂthe base 10٣ the neutral voltage 1100313 0101211010 method as in Equation (15):
Strictly speaking. Equation (15) represents a voltage differential principle between two voltages inputs (31V
from the neutra) voltage transformer and 310 from the broken-delta busbar voltage transformer) 0٣ four
voltages (//. ﻫﻤﺞ٩ ا. and ا. 1 اthe bus zero-sequence 15 derived internally 11 the relay by adding the three
phase voltages). The neutral voltage unbalance method, being truly 3 differential principle. 15 also not
susceptible 10 transients and high-frequency components. These components 2003٣ in all the compared
voltages 311 لcancel mutually 35 long as the instrument transformers used have similar frequency
characteristics and the relay uses similar fillers 10 treat all the involved voltage signals.
Known 101211005 can be applied 10 02131122٤ sensitivity 211 لsecurity of the protection ftnction
[Equation (15 ) ا. 1٦ addition 10 3 pickup threshold, a definite 0٣ inverse-time delay can 0 عused, 0٣ 3 ٤011٦ 0٤
restraint as a countermeasure 10 errors 11ا1 عinvolved voltages.
Often, the 310 signal 15 understood as correction 10 a simple neutral overvoltage protection responding 10
1 During 5٧5٤٤1٦ faults with ground, both 310 and 31 increase 111 the same proportion, resulting 1٦ 3 low
operating signal 10, 211 لtherefore allowing 0٣ better sensitivity w ithout the need for time coordination.
Equation (15) yields an extra protection ftmction. By analyzing the ٧2210٣ 0051101 0٤ the operating signal
w ith respect 10 the ﻻط5 voltage, and knowing whether the units fail short (bank w ithout fuses) 0٣ open (bank
with 10525). the relay can determine 111 which phase the unit failure occurred. This rudimentary, yet
effective, fault location speeds up troubleshooting 211 لrepairs of the bank.
Note that the operating principle [Equation (15)1 assumes a perfectly balanced bank. ٨1 inherent bank
unbalance will cause a standing operating signal limiting sensitivity 0٤ the اھﺎﻻعvoltage unbalance
function. ٨ more accurate equation can 0 عderived 110111[Equation ( 13)] as follows 111؛Equation (16):
Multiplying by X A and grouping the terms 10 lead 10 3 10 and 3 ٧ yields Equation (17):
Equation (17) allows 10+ following the expected equation with the extra terms signifying the standing
unbalance signal, 35 11 Equation (18):
Now', the 00131110 signal 0 the neutral voltage unbalance method compensated for inherent bank
unbalance can be written as 111 Equation (19):
=ﻟطء + 1) (20)
Introducing 10 k factors 10 describe the inherent bank unbalance, ١ عobtain Equation (21) and
Equation (22):
*«ب
. = |ﯾﻶ٦ «««ل ٤=ﻋك-ا (2 )ا
For balanced 0211*5.11٦ ع،’,values [Equation (21)] 3٣ عzeros, and 1 عstanding unbalance signal 15 zero 35
ااع. ا1 such circumstances, the more general Equation ( ا9) simplifies 10 Equation ( ا5 ).
Equation (21) and Equation (2) 3110٧ analyzing both 11 عsensitivity of the function and 15 اsecurity under
measurement 0110٣5 0٣ temperature drifts.
Note that the concept 0٤ self-setting 0٤ the ،’-values still applies. 11٦ ،’-values are selected 10 null out the
standing unbalance. The phasor equation 10٣ the standing unbalance 15 as follows 11 Equation (23):
15 لset 0٤1٧0 equations (real and imaginary parts) that can be solved for the ٤٧0 unknowns يand ،٦٠٠
Compensation 10٣ the inherent bank unbalance can عperformed using Equation (23) 0٣ using the
memorized (M) value of the standing unbalance as follows in Equation (24):
٦٦ 01٦٣ words, when capturing the unbalance signal 25 a standing value of the operating quantity 10. the
positive-sequence voltage is captured as well. ١Vhen using it for compensation, the relay applies 1٦ع
positive-sequence voltage 2 اthe time 10 account 10٣ changes 11٦ the bus voltages between the moment 0ا
compensation and the historical moment 0 اcapturing the inherent unbalance value.
Note that the neutral voltage unbalance method does 0 ا1٦3 ع2٦ لassumptions as 10 1 ﻋﺎinternal
connections 0 اthe impedances constituting 1٦ bank. Therefore, 11 applies 10 both the wye- 2 لH-
connected configurations as long as the bank 15 ungrounded.
HHH
(اال
II' the grounding impedance 15 relatively low, then this configuration 2311 ﻋطprotected with the phase
voltage dificrcntial method. 11 1115 approach, cither the neutral-point voltage 15 measured طthe relay, and
used as shown 111 Equation (25). 0٣ the voltage 15 neglected resulting 11 the reduced sensitivity 10 maintain
security of the finction.
l i the grounding impedance 15 relatively high, then this configuration can be protected using 2 modified
neutral voltage unbalance method. Equation (25) holds true 10٣ 1ا1 عbank 0٤ Figure ا ا:
٠٠»,٠-٠,'1٠'í (25)
By performing similar mathematical manipulations as 10٣ the neutral voltage unbalance method. ١٧ عobtain
the following balance equation i n Equation (26):
which 3110١٧5 for creating the following protection Auction 11 Equation (27):
)he operating signal 111Equation (27) 15 similar 10 the neutral voltage unbalance method 10[ ungrounded
banks. 11٦ عlast 10 terms compensate tor the inherent bank unbalance. The second ٤٤٣1includes the ratio
01 1 ع0ا135 عand neutral impedances 11٦ addition 10 the multiplier 0٤ 3 0 اthe traditional neutral voltage
unbalance method. Neglecting the inherent unbalance, one may apply ٦ ( عb l o w i n g protection principle 11
Equation (28):
»=3ا%-(3+٨)*١ (28)
which can be implemented using 4 neutral voltage unbalance relay capable ot' ratio compensation, 50 that
عX A /X\ value 15 taken 1110 account.
8.2.4 Unbalance protection method ٤٥٣ bank grounded through هCT with resistive burden
٨ 551111111 ع10٣ simplicity the CT [3110 to he ا: I, the following balance equation 11 Equation (29) holds 111ع
(11 actual installations, one needs 10 (actor the CT ratio):
Assuming the 011* 10 0 عperfectly balanced, we can simplify Equation (29) as follows 11٦ Equation (30):
را+1»+ا+**ز1*-0 (30)
٨5 Equation (31) balances the neutral voltage at 11٦ عbus with a voltage associated with 1 عban* neutral,
this 1111ا10 ل15 sometimes referred 10 as the neutral voltage unbalance method. Indeed, the method ن41 be
implemented using a neutral voltage unbalance relay capable 0 ( ratio compensation, 50 that the // ﻋﻼال15
taken 1110 account, l o v e v e r , the relay requires also shifting one of' the 10 compared voltages ط90٠ [the
،٧١٦ value 11 Equation (31)1.
The operating signal 0 اthis unbalance 0101221101 method 15 based 0٦ Equation (32):
FO p = | 3 x r 0 + y x | x r s | (32)
Knowm methods ٤3٦ عapplied 10 balance the sensitivity and security of the protection function. 1٦ addition
10 2 pickup threshold, a definite 0٣ inverse-time delay can be used, 0٣ 4 10111 0٤ restraint 25 a
countermeasure 10 ٤٣٣0٣5 11٦ the involved voltages.
111510 be noted that unlike the previously derived methods, 115 method 15 not truly 3 differential method.
One 0٤ the ٤٧0 voltages compared needs 10 be shifted 0٧ 90. which 102315 the balance holds true for
ftmdamental frequency phasors only. Transients 11٦ the measured signals will not necessarily mutually
cancel, calling for very strict filtering of the 10 voltages before using them 11 the operating equation 11
Equation (32).
The protection method defined by Equation (31) 15 related more 10 monitoring the apparent zero-sequence
impedance 0 the bank than 10 the true neutral voltage differential principle (the actual neutral point voltage
15 zero in this case, and as 511٤٦.11 cannot be balanced against any other signal 10 detect bank failures). 10
understand better, assume a simple pickup 15 used 10 actuate the protection ftmetion, 05 in Equation (33):
| أق>اآﻻرﺑﺂ (36)
% 15 the apparent zero-sequence impedance 0 اthe bank: -jX 15 the expected value 0 اthe zero-sequence
impedance of, the bank: the left-hand side 0 اEquation (37) defines a circle around the expected value of the
bank impedance: ﻻلthe right-hand side 0 اEquation (37) defines the radius 0 اthe circular pickup
characteristic (Eigure 13). 1115 radius 15 current dependent-smaller 14 large zero-sequence current 15
present, and larger if a small zero-sequence current is present, That dependence 011 the level of the zero-
sequence current has 4 positive impact 011 اا1 security and sensitivity of this unbalance protection function.
■ ااب٠،٠٢■
I.--'""
٨5 50٨1 ﻻطEquation (37). however, the method effectively responds 10 the apparent zero-sequence
impedance of 1 ع010* 051010 3 circular (110110) characteristic with the center 31 ٨v, and 3 current-dependent
radius.
Referring 10 the original Equation (32) 311 لexamining 1 عimpact 0٤ the inherent bank unbalance, the
operating voltage can be obtained by rearranging the terms as was done for the neutral voltage unbalance
method 11 Equation (38):
<'ء٢|ب*ل./ﺑﺣﻶ٢ﺳﺎ (38)
Compensation 10٣ t i e inherent bank unbalance can be performed using Equation (39). or using the
memorized value 0٤ the standing unbalance 35 follows 11 Equation (40):
r n —
I ن (ةﻵ’ا
vz > X 11 (40)
Note that 115 اmethod does 00 اmake any assumptions as 10 the internal connections 0 اthe itnpedances
constituting the bank phases, Therefore. it applies 10 both the wye- and H-connecled configurations as long
ه5 اا٦ عneutral 0011115 solidly grounded.
Consider 2 capacitor bank 35 5٦٦0٧1٦11٦ Figure 14 11 اeach phase comprising 10 parallel impedances. The
double bank 01 عgrounded 0٣ ungrounded. 1115 applies 10 a single bank with 10 strings per phase or 10
4 double 41* with a single string per phase 111 each bank.
اداداﻧط
اﻻوار
Z.HH1
٨ common voltage 15 applied across the ٤0 impedances, 311 لtherefore, the following holds true 10٣ each
phase 0 ا11 ع00* 11 Equation (41):
The phase current unbalance method responds 10 the vectorial difference bet١veen the two currents, as
1010١٧5 in Equation (42):
(42)
Note that the total phase current drawn ط٧ the bank 111 the considered phase 15 as 10110٧5111 Equation (43):
Using Equation (43) 10 calculate the hank voltage and substituting ع 010 voltage 11 Equation (42) yields
Equation (44):
When the 10 banks 4٣ عperfectly matched (٠٢, - ٢ ). the differential current 15 zero. ١ hen there 15 an
inherent unbalance between 1 عbanks or when the failure occurs, the differential current reflects the
amount o f unbalance.
ذب (45)
The 002131110 signal o f the phase unbalance method compensated for the inherent unbalance 15 25 11
Equation (46):
/op=|/dif-*|X/i| (46)
I f the method 15 110٤ compensated 10٣ the inherent unbalance (the ،-value assumed 10 be zero), then the relay
51111 اام٧ responds 10 the following measured differential current i n Equation (47):
Note that the operating principle 35 defined 11 Equation (46) 15 0٤ 0 dift٠erential kind, meaning 10 currents
are compared with a scaling factor being a real number (imag(،٦) - 0). 1115 means that the phase current
unbalance 11012110 ل15 1101susceptible 10 transients and high-frequency components these components
appear 11 both of the compared currents and cancel mutually. 11 contrast, 1 عuncompensated principle 0٤
Equation (46) responding 10 the differential current 15 susceptible 10 elevated current reading during
transients.
The concept 0 اself-setting can be applied 10 this protection method using Equation (48):
Implementation 0 اEquation (48) requires measuring the total bank current. More often, the ﻻط5 0142 ع15
available 10 11 عrelay. ٤0٣ grounded banks, 4 fixed relationship exists between the phase voltage and اا1
phase current. Therefore, the following implementation is feasible 10٣ the phase current unbalance method,
compensated 10٣ the inherent unbalance, as 1٦ Equation (49):
Equation (49) can ﻋطfollowed directly, 0٣ the alternative method can ع used 35 explained earlier. 11
Equation (50) and Equation (51):
ا0م:70*“اا١|ةأ (50)
/ ٧ NB : ﻷا١(ﻵ٧) X، (51)
The angle between the operating current and 1 phase voltage 0٣ current can be used to locate the '؛ailed
unit, assuming the relay 1105 whether the elements t٠ail 511011 0٣ open ("left” bank ٧5. “right" bank). In
addition, the phase current unbalance method 15 phase segregated 211 لnaturally 001115٤0 1ا١ عaffected phase.
Consider a capacitor bank 01 Figure ا5 with each phase comprising 1٧0 parallel impedances. The bank 21٦
be grounded 0٣ ungrounded. The ditTerential current measurement 15101 performed 01 a per-phase basis as
11 the phase current unbalance method but between the neutrals 0٤ the two banks.
ك٦١ ٨٢٦
I Inn».
IlkirN
(iroutklcd blink
1011 the derivation 10٣ 11٦ عphase current unbalance method, we obtain Equation (52):
111 عneutral differential measurement 15 the sum of the phase differential signals: therefore, 35 11
Equation (53):
Zdifv - Zdifa + 70FB + /difc =و X وا+د٠ هx / ٥+ ج X / ع (53 )
Equation (53) allows for waiting the following neutral current unbalance method compensated 10٣ the
inherent bank unbalance 11٦ Equation (54):
The uncompensated version uses just 1 عmeasured neutral ditTerential current, 35 11 Equation (55):
Note that the operating principle as defined by Equation (54) 15 0٤ a differential kind, meaning that the
involved currents are compared with scaling (actors being real numbers, 11115 means that the compensated
neutral current unbalance method 15 not susceptible 10 transients and high-frequency components—these
201110010215 appear 11 all the compared currents and cancel mutually. 111contrast, the uncompensated
principle as defined by Equation (55) responding 10 the neutral differential current 15 susceptible 10 elevated
current reading during transients,
)he ('-values in Equation (54) cannot be, however, self-set by the relay. The three unknowns ( ٤٠ ( زand ٨٤)
cannot be calculated 1011 the two equations available ( ااﻟﺎout the real and imaginary parts 0٤ the standing
operating signal). Some implementations work 011symmetrical components rather than 01 phase currents
and ااﻟﺎout the standing unbalance signal caused by the positive- and negative-sequence components only,
as in Equation (56):
Implementation 0٤ Equation (56) allows for self-setting the compensation for the positive- and negative-
sequence components of the inherent unbalance, leaving the zero-sequence uncompensated. The latter 1114٧
be acceptable, particularly for ungrounded banks w here zero-sequence currents are not present.
The method can be compensated ا0٣ the inherent unbalance using 0114225 instead of currents 1٦ the way
explained for the phase current unbalance method.
The angle between the operating current and 1 ع035 ع01102 عor current can be used 10 locate the fault
assuming the relay knows whether the capacitor units fail 511011 0٣ open ("left ٠ bank ٧5. "right bank and
the affected phase).
1٦ عunbalance relays should be set 01٦1٦ ع3515 of maximum continuous system operating voltage.
8.3.1 Inherent bank unbalance, system unbalance, and other sources ٥٢2٣٣٥٣
11 practice, the unbalance seen by the unbalance relay, due 10 1055 0٤ individual capacitor units 0٣ elements,
15 somewhat different from the calculated value because 0 ا٤1٣0٣5described 1٦ the following list.
a) The primary unbalance, which exists 01 3 ااcapacitor bank installations (with 0٣ without fuses),
15 due 10 basically ٤٧0 factors: 1) system voltage unbalance 311 2) bank inherent unbalance due
10 capacitor manufacturing tolerance. Secondary unbalance errors 1٦13٧ be introduced by sensing
device tolerance and variation and 0 اrelative changes 11 capacitance due 10 difference 1٦
capacitor unit temperatures in the bank.
The 10 ااunbalance error w ill be a vectorial combination of the primary 21 لsecondary effects.
The error may ع11 4 direction 10 prevent unbalance relay operation 0٣ 10 cause 4 false
operation. The amount 0 اinherent unbalance 10٣ various configurations ,nay be estimated using
the equations 1٦ 8.4 through 8.7 211 لAnnex (. ٨ worst-case estimate ٤٩٦ be made ط٧ assuming
the unbalance errors to ﻋﻂadditive.
If the unbalance error approaches 500% 0 اthe alarm setting, then compensation may ﻋﻂ
beneficial 10 correctly alarm for the failure of one unit 0٣ element as specified. Subclause 8.2
explains 1 عprinciples of compensation. (011102115411011 can reduce errors ﻋﻠﺎل10 both system
unbalance and bank inherent unbalance. 11 some cases, a different bank connection can improve
the sensitivity ١١ithout adding compensation.
0٣ example, a١٣٧ ع011* can be split 1110 a ١vye-١١,ye bank, thereby doubling the sensiti١tty 0ا
the 001221101and greatly reducing the effect 0 اsystem ١oltage unbalance.
For certain capacitor ban* configurations, some faults ١vithin the ban* will not cause 31 unbalance signal
using certain unbalance methods, such 35 the 10 10112:
— Rac*-10-rac* faults for banks ١١٠ilh٤٧0 series groups connected phase-over-phase 21 لusing
neutral ١ oltage 0٣ current for unbalance protection methods
— R3c*-to-rac* faults for certain ! ا-bridge connections
Refer 1 م7 ا.5 for a discussion of these conditions.
٤0٣ phase-o١er-phase wye-wye and 11-0٣102 عbanks, correct bonding 0٤ the racks 15 required 50 that the
unbalance protection w i l l be responsive to rack-to-rack flashover. See Figure 16 ؛,or an illustration 0٤ the
bonding tor 3 wye-wye bank.
A-Phase A-Phase-
Rack
B-Phase B-Phase
PgsV
ادوا
C-Phase. C-Phase-
(٨)
(٨) Incorrect rack bonding (all 011 same side): 10 neutral current through the current transformer tor 4 rack٠to٠rack
insulator flashover.
(13) Correct rack 001 ل1110 (011 alternate sides): neutral current w i l l 110١٧ though a current transformer (or a r a c k o - r a c k
insulator flashover.
N()TE—B ding is similar lor a grounded wye٠wye bank for a phase٠ovcr٠phasc design.*
Ambiguous indications may come 101٦ 10 or more different conditions 0 اthe 01 but provide ﻋﺎsame
indication. Initial failure 11 indicate a failure. اﻟﺎطsubsequent failures may cancel اا٦ عfirst failure 10
indicate a normal state. For instance, under 001 اﻟﻢconditions with 3 balanced 311*. negligible current may
" Notes 1 text, tables, ﻻادfigures of a standard ﻋدgiven ٤0 information only and 00 not contain requirements needed10 implement
111 ؟standard-
110٢ through the current transformer between 1 عneutrals of 311ungrounded wye-wye capacitor hank.
Howe١’er٠ the same negligible current may flow through this current transformer i f an equal number of units
0٣ elements 3٣ عremoved 1101٦1the same phase 011both sides 0٤ the bank. This condition 15 undesirable, and
the indication 0٤ such 4 condition 15 obviously ambiguous.
Where ambiguous indication 15 a possibility’, 1٤15 desirable 10 have 4 sensitive alarm (preferably 011 fijse
operation for fused 0215 0٣ one faulted element 10٣ firseless 0٣ unftised banks) 10 minimize the probability’
of continuing operation with canceling failures that result 11٦ continuing, undetected overvoltages 01 the
remaining units.
— ا1 wyc-wyc banks (Figure 17). the operation 0 اfuses 0٣ short-circuiting 0 اelements 11 0 ع١٧٧ع
may cancel 1 unbalance signal generated 11 the other wye.
— 111!!-bridge banks (Figure 18). the operation 0 اfuses 0٣ short-circuiting o f elements 111one leg
o f the ااmay cancel 11 unbalance 51211 الgenerated 111another leg o f the !1.
،،AC
When designing 3 capacitor bank protection scheme, i t 15 always desirable 10 select alternative schemes 10
reduce 1٦ عpossibility’ 0٤ maloperations during canceling failures. For example, for 1٦ عscheme shown 1٦
Figure 17. failure of the neutral current unbalance scheme 1113 be backed ﻣﻠﺎby application of the neutral
voltage unbalance scheme as well.
Figure 18—H 1492: Compensating failures result in no unbalance signal 2٧2٦ though ٤2 bank
may 2 unbalanced
-l
ل. 7 ﺗﺤﻊ
;; c
١oltige
[<-١<
DiiTircnIill
— R،٠la.١ (7٣)
ال
TT ٢ أ ه
Unbalance ٣2 ا0 1110delay times are set based 0٦ the following considerations:
3) The unbalance 11110 relay time delay should 0 عminimized 10 reduce damage 110111 01 arcing fault
within the 021 structure 00 لprevent exposure 0 اthe remaining capacitor units 10 overvoltage
conditions beyond their permissible limits. For a single-phase 0٣ an open-phase condition, the
time delay should also be 511011 enough 10 avoid damage 10 the current transformer 0٣ voltage
transformer and 10 the relay system.
b) The unbalance trip relay should have enough time delay 10 avoid false operations due 10 inrush,
system ground faults, switching 0 اnearby equipment, and nonsimultaneous pole 002101101 0ا
the energizing switch 1 اthese affect the applied unbalance protection principle. 0٣ 111051
applications, 0.1 5 should be adequate. 0٣ unbalance relaying systems that do 110 اcompensate
for system unbalance and may therefore operate 01 a system voltage unbalance (ground fault),
time coordination w ith upstream protection 15 required 10 avoid tripping due 10 a system fault.
However, longer delays increase the probability 0 اcatastrophic bank failure.
c) With grounded capacitor batiks, the failure of one pole of the switching device or the single
phasing from a blown bank 105 will allow' zero-sequence currents 10 flow’ 1٦٦ 5٧51٤1٦٦ ground
relays. Capacitor bank relaying, including the operating time 0٤ the switching device, should be
coordinated w ith the operation of the system ground relays 10 avoid false tripping.
)ل11 عunbalance 1٣1 مrelay may need 10 عdelayed 10 account for the settling lime 0ﻋﺎا ا
protection 5512111011 initial energization and for the transient response of certain capacitor
voltage transl'ormers, and 50 01. w hich may ﻋﻂ4 part 0f the unbalance 101021101 system.
) 11٦ عunbalance 1٣10 relay scheme ٤4٦ have a lockout feature 10 prevent inadvertent closing of the
capacitor 01* sw itching device if an unbalance trip has occurred.
f) 10 allow 10٣ the 2112215 0 اinherent unbalance, the unbalance relay trip should عset 10 operate
at a signal level halfway betw een the critical step and the next low er step. The critical step 15 the
number 0٤ fuse operations or shorted elements that ااcause 311 overvoltage 01 healthy
capacitor units 11٦ 2055 0 ا%110 0ا11 عcapacitor ا11 اrated 01102 ع0٣ 1١ عcapacitor unit
manufacturer’s recommended maximum continuous operating voltage, 11 addition, for
internally fused capacitor units, the critical step may be the number 0 اinternal fuse operations at
w hich tripping 510011 occur 45 recomiended by the capacitor manufacturer.
2) 1 اsw itch failure 0٣ single phasing due 10 4 blown main fuse could result 11٦ continuous voltage
exceeding 11٦ عrelay rating, operation of the lockout relay should deenergize the voltage relay. 11
chattering of the seal-in unit 15 4 problem w hen used 011ac, a lockout relay contact can bypass
1 عvoltage relay contact.
1٤15 desirable 10 apply 01 unbalance relay w ith ٤٦٧0 0٣ more sensing 510295. each w ith individual pickup and
time delay settings. 1٦15 allows flexibility 10 set 1 عstages with different operate times 10 provide better
coordination 10٣ unbalances 0٤ different severity.
Ideally the alarm level should be set 10 detect failure 0٤ 3 single capacitor unit, but not to assert a nuisance
alarm due 10 system unbalance. The unbalance signal during normal 021 operation may be signiflcant due
to errors 35 described earlier 11 8.3. 1. It is a good practice 10 monitor the unbalance signal over 3 period 0ا
lime and then set the alarm level accordingly. The alarm signal should have sufficient time delay 10
override external disturbances if they affect the applied unbalance protection principle.
