Ceiling Mounted Precision Air Conditioners/Air Handlers
3.5-35 kW / 60 Hz
CeilAiR ENGINEERING MANUAL

Notice

This document contains information protected by copyright. All rights are reserved. The owner of the equipment
for which this manual is written may photocopy the contents of this manual for internal use only. No part of this
document may be photocopied, reproduced, or translated into another language for use by anyone other than the
owner of the equipment for which this manual is written without the prior written consent of STULZ Air Technology
Systems, Inc. (STULZ).

This document contains confidential and proprietary information of STULZ Air Technology Systems, Inc.
Distributing or photo- copying this document for external distribution is in direct violation of U.S. copyright laws
and is strictly prohibited without the express written consent of STULZ.

Unpublished — rights reserved under the copyright laws of the United States and of other countries. Other
brands and tradenames are trademarks of their respective owners.

Copyright 2018 by STULZ Air Technology Systems, Inc. Printed in the United States of America.
All rights reserved.

STULZ Air Technology Systems, Inc.


1572 Tilco Drive
Frederick, MD 21704 USA
https://www.stulz-usa.com/en/

iii
CeilAiR ENGINEERING MANUAL

Table of Contents DX - Self-Contained Glycol Cooled Cooling Capacities,


3.5−17.5 kW............................................................................ 18
DX Dual Compressor - Self-Contained Glycol Cooled
Model Nomenclature Guide Specifications ............ 1
Cooling Capacities, 14−35 kW .......................................... 18
DX Models ............................................................................................. 1
DX Free Cooling/Alternate Water Source.......................... 19
Air-Cooled, Self-Contained: Integral Self-Contained
DX with Free Cooling - Self-Contained Water Cooled
(Models OHS-012/040-AS) ...................................................... 1
Technical Data, 3.5−17.5 kW ............................................. 19
DX - Evaporator Sections: Air Cooled Remote Evaporator
DX Dual Compressor with Free Cooling - Self-Contained
(Models OHS-( )-()AR) ................................................................... 1
Water Cooled Technical Data, 14−35 kW ...................... 20
DX - Water Cooled Systems: Integral Self-Contained
DX with Free Cooling- Self-Contained Glycol Cooled
Models OHS-( )-W / DW .............................................................. 1
Technical Data, 3.5−17.5 kW ............................................. 21
Chilled Water Air Handlers ............................................................... 1
DX Dual Compressor with Free Cooling - Self-Contained
Chilled Water System (Models OHS-( )-C).............................. 1 Glycol Cooled Technical Data, 14−35 kW ...................... 22
DX with Alternate Water Source Technical Data,
CeilAiR Models ........................................................ 2
3.5−17.5 kW............................................................................ 23
Selected Standard Features ........................................................... 4
DX with Alternate Water Source, 14−35 kW ................. 23
Specific Model Standard Features ............................................... 4
DX with Free Cooling - Self-Contained Water Cooled
Cooling Capacities, 3.5−17.5 kW ..................................... 24
Technical Specifications and Performance/
Capacity Data .......................................................... 5 DX Dual Compressor with Free Cooling - Self-Contained
Water Cooled Cooling Capacities, 14−35 kW .............. 25
Direct Expansion Air/Water/Glycol-Cooled Models .......... 6
DX with Free Cooling - Self-Contained Glycol Cooling
DX - Self-Contained Air Cooled (AS) 3.5 – 10.5 kW /
Capacities, 3.5−17.5 kW ..................................................... 26
Split Air Cooled (AR) Technical Data, 3.5–17.5 kW ....... 6

Table Of Contents
DX Dual Compressor with Free Cooling - Self-Contained
DX Dual Compressor- Split Air Cooled Remote w/
Glycol Cooling Capacities, 14−35 kW ............................. 27
Condenser Technical Data, 14–35 kW .............................. 7
DX with Alternate Water Source Cooling Capacities,
DX Dual Compressor- Split Air Cooled Remote w/
3.5−17.5 kW............................................................................ 28
Condenser Technical Data, 14−35 kW (Cont) ................. 8
DX with Alternate Water Source Cooling Capacities,
DX - Split Air Cooled w/Condensing Unit Technical
14−35 kW................................................................................. 29
Data, 3.5−17.5 kW .................................................................. 9
Alternate Water Source 42 °F EWT Cooling
DX Dual Compressor - Split Air Cooled w/Condensing
Capacities ................................................................................... 30
Unit Technical Data, 14−35 kW .........................................10
Alternate Water Source 42 °F EWT Cooling
DX- Self-Contained Water Cooled Technical Data,
Capacities ................................................................................... 31
3.5−17.5 kW ............................................................................11
Alternate Water Source 50 °F EWT Cooling
DX Dual Compressor - Self-Contained Water Cooled
Capacities ................................................................................... 32
Technical Data, 14−35 kW ..................................................12
Alternate Water Source 50 °F EWT Cooling
DX - Self-Contained Glycol Cooled Technical Data,
Capacities ................................................................................... 33
3.5−17.5 kW ............................................................................13
Chilled Water Models ............................................................... 34
DX Dual Compressor - Self-Contained Glycol Cooled
Technical Data, 14−35 kW ..................................................14 Chilled Water Air Handler Technical Data,
3.5−10.5 kW............................................................................ 34
DX - Self-Contained Air Cooled (AS) 3.5 - 10.5 kW /
Split Air Cooled Cooling Capacities, 3.5–17.5 kW ......15 Chilled Water Air Handler Technical Data,
14−35 kW................................................................................. 35
DX Dual Compressor- Split Air Cooled Remote w/
Condenser Cooling Capacities, 14−35 kW ...................15 Chilled Water Air Handler Cooling Capacities,
3.5−12 kW................................................................................ 36
DX - Split Air Cooled w/Condensing Unit Cooling
Capacities, 3.5−17.5 kW .....................................................16 Chilled Water Air Handler Cooling Capacities,
3.5−12 kW (Con’t) .................................................................. 37
DX Dual Compressor - Split Air Cooled w/Condensing
Unit Cooling Capacities, 14−35 kW .................................16 Chilled Water Air Handler Cooling Capacities,
14−35 kW................................................................................. 38
DX- Self-Contained Water Cooled Cooling Capacities,
3.5−17.5 kW ............................................................................17 Chilled Water Air Handler Cooling Capacities,
14−35 kW (Con’t) ................................................................... 39
DX Dual Compressor - Self-Contained Water Cooled
Cooling Capacities, 14−35 kW ..........................................17 Chilled Water 42 °F EWT Cooling Capacities ................. 40
Chilled Water 42 °F EWT Cooling Capacities ................. 41

iii
CeilAiR ENGINEERING MANUAL

Chilled Water 50 °F EWT Cooling Capacities ................. 42 With Condensate Pump (OHS-048 −
Chilled Water 50 °F EWT Cooling Capacities ................. 43 OHS-120 C) .............................................................................. 55
Without Condensate Pump (OHS-048 −
Electrical Data (FLA / MCA / MFS) ........................ 43 OHS-120 C) .............................................................................. 55
DX Air, Water, and Glycol Cooled ............................................. 45
Dimensional Data and Installation Drawings ........ 57
With Condensate Pump (OHS-012 −
OHS-060 AS)............................................................................ 45 Physical Data and Connection Sizes ...................................... 58
Without Condensate Pump (OHS-012 − Air Cooled Systems ...................................................................... 60
OHS-060 AS)............................................................................ 45 DX Air Handling Units .................................................................. 64
With Condensate Pump (OHS-012 − Water/Glycol Systems ................................................................ 66
OHS-024 / AR, W, G) ............................................................. 45 Chilled Water Systems ................................................................ 70
Without Condensate Pump (OHS-012 − OHS-024 /
AR, W, G) ..................................................................................... 46 CeilAiR Product Guide Specifications ................... 72
With Condensate Pump (OHS-032 − OHS-060 / AR, SUMMARY .......................................................................................... 72
W, G) ............................................................................................. 46 Design Requirements ...................................................................... 72
Without Condensate Pump (OHS-032 − OHS-060 / Quality Assurance ............................................................................. 72
AR, W, G) ..................................................................................... 47
Cabinet ................................................................................................. 72
With Condensate Pump (OHS-048 − OHS-120 DAR,
Air Flow Patterns ............................................................................... 72
DW, DG) ....................................................................................... 48
“Ductless” Spot Cooler (Models OHS-012
Without Condensate Pump (OHS-048 − OHS-120
thru 040-( ) only) ........................................................................... 72
DAR, DW, DG)............................................................................ 47
Ducted Evaporator (Available on all model sizes) ............... 72
With Condensate Pump (OHS-012 − OHS-032
AHU) ............................................................................................. 49 Air Filtration ......................................................................................... 72
Without Condensate Pump (OHS-012 − OHS-032 Mechanical Components................................................................ 72
AHU) ............................................................................................. 49 Blowers/Motors ................................................................................ 72
With Condensate Pump (OHS-040 − Direct Drive Systems ................................................................... 72
OHS-060 AHU) ........................................................................ 50 Belt Driven Systems .................................................................... 72
Without Condensate Pump (OHS-040 − OHS-060 Refrigeration System ....................................................................... 72
AHU) ............................................................................................. 49
Scroll Compressor........................................................................ 72
With Condensate Pump (OHS-048 − OHS-120
Evaporator Coil. ............................................................................. 73
DAHU) ......................................................................................... 51
Air Cooled Heat Rejection ......................................................... 73
Without Condensate Pump (OHS-048 − OHS-120
DAHU) ......................................................................................... 51 Water Cooled Heat Rejection ....................................................... 73
DX Free Cooling and Alternate Water Source .................... 51 Chilled Water System .................................................................. 73
With Condensate Pump (OHS-012 − OHS-024 HAR, Chilled Water Control Valve ......................................................... 73
HW, HG) ...................................................................................... 51 Overflow Safety Float Switch ........................................................ 73
Without Condensate Pump (OHS-012 − OHS-024 Remote Start/Stop .......................................................................... 73
HAR, HW, HG) ........................................................................... 51 Electrical System .............................................................................. 73
With Condensate Pump (OHS-032 − OHS-060 HAR, A-Tech-1.1 Controller...................................................................... 74
HW, HG) ...................................................................................... 52
E2 Series Controller .............................................................................. 74
Without Condensate Pump (OHS-032 − OHS-060
Field Configurable ........................................................................ 74
HAR, HW, HG) ........................................................................... 52
Password Protection ....................................................................... 74
With Condensate Pump (OHS-048 − OHS-120 DAR,
DW, DG) ....................................................................................... 53 Restorable Parameters/Factory Defaults ........................... 74
Without Condensate Pump (OHS-048 − OHS-120 Timer Feature ................................................................................ 74
DAR, DW, DG)............................................................................ 53 A/C Grouping pLAN Operation ............................................... 74
Chilled Water ................................................................................. 54 Remote BMS ...................................................................................... 75
With Condensate Pump (OHS-012 − OHS-040 C) ... 54 Alarms .............................................................................................. 75
Without Condensate Pump (OHS-012 − E2 Constant Contact .................................................................... 75
OHS-040 C) .............................................................................. 54

iv
CeilAiR ENGINEERING MANUAL

Full-Floating Hot Gas Bypass .................................................. 75


Snap-acting Hot Gas Bypass ....................................................... 75
High-Static Pressure Belt Drive Blowers .............................. 75
Low Entering Condenser Water Kit ....................................... 75
Steam-Generating Humidifier...................................................... 75
Dehumidification Cycle .............................................................. 75
Electric Reheat/Heat...................................................................... 76
Hot Gas Reheat ............................................................................ 76
Hot Water Reheat/Heat ............................................................ 76
SCR Fired Reheat/Heat (Requires E²controller) .............. 76
Low Profile Condensate Pump ................................................ 76
All-Metal Condensate Pump (optional). ................................ 76
Dual Overflow Safety Switches ............................................... 76
Air Filtration ........................................................................................ 76
Smoke Detector ........................................................................... 76
Firestat ............................................................................................ 76
Water Detectors ........................................................................... 77
Compressor Sound Jacket ....................................................... 77
Electrical Options ......................................................................... 77
Three Phase Power Supply ...................................................... 77
277/1/60 Power Supply ......................................................... 77
Main Power - Electric Non-Fused Service Switch ............ 77
Controller Options........................................................................ 77
A-Tech-1.2 Controller ..................................................................... 77
Air-Side Economizer Controls ................................................. 78
Alternate Water Source ............................................................. 78
Code Conformance ......................................................................... 78

v
CeilAiR ENGINEERING MANUAL

Nomenclature

OHS-XXX-XX-XX
Nominal
System Capacity in Configuration Options
1,000’s of
BTU/Hr
AWS = Alternate Water
AHU = Air Handling Unit
Source FC = Free
AR = Air-Cooled Remote
OHS = 012, 018, 024, D( ) = Dual Circuit Cooling
032, (Split) AS = Air-Cooled
CeilAiR H( ) = Horizontal LP = Low Profile
040, 048, 060, Self-Contained C =
Overhead 072, Discharge (“H- Configuration SF =
System 084, 120 Series”) Chilled Water System
Same-Face Air Pattern
G = Glycol-Cooled SP = Special
W = Water Cooled
Configuration *

OHS 040 H G FC

* Call 888 529 1266 for additional information.


Example: OHS-040-HG-FC
Overhead System, 40,000 BTU/Hr Capacity, Horizontal Discharge, Glycol Cooled with optional Free Cooling: OHS-040-G-FC

STULZ Condensers and Condensing Units are documented in our Heat Rejection Engineering Manual.

STULZ Pump Packages and Drycoolers are documented in our Glycol Systems Engineering Manual.

vi
CeilAiR ENGINEERING MANUAL

Water Regulating Valves


Model Nomenclature Guide Head pressure shall be automatically controlled by a factory
Specifications installed 2-way water regulating valve rated for 150 psi wwp
3-way and high pressure 300 to 400 psi rated valves are
DX Models available as options. See “Water and Glycol Regulating
Air-Cooled, Self-Contained: Integral Self- Control Valves” on page 74.
Contained (Models OHS-012/040-AS) * 2-way valves are factory installed; 3-way valves are field
installed.
The system shall be a self-contained, ceiling mounted air con-
ditioner with factory mounted integral air cooled condenser with DX - Glycol-Cooled Systems: Integral
centrifugal blower. Self-Contained (Models OHS-( )-G / DG)
The condenser shall be sized to provide the total heat of rejec- The system shall be a self-contained, ceiling mounted air
tion of the system at a 95 °F DB ambient temperature. conditioner to include integral glycol cooled, coaxial con-
The system shall require only single point supply power con- denser with factory installed head pressure glycol regulating
nection and the system shall ship from the STULZ factory with control valve(s). Condenser (source) glycol solution shall be
a full operating refrigerant charge. provided via a CeilAiR model GPS-( )-( ) / FSS/FDS remote
glycol pump package and drycooler system.
DX - Evaporator Sections: Air Cooled Remote
The system shall require only single point supply power
Evaporator (Models OHS-( )-()AR) connection and shall ship from the STULZ factory with a full
The system shall be a remote (split) air cooled, ceiling mounted operating refrigerant charge.
air conditioner evaporator. The evaporator section shall house,
as a minimum, the evaporator coil, expansion valve, compressor, Glycol Regulating Valves
evaporator blower/motor and associated electrical and refrig- Head pressure shall be automatically controlled by a fac-
eration components. tory-installed 2-way glycol regulating valve rated for 150
The OHS-( )-()AR evaporator section shall be located at some psi wwp 3-way and high pressure 300 to 450 psi rated
distance from its corresponding CeilAiR model HES-( )-()CAA valves are available as options. “Water and Glycol
indoor or SCS-( ) outdoor air cooled condenser. Regulating Control Valves” .
The evaporator system shall require only single point main
power supply connection and the system shall ship from the
Chilled Water Air Handlers
STULZ factory with a dry nitrogen holding charge ready for field
Chilled Water System (Models OHS-( )-C)
refrigerant (R-407C) charging.
The system shall be a ceiling mounted chilled water air condi-
STULZ Condensers and Condensing Units are documented in
tioner to include chilled water cooling coil, evaporator blower
the STULZ Heat Rejection Engineering Manual.
and motor and chilled water control valve. Chilled water shall
be provided by a remote liquid chiller system.
DX - Water Cooled Systems: Integral Self-
Contained Models OHS-( )-W / DW Chilled Water Control Valve
The system shall be a self-contained, ceiling mounted air con- Cooling capacity shall be controlled with a slowly opening
ditioner to include integral water cooled, coaxial condenser with and slowly closing 2-way motorized control valve rated for
head pressure water regulating control valve(s) (not applicable to 300 psi wwp 3-way 300 psi motorized valves and 2 or 3-
OHS( ) ( ) G-W-FC models)*. Condenser (source) water shall be way modulating valves are available as options (except on
provided by cooling tower or some other remote water source. OHS-( )-( )-G-W-FC models). See “Chilled Water and AWS
The system shall require only single point supply power connec- Control Valves” on page 75.
tion and shall ship from the STULZ factory with a full operating
refrigerant charge.

1
CeilAiR ENGINEERING MANUAL

2
CeilAiR ENGINEERING MANUAL

3
CeilAiR ENGINEERING MANUAL

OHS Model: 012/040-( ) 012/040-H( ) 048/060-( ) 048/120-D( )

SELECTED STANDARD FEATURES


TEMPERATURE CONTROL
Cooling Only Standard Standard Standard Standard
Heating / Reheating Control Optional Optional Optional Optional
HUMIDITY CONTROL
Electrode Canister Steam Humidifier Optional Optional Optional Optional
Dehumidification Mode with Reheat Optional Optional Optional Optional
CONTROLS
A-Tech-1.1 single stage controls Standard Standard Standard N/A
A-Tech-1.2 two stage controls Optional Optional Optional Standard
E² Microprocessor Controller Optional Optional Optional Optional
CABINET
All Aluminum Construction Standard Standard Standard Standard
Insulated SS or Polymer Condensate Drain Pan Standard Standard Standard Standard
1/2", 2 lb Density Thermal & Sound Insulation Standard Standard Standard Standard
Rubber Hanging Vibration Isolators Standard Standard Standard Standard
FILTERS / GRILLES
Spot Coolers with bottom supply / return filter grille Standard N/A N/A N/A
Ducted Units with flanged ducted connections Optional Standard Standard Standard
DX-REFRIGERATION CIRCUIT
R407C Refrigerant Standard Standard Standard Standard
Scroll Type Compressor(s), (unless otherwise noted) Standard Standard Standard Standard
High Efficiency, Aluminum Fin / Copper Tube Coils Standard Standard Standard Standard
Thermal Expansion Valve Standard Standard Standard Standard
Refrigerant Sight Glass & Filter/Drier Strainer Standard Standard Standard Standard
Refrigerant Service Valves Standard Standard Standard Standard
BLOWERS / MOTORS
Direct-Drive Evaporator Motors Standard N/A N/A N/A
Belt-Drive Evaporator Motors N/A Standard Standard Standard
ELECTRICAL
Power Supply ------------------------- See Electrical Tables ----------------------
Multi-Voltage Control Transformer (24V Class II) Standard Standard Standard Standard
Individual Motor Starter(s) / Contactor(s) Standard Standard Standard Standard
SAFETY FEATURES
Condensate Pan Overflow Safety Switch(es) Standard Standard Standard Standard
High / Low Refrigerant Pressure Switches (DX units) Standard Standard Standard Standard
Motor Overcurrent and Overload Protection Per UL 1995 Standard Standard Standard Standard

SPECIFIC MODEL STANDARD FEATURES


AIR COOLED
Low Ambient Head Pressure Control --------Three types available 0°F, -20°F or -30°F ---------
WATER / GLYCOL COOLED
2-way, 150 psig Water/Glycol Regulating Valves Standard Standard Standard Standard
High Pressure & 3-way Valves Optional Optional Optional Optional
Coaxial, Tube-in-Tube Heat Exchanger Standard Standard Standard Standard
ALL SPLIT DX SYSTEMS
Liquid Line Solenoid Valve to Prevent Liquid Slugging Standard Standard Standard Standard
DUAL CIRCUIT DX SYSTEMS
Two(2) Independent Refrigerant Circuits N/A N/A N/A Standard
Two(2) Equal Horsepower Scroll Compressors (1 per circuit) N/A N/A N/A Standard
A-Tech-1.2 two stage controls N/A N/A N/A Standard
CHILLED WATER SYSTEMS
2-way, 300 psig Motorized Valve Standard Standard Standard Standard
Modulating, High Pressure & 3-way Valves Optional Optional Optional Optional
CODE CONFORMANCE
NRTL Conformance Compliance to UL 1995 Standard Standard Standard Standard Standard
NYC MEA-163-88-E / Chicago Code Approval Standard Standard Standard Standard

4
CeilAiR ENGINEERING MANUAL

Technical Specifications and Performance/Capacity Data

This section contains technical specifications and performance/capacity data tables for the different CeilAiR cooling systems
available from STULZ:
• DX - Air Cooled/Water Cooled/Glycol Cooled Models
• DX with Free Cooling and DX with Alternate Water Source Models
• Chilled Water Models

Common Specification Data


The following technical specification applies to all OHS models:
Condensate drain connections: all OHS-012/040_2X4 units have a ¾ in. PVC pipe. All other units have a ¾ in. FPT
drain fitting.

5
CeilAiR ENGINEERING MANUAL

Direct Expansion Air/Water/Glycol-Cooled Models

DX - Self-Contained Air Cooled (AS) 3.5 – 10.5 kW / Split Air Cooled (AR) Technical Data, 3.5–17.5 kW
Model OHS- 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-AR
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 5 5 5 5 5 10 10
Optional Heater, kW N/A N/A N/A N/A N/A N/A N/A
Hot Gas Reheat
Total Capacity, kW (MBH) 3.3 (11.4) 5 (17) 6.2 (21.2) 7.5 (25.7) 9.1 (30.9) 14.5 (49.3) 15.9 (54.2)
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 6.1 (20.7) 9.5 (32.4) 10.2 (34.9) 14.8 (50.4) 16.2 (55.3) 28.5 (97.1) 32.6 (111.2)
Flow rate, GPM 1 2 2 3 3 4 5
Pressure Drop, ftH2O-Coil 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 3.5 (12) 5.3 (18) 7 (24) 9.4 (32) 11.7 (40) 14.1 (48) 17.6 (60)
Condensate, lb/hr 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 2–5 2-5 2-5 2-5 2-5 4-10 4-10
Power Input, kW 1.7 1.7 1.7 1.7 1.7 3.4 3.4
Standard Control Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Nominal Horsepower, hp 1/4 1/4 1/4 1/3 1/2 1 1 1/2
Rated Airflow ft /min @ inH2O ESP
3
500 @ 0.3 750 @ 0.3 900 @ 0.3 1000 @ 0.3 1415 @ 0.3 2200 @ 0.5 2500 @ 0.5
Standard Drive Method Direct Direct Direct Direct Direct Belt Belt
Optional Drive Method Belt Belt Belt Belt Belt N/A N/A
-

Evaporator Coil - Aluminum Fin, Copper Tube


Rows 3 3 3 3 3 4 4
Face Area, ft 2
2.1 2.1 2.1 2.8 2.8 5.0 5.0
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Quantity 1 1 1 1 1 1 1
Input, kW 1.4 1.6 2.1 2.7 2.8 4.4 5
Total Heat of Rejection, kW (MBH) 5.2 (17.6) 7.1 (24.3) 9.2 (31.5) 11.9 (40.5) 12.8 (43.8) 20.5 (70.1) 22.7 (77.4)
Filters - 1 in. deep throwaway
Nominal Size, in. 20×20 20×20 20×20 20×20 20×20 20×16 20×16
Quantity 1 1 1 1 1 2 2
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant: (OHS-012/060-()AR only):
Liquid Line OD, in. 3/8 3/8 3/8 1/2 1/2 1/2 1/2
Quantity 1 1 1 1 1 1 1
Hot Gas Line OD, in. 1/2 1/2 5/8 5/8 7/8 7/8 7/8
Quantity 1 1 1 1 1 1 1
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Wt. (OHS-()-AS), lb 210 215 220 255 265 N/A N/A
Approximate Wt. (OHS-()-AR), lb 160 165 170 205 215 370 380

6
CeilAiR ENGINEERING MANUAL

Air Cooled Condenser Data - (Self Contained)


Model OHS @ 95°F Amb. 012-AS 018-AS 024-AS 032-AS 040-AS 048 060
Integral Centrifugal Blower, Air Cooled Condenser Data for Self-Contained Model OHS-( )-AS
Condenser Blower Data
Rated Airflow, ft3/min @ inH2O ESP 750 @ 0.3 1400 @ 0.3 1400 @ 0.3 2000 @ 0.3 2000 @ 0.3 N/A N/A
Nominal Horsepower, hp 1/3 1/2 1/2 1/2 1/2 N/A N/A
Drive Method Direct Direct Direct Direct Direct N/A N/A
Condenser Coil:
Rows 4 4 4 4 4 N/A N/A
Face Area, ft 2
2.1 2.1 2.1 2.8 2.8 N/A N/A
Low Ambient Control
Standard Min. Op. Amb., °F 0 0 0 0 0 N/A N/A
Head Pressure Method Motor Speed Motor Speed Motor Speed Motor Speed Motor Speed N/A N/A

NOTES:
Compressor is integral to the OHS-( )-AS Self-Contained Unit.

Refer to the STULZ Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and
Indoor Air Cooled Condensers used with OHS-( )-()AR Split Systems.

-
DX Dual Compressor- Split Air Cooled Remote w/ Condenser Technical Data, 14–35 kW
Model OHS- 048-DAR 072-DAR 084-DAR 120-DAR
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Hot Gas Reheat
Total Capacity, kW (MBH) 6.2 (21.2) 9.5 (32.3) 10.9 (37.2) 14.8 (50.5)
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.8 (50.4) 28.7 (97.9) 29.3 (99.8) 38.2 (130.5)
Flow rate, GPM 3 3 3 10
Pressure Drop, ftH2O-Coil 0.3 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.1 (48) 21.1 (72) 26.4 (90) 35.2 (120)
Condensate, lb/hr 50 75 94 125
Control Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 3/4 1 1/2 2 3
Rated Airflow, ft /min @ inH2O ESP
3
1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 4 4 4

Continued on next page

7
CeilAiR ENGINEERING MANUAL

DX Dual Compressor- Split Air Cooled Remote w/ Condenser Technical Data, 14−35 kW (Cont)
Model OHS- 048-DAR 072-DAR 084-DAR 120-DAR
Face Area, ft 2
4.1 6.7 6.7 10
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
Input per Compressor, kW 2.1 2.8 3.8 5.0
Total Heat of Rejection, kW (MBH) 18.5 (63.3) 25.4 (86.6) 32.3 (110.2) 45 (153.4)
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant
Liquid Line OD, in. 3/8 1/2 1/2 1/2
Quantity 2 2 2 2
Hot Gas Line OD, in. 5/8 5/8 7/8, 7/8
Quantity 2 2 2 2
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 420 450 510 580

8
CeilAiR ENGINEERING MANUAL

DX - Split Air Cooled w/Condensing Unit Technical Data, 3.5−17.5 kW


Model OHS- 012-AHU 018-AHU 024-AHU 032-AHU 040-AHU 048-AHU 060-AHU
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 5 5 5 5 5 10 10
Optional Heater, kW N/A N/A N/A N/A N/A N/A N/A
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB:
Total Capacity, kW (MBH) 6.1 (20.7) 9.5 (32.4) 10.2 (34.9) 14.8 (50.4) 16.2 (55.3) 28.5 (97.1) 32.6 (111.2)
Flow Rate, GPM 1 2 2 3 3 4 5
Pressure Drop, ftH2O-Coil 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 3.5 (12) 5.3 (18) 7 (24) 9.4 (32) 11.7 (40) 14.1 (48) 17.6 (60)
Condensate, lb/hr 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 2-5 2-5 2-5 2-5 2-5 4-10 4-10
Power Input, kW 1.7 1.7 1.7 1.7 1.7 3.4 3.4
Standard Control Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Nominal Horsepower, hp 1/4 1/4 1/4 1/3 1/2 1 1 1/2
Rated Airflow, ft3/min @ inH2O ESP 500 @ 0.3 750 @ 0.3 900 @ 0.3 1000 @ 0.3 1415 @ 0.3 2200 @ 0.5 2500 @ 0.5
Standard Drive Method Direct Direct Direct Direct Direct Belt Belt
Optional Drive Method Belt Belt Belt Belt Belt N/A N/A
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 3 3 3 3 4 4
Face Area, ft2 2.1 2.1 2.1 2.8 2.8 5.0 5.0
Filters - 1 in. deep throwaway
Nominal Size, in. 20×20 20×20 20×20 20×20 20×20 20×16 20×16
Quantity 1 1 1 1 1 2 2
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant
Suction OD, in. 5/8 3/4 3/4 3/4 7/8 7/8 7/8
Quantity 1 1 1 1 1 1 1
Liquid Line OD, in. 3/8 3/8 3/8 1/2 1/2 1/2 1/2
Quantity 1 1 1 1 1 1 1
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 120 120 120 155 165 270 280

Refer to the STULZ Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensers

9
CeilAiR ENGINEERING MANUAL

DX Dual Compressor - Split Air Cooled w/Condensing Unit Technical Data, 14−35 kW
Model OHS- 048-DAHU 072-DAHU 084-DAHU 120-DAHU
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.8 (50.4) 28.7 (97.9) 29.3 (99.8) 38.2 (130.5)
Flow rate, GPM 3 3 3 10
Pressure Drop, ftH2O-Coil 0.3 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.1 (48) 21.1 (72) 26.4 (90) 35.2 (120)
Condensate, lb/hr 50 75 94 125
Control Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 3/4 1 1/2 2 3
Rated Airflow, ft /min @ inH2O ESP
3
1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant
Suction Line OD, in. 3/4 7/8 7/8 7/8
Quantity 2 2 2 2
Liquid Line OD, in. 3/8 1/2 1/2 1/2
Quantity 2 2 2 2
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 320 350 410 480