Subclause 8.2 explains the fundamentals 0٤ the neutral voltage unbalance method. The neutral voltage
unbalance protection method 15 mostly used ا0٣ ungrounded banks where the voltage-sensing device 15
connected between 1 ع00 * neutral and the ground. 11115 method compares the zero-sequence voltage at
the bus w ith the zero-sequence voltage at the bank neutral point, Figure 20 and Figure 21 show protection
connections 10٣ 4 single-wye ungrounded 0.
8.3.6.1.1 Neutral voltage unbalance protection 2٤٥0 ٤٥٣ ungrounded ١٧٧2 banks
٨ neutral unbalance protection method with ن01110211541101 ا0٣ inherent unbalance 15 normally required for
very, large banks. The neutral unbalance signal ﻋﻠﺎل10 the loss of one 0٣ 10 individual capacitor units 1114٧
be 1055 than the normal inherent unbalance. Unbalance compensation should be used 1 اthe inherent
unbalance exceeds 011 عhalf of the desired setting forل012ن1110failure 1٦ a capacitor unit.
The voltage-sensing device tnay be a voltage transformer, capacitive potential device, or resistive potential
device. 11 عvoltage-sensing device should be selected 10٣ the lowest voltage ratio attainable, ١vhile still
being able 10 withstand transient and continuous overvoltage conditions 10 obtain the 1113111011111 unbalance
detection sensitivity. Ho١vever, 4 voltage transformer used 11٤15 application should be rated 10٣ ااﻻsystem
voltage because the neutral voltage can under some conditions rise 10 as high 35 2.5 per-unit during
switching. Under these conditions, an underrated voltage transformer 1 ااbe driven into deep saturation
(Hamer 2 لOwen ا1461).
11٦ عuse of an underrated resistance potential device, with secondary voltage limiter, 311 permit relay
operation with an open phase 10 the capacitor bank. The resistive potential device should عcapable 0٤
١vithstanding this overvoltage condition.
De-energized ungrounded wye capacitor banks may have voltage induced 011 the capacitor bank from an
overhead transmission line, adjacent energized capacitor bank, or other energized object. (01 occasion, 11115
has caused the unbalance relay 10 alarm or trip, even though the capacitor bank 15 not energized. 10 201ل
this situation, 1٤15 suggested that an auxiliary contact 0٤ the capacitor s١١٠itch عused ٤0 short circuit the
output 0٤ the neutral 10 ground transformer ( 0 11 some other way disable the unbalance protection) when
the 5٧1٤٤ 15 in the open position.
/٦ a enatjve
bus 3V0
Neutral Voltage
Unbalance ﺑﮭﺎه
(59NLI)
Figure 21(a) shows a variation of the neutral unbalance relay 0101221101scheme for 01 ungrounded١٧٧ع
capacitor 310 using three line-to-ncutral voltage transformers with their secondaries connected 111 broken
delta and then connected 10 an overvoltage relay. Compared 10 the scheme 11 Figure 2 1 ( ) . اا15 scheme has
1 عadvantage 0 ا00 اbeing sensitive 10 5٧512111 voltage unbalance. Also, the unbalance voltage 10 ﻋﺎا
overvoltage relay 15 three times the neutral 51 ا1 voltage as obtained from Figure 21(0). ٤0٣ the same
voltage transformer ratio, there 15 3 gain 0 اthree 11 5٤٦511٧11٧ over the single neutral- 0 ground voltage
transformer scheme. The voltage transformers should be rated for line-to-line voltage.
١cutral ١ol٠ag<*
اn b« liner R ، li١
(59١ج ا
MJ) اا
However. ط0اا1 hemes 50١11 11 Figure 21 ل0 00 اtake into account 010* inherent unbalance, 3ﻋﺎ ل
additional scheme 50١11 11 Figure 21(a) does not compensate 10٣ 5٧51٤1٦ unbalance. Both of, these
disadvantages 3٣ عaccounted !'or 11 the scheme shown 111 Figure 20.
8. 3.6.1. 2 Neutral voltage unbalance protection method ٤٥٣ grounded ٧٧٧2 banks
'!'he protection 15 based 011a voltage measurement derived from a current transformer connected bet١vcen
1 عcapacitor 0010* neutral and the ground. 11٦ عcurrent transformer output can عput through a burden
resistor. ٨ sensitive voltage relay ١vith a fundamental band-pass filter should be used for ﻋﺎunbalance
protection.
Fhc current transformer with a wound primary used 11 this application has unusual overvoltage and current
requirements (Harder 1351) (10.5 311 ل10.6). Single-turn CTs 0 ا600 ٧ ratings have been used 111 the
industry. 11٦ عratio 15 selected 10 give both adequate ovcrcurrcnt capability 41 لappropriate signal for
protection.
/ 2ل00ﻋﻼ
/٦ ٦ measured bus 300
Neutral Voltage
Unbalance Relay
(59)ﻟﺎﻟﺎ
Figure 22—Neutral voltage unbalance protection method ٤٥٣ grounded single-wye bank
1٦ عneutral 01102 unbalance relay shown 11 Figure 22 could be 4 voltage relay connected across the
neutral (1 with the [251510[ 45 15 the case 111 small, grounded wye capacitor banks.
Because of the presence of harmonic currents (particularly the third, a ero-sequence 1131111001 that 110١٧5
1٦ 100 neutral-to-ground connection), the relay should ﻋﻂtuned 10 reduce 1 اsensitivity 10 frequencies other
141 ﻋﺎاpower frequency.
The voltage 221055 the burden resistor 15 11 phase w i t h the neutral-to-ground current, 11115 neutral-to-ground
current 15 the vector 511111of the three phase currents, w h i c h are 90 out 0٤ phase w i t h the system phase-to
ground voltages. 11115 scheme may عcompensated 10[ power 5٧5٤٤1٦ voltage unbalances, by accounting
٤0+ the 9(0 phase shift, and 15 110٤usually appropriate ٤0٣ very' large capacitor banks requiring very sensitive
settings. 11115 90 phase shift may be accounted 10٣ internallyﻻ5أ112 relays supporting ٤1115 application 0٣
compensated externally using appropriate phase-shifting components and techniques. The value 0 اthe
resistor 1 should 0 عchosen such 35 the voltage measured at 1١ عbank neutral 0011٦1input 0 اthe relay
matches 115 3٧0 during system unbalance.
11 some designs, the voltage relay operates a latching 0٣ lockout relay 10 initiate the opening 0 اthe
capacitor sw i t c h and 10 block 15 اclosing. Contacts 0 اthe lockout relay should also short out the neutral
current transformer secondary'.
8 .3 .6.1.3 Neutral voltage unbalance protection method for ungrounded double-wye banks
Ungrounded double-wye 01*5. as shown 11 Figure 23. can be protected 1151112 the neutral voltage
unbalance method. 1115 method 15 not sensitive 10 system voltage unbalance 0٣ 1٣ لharmonic components.
Protective relays designed 10 compensate 10٣ inherent unbalance 0٤ the bank ٧1 ااachieve greater
sensitivity.
The neutral voltage value can be determined 111the same manner used for 4 single-wye bank as one section
o f the double-wye 0. Protection scheme connection i s as shown i n Figure 23(4). Although a low-ratio
voltage transformer w o u l d be desirable, a voltage transformer rated for 5٧512111voltage 15 required 10٣ the
ungrounded neutral. The resulting unbalance signal voltage may عvery small.
ا801 اschemes 1٦ Figure 23 00 not compensate 10٣ 001 inherent unbalance and may 110 اprovide sufficient
sensitivity 10 protect individual capacitor units.
ت
١c٠tm٢٤١١11-٤
ا ااا1
Kein. ‘
h> |b>
I n scheme ( b ) 11 Figure 23. the neutrals 0ا ﻋﺎtwo capacitor sections are connected 10 4 voltage
transformer. T h e voltage transformer. 0٣ potential device, i s used 10 measure the voltage (shift) between ﻋﺎا
capacitor 001 neutral and ﻋﺎاground. 111 relay should preferably have 4 harmonic filler and respond o n l y
to the fundamental.
40
Copyright © 2013 IEEE. ااه 19ا8 reserved
IEEE Std C37 99-2012
ﻋﻌﻌﺎGuide for ااProtection اهShunt Capacitor Banks
The neutral current unbalance method responds 10 the cunent circulating between the connected neutrals ol,
10 parallel banks. 1115 used 10٣ both grounded and ungrounded banks. ا٤ 1٦ عbanks are 001 perfectly
balanced, then the circulating cunent 15 not zero, which degrades the sensitivity 0 اprotection. Therefore,
relays providing compensation for bank inherent unbalance facilitate more sensitive and reliable protection.
11 Figure 24. basic schemes 10٣ both grounded 21 لungrounded banks are shown. ٨ ااschemes respond 10 a
differential cunent. This 15 the vector difference of the neutral cunents flowing 11٦ the paralleled banks. The
scheme 1٦ Figure 24(3) 15 for an ungrounded ١٧٧ bank, while the schemes 11 Figure 24(b) and Figure 24(c)
3٣ عfor grounded banks. 10 compensate 10٣ unwanted circulating zero sequence current caused by capacitor
unit differences, the total bank zero sequence current can be measured. The dashed lines 111 Figure 24 show
this 11 اﻟﺎم. This additional compensation allows for more sensitive relay settings.
ﺣﮭﮫ
١t'u(rii<٠rrcH
ھﮫ
1)
ار
ارا1 unt
<ا٠اا٠١ M>١ I
11٦ عneutral current 15 one halt, that 0 ا2 51 ﻋﺎعgrounded bank 0 اthe same size. However, the current
transformer 12110 and relay rating may عselected 10٣ the desired sensitivity because they are not subjected
10 sw itching surge currents 0٣ single-phase load currents 251 ١ ل2٣ w ith the grounded neutral scheme.
٦٦ (٤) 1٦ Figure 24 (10٣ grounded-wye 211*5). the neutrals 0٤ the two sections are grounded through
11٦ 5٤٦٤1
separate current transformers 10 a common 010ا11ل. The current transformer secondaries are cross
connected 10 4 neutral current unbalance relay 50 that the relay 15 insensitive 10 any outside condition that
affects both sections of the capacitor bank 1٦ the same manner. The current transformers ٤21 be subjected
10 switching transient currents and, therefore, require surge protection. They should be sized ا0٣ single-
phase load currents if possible. Alternatively, the connections from neutral 10 ground from the 1٧0 wyes
may ع11 opposite directions through a single-window? current transformer as shown 111 scheme ( )ط11
Figure 24.
Voltage differential protection methods for grounded-wye capacitor 0215 3٣ عillustrated 11٦ Figure 25(a) 10٣
3 single wye-connected bank 311 ل11 Figure 25(b) 10٣ a double wye-connected bank. 1115 approach 15.1٦
essence, three separate single-phase voltage differential relays monitoring 22٤1٦ phase 0 اthe 000110٣ bank.
٨ signal responsive 10 the 1055 0 اindividual capacitor elements 0٣ units 15 derived ط٧ comparing the
capacitor 3 tap voltage with the bus voltage. The capacitor bank 10 مvoltage is obtained لconnecting a
voltage-sensing device 41055 the ground end parallel group (0٣ groups) of capacitors as 1٦ the case of fused
capacitor banks. This may عa midpoint tap, where the voltage 15 measured between the midpoint of the
phase 21 لground. Alternatively, the tap voltage may be measured across low-voltage capacitors (that 15. a
capacitiveا١1ل
5 111 ) at the neutral end 0 اthe phase 45 11 1ا١ عcase 0 اa fiiseless capacitor bank. The bus voltage
15 usually available. Tapping 21055 the bottom series groups 0٣ a midpoint tap 15 not possible for fuseless
banks ١٧11 multiple strings because the 51٣1105 are not connected 10 each other at the tap point. Tapping
421055 the low-voltage capacitors 15 suitable 10٣ fuseless capacitor banks.
A Her checking that ااهcapacitors are 200 لand 110 fiises have operated 111 the externally fused bank, the
voltage levels 4٣ عinitially adjusted 10 be equal. The initial difference signal between the capacitor bank tap
voltage 0 لthe bus voltage signals 15 zero, and the capacitor tolerance and initial system voltage unbalance
15 compensated. 1٤ the system voltage unbalance should vary, then the relay system 15 still compensated
because 4 given percentage change 111ﻻط5 voltage results in the same percentage change 011 the 204110٣
bank tap. Any subsequent voltage difference between capacitor lap voltage and bus voltage 1 ااbe due 10
unbalances caused ﻻط1055 0 اcapacitor units within that particular phase. Secondary' errors may ع
introduced ﻻطsensing device variation and temperature differences between capacitor units within the
00*. 1055 of capacitor units 11 each phase 15 delected independently (Alexander 1132] and 101٦ [BI3]).
Voliiur
،اﻻ
١اا
ل3ع
lllffcrratlil
Rrla١ ٠MT١٦
(b)
(4) - Grounded single wye-connected capacitor bank
(b) - Grounded double wye-connected capacitor bank
The sensitivity 0 اthis method 15 high, and 1٤15 particularly well suited 10٣ high-voltage banks or banks that
consist of a large number 0٤ capacitor units.
It, the Htsed bank 15 tapped at the midpoint. 11121 the sensitivity 15 the same ٤0٣ failures within and outside
the tapped 0011101. If the bank 15 tapped belo١v (above) the midpoint, then the sensitivity 10٣ failures within
the tapped portion will عgreater (1255) than 10٣ failures outside the 10 مportion. 11015 difference may cause
difficulty 11٦1 achieving an appropriate relay setting. The sensitivity for a midpoint tap and 3 10 مacross low-
voltage capacitors 4 اthe neutral 21 لof the phase 15 the same.
For grounded double wyconnected capacitor banks having both tap and bus voltages available, it 15
possible 10 connect the voltage differential protection between 00111 tap voltages 0٤ the parallel bank strings
and between bus voltage and each tap voltage. 11115 approach will still finction 1 اthere 15 a unit failure both
above 211 ل10٧ the VT connection point.
The voltage differential relay has 10ا0 عblocked from operation 114 VT fuse fails. The voltage differential
must 4150 be disabled w hen the bank 15 taken out of service. The single ﻻط5 voltage input may cause an
unw anted operation.
In fitseless single-wye 005 11 اa large number of series elements, the capacitance changes due to
unequal solar heating 01 the capacitor ل1ا5 could be sufficient 10 cause nuisance alarms 0٣ 11105 with
conventional relays. The use of modern relays w ith dynamic unbalance compensation w ill mitigate this
problem. Differentially connected voltage 0٣ current unbalance configurations 0٤ double-wye banks have
inherent compensation 10 reduce the unequal solar heating effect.
Figure 26 5٦0٧5 a special (split-wye) configuration 01 fuseless banks similar 10 the double-wye
configuration 10 mitigate the effect 0٤ unequal solar heating 01 51٣11105. The 10 مvoltage transformer 15
connected across the phase 51 ع0 اlow-voltage capacitors connected 011 the neutral 51 ﻋﻞof tw o groups 0ا
capacitor strings. 1٦ عdifferential voltage will be zero 1٤ 1٦ عnumber 0 اstrings 01٦either side 0٤ 1٦ع
transformer 15 اﻟﻠﺎوع0٣ there will 0 عa standing voltage across the transformer with an ﻻ1 اﻟﻠﺎوعnumber of
51٣11105 011 either side. Unbalance calculations ٣ عthe same as those for single ٧ ع011*.
Voltage
Relay٠#7٧)
ودددا
ﻋﺳﺎاﻣﻣﺎ١ 1٥ ﻋﺤﺪام٤
ﻟﻠﯾﺎ
Figure 26—Spirt ٧٧2 configuration, voltage differential measurement
(only م252 B shown)
Figure 27 505 1٧0 basic schemes using phase current unbalance protection. Tie scheme 111Figure 27(2)
15 using a 1٦40٧-1٧0 ع (1 with parallel banks connected at the neutral point, ٧11 عthe scheme 1٦
Figure 27() 15 for an H-bridge 31.
The (1 is used 10 measure the vector sum 0 اthe 10 currents. The relays that can compensate 10٣ capacitor
unit differences w i l l provide more sensitive protection. I t h e two banks are slightly different 111size, then
the resulting circulating current can عcompensated 10٣ اطmonitoring total phase current (dashed lines).
This w i l l also allow’ 10٣ a more sensitive relay setting.
ا
I
I
ا
ا
\
\ 100012
ا
ا
٣ '
ا Phitr ( urrrlt
داﻃﺎ
ا I n!i*l»nti‘
ل- Rdl) iwh
\ grounded or
(1) ungrounded
--------------------------------م
ﺗطﻊ
l'h«»(urrrnt
اnbalinct
Rrl،١ <t»O|٠»
()ه grounded or
(4) - phase current unbalance protection method for double w y c onnectcd capacitor
00* using w indow' type ٤15 at the neutral point connection
(b) - phase current unbalance protection method for double w e-connected »,bridge
configuration capacitor bank
The scheme shown 11 Figure 27(2) can be applied 10 banks w ith the same string reactances only, while the
scheme 50١٧1٦ 11 Figure 27(0) can عapplied 10 H-bndge configurations where string reactance 15
different. For H-bridge configurations, the crossbar should 0 عconnected at the bank 11111100111ا. I f a regular
CT 15 used 11٦ the H-bridge configuration, then surge protection 15 required. Alternatively, the connection
٤311be made with 2 w indow-type C T w ithout surge protection.
Very large grounded wye-connected capacitor banks (1... al voltages of 345 ٧ and above) require a
protective device sensitive enough 10 detect the 1055 of a single-capacitor unit in externally fused banks 0٣
1٦ ع10550٤ 3 few elements 111 internally fused 0٣ fuseless 2115. «ecause the failure 0 ا3 single unit 1٦ 1ع
large bank generates 211 operate signal that 15 50 low, the signal may be belo١v 1٦ عsensitivity (cutoff) level
0٤ 1٦14٦٧ traditional protective devices. Depending 01 the unbalance method, the system and bank inherent
unbalance can make the situation worse: During normal operating conditions, the operate signal may ع100
ا1. ٦ herefore, when the protective method 2 لparticular protective device are 1112 selected 10٣ a large
capacitor bank, 1115 preferable 10 105 ع11105 عthat compensate 10٣ system and inherent bank unbalance, and
that allow for achieving the required sensitivity. Typically, few protective ftnctions 3٣ عused 10 protect
large capacitor banks, including ٤٧0 10 three unbalance functions and three 10 five conventional functions.
For example, the voltage differential relay 11 Figure 8 compares voltages 011secondaries 0 اvoltage
transformers connected 10 the capacitor 311*5 tap 0011 and the bus. ٨ capacitor bank's tap 0011
connection depends 01 the type and configuration of the bank, 35 shown 111 Figure 8. 11 the case of many
capacitor banks (for example, externally fused, internally fused, and fuseless banks), low-voltage protection
capacitors 4٣ عused, as shown 111 Figure 8. Resistors 1114 ٧ عused 111 series with voltage transformers 10
avoid ferroresonance problems, 11 many externally fused banks, the voltage transformer 111 each phase 15
connected across 0 ٦ ع0٣ more series groups depending 0٦ the sensitivity requirement.
For ٧٣٧ large EHV capacitor banks, 4 backup (redundant) capacitor 001 neutral voltage unbalance
protection scheme is generally provided. The unbalance 0101221101 relay 11٦ Figure 8 15 connected 10 a
voltage transformer that measures the voltage across 4 lo١v-voltage capacitor unit 111 the capacitor bank
neutral. The unbalance relay 15 5 اع10 detect the 1055 0 اa specified number 0 اcapacitor units 0٣ elements
depending 01 the type of the capacitor bank. The relay 15 set 10 trip after a lime delay if the overvoltage
greater than the allowable level occurs 01 the remaining units 0٣ elements. The relay criterion 15 described
11 detail 1118.2 through 8.6. Relay setting philosophies may differ from 0٦ عapplication 10 another.
However, a 511011 time delay should be provided 10 prevent nuisance tripping (of a capacitor bank 1٦ 31
alarm state) 0 a system overvoltage transient. However, both voltage differential 3 لneutral voltage
unbalance relays rely 0٦ the same bus VT 10٣ correct operation: 11 case 0 اfailure 0 اthe latter, 011
functions become nonft nctional. Therefore, provision should be made 10 back up ٧1 0٣ use a current-based
method as well.
11٦ عovervoltage relay mentioned previously 510011 either use fundamental frequency quantities 0٣ ﻋﻂ
equipped w ith 3 fundatnental frequency band-pass filter 10 avoid false operations due 10 harmonic currents.
٨ third harmonic blocking filter may not prevent all false operations of this relay.
Some relays provide compensation schemes 10 overcome the effects of system and bank inherent unbalance
on sensitivity. 11 1115 regard, the neutral voltage 15 compared 111٦٣ with the open delta voltage 01٦ the ل5
voltage transformer 11 grounded ١vye-connected banks 0٣ w ith voltage across another ,ow-voltage capacitor
(not show n 11 Figure 8) 1٦case of double wye-connected banks.
3) Damaging transient voltages appearing 011 control ٢1٣1111(see IEEE Std (37.90. (ا٨)ا.
)ط Excessive current ؛lowing 10٣ longer limes due 10 the failure 0 اthe switching device. The
latching 0٣ lockout relay operated ط٧1ا1 عunbalance relay should have contacts 1 ٣ ل10 51011out
the neutral current transformer secondary.
٨ current transformer loading resistor, if used, should عable 10 withstand rapid 12411112 111 the event 0ا
single 01135100 until 1 عunbalance protection voltage relay and lockout relay 002101.
١Vound primary current transformers used 10 measure neutral current may be subject 10 damaging high-
voltage transients associated 11 اcapacitor switching 0٣ capacitor discharge 1110 nearby faults and may
require special protection. Current transfonners installed neutral 10 ground for unbalance protection are
particularly vulnerable because 0٤ the sensitivity requirements. I f metal 01 ﻋل٧311510٣5 (10٧5) are used 10
protect 1 عcurrent transformers 0٣ relays, then ٤3٣ عshould عtaken 10 ascertain that the 10٧5 have
adequate energy-absorbing capability. ٨ capacitor switching 0٣ fault transient may have very high energy.
٨ shorted 10٧ may disable the unbalance protection (Harder 851)ا. See 10.5 for additional comments.
The unbalance relay should coordinate with the individual capacitor unit fuses 50 that the fuses operate 10
isolate a defective capacitor unit before the protection switches the bank out 0 اsen ice. (٨ reliable fuse
operation provides a convenient, visual means 10٣ locating the defective capacitor unit(s)[٠
١Vhere possible. ااunbalance relay should be sensitive enough 10 alartTt for ا1055 0 ا0 عunit within 4
group. ا1 should also trip 4ا ل0 اع0 اﻻ01 the 105 0 اadditional 004٤110٣ units that cause a group
overvoltage 11 excess 0 ا%1100 0 اcapacitor unit rated voltage (0٣ the capacitor unit manufacturer’s
recommendation).
11٦ عtrip level 15 based 01٦protecting ا٦ capacitor units 31 لfuses from excessive voltages. 1٦ عalarm level
15 based 0٦ providing 31 early indication 0 اfailures within the 31.
The number o f blown fuses 10٣ trip can be determined by knowing 1٦ voltage 0٦ the capacitor units 11
parallel with the blown fuses (ICu) indicated 11٦ 8,4.3 10 8.4.6 and the capability 0 اthe units based either 01
industry standards 0٣ 01 the documentation provided ﻟطthe manufacturer. 11 the example calculated 11
Table 2 and Table 3, for standard units applied at rated voltage with 4 continuous contingency overvoltage
capability o f ا10%, tripping should occur after the operation 0 اthe first fuse, ٨1 this point, the voltage 0٦
the capacitor units 11 parallel with the blown foses is greater 1131 11ا% (above the 110% overvoltage
capability).
The number 0 اcapacitor units 11٦ parallel per series group 15 governed ٧ 0 ﻻ3 minimum and 4 maximum
limitation and can عeither single ١٧ ع0٣ double wye (see IEEE Std 1036). 1٦15 arrangement may result 11
1255 than ا%10 ٧01ا32 ع01٦1 parallel units after the operation 0٤ the first fuse. Alternatively, the bank might
ﻋطmade o f slightly higher voltage units 50 that the resulting overvoltage w ould not عabove ا100% o f the
unit rating after the operation 0 اthe first fose.