10
CeilAiR ENGINEERING MANUAL

DX- Self-Contained Water Cooled Technical Data, 3.5−17.5 kW


Model OHS- 012-W 018-W 024-W 032-W 040-W 048-W 060-W
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 5 5 5 5 5 10 10
Optional Heater, kW N/A N/A N/A N/A N/A N/A N/A
Hot Gas Reheat
Total Capacity, kW (MBH) 3.6 (12.4) 5.2 (17.7) 6.5 (22.2) 7.9 (27) 9.5 (32.4) 15 (51) 16.4 (56.1)
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 6.1 (20.7) 9.5 (32.4) 10.2 (34.9) 14.8 (50.4) 16.2 (55.3) 28.5 (97.1) 32.6 (111.2)
Flow rate, GPM 1 2 2 3 3 4 5
Pressure Drop, ftH2O - Coil 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 3.5 (12) 5.3 (18) 7 (24) 9.4 (32) 11.7 (40) 14.1 (48) 17.6 (60)
Condensate, lb/hr 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 2–5 2–5 2–5 2–5 2–5 4–10 4–10
Power Input, kW 1.7 1.7 1.7 1.7 1.7 3.4 3.4
Standard Control Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Nominal Horsepower, hp 1/4 1/4 1/4 1/3 1/2 1 1 1/2
Rated Airflow, ft3/min @ inH2O ESP 500 @ 0.3 750 @ 0.3 900 @ 0.3 1000 @ 0.3 1415 @ 0.3 2200 @ 0.5 2500 @ 0.5
Standard Drive Method Direct Direct Direct Direct Direct Belt Belt
Optional Drive Method Belt Belt Belt Belt Belt N/A N/A
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 3 3 3 3 4 4
Face Area, ft2 2.1 2.1 2.1 2.8 2.8 5.0 5.0
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Quantity 1 1 1 1 1 1 1
Input, kW 1.2 1.2 1.6 2.1 2.2 3.4 3.9
Water Cooled Condenser Data - Based on 0% glycol solution
Total Heat of Rejection, kW (MBH) 5.5 (18.9) 7.1 (24.3) 9.4 (32.1) 12.1 (41.3) 13.1 (44.9) 20.7 (70.6) 22.8 (77.9)
GPM @ 85 °F EWT 3.8 4.9 6.4 8.3 9.0 14.1 15.6
Pressure Drop, ftH2O-Total Unit 10.0 6.5 11.0 11.7 13.9 16.5 22.7
Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial
Head Pressure Control
Standard Control - 2-way, 150 psi Water Regulating Valve, (factory installed)
Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Source Water In/Out OD, in. 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8
Filters - 1 in. deep throwaway
Nominal Size, in. 20×20 20×20 20×20 20×20 20×20 20×16 20×16
Quantity 1 1 1 1 1 2 2
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 180 200 210 245 260 395 405

11
CeilAiR ENGINEERING MANUAL

DX Dual Compressor - Self-Contained Water Cooled Technical Data, 14−35 kW


Model OHS- 048-DW 072-DW 084-DW 120-DW
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Hot Gas Reheat
Total Capacity, kW (MBH) 6.4 (21.9) 9.7 (33.2) 11.2 (38.2) 15.4 (52.5)
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.8 (50.4) 28.7 (97.9) 29.3 (99.8) 38.2 (130.5)
Flow rate, GPM 3 3 3 10
Pressure Drop, ftH2O-Coil 0.3 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.1 (48) 21.1 (72) 26.4 (90) 35.2 (120)
Condensate, lb/hr 50 75 94 125
Control Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 3/4 1 1/2 2 3
Rated Airflow, ft3/min @ inH2O ESP 1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
Input per Compressor, kW 1.6 2.2 3 3.9
Water Cooled Condenser Data - Based on 0% glycol solution
Total Heat of Rejection, kW (MBH) 18.6 (63.5) 25.6 (87.4) 32.5 (110.8) 45.2 (154.1)
GPM @ 85 °F EWT 12.7 17.5 22.2 30.8
Pressure Drop, ftH2O-Total Unit 12.4 17.9 12.4 25.7
Type Coaxial Coaxial Coaxial Coaxial
Head Pressure Control
Standard Control - 2-way, 150 psi Water Regulating Valve, (factory installed)
Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4
Source Water Inlet/Outlet OD, in. 1 1/8 1 1/8 1 3/8 1 3/8
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 440 470 550 625

12
CeilAiR ENGINEERING MANUAL

DX - Self-Contained Glycol Cooled Technical Data, 3.5−17.5 kW


Model OHS- 012-G 018-G 024-G 032-G 040-G 048-G 060-G
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 5 5 5 5 5 10 10
Optional Heater, kW N/A N/A N/A N/A N/A N/A N/A
Hot Gas Reheat
Total Capacity, kW (MBH) 3.3 (11.3) 4.9 (16.8) 6.1 (20.9) 7.4 (25.3) 9 (30.6) 14.1 (48.2) 15.5 (52.9)
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 6.1 (20.7) 9.5 (32.4) 10.2 (34.9) 14.8 (50.4) 16.2 (55.3) 28.5 (97.1) 32.6 (111.2)
Flow rate, GPM 1 2 2 3 3 4 5
Pressure Drop, ftH2O-Coil 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 3.5 (12) 5.3 (18) 7 (24) 9.4 (32) 11.7 (40) 14.1 (48) 17.6 (60)
Condensate, lb/hr 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 2-5 2-5 2-5 2-5 2-5 4-10 4-10
Power Input, kW 1.7 1.7 1.7 1.7 1.7 3.4 3.4
Standard Control Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Nominal Horsepower, hp 1/4 1/4 1/4 1/3 1/2 1 1 1/2
Rated Airflow, ft3/min @ inH2O ESP 500 @ 0.3 750 @ 0.3 900 @ 0.3 1000 @ 0.3 1415 @ 0.3 2200 @ 0.5 2500 @ 0.5
Standard Drive Method Direct Direct Direct Direct Direct Belt Belt
Optional Drive Method Belt Belt Belt Belt Belt N/A N/A
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 3 3 3 3 4 4
Face Area, ft2 2.1 2.1 2.1 2.8 2.8 5.0 5.0
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Quantity 1 1 1 1 1 1 1
Input, kW 1.4 1.7 2.2 2.9 3 4.7 5.3
Glycol Condenser Data - Based on 40% ethylene glycol solution
Total Heat of Rejection, kW (MBH) 5.1 (17.3) 7.0 (24) 9.2 (31.3) 11.8 (40.3) 12.8 (43.6) 20 (68.4) 20 (75.4)
GPM @ 110 °F EGT 3.8 5.3 6.9 8.9 9.7 15.1 16.7
Pressure Drop, ftH2O-Total Unit 10.1 7.0 11.8 12.8 15.2 18.0 24.5
Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial
Head Pressure Control
Standard Control - 2-way, 150 psi Glycol Regulating Valve, (factory installed)
Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Source Glycol In/Out OD, in. 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8
Filters - 1 in. deep throwaway
Nominal Size, in. 20×20 20×20 20×20 20×20 20×20 20×16 20×16
Quantity 1 1 1 1 1 2 2
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 180 200 210 245 260 395 405

13
CeilAiR ENGINEERING MANUAL

DX Dual Compressor - Self-Contained Glycol Cooled Technical Data, 14−35 kW


Model OHS- 048-DG 072-DG 084-DG 120-DG
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Hot Gas Reheat
Total Capacity, kW (MBH) 6 (20.6) 9.3 (31.6) 10.7 (36.4) 14.5 (49.3)
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.8 (50.4) 28.7 (97.9) 29.3 (99.8) 38.2 (130.5)
Flow rate, GPM 3 3 3 10
Pressure Drop, ftH2O-Coil 0.3 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.1 (48) 21.1 (72) 26.4 (90) 35.2 (120)
Condensate, lb/hr 50 75 94 125
Control Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 3/4 1 1/2 2 3
Rated Airflow, ft /min @ inH2O ESP
3
1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 4 4 4
Face Area , ft2 4.1 6.7 6.7 10.0
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
Input per Compressor, kW 2.2 3 4.1 5.3
Glycol Condenser Data - Based on 40% ethylene glycol solution
Total Heat of Rejection, kW (MBH) 18.1 (61.8) 24.7 (84.4) 31.5 (107.6) 43.7 (149.2)
GPM @ 110 °F EGT 13.7 18.7 23.8 33.0
Pressure Drop, ftH2O-Total Unit 13.6 20.0 13.9 28.1
Type Coaxial Coaxial Coaxial Coaxial
Head Pressure Control
Standard Control - 2-way, 150 psi Glycol Regulating Valves, (factory installed)
Optional Control - Refer to the Optional Guide Specifications Section for High Pressure and 3-way Valve Options
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4
Source Glycol Inlet/Outlet OD, in. 1 1/8 1 1/8 1 3/8 1 3/8
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 440 470 550 625

14
CeilAiR ENGINEERING MANUAL

DX - Self-Contained Air Cooled (AS) 3.5 - 10.5 kW / Split Air Cooled Cooling Capacities, 3.5–17.5 kW
Model OHS- 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-AR
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft /min and ESP ratings)
3

80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 4.1 (14) 5.7 (19.5) 7.5 (25.7) 9.6 (32.8) 10.5 (35.8) 17.6 (60) 19.3 (66)
Sensible, kW (MBH) 3.1 (10.6) 4.5 (15.2) 5.7 (19.5) 6.9 (23.4) 8.2 (28) 14 (47.7) 15.4 (52.4)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 3.7 (12.7) 5.3 (18) 6.9 (23.6) 8.8 (30) 9.6 (32.7) 16.1 (55) 17.7 (60.5)
Sensible, kW (MBH) 3.1 (10.6) 4.5 (15.4) 5.6 (19) 6.7 (22.9) 8 (27.4) 13.8 (47) 15.1 (51.6)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 3.5 (12) 5 (17.2) 6.6 (22.5) 8.4 (28.5) 9.1 (31.1) 15.4 (52.4) 16.9 (57.6)
Sensible, kW (MBH) 3 (10.4) 4.4 (15.1) 5.4 (18.6) 6.6 (22.4) 7.8 (26.7) 13.5 (46) 14.8 (50.6)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 3.9 (13.4) 5.5 (18.9) 7.2 (24.6) 9.2 (31.3) 10.2 (34.7) 16.9 (57.7) 18.6 (63.4)
Sensible, kW (MBH) 3.5 (11.8) 5 (17) 6.1 (20.9) 7.3 (24.9) 9.1 (30.9) 15.3 (52.1) 16.8 (57.3)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6.7 (23) 8.5 (28.9) 9.4 (32.1) 15.7 (53.4) 17.2 (58.6)
Sensible, kW (MBH) 3.3 (11.4) 4.8 (16.4) 6 (20.5) 7 (23.9) 8.7 (29.7) 14.7 (50.3) 16.2 (55.3)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.4 (11.6) 4.9 (16.7) 6.4 (22) 8 (27.4) 8.9 (30.5) 14.9 (50.9) 16.4 (55.8)
Sensible, kW (MBH) 3.3 (11.1) 4.7 (16.1) 5.9 (20.1) 6.9 (23.6) 8.5 (29) 14.4 (49.2) 15.8 (54.1)

DX Dual Compressor- Split Air Cooled Remote w/ Condenser Cooling Capacities, 14−35 kW
Model OHS- 048-DAR 072-DAR 084-DAR 120-DAR
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 15.8 (53.7) 21.7 (73.9) 27 (92.1) 38.2 (130.4)
Sensible, kW (MBH), kW (MBH) 12 (40.9) 18.2 (62.1) 20.8 (71.1) 28.7 (98)
75 ° F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 14.4 (49.3) 19.8 (67.6) 24.6 (84) 35 (119.6)
Sensible, kW (MBH), kW (MBH) 11.8 (40.3) 18 (61.5) 20.8 (70.8) 28.2 (96.2)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 13.8 (47) 18.8 (64.3) 23.4 (79.8) 33.2 (113.4)
Sensible, kW (MBH) 11.6 (39.5) 17.6 (60.2) 20.4 (69.6) 27.7 (94.6)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 15.1 (51.6) 20.7 (70.7) 25.7 (87.7) 36.6 (124.9)
Sensible, kW (MBH) 13 (44.3) 20 (68.1) 23.2 (79.1) 31.2 (106.5)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 14 (47.9) 19.2 (65.6) 23.7 (80.8) 33.9 (115.5)
Sensible, kW (MBH) 12.6 (42.8) 18.8 (64.1) 22.3 (76.2) 30.1 (102.9)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 13.4 (45.6) 18.4 (62.8) 22.5 (76.7) 32.2 (110)
Sensible, kW (MBH) 12.3 (42) 18.1 (61.9) 21.6 (73.7) 29.6 (100.9)

15
CeilAiR ENGINEERING MANUAL

DX - Split Air Cooled w/Condensing Unit Cooling Capacities, 3.5−17.5 kW


Model OHS- 012-AHU 018-AHU 024-AHU 032-AHU 040-AHU 048-AHU 060-AHU
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 4.1 (14) 5.7 (19.5) 7.5 (25.7) 9.7 (32.9) 10.7 (36.5) 17.6 (60) 19.3 (66)
Sensible, kW (MBH) 3.1 (10.6) 4.5 (15.2) 5.7 (19.5) 7.2 (24.6) 8.8 (30.1) 14 (47.7) 15.4 (52.4)
75 °F DB / 62.5 °F WB, 50% RH

Total, kW (MBH) 3.7 (12.7) 5.3 (18) 6.9 (23.6) 8.9 (30.4) 9.9 (33.8) 16.1 (55) 17.7 (60.5)
Sensible, kW (MBH) 3.1 (10.6) 4.5 (15.4) 5.6 (19) 7.1 (24.2) 8.6 (29.3) 13.8 (47) 15.1 (51.6)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 3.5 (12) 5 (17.2) 6.6 (22.5) 8.5 (29) 9.5 (32.3) 15.4 (52.4) 16.9 (57.6)
Sensible, kW (MBH) 3 (10.4) 4.4 (15.1) 5.4 (18.6) 6.9 (23.7) 8.4 (28.5) 13.5 (46) 14.8 (50.6)
80 °F DB / 65°F WB, 45% RH
Total, kW (MBH) 3.9 (13.4) 5.5 (18.9) 7.2 (24.6) 9.3 (31.7) 10.3 (35.1) 16.9 (57.7) 18.6 (63.4)
Sensible, kW (MBH) 3.5 (11.8) 5 (17) 6.1 (20.9) 8.1 (27.6) 9.8 (33.4) 15.3 (52.1) 16.8 (57.3)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6.7 (23) 8.6 (29.5) 9.6 (32.8) 15.7 (53.4) 17.2 (58.6)
Sensible, kW (MBH) 3.3 (11.4) 4.8 (16.4) 6 (20.5) 7.7 (26.3) 9.2 (31.5) 14.7 (50.3) 16.2 (55.3)
72°F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.4 (11.6) 4.9 (16.7) 6.4 (22) 8.3 (28.2) 9.2 (31.4) 14.9 (50.9) 16.4 (55.8)
Sensible, kW (MBH) 3.3 (11.1) 4.7 (16.1) 5.9 (20.1) 7.5 (25.6) 8.9 (30.5) 14.4 (49.2) 15.8 (54.1)

DX Dual Compressor - Split Air Cooled w/Condensing Unit Cooling Capacities, 14−35 kW
Model OHS- 048-DAHU 072-DAHU 084-DAHU 120-DAHU
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °FWB, 50% RH
Total, kW (MBH) 15.8 (53.7) 21.7 (73.9) 27 (92.1) 38.2 (130.4)
Sensible, kW (MBH) 12 (40.9) 18.2 (62.1) 20.8 (71.1) 28.7 (98)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 14.4 (49.3) 19.8 (67.6) 24.6 (84) 35 (119.6)
Sensible, kW (MBH) 11.8 (40.3) 18 (61.5) 20.8 (70.8) 28.2 (96.2)
72 °F DB/ 60 °F WB, 50% RH
Total, kW (MBH) 13.8 (47) 18.8 (64.3) 23.4 (79.8) 33.2 (113.4)
Sensible, kW (MBH) 11.6 (39.5) 17.6 (60.2) 20.4 (69.6) 27.7 (94.6)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 15.1 (51.6) 20.7 (70.7) 25.7 (87.7) 36.6 (124.9)
Sensible, kW (MBH) 13 (44.3) 20 (68.1) 23.2 (79.1) 31.2 (106.5)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 14 (47.9) 19.2 (65.6) 23.7 (80.8) 33.9 (115.5)
Sensible, kW (MBH) 12.6 (42.8) 18.8 (64.1) 22.3 (76.2) 30.1 (102.9)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 13.4 (45.6) 18.4 (62.8) 22.5 (76.7) 32.2 (110)
Sensible, kW (MBH) 12.3 (42) 18.1 (61.9) 21.6 (73.7) 29.6 (100.9)

16
CeilAiR ENGINEERING MANUAL

DX- Self-Contained Water Cooled Cooling Capacities, 3.5−17.5 kW


Model OHS- 012-W 018-W 024-W 032-W 040-W 048-W 060-W
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft /min and ESP ratings)
3

80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 4.8 (16.4) 6.2 (21.1) 8.2 (28) 10.4 (35.6) 11.5 (39.1) 18.8 (64.3) 20.7 (70.7)
Sensible, kW (MBH) 3.4 (11.7) 4.7 (16) 6 (20.5) 7.2 (24.6) 8.6 (29.5) 14.4 (49.2) 15.9 (54.1)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 4.4 (14.9) 5.7 (19.3) 7.5 (25.8) 9.6 (32.7) 10.5 (35.8) 17.2 (58.8) 19 (64.7)
Sensible, kW (MBH) 3.3 (11.3) 4.6 (15.6) 5.9 (20.1) 7.1 (24.3) 8.4 (28.8) 14.2 (48.6) 15.7 (53.4)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 4.1 (14) 5.4 (18.4) 7.2 (24.6) 9.1 (31.2) 10 (34.1) 16.4 (56.1) 18.1 (61.7)
Sensible, kW (MBH) 3.2 (11.1) 4.8 (16.4) 5.8 (19.7) 7 (23.8) 8.2 (28.1) 14 (47.6) 15.3 (52.3)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 4.6 (15.6) 6 (20.4) 7.9 (26.8) 10 (34.2) 10.9 (37.4) 18.1 (61.6) 19.9 (67.7)
Sensible, kW (MBH) 3.6 (12.4) 5.2 (17.6) 6.4 (21.8) 7.7 (26.3) 9.3 (31.6) 15.7 (53.6) 17.3 (59)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 4.2 (14.4) 5.6 (19) 7.3 (24.9) 9.3 (31.6) 10.3 (35.1) 16.7 (57.1) 18.4 (62.8)
Sensible, kW (MBH) 3.6 (12.3) 5 (17) 6.2 (21.1) 7.4 (25.4) 9 (30.6) 15.2 (51.8) 16.7 (57)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 4 (13.6) 5.3 (18.1) 6.9 (23.7) 8.8 (30.1) 9.8 (33.5) 16 (54.5) 17.5 (59.8)
Sensible, kW (MBH) 3.5 (12) 4.9 (16.7) 6.1 (20.7) 7.3 (24.8) 8.9 (30.5) 14.9 (50.8) 16.4 (55.9)

DX Dual Compressor - Self-Contained Water Cooled Cooling Capacities, 14−35 kW


Model OHS- 048-DW 072-DW 084-DW 120-DW
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 16.8 (57.2) 23.2 (79.2) 28.9 (98.8) 40.8 (139.2)
Sensible, kW (MBH) 12.4 (42.3) 18.7 (63.8) 21.6 (73.7) 29.8 (101.7)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 15.4 (52.6) 21.3 (72.5) 26.5 (90.5) 37.4 (127.7)
Sensible, kW (MBH) 12.2 (41.6) 18.5 (63.2) 21.3 (72.8) 29.3 (100)
72°F DB / 60 °F WB, 50% RH
Total, kW (MBH) 14.7 (50.1) 20.2 (69) 25.2 (86.1) 35.6 (121.6)
Sensible, kW (MBH) 12 (40.8) 18.2 (62) 20.9 (71.4) 28.7 (98)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 16.1 (54.9) 22.2 (75.8) 27.6 (94.3) 39.1 (133.3)
Sensible, kW (MBH) 13.4 (45.7) 20.6 (70.4) 23.8 (81.2) 32.3 (110.1)
75 °F DB / 61°F WB, 45% RH
Total, kW (MBH) 14.9 (51) 20.6 (70.2) 25.5 (87.1) 36.2 (123.5)
Sensible, kW (MBH) 12.9 (44.2) 19.8 (67.7) 23.1 (78.7) 31.2 (106.3)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 14.2 (48.6) 19.6 (66.8) 24.3 (82.8) 34.5 (117.6)
Sensible, kW (MBH) 12.7 (43.4) 19.1 (65.2) 22.7 (77.3) 30.6 (104.3)

17
CeilAiR ENGINEERING MANUAL

DX - Self-Contained Glycol Cooled Cooling Capacities, 3.5−17.5 kW


Model OHS- 012-G 018-G 024-G 032-G 040-G 048-G 060-G
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67°F WB, 50% RH
Total, kW (MBH) 3.9 (13.4) 5.6 (19) 7.4 (25.1) 9.4 (32) 10.2 (34.9) 16.7 (57.2) 18.4 (62.7)
Sensible, kW (MBH) 3.1 (10.4) 4.4 (15.1) 5.6 (19.2) 6.8 (23.1) 8.1 (27.5) 13.6 (46.6) 15 (51.1)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 3.6 (12.2) 5.1 (17.5) 6.7 (23) 8.3 (28.2) 9.3 (31.9) 15.3 (52.3) 16.8 (57.3)
Sensible, kW (MBH) 3.1 (10.5) 4.5 (15.2) 5.5 (18.7) 6.9 (23.7) 7.9 (27) 13.5 (45.9) 14.8 (50.4)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 3.4 (11.5) 4.9 (16.7) 6.4 (21.9) 8.1 (27.8) 9 (30.5) 14.6 (49.8) 16 (54.5)
Sensible, kW (MBH) 3 (10.2) 4.4 (14.9) 5.4 (18.3) 6.5 (22) 7.8 (26.5) 13.2 (45) 14.5 (49.4)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 3.8 (12.9) 5.4 (18.4) 7 (24) 9 (30.6) 9.9 (33.8) 16.1 (54.9) 17.6 (60.1)
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.8) 6 (20.5) 7.2 (24.5) 8.9 (30.5) 15 (51.1) 16.5 (56.1)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 3.5 (11.8) 5 (17) 6.6 (22.4) 8.3 (28.2) 9.2 (31.3) 14.9 (50.8) 16.3 (55.6)
Sensible, kW (MBH) 3.3 (11.2) 4.7 (16.2) 5.9 (20.2) 6.9 (23.7) 8.6 (29.3) 14.4 (49.1) 15.8 (53.9)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.3 (11.1) 4.8 (16.2) 6.3 (21.4) 7.9 (27.1) 8.7 (29.8) 14.2 (48.4) 15.4 (52.7)
Sensible, kW (MBH) 3.2 (10.9) 4.6 (15.9) 5.8 (19.8) 6.9 (23.4) 8.4 (28.6) 14 (47.7) 15.2 (51.9)

DX Dual Compressor - Self-Contained Glycol Cooled Cooling Capacities, 14−35 kW


Model OHS- 048-DG 072-DG 084-D 120-DG
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft /min and ESP ratings)
3

80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 15 (51.3) 20.6 (70.2) 25.6 (87.4) 36.3 (124)
Sensible, kW (MBH) 11.6 (39.7) 17.9 (61) 20.4 (69.5) 27.9 (95.3)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 13.7 (46.8) 18.8 (64.1) 23.3 (79.6) 33.1 (113)
Sensible, kW (MBH) 11.5 (39.2) 17.6 (60.2) 20.3 (69.4) 27.5 (93.9)
72 °F DB/ 60 °F WB, 50% RH
Total, kW (MBH) 13.1 (44.6) 17.9 (61) 22.2 (75.6) 31.5 (107.5)
Sensible, kW (MBH) 11.3 (38.4) 17.2 (58.5) 20 (68.1) 26.9 (91.9)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 14.4 (49.2) 19.7 (67.3) 24.3 (83.1) 34.8 (118.7)
Sensible, kW (MBH) 12.7 (43.3) 19.2 (65.4) 22.7 (77.4) 30.5 (104.1)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 13.3 (45.5) 18.4 (62.6) 22.5 (76.6) 32.1 (109.6)
Sensible, kW (MBH) 12.3 (41.8) 18.1 (61.8) 21.5 (73.4) 29.4 (100.4)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 12.7 (43.3) 17.5 (59.9) 21.4 (73.2) 30.5 (104.2)
Sensible, kW (MBH) 12 (41) 17.5 (59.6) 20.8 (71.1) 28.8 (98.4)

18
CeilAiR ENGINEERING MANUAL

DX Free Cooling/Alternate Water Source


DX with Free Cooling - Self-Contained Water Cooled Technical Data, 3.5−17.5 kW
Model OHS- 012-HW-FC 018-HW-FC 024-HW-FC 032-HW-FC 040-HW-FC 048-W-FC 060-W-FC
Flow Rates, Free Cooling Coil
Flow Rate, GPM 3.8 4.9 6.4 8.3 9.0 14.1 15.6
Evaporator Blower / Motor, DX w/ Free Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1/4 1/3 1/2 1/2 3/4 1 1/2 2
Rated Airflow, ft /min @ inH2O ESP
3
500 @ 0.5 750 @ 0.5 900 @ 0.5 1000 @ 0.5 1415 @ 0.5 2200 @ 0.5 2500 @ 0.5
Drive Method Belt Belt Belt Belt Belt Belt Belt
Evaporator Coils, (Both DX and Free Cooling Respectively) - Aluminum Fin, Copper Tube
DX Coil
Rows 3 3 3 3 3 4 4
Face Area, ft 2
2.1 2.1 2.1 2.8 2.8 5.0 5.0
FC Coil
Rows 4 4 4 4 4 4 4
Face Area, ft2 2.1 2.1 2.1 2.8 2.8 5.0 5.0
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 5 5 5 5 5 10 10
Optional Heater, kW N/A N/A N/A N/A N/A N/A N/A
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 2-5 2-5 2-5 2-5 2-5 4-10 4-10
Power Input, kW 1.7 1.7 1.7 1.7 1.7 3.4 3.4
Standard Control Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Quantity 1 1 (1 1 1 1 1
Input, kW 1.2 1.2 1.6 2.1 2.2 3.4 3.9
DX Water Cooled Condenser Data - Based on 0% glycol solution
Total Heat of Rejection, kW (MBH) 5.5 (18.9) 7.1 (24.4) 9.4 (32.1) 12.1 (41.3) 13.1 (44.9) 20.7 (70.6) 22.8 (77.9)
GPM @ 85 °F EWT 3.8 4.9 6.4 8.3 9.0 14.1 15.6
Pressure Drop, ftH2O-Total Unit 12.1 16.3 26.9 21.6 25.1 16.5 22.7
Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial
DX-Head Pressure and Free Cooling Coil Control Valve Combinations
DX Head Pressure Control Valve Type - - - - - - - - 3-way, 150 psi DX Condenser Source Regulating Valve - field installed - - - - - - - -
Free Cooling Valve - 3-way, Spring Actuated (Open/Close):
FC Valve Size, in. 1/2 3/4 3/4 3/4 3/4 1 1
Cv 5.0 5.0 5.0 5.0 5.0 7.0 7.0
Valve Pressure Rating, psi 300 300 300 300 300 300 300
Optional Valve Combinations - Please refer to “Free Cooling System Valves” on page 74 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Com-
bination Options.
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Source Water In/Out OD, in. 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8
Filters - 1 in. deep throwaway
Nominal Size, in. 20×16 20×16 20×16 20×20 20×20 20×16 20×16
Quantity 1 1 1 1 1 2 2
Physical Size - (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 245 265 275 300 310 500 510

19
CeilAiR ENGINEERING MANUAL

DX Dual Compressor with Free Cooling - Self-Contained Water Cooled Technical Data, 14−35 kW
Model OHS- 048-DW-FC 072-DW-FC 084-DW-FC 120-DW-FC
Flow Rates, Free Cooling Coil
Flow rate, GPM 12.7 17.5 22.2 30.8
Evaporator Blower / Motor, DX w/ Free Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1 1 1/2 2 3
Rated Airflow, ft3/min @ inH2O ESP 1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coils, (Both DX and Free Cooling Respectively) - Aluminum Fin, Copper Tube
DX Coil:
Rows 4 4 4 4
Face Area, ft 2
4.1 6.7 6.7 10.0
FC Coil:
Rows 4 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
Input per Compressor, kW 2.2 3 4.1 6
DX Water Cooled Condenser Data - Based on 0% glycol solution
Total Heat of Rejection, kW (MBH) 18.6 (63.5) 25.6 (87.4) 32.5 (110.8) 45.2 (154.1)
GPM @ 85 °F EWT 12.7 17.5 22.2 30.8
Pressure Drop, ftH2O-Total Unit 26.8 25.2 28.3 25.7
Type Coaxial Coaxial Coaxial Coaxial
DX-Head Pressure and Free Cooling Coil Control Valve Combinations
DX Head Pressure Valve Type - - - - - - -3-way, 150 psi DX Condenser Source Regulating Valve - field installed - - - - - - -
Free Cooling Valve - 3-way, Spring Actuated (Open/Close):
FC Valve Size, in. 1 1 1 1
Cv 7.0 14.0 14.0 14.0
Valve Pressure Rating, psi 300 400 400 400
Optional Valve Combos - Please refer to “Free Cooling System Valves” on page 74 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve
Combination Options.
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4
Source Water In/Out OD, in. 1 1/8 1 1/8 1 3/8 1 3/8
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Physical Size - (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 550 570 660 745

20
CeilAiR ENGINEERING MANUAL

DX with Free Cooling- Self-Contained Glycol Cooled Technical Data, 3.5−17.5 kW


Model OHS- 012-HG-FC 018-HG-FC 024-HG-FC 032-HG-FC 040-HG-FC 048-G-FC 060-G-FC
Flow Rates, Free Cooling Coil
Flow Rate, GPM 3.8 5.3 6.9 8.9 9.7 15.1 16.7
Evaporator Blower / Motor, DX w/ Free Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1/4 1/3 1/2 1/2 3/4 1 1/2 2
Rated Airflow, ft3/min @ inH2O ESP 500 @ 0.5 750 @ 0.5 900 @ 0.5 1000 @ 0.5 1415 @ 0.5 2200 @ 0.5 2500 @ 0.5
Drive Method Belt Belt Belt Belt Belt Belt Belt
Evaporator Coils, (Both DX and Free Cooling Respectively) - Aluminum Fin, Copper Tube
DX Coil
Rows 3 3 3 3 3 4 4
Face Area, ft2 2.1 2.1 2.1 2.8 2.8 5.0 5.0
FC Coil
Rows 4 4 4 4 4 4 4
Face Area, ft2 2.1 2.1 2.1 2.8 2.8 5.0 5.0
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 5 5 5 5 5 10 10
Optional Heater, kW N/A N/A N/A N/A N/A N/A N/A
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 2-5 2-5 2-5 2-5 2-5 4-10 4-10
Power Input, kW 1.7 1.7 1.7 1.7 1.7 3.4 3.4
Standard Control Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Quantity 1 1 1 1 1 1 1
Input, kW 1.4 1.7 2.2 2.9 3 4.7 5.3
DX Glycol Condenser Data - Based on 40% ethylene glycol solution
Total Heat of Rejection kW (MBH) 5.1 (17.3) 7 (24) 9.2 (31.3) 11.8 (40.3) 12.8 (43.6) 20 (68.4) 22.1 (75.4)
GPM @ 110 °F EGT 3.8 5.3 6.9 8.9 9.7 15.1 16.7
Pressure Drop, ftH2O-Total Unit. 11.8 21.1 38.4 28.1 34.3 20.1 24.9
Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial
DX-Head Pressure and Free Cooling Coil Control Valve Combinations
DX Head Pressure Valve Type - - - - - - - 3-way, 150 psi DX Condenser Source Regulating Valve - field installed - - - - - - -
Free Cooling Valve - 3-way, Spring Actuated (Open/Close):
FC Valve Size , in. 1/2 3/4 3/4 3/4 3/4 1 1
Cv 5.0 5.0 5.0 5.0 5.0 7.0 7.0
Valve Pressure Rating, psi 300 300 300 300 300 300 300
Optional Valve Combinations - Please refer to “Free Cooling System Valves” on page 74 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve
Combination Options
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Source Glycol In/Out OD, in. 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8
Filters - 1 in. deep throwaway
Nominal Size, in. 20×20 20×20 20×20 20×20 20×20 20×16 20×16
Quantity 1 1 1 1 1 2 2
Physical Size - (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 245 265 275 300 310 500 510
See the Glycol Pump/Drycooler Engineering Manual for drycooler data, optional 105 °F amb. selections and optional glycol pump packages.