The trip level 001 لnormally be set 10 operate reliably afier the operation 0 اthe fuse that results 11 more
than 1100% o f capacitor unit rated voltage 01٦parallel units. The relay may be set midway between the
unbalance signal with that fose having operated 3 لthe unbalance signal with one 1255 fose having
operated. (Alternatively, ٦ ا%100 0 اcapacitor
the trip relay could be set at an unbalance that would result 11
unit rated voltage 011the remaining elements, regardless o f w hether اا15 condition could be anticipated 1٦
service.)
111 عsample calculations 1118.4.4 through 8.4.6 are 11 three groups, as follows:
a) ١Vye٠delta, and single٠phase (see 8.4.4 10٣ discussion. Figure 28 through Figure 30 10٣ the 0010
diagram, and Table 2 through 1001 4 (0٣ tabulated calculations). These calculations provide the
110111121101 required (0٣ setting ﻋﺎاunbalance protection based 011 the 10110٧100:
) اNeulral-to-ground voltage for ungrounded ٧ عbanks
2) Neutral current 10٣ ungrounded wye-wye banks
3) Neutral voltage difference for ungrounded wye-wye 03115
4) Neutral-to-ground current for grounded wye banks
5) Voltage across low-voltage capacitors at 11 neutral end 0 اeach phase 0٣ 11 1 عneutral-
to-ground connection 0 اgrounded wye banks
6) !difference in neutral-to-ground currents for grounded wye-wye banks
7) Delta and single-phase bank protection based 01٦schemes similar 10 item a l ) through
item a6)
)طTap voltage 010102101٦schemes (see 8.4.5 10٣ discussion. Figure 3 ا10٣ the bank diagram, and
Table 5 for tabulated calculations). These calculations provide 1 ﻋﺎinformation required ا0٣
5211110 the unbalance 0101221101 based 01 the 10101112:
The system of units used 10٣ 11105٤ of these calculations assumes every normal nonzero voltage, capacitance,
and current 15 اper-unit under 1101111 اهconditions, w ith 100 foses having operated.
Some examples are not realistic. ٤0٣ instance, for high-voltage banks with several series groups, 11 15
desirable 10 have at least 10 parallel capacitor units in each series group 50 that voltage 15 not excessive 011
the remaining capacitor 111115111a group after the 002141101of one fuse. ٨150. having many parallel units
2125 substantial overcurrent for fast fuse 0102101101 011 a faulted unit. Fewer parallel units have been used 11
some examples 111 this subclause 10 keep 1 عdiagrams simple enough 10 read.
In addition 10 providing the 1122255 ﻟﮫinformation for protective relay settings, 1115 type of tabulation gives
4 200 لfeel for the performance of the bank w ith varying numbers 0٤ fuses having operated.
٤0٣ specific 000 configurations, it 15 possible 10 combine the calculations 0٤ the various columns and to
calculate only 1 عfollowing:
٤0٣ some cases, because 0 اthe complexity of the configuration, 1 عresulting 2014110105 become onerous.
The layout 0٤ the tabulated calculations 1118.3.4 through 8.3.6 15 general 4 لallows for the analysis 0 ا3
w ide variety 0 اcapacitor bank configurations.
'tabulations ا1 عthose illustrated 1118.4.4 through 8.4.6 have been اﻟﺎ ﻣﺎﻋﺎ111understandingﻟﺎ1 عperformance
0 اa proposed bank before purchase. In addition, a ٤0م٧ of the tabulation at ﻋﺎاcapacitor bank location can
ﻋﻂhelpful ا0٣ those concerned w ith the future maintenance of the bank. Some manufacturers of capacitor
banks may provide ا151٧ ﻋﻢof tabulation 10٣ the banks they propose or supply.
Step-by-step calculations 3 لprincipal equation for each column for banks configured as per Figure 28
through Figure 30 are given 111 Table 2 through Table 4 [50111 equations for the conditions where 4
capacitor unit was short-circuited (50) but ﻟﺎ ﻋﺎا5ا ع105 00 اyet blown (5 )ﻟﺎ0٣ different from the equations
11 the tables. Also, different equations are used for cases w here ﻋﺎاequations shown 11 اtables result 111 4
division ٧ 22٣0. Some of these equations 10٣ unusual conditions are 001 01٧21 11 the tables.)
These tabulations illustrate the unbalance that occurs 111 the affected parts 0 اthis 000 as لresult 0ا
individual fuse operations.
The column headings 11 the tabulations are based on wye-connected, three-phase capacitor banks. For
delta-connected banks, 1 same formulas and tabulation(s) can be used by treating 1 leg 0 اthe delta 45 one
phase 0 اa grounded wye bank: االformulas are identical. ٤0٣ a delta bank, the currents shown as per-unit
of-phase current become per-unit-of-leg current (phase current divided by ٧3) The difference current
(equal wyes) 2201105 the difference 111 current between two equal delta-connected legs.
(ه 43 ﻟم
ﺳﻌﻠﻼ٠ ﻟﻣﻠﻠﺗﻠﻠل
nun, ٠ 3005353
1 3333 3333
1
TR 111 Figure 28 represent. ؟a resistor potential device 0٣ a voltage trans ormer 01 an ungrounded bank; 3
current transformer 0٣ a low-voltage capacitor; 0٣ a direct ground 011 a grounded bank.
Table 2 illustrates the unbalance calculations 10٣1 عsingle wye-connected bank and gives tabulated results
for the sample bank shown 11٦ Figure 28.
Table 2—Unbalance calculations ٤٥٣ the single wye-connected capacitor bank in Figure 28
Number 0٤ blown capacitor fuses "
( The number o f f uses that have blown 11 one
Column title F rmula 111 ctimmeiif ع parallel group of capacitor units, n 0 is the
,system normal c o n d i t i o n . )
0 su 1 2 3 4
Current luzVcttxCu
through 0 1.0000 10667 1 1034 12308 13913 16000
The current through the individual capacitor units 11 the
affected
group with the blow n fusc(s), per-unit of the value with 110
capacitors) fuses blown. Note that for healthy capacitor units Cli ا.
hi
fhc value for 5 ﻻindicates the short circuit current
available 10 blow the fuse 0٦ 2 faulted capacitor unit. 11115
value may be used 1٥ estimate die maximum clearing lime 1 1(0)00 10662 11,63 12632 14646 17143
of the fuse (assuming 110 discharge from parallel
capacitors 100 the faulted one). = (ﻟﺎك(ا ﻋﺘﺈ
Phase current I|>h = C|)xV!n 0 1(0000 ا 3333 09666 09231 08606 0.8000
change
The current 11 the phase with the blown fuses. This 1113 1 1(0000 to.2toXX٠0.9767 0.9474 0.9091 0.8671
!ph
be useful for setting protection based 011 phase current.
Ground /ى-(ا-7)*(ا-/0)اا
1111111 0 0.00.0) -0 33 3 3 00345 00743 0.1207 0.1769
change "The change 1٦ cufrcnto10 ground, which 1 used witoh
NOTE ا voltage equation 1 convenient 10 develop based 011 الinstant in time when the affected phase has 0 عper-unit voltage
3 لthe other 1*0 phases have 0 5 per-unit voltage Eor 11115 condition, the 1*0 unaffected phases can ﻋطparalleled, and the voltage
divider between -05 per-unit and -1 per-unit ٤31 be calculated for die midpoint voltage, which 15 recorded as 1214
NOTE 2/٤ the per-unit change 111current 10 ground 1 ىthe per-unit change 111 voltage across 3 low-voltage capacitor 111 the affected
phase. ااis also the per-unit change أ1 voltage across اlow-voltage capacitor 111 اا1 ncutral-to-ground ٤01111٤1011because the other ٤0
phase cutTcnts ل0 not change 11 3 grounded ٦٩9 عbank.
NOTE— A ا1 لnumber u f unbalance protection methods 15 available 10٣ the single wye-cunnecled bank‘ However,
when the bank 15 connected in a double wye, the number 0 اprotection methods available 15 increased, thus, allow ing
more flexibility 21 لsecurity tor protective purposes.
٩٠
11٤ 111Figure 29 represents 3 current transformer 0٣ a resistor potential device 0٣ 3 voltage transformer 0٦
31 ungrounded bank: a current transformer 0٣ a lo١v-voltage capacitor: 0٣ 3 direct ground 01 3 grounded
bank.
Current hfzCcuxCit
through 0 1 (XXX) 10667 11034 123 08 1 3 9 1 3 1.6000
T h e current through the individual capacitor units 1 t h e
affected
group w ith the blown fuse(s), per-unit 0 the v a l u e ١1 ا110
capacitor(s)
11155 blow n.ل01 عthat for healthy capacitor units Cu - 1.
lit
11 عvalue for 5 ﻻindicates the power 3re٩uenc٠١ current
available 10 blow the fuse 01 3 faulted capacitor unit. 11115
ا 10000 10667 1ا107 1,2491 1.4208 ا6634
v a l u e may be used 10 estimate t h e m a x i m u m clearing t i m e
o f the fuse (assuming 110 discharge from parallel capacitor
units into the faulted one).
Current 11 lyzCsxVln
affected ١١٦ع 0 1 (XXX) 13333 09655 0,92-31 0.8090 )ااااا
The per-unit current 111 t h e series/parallel 210 0 مwith t h e
Iv blown ftise(s). 1115 v a l u e may be useful for differential
schemes comparing 111 current 111 different scries, /parallel ا 1(000) 12537 109719 0,9.308 0.8917 0317
groups.
(11,11 111 IphzCpxVln
affected
0 1(000) ا 1905 09٤03 00500 09255 0.8857
The current 11 the phase w ith the blow n fuses. 11115 may be
phase
0/
useful 10٣ setting protection based 01 phase current. ا 1.0000 1.119*1 1 6 8 1 0,970-3 0.9490 0 9208
N u m b e r 0 اblown c a p a c i t o r fuses n
(The number of fuses 11131 have 1011 1
(,»Il, 1 ,1 title f o r m u l a 111 comment ع 011 عparallel group of capacitor units, n 0
is ا1 عsystem normal condition. n)
II st ا 2 3 ل
(110111ل te = (l-G)x(l-٠٨)
current () 0.0000 01905 00197 00440 00745 0.1143
change The change 11 current 10 ground, which 15 used ١1ﻻ
protective relay schemes utilizing either ncutra!,Oground
/
current, or the voltage across a low-voltage capacitors) in ا 00000 0000 0 0000 (0.0000 0 0 0 0 0 )ااااااا
the neutral or 111 each phase.
Neutral ﺛﺘﺜﻴﺚ»ا
current 0 0 0000 0 010 010 0 0 0 0 0 00000 00000 0(0000
between wyes Unbalance current for ungrounded wye-wye banks, [The
ط current 15 calculated assuming the neutral-to-ground (zero
sequence) voltage 15 applied 3 اthe neutral of the ١ عw ith ا 0.0000 0,0896 0.0099 00223 0 . 0 8 2 0.(594
no blown fuses,]
*
441444
mi
Calculations arc similar 10 a double ١٤٧ع-0111 ﻟﻌﻌﻊ00 with uneven 105 عshown 111Figure 30 with all
formulas applicable. Additionally, differential current between two equal legs 15 calculated, which makes i t
suitable 10٣ the phase current unbalance method.
Table 4—Unbalance calculations for ٤٤2 double wye٠connected capacitor bank i n Figure 30
N u m b e r 0 اblown c a p a c i t o r fuses n
(The number of ftises that have blown أ1
( (»Innin title F o r m u l a 1111 ٤0 111,11
ع11٤ اﻟﻢ
011 parallel group of capacitor units. 0 - 0
15 the system normal condition !
0 st ا 2 3 4
اﻟﺎ.
Parallel group
ي-ع 0 1.0000 0857 ا0.7143 0.5714 0 4 2 8 6
per-unit
The capacitance of the parallel group of capacitors that
capacitance
ا sc
٤٤
includes the blow n I'U5C(S). 1.0000 0457 ا07113 0.571 (0 4286
Affected wye
capacitance ٥= ‘ 0 ا 0000 ا 3333 090600 0.9091 0.8421 07500
٨ variety 0٤ protection schemes, primarily 10٣ grounded ٧٧ع 015. 15 based 01 the measurement 0 اa
voltage across some number 0٤ series groups 0 اthe bank. 1٧0 common schemes are 10
1٦ either case, the measured voltage may be compared ١vith the phase 0110295 (differential protection) 0٣
combined ١vith each other to determine unbalance.
Regardless 0٤ the relay 10 عused, the schemes are based 0٦ the change 111 tap voltage caused by a change 11
the 211٤٤1٧ عcapacitance 0٤ one 521125 group, resulting 110111 4 Failure and/or capacitor tfrse operations. 11١15
change may depend 011 whether the aft٠ected capacitor units are located outside 0٣ inside the tap 0011101of
the 00. 11٦ عcalculations assume ااهof the blown tfrses 3٣ ع1٦ 011 عseries group 1٦ 011 ع035( عeither inside
0٣ outside the tap portion, اﻻط10٤ both places at the same time).
Figure ؤI illustrates a midpoint-tapped capacitor bank. Table 5 gives the unbalance calculations 10٣
grounded wye, delta, 0٣ single-phase banks.
For delta 0٣ single-phase banks, tap 15 from the 10 مpoint 10 1١ عreference end of the 120 or bank (instead of
the neutral). The calculations are made 111 the same 3 ﻷ25 shown 10٣ three-phase grounded wye 211*5.
٩
B
ه
d
Blown fUMfi-
lappod
45441411141 TTTT1144T4 1 41111
41111111111 1111٤ 4ﻟﻣل
»ل tiinlliii!
ﻟﻠﻠﻠﻠﻠﺑﯾﯾﻛم Y
غ
1111
U
إ ٠
ا
1
٠
٦ Blown Kimi-
n { اxxlKin
'٦٢
Tap voltage
<l v >g =
change, 0٤٣-
unit o f normal The per-unit change 11 the 10 مvoltage, assuming ا per-unit 15 00000 02500
0.0196 0.(0426 0.(0698
-01026
٨1 11-0٣1ل0 عmay ا ع15 ﻟﻊ10٣ unbalance protection 111 3 variety of* capacitor 001* connections: grounded
wye, ungrounded wye, delta, and single phase (series capacitors). The !!,bridge 15 based 011a current
measurement 11 a leg connecting 10 strings of* capacitors together near the midpoints of the strings. 11ع
current transformer for unbalance detection appears 01اا1 عcrossbar of the capital letter ( ا اfigure 32). thus,
the designation !؛-bridge. Any change 11٦ the capacitance of any capacitor 111 the bridge will cause a change
in the II current.
Calculations (130 ا6) are based 01٦ ftise operations 11 one parallel group of capacitor 1110115. The ambiguity
resulting 11011٦ the operation 0٤1155 11 another part of 1 bank that may cancel the unbalance signal needs
a sensitive alarm level (preferably 01٦ عfijse) 50 that the defective unitع311 be replaced before there are many
scattered 115 عoperations, 1٦ addition, assuming that one 0٣ ٤0 ‘canceling” fuse operations occur at 1٦ع
٤111
٦ ع0 اunacceptably high voltages 01 the affected capacitor units, 11 may be desirable 10 set the 1٣10 level
somewhat low er than suggested by the overvoltages of Table 6.
ا1ع End
اب-ﺳب
ﯾﺎن
ﯾﺎن
iiiiliil
٢٣ اﻣﻣم
ﻟﻴﻤﺎن
ﯾﻣﺎن
;؟٢ ٩٣ ٢ أ١ آت٣
ال
5 5 15 ﻣﻣﻣﻣم1 5 ﻧم5
١ ١ ﻻﻟﺗم١ ١ ﻟﻠﻠﻠﻠلﺟﻠر
ﻳﻤﺎن
رﻣﺎ-
ا؟-
-)ﯾﻣﺎ
-ﯾﻣﺎل
-ﯾﻣﺎل
ﯾﺻﺎن
1
rí
1 ﻟﻣﻣﻣﻣﻣم
1 آﻧم ﺟﻠﺣم ﻣﻧم١ <ﻟﻣﻠﻣﻣمأﻧم م
1 1 1 1 ١ ٦١
1 T T
دا Blown
اﻣﺮرﻋﺎor reference 1
(5=)ﻟﺎ55*ﺣﺞ
The example illustrated 11 Figure 32 and Table 6 15 not 3 recommended 1!-bridge design 05 the overvoltage
01 remaining units may عexcessive after the first ftise operation. Better practice ١١ould normally be 10
have more parallel units or fewer series groups, 50 that there could ﻋطan alarm before trip.
1٦٤٤1113اا٧ ﻟﺎا5 ﻟﻊcapacitor units (Figure 33) 3٣ عsubject 10 0210 ا142 41055 elements and uses within ﻋﺎا
unit as internal uses blew' and remove elementsا10111 4 parallel group. The overvoltage 011 these remaining
elements and fuses should be considered in addition 10 the overvoltage 01 units without blown fuses. The
bank design W'ill dictate unbalance signals available 10 the relay, which 11115 اturn affects ﻋﺎاprotection
sensitivity.
ﻟﺂ٦١
The setting of the unbalance 0101221101 of an internally fused capacitor bank should ا0 عinto consideration
the capability of the internal fuses, the transient overvoltage capability 0 اthe 211121115. 41 ل1ﻋﺎ
consequences of a failure 10 the case or the failure of an internal fuse. These considerations are 11 addition
10 the usual considerations 0 اexternal arcing within the 0011 and avoiding exposure of healthy capacitor
units 10 voltages 111 excess 0 ا ا%100 0 اtheir rated voltage.
11 an internally fused capacitor bank.اا1 عunbalance detection gives an indication 0 اthe total number 0ا
failed capacitor elements within 3 capacitor unit. 11 practice, the actual number 0 اfailed elements canﻋﻂ
determined only ٧ a complete measurement 0 اال اunits 111 4 bank. 11115 measurement may be
recommended 011 اw hen 2 relay alarm 0٣ trip occurs, and 11 ,nay 0٣ may not be 3 0011 of the regular
maintenance schedule.
— The number 0 اoperated fuses 11 the affected capacitor unit 0005 not exceed the maximum
number recommended by the manufacturer.
— The 01142 ع011the healthy capacitors does 110 اexceedاا1 عcontingency overvoltage capability 0ا
the capacitor units (usually ا%100 0 اrated voltage). 01 that ﻋﺎclement voltage 11 1 عunit
with blown fases may exceed ا100% of normal
10[ instance. 10٣ ﻋﺎاexample 51١0١٧1111 Figure 34 and Figure 35, the number of blown fuses is shown 11 the
top ٣0١٧ of Table 7. If the capacitor manufacturer recommends that the bank should ﻋﻂtripped after the
operation 0 اthe seventh fuse, then 10 assure reliable operation, the [ا1 مrelay 5 اع001 اwould ﻋﻂmidway
between ﻋﺎاunbalance signal with 51 fuses having operated and the unbalance 5101 ال١1 ااseven fuses
having operated. For this example, اا٦ عvoltage 011 the healthy capacitor units with seven fuses blown 111 011ع
capacitor 15 about 1.069 per-unit, w hich 15 Ie55 than 10% overvoltage. For banks ١٧11٣ the voltage 01 the
healthy units becomes excessive before the maximum number 0 اblown fuses recommended ط٧ ﻋﺎ
manufacturer, the trip relay 5 انlevel would be set halfway between the signal associated w ith ﻋﺎmaximum
number 0 اblow n fuses w ith acceptable voltage 011 healthy capacitor ل1115and اا٦ signal associated with ﻋﺎ
number 0 اfuses that results 11 excessive voltage 00 healthy capacitor units.
The alarm would be set above natural errors 50 that it would operate reliably 0٦ the 1055 0 ﻋﺎ اfirst 0٣
second 105. 115 alarm set point would typically عhalfway ٤١221 the signal associated with the
selected number 0 ا11505having operated and ﻋﺎاsignal associated with one fewer fuse having operated.
The actual unbalance signal will depend 01 1 عprotection scheme employed for the bank, ٨ w ide variety 0٤
protection schemes are 11 use 011 internally fused shunt capacitor banks. 11٦ عunbalance signals for some of
the more 0111110٦connections 4٣ عgiven 11 Figure 34 41 لTable 7. ( h e r calculated values arc given 11
8.4.5 and 8.4.6 under separate discussions 0٤ tap voltage and ! ا-bridge protection schemes.
11 addition 10 providingاا1 عnecessary information for protective relay settings, this type of tabulation gives
a good اﻋﺎfor the performance 01 عbank with varying numbers 0 اinternal fuses having operated. Some
manufacturers 0 اinternally fused capacitor banks w ill provide this 10 ع0 اtabulation 10٣ the banks they
propose or supply.
0 اcourse, it 15 possible 10 combine the calculations 0٤ 1 various columns and calculate only the
following:
Because 0٤ the complexity’ 0٤ the configuration (for example, parallel elements and series 010105 11٦ 3
capacitor unit, parallel capacitor 1111511 a group, series 210110511 a string, 3 لparallel capacitor units 111 a
phase), the resulting equations become complex.
111 عtime delay for tripping should ﻋﻂminimized ٤0 reduce the probability’ 0٤ case rupture 11 the event 0٤ 2
fault 10 the case 0٣ fase failure w ithin 3 capacitor unit. 11 addition ٤0 the considerations 0٤ 8.2.4. 111٦35 be
desirable to coordinate with the melting 0٤ an individual fase element where there 1510 parallel energy to
speed up the fase operation. [The manufacturer 0٤ the capacitor units should ﻋﻂable 10 supply the
1113٢111111111 clearing time (curve) for the internal 11525.] There 15 no need 10 ٢٧31110 coordinate for fase
operation with unbalance signals that are larger than would occur for 3 shorted element before tuse
operation.
Normally, a time delay of 0.01 5 ٤0 0.05 5 15 adequate for this coordination. With this intentional time delay
11 1 عtrip clay, the additional time required 10٣ the lockout relay 3 لbreaker operation may result 11٦1 total
clearing 1111105 of 11٦ عorder 0٤ 0.1 5 for a capacitor unit with 311 internal fault 0٣ 2 capacitor bank 1 ﻟﺎ21
arcing fault. ٨ time 0٤ 0.1 515 reasonably achievable 10 clear a capacitor bank w ith 3 problem, but it still
may result 11 substantial damage, ( n e e 03115 of 2 capacitor bank start to become damaged, then farther
damage will escalate rapidly. Such escalation will increase the [15 of major damage and I r e and 114٧
result 11 increased damage 10 the capacitor 021. Keeping the clearing time 51101115 important 10
minimizing damage 11 1 عe ent 0 اa fault ١١*ithin 2 hank.
With internally fused capacitors, it 15 not appropriate 10 use protection schemes ١١ith enough delay 10
override the effect of system faults (١١*hich may persist 10٣ cycles).
fienerally, the 111051 appropriate alarm level 15 the lowest le١*el thatع311 عset without resulting 11 false
alarms from thermal ١ariations 11 capacitance within the hank, practical initial hank balance, and 50 on.
(11٦ عearliest reliable alarm gi١*es maximum opportunity* 10 repair the capacitor bank during 4 scheduled
outage.) Responding reasonably 10 early alarms and maintaining the bank 11٦ the best possible condition
tend 10 minimize the probability of farther element failures and forced 0٣ unscheduled outages and 10
maximize the availability 0 اthe hank. False or unreliable alarms ٤31 be costly, and they decrease the
credibility 0٤ the capacitor protection.
11 unbalance protection schemes with ambiguous indication, 1115 desirable 10 use an alarm setting sensitive
10 ا1 عloss 0 اthe first element 10 avoid the ambiguity. This alarm should seal in 50 that 1 اshould be
manually reset after the removal of' the failed capacitor units 110111 the bank. It would عundesirable to ha١e
1 عalarm shut off after the operation 014 subsequent ل5 عthat cancels the unbalance signal.
11٦ عtiming 0 اthe alarm should be long enough 10 a١’0id operation during system faults or temporary*
overvoltages but 511011 enough 111 the case of ambiguous schemes 10 minimize the probability 0 10
compensating fase operations before the initiation of the alarm. Usually about a i d s delay 15 appropriate
for the alarm.