21
CeilAiR ENGINEERING MANUAL

DX Dual Compressor with Free Cooling - Self-Contained Glycol Cooled Technical Data, 14−35 kW
Model OHS- 048-DG-FC 072-DG-FC 084-DG-FC 120-DG-FC
Flow Rates, Free Cooling Coil
Flow Rate, GPM 13.7 18.7 23.8 33.0
Evaporator Blower / Motor, DX w/ Free Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1 1 1/2 2 3
Rated Airflow, ft3/min @ inH2O ESP 1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coils, (Both DX and Free Cooling Respectively) - Aluminum Fin, Copper Tube
DX Coil:
Rows 4 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
FC Coil:
Rows 4 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
Input per Compressor, kW 2.2 3 4.1 5.3
DX Glycol Condenser Data - Based on 40% ethylene glycol solution
Total Heat of Rejection, kW (MBH) 18.1 (61.8) 24.7 (84.4) 31.5 (107.6) 43.7 (149.2)
GPM @ 110 °F EGT 13.7 18.7 23.8 33.0
Pressure Drop, ftH2O-Total Unit 37.8 34.8 41.0 29.5
Type Coaxial Coaxial Coaxial Coaxial
DX-Head Pressure and Free Cooling Coil Control Valve Combinations
DX Head Pressure Regulating Valves:
DX Head Pressure Type - - - - - - - - - - -3-way, 150 psi DX Condenser Source Regulating Valve - field installed - - - - - - - - - - -
Free Cooling Valve - 3-way, Spring Actuated (Open/Close):
FC Valve Size, in. 1 1 1 1
Cv 7.0 14.0 14.0 14.0
Valve Pressure Rating, psi 300 400 400 400
Optional Valve Combos - Please refer to “Free Cooling System Valves” on page 74 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combi-
nation Options
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4
Source Glycol In/Out OD, in. 1 1/8 1 1/8 1 3/8 1 3/8
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Physical Size - (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 550 570 660 745
See the Glycol Pump/Drycooler Engineering Manual for drycooler data, optional 105 °F amb. selections, and optional glycol pump packages.

22
CeilAiR ENGINEERING MANUAL

DX with Alternate Water Source Technical Data, 3.5−17.5 kW


Model OHS- 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS 048-AWS 060-AWS
2-way (standard) - Spring Actuated (Open/Close)
Size, in. 1/2 3/4 3/4 3/4 3/4 1.0 1.0
Cv 3.5 3.5 3.7 3.7 3.7 8.0 8.0
Valve Pressure Rating, psi 300 300 300 300 300 300 300
Pressure Drop, ftH2O-Total Unit 8.0 14.6 19.4 14.2 22.6 10.4 12.7
3-way (optional) - Spring Actuated (Open/Close)
Size, in. 1/2 3/4 3/4 3/4 3/4 1.0 1.0
Cv 5.0 5.0 5.0 5.0 5.0 7.0 7.0
Valve Pressure Rating, psi 300 300 300 300 300 300 300
Pressure Drop, ftH2O Total Unit 7.1 12.9 17.0 11.2 17.5 11.8 14.4
Evaporator Coil, Alternate Water Source - Aluminum Fin, Copper Tube
Rows 4 4 4 4 4 4 4
Face Area, ft2 2.1 2.1 2.1 2.8 2.8 5.0 5.0
Evaporator Blower / Motor, Alternate Water Source - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1/4 1/3 1/2 1/2 3/4 1-1/2 2
Rated Airflow, ft3/min @ inH2O ESP 500 @ 0.5 750 @ 0.5 900 @ 0.5 1000 @ 0.5 1415 @ 0.5 2200 @ 0.5 2500 @ 0.5
Drive Method Belt Belt Belt Belt Bel Belt Belt
Connection Sizes, Alternate Water Source - Copper, (@ 75° F DB / 62.5 °F WB EAT flow rate conditions.)
Chilled Water In/Out OD, in. 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8

DX with Alternate Water Source, 14−35 kW


Model OHS- 048D()-AWS 072D()-AWS 084D()-AWS 120D()-AWS
Alternate Water Source Control Valve - Sized for Medium Flow @ 75 °F DB / 62.5 °F WB EAT Conditions
2-way (standard) - Spring Actuated (Open/Close)
Size, in. 1 1 1 1
Cv 8.0 14.0 14.0 4.0
Valve Pressure Rating, psi 300 400 400 400
Pressure Drop, ftH2O-Total Unit 19.4 20.7 24.1 12.5
3-way (optional) - Spring Actuated (Open/Close)
Size, in. 1 1 1 1
Cv 7.0 14.0 14.0 14.0
Valve Pressure Rating, psi 300 400 400 400
Pressure Drop, ftH2O-Total Unit 17.0 20.7 24.1 12.5
Evaporator Coil, Alternate Water Source - Aluminum Fin, Copper Tube
Rows 4 4 4 4
Rows/Face Area, ft2 4.1 6.7 6.7 10.0
Evaporator Blower / Motor, Alternate Water Source - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1 1 1/2 2 3
Rated Airflow, ft3/min @ inH2O ESP 1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Connection Sizes, Alternate Water Source - Copper, (@ 75 °F DB / 62.5 °F WB EAT flow rate conditions.)
Chilled Water In/Out OD, in. 1 1/8 1 1/8 1 1/8 1 3/8

23
CeilAiR ENGINEERING MANUAL

DX with Free Cooling - Self-Contained Water Cooled Cooling Capacities, 3.5−17.5 kW


Model OHS- 012-HW-FC 018-HW-FC 024-HW-FC 032-HW-FC 040-HW-FC 048-W-FC 060-W-FC
DX Cooling Capacity - kW (MBH), (includes standard DX w/ FC evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 4.8 (16.4) 6.2 (21.1) 8.2 (28) 10.4 (35.6) 11.5 (39.1) 18.8 (64.3) 20.7 (70.7)
Sensible, kW (MBH) 3.4 (11.7) 4.7 (16) 6 (20.5) 7.2 (24.6) 8.6 (29.5) 14.4 (49.2) 15.9 (54.1)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 4.4 (14.9) 5.7 (19.3) 7.5 (25.8) 9.6 (32.7) 10.5 (35.8) 17.2 (58.8) 19 (64.7)
Sensible, kW (MBH) 3.3 (11.3) 4.6 (15.6) 5.9 (20.1) 7.1 (24.3) 8.4 (28.8) 14.2 (48.6) 15.7 (53.4)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 4.1 (14) 5.4 (18.4) 7.2 (24.6) 9.1 (31.2) 10 (34.1) 16.4 (56.1) 18.1 (61.7)
Sensible, kW (MBH) 3.2 (11.1) 4.8 (16.4) 5.8 (19.7) 7 (23.8) 8.2 (28.1) 14 (47.6) 15.3 (52.3)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 4.6 (15.6) 6 (20.4) 7.9 (26.8) 10 (34.2) 10.9 (37.4) 18.1 (61.6) 19.9 (67.7)
Sensible, kW (MBH) 3.6 (12.4) 5.2 (17.6) 6.4 (21.8) 7.7 (26.3) 9.3 (31.6) 15.7 (53.6) 17.3 (59)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 4.2 (14.4) 5.6 (19) 7.3 (24.9) 9.3 (31.6) 10.3 (35.1) 16.7 (57.1) 18.4 (62.8)
Sensible, kW (MBH) 3.6 (12.3) 5 (17) 6.2 (21.1) 7.4 (25.4) 9 (30.6) 15.2 (51.8) 16.7 (57)
72°F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 4 (13.6) 5.3 (18.1) 6.9 (23.7) 8.8 (30.1) 9.8 (33.5) 16 (54.5) 17.5 (59.8)
Sensible, kW (MBH) 3.5 (12) 4.9 (16.7) 6.1 (20.7) 7.3 (24.8) 8.9 (30.5) 14.9 (50.8) 16.4 (55.9)
FREE-COOLING CAPACITY - kW (MBH) @ 45°F Entering Water Temperature, 0% Glycol Solution
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 6 (20.6) 8.1 (27.8) 9.7 (33) 11.5 (39.2) 14.1 (48) 22.2 (75.6) 24.5 (83.5)
Sensible, kW (MBH) 4.2 (14.4) 5.9 (20.1) 7 (23.8) 8.2 (28.1) 10.5 (36) 16.4 (56) 18.3 (62.3)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 4.8 (16.2) 6.5 (22.1) 7.7 (26.2) 9.1 (31.1) 11.3 (38.6) 17.7 (60.4) 19.6 (66.8)
Sensible, kW (MBH) 3.8 (13) 5.3 (18.2) 6.3 (21.6) 7.4 (25.3) 9.6 (32.7) 15 (51.1) 16.7 (56.9)
72° F DB /60 °F WB, 50% RH
Total, kW (MBH) 4.1 (14) 5.6 (19.1) 6.6 (22.6) 7.9 (26.8) 9.8 (33.6) 15.3 (52.4) 17 (58)
Sensible, kW (MBH) 3.5 (12) 5 (16.9) 5.9 (20.1) 6.9 (23.4) 8.9 (30.4) 13.9 (47.5) 15.5 (53)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 5.6 (19) 7.6 (25.9) 9 (30.6) 10.7 (36.4) 13.2 (45.2) 20.7 (70.8) 22.9 (78.3)
Sensible, kW (MBH) 4.4 (15.1) 6.2 (21.3) 7.4 (25.2) 8.6 (29.5) 11.2 (38.2) 17.5 (59.6) 19.5 (66.4)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 4.5 (15.4) 6.2 (21) 7.3 (24.8) 8.6 (29.4) 10.8 (36.8) 16.9 (57.6) 18.6 (63.6)
Sensible, kW (MBH) 4 (13.6) 5.6 (19.1) 6.6 (22.6) 7.7 (26.3) 10 (34.2) 15.7 (53.6) 17.5 (59.7)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.9 (13.3) 5.3 (18.1) 6.2 (21.2) 7.5 (25.4) 8.9 (30.3) 14.1 (48.3) 15.7 (53.6)
Sensible, kW (MBH) 3.7 (12.6) 5.2 (17.6) 6.1 (20.9) 7.2 (24.4) 8.9 (30.3) 14.1 (48.3) 15.7 (53.6)

24
CeilAiR ENGINEERING MANUAL

DX Dual Compressor with Free Cooling - Self-Contained Water Cooled Cooling Capacities, 14−35 kW
Model OHS- 048-DW-FC 072-DW-FC 084-DW-FC 120-DW-FC
Net DX Cooling Capacity - kW (MBH), (includes standard DX w/ FC evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 16.8 (57.2) 23.2 (79.2) 28.9 (98.8) 40.8 (139.2)
Sensible, kW (MBH) 12.4 (42.3) 18.7 (63.8) 21.6 (73.7) 29.8 (101.7)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 15.4 (52.6) 21.3 (72.5) 26.5 (90.5) 37.4 (127.7)
Sensible, kW (MBH) 12.2 (41.6) 18.5 (63.2) 21.3 (72.8) 29.3 (100)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 14.7 (50.1) 20.2 (69) 25.2 (86.1) 35.6 (121.6)
Sensible, kW (MBH) 12 (40.8) 18.2 (62) 20.9 (71.4) 28.7 (98)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 16.1 (54.9) 22.2 (75.8) 27.6 (94.3) 39.1 (133.3)
Sensible, kW (MBH) 13.4 (45.7) 20.6 (70.4) 23.8 (81.2) 32.3 (110.1)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 14.9 (51) 20.6 (70.2) 25.5 (87.1) 36.2 (123.5)
Sensible, kW (MBH) 12.9 (44.2) 19.8 (67.7) 23.1 (78.7) 31.2 (106.3)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 14.2 (48.6) 19.6 (66.8) 24.3 (82.8) 34.5 (117.6)
Sensible, kW (MBH) 12.7 (43.4) 19.1 (65.2) 22.7 (77.3) 30.6 (104.3)
FREE-COOLING CAPACITY - kW (MBH) @ 45°F Entering Water Temperature, 0% Glycol Solution
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 19.1 (65) 33.6 (114.5) 37.9 (129.5) 45.7 (155.8)
Sensible, kW (MBH) 13.8 (47.2) 24.2 (82.7) 27.2 (92.9) 33.4 (114)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 15.2 (51.7) 27.2 (92.8) 30.4 (103.8) 36.4 (124)
Sensible, kW (MBH) 12.6 (42.9) 22.3 (75.9) 24.8 (84.7) 30.4 (103.8)
72 °F D B / 60 °F WB, 50% RH
Total, kW (MBH) 13.1 (44.7) 23.8 (81.3) 26.6 (90.6) 31.4 (107.3)
Sensible, kW (MBH) 11.7 (39.9) 20.8 (71) 23.2 (79.2) 28.3 (96.5)
80 °F DB /65 °F WB, 45% RH
Total, kW (MBH) 17.7 (60.5) 31.8 (108.7) 35.7 (121.7) 42.6 (145.4)
Sensible, kW (MBH) 14.7 (50) 26 (88.5) 29 (98.9) 35.5 (121.2)
75°FDB/61°FWB, 45% RH
Total, kW (MBH) 14.4 (49) 26.3 (89.8) 29.2 (99.7) 34.5 (117.9)
Sensible, kW (MBH) 13.2 (44.9) 23.6 (80.4) 26.2 (89.4) 31.9 (108.8)
72°FDB/58.5°FWB, 45% RH
Total, kW (MBH) 12.3 (42) 23.1 (78.9) 25.5 (87.2) 29.6 (100.9)
Sensible, kW (MBH) 12.1 (41.4) 22 (75.1) 24.4 (83.4) 29.4 (100.3)