11 managing the protection of an internally fased capacitor bank, 11٦ عunbalance 01012210 should not ع
reset 0٣ *rebalanced,' without first making sure that all capacitor units with failed elements have been
removed from the bank.
If the installation 1510 ﻋﻂrebalanced ١vith units having one (0٣ ٤٦٧0) 111 لelements remaining in service,
then the trip level should ﻋﻂadjusted downward 50 that the 111505 31 لelements 1٦ these units 00 not exceed
their capability before operation of the trip relay.
11٦ عsample calculations in 8.5.4 through 8.5.6 3٣ ع1111 ع10 ا101110three groups:
4) Wye, delta, and single phase (see 8.5.4 for discussion. Figure 34 for the bank diagram, and
100 ع7 for tabulated calculations). These calculations provide 11٦ عinformation required for
setting the unbalance protection based 01 the following:
)ا Neutral-to-ground 01130 عfor ungrounded wye 015
2) Neutral current for ungrounded w*ye-wy*e banks
3) Neutral voltage difference 10٣ ungrounded wye-wye 03115
4) Neutral-to-ground current for grounded wye banks
5) Voltage across low*-١*o!tage capacitors at the neutral 211 0 اeach phase 0٣ 1٦ neutral-to-
ground connection 0 اgrounded ١١*ye banks
6) Difference 1 neutral-to-ground currents for grounded wye-١١y banks
7) Delta and single-phase bank protection based 0٦ schemes similar 10 item a l ) through
item 26)
b) !؛-bridge 0101221101schemes (see 8.4.5 10٣ discussion. Figure 36 for the 00* diagram, and
Table 8 10٣ tabulated calculations). These calculations provide 11٦ عinformation required for
setting 1٦ عunbalance 01012211011 based 01 the current between 11110100111٤5 0٤ 10 similar 1295
connected phase 10 neutral or ground, phase 10 phase, or 1٦ the 0025 (series capacitors).
c) Tap voltage protection schemes (see 8.4.6 tor discussion. Figure 37 ا0٣ the bank diagram, and
Table 9 10٣ tabulated calculations). These calculations provide the information required for
5211أ112the unbalance protection based 01 the following:
)ا Midpoint ٤0 ground tap voltages 10٣ grounded wye banks
2) Differential protection, comparing 11٦ عvoltage across 0 ٦ ع0٣ 1110٣ series groups with
the 5٧5٤٤1٦ line 10 ground voltage for grounded ٧ عbanks
3) Delta and single-phase bank protection based 01 schemes similar 10 item c l ) and
11211 2)
11٦ عsystem 0 اunits used 10٣11105 0٤ these calculations assumes e١'ery normal nonzero voltage, capacitance,
and current 15 اper-unit under normal conditions, w ith 110 fttses having operated (exceptions 0٣ عindicated).
11٦ عprincipal equation 10٣ each ٣0٢ of tabulated values 15 01٧٤1٦11٦ the first column of Table 7. [Some
equations 10٣ the conditions where 21 element has faulted, اﻟﺎطthe fijse has 10 ا٧ اعblown (SE), are
different. Different equations 3٣ ع0150 052 ل10٣ cases where the equations 11 Table 7 result 11 dividing ط٧
7210.]
These 1001013110٦5 illustrate the unbalance that occurs 11 the affected phase 0 اthe bank as 3 result 0٤
individual fuse operations.
Tabulations 0 اthe sample 01* 3٣ provided 10٣ both grounded and ungrounded banks. 10٣ delta-connected
banks, the same formulas 3111 tabulation(s) ع31 ﻋﻂused ط٧ treating 3 120 0٤ the delta 35 one phase 0 ا3
grounded ٦ عbank; all formulas 3٣ عidentical. For 3 02113 bank, 11 عcurrents 51101 35 per-unit-of-phase
current become pcr-unit-of-lcg current (phase current divided by ٧3). The difference current (equal wyes)
becomes the difTercnce 1٦ current between 10 equal delta-connected legs.
ي
--ص ل ا
Affected
string ًﻫﺪﺳﺎ 0 10000 103710 09079 00956 09929 0 9899
capacitance The per-unit capacitance o f the string of (parallel groups
0 )اcapacitor units from phase 10 neutral that includes the
affected capacitor unit. For the group including the affected
unit, the per-unit capacitance is Cg For all 01٦٤٣ groups, ا 1(0(000 ( ا03710 100079 0 . 9 9 5 6 00929 0 9899
the per-unit capacitance 151.
Per-unit ع ع
capacitance, Cp: ; 1 1(0000 101(01 0.9994 00988 0.9981 0 9972
phase ١١ilh The per-unit capacitance of the phase (all parallel 5 ﻻ1125)
affected 111 1111includes the affected unit. For 1111calculation the
capacitance of the affected string 1 Cs. 111 capacitance 0٤ ا 10000 10101 09994 0.9988 0098 ا0 9972
Cp
all the other 511100515 اper-unit.
Neutral-to-
171-ي-0(4)ي
ground 0 0001 0.0000 (0.(00(00 0,000(0 0 0000 00000
voltage (per- The neutral-to-ground voltage. 10 210 ﻟﻌﻠﻼbanks (7 -
unit of ,7g) 0)١ this voltage is always 0 For ungrounded wye banks, the
Ing calculation assumes the affected phase has 3 capacitance
Cp, and the other 1٦0 phases each have a per-unit ا 0 0000 0.0034 0.(00(02 0.0004 0.0006 0 018)9
capacitance 0٤1.
Voltage 0٦ ا/=11ي+1
affected 11 ع٧0112٤ عline 10 neutral 22105511 عphase that includes 0 10000 100(00 1 0 0 0 0 1 0 0 0 0 1 . 0 0 0 0 ا00100
phase 1٦ عaffected unit. ١٨٧11 اfused units, the operation of the fuse
ا/ور reduces the capacitance of diat phase and increases the
١oltage 01055 the affected phase; therefore, the numbers
are a,١١ays greater 111111 one except before the operation 0٤
ا 1 ( 0 0 0 ) 0 9066 10002 1 . 0 0 0 4 1.(0006 1(0009
Voltage 0 Ve:VcuxVg
affected 0 10(000 0 0000 1 0 5 6 6 11200 1 . 1 9 1 5 12127
The actual per-unit voltage 01 the affected elements, based
elements
01 the actual voltage 01 the affected unit.
١’e ا 1 0 ( 0 0 ) 0.(0000 1 . 0 5 6 8 1.1205 1 . 1 9 2 1 1.2739
NOTE ا-For Vng calculations, it 15 convenient 10 develop this equation based 01 an instant 111 time when the affected
phase has اperunil voltage and the other ٤٧0 014525 have 0.5 per-unit voltage. ٤0٣ 115 condition. 1 عtwo
unaffected phases can be paralleled, and the voltage divider between - 0 . 5 per-unit and + اper-unit can نcalculated
tor the midpoint voltage, which 15 recorded as I ng,
NOTE 2-Calculations above apply 10 t0olh single 31 لdouble wye-connected banks: double wyc-connccted banks
calculations are applicable starting from the 1st value calculation onward.
-'1
اﺳﻞ
ل
11٤ 111 Figure 35 represents a resistor potential ل٧1 ﻋﻊ0٣ a 0ا100 عtransformer 011 an ungrounded 0010 0٣ a
direct ground 01 a grounded bank.
٨1 I!-bridge may ﻋﻂused 10٣ unbalance protection 111 3 variety 0 اcapacitor bank connections: grounded
wye, ungrounded wye. delta, and single phase (scries capacitors). rhe I!-bridge 15 based 011 4 current
measurement in a leg connecting 10 strings 0 اcapacitors together near the midpoints of the strings. 11ع
current transformer appears 10 ع0٦ ﻋﺎاcrossbar 0ا ااcapital letter ( ااsec Figure 36). thus, the
designation ! ؛-bridge. ٨٦٧ change 11 the capacitance of any capacitor 111 the bridge ١١ill cause a change 11
the current in the II.
Calculations (see Table 8) 3٣ عbased 01 internal 15 عoperations 11٦ one group 0 اelements 11 01٦ عcapacitor
unit. The ambiguity resulting 110111 the operation 0 ا1525 111another part 0 اthe bank اﻟﺎ1113٧cancel ﻋﺎ
unbalance signal needs 10 be addressed (see 8.3.3).
٤0٣ an unsymmetrieal arrangement such as shown 1٦ Figure 36. 1 effects 0 اblo١١’ing fuses 11 units 11
other 00115 of the bank 01 the overvoltages and H current, 41 ل50 01. may easily be investigated by
appropriately changing the 4 اا125 05/. /20. 41 وﻟﻢ ل50 that the affected unit appears 10 ﻋﻂ11٦ ﻋﺎI0١١er 1211
part of Table 8. ٨ اا0 اthese calculations assume that االblo١١T! fuses are 11٦ 01٦ عgroup 0 اthe affected unit
only.
ا1ااع
١umbcr 0٤ b l o w n c a p a c i t o r 10525/
111 عnumber o f fuses ihat have blown 11 0ع
parallel group o f e l e m e n t s inside 01٦ عcapacitor
01 111ع
11111 formula and comment ع unit/ 0 15 the system normal condition.
/ 5أ ا511 عcondition w ith 1 shorted c l e m e n t
(5٤) before the operation 0 the element fuse ]
(1 SE ا 2 3 4
Affected
phase ٠,م(د-ا, 0 1.0000 ا0000 101(00 1,0000 1 0 0 0 0 10000
voltage The voltage across the affected phase, that 15, 1 for
رراا grounded wye 0٣ delta, w here ى- 0. ٤0٣ungrounded
wye, this voltage 15 the per-unit voltage 41055 the
affected phase including t h e effect 0 اthe neutral shift ا 1.0000 0 9978 1,0001 10002 1 0 0 0 4 10005
from capacitance unbalance.
H leg
voltage,
17إ-ي 0 0.4280 04247 0.4288 0,4290 0 4 2 9 2 0.4295
(per-unit 0٤ The voltage o f the 11 leg, per-unit o f the actual voltage on
1/91) t h e affected phase.
ا 104246 04247 (04288 (04290 0 4 2 9 2 04295
راا
H current, per
=اا-1»(٤-1)(ﻟﺔ٤)()ﻛﺜﯿﻜﺪ
unit of total 0 0(00010 0 0(004 0 (0008 0(0012 0(0017
00070
phase current 11٦ عcurrent 1٦ the ااleg, per-unit o f the normal total
th phase current for a wye-connected 0 single-phase bank 0
ا 00000 00001 0<MX)S 00012 0(0017
per-unit 0٤ total leg current for a d e l t a bank. 0.0070
Voltage 0٦ ررا- ا ﺛﺚ
affected CH - ر،+(ع-1٠ب،م*ز-|ا 0 1 0(00 04494 1.0078 1.0164 1.0260 1.0368
capacitor unit The ٧01132 across the affected capacitor unit, per-unit 0ا
Vcu 11 عvalue w ith 110 fuses b l o w n , ا 1.0000 0,8475 1.0079 1.0166 I 0 '4 10373
Voltage 011
affected ١٤ --٤٢٢٢ 1 0 ) 0 0 0 0000 1,0510 1.1088 1 1 7 2 5 I 2 4 1
element The voltage 21055 the remaining elements 11 the affected
Ve element group (0150 t h e voltage 11055 the blown fuses in
that group), per-unit o f the v a l u e w i t h 110 fuses b l o w n . ا 1 0000 010(000 10517 1.1090 11730 1 2445
Current /ر-رﻳﺮرا
through 0 1(0000 1 2 7 4 2 0.0450 0.9702 00527 0.9331
The current through the affected capacitor unit, per-unit 0٤
affected
11 عv a l u e ١111 ﻣﻢfuses b l o w n . T h e v a l u e for S E indicates
capacitor unit
the 00١٤٤ frequency current a v a i l a b l e 10 ٤10 the fuse 01
In a faulted element. 1115 0ﻋﻼ may عused 10 estimate the
ا ا2713 0,9410 (0.9704 0 9 5 3 1 0 9 3 3 6
m a x i m u m clearing l i m e o f the fuse (assuming 10
discharge 110 parallel elements 1010 the faulted o n e ) .
٨ variety 0٤ 101012٤1101schemes, primarily 10٣ grounded wye banks, are based 01 the measurement 0 ا4
voltage 21055 some number 0٤ series groups 0٤ the 001. 10 common schemes are 10 perform the
following:
Regardless 0 ا1 عrelay 10 عused, the schemes 3٣ عbased 01 the change 11 tap voltage as 3 result of a
change 1٦ the capacitance 01 an affected capacitor unit. 11115 change may depend 01 whether the affected
capacitor unit 15 located outside or inside the tap portion 0٤ the bank, f igure 37 illustrates a midpoint-
tapped capacitor bank. Table 9 gives foe unbalance calculations for grounded wye or single-phase banks.
٩ح
ه
1 ؛
ﻟﻣﻠﮭﻲ - ٦
ل
&
Aftcdtd اا ﻣﺎ ﻋﻠدا٠nx*f«
1 اطﮫ2 9 — Unbalance calculations ٤٥٣ voltage differential protection for the tapped
wye-connected capacitor bank i n Figure 37
d u m b e r , 0 اblo٠١n capacitor fuses ﻧم
(11٦ number,of fuses that have blown 11 one
parallel g r o u p ,0 f elements inside one capacitor
C o l u m n title 1«0٣11111 a n d ٤011111٤11٤ 001./-015 the system normal condition. - SE
i s t h e c o n d i l i t n ١v؛th a shorted element (SE)
before 1 ع0 pcration 0 اthe clement fuse.]
10 SE 1 2 3 4
Affected
دم:ﻟﺎﻟﺂ١ال٠ﺋﺔ ل:
capacitor per-
unit The per-unit capacitance 011 عaffected capacitor unit, based 1(0(00(0 .5000 0 . 9 7 0 2 6 0.95455 0 - 9 2 0 5 7 (0,900(0
capacitance on the number of blown fuses 111 one group (11 111 affected
Cit capacitor).
Affected phase وع- ي
capacitance ي- p،+<p٣-(i+c«0x(í-l
03133 03387 03331 03328 03324 03321
٢٠’, 11٦ capacitance 0٤1٦ عphase 10 ﻟﻢ10 end, as,suming the
capacitance of one healthy capacitor unit 15 اper-unit
8.6 Fuseless c a p a c i t o r b a n k s
The internal construction o f the capacitor units used 111 fuseless capacitor 0315 15 similar 10 that used for
externally fused hanks. The parallel-connected capacitor unit o f Figure 38(4) illustrates 3 unit with 10 series
210005 of three elements each. 11 1115 construction. 1٤one element fails, then 11short-circuits itself and 11٦ع
1٧0 elements 11 parallel ٧111 11.
In ٤ capacitor bank, individual capacitor units 2٣ عconnected 111series with each 01٦٣ from the phase
connection 10 1 عneutral connection. Each such series connection 15 a "string.” Within the 511100. all 0٤ 1ع
2121112115 (groups) are 11 series with each other. ٤0٣ instance, if the 51٣100 0051515 of 51 capacitor 111115.
each having eight series (21011105 of) elements, the string would have 6 *8- 48 elements 11 series (see
figure 39). 1٤0 ع01١ عelements fails, the applied voltage 1511121 divided among the remaining (2101105 01)
healthy elements 11 series with ٤ عfaulted element, )he voltage across the remaining elements will thus ع
48/47 of what ٤ 10101 been before the failure.
٢١ﺣم٠"٦ﺟم٦ ٢٩""م٦م
ا
٨٨ ا I ٨٧٨٨
HHHHHHHHHHh
HHHHHHHHHHF
The calculation 0٤ unbalance performance of 11521255 capacitor banks 15 based 011 the number 0٤ tailed
elements (element 2101105) 311ل01 the total number of (groups 01) elements 111 series.
(011 occasion, series connected capacitor units [see f igure 3 8( ])طhave been offered for useless capacitor
banks. Series connected capacitor units have the individual elements connected 111 series 51111125 between
the terminals, 111 a number of such series strings 111 each unit, üanks built with series connected capacitor
units need more sensitive unbalance protection requiring 31 advanced protection compensating system 10
correct 10 inherent unbalances and utilizing biasing for security.
٨5 indicated, the number of elements 11 series 11 لstring 15 the number of capacitor units 111 5115 times the
number of elements 11 series 11 each capacitor unit. Sometimes the manufacturer will provide the number
of elements 11 scries. Secﻻ1 عcapacitor unit nameplate or data sheet. 1 ا1 عnumber of scries elements per
capacitor unit 15 00 اavailable 11011ا manufacturer, then the number may طestimated, tach clement
usually 135 3 0001 11 اﻟمvoltage rating 0٤ 1800 ٧ 10 2400 ٧. Dividing the capacitor unit voltage ط٧ 2400 0ل
rounding up 10 the ٤٤ integer will usually ع1 ل عuseable estimate 10٣ the unbalance calculations and
settings. 10٣ instance, 1 7960 ٧ capacitor unit will probably have about 7960 / 2400 - 3.3. which rounds ﻣﻼ
10 10ﻻ٣ scries elements. (11 may have five series elements per capacitor unit, which will 1100 a small
difference 11 the overvoltages 11 لunbalance signals. However, the settings based 01 four scries elements
١vill still provide adequate protection for the five scries element design.)
11 a 10521255 capacitor bank, the unbalance detection gives an indication 0 the total number 0٤ failed
elements within a string 0٤ capacitor units. The location 0٤ these failures 15 determined by capacitance
measurements 01 the strings indicated by the unbalance protection,
The trip level should be set 50 that 1٦ عvoltage 0٦ the remaining elements 1٦ the atTected string 0005 1101
exceed the maximum recommended by industry standards 0٣ 1٦ manufacturer.
The number 0٤ shorted elements for trip and alarm can be determined by knowing the ٧01122 01٦ the
affected elements (for instance, the Ve value calculated 11 Table 10) and the capability of the elements
(either 110% 0 ا٣411112based 011 industry standards 0٣ the information provided by the capacitor
manufacturer), ttased 01 the example calculated 11 Table 10. 10٣ standard capacitor units applied at rated
voltage and element capability of ا%100. 11001112should occur after the shorting of the fifth element. ٨ اthis
point, the voltage 01٦ the remaining elements 15 ا10.26 .
(.alculations may also عmade w ithout know ing the number 0 اseries 221112015 by using the total string
capacitance and tripping 01٦ the capacitance change that w i l l result 11 a ا100 % voltage 01 the remaining
capacitors 1٦ the string. ٨150.10 avoid case rupture 11٦ the event 0 اa terminalto-case fault, the bank should
trip on the loss o f elements equivalent 10 the shorting of one capacitor unit. ٤0٣ capacitor banks 11 ا1110٣ع
than 1) capacitor units 00٣ string, the tripping 10٣ the 1055 0٤ one capacitor unit w i l l be lower than ا ا00 %
0 ا142 ع0٦ the remaining units.
10 verify that elements are 1101subjected 10 voltages 1٦ excess o f their intended application, the trip would
normally be set halfway between the signal associated with four shorted elements and the signal associated
w ith five shorted elements (10٣ the example calculated in Table 10). Alternatively, the trip relay may be set
at an unbalance 11131 w ould result 1 ٦ ا10 % voltage on the remaining elements.
11 managing the protection 0 اa fuseless capacitor bank, the unbalance protection should 101 be reset or
"rebalanced" without first verifying that ااهcapacitor units w ith failed elements have been removed 110111
the bank 3 لreplaced w ith healthy capacitor units. I f the installation 15 10 be rebalanced w ith units having
0٦( ع0٣ 10 ) shorted elements remaining 1٦ service, then the trip fevel should عadjusted downward 50 that
the elements 111 these ﻻ1115do not exceed 11٦٤1٣ capability before operation of the trip relay.
11٦ عtime delay for tripping should be minimized 10 minimize the probability 01 major damage 111 the event
0٤ a major problem 11 the bank. Practical limitations 01٦1 the minimum l i m e include the follow ing:
3) Preventing a bank that is operating in the alarm state from tripping on a system transient
overvoltage.
b) Accounting for the settling time 0 اthe protection 5٧5٤٤1٦٦ 01 initial energization and for the
transient response 0 اcertain capacitor voltage transformers, and 50 on, which may be 3 part of
the unbalance protection system,
c) Preventing smaller banks that do not incorporate system unbalance compensation in the
protection scheme 1101111٣1001110ﻟﺎل٣11103 5٧51٤1٦fault.
Normally a time delay 0 ا0,0 ا5 10 0.05 5 15 adequate 10٣ this coordination. ١٧ith this intentional time delay
11 the trip relay, the additional time required 10٣ 1 عlockout relay and breaker operation may result 11٦ total
clearing times 0 اthe order of 0.1 5. ٨ time 0 ا0. ا5 15reasonably achievable to clear a capacitor bank w ith a
problem, but 11 still may result 111substantial damage. (0٦٤ عparts 0 ا2 capacitor bank Stan 10 become
damaged, funher damage w i l l escalate rapidly. Such escalation w i l l increase the risk of other datuage 11 the
substation. Keeping the clearing time shon 15 important 10 minimizing damage in the event 0 اa fault within
a2
Longer time 02105 are 501112111125 ue0 for uncompensated protection (10 avoid tripping during 4 system
fault that may persist 10٣ a longer period of time), and the risk 0 اmajor damage 111 the hank 15 accepted.
Other users may allow the hank 10 trip 10٣ these conditions 111 order 10 minimize the possibility’ 0٤ hank
damage.
the alarm would he 5 احabove natural errors 50 that it would operate reliably 01 1 عshorting 0 اthe first 0٣
second element. ٦his alarm set point would typically عhalfivay between the signal associated with the
selected number of shorted elements 00 ل11 عsignal associated with 0٦ عfewer shorted elements.
(’,enerally, the most appropriate alarm level 15 the lowest level that can 0 عset without resulting 111 false
alarms from thermal variations 111 capacitance within the bank, practical initial 011* balance, and 50 0.
(The earliest reliable alarm gives maximum opportunity’ 10 repair the capacitor bank during 4 scheduled
outage.) Responding reasonably 10 231٧ alarms 2 لmaintaining 1 عbank 1٦ the best 00551 ﻋﺎطcondition
tend 10 minimize the probability 0 اfurther element failures and forced 0٣ unscheduled outages and 10
maximize the availability 0 اthe bank. False 0٣ unreliable alarms can 0 عcostly, and they reduce the
credibility of the capacitor protection.
11 unbalance protection schemes with ambiguous indication, it 15 desirable 10 use an alarm setting sensitive
10 the 1055 0 ا1 عfirst element 10 avoid any ambiguity. 11115 alarm should seal أ1150 that it should be
manually reset after the removal of the failed capacitorﻻ1011( 5) 11011111 عbank. 11 w ould عundesirable 10
have the alarm 20 44٧ after the 5ا10111110 0ا4 subsequent 212111211 that cancels the unbalance signal.
11٦ عtiming 0 the alarm should be long enough 10 avoid operation during system faults 0٣ temporary’
overvoltages but short enough 111 the case 0٤ ambiguous schemes 10 minimize the probability of 1٧0
compensating fuse operations before the initiation 0٤ the alarm. Usually about 4 105 delay 15 appropriate
tor the alarm.
11٦ عsample calculations 1٦ 8.6.4 provide the information required 10٣ setting the unbalance protection
based 01٦ the following:
11 addition ٤0 providing the necessary information 10٣ protective relay settings, 115 10 ع0 اtabulation gives
3 good feel 10٣ the performance of the bank with varying numbers 0٤ shorted 212112115. Some
manufacturers 0111521055 capacitor banks w ill provide 11151٧0 عof tabulation 10٣ the 015 they propose 0٣
supply.
11 15. 0٤ course, possible 10 combine the calculations of the various columns and 10 calculate 01٧ the
voltage 0٦ the affected elements, the voltage 0٦ the affected unit (which 15 also the voltage 01 1 عparallel
units), and the unbalance signal for 1٦ عty pe 0٤ protection 10 عutilized, because 0 اthe complexity’ of the
configuration (for 2211101. parallel element and series groups 11 a capacitor unit, parallel capacitor units
11 a group, series 210105 111 a string, and parallel strings 11٦ a phase), the resulting equations become
complex.
Figure 39 illustrates 23 generalized wye-connected fuseless capacitor bank. The figure shows two strings 1٦
the left ١٧٧ and one 51٣11011 the right w٧e. 11٦ the calculations of Table 10. the total number 0٤ strings (59)
and the number 0 اstrings 111 the left wye (5/) can be specified. For 2 single-wye bank, 5 ا- 59. ٤0٣ the
calculations, all failures 2٣ عassumed 10 be 11 the leftmost string. This 51٣10215 defined 35 0٦ عstring. اا
other strings have more 0٣ less capacitance than the leftmost string, then they may be specified as fractional
strings. For instance, if the leftmost string 15 made ﻣﻼ0٤ 400 k a r units 211 ل0٦ عof the other strings 15 made
ﻣﻼ0 اthe same number 211 لvoltage rating 0 ا600 ٧3٣ units, the string with the 600 k a r units would be
considered 1.5 51111125 0٣ calculation purposes. 0٣ the example of Figure 39. the bank 15 considered 10
have 10 strings 11 each phase 0٤ the left ٧( عSI) 31 لthree 51111125 in each phase of the bank (5/9). With
such an unbalanced arrangement, the calculations would normally عdone both ١1 اSI - 2 2 ل5/ - 1 10
investigate the effects of failures 111 both wyes.
٩
n
ه
11 11 11 11 11
12
١ل
ارر
I
Note: 11.12 ٨ ل13 arc 11 عappropriate low voltage capacitors, current transformers, voltage transformers, etc.
for ااprotection being ﻻ
11١ عprincipal equation for each calculated value 15 given 11 the second column 0٤ Tahle 10 These
tabulations illustrate the unbalance that 02211151٦ the affected phase of the bank as 2 result of the shorting of
elements 111 one string.
The actual unbalance signal 1 ااdepend on the protection scheme 21110ا0٧ ﻟﻊ10٣ the 21. ٨ 11 عvariety of
protection schemes are in use 0٦ fijseless shunt capacitor 011*5. 11٦2 unbalance signals for usual
connections are given 111 Table 10.
The column headings 11 the tabulations 3٣ عbased 01٦ wye-connected, three-phase capacitor banks. For
delta-connected 0215. the same formulas 31 لtabulation(s) can عused by treating a leg 0٤ the delta as one
phase 0 ا3 grounded ١٧٧ عbank: all formulas are identical. 0٣ a delta bank, the currents shown 35 per-unit-
of-phase current become per-unit-of-leg current (phase current divided ٧). 111 difference current (اﻟﻠﺎوع
٧25) becomes the difference 111 current between two equal delta-connected legs.
Table 10 —Unbalance calculations ٤٥٣٤ ا2 fuseless double wye-connected capacitor bank
i n Figure 39
ل111٤ 0 اshorted c a p a c i t o r e l e m e n t s c
(111 عnumber o f e l e m e n t s that have shorted
f ,111111,> t i t l e F u r m u l a رر11 c o m m e n t ٤ أ1 one string o f e l e m e n t s between phase
00 لneutral.)
ﻟﺎ 1 2 3 4 5
S t r i n g per-unit
0 1.0000 1.0213 10435 1.0667 1.0909 1.1163
capacitance T h e capacitance of the affected string o f capacitor 11115
Cst 1 1.0000 1.0213 1 ( 0 4 3 , 10667 109(09 11163
Affected ٦ أ - ﻋﻴﺚ
capacitance ه ا0000 10106 ا0217 1 0 3 3 3 1 0 4 5 5 1 0 5 8 1
The capacitance o f all s t r i n g s o f capacitors 111 phase 0اا ا1ع
أ
wye that includes the affected string. 10 اا0ا11٦ عstrings
111 that wye except the affected string, the per-unit
capacitance i s SI — 1 . ٤0٣ the affected string, t h e per-unit ا ا0000 10106 10217 1 0 3 3 3 1 0 4 5 5 10581
capacitance i s ا
Voltage 0٦ 1171-17و
affected phase The voltage line 10 neutral 31055 t h e phase that includes
Vln 0 1.0000 1(00(00 1(0000 1 0000 1(0000 1(0000
111 affected string. W i t h useless capacitor banks, the
shorting o f elements increases the capacitance o f that phase
1 لdecreases the voltage across t h e a l t c c t e d phase:
therefore, t h e voltage 15 always less than اper-unit with
shorted elements, except ١111 grounded wye banks. ا 1,(0000 0,9976 00052 0 9 9 2 6 (0 99(01 0 98"’22
N u m b e r of s h o r t e d c a p a c i t o r e l e m e n t s c
( T h e number o f elements that have shorted
1011 11111 tit,،‘ 10 1٠111 11 a n d ٤011111111ع٤ G 111 011 عstring o f elements between phase
and neutral.)
ﻻ 1 2 3 4 5
wye. 11115 e q u a t i o n may عuseful for estimating the
increase 111 voltage 11055 a low-voltage capacitor a t the ا 1.0000 ا.008 و1.016X 1.0257 1 0 3 5 0 10146
neutral 1 لof the affected phase o f the affected wye.
Current 1٦ /9-٤91/7
0 1.0000 1.0071 1 0 1 4 5 1 0 2 2 2 1 0 3 0 3 ا 0388
affected phase
The current 1111٦ عaffected 01105 1115 equation may ع
Jph
useful 10٣ setting protection based on phase current or the
voltage across 2 low 204٤110٣ at the neutral end o f t h e ا 1.0000 10047 1.0096 1.0147 ا0200 10255
affected phase.
Groand ع-(1-7)*(1-9))إ
current ٤11011٤
٤0٣ 105 عwith protective relay schemes utilizing neutral-to 0 0.0000 00071
و 0.0145 00 وو0.0303 (00300
ground current, or ل1 عvoltage 11055 a low-voltage
capacitor 111 the neulral-lo-ground connection.
unaffected wye.]
Difference /٤9-ل-119*()ا Applicable 10 equal wyes only (5م 2 X SI)
current, equal 0
wyes For 2100ﻟﻌﻞ wye-wye banks where lhe difference 111 lhe
neutral cutrent between t h e 10 equal wyes 15 05 لas 3
hi
basis 10 protection. Values are per-unit of total phase ا ل0 اapplicable
current
NOTE ا For Fhg catenations. ا اأ5 convenient to develop 115 equation Eased 01 an install! ااأtime when (ا1 عaffected ptiasc lias
اper-unit voltage and the other two phases have 0,5 per-unit voltage. For this condition, the two unaffected phases ٤311be paralleled.
3 لthe voltage divider between -0,5 pe٢-un,t 3 ل+1 per-unit can be calculated for ﻋﺎاmidpoint voltage, which 15 recorded as 1912
101 ﻗﺎ2 —Calculations above apply 10 both single 31 لdouble wye-connected 3115 double wye-connected banks calculations are
applicable starting 110111 the /١■ value calculation onward.
This subclause covers the 101111 ﻻ1051,01unbalance calculations for unfused capacitor banks ااأﻻط11 the same
way as conventional externally 0٣ internally fused banks (groups of capacitor units in parallel with each
other and the groups connected 111 series from phase 10 neutral 0٣ ground) but with 10 fuses either internally
0٣ externally. These banks are normally of modest 512: therefore, fuses or subdivision of the bank 11110
multiple strings are 110 اrequired 10 limit the 21110٧ 1110 a fault within the 0010.
Capacitor units in unfused capacitor banks 3٣ عsubject 10 overvoltage across elements within a unit ل5
elements become shorted within the unit. The overvoltage 01٦ these remaining elements should be
considered 11 ﻋﺎprotection 0 اunfused capacitor banks. Excessive voltage 01 remaining elements may lead
10 cascading violent failure during system transient overvoltages. 1115 consideration 0٤ excessive voltage
011 retraining element 151٦ addition 10 the usual considerations of 1010122110110٣ externa! arcing within the
hank and avoiding exposure of healthy capacitor units 10 voltages 11 excess 0٤ ا100 % of their rated voltage.
11 an unfused capacitor hank, the unbalance detection gives an indication 0٤ the number 0٤ failed element
groups within one capacitor unit. 11 practice, the actual number of failed 2121112015 throughout the bank can
only ﻋﻂdetermined ط٧ a measurement 0 اall series groups 111a bank. 'This measurement may ﻋﻂ
recommended only when 21 alarm 0٣ relay trip has occurred and may 0٣ may not be a part of the regular
maintenance ﻋﺎﻟﻠﻌﻊ؟
10 calculate the overvoltage 01٦ the remaining element groups 11 a capacitor unit, the number of element
groups 111 each capacitor unit should be specified. Sometimes the manufacturer will provide the number 0ا
elements 11 the series. 52 عthe capacitor unit nameplate or data sheet. ااthe number of series elements per
capacitor unit 15 not available f٠rom the manufacturer, then the number may be estimated. Each element
usually 1135 a nominal voltage capability 0 اbetween 1800 ٧ and 2400 ٧. 1011 ل1110 11 عcapacitor unit
voltage by 2400 and rounding ﻣﻠﺎ10 the next integer will usually give a useable estimate ا0٣ the unbalance
calculations and settings, l o r instance, a 7960 ٧ capacitor unit will probably have about
7960 / 2400 - 3.3. which rounds ﻻ0 10 tour series elements. (1 اmay have five series elements per
capacitor unit, which w 11 make a small difference 111 the overvoltage and unbalance signals. However, the
setting based 011 four series elements w ill 5 اااprovide adequate protection 10٣ a five series element design.)
— The voltage 01 the remaining elements 11 the affected capacitor unit does 10 اexceed ﻋﺎا
maximum recommendedط٧اا1 ع,nanufacturer.
— The voltage 01٦ the healthy capacitors does 101 exceed the contingency overvoltage capability 0٤
the capacitor units (usually ا10 % of rated voltage).
For simplicity, the protection may be set 10 trip 011 the shorting of the first element group.
The number of shorted element groups 10٣ trip and alarm can ﻋﻂdetermined by knowing the voltage 01 the
remaining elements 11٦ the capacitor unit with the shorted element group(s) (10٣ instance, the Ve value
calculated 1 Table )ا ا311 لthe capability 0٤ the capacitor ﻻ1115based 0٦ the information provided by 11٦ع
manufacturer. Based 011 the example calculated 11 Table اI, for capacitor units with 31 element capability
0 1252%. tripping should occur after the 511011110 0 اthe third element group. ٨1 115 point, the voltage 0٦
the remaining elements 15 39ا%.
10 352113111 reliable operation after the shorting 0 اthe third element, the trip level 001 ع لnormally set
midway between the unbalance signal associated w ith 10 operated elements 411 the unbalance signal with
three shorted elements. Alternatively, the trip relay could be set 31an unbalance that would result 11 125%
voltage 01 the remaining 212111215.
If the capacitor unit capability 1510٤ available from the manufacturer, then usually a value of about 125%
01 the stressed eletnenis 15 reasonable 1٤ 3 restrike free switch 0٣ circuit breaker 15 being used 0٣ the
installation 15 being protected with surge arresters at 0٣ below’ 2 per-unit. For 31 energizing transient
voltage 0٤ 2 per-unit, 1 عremaining element 2101105 would عsubjected to a stress 0٤ (2 X 1.25 -) 2.5 per-
unit, w hich should عw ithin the capability' of standard capacitor units.
The alarm would be set above natural errors 50 13 ا11would operate reliably 01 the shorting 0٤ the 11٣5٤
element. 1115 alarm set point would typically be 50% 10 75% of the signal associated w ith one shorted
clement. For unbalance protection schemes w ith ambiguous indication, 1015 alarm should seal 11 50 that 1٤
should ﻋﻂmanually reset after the removal 0٤ the failed capacitor 1110115 110111 the bank. 1٤ would be
undesirable to have the alarm 11111 off after the shorting 0 3 subsequent 21211121 that cancels the unbalance
signal.
T e lime delay tor tripping should be minimized 10 decrease the probability, 0٤ 35 عrupture 0٣ excessive
damage in the event of' an internal capacitor unit t٠ault 10 the case 0٣ an arcing fault i n the capacitor bank.
Practical limitations 01 the minimum time include the following:
a) 10 avoid tripping during 4 nearby 55٤٤111fault (10٣ protection systems sensitive 10 unbalanced
system voltages)
b) 10 401 ل4 bank 1١4 15 operating 111the alarm state 110111tripping 01٦ a system temporary
overvoltage
c) 10 account 10٣ the settling time 0 اthe protection system 0٦ initial energization and 10٣ ﻋﺎا
transient response 0 اcertain capacitor voltage transformers, which may be 3 03٣1 0 ا1ع
unbalance protection system
Normally, a time delay 0 ا0.01 5 10 0.05 5 15 adequate for 1115 coordination. W i t h 115 intentional time delay
11 the trip relay, 1 عadditional time required for the lockout relay 01 لbreaker operation may result 11٦ total
clearing times o f the order of 0.1 5 for a capacitor unit with 411internal fault 0٣ 4 capacitor 00* ١١٠ith 0٦
arcing fault. ٨ time o f 0.1515 reasonably achievable 10 clear 3 capacitor 01* ١11 اa problem اﻟﻣﺎطstill may
result 1٦ substantial damage. Once 03115 0 ا3 capacitor bank start 10 become damaged, further damage ٧1اا
escalate rapidly. Such escalation ٧ اااincrease the [15 اo f major damage and ا1٣ ع11 ل1114٧result 111increased
damage 10 the capacitor bank. Keeping the clearing time short 15 important 10 minimize damage ١vhen a
fault occurs within a bank.
The timing 0ا ا٦ عalarm should 0 عlong enough 10 avoid operation during system faults 0٣ temporary
overvoltages but short enough 11٦ the case 0 اambiguous schemes 10 minimize the probability 0 ا10
20111021015311110 fuse operations before the initiation 0٤ 11٦ alarm. Usually about a 10 s delay 15 000100٣101
for 1 عalarm.
11 managing the 010122110110٤ an unfitsed capacitor bank, 11٦ عunbalance protection should 1001be reset 0٣
“rebalanced" without first assuring that all capacitor units with failed elements have 0221 removed from the
031* and replaced with healthy capacitor 0115.
The sample calculations 1٦ 8.7.4 provide 1ع information required for 52111112 the unbalance protection
based 01٦ the following:
e) Voltage across low-voltage capacitors at the neutral 21110 اeach phase 0٣ 111 the neutral-to-
00 ﻻ111connection 0 اgrounded ١٧ عbanks
0) ٦٦) ا
Delta and single-phase bank protection based 011schemes similar 10 item a) through 1٤٤1
The system o f units used for most of these calculations assumes every normal nonzero voltage, capacitance,
and current 15 اper-unit under normal conditions, ١vith no shorted elements.
1٤ 15. 0٤ course, possible 10 combine the calculations 0 اthe various columns and 10 calculate only the
voltage 0٦ the affected elements, the voltage on the affected unit (which 15 also the voltage 01 1 عparallel
units), and the unbalance signal 10٣ the type 0٤ protection 10 عutilized, because 0 اthe complexity of the
configuration (10٣ example, parallel elements and series groups 11 a capacitor unit, parallel capacitor units
11 a group, series groups 111 4 string, and parallel capacitor units 11 a phase), the resulting equations become
complex.
Table ا اillustrates unbalance calculations for unfused capacitor 015 when elements (element groups) 4٣ع
shorted 11 0 عcapacitor ﻻ1٤ The principal equation for each calculated values 15 given 11 the second
column of Table 11.
The ٣0٧ headings 111 the tabulations are based 01٦ wye-connected, three-phase capacitor banks. For delta-
connected banks, the same formulas and tabulation(s) can be used ا0 اtreating a leg 0 اthe delta as 011 عphase
0 ا4 grounded١٧٧ عbank; all formulas are identical. For لdelta bank, the currents shown as per-unit 0ا-
phase current become per-unil-of-leg current (phase current divided by 3). 1٦ عdifference current (equal
١vyes) becomes the difference 11٦ current between ٤٧0 equal delta-connected legs.
11 11 11 11 11 11
12
١1 اﺣﺎC٥p،KltO٢
ل
( ٧٥ ﻋﺎ1ا. 12 and 13 arcاا١ عappropriate low ١0111 ﻋﻊcapacitors, current transformers, voltage transformers,
etc., for the protection 2100 used.)
Parallel group
per-unit 0 1 . ( 0 0 0 ) 10370 10٩33 I |4)اد 12222 1.3333
1٦ عcapacitance ot٠lhe group of capacitors that includes
capacitance
the affected unit. For all of the units 11 that group اﻣﻊ
t-K the affected unit اا1 عper-unit capacitance is 1. ٤0٣ the
affected 1111 the per-unit capacitance 15 ( ا 1(0000 1037(0 1(0033 ا 1420 1.2222 1.3333
Affected wye
capacitance ده 0 1.10000 10370 ا (0033 1 1120 12222 ا 3333
٤ 11 عper-unit capacitance of the ( phase 01) the wye that
includes the affected capacitor unit. For the series group
including the affected unit, the per-unit capacitance 18
1 1.10010101 0*710 ا (0833 1 1429 ا2222 ا3333
Cg٠ For all other 511٤5 groups, the per-unit capacitance
is 1
Affected per, c ﺗﺜﻴﺜﺚ
0111 phase 0 l.(XMX) 10105 10417 110714 1111 11667
Voltage 01 Vln:\-Vng
affected phase 11 عvoltage line 10 neutral 21055 lire phase that includes 0 1.10000 l.(XXX) I (XXX) ).(XXX) !.(XXX) 1 (XXX)
١٦H the affected unit. With unfused banks,
the shorting of the elements increases the capacitance 0ا
that phase 0 لdecreases the voltage across the affected 1 1 10000 09 930 ( 0 , 9 8 6 3 00767 10,9643 (0.9474
phase: therefore, the numljers arc always less 1113111.
Voltage on ﻋﻧﻣﺈ٠،/آع
affected unit ه : 00010 1 (000(0 I ( X X X , 1 10000 1(000(0 1(0000
١٦٦< The actual per-unit voltage 01 the affected capacitor
umt. based 0 the capacitance division 0 اthe
actual voltage 01 the affected phase (1/7). 1.0000 09939 10,9863 09767 10,9643 09474
Voltage 0٦ Ve = VcirxCu
affected 0 1 10000 1,1111 12500 14286 1,6667 20000
The actual per-unit voltage 01 the remaining elements 111
elements
the affected capacitor unit, based 011 the actual voltage
٦’e ا 1.0000 11(043 1.2329 13053 1.10071 1,8947
01 the affected capacitor unit.
Highest The highest voltage 01 capacitor units 11 the bank, 10
voltage 01٦ multiple-series groups, the capacitors are 11 the same
other umts phase and the per-unit voltage 15 ) 1,10000 1 (000(0 1(0000 11000(0 1,(0000 1(0000
راا 17-ﻟﯿﺪ
For single-series group banks. ٦ عovervoltage 0ا
interest 15 11 the other 1٨0 phases:
I (XXX) 10053 1(0119 1 0202 10*11 10459
1»-0054(ل3:2 41*)
Affected wyc /١٤1/7 0 1.10000 0370 1033 ا 1420 ا 2222 13333
(01ﺗﺎ !—For 1/1 عcalculations. 1٤15 convenient 10 develop this equation based 011311 instant 111 time when the affected phase lias
اper-unit 0 اا3 ﻻال ﻋمthe other ٤٤٥ phases have 05 per-unit voltaic. For this condition, the two unaffected pliases can be
paralleled, and the voltage divider between 05 per-unit and 1 per-unit can ﻋطcalculated lor ا1 عmidpoint voltage, which is
ﻣﻣزازج
recorded as
٢01 ﺗﺎ2 —Calculations above apply 10 both أ1 ﻋﺎ31 لdouble w٦ye-connected banks: double wye-connected banks calculations are
applicable starting from the اvalue calculation onward-
Capacitor unit, ؟used 11 111٤٤٣ banks may be required 10 have more stringent ratings than typical capacitor
units due 10 the harmonics normally present 1٦ the filter 00* environment. 11 these applications, higher
capacitor voltage ratings and fitse current ratings may عrequired. Generally, the additional overloading
specifications 01 the various filter bank components should accommodate 1 ﻋﺎhigher peak voltages and the
increased losses imposed 01 the reactors 211 ل٣251510٣ assemblies. For more details on applications, please
refer to IEEE Std ,531™.
Figure 4 اillustrates 0٦ عpossible primary protection scheme 10٣ 3 solidly grounded-wye connected filter
bank (redundant protection 15 typically applied but 15 not shown 111 figure). ل0٤ عthat the ٤11٠" arrangement
0٤ the four ( وcapacitors results 11 31 equivalent capacitance 0٤ c? and likewise that the ٠11٠" arrangement of
the four Cl capacitors results 11 an equivalent capacitance of (. 111 عreactor اand capacitor c١ are tuned 10
the findamental frequency (/٠٠ typically 50 112 0٣ 60 112) 10 minimize the fundamental frequency losses 11
1٤.
ﺣﻢ
٠٠ ﻣﺾ
( ات15 selected 50 that 15 اseries combination with داحand ﻣﺎtunes 10 the frequency that 15 desired 10ﻋﻂ
filtered.
LCiC:
c<2
Figure 42 shows a similar protection scheme lor an ungrounded-wye connected filler bank.
1٦ عovercurrent finction (50/51) provides Fast 11100111210٣ high-level 5011 circuits near the circuit breaker
terminal. 11٦ 225 0 اlow-magnitude overcunrents, properly coordinated, time-delayed alarm 211 لtripping
signals are initiated due 10 the abnormal conditions 11 the filter bank, special emphasis 15 given 10 the
response 0٤ the overcument relays (50/51) 10 hatmonic cumenls present because some types 0٤ relays
operate 01 peak current measurements and improperﻟﺎ5 عot٠these relays 20iay result 111 undesired operations.
11115 010121101115 redundant 10 the differential (87).
Thermal overload protection 14٧ be implemented using 4 thermal overcurrent relay (49) 111 each phase 0ا
the filter bank. This relay 15 responding 10 root-mean-square (115) current used with thermal analog
modeling and ambient temperature and can عset 10 trip al 115 ﻟﺎع٢٢21 values 0٣ temperature that will
cause damage 10 the reactor. 11١15 sensitive 01012٤ 101115 not achievable with fuses and 15 ,nore sensitive
than a traditional 51 relay.
٨ neutral (51) overcurrent may 0 عused 10 detect ground faults sensitively 11 ﻋﺎsolidly grounded-wye
bank. 11115 relay would operate 011 the residual sum of each phase current (/* - / و+/ي+ /( ). 115 51191
2٣0ﻻ1 لovercurrent relay 15 time-delayed and coordinated ١vith system ground relaying 10 avoid undesired
tripping ا0٣ system ground faults as the grounded-wye filter bank 15 4 path for ground fault current. Il may be
possible 10 supervise ("torque control,) this element with a voltage element that monitors the zero sequence
terminal voltage, 3٧0. System ground faults 111 the vicinity of the filter bank generally produce substantial
3٧0. while little 3٧0 15 produced for slight unbalances 111 ﻋﺎاfilter bank itself. Both phase and ground
overcurent relays provide backup 10 the differential protection. 1 اit 15 determined اﻟﺎاthis phase dilTerential
15110 اsensitive enough for adequate ground fault protection, then 3 restricted earth fault (87٨٢) differential
can be applied. 115 relay compares ﻋﺎاresidual current al the terminals 0 ﻋﺎا اfilter bank 10 the neutral
current. With modem microprocessor relays, this element 15 easily achieved and implemented inside the
three-phase 87 relay shown in Figure 41.
1٦ the ungrounded-wyre filter bank (Figure 42). the potential device connected from the neutral bus 10 the
ground 15 typically a ٧2٣٧ high resistance ل1ل٣ [ ﻟﻌﺎلfor ااﻟﺎاline-ground potential. 1115 scheme delects
the neutral voltage shift resulting 110111 capacitor failures 11 1 عhigh-voltage ((1) 0٣ low-voltage ((0)و
sections 0 اthe filter bank. The 59 لrelay can be compensated with the bus residual voltage (3٧0) 10
accommodate existing 5٧512111 voltage unbalance for improved relay sensitivity, ff not compensated, then
1115 relay must عcoordinated with 1٦ عupstream ground fault relays 50 that 11 0005 not trip during upstream
ground faults. The protection relay should عset 10 detect 1 0٣( وfailures and trip the bank for failed units
11 either capacitor 3.