25
CeilAiR ENGINEERING MANUAL

DX with Free Cooling - Self-Contained Glycol Cooling Capacities, 3.5−17.5 kW


Model OHS- 012-HG-FC 018-HG-FC 024-HG-FC 032-HG-FC 040-HG-FC 048-G-FC 060-G-FC
Net DX Cooling Capacity - kW (MBH), (includes standard DX w/ FC evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 3.9 (13.4) 5.6 (19) 7.4 (25.1) 9.4 (32) 10.2 (34.9) 16.7 (57.2) 18.4 (62.7)
Sensible, kW (MBH) 3.1 (10.4) 4.4 (15.1) 5.6 (19.2) 6.8 (23.1) 8.1 (27.5) 13.6 (46.6) 15 (51.1)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 3.6 (12.2) 5.1 (17.5) 6.7 (23) 8.3 (28.2) 9.3 (31.9) 15.3 (52.3) 16.8 (57.3)
Sensible, kW (MBH) 3.1 (10.5) 4.5 (15.2) 5.5 (18.7) 6.9 (23.7) 7.9 (27) 13.5 (45.9) 14.8 (50.4)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 3.4 (11.5) 4.9 (16.7) 6.4 (21.9) 8.1 (27.8) 9 (30.5) 14.6 (49.8) 16 (54.5)
Sensible, kW (MBH) 3 (10.2) 4.4 (14.9) 5.4 (18.3) 6.5 (22) 7.8 (26.5) 13.2 (45) 14.5 (49.4)
80 °F DB / 65°F WB, 45% RH
Total, kW (MBH) 3.8 (12.9) 5.4 (18.4) 7 (24) 9 (30.6) 9.9 (33.8) 16.1 (54.9) 17.6 (60.1)
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.8) 6 (20.5) 7.2 (24.5) 8.9 (30.5) 15 (51.1) 16.5 (56.1)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 3.5 (11.8) 5 (17) 6.6 (22.4) 8.3 (28.2) 9.2 (31.3) 14.9 (50.8) 16.3 (55.6)
Sensible, kW (MBH) 3.3 (11.2) 4.7 (16.2) 5.9 (20.2) 6.9 (23.7) 8.6 (29.3) 14.4 (49.1) 15.8 (53.9)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.3 (11.1) 4.8 (16.2) 6.3 (21.4) 7.9 (27.1) 8.7 (29.8) 14.2 (48.4) 15.4 (52.7)
Sensible, kW (MBH) 3.2 (10.9) 4.6 (15.9) 5.8 (19.8) 6.9 (23.4) 8.4 (28.6) 14 (47.7) 15.2 (51.9)
FREE-COOLING CAPACITY - kW (MBH) @ 45°F Entering Glycol Temperature, 40% Ethylene Glycol Solution
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 4.7 (16) 6.6 (22.7) 8.1 (27.8) 9.5 (32.4) 11.6 (39.4) 16.7 (57.1) 18.7 (63.7)
Sensible, kW (MBH) 3.7 (12.5) 5.3 (18) 6.4 (21.7) 7.4 (25.1) 9.4 (32.2) 14.2 (48.5) 15.9 (54.3)
75 °F DB /62.5 °F WB, 50% RH
Total, kW (MBH) 3.8 (12.9) 5.3 (18.2) 6.5 (22.2) 7.6 (25.9) 9.3 (31.7) 13.3 (45.4) 14.8 (50.6)
Sensible, kW (MBH) 3.4 (11.5) 4.8 (16.4) 5.8 (19.8) 6.7 (22.8) 8.6 (29.3) 12.9 (44.1) 14.5 (49.3)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 3.3 (11.2) 4.6 (15.7) 5.6 (19.1) 6.6 (22.5) 8 (27.3) 11.7 (40) 13.1 (44.6)
Sensible, kW (MBH) 3.1 (10.7) 4.5 (15.2) 5.4 (18.4) 6.2 (21.2) 7.9 (27) 11.7 (40) 13.1 (44.6)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 4.4 (15.1) 6.3 (21.3) 7.6 (26) 8.9 (30.4) 10.9 (37.1) 15.6 (53.2) 17.4 (59.3)
Sensible, kW (MBH) 3.9 (13.4) 5.6 (19.2) 6.8 (23.1) 7.8 (26.6) 10 (34.3) 15.1 (51.7) 16.9 (57.8)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 3.6 (12.2) 4.9 (16.8) 6.1 (20.8) 7.2 (24.6) 8.6 (29.4) 13 (44.5) 14.5 (49.6)
Sensible, kW (MBH) 3.5 (12) 4.9 (16.8) 6 (20.6) 7 (23.8) 8.6 (29.4) 13 (44.5) 14.5 (49.6)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.1 (10.7) 4.5 (15.3) 5.4 (18.5) 6.2 (21) 7.7 (26.4) 11.7 (39.9) 13 (44.5)
Sensible, kW (MBH) 3.1 (10.7) 4.5 (15.3) 5.4 (18.5) 6.2 (21) 7.7 (26.4) 11.7 (39.9) 13 (44.5)

26
CeilAiR ENGINEERING MANUAL

DX Dual Compressor with Free Cooling - Self-Contained Glycol Cooling Capacities, 14−35 kW
Model OHS- 048-DG-FC 072-DG-FC 084-DG-FC 120-DG-FC
Net DX Cooling Capacity - kW (MBH), (includes standard DX w/ FC evaporator motor heat @ std ft /min and ESP ratings)
3

80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 15 (51.3) 20.6 (70.2) 25.6 (87.4) 36.3 (124)
Sensible, kW (MBH) 11.6 (39.7) 17.9 (61) 20.4 (69.5) 27.9 (95.3)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 13.7 (46.8) 18.8 (64.1) 23.3 (79.6) 33.1 (113)
Sensible, kW (MBH) 11.5 (39.2) 17.6 (60.2) 20.3 (69.4) 27.5 (93.9)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 13.1 (44.6) 17.9 (61) 22.2 (75.6) 31.5 (107.5)
Sensible, kW (MBH) 11.3 (38.4) 17.2 (58.5) 20 (68.1) 26.9 (91.9)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 14.4 (49.2) 19.7 (67.3) 24.3 (83.1) 34.8 (118.7)
Sensible, kW (MBH) 12.7 (43.3) 19.2 (65.4) 22.7 (77.4) 30.5 (104.1)
75 °F DB / 61°F WB, 45% RH
Total, kW (MBH) 13.3 (45.5) 18.4 (62.6) 22.5 (76.6) 32.1 (109.6)
Sensible, kW (MBH) 12.3 (41.8) 18.1 (61.8) 21.5 (73.4) 29.4 (100.4)
72 °F DB / 58.5°F WB, 45% RH
Total, kW (MBH) 12.7 (43.3) 17.5 (59.9) 21.4 (73.2) 30.5 (104.2)
Sensible, kW (MBH) 12 (41) 17.5 (59.6) 20.8 (71.1) 28.8 (98.4)
FREE-COOLING CAPACITY - kW (MBH) @ 45°F Entering Glycol Temperature, 40% Ethylene Glycol Solution
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 15.9 (54.1) 26.1 (89) 31.1 (106) 35.1 (119.7)
Sensible, kW (MBH) 12.5 (42.7) 21.2 (72.4) 24.4 (83.3) 29.1 (99.4)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 12.7 (43.3) 21.2 (72.3) 25.2 (85.8) 28.1 (95.7)
Sensible, kW (MBH) 11.4 (39.1) 19.5 (66.7) 22.5 (76.7) 26.6 (90.9)
72 °F DB / 60°F WB, 50% RH
Total, kW (MBH) 10.9 (37.3) 18.3 (62.4) 21.9 (74.6) 24.1 (82.1)
Sensible, kW (MBH) 10.6 (36.2) 18.1 (61.8) 20.9 (71.4) 24.1 (82.1)
80 °F DB / 65°F WB, 45% RH
Total, kW (MBH) 14.9 (50.8) 24.9 (85) 29.5 (100.8) 32.9 (112.3)
Sensible, kW (MBH) 13.4 (45.7) 22.9 (78.1) 26.3 (89.7) 31.2 (106.3)
75 °F DB / 61°F WB, 45% RH
Total, kW (MBH) 11.7 (39.9) 20 (68.4) 23.9 (81.7) 27.1 (92.4)
Sensible, kW (MBH) 11.7 (39.9) 20 (68.4) 23.9 (81.7) 27.1 (92.4)
72 °F DB / 58.5°F WB, 45% RH
Total, kW (MBH) 10.6 (36.3) 18 (61.3) 21 (71.5) 24.3 (82.8)
Sensible, kW (MBH) 10.6 (36.3) 18 (61.3) 21 (71.5) 24.3 (82.8)

27
CeilAiR ENGINEERING MANUAL

DX with Alternate Water Source Cooling Capacities, 3.5−17.5 kW


Model OHS- 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS 048-AWS 060-AWS
Gross Cooling Capacity - kW (MBH) @ 45 °F EWT, 0% Glycol Solution (includes motor heat @ std ft3/min and ESP ratings).
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 6.7 (23) 9.1 (31) 10.3 (35.3) 11.9 (40.7) 15.2 (51.8) 24.5 (83.4) 26.6 (90.8)
High Flow
Sensible, kW (MBH) 4.5 (15.3) 6.3 (21.4) 7.2 (24.6) 8.39 (28.6) 11.0 (37.5) 17.3 (58.9) 19.0 (64.9)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.8 (19.6) 7.8 (34.0) 8.8 (43.1) 10.2 (23.3) 13.0 (36.8) 20.9 (18.6) 22.8 (21.9)
Total, kW (MBH) 6.2 (21.2) 8.5 (29) 9.6 (32.9) 11.1 (37.9) 14.2 (48.5) 22.6 (77) 24.8 (84.5)
Med Flow
Sensible, kW (MBH) 4.26 (14.6) 6.0 (20.5) 6.9 (23.6) 8.0 (27.3) 10.5 (35.9) 16.4 (56.1) 18.2 (62.1)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.3 (11.2) 5.8 (19.8) 6.6 (25.1) 7.6 (13.6) 9.7 (21.5) 15.5 (10.7) 17.1 (12.7)
Total, kW (MBH) 5.7 (19.4) 7.8 (26.8) 9 (30.7) 10.2 (34.8) 13.3 (45.3) 20.4 (69.7) 22.5 (76.8)
Low Flow
Sensible, kW (MBH) 4 (13.8) 5.7 (19.5) 6.6 (22.6) 7.6 (25.9) 10.1 (34.4) 15.5 (52.7) 17.2 (58.5)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.3 (6.8) 4.5 (12.2) 5.2 (15.8) 5.8 (8.3) 7.6 (13.4) 11.7 (6.4) 13.0 (7.7)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 4.8 (16.5) 6.7 (22.8) 7.6 (25.9) 8.8 (30.1) 11.3 (38.7) 17.9 (61) 19.7 (67.1)
High Flow
Sensible, kW (MBH) 3.8 (13) 5.4 (18.5) 6.3 (21.3) 7.2 (24.6) 9.5 (32.6) 14.9 (50.9) 16.5 (56.4)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.2 (10.7) 5.7 (19.4) 6.5 (24.6) 7.6 (13.4) 9.7 (21.5) 15.4 (10.6) 17.0 (12.7)
Total, kW (MBH) 4.4 (15.1) 6.2 (21) 7.1 (24.2) 8.1 (27.6) 10.6 (36) 16.1 (54.8) 17.8 (60.8)
Med Flow
Sensible, kW (MBH) 3.6 (12.3) 5.1 (17.6) 6 (20.4) 6.8 (23.3) 9.1 (31.1) 14 (47.6) 15.5 (53)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.1 (6.0) 4.2 (11.1) 4.9 (14.5) 5.6 (7.6) 7.3 (12.5) 11.1 (5.8) 12.4 (7.1)
Total, kW (MBH) 4.1 (13.8) 5.7 (19.4) 6.5 (22.3) 7.4 (25.4) 9.7 (33.1) 14.3 (48.8) 15.8 (54)
Low Flow
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.6) 5.7 (19.3) 6.5 (22.1) 8.6 (29.3) 12.9 (44.1) 14.3 (49)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.7) 3.3 (6.8) 3.8 (8.9) 4.3 (4.7) 5.6 (7.6) 8.3 (3.4) 9.2 (4.1)
72 °F DB / 60 °F WB, 50% RH

Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.6) 5.7 (19.3) 6.5 (22.1) 8.6 (29.4) 13.4 (45.6) 14.8 (50.5)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.4 (7.5) 4.7 (13.6) 5.5 (17.8) 6.3 (9.5) 8.1 (15.4) 12.6 (7.4) 13.9 (8.8)
Total, kW (MBH) 3.6 (12.4) 5 (17.2) 5.8 (19.7) 6.7 (22.7) 8.6 (29.4) 12.6 (43) 13.8 (47.2)
Med Flow
Sensible, kW (MBH) 3.2 (11.1) 4.6 (15.7) 5.3 (18.2) 6.1 (20.9) 8.1 (27.6) 12.1 (41.3) 13.4 (45.7)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.5 (4.2) 3.5 (7.7) 4.0 (10.0) 4.6 (5.4) 6.0 (8.6) 8.7 (3.7) 9.6 (4.5)
Total, kW (MBH) 3.3 (11.1) 4.5 (15.3) 5.1 (17.5) 5.9 (20.1) 7.6 (25.8) 9.9 (33.8) 11 (37.6)
Low Flow
Sensible, kW (MBH) 3 (10.3) 4.2 (14.5) 4.9 (16.7) 5.6 (19.2) 7.4 (25.1) 9.9 (33.8) 11 (37.6)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.9 (2.2) 2.6 (4.5) 3.0 (5.7) 3.4 (3.1) 4.4 (4.9) 5.8 (1.6) 6.4 (2.1)

28
CeilAiR ENGINEERING MANUAL

DX with Alternate Water Source Cooling Capacities, 14−35 kW


Model OHS- 048D()-AWS 072D()-AWS 084D()-AWS 120D()-AWS
Gross Cooling Capacity - kW (MBH) @ 45 °F EWT, 0% Glycol Solution (includes motor heat @ std ft /min and ESP ratings).
3

80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 20.7 (70.5) 39.3 (134.1) 42.3 (144.4) 48.9 (166.9)
High Flow
Sensible, kW (MBH) 14.4 (49.3) 26.6 (90.8) 28.9 (98.7) 34.5 (117.9)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 17.6 (43.1) 33.5 (46.3) 36.1 (53.2) 41.8 (18.6)
Total, kW (MBH) 19.3 (65.8) 36.8 (125.6) 39.6 (135.1) 45.1 (154)
Med Flow
Sensible, kW (MBH) 13.8 (47.2) 25.5 (87) 27.7 (94.6) 32.9 (112.2)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.2 (25.1) 25.2 (27.5) 27.1 (31.5) 31.0 (10.7)
Total, kW (MBH) 18 (61.5) 34.4 (117.4) 37.1 (126.6) 40.8 (139.3)
Low Flow
Sensible, kW (MBH) 13.2 (45.2) 24.4 (83.4) 26.6 (90.8) 30.9 (105.5)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 10.4 (15.8) 19.6 (17.4) 21.2 (20.1) 23.4 (6.4)
7 5°F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 15.2 (51.9) 29 (99.1) 31.3 (106.7) 35.7 (121.9)
High Flow
Sensible, kW (MBH) 12.5 (42.7) 23 (78.5) 25.1 (85.5) 29.8 (101.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.0 (24.6) 24.8 (26.9) 26.8 (30.8) 30.8 (10.6)
Total, kW (MBH) 14.2 (48.4) 27.3 (93.3) 29.5 (100.6) 32.1 (109.7)
Med Flow
Sensible, kW (MBH) 1.2 (4) 22.2 (75.7) 24.2 (82.4) 27.9 (95.3)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 9.8 (14.5) 18.8 (16.1) 20.3 (18.5) 22.2 (5.8)
Total, kW (MBH) 13.1 (44.6) 25.6 (87.3) 27.8 (94.8) 28.6 (97.6)
Low Flow
Sensible, kW (MBH) 11.3 (38.7) 21.3 (72.6) 23.3 (79.4) 25.8 (88.2)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 7.6 (8.9) 14.6 (10.2) 15.9 (11.9) 16.6 (3.4)
2 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 12.6 (43.2) 24.3 (83.1) 26.2 (89.6) 29.2 (99.5)
High Flow
Sensible, kW (MBH) 11.3 (38.7) 21 (71.6) 22.9 (78) 26.7 (91.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.0 (17.8) 20.9 (19.6) 22.5 (22.6) 25.2 (7.4)
Total, kW (MBH) 11.6 (39.5) 23 (78.6) 24.9 (84.9) 25.2 (86)
Med Flow
Sensible, kW (MBH) 10.7 (36.4) 20.2 (69.1) 22.1 (75.2) 24.2 (82.7)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.0 (10.0) 15.8 (11.9) 17.2 (13.7) 17.4 (3.7)
Total, kW (MBH) 10.3 (35) 21 (71.6) 22.8 (77.8) 19.8 (67.6)
Low Flow
Sensible, kW (MBH) 9.8 (33.4) 19 (64.9) 20.8 (70.8) 19.8 (67.6)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 6.0 (5.7) 12.0 (7.2) 13.1 (8.4) 11.6 (1.6)

29
CeilAiR ENGINEERING MANUAL

Alternate Water Source 42 °F EWT Cooling Capacities


Model OHS- 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS
Gross Cooling Capacities - kW (MBH) for 42 °F Chilled Water Entering the Cooling Coil
80 °F DB / 67 °F WB
Total, kW (MBH) 7.7 (26.3) 10.5 (35.7) 11.9 (40.6) 13.6 (46.5) 17.4 (59.3)
High Flow
Sensible, kW (MBH) 4.9 (16.8) 6.9 (23.4) 7.9 (27.1) 9.2 (31.4) 12 (41)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 6.6 (25.0) 8.9 (43.9) 10.1 (55.8) 11.6 (29.8) 14.8 (47.2)

Med Flow Total, kW (MBH) 7.2 (24.6) 9.8 (33.5) 11.2 (38.2) 12.8 (43.7) 16.3 (55.8)
(10 °F Sensible, kW (MBH) 4.7 (16) 6.6 (22.5) 7.6 (26) 8.8 (30) 11.5 (39.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.9 (14.8) 6.7 (25.8) 7.6 (32.9) 8.7 (17.6) 11.1 (27.7)

Low Flow Total, kW (MBH) 6.6 (22.7) 9.1 (31.2) 10.5 (35.8) 11.8 (40.4) 15.3 (52.3)
(12 °F Sensible, kW (MBH) 4.4 (15.2) 6.3 (21.4) 7.3 (24.9) 8.3 (28.5) 11 (37.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.8 (9.1) 5.2 (16.1) 6.0 (20.8) 6.7 (10.9) 8.7 (17.6)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 5.7 (19.5) 7.8 (26.8) 9 (30.6) 10.3 (35.2) 13.2 (45.2)
High Flow
Sensible, kW (MBH) 4.2 (14.4) 6 (20.3) 6.9 (23.6) 8 (27.1) 10.5 (35.8)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.9 (14.5) 6.7 (25.9) 7.6 (33.2) 8.8 (17.9) 11.3 (28.4)

Med Flow Total, kW (MBH) 5.2 (17.9) 7.3 (24.8) 8.4 (28.6) 9.5 (32.5) 12.4 (42.3)
(10 °F Sensible, kW (MBH) 4 (13.6) 5.7 (19.4) 6.6 (22.5) 7.5 (25.7) 7.1 (24.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.6 (8.2) 5.0 (15.1) 5.7 (19.3) 6.5 (10.2) 8.5 (16.7)
Total, kW (MBH) 4.8 (16.4) 6.7 (22.9) 7.8 (26.7) 8.8 (29.9) 11.4 (39.1)
High Flow
Sensible, kW (MBH) 3.8 (12.9) 5.4 (18.4) 6.3 (21.4) 7.1 (24.4) 9.5 (32.5)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.8 (5.0) 3.8 (9.2) 4.4 (11.9) 5.0 (6.3) 6.5 (10.2)
72 °F DB / 60 °F WB
Total, kW (MBH) 4.7 (16.1) 6.6 (22.4) 7.5 (25.8) 8.7 (29.6) 11.2 (38.4)
High Flow
Sensible, kW (MBH) 3.8 (13) 5.4 (18.5) 6.3 (21.5) 7.2 (24.6) 9.6 (32.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.1 (10.4) 5.7 (19.0) 6.4 (24.0) 7.4 (13.0) 9.6 (21.0)

Med Flow Total, kW (MBH) 4.3 (14.8) 6.1 (20.7) 7 (23.9) 7.9 (27.1) 10.4 (35.4)
(10 °F Sensible, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6 (20.4) 6.8 (23.2) 9.1 (31)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.0 (5.9) 4.2 (10.8) 4.8 (14.0) 5.4 (7.4) 7.1 (12.1)

High Flow Total, kW (MBH) 4 (13.5) 5.6 (19) 6.4 (22) 7.3 (24.9) 9.5 (32.5)
(12 °F Sensible, kW (MBH) 3.4 (11.6) 4.8 (16.5) 5.7 (19.3) 6.4 (21.9) 8.5 (29.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.4) 3.2 (6.6) 3.7 (8.6) 4.2 (4.5) 5.4 (7.3)
(Note: The above Cooling capacities @ standard ft3/min and ESP as shown on page 23, Evaporator Blower/Motor.)

30
CeilAiR ENGINEERING MANUAL

Alternate Water Source 42 °F EWT Cooling Capacities


Model OHS- 048-AWS 060-AWS 072-AWS 084-AWS 120-AWS
Gross Cooling Capacities - kW (MBH) for 42 °F Chilled Water Entering the Cooling Coil
80 °F DB / 67 °F WB
Total, kW (MBH) 28.2 (96.3) 30.7 (104.8) 45 (153.4) 48.5 (165.4) 56.2 (191.9)
High Flow
Sensible, kW (MBH) 19 (64.7) 20.8 (71.1) 29.1 (99.3) 31.6 (107.9) 37.7 (128.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 24.0 (24.2) 26.2 (28.4) 38.3 (59.6) 41.3 (68.6) 42.0 (24.2)

Med Flow Total, kW (MBH) 26.3 (89.7) 28.7 (97.8) 42.4 (144.6) 45.6 (155.7) 52.3 (178.6)
(10 °F Sensible, kW (MBH) 18.1 (61.7) 19.9 (67.9) 27.9 (95.3) 30.3 (103.5) 35.9 (122.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 17.9 (14.1) 19.6 (16.6) 28.9 (35.7) 31.2 (41.0) 35.8 (14.1)

Low Flow Total, kW (MBH) 23.8 (81.3) 17.5 (59.6) 39.7 (135.6) 42.9 (146.3) 47.5 (162)
(12 °F Sensible, kW (MBH) 17 (57.9) 18.8 (64.2) 26.7 (91.3) 29.1 (99.3) 33.7 (115.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.6 (8.4) 15.0 (10.1) 22.6 (22.7) 24.5 (26.3) 27.2 (8.4)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 21.1 (72.1) 23.2 (79.1) 33.9 (115.7) 36.5 (124.7) 42.1 (143.5)
High Flow
Sensible, kW (MBH) 16.5 (56.2) 18.2 (62.1) 25.2 (86.1) 27.5 (93.7) 32.7 (111.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 18.1 (14.3) 19.9 (17.1) 28.9 (35.8) 31.2 (41.1) 36.2 (14.3)

Med Flow Total, kW (MBH) 19.1 (65.3) 21.1 (72) 31.9 (108.8) 34.3 (117.1) 38.1 (129.9)
(10 °F Sensible, kW (MBH) 15.5 (52.8) 17.2 (58.6) 24.3 (82.8) 26.4 (90) 30.7 (104.9)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.1 (7.9) 14.5 (9.6) 21.8 (21.4) 23.5 (24.5) 26.2 (7.9)
Total, kW (MBH) 17.3 (58.9) 19.1 (65.2) 29.7 (101.5) 32.3 (110.2) 34.3 (117.1)
High Flow
Sensible, kW (MBH) 14.5 (49.4) 16.1 (55) 23.2 (79.2) 25.4 (86.6) 28.8 (98.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 9.9 (4.7) 11.0 (5.7) 17.0 (13.6) 18.5 (15.8) 19.8 (4.7)
72 °F DB / 60 °F WB
Total, kW (MBH) 17.6 (59.9) 19.3 (65.9) 28.7 (97.8) 30.9 (105.3) 34.9 (119.2)
High Flow
Sensible, kW (MBH) 14.9 (50.8) 16.5 (56.3) 23 (78.6) 25.1 (85.5) 29.6 (101)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 15.1 (10.2) 16.6 (12.3) 24.5 (26.4) 26.4 (30.3) 30.2 (10.2)

Med Flow Total, kW (MBH) 15.8 (53.9) 17.4 (59.5) 27 (92) 29.1 (99.2) 31.4 (107.1)
(10 °F Sensible, kW (MBH) 13.9 (47.5) 15.4 (52.7) 22.2 (75.6) 24.1 (82.4) 27.6 (94.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 10.8 (5.6) 12.0 (6.8) 18.5 (15.8) 20.0 (18.2) 21.6 (5.6)

High Flow Total, kW (MBH) 13.9 (47.4) 15.3 (52.2) 24.9 (84.9) 27 (92.2) 27.6 (94.1)
(12 °F Sensible, kW (MBH) 12.8 (43.5) 14.1 (48.2) 21.1 (71.9) 23 (78.5) 25.3 (86.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.0 (3.2) 8.8 (3.8) 14.2 (9.9) 15.5 (11.4) 16.0 (3.2)
(Note: The above Cooling capacities @ standard ft3/min and ESP as shown on page 23, Evaporator Blower/Motor.)

31
CeilAiR ENGINEERING MANUAL

Alternate Water Source 50 °F EWT Cooling Capacities


Model OHS- 012-AWS 018-AWS 024-AWS 032-AWS 040-AWS
Gross Cooling Capacities - kW (MBH) for 50 °F Chilled Water Entering the Cooling Coil
80 °F DB / 67 °F WB
Total, kW (MBH) 5.1 (17.3) 7 (23.7) 7.9 (27.1) 9.2 (31.6) 11.8 (40.3)
High Flow
Sensible, kW (MBH) 3.8 (13) 5.4 (18.4) 6.3 (21.4) 7.2 (24.7) 9.5 (32.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.4 (11.6) 6.0 (20.6) 6.8 (26.0) 7.9 (14.5) 10.1 (22.7)

Med Flow Total, kW (MBH) 4.7 (15.9) 6.5 (22.1) 7.4 (25.4) 8.5 (29.1) 10.8 (36.8)
(10 °F Sensible, kW (MBH) 3.6 (12.3) 5.2 (17.6) 6 (20.5) 6.9 (23.5) 9.2 (31.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.2 (6.5) 4.5 12.0 () 5.1 (15.3) 5.8 (8.2) 7.6 (13.4)
Total, kW (MBH) 4.3 (14.6) 6 (20.4) 6.9 (23.7) 7.8 (26.8) 10.3 (35.1)
Low Flow
(12 °F Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.8) 5.8 (19.6) 6.5 (22.3) 8.7 (29.8)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.5 (4.0) 3.4 (7.4) 4.0 (9.7) 4.5 (5.1) 5.9 (8.3)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 3.5 (12.1) 4.9 (16.7) 5.6 (19.2) 6.6 (22.4) 8.4 (28.8)
High Flow
Sensible, kW (MBH) 3.2 (11) 4.6 (15.6) 5.3 (18.2) 6.1 (20.9) 8.1 (27.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.1 (6.1) 4.2 (10.9) 4.8 (14.0) 5.7 (7.8) 7.2 (12.3)

Med Flow Total, kW (MBH) 3.2 (10.9) 4.4 (14.9) 5 (17) 5.8 (19.9) 6.9 (23.4)
(10 °F Sensible, kW (MBH) 3 (10.3) 4.2 (14.4) 4.9 (16.7) 5.7 (19.3) 6.9 (23.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.2 (3.3) 3.0 (5.8) 3.4 (7.4) 4.0 (4.2) 4.8 (5.7)
Total, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4)
High Flow
Sensible, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.5 (1.3) 2.1 (2.9) 2.4 (3.9) 2.6 (1.7) 3.5 (3.1)
72 °F DB / 60 °F WB
Total, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5)
High Flow
Sensible, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.5) 3.2 (6.6) 3.7 (8.7) 4.1 (4.3) 5.5 (7.3)

Med Flow Total, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6)
(10 °F Sensible, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.6 (1.6) 2.3 (3.5) 2.7 (4.6) 2.9 (2.1) 3.8 (3.7)

High Flow Total, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3)
(12 °F Sensible, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.1 (0.7) 1.6 (1.6) 1.9 (2.3) 2.0 (0.8) 2.6 (1.7)
(Note: The above Cooling capacities @ standard ft /min and ESP as shown on page 23, Evaporator Blower/Motor.)
3

32
CeilAiR ENGINEERING MANUAL

Alternate Water Source 50 °F EWT Cooling Capacities


Model OHS- 048-AWS 060-AWS 072-AWS 084-AWS 120-AWS
Gross Cooling Capacities - kW (MBH) for 50 °F Chilled Water Entering the Cooling Coil
80 °F DB / 67 °F WB
Total, kW (MBH) 18.8 (64.2) 20.5 (69.8) 30.1 (102.6) 32.5 (110.9) 37.4 (127.6)
High Flow
Sensible, kW (MBH) 15 (51.2) 16.5 (56.4) 22.8 (77.6) 24.8 (84.8) 29.8 (101.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 16.1 (11.4) 17.6 (13.4) 25.7 (28.3) 27.9 (32.7) 32.2 (11.4)

Med Flow Total, kW (MBH) 17.2 (58.7) 19 (64.8) 28.3 (96.4) 30.5 (104) 34.2 (116.7)
(10 °F Sensible, kW (MBH) 14.2 (48.5) 15.8 (53.9) 22 (74.9) 23.9 (81.7) 28.2 (96.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.8 (6.4) 13.1 (7.8) 19.4 (16.9) 21.0 (19.5) 23.6 (6.4)

Low Flow Total, kW (MBH) 15.5 (52.9) 17.1 (58.5) 26.7 (91) 28.7 (97.9) 30.8 (105)
(12 °F Sensible, kW (MBH) 13.3 (45.5) 14.8 (50.5) 21.2 (72.4) 23.1 (78.8) 26.5 (90.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.9 (3.8) 9.9 (4.6) 15.3 (10.9) 16.4 (12.5) 17.8 (3.8)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 12.8 (43.6) 13.3 (45.4) 22.1 (75.5) 23.7 (80.9) 25.3 (86.5)
High Flow
Sensible, kW (MBH) 12.4 (42.4) 13.3 (45.4) 19.9 (67.8) 21.6 (73.6) 24.7 (84.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.0 (5.6) 11.5 (6.1) 19.0 (16.3) 20.4 (18.6) 22.0 (5.6)

Med Flow Total, kW (MBH) 10.6 (36.1) 11.7 (40) 21 (71.7) 22.3 (76.3) 20.9 (71.4)
(10 °F Sensible, kW (MBH) 10.6 (36.1) 11.7 (40) 19.2 (65.4) 20.7 (70.6) 20.9 (71.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 7.3 (2.7) 8.2 (3.3) 14.4 (9.9) 15.4 (11.2) 14.6 (2.7)
Total, kW (MBH) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
High Flow
Sensible, kW (MBH) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.1 (1.2) 5.7 (1.6) 9.2 (4.4) 10.0 (5.1) 10.2 (1.2)
72 °F DB / 60 °F WB
Total, kW (MBH) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
High Flow
Sensible, kW (MBH) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.5 (3.5) 9.5 (4.3) 14.1 (9.5) 15.4 (11.1) 17.0 (3.5)

Med Flow Total, kW (MBH) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
(10 °F Sensible, kW (MBH) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.7 (1.6) 6.4 (2.0) 10.0 (5.1) 11.0 (6.0) 11.4 (1.6)
Total, kW (MBH) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
High Flow
(12 °F Sensible, kW (MBH) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.6 (0.5) 4.1 (0.7) 7.0 (2.7) 7.7 (3.2) 7.2 (0.5)
(Note: The above Cooling capacities @ standard ft3/min and ESP as shown on page 23, Evaporator Blower/Motor.)