اا ام
€>01
*طﺑﻌﺎ ي
٢٦
١c٠nr٠il unKiJ.i k،
ﻟﺂﻋﻠﺎﻳﺄ
اا phasr
Ő0,
52
م
Span ت(م
ﺗل ل
I* ll
The 0311101110 resistor R 11٦ each phase 0 اthe 1111٣ hank should also he protected against fundamental and
harmonic overloads. The 511٤ relay shown 11 Figure 4 ا10٣ 115 purpose should respond 10 the true 115
current flowing through the resistor. The time overcurrent curves should provide coordination with the 121
overload capability 0 the resistor.
Fach Filler 15 protected ط٧ an overvoltage relay that serve. ؟10 protect the filler bank against continuous
fundamental Frequency overvoltages as ااع35 against severe overvoltages. The continuous overvoltage
protection should عlime-delayed and coordinated with the system automatic voltage controls.
Severe overvoltages cause excessive stress 0٦ the capacitor units. Peak measuring relays 3٣ عrecommended
For 115 application and should ﻋﻂset 10 coordinate with 1٦ عwithstand capability curves as specified by lhe
capacitor manufacturers. ()vervoltage and overload protection can عprovided using current integration
methods 10 calculate lhe t i e overvoltages imposed 011 ﻋﺎاcapacitor units.
T e high-voltage Ci and low-voltage c? capacitor banks 0 اa typical filter (as shown 1٦ Figure 4 اand
Figure 42) are protected by separate unbalance protection schemes as detailed in Clause 8 oF this guide.
However, many other unbalance protection schemes can be applied 0٦ filter 4105 depending 0٦ the
arrangement 0٤ lhe capacitors and 011 whether lhe system and 41* unbalance compensation Features 4٣ع
needed.
٨1٦01٦٤٣ unbalance protection scheme 15 illustrated in the 51 R and 60 discrete relays shown 11٦ Figure 41
and Figure 42. 111 this case, 4٦ unconventional capacitor unbalance scheme 15 provided by means oF current
measurements 11 the resistor branch or between 1225 oF the high-voltage and low-voltage capacitor banks as
4 result oFcapacitor Failures. Note that the 60 ٣ا4٧ 111 000 C | (Figure 41 ) 15 only sensitive 10 imbalances 11
the الbank 31 لthat lhe 60 11٦ bank c. likewise 15 only sensitive 10 imbalances in 11 و00 *. Also. 1115
protection may require that اﻟﻠﺎلbushing capacitor units be provided 50 that the current through the ٤٧0
1205 can be measured independently.
This unbalance protection scheme should carefully evaluate the effect 01٦ the protection oF 01٦ 1101111ال
55٤111 Frequency as well as deviations 1٦ capacitor values as a Function 0٤ temperature ((JOcfT). In 11115
regard, lhe availability’oFthe filter bank is considerably improved iFcompensation means 3٣ عprovided.
MultiFrequency filter banks are normally applied 11 applications such as high-voltage ﻋﻞconverter stations
where two 0٣ more harmonics are 10 0 عshunted off lhe system. The high-voltage capacitor can عused 10٣
both Frequencies. The low-voltage 5221101٦15 tuned 50 that more than 0٦ عFrequency can عshunted off lhe
5٧5٤٤1٦. Standard protection may be applied 10 the high-voltage and low-voltage sections. Figure 43
illustrates 01٦ ع005510 ﻋﺎ10٣111٦3٣٧
protection scheme For 3 multiFrequency filter bank.
Neutral unbalance protection may be used (59٢). but 1115 important 10 verity ihat lhe relay has a narrow
Fundamental (e.g.. 60 112) Frequency band-pass filter. There may be 3 high level 0 اharmonics present,
which could cause False alarms and trips 1 اthe relay operates on anything other than 1 عFundamental
Frequency. The filter bank likely would ﻋﻂlarge and. therefore, should have 4 compensation circuit 10
handle system unbalance and the inherent unbalance of lhe bank as described for 1 ع59 N fimciion 11 9. ا.2.
1115 1010121101 will detect 2 shorted turn 111 the ٣2210٣5 35 well as failed capacitor units. 01 عthat lhe low-
voltage capacitor shown 11٦ Figure 43 may actually عthe parallel combination of tw o 0٣ more low -voltage
capacitors. 11٦ عhigh-voltage 311 لlow-voltage capacitor banks (( اتand c.) can be protected ﻟﺎ5أ112 an ا1
connection 25 described 111 9. ا.5 (60 relay).
٧ollage differential protection is not recommended For a multi frequency filter bank because 1 عvoltage 15
normally connected from ﻻط ا5 10 ا٦ عground. The low-voltage section makes it difficult 10 balance lhe
1٧0 voltage sources because the voltage change will be different 1 اa high-voltage capacitor unit fails as
compared 10 a low-voltage capacitor unit. 11٦ عvoltage across a section 0 اthe high-voltage 41* may ع
compared 10 the bus voltage, but 2 special voltage transformer would be required 10 accommodate the
required basic impulse level (811).
52
Cl
Voltage 1٢1-1٨1111
-1
11 ا phase!
trigital relays may be influenced ط٧ harmonic distortions i f the predominant orders of, harmonic 05111411005
3٣ عnot predicted. 11٦ عdigital band-pass 111٤٤٣ response provided 11 ا relay may have 4 10١ attenuation
factor at a given harmonic frequency and may cause undesired tripping o f the filter banks.
The expected reliability 0٤ اا1 عrelay protection depends 01 the protection technology used, the design 31ل
manufacturing approaches, and ﻋﺎاenvironment 11 ١vhich ﻋﺎrelays 3٣ عapplied. 10 improve ﻋﺎا
availability 0 اfilter banks, appropriate ل014 and experience related 10 harmonic distortion 5 ﻋﻂ ﻟﺎ ﻟﺎﻫﺎ
considered 11 the selection of the protection scheme.
04
Copyright © 2013 IEEE. ااهrights reserved.
IEEE Sid 337 99-2012
IEEE Guide for ا Protection of Shunt Capacitor Banks
5٧5 3٣ عused 11٦ strategic installations 10 compensate reactive po١ver rapidly for maintaining 21 acceptable
5٧5٤٤11voltage profile and for improving 1٦ عoverall stability 0 اthe poer system. Voltage flicker is also
reduced in industrial applications (such as steel m i l l arc furnaces) when SVCs and harmonic filters are
provided. ٨1 example 0٤ 41٦ 5٧( installation 15 illustrated 11 Figure 44.
ا hkr
Reactors
ا٠١ r ا,11،
ا ؛1■■■ L l C٠-Il<.ir ﻻﺳﺊ
اا II
ا hJttn
'■٠■٠٠■■ I
Protection 0 ا5٧(5 15provided اطa combination o f conventional protective relays and protective 10111005
contained 111the SVC control system (IEEE Power System Relay Committee [1371). These functions 4٣ع
made up 0 اa number 0 ا20٦5 10 اا ﻋﻠﻠﺎ اع٦ عSVC 50٧1ﻣﻊ-ل transformer, low-voltage buses, reactor
branches, capacitor branches, fillers, and thyristors.
This guide applies equally 10 the protection 0 اthe fixed 0٣ thyristor-switched capacitor (TSC) banks
provided as an integral part 0 اan S V C installation. In this regard. Clause 7 and Clause 8 describe various
protection methods that 241 be applied ط٧ conventional relays 10 shunt capacitor banks along with additional
methods illustrated 11٦ Table 12 and Figure 45.
٠ ًﻟﯾﺎ
n
ﻟﻢ
5٧ capacitor 0115 11٦ the 15( mode are provided with air-core reactors connected 1٦ series 10 limit the
inrush generated 1101٦ thyristor switching. The 52192110٦ 3 لsetting of the overcurrent protection should
consider 3 mistire 11 the 15( valve (accounting 10٣11 عmagnitude 3 لtime duration 01 inrush and outrush
currents) and should coordinate ١vith other protective functions provided 11 the controls.
Harmonics 3٣ an important factor 10 consider 11 the protection 0 اcapacitors 11٦ the 15( mode. Adequate
overcurrent and overvoltage protection 1025 211 لsettings should 0 عprovided 10 counter the effect 0٤
harmonics generated ط٧ the thyristor-controlled reactors (T Rs) 2 ﻟﺄ لother unusual hamionic distortion
such 45 those resulting from geomagnetic disturbances (Henmouyal et al. 1831). In this regard, true 115-
based overcurrent relays are required 10 protect the series limiting ٣22210٣5 adequately against overloads,
while peak-measuring voltage relays should be provided ا0٣ the protection of capacitors against
overvoltages (see Table )ا.
Harmonics are produced by the switching elements 0 اSVCs. which may require harmonic filtering. For
instance. 3 six-pulse* phase-controlled reactor unit employs three TCRs connected 11٦ delta. 0 ﻟﻞhamionics
(2.0.. 51ا٦. 711٦. 11th, 0 ل13th) will be injected into the power system during balanced steady-state
conditions.
Il’ filters are required. 1٦ عeffectiveness 0 اsuch filtering depends mainly 01 the 5٧5٤٤111 impedance nomially
referred 10اط٧ an R٠x locus, which 1114٧ detemiine the need lor additional single, 0٣ double-tuned shunt
112٣5. These “؛liters w i l l operate 25 an equivalent shunt capacitor hank generating reactive power at system
frequency. 501 ع0٤ the 010121101 methods discussed 111Clause 7 and Clause 8 3٣ عapplicable 10 5٧ ’؛liter
bank protection. However, as noted 11 9 اand 9.2. the unbalance protection can ع1110٣ عdemanding,
depending 01 1١’؛ عliter configuration (single-frequency tuned 0٣ multifrequency tuned) and the system
voltage 10 which the harmonic ’؛liters 3٣ عconnected.
٨ ااcapacitor switching devices should be applied within their maximum voltage, frequency, 0 لcurrent
ratings, including transient inrush current and frequency. Reference should عmade 10 ﺗﺎﺗﺎ ﺗﺎاStd (37.04.
A N S I (37.06 ﺗﺎﺗﺎﺗﺎا5( ﻻ3.012™, and ﺗﺎﺗﺎﺗﺎاStd C37.66™ ا0٣ rating and application information.
The current 1411112 0 اthe switching device should include the effects 0 اsystem overvoltage (<1100%).
capacitor-unit capacitance tolerance (< ا15%), and system harmonics (<ا ا%00) 10 0٣011 عadequate margins
for most capacitor switching duties.
Curt
Itage, Current
ز٠ا0٨
Figure 46— Opening the circuit to ه single-phase capacitor أ 02 step
٨1٦ important consideration involving application 0 اcircuit breakers 0٣ circuit switchers 10٣ capacitor
switching 15 11٦ عtransient overvoltage that may عgenerated ﻷطrestrikes during the opening operation. ٨1
current zero, the capacitor 15 left charged 10 nearly f t l l p e a k ا1٦ عvoltage. Little recovery voltage appears
across the switching device contacts at this instant, and the capacitance-current arc 15 usually interrupted 2ا
the first current 22٣0 after the switching device contacts open. After interruption, the normal frequency
alternation 0٤ the voltage 01 the source 511 ع0٤ the switching device results 11 a recovery voltage across the
open contacts, 0.5 cycle later, approaching tw ice the peak ا1٦ عvoltage I see Figure 46(a)]. If, a breakdown
were 10 occur at 90٥ as shown 1٦٦ Figure 46()ط, the capacitor voltage immediately attempts 10 equalize with
the system voltage. The circuit 15 oscillatory’. ٨1 the first peak 0 اthe transient, the 2102110٣ voltage w ill,
depending 01 0011101102. overshoot by an amount approaching the ditTerence between the two voltages
immediately 10٣10٣10 the restrike. 11115 high transient overvoltage 1113٧ damage equipment. If,1 عcurrent 15
interrupted at 11٦ عfirst high-frequency current zero, then 11 عtransient voltage peak 15 trapped 01111٦ع
capacitor bank. The recovery' voltage reaches a value greater than that Following 11 عfirst interruption.
However, the contacts have moved Farther 40311 and٤ا1 عbuildup of, dielectric may prevent additional
restrikes.
1 ا11 عgap between the open contacts breaks ل0٧٦ 1255 than 0.25 cycles after current 2210. then the
amplitude oF the voltage oscillation will not exceed the normal transient voltage that occurs when the bank
15 first energized. The breakdow n 15 defined as reignition rather than as 4 restrike.
11 Figure 46(b), the restrike 15 shown 10 occur 2 ااﻟﺎ0.5 cycle after current interruption. This condition 15
the worst possibility 10٣ the first restrike because ا1 عrecovery voltage has reached 115 maximum 3 لthe
resultant surge voltage can, theoretically, reach three times normal line-to-ground crest voltage. 111 actual
practice, 11seldom exceeds 2.5 times normal Additional restrikes can produce higher crest voltages, and
the sudden voltage changes and high-frequency oscillations may produce other relatively higher voltages
elsewhere 01 1 عsystem. Therefore, 10 protect the entire system, it 15 desirable to limit restrikes and ﻋﺎ
voltage phenomena resulting 1101٦1 them.
Under special circuit arrangements, 11 may ع0055101 ع10٣some switching devices 10 interrupt the transient
current caused by 3 prestrikc w hen energizing 3 capacitor bank. Overvoltages may result w hen 1٦ عcontacts
close after 31 interruption of the transient current. The resulting transient can produce overvoltages.
11 4 station where large capacitor banks 4٣ عconnected 10 4 common bus, 11 may عprudent 10 verify that the
transient capacitor discharge current 1110 3 nearby fault docs 10٤ exceed the capability 0 ا3٧ circuit
breakers ٥٣ circuit sw itchers connected to 11 عbus.
where
ددا1.33
11 addition to involving the contact capability, the transient inrush current through 1 switching device may
also cause secondary flashover 0 bushing current transformers (8(15). The voltage developed 11 the
secondary circuit 15 proportional to the frequency and magnitude 0 اthe 1٣31٤1٦؟٦٤ inrush current:
V B C T ، ( / p i ، / B C T R ) * (4) * (/٢//)
where
101ﺗﺎ11١ عcurrent transformer burden reactance 15 the sum of the reactances ٥ ﻧﺎ اcurrent transformer, the leads,
211 لthe relay,
111 عswitching equipment manufacturer should be consulted if the /// ال0٣ crest values of the inrush current
exceed the limits specified 11 Table 1 ٨ through Table 3٨ 0 ا٨ل5( ا2000-37.06.
10.2 I n r u s h control d e v i c e s
Energizing a capacitor bank ١11 اresult 11 a transient inrush current. The magnitude and frequency 0٤ 11115
inrush current are 2 function 0٤ the applied voltage (point 011 the voltage wave 3 اclosing), the capacitance
0٤ the circuit, the inductance 0٤ the circuit, the initial charge of the capacitor bank at the instant of closing,
3 لthe damping 011 عcircuit due 10 closing resistors or other resistance 11 ا1 عcircuit. See Annex 10 for
inrush current calculations.
The transient inrush current 10 a single isolated bank 15155 13٦ the available short-circuit current at the
capacitor location. Because a switching device should meet the momentary current requirement 0٤ ﻋﺎ
5٧5٤٤11٦. transient inrush current 15 not 3 limiting factor 11 applying switching devices on isolated capacitor
banks. However, 1115 important 10 check the momentary’ rating of other sw itching devices not intended for
fault current interruption.
When capacitor 0115 arc sw itched back 10 back (that 15. 011 ع0٣ more energized w hen another is connected
10 the same 115). transient currents of high magnitude and high frequency 1113٧110١٧ betw een the banks 0٦
closing of the switching device or 11 1 عevent of a restrike 01 opening. 11٦ عoscillatory current 15 limited
only by the impedance 0 اthe capacitor banks and the circuit between them, and the peak inrush may be
much higher than the peak 0 the available short-circuit current at the bus. The transient current usually
decays 10 zero 11 a fraction 0 اa cycle 0 اthe power frequency. 11٦ عcomponent supplied ط٧ the 00١٧٤٣
source 15 usually 50 small it may عneglected.
The magnitude 0٤ inrush current 0 ل115subsequent cfTccts10 3 sw itched capacitor 030 may ﻋﻂgreatly
reduced by use 0 اinrush-currcnt-limiting reactors. ٨ capacitor sw itching device furnished with preinsertion
resistors 0٣ inductors or 3 sw'itch that uses zero-crossing controls minimizes the sw itching inrush transient,
but 11 does 10 اhelp the outrush transient for close 111100115. When used for daily sw itching of back-to-back
capacitor banks, the ا1 ﻋﺎ0 اthe sw itching device contacts can عextended by increasing the inductance
between 005 طadding 11 currcnt-limiting reactors. 1he reactors will also reduce the outrush currents
(see IEEE Std (57.1 61٩)ا. Evaluate the effect 0 اthe outrush 01 the components that w ill be affected before
adding 3 reactor.
Capacitor 21* installations using series reactors 10 control back-to-back capacitor bank switching
transients 3٣ عpotentially subject to capacitor terminal faults 35 well 35 faults between the capacitor bank
and 115 series reactor that 113 عproblematic 10 clear due 10 the excessive rate of [15 ع0٤ 1131151211٤recovery
voltage (11٤1٤٧) across the capacitor breaker contacts. See 6. 1 for discussions 01 the use 0٤ current-limiting
reactors. Refer to 11 عIEEE Std 1036 for more information.
00
Copyright © 2013 IEEE. ااه 19ا8 reserved
IEEE Std C37.99-2012
ﻋﻌﻌﺎGuide for ااProtection of Shunt Capacitor Banks
The 10211011121101٦ of inrush 10 a single switched shunt capacitor bank 211ل10 a 01* switched bac* 10 back
١11 اa parallel energized 0011* 0٣ banks 15 discussed 16.1.1113 given application, the 11112115 and 0112225
associated with inrush 10 a capacitor bank may precipitate undesirable resonant effects with other parts of
the 5٧5٤٤1٦. induce hazardous surges 11 51311011 control cable, and interfere w ith communication facilities in
the area,
(losing resistors 0٣ inductors 01 the 311* switching device, 0٣ current-limiting reactors installed 1٦ series
١1ا a switched capacitor ban*, اااserve 10 alter the frequency of the inrush transients and reduce the
magnitude 0٤ the transients. ٦he reactors applied should have a sufficiently high ا81 اrating 50 that 2405 0٣
surge arresters required for reactor protection will not short out the ٣2410٣5 during energization 0 اthe
capacitor 01. Synchronous 0٣ zero voltage closing of the switched 01* can also reduce the severity 0ا
the switching transients (see 6. ) ا.
In bac*-t0-back sw itching applications, the addition of even 4 minimal amount of inductance between
banks w ill significantly reduce the magnitude of inrush currents flow ing from 1٦ عenergized bank(s) 10 1٦ع
bank being energized.
(؛rounded wye shunt capacitor banks (as well 45 other substation equipment capable 0 اgenerating 0٣
transmitting high-frequency transients 10 the ground 11131) should 0 عinstalled 05 far away as practical from
the control building 30 لcable trenches.
1 ightning surges and the switching 0 اcapacitors can result 11 significant system overvoltages. The ability
0 اthe surge arrester 10 dissipate energy' that results during capacitor switching operations 15 0 اparticular
importance 10 assure proper surge arrester 512٤110. Restrikes 0٤ the capacitor bank switching device
generally cause the highest transient overvoltages, particularly ا0٣ isolated banks. Significant transient
overvoltages 31 also occur at the capacitor bank due 10 surge magnification of resonant circuits 01 the
power 5٧51211٦ associated with switching 0 ا4 remote capacitor bank, cable, 0٣ transmission line. Metal,
01 ﻋﻞsurge arresters are generally better than silicon-carbide surge arresters because they usually have 3
higher energy duty 10٣1 same airester rating and typically absorb less energy per transient event.
Refer 10 1٦ عsurge arrester application guides 1٦ IEEE Std C62.21١| (10٣ 02 مsilicon carbide surge arresters)
and IEEE Std £62.22™ (10٣ metal 011 عsurge arresters) 10٣ fitrther information 0٦٦surge arrester
application.
1٤ a voltage transformer capacitor-coupled voltage transformer, or potential device connected 110111 the
bank neutral 10 ground 15 used for unbalance detection, then it should be capable 0٤ w ithstanding sw itching
surge 011005 010.5 10 2.5 times system phase-to-neutral voltage w ithout malfunction (Hamer 311( ل0٧21
[136]). ٨ اhigher system voltages, higher 14110 voltage transformers are required. The use of these higher
ratio voltage transformers can make the neutral voltage unbalance detection methods become insensitive.
٧ عrequired (52 عClause 8).
Special relaying techniques 1114
٨ reasonably conservative voltage rating 10٣ the neutral wound primary current transformer to withstand
the 511٣22 voltages appearing at the bank neutral 15 0,2 1111125 the system line-to-line voltage (Harder |B5]).
However w indow-type current transformers rated 0.1 0٤ system voltage (even 600 ٧ rated (15) have been
2010112 لwithout trouble, 01 small banks, these curtent transformers are often 01111 ل0٣11110٣٧types with
١0٦ ratios, during switching, 1 عbank neutral transient voltage rise can stress the insulation across the
current transformer's wound primary, 11can 050 اstress the insulation between the case (which 15 usually
grounded 10 3 local 51100011structure) and the secondary winding due 10 the fact that the secondary neutral
15 usually grounded at the remote end (that 15. at the relay location) 10٣ 541٤٧ reasons. Although the voltage
stress between 1 ﻋﺎgrounded case and the secondary winding could ﻋﻂeliminated by grounding the
secondary circuit at the current transformer location, this alternative 15 not recommended, 10 do 50 would
impress the bank transient potential rise 01 the secondary cable and present hazardous voltages at 1 عrelay
location, Refer 10 IEEE 51( ل57.13.3 for more information, (ienerally, the secondary winding can
withstand these short-duration transients without difficulty, ٨150. coupling of this transient voltage 10 the
secondary cable can 0 عgreatly reduced by routing the cable closely parallel 10 the primary ground
conductor down 10 the ground mat and 111211 closely paralleling the ground mat conductors en route 10 the
relay location. 111 special instances where excessive neutral transient voltages are encountered, 1 اmay be
necessary 10 insulate 11٦ عtransformer case 11011 the local ground 10 allo١v connection 0٤ 011 ع51 ﻋﻞ0٤ the
secondary winding 10 the transformer case, 11115 approach ٧1 ااeliminate the stress between the secondary
11 ل1112and the 0٣ عand will increase the stress between 11٦ عprimary winding and 1 عcore. However, the
primary insulation ٤3٦ generally عexpected 10 be more robust 11131 the secondary insulation.
10 protect the primary w inding insulation 013 wound primary current transformer, it 15 common practice 10
install a 10 لgap 0٤ 1.2 1٦٦11110 1.6 1٦٦1٦1 connected directly 2210551٦ عprimary terminals (Harder [1351).11115
arrangement 1 ااlimit the voltage impressed 221055 the winding and prevent primary tum-10-tum
breakdown, ٨ high-energy, gas-tilled protector tube or low-voltage surge arrester (varistor) should be
connected across the secondary terminals 10 protect the secondary ٧10 ل100 from tum-10-tum breakdown.
(Eailurc of an inadequately rated varistor 15 likely 10 short-circuit the current transformer 0 لcause the
unbalance protection 10 be inoperative.) 11115 device should عinsulated from local ground, again 10 avoid
impressing the bank transient potential 01 the secondary circuit. The surge arrester should عchosen 10
limit the current transformer secondary voltage 10 coordinate with the secondary circuit insulation voltage
rating.
Nonsimultaneous 1113110 and 1231110 1111105 of the three poles 0٤ the capacitor bank switching device may
3110٧ ftdl phase current 10 flow,11 the neutral current transformer and relay during the sw itching time. 11115
current can flow' for 31 indefinitely long period 0 اtime 110 ع0٣ two 00105 0 ا11٦ عbank switching device fail
10 operate. 10٣ 11115 reason, 11 may be desirable 10 select 3 neutral current transformer that can 2201111110101
this current without damage or malftnction. ٤0٣ more information 01 surge protection 0 current
transformers, see 10.6.1.