33
CeilAiR ENGINEERING MANUAL

Chilled Water Models


Chilled Water Air Handler Technical Data, 3.5−10.5 kW
Model OHS- 012-C 018-C 024-C 032-C 040-C
Chilled Water Control Valve - Sized for Medium Flow @ 75 °F DB / 62.5 °F WB EAT Conditions
2-way (standard) - Spring Actuated (Open/Close)
Size, in. 1/2 3/4 3/4 3/4 3/4
Cv 3.5 3.5 3.5 3.5 3.5
Valve Pressure Rating, psi 300 300 300 300 300
Pressure Drop, ftH2O-Total Unit 8.0 14.6. 19.4 14.2 22.6
3-way (optional) - Spring Actuated (Open/Close)
Size, in. 1/2 3/4 3/4 3/4 3/4
Cv 5.0 5.0 5.0 5.0 5.0
Valve Pressure Rating, psi 300 300 300 300 300
Pressure Drop, ftH2O-Total Unit 7.1 12.9 17.0 11.2 17.5
Chilled Water Coil - Aluminum Fin, Copper Tube
Rows 4 4 4 4 4
Face Area, ft2 2.1 2.1 2.1 2.8 2.8
Evaporator Blower / Motor - DWDI Centrifugal
Nominal Horsepower, hp 1/4 1/4 1/4 1/3 1/2
Rated Airflow, ft3/min @ inH2O ESP 500 @ 0.3 750 @ 0.3 900 @ 0.3 1000 @ 0.3 1415 @ 0.3
Standard Drive Method Direct Direct Direct Direct Direct
Optional Drive Method Belt Belt Belt Belt Belt
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 5 5 5 5 5
Optional Heater, kW N/A N/A N/A N/A N/A
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB:
Total Capacity, kW (MBH) 6.1 (20.7) 9.5 (32.4) 10.2 (34.9) 14.8 (50.4) 16.2 (55.3)
-

Flow rate, GPM 1 2 2 3 3


Pressure Drop, ftH2O-Coil 0.1 0.3 0.3 0.3 0.3
Control Motorized Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB:
Total Capacity, kW (MBH) 3.5 (12) 5.3 (18) 7 (24) 9.4 (32) 11.7 (40)
Condensate, lb/hr 13 19 25 34 42
Control Motorized Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 2-5 2-5 2-5 2-5 2-5
Power Input, kW 1.7 1.7 1.7 1.7 1.7
Standard Control Cycling Cycling Cycling Cycling Cycling
Filters - 1 in. deep throwaway
Nominal Size, in. 20×20 20×20 20×20 20×20 20×20
Quantity 1 1 1 1 1
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4 1/4
Chilled Water In/Out OD, in. 5/8 7/8 7/8 7/8 7/8
Physical Size (Please refer to the dimensional drawings starting on page 57 for detailed dimensional data.)
Approximate Weight, lb 120 125 125 160 170

34
CeilAiR ENGINEERING MANUAL

Chilled Water Air Handler Technical Data, 14−35 kW


OHS Model OHS-048-C OHS-060-C OHS-072-C OHS-084-C OHS-120-C
Chilled Water Control Valve - Sized for Medium Flow @ 75 °F DB / 62.5 °F WB EAT Conditions
2-way (standard) - Spring Actuated (Open/Close)
Size , in. 1 1 1 1 1
Cv 8.0 8.0 14.0 14.0 14.0
Valve Pressure Rating, psi 300 300 400 400 400
Pressure Drop, ftH2O-Total Unit 10.4 12.7 20.7 24.1 12.5
3-way (optional) - Spring Actuated (Open/Close)
Size, in. 1 1 1 1 1
Cv 7.0 7.0 14.0 14.0 14.0
Valve Pressure Rating, psi 300 300 400 400 400
Pressure Drop, ftH2O-Total Unit 11.8 14.4 20.7 24.1 12.5
Chilled Water Coil - Aluminum Fin, Copper Tube
Rows 4 4 4 4 4
Face Area, ft 2
5.0 5.0 6.7 6.7 10.0
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1 1 1/2 1-1/2 2 3
Rated Airflow, ft /min @ inH2O ESP
3
2200 @ 0.5 2500 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt Belt
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10 10
Optional Heater, kW N/A N/A 15 15 15
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 28.5 (97.1) 32.6 (111.2) 28.7 (97.9) 29.3 (99.8) 38.2 (130.5)
Flow rate, GPM 4.0 5.0 3.0 3.0 10.0
Pressure Drop, ftH2O-Coil. 0.4 0.6 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB:
Total Capacity, kW (MBH) 14.1 (48) 17.6 (60) 21.1 (72) 26.4 (90) 35.2 (120)
Condensate, lb/hr 50 63 75 94 125
Control Motorized Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-10 4-15 4-15 4-15
Power Input, kW 3.4 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling Cycling
Filters - 1 in. deep throwaway
Nominal Size, in. 20×16 20×16 20×20 20×20 24×24
Quantity 2 2 2 2 2
Connection Sizes - Copper, (Water In/Out connections are sized for flow rates at 75 °F DB / 62.5 °F WB EAT conditions.)
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4 1/4
Chilled Water In/Out OD, in. 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8
Physical Size (Please refer to the dimensional drawings starting on page 57 for detailed dimensional data.)
Approximate Weight, lb 280 290 365 415 495

35
CeilAiR ENGINEERING MANUAL

Chilled Water Air Handler Cooling Capacities, 3.5−12 kW


Model OHS- 012-C 018-C 024-C 032-C 040-C
Cooling Capacities - kW (MBH) for 45 °F EWT, 0% Glycol Solution (@ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 6.7 (23) 9.1 (31.1) 10.4 (35.4) 12 (40.8) 15.2 (52)
High Flow
Sensible, kW (MBH) 4.5 (15.3) 6.3 (21.4) 7.3 (24.8) 8.4 (28.7) 11 (37.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.8 (19.6) 7.8 (34.0) 8.8 (43.1) 10.2 (23.3) 13.0 (36.8)
Total, kW (MBH) 6.2 (21.2) 8.5 (29.1) 9.7 (33.1) 11.1 (38) 14.3 (48.7)
Med Flow
Sensible, kW (MBH) 4.3 (14.6) 6 (20.5) 7 (23.8) 8 (27.4) 10.6 (36.1)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.3 (11.2) 5.8 (19.8) 6.6 (25.1) 7.6 (13.6) 9.7 (21.5)
Total, kW (MBH) 5.7 (19.4) 7.9 (26.8) 9.1 (30.9) 10.2 (35) 13.3 (45.4)
Low Flow
Sensible, kW (MBH) 4 (13.8) 5.7 (19.5) 6.7 (22.8) 7.6 (26) 10.1 (34.5)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.3 (6.8) 4.5 (12.2) 5.2 (15.8) 5.8 (8.3) 7.6 (13.4)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 4.8 (16.5) 6.7 (22.8) 7.7 (26.1) 8.8 (30.2) 11.4 (38.9)
High Flow
Sensible, kW (MBH) 3.8 (13) 5.4 (18.5) 6.3 (21.5) 7.2 (24.7) 9.6 (32.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.2 (10.7) 5.7 (19.4) 6.5 (24.6) 7.6 (13.4) 9.7 (21.5)
Total, kW (MBH) 4.4 (15.1) 6.2 (21.1) 7.1 (24.4) 8.1 (27.7) 10.6 (36.2)
Med Flow
Sensible, kW (MBH) 3.6 (12.3) 5.2 (17.6) 6 (20.6) 6.9 (23.4) 9.1 (31.2)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.1 (6.0) 4.2 (11.1) 4.9 (14.5) 5.6 (7.6) 7.3 (12.5)
Total, kW (MBH) 4.1 (13.8) 5.7 (19.4) 6.6 (22.5) 7.5 (25.5) 9.8 (33.3)
Low Flow
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.7) 5.7 (19.5) 6.5 (22.2) 8.6 (29.5)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.7) 3.3 (6.8) 3.8 (8.9) 4.3 (4.7) 5.6 (7.6)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 4 (13.5) 5.5 (18.8) 6.4 (21.8) 7.3 (24.9) 9.5 (32.5)
High Flow
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.7) 5.7 (19.5) 6.5 (22.2) 8.7 (29.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.4 (7.5) 4.7 (13.6) 5.5 (17.8) 6.3 (9.5) 8.1 (15.4)
Total, kW (MBH) 3.6 (12.4) 5.1 (17.2) 5.8 (19.9) 6.7 (22.8) 8.7 (29.6)
Med Flow
Sensible, kW (MBH) 3.2 (11.1) 4.6 (15.7) 5.4 (18.4) 6.1 (21) 8.1 (27.8)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.5 (4.2) 3.5 (7.7) 4.0 (10.0) 4.6 (5.4) 6.0 (8.6)
Total, kW (MBH) 3.3 (11.1) 4.5 (15.4) 5.2 (17.7) 5.9 (20.2) 7.6 (26)
Low Flow
Sensible, kW (MBH) 3 (10.3) 4.3 (14.5) 4.9 (16.9) 5.7 (19.3) 7.4 (25.3)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.9 (2.2) 2.6 (4.5) 3.0 (5.7) 3.4 (3.1) 4.4 (4.9)

Continued on next page

36
CeilAiR ENGINEERING MANUAL

Chilled Water Air Handler Cooling Capacities, 3.5−12 kW (Con’t)


Model OHS- 012-C 018-C 024-C 032-C 040-C
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 5.9 (20.3) 8.1 (27.8) 9.3 (31.8) 10.8 (36.9) 13.9 (47.4)
High Flow
Sensible, kW (MBH) 4.6 (15.6) 6.5 (22.1) 7.5 (25.7) 8.7 (29.7) 11.5 (39.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.1 (15.7) 6.9 (27.5) 8.0 (35.4) 9.2 (19.5) 11.8 (30.8)
Total, kW (MBH) 5.5 (18.9) 7.7 (26.2) 8.8 (30.1) 10.1 (34.6) 13.1 (44.9)
Med Flow
Sensible, kW (MBH) 4.4 (15) 6.2 (21.3) 7.3 (24.8) 8.3 (28.5) 11.1 (37.8)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.8 (9.1) 5.2 (16.3) 6.0 (21.1) 6.9 (11.5) 9.0 (18.5)
Total, kW (MBH) 5.1 (17.6) 7.2 (24.5) 8.3 (28.3) 9.5 (32.3) 12.3 (42.1)
Low Flow
Sensible, kW (MBH) 4.2 (14.3) 6 (20.5) 7 (23.9) 8 (27.3) 10.6 (36.3)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.9 (5.7) 4.1 (10.4) 4.7 (13.4) 5.4 (7.2) 7.0 (11.7)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 4.5 (15.2) 6.2 (21.2) 7.2 (24.4) 8.3 (28.2) 10.7 (36.6)
High Flow
Sensible, kW (MBH) 3.9 (13.4) 5.6 (19.2) 6.5 (22.3) 7.5 (25.6) 10 (34)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.8 (9.3) 5.4 (17.0) 6.1 (21.9) 7.0 (11.8) 9.2 (19.3)
Total, kW (MBH) 4.2 (14.2) 5.8 (19.8) 6.7 (22.7) 7.7 (26.2) 9.9 (33.9)
Med Flow
Sensible, kW (MBH) 3.8 (12.9) 5.4 (18.3) 6.2 (21.3) 7.1 (24.3) 9.4 (32.2)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.9 (5.4) 4.0 (9.9) 4.6 (12.7) 5.3 (6.9) 6.8 (11.0)
Total, kW (MBH) 3.8 (13) 5.3 (18) 6 (20.6) 7 (23.8) 8 (27.5)
Low Flow
Sensible, kW (MBH) 3.6 (12.1) 5 (17.1) 5.8 (19.9) 6.7 (22.8) 8 (27.5)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.2 (3.2) 3.0 (5.9) 3.5 (7.6) 4.0 (4.2) 4.6 (5.4)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.7 (12.7) 5.1 (17.4) 5.7 (19.4) 6.8 (23.3) 8.3 (28.4)
High Flow
Sensible, kW (MBH) 3.6 (12.1) 5 (17.1) 5.7 (19.4) 6.7 (22.9) 8.3 (28.4)
(8°F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.2 (6.6) 4.4 (11.8) 4.9 (14.4) 5.9 (8.5) 7.1 (12.1)
Total, kW (MBH) 3.2 (10.8) 4.5 (15.3) 5.2 (17.8) 5.7 (19.4) 7.5 (25.7)
Med Flow
Sensible, kW (MBH) 3.2 (10.8) 4.5 (15.3) 5.2 (17.8) 5.7 (19.4) 7.5 (25.7)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.2 (3.1) 3.1 (6.2) 3.6 (8.1) 3.9 (4.0) 5.2 (6.7)
Total, kW (MBH) 2.9 (9.7) 4 (13.8) 4.7 (16.1) 5.1 (17.2) 6.7 (22.9)
Low Flow
Sensible, kW (MBH) 2.9 (9.7) 4 (13.8) 4.7 (16.1) 5.1 (17.2) 6.7 (22.9)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.7 (1.6) 2.3 (3.7) 2.7 (4.8) 2.9 (2.1) 3.9 (3.9)

37
CeilAiR ENGINEERING MANUAL

Chilled Water Air Handler Cooling Capacities, 14−35 kW


Model OHS- 048-C 060-C 072-C 084-C 120-C
Gross Cooling Capacity - kW (MBH) @ 45 °F EWT, 0% Glycol Solution (@ std ft /min and ESP ratings).
3

80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 24.6 (83.8) 26.7 (91.1) 39.3 (134.1) 42.3 (144.4) 48.9 (166.9)
High Flow
Sensible, kW (MBH) 17.4 (59.3) 19.1 (65.3) 26.6 (90.8) 28.9 (98.7) 34.5 (117.9)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 20.9 (18.6) 22.8 (21.9) 33.5 (46.3) 36.1 (53.2) 41.8 (18.6)
Total, kW (MBH) 22.7 (77.4) 24.9 (84.8) 36.8 (125.6) 39.6 (135.1) 45.1 (154)
Med Flow
Sensible, kW (MBH) 16.5 (56.4) 18.3 (62.4) 25.5 (87) 27.7 (94.6) 32.9 (112.2)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 15.5 (10.7) 17.1 (12.7) 25.2 (27.5) 27.1 (31.5) 31.0 (10.7)
Total, kW (MBH) 20.5 (70) 22.6 (77.2) 34.4 (117.4) 37.1 (126.6) 40.8 (139.3)
Low Flow
Sensible, kW (MBH) 53.1) 17.3 (58.9) 24.4 (83.4) 26.6 (90.8) 30.9 (105.5)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.7 (6.4) 13.0 (7.7) 19.6 (17.4) 21.2 (20.1) 23.4 (6.4 )
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 18 (61.3) 19.8 (67.5) 29 (99.1) 31.3 (106.7) 35.7 (121.9)
High Flow
Sensible, kW (MBH) 15 (51.2) 16.6 (56.8) 23 (78.5) 25.1 (85.5) 29.8 (101.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 15.4 (10.6) 17.0 (12.7) 24.8 (26.9) 26.8 (30.8) 30.8 (10.6)
Total, kW (MBH) 16.2 (55.2) 17.9 (61.1) 27.3 (93.3) 29.5 (100.6) 32.1 (109.7)
Med Flow
Sensible, kW (MBH) 14.1 (48) 15.6 (53.3) 22.2 (75.7) 24.2 (82.4) 27.9 (95.3)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.1 (5.8) 12.4 (7.1) 18.8 (16.1) 20.3 (18.5) 22.2 (5.8)
Total, kW (MBH) 14.4 (49.2) 15.9 (54.4) 25.6 (87.3) 27.8 (94.8) 28.6 (97.6)
Low Flow