11 15 ١ ااعdocumented that the switching 0 اcapacitive currents produces transients that are markedly
different 1101111105 عproduced اطother power system switching operations (Greenwood et al. 1341). For
capacitor bank switching, the difterences 3٣ عas follow s:
1٤ preinsertion inductors are utilized, then 023* transient currents are generally 1255 than 3000 ٨. The
oscillatot-y frequency 15 01 the order 0٤ several hundred hertz, ٦he maximum /// ال15. therefore. 1255 than
10 ٨/45, One source (Abdulrahim et al, 18 ا1) 135 pointed out that additional ver high-frequency switching
transients 0٤ several megahertz (due 10 traveling waves 011 the capacitor 001 *اbus) w 110150 be produced
211 لsuperimposed 01 the transients already described, 11115 transient 15 similar, 1 ا1101identical. 10 the
transients generated by switching a length 0٤ high-voltage bus w ith 2 disconnect sw itch.
Te rate 0 اchange of the current (///) 15 a usefol indicator of the potential for inducing interterence 11
nearby control circuits. Although switching with preinsertion resistors reduces the peak current and
eliminates the oscillation, it 0095 110٤ reduce 11 عinitial 0// ل/. 11115 131 عof change 15 determined only by the
voltage across the sw itch before closing and the circuit-loop inductance:
dlldrVIL
Surge 0101221101 techniques for capacitor bank applications should take 1110 consideration the different
character 0 ا11 عtransient currents produced during bank switching (higher 023* currents 21 لlower
oscillation frequencies) 11131 are experienced with other pow er system switching operations.
11٦ عcirculating paths 0 اthe transient currents are 050 اimportant. These currents low' 11110 11٦ عcapacitor
31* buses, 00 ground connections, 0 لcapacitor bank ground grid, For some conditions, the currents
3150 flow 1110 the bus interconnections between the 111311 switching station 3 لthe capacitor bank, as ٧ع11
as 1110 the main station buses and ground grid. 10 ﻋﻠﺎ10 the combination of high cunent and high frequency,
significant transient potential differences can appear across 001110٦5 0 اthe ground 0[1 ﻋﻠﻤﺎل ل10 the grid
inductance. The currents 3٣ ع0150 accompanied by strong high-frequency magnetic fields. Therefore,
control cables 111 these areas are prone 10 inductive interference and require careful 41120110110 routing,
shielding, and grounding.
When the transient currents produced during capacitor 0011* switching pass through 11٦ عprimary 0 اthe
current transformer 115 secondary circuit can experience a large transverse-mode interference voltage. 1115
not induced through 5113٧ coupling but by the normal transformer action of the current transformer. 11115
can present 3 serious problem 10٣ both 11٦ عcurrent transformer and the equipment and instruments that
make ﻣﻠﺎ115secondary' burden, such as protective relays and data transducers. The reactance of the burden
components الthese frequencies can be more than 100 times their 60 112 values. ٨5 a consequence, high-
frequency transient currents, which can عa few hundred amperes, can produce extremely high voltages
across inductive burdens.
The suggestion 15 sometimes made that current transformer saturation w ill prevent the production of such
high secondary 0110025 1٦15 suggestion 1510 اtrue for this situation, how ever. The secondary' volt-second
product 10٣ each half cycle 0٤ the high-frequency oscillation 15 small compared 10 that required 10 produce
current transformer core saturation 3 ا60 112. Therefore, voltage limiting ط٧ current transformer saturation
15 not likely to occur.
Overvoltage protection of the current transformer secondaiy circuit 15 thus required 10 prevent damage 10
the current transformer w inding and the connected burdens, 115 protection usually takes the form 0٤ high-
current-rated varistors 0٣ spark 2205 connected directly across the current transformer secondaiy terminals.
1٤the current transformer 1135 a w ound primary, then 3 gap 0٣ a surge arrester 1113٧ 2150 be needed across the
primary (l a d e r |B5|). ٧aristors applied 10 the secondary’ should be selected ١111 a sufficient energy’-
absorbing rating 10 withstand the 52201110 current oscillations (52 ع10.5). Also, 10 maintain voltage-
limiting action, the varistor 512 عshould عselected 50 that the peak current 4005 not drive 11 422 م1110the
voltage tum-up region on the varistor’s ٧/1 curve. Figure 47 illustrates this 0011. Manufacturers 0٤
varistors can supply ٧/ اcharacteristic ٤1105 suitable for checking 115 condition.
اا اااا
Amperes
10 2 degree, the secondary’ high-voltage problem can be minimized ٧ selecting the current transformer
ratio and burden 10 reduce the level of 11٦ عsecondary’ current‘ ٨150.eliminating inductive components 11 the
secondary’ burden ٧1 ااreduce the secondary* voltage. Solid-state 1213٧5 3٣ particularly beneficial 111 this
respect because their current burdens are lo١v and essentially resistive.
The 1012201102 discussion 15 best illustrated by a numerical example. Figure 48 shows 2 one-line diagram
for a 230 ٤٧station 1ا a shunt capacitor bank. 11٦ عbank 15 rated 40 000 kar and ١٧ع 15 connected 1ﻻ٦
2 grounded neutral. 11 the figure, the line circuit breakers have 1200/5 ratio current transformers, and the
capacitor bank 15 111service ٧ 11211 a phase-to-ground fault occurs 01 ٦ ا1٦ 3 just outside the station. The
distance along the 230 ٤٧circuit 110111 the capacitor bank 10 the fault 15 about 150 1.
t i n e 41 ■ ا٦< 2 ﻋﺎرا4 3
ﺻﺻﻠﺻص
ﺻﺻﻠﺻص
Capacitor Bank
40 MV٨٠ O k V
(110ﻟﻠﻞ Wye
وا
اﺣﺟم
23(1 k V
(ﺻﺻن
(ﺻﺻن
،III *1
٤1
ﻻو٣2 48 — One-line diagram ٥٢230 kV station w i t h 2 shunt capacitor bank
Upon occurrence of the fault, the capacitor bank discharges through the bus-ground loop inductance, which
15 about 350 1411. Because there 15 little resistance 111 the loop. ﻋﺎcurrent 15 oscillatory. The frequency 0ا
1 عoscillation depends 011 the loop inductance and 01 1٦ عbank capacitance. The capacitance of the bank
can 0 found 110111115 voltage rating and its power frequency kilovar rating:
1
c٠ : 2.65xkvar> I
٠٨»«اا ﻟﻌﺂ
(,=2.0 ﺗﻼ
/ ا اي،
1٢011-111 عcapacitance 1511 microfarads (111) and the inductance 15 111 microhenries (1111).
/-6105 ا12
ا-4ﺳﺴﻠﻞ٠ر|ﻟﻢ
٤--»2«2 ٨
= 59.1 A ده6015 Hz
11٦ عcurrent transformer secondary burden impedance, at 60 Hz, 15 1 +1 زQ، ٨ ا6015 Hz, the burden
impedance 15 about ا0 ,,100 ﯾﻊ, 1٦م ع23* magnitude 0 ا1٦ عoscillatory voltage transient across the
ل3٣٧ 0٤ the current transformer 15 then:
522011
= 0(591*(1141591 *(100)]
= 5910 V @ 60,5 Hz
1115 voltage 15 100 much 10 allow across the relay and instrument burdens 0٣ the current transformer
secondary' winding insulation. Some 11123٦510 clamp 0٣ limit the voltage 10 3 lo١ver amount 15 required,
such as a spark 03 م0٣ high-current varistor. Protective relays operating 1101٦ these current transformers 0٣
from the bank-tie current transformers should also have 3 filter 10 exclude the 6 kHz discharge current
calculated previously 0٣ be designed 10 ignore its presence.
The peak voltage, peak current, and frequency produced 111 3 21٧٤1٦ installation will vary 110111٤115 example
depending 01 the bank capacitance, current transformer ratios, 5٧51211 voltage, and burden impedance.
Voltage signal sources of various 105 are used 11 capacitor bank protection schemes 10 detect abnormal
conditions 11 the bank. Because they are located close 10 the capacitor bank, these devices can be directly
200 52 ل10 the transients 0٣ surges produced during capacitor bank switching. Surge 0101921101 0٤ these
devices 15 mainly 10 prevent overstress 111 the primary-to-secondary insulation and the secondary-to-ground
(case) insulation by the transient ground potential differences produced 11٦ the bank area during switching,
٨ peninsula 010
ا11ل1012arrangement 10٣ the capacitor bank (along with proper control cable shielding,
grounding, and routing) provides better surge protection for 2 عvoltage signal sources than the single-point
grounding scheme. The higher cost of peninsular grounding may be justified ا0٣ large ﺗﺎ11٧ capacitor bank
installations.
١Vith the single-point grounding arrangement, the 01 neutral transient potential will be about 0.25 that 01
the capacitor bank bus (20 kV 10 60 kV 0٣ higher). 111 this case, a voltage transformer connected 10 measure
the capacitor bank voltage, bus 10 neutral, would need 10 be 4 10-0115 11112 design 50 the case could be
safely grounded 10 the station ground grid (refer 10 6.1).
Use 0٤ a single bushing transformer, with the case (primary ground) connected 10 the 0210* neutral, would
impress the neutral transient voltage between the case 2 ل11 عsecondary* winding, ١٧1111115 grounded
through 1 control cable at the relay location. Failure 0٤ the secondary winding insulation would ع4
511011٤ 0055111ا٧. Figure 49 and Figure 50 illustrate the situation.
ا ا
Sciimibn
Suliim (irvunit
(’jpaciuiBank
٤ Two ا ا \'T
ﺗﻜﻠﺎﻣﻨﺎ
ﻟﺎس
٠س
Hank \cii٢٢.r٠l
1 ا
('onnatcdtc
ا Elution (iwund
Single ٢ﻟﺎ
ا
،ا٢«,ﺳﺎ
ي Station ،,round
(021110 ال1110 ا-01130 عand El IV 111301اع1 عvoltage transformer often have primary winding 5ااع-
resonant frequencies 11 the range 0 ا500 اlz 10 2000 ا12. If the bank switching frequency coincides w ith this
self٠rcsonance. then the capacitor 00 transient may ﻋﻂstrongly amplified 111 the voltage transformer
output voltage. There 15 probably little risk of damage 10 the voltage transformer, اﻟﺎطthe operation 0 اrelays
and controls connected 10 ﻋﺎاvoltage transformer may ﻋﻂadversely a fleeted. ٨ resistor 11 series 0٣ parallel
with the secondary of the transformer can ﻋﻂused 10 dampen the oscillation. The resistor value should ﻋﻂ
such that 11 does not influence the signal level 10 the rclay.
Finally, االtypes 0 اvoltage transducers, voltage transformers, capacitor-coupled voltage transformers, and
resistance potential devices ٤3٦. with some 1055 11٦ fidelity, reproduce the capacitor bank switching transient
voltage. 1٤ will appear 11 the transverse mode 4 the output terminals 0٤ the device. 1115 011422. 100. may
affect the operation of relay 55121115.
11 25 already 221 mentioned 13 اcapacitor 21* switching produces the same megahertz transients that
occur 11٦ other high-voltage switching operations, as ااعas 15 اcharacteristic high-energy kilohertz
transients. Protective relay systems for capacitor bank applications should have incorporated 11 1٦٤1٣ design
surge protection 12 ا15effective for both types of interference.
Experience has 5٦٥١٨1 that interference 11 control circuits caused by high-voltage switching operations 15
always stronger 11111٦ عcommon mode than in 1٦ عtransverse mode. Surge protection techniques have been
directed mostly toward reducing the 011111001 mode. Some 0 اthese techniques (such 25 control cable
routing, cable shielding 211 ل210ا1ل111. and isolation), which 3٣ عhighly effective at megahertz frequencies,
are 2150 effective against 1 ع11012112common mode interference due to capacitor bank sw itching 3 لare,
therefore, recommended for such installations.
On ﻟﺎ٦ عother 31 ل. the surge filters [for example, passive electromagnetic interference filters] used in ﻋﺎا
inputs 10 relay systems, although highly effective at megahertz frequencies, are ineffective against capacitor
bank switching transients 11 the kilohertz frequency range. Passive kilohertz surge filters for relay input
circuits would require much larger inductors and capacitors, w hich could present severe loading problems
for current transformers and voltage transformers. Such filters are often not practical.
11 capacitor bank switching, the kilohertz interference 111 the s٠ econdary circuits 15 511011225111٦ the
transverse mode because. 3 ىalready described, 1٤ 15 coupled 10 the secondary circuits of, current
transf'ormers and voltage transformers by the normal transformer action of 1105 عdevices. Recause it 15 not
practical ٤0 use passive kilohertz filters 11 1 عcurrent transformer and voltage transformer secondary ac
relay input circuits, the required filtering action should be achieved by other means. 011 عapproach 1510
design active filters 35 an integral 031 of the relay analog signal processing circuits.
Finally, all 2 ع111 اﻟﺎمconnections 10 ﻋﺎrelay system should be protected 20311151 overvoltages by using
varistors 0٣ spark 2205.
IEEE 5 ﻟﺎ525’١٠ provides guidance 011 routing 01’ control cables. ﺗﺎﺗﺎ ﺗﺎاStd ا ا43آ١ اprovides guidance 01
shielding of low-voltage cables. 11٦ عfolloving information is extracted ا10111these guides.
٨ ااcontrol cable duct runs, cable trenches, 0٣ direct [ﻟﺎط1 ﻟﻦcontrol cables 00 اspecifically associated with
capacitor controls or protection should be removed 110111 the iminediate area around the capacitor bank.
This step 15 10 avoid induction of surges 1110 relaying systems or possible control cable failure during
capacitor 001 switching.
The routing 0 اcontrol cables 1’rom neutral current transformers 0٣ voltage transformers should عkept al
right angles with respect 10 the common neutral for single-point grounding 41 لin parallel with اا٦ ﻋﺎا عto the
substation ground for peninsular grounding 10 minimize induction. These induced voltages can also ﻋﻂ
minimized by shielding the cables and using a radial configuration 10٣ circuits (circuits completely
contained within 01٦ عcable 50 that inductive loops are not formed),
Control cables entering 1٦ عcapacitor bank area should عkept 05 close 35 0055101 ع10 the ground 0111
conductors (that 15.144/0 AWG copper minimum) 11 1٦ عcable trench, or 01 10 مof the duct run, 0٣ alongside
a ground grid conductor if direct buried. 11115 grounding arrangement 15 mandatory if a peninsula ground 15
used. Multiple conol cable shield grounds 3٣ عrecommended: 0 ٦ ع21the cable termination 11٦ the capacitor
area, another where the cable enters the main cable trench or duct run, 001 another where the cable enters
the control house, 0٣ at the final termination 0٦ the relay panel. ٨ ااspare 0٣ unused conductors 0 اcontrol
cables should be grounded at least at one end.
The induced voltages [011111101 mode (between a signal pair and ground) 31 لtransverse mode (between the
signal wires)] will be affected 0٧ the 30 اconstruction (10٣ example, shielded twisted pairs 0٣ random lay
w ithout shielding) and by w hether 1٦ shields and unused conductors are grounded. 1٦ عouter shield should
normally be grounded at both ends 10 reduce the common and transverse induced voltage.
If 1 ع503٣ عconductors and internal shields are grounded at both ends, then the induced common mode
voltage 1 ع ااreduced, but the induced transverse mode voltage can be increased due 10 1 عcurrent flow'
through the spare conductors coupling 10 1٦ عother cable conductors.
11.1 Resonance
٨ shunt capacitor bank forms 4 resonant circuit with 5512111 inductive elements. The natural resonant
frequency may be excited while sw itching a remote capacitor bank and give rise 10 excessive 0110025 ﻟﺎل
currents and the possible failure 0 اequipment such as other capacitors, surge arresters, instrument
transformers, and 10505. These undesirable resonant effects are more likely 10 occur if the capacitor bank
switching device 135 a long arcing time and multiple restrike characteristics.
The natural resonant frequency 0٤2 single-capacitance shunt capacitor bank (10 a ؛liter bank) 15 simply
related 10 the inductance of the system 211 لthe capacitance of the bank:
/ ﺻﺪ
11١1515 ﻋﺎاfrequency الwhich the magnitude of the system inductive reactance equals that of the capacitive
reactance 0 ﻋﻠﺎ اbank presenting 1 lo١v-impcdance ﻟﺎﻟﻢfor current llow at اﻟﺎfrequency. ﻋﺎا اا
fundamental frequency 0 ﻋﺎا اpower system is /o١then the resonant frequency can ﻋﻂexpressed 45:
( ٥: ٧٦ (" ت1)0
ÜO٧LC
(.arrying this birther, 31٦1 expression for the harmonic resonance 0٤ 4 particular capacitor 00* in ٤٤11105 0٤ its
512 عand the short-circuit capacity of the system can be developed 45 101105:
Neglecting resistance, 1٦ عimpedance can be approximated 10 the reactance: 2( ( ح and ZSYS حXL:
”| ١ n | :ج
So, 4 50 mvar shunt, single-capacitance 0011 applied 10 a power system bus w ith 1350 mva of short circuit
ط1 ﻋﻂااز عtuned near 1 عfifth harmonic:
00110
«-28-53
٥/٠rise ي ﺗﻚ
11 15 interesting 10 note that 115 equation can عrelated 10 the equation 10٣ the percentage voltage ٣15ع
produced by the capacitor bank as well:
٧ 50 - ٧%risc
What 115 111201511 practical terms 15 that 4 single-capacitance shunt bank installed 11 the power system 10
produce 2 2% voltage rise would naturally عresonant near the seventh harmonic. Likewise, 2 4% 15ع
would tune near the 111 اharmonic. Refer 10 Figure 5 ا٤0٣ a plot of the harmonic number against the
percentage voltage rise.
ةةة0ةه0ةةةة0
<٥٠ ب
H a r n o i c Number
؟١٠١ه؟ ﻫﺞ
٠ ج دب ﻫﺞ د
3.75%
4.75%
3.250%
3.500%
5.250%
5.500%
2.750%
5.000%
4.250%
4.500%
2.000%
2.500%
1 25%
4.0%
6.0%
1.00%
1.75%
1.50%
3.00%
5.75%
2.25%
11.2 Harmonics
The capacitor bank may also resonate with harmonic currents produced elsewhere, such 35 remote loads.
The use 0٤ thyristors 11 industry ٤0 derive variable potential ﻋﻞ101٦ an ac source 15 extensive and growing.
Such phase-controlled thyristors generate harmonics, particularly third, fifth, seventh, 3 لeleventh. More
instances 0٤ parallel resonance are occurring due to this cause. Some examples 0٤ hannonic series
resonance with utilities, due 10 adjacent utility loads, have ط221 noted. These resonant circuits also include
utility distribution circuits 1 ﻻcapacitors that supply medium-voltage industrial 3 لcommercial loads. 11٦
most instances, some form of harmonic voltage 3 لhighharmonic capacitor currents 3٣ عinvolved.
Capacitors rated 10٣ higher voltage may ع ا5( ﻟﻊSteepes and Stratford [8121: Miller [Bll];
McCauley et al. ا891).
٨٣ عfurnaces, 11 the 111 part 0 اtheir cycle, produce 4 similar array 0٤ troublesome harmonics, including
even-ordered harmonics. While the large lumaces are connected 10 51111 high-vollage sources, small
installations 011 distribution circuits nevertheless produce the same effect.
Another objection 10 harmonics 1٦ the po١ver system 15 the noise interference produced 111 communications
circuits. ٧01 عfrequency noise interference comes primarily from the residual 0٣ zero-sequence currents
that are odd multiples 0 اthe third (the ninth and fifteenth harmonic 0 اthe fundamental frequency),
(rounded capacitor banks provide a 10٧ impedance path 10٣12 5 عcurrents 10 flow.
The measure 0 اthe capability of a power circuit 10 act as a noise source 15 the telephone influence factor
(IEEE 511 469 r١’). Before attempting 10 apply corrective measures 10 3 capacitor bank that 15 suspected 01
causing interference, the source of the noise should he located. The 95٤ corrective measures are usually
applied at the source, if corrections should be made at the capacitor 01. then modifications to change the
resonant frequency can be made.
Before energizing power equipment, there are the usual pre-commissioning checks 10٣ instrument
transformer ratio, polarity, and excitation: circuit dielectric withstand; proper 0021311010 protective
devices; and visual verification 0 اproper connections 3111clearances, clean insulators, 211 50 on. 1٦ع
nameplate information 211 wiring should be checked 10 verify that the construction 15 correct 31 لagrees
with 1١ construction drawings. Test trip and verify the logic 0٤ 1 عschemes. 1٦ addition, some
recommended checks specific to capacitors are addressed in 12.1.1 through 12.1.6.
inspect all capacitor unit fiises (if used) for proper connections 211 لclearance. The 211* switching device
211 لground 5٢٧1٤ (1٤used) should be checked 10٣ proper operation. Capacitor unit nameplates should be
checked for the correct voltage for the desired number of units 11 series (fieless design) 0٣ units in series
210005 with parallel capacitor units per series group. Secondary circuits should be checked for proper
grounding of cable shields and spare control ٢٢٧1٣25 (52 ع10.7 ).
The capacitance of each capacitor unit should ﻋطchecked 10 verify' that it 15 w ithin specified tolerance and
for future testing reference. Usually, the capacitor manufacturer w ill maintain capacitor tolerances to w ithin
±2% of each other w ithin 2 01٢21 bank. ٤0٣ fuseless designs, measuring and comparing the capacitance 0ا
each series 5٣112 of units 15 adequate.
٨ ااrelaying associated with the capacitor installation should be checked 10٣ proper operation. Where
possible, this step should be done by putting the appropriate signal 01 1 عprimary terminals of 10 عsensing
device (CT and/or ٧1). 211 لchecking for appropriate operation 0٤ the relays 21 لcircuit breakers.
The unbalance 213 لinstallation that detects the change 11 capacitance should be calibrated 10 verify both
proper pickup current 011 لproper 11111 delay. (Excessive time delay 111 ع11 مoperation 31 result in severe
damage 10 the capacitor bank and associated equipment.) 11٦ lockout and trip operation should 2150 be
checked.
Backup or redundant overcurrent relays should عtested ٤0 verify proper pickup current 21 لtime delay.
The 521111125 used should be compared with the desired values that 1٦2 عbeen calculated.
1٦ عoscillographic recording capability 0 اa microprocessor relay 0٣ 2 portable recorder can assist 1٦
diagnosing problems associated with initial energization 0 ا3 large capacitor bank. The following
parameters should عrecorded:
Verity that all relaying systems 3٣ عoperational prior 10 energizing the capacitor bank. The oscillographic
equipment should ﻋﻂstarted immediately before the circuit breaker, circuit switcher. 0٣ equivalent
switching device 15 closed. It' the relay protection operates 10 trip immediately after initial closing, then the
follow ing procedure should be initiated:
After the capacitor bank 1135 been energized and all protection has been properly adjusted, the alarm level
(1٤ used) 211 لthe lockout operation 13 be checked. Depending 0 ٦ ﻋﺎbank construction, it may ﻋﻂ
ط1 ع10 check for proper trip and alarm performance 11 operation by removing or adding 200100111
00551
capacitors 1٦ the bank. Modify the bank 10 create 211 alarm situation. Measure the unbalance and verify that
the level measured 15 close 10 the expected value. The alarm should م1 *عup. Verify operation of any remote
displays, if used.
Modify ا1 عbank to create 2 trip situation. L rgize the bank. 10 ل11٧1102units 110111 different groups, series
strings. 0 02505 instead 0٤ 3 اا110111 0٦ عgroup, string, or phase tests the unbalance protection and produces
less stress 01 ﻋﺎremaining 110115. Verify 01000٣ relay targets and remote displays, if used.
12.2 R e s p o n s e to a l a r m ٥٣ l o c k o u t (trip)
It, available, review oscillographic records 10 determine 1٦ عmagnitude 0٤ the unbalance current 0٣ collage
0٦ 1 عphase.
Immediately inspect the bank 10٣ ا0٧1 fuses (1 اapplicable), possible flashover damage, and obvious
capacitor unit failures.
12.2.3 Testing
11 externally fused banks, test capacitors that are not obviously defective اﻟﺎطhave blown fuses. 11 cases
where a large number 0 اthe capacitor units 1٦ the bank have blown Rises (10٣ example, 25% 0٣ more), it 15
advisable 10 test all capacitor units and verify Rise ratings. Measure the capacitance 11 other 1٧005 0 اbanks.
Measure the series strings 111 the 10521255 design and the individual capacitor units 111 the internally and
unfused designs.
Replace the defective capacitor units andOr Rises. ١٧1٦٤٦ capacitors are arranged 11٦ parallel, units can be
removed 0٣ relocated from other phases 10 rebalance 1ا٦ عseries-parallel groups for capacitance and voltage.
Relocation of capacitor units 31 لchanges 10 the bank configuration may require a change 11 the unbalance
relay settings.
If only 1 ع115(5) 15 (are) blown, then make sure that 1٦ عcapacitor unit(s) 15 (are) checked 10[ 1ع
capacitance value and visual deformation such 45 bulging. If the capacitance 15 out 0 اtolerance 0٣ if the
unit 15 bulged, then it 15 recommended 10 replace both the fuse(5) and the capacitor unit(5).
If only a few capacitor units have been replaced, then the bank can عrelumed 10 service with a 111 111 ﻻ1
of readjustment of the unbalance relay. 1115 adjustments 311 be performed after ﻋﺎ010* 15energized.
1 اa large number 0 اthe capacitor units have been replaced, then attention tnay have 10 be given 10
recalibration 0 اthe sensitive protection after the bank 15 reenergized. Refer 10 12. ا.5.
Additional tests, as noted 1112.1 .6, 114٧ be performed 10 verity the 010122101scheme.
When system conditions permit, the bank should be taken out of service 10 replace defective capacitor units
and/or capacitor fuses. If replacement capacitor units are not available, then 10[ some 030 designs, 11 may
be possible 10 rebalance the bank ط٧ disabling corresponding units from all phases. Such rebalancing, or
other changes 10 the bank configuration, may require 3 change 11 unbalance relay settings.
11 addition 10 lheir protective functions, microprocessor relays 311 ل010010111110 ط1 عlogic devices can
provide enhanced monitoring and control 0٤ 3 shunt capacitor hank. These devices are capable 0٤ providing
automatic s١vitching based 0٦ time 0 اday, 5٧51٤1٦ 01100. and power factor, 0٣ any combination thereof.
During system contingencies, these devices ع31 provide fast bank switching and coordinate device
operation. These relays may 2150 provide detailed operational data 110111 عcapacitor bank, including but
10 اlimited 10 annunciation 0٤ capacitor can failure and bank unbalance conditions.
In addition 10 the features mentioned, modem relays provide the following features:
Annex A
(informative)
Bibliography
Bibliographical references 3٣ عresources that provide additional 0٣ helpful material but 00 not need 10 be
understood or used 10 implement this standard. Reference 10 these resources 15 made or informational 115ع
only.
(Bl) Abdulrahim, 1. ل., p. ٧1. Anderson, and ٨. ٨ . Fouad. “Inrush Currents 11 a Switched Parallel
Capacitor Bank,” /٤٤ Conference /20/92( 66-101.
[132] Alexander, 1٤. w . , “Synchronous (1051110 (’ontrol for Shunt Capacitors,” /٤٤٤ Transactions on
/291٤2/,1/2/91/1/1 and Systems, vol. PAS-104, no. 9. pp. 2619-2626. Sept. 1985.
[33 ]اBenmouyal, Ci., 11. Bilodeau, 5. 1٤. c'hano, and Ci. Sybille, ٠٠٧٤١٨٧ Algorithm 10٣ Protection 0ا
C apacitor Banks Exposed 10 Harmonic (-)vervoltages,” /٤٤٤ Transactions on /201١2 /02/٤12. vol. 8. 10. 3,
pp. 898-904, July !993.
[34 ]اGreenwood, ٨. .. D. 1٤. Kurtz, and ل. (. Sofianek, ٨ Ciuidc 10اا1 عApplication 0 اVacuum Circuit
Breakers,” /٤٤ Transactions 097 /201٤21/9/91٤1/115 and Systems , vol. 1٨5 90. pp. 1589-1597. July/Aug.
1971
[35 ]اHarder, ل. ﺗﺎ.. “Selection and Protection of Current Transformers 10٣ ﻻ5 ع111Shunt Capacitor Banks.’*
IEEE PES Conference Paper ٨ 76 335-0.9
[36 ]اHamer, 1٤. 11.. and Owen, 1٤. E.. *‘Neutral Displacement 0 اUngrounded Capacitor Banks During
Switching,” /٤٤ 770/11٤/19975 991 /201 24/9/901/11 0/1/51 /2991. vol. 10٨5-90. pp. 1631 1638. 1111٧/٨112.
1971.
[137] ! ﺗﺎﺗﺎ ﺗﺎPower 5٧51٤1٦1 Relaying Committee, “Static ٧٨1٤ Compensator Protection,” IEEE
Transactions on Power Delivery٠ vol. 10.00.3.00. 1224-1233, July 1995.
[BX] ﺗﺎﺗﺎ ﺗﺎاSurge Protective Device Committee, ‘,Impact 0 اShunt Capacitor Banks on Substation Surge
Environment and Surge Arrestor Applications,” /٤٤ Transactions ٠„ /20١٤2٠ Delivery. vol. 11.10. 4. pp.
I798-I8o9.()ct. 1996.
[39 ]اMcCauley, 1. M.. 10. ا. Pelfrey, w . (. Rocttger, and . ﺗﺎ. Wood, “The Impact of Shunt Capacitor
Installations 01 Power Circuit Breaker Application,” /٤٤٤ Transactions on /201 24/7/9 0/15 and Systems.
vol. PAS-99, 00. 6. pp. 2210-2222, Nov. Dec. 1980.
[BIO] Mendis, 5. 1.. M. 1. Bishop. J. (. McCall, and ١٧. M. Hurst, “Dvercurrent Protection of Capacitors
Applied 01 Industrial Distribution Systems,” /٤٤ Transactions 997 Industry 4/9/9/121/ 9,1؟. vol. 29, 110. 3,
May/June 1993.
[311 ]اMiller, D. F., “Application Guide for Shunt Capacitors 01 Industrial Distribution Systems at
Medium Voltage Levels,” /٤٤٤ Transactions on //7///٢/,٦ 4/9/9/ 201/19 1. vol. 1٨-12. 110. 5, ﻣم. 444459 .
Sept./0ct. 1976.
[13121Steepes, 10. E., 2 ل1٤. 1. Stratford, “Reactive Compensation 21 لHarmonic 511001255101for
Industrial Power Systems Using Thyristor Converters,” /٤٤٤ Transactions 6997 Industry 4/7/9/٤21/027. vol.
1A-I2, 110. 3. pp. 232-254, May/June 1976.
[ ا313] 10٦. ٨. o . , “A Static Voltage Differential Relay for Protection 0 اShunt Capacitors.” AIEE
Transactions on Power Apparatus and Systems, vol. 80, part 111.00. 10861088. Feb. 1961.
11115 document can عaccessed 011 the 10010ا15ا1 ﻟﻊReports** page 3٤ http:Z/u٦vw.pe5-p5rc org
Annex 8
(informative)
Symbol definition
Chn 15 the capacitance 1101٦1 اا120 or ٤0 م10011٤10 neutral 0٣ reference 211 ل0٤ a capacitor bank.
7 15 the per-unit capacitance 0٤ the affected group 11٦ 211 internally fused capacitor 11 1٤
Cp is the per-unit capacitance of the phase (leg if the bank is delta-connected) with the
affected capacitor 11111(5).
Cs 15 the per-unit capacitance 0٤ 3 string (0٣ 122) 0 اcapacitor units with affected capacitor
un؛t(s).
Ctn 15 the capacitance 110111 tap 10 neutral 0٣ reference end for 3 tapped capacitor bank.
أ 1511 عper-unit capacitance 0٤ the parallel strings 11 the phase 0 the wye with affected
elements.
/ 15 the number 0 blown fuses (eliminated elements) 11٦ 0٦ عgroup 0 اan internally fused
capacitor unit.
دﺑﻰ 15 the variance of phase angle bet١veen two phases 110111 ا20 °.
/ل 15the difference in neutral-to-ground current between two equal grounded wye banks.
//1 15 ا neutral current between wyes for wye-wye 00105. per-unit of normal total phase
current.
\ 15 the 11110٤٣ of parallel elements 1٦ one 210 0 م0 ا311internally fused capacitor unit.
p 15 the number of parallel capacitors 0٣ series group (11٦ the affected group 01111115).
5 151٦ عnumber 0 اseries 010005 1٦ a ban* (phase-to-neutral for wye-connected banks and
phase 10 phase 10٣ delta-connected banks).
St 15 1 عnumber of series groups, sensing tap to ground 0٣ reference end for tapped banks
211 لsensing ا1 leg 10 ground or reference end for 11-bridge banks.
127ر 15 the voltage across capacitor units 11٦ affected series group (per-unit 0٤ normal voltage).
Ve 15 the voltage across affected elements 11 31 internally fiised capacitor unit (per-unit 0٤
normal voltage).
19 15 the voltage across affected elements 111an internally fused capacitor unit ﻋﻼل10
unbalance w ithin the unit (per-unit of actual unit operating 011422).
Vh 15 11 highest voltage 01 other units 11 the 410 when this 15 higher than the voltage on
the parallel units Vcu 0٣ 111 the same string ا.
١'1 15 the line-to-neutral voltage of affected phase, per-unit of normal line 10 neutral voltage.
Annex ع
(informative)
Table ('.I 15 intended as a rule 0٤ thumb ٤0٣ determining the eft'ect 0٤ inherent unbalances 01 the
displacement 0٤ carious bank protection schemes.
Annex ه
(informative)
دا١:آﺻﻠﺎم١
(_ا٨)«ه٠ب1٠ي
'■)ؤ:ل٠٠*|٧آ
/( (/ﺟﯾو
0.2 Energizing هbank with another on ٤2 same bus ٧٧٤٤ no charge on ٤2 bank
being switched
(kA ؛H
where
k١a٢T 15 kva٢٦ + k a 2
/ﻋو i s t h e symmetrical 11115 short-circuit current (٨)
GTE -The previous expressions tor inrush current a p p l y 0ﻻ t o r energizing uncharged capacitors. I t ' capacitors 1٣
charged, 15 d u r i n g 1 rcstrikc across an interrupting s w i t c h , thenاا1 عinrush current n a y be t w i c e these values.
See I E E E S t d <25()20-7.012و.
Annex ع
(informative)
Bonk rating:
٤٦٧ 69 k V
mvar 180 mvar
Connection f o u n d e d wye
Rated current 150.79٨ kvar/(l.73xkV)
Series groups 'phase* s
Number 0 اcans per 52٣125 group. Pt 20
Ao
u-
1
٠ 064 8
S-2 ١ene٠s groups line to neutral ا - 20 parallel units per phase
11 bionuses ﻓﺎ- 10 ٠0”ا1 grounded. ٠٠l’,tl ungrounded
Series 210005/0135 5
Number 0٤3٦5 0٤٣ series group. Pt ٠
Grounding, 7 (grounded) 0
Neutral 1 ratio—50/5 ٨ 10
1he nominal capacitor parallel group voltage is (690 kV / ٧3) / 2 series groups - 19,92 ٧.
٨5 per the statement 11 8.4. ا. the unbalance relays 3٣ ع5 011the basis 0٤ ا1 عmaximum system operating
voltage, 11٦ عmaximum system operating voltage 15 72.5 ٤٧ 10٣3 69 ٤٧ system:
“Where possible, the unbalance relay should be sensitive enough 10 alarm for 1 عloss of one unit ١vithin a
group, 11 should 2150 trip 41 لlock 0 ﻻ01 1 ع1055 0 اadditional capacitor units that cause a group
overvoltage 11٦1 excess 0 ا ا10 % of capacitor unit rated voltage (0٣ the capacitor unit manufacturers
recommendation).,’
From Figure 28 and Figure 29. and from Table 2 and Table 3:
٤٣01٦٦ Table 2 and Table 3 (note that 11٦ Table 3. Pt - Pa and Cs - Cp for لsingle ٧ عbank):
Pt-n
Vcu - * . Cp - ٦)١) I . and *
Pt
Pt — n
(5-1)+
Pt
٤0 the ا055 0 اone individual capacitor unit, the voltage of the affected group will be:
The neutral unbalance protection ١1 ع ااprogrammed 10 43٣111 اfor 115 condition. The alarm setting will be
equal 10 50% of the value 35 suggested 111 8.4.2.
For the 1055 of two 111ل11 اﻟﻼلcapacitor units, (1 عvoltage 0٤ the affected g٢oup اااhe:
1٤١،(2)ﺛﯾﯾﯾﺢ-1.053ﺳم
t■٥-,٠
11115 exceeds the continuous maximum rating 0 اthe capacitor units when the system 15 operating 31
11141111ﻻ111system voltage,
11٦ عneutral unbalance protection will be programmed 10 trip for 1115 condition, 11٦ ع5111112 ﻻﻻمbe
halfway 1٦ between the trip and alarm setting 05 discussed 1118.4.2.
ءي/ر.ر/1/ر1/ر/رر1ﯾﻊ
11٦ عequation 110111 Table 2 15 used 10 determine the neutral unbalance current, 7g٠ following the 1055 0٤
capacitor units:
/ي-(ا-7)(1-//9/7)
where
lpl.-Cp.Cp-
)ﻻام(ر
Tie unbalance alarm will عset 10 detect the 1055 0 ا01٦ عindividual capacitor unit, 0٣ 1 ع1055 0ا0٦ عunit,
٤ عneutral current 11 اbe:
2 20
/(ي1) = ا- * - )ا - 0.026 pu = 0.026x1 50.79 = 3 ووApri
(20-1)(2-1)+20
The resulting secondary 1 current will 00 4.12/10-0,412 ٨5. and the voltage applied to the unbalance
relay will 2 4.12 ٧. Set the relay alarm pickup at 500% of this value, 2.06 ٧٠
The unbalance trip will be set 10 trip 10٣ the 1055 of 10 individual capacitor units assuming maximum
5٧51٤11 operating voltage, ٤0٣11
٦ ع1055 0 ا10 units, the neutral current will be:
111 عresulting secondary' CT current will be 8.64 / 10 - 0.833 ٨5. and the voltage 2100ا1 ل10 the unbalance
relay ١ اااbe 8.33 ٧. Set the relay 10 trip at 8.0 ٧.
1he relay ٣ ااأnot trip 10٣ the 1055 of one capacitor unit 411 لwill trip only if the current unbalance 12225 3
١’alue that results 111 ا%100 ؟oltage on 1 عcapacitor units. Note that the tripping 15 delayed 10 coordinate
with other relays 11 the system as described 11 8.3.4.
ا ل] ل ]] ﻟل٦آآآ ؛ي
٢١ ؛ي ﺿﺟن، 7٦آآآ٢ ]ﻟل] ﻟل:
ﻟﻣل ﻟل ال أل ﻟل
ل
ﻧﻢ
ﻵأ٢_ﻧم١
; -1 [ [ [ [
ًا
٢
دﻟﺠﻤﻠﺎد
!—)ﻋب
ﻋﺻﺎب
*ﻣرد
-ا
٦
م
—اﻟﻣﻼب
1٦٦
■-٠ل-|
اا1 1٠ .1 ًا ًا ًا
م
ا
٠١٠
)ا1
0ﻟﻣر٩
[ ب■"ﻟﻠم أ Í )ًل[ا
[ ٦ﻟﻠل ﺣﺳﺎن
—*ﻣرد
ﺣﺎد
—()ﺟﻼﺑر
ة؟
(ﺑﮭم
1-
I
I
ﺣﺻﺎد
—اأ—ﻣﻼس
— ا:■
اذ---■-
-*ااﻋل
ب١— ﻣب
—(ﺑب
أل
Figure E.2—Sample ungrounded ٧٧٧2 externally used capacitor bank
5٧5٤٤1٦٦ nominal phase-phase 01100 = ع138٤٧ Rated bank 5٧512111 0ا140= ع151 ٤٧
8997 rating:
k٧ 151 k٧
52٣125 groupsphase. 5
٧(151/1.73)/5 I7.4k٧
Neutral PT 300٠
،’The unbalance relay should coordinate ١1 اthe individual capacitor unit fuses 50 that the 1525 operate 10
isolate a defective capacitor unit before the protection switches the 21* out of service. (٨ reliable 1se
operation provides a convenient, visual means ٤0٣ 10311112 the defective capacitor unit(s)٠]
Where possible, the unbalance relay should be sensitive enough 10 alarm ١0٣ the 1055 of 0٦ عunit within 4
group. It should also trip and lock out 01 the 1055 0 اadditional capacitor units that cause 4 group
overvoltage 11 excess of 110% 0٤ capacitor unit rated voltage (or the capacitor unit manufacturer’s
recommendation),’*
ا ا00 % of the capacitor ﻟﺎ1 اrated voltage 15 17.4 ٧*1.1- 19.14 ٤٧.
NOTE— Calculated values 0٣ the following situations 2٣ ع025ل 1011 tbe output of a ٧12٤٨10أا document.
S*Cg
Cs٦= — Affected wye capacitance ٤٢ -ا
Cg * ( 5 - 1 )
(Cs X 1١ﻻ١ بPt - P aا ٨ ﻻﻧﻨﺎا01 5 عcapacitance
(/2:=- ٠ : ٦ا
Cp
Pl
InxCs
1رر — ú Voltage 011 affected series group Vvu ; ١
I'/n X s otherwise
UIRATE - Normal unit current at maximum system voltage - UVAR/UVOLTS - 238 A * 10/
,6.74x103 =14,22 A
Capacitor rated voltage is ا7.4 kV. Voltage 01 group with 110!’use failures 15 16.74 kV. At 105% system
voltage. ﻋﺎاcapacitor units are operating al 96.20% of rated voltage.
1/1 * ىotherwise
W i t h 0٦ ع115اط ع0١11 within a parallel group, the voltage 01 ﻋﺎاaffected group (the group experiencing the
fuse failure) rises 10 17.85 ٤٧. This 15 102% of the capacitor unit voltage rating. The primary ncutral-o
ground voltage 15 425 ٧. ٨ reliable alami threshold for detecting this condition would عset at 80% 0 اthe
calculated voltage level.
\٦1
Copyright © 2013 IEEE. ااهrights reserved.
IEEE std 23799-2012
IEEE Guide for ااProtection 0Í Shunt Capacitor Banks
V1n*Cs
Vcu :ت c if Cg Voltage on affected series group Few = 1 . 1 4 1
1/7 xV otherwise
f c w P R l = Vcu X UVOLTS ٧0
ا142 ع011afTected group H™PRI=19.11kV
With two fuses blown within 2 single 210مﻻ.ا٦ عvoltage on the affected group rises 10 19.11 ٤٧. which 15
109.7% of rated voltage. Set 1 عtrip threshold for the bank halfWay between the اand 2 fuse blown
neutral-to-ground voltage levels 10٣ reliable detection of the second fuse failure.
[- ٠
System nominal voltage - 6 9 kV # Parallel strings 11 left wye (same 35 # strings per phase - 4)
Bank rating:
٧ 76 kV
111٦11 12.010٦2[
*٧(76/1.73)/4 11.0 kV
٧( 11.0/6) 1.83٦٧
As .stated in 8.6.2:
"The number 0 اshorted 10 11121ا5 tor trip 311 لalarn can عdetermined طkno١ving the voltage 011 the
affected elements (for instance, the 1 value calculated 11 Table 10) and 111 capability of the elements
(either ا%10 0 اrating based 011 indus/’ standards 0٣ the information provided by the capacitor
manufacturer).,’
ا ا00 % of capacitor element rated voltage 15 1.83٧*1.1- 2.02 ٤٧.
- 3xPm٠xü٦x إ5ر1
/=إ-
Neutral current between wyes /ور-0
120
Copyright © 2013 IEEE. ااه19ا8 reserved'
ﻟﯨﻌﻌﺎ 237 2012-99
ﻋﺗﻌﻌﺎGuide for the Protection of Shunt Capacitor Banks
With zero element failures, the voltage on the elements 15ا8 28 ٧٠which 15 91.35% o f rated voltage.
ه( م١'*ﻵﺑﺮﺳﺪ1-ﻣﻊ
ري: ﻟﺞ Affected phase capacitance (=1.011
/ اﻟﺜﻜﯿﺜﺜﺜﻠﺚ
In: ة Neutral current between ١vyes /7 = 0
/,1011 R|x/,
Neutral current betveen ١vyes "اى-"
With one element shorted 1٦ the ,string, the voltage on the remaining elements in the string 15 ا908 ٧٠ hich
15 94.5% of the rated element voltage. Primary neutral-to-ground current 15 1.982 primary 0٣ 0.198 ٨
secondary. Set the alarm threshold ٤0 800% of this level 10٣ reliable detection 0 ا3 single element failure
within a string.
م ااا١+دد
>|ا- ٦
Affected phase capacitance ي: 1.05
, - ﻛﻴﺜﺎة2ﻟﺖ
Sp Neutral current bet١veen wyes 1٠أ:ه
/1101 :-/0/,*0/,111ا
Neutral current between wyes hl P R 1 - 0
With four ا11 لelements, the voltage 011 the affected elements 15 109.6%. 10 trip the bank 10٣ this level 0ا
unbalance reliably, set the unbalance current element halfway between the neutral-to-ground current for
four element failures, and for three element failures:
1[1 مthreshold - (9.116 - 6.511)/2+6.51 1- 7.836 ٨ primary, 0.78 secondary (50:5 (1 ratio).
System nominal voltage - 230 ٤٧ # Parallel 5ا٣1110511 left wye (5/) - ا
/207 rating:
kV 250 kV
52٣125 groups'phase, 5 10
٧*(250/1.73)/10 144 ٦٧
٧( 14.4/ 4( 3.61٦٧
٨5 stated in 8.6.2٠
The number 0 shorted elements 10٣ trip 211 لalarm can عdetermined ط٧ kno١ving the voltage 01 the
affected elements (10٣ instance, the 12 value calculated 11 Table 10) and the capability of the elements
(either 110% 0 اrating based 011 industry standards 0٣ the information provided ا0٧ the capacitor
manufacturer).١٠
c٦٠
c>
—
ث
ﻟﻠﺗك Shorted per-unit capacitance ١- ا
ع ۴*ﻟﺎS1١*Sp-S١
Cp- Sp Affected phase capacitance ٩٦= ١
/g = ( l - i ; ) x ( l - / 9 / ) ) ( r o u n d current /4-0
/ر,-ﺛﺜﺜﺜﺔ -0
اﻻﻻعcurrent between wyes
5م /0
MR := /9/ x/9/PR !*| /،/ا Difference current between equal ٧05 MPRI - 0
1210112 رﯾﺎ
!'//PR[
Voltage 01 affected elements
RRI2 = 3,486 kV
The voltage 01٦each element with zero tailed elements 15 3486 ٧ al 105% nominal system 01142. 1115 15
96.8% o f the rated element voltage.
Cy — ﻛﻛﺎﺗك
C) ة Shorted per-unit capacitance Cy: 1.026
م رددرا
Cp; ، Affected 01135 عcapacitance £.),= 1.013
/ر, -ﻟﻠﺛﻛﺛﺎﺛث
Sp Neutral current between wyes ln = >؟
/,01 1 :-//0/7//0,1011 1 7
Neutral current between ٦٦٢٧15 /,,PR! = 0 . 7 1 8
/،/PRI :-//,/,*//,/,PRI I/Í/I Difference current between equal ٧05 /Í/PRI- 1.436
For 4 single failed element, the voltage 0111 عaffected elements nses 10 3545 ٧. ١١hich 15 98.5% of the
rated element ١٠oltage. 10 detect this condition reliably, set the phase unbalance elements 10 800% 0٤ 1ع
calculated difference current bet١١een اﻻ وع١١yes.
/,- -ث0
5م Neutral current between wyes / 0.05,
/PRI :=/,/x/,/PR,x/,,
Neutral current between ١٧5 /PRI -6.103
With seven failed elements, the voltage 01 each element [150510 3942 ٧. 1115 15 109.5% of the [ated
element voltage.
ي ع
=و|ا ة Affected phase capacitance (-1.125
j ٦x١٠ngxGx٢Sp-ÍU١
In: Sp Neutral current between ١٧25 f« 0.06
/»PRl:=/p/jx/phPR]x/n
Neutral current between wyes M P R 1 : 7.228
With 210٤ failed elements, the voltage across the remaining elements 11٦1 the string rises 10 4016 ٧. 1111515
اا%1.5 0٤ the rated element voltage. 10 determine the trip threshold, find 4 current unbalance point
halfivay bet١veen seven and eight unit failures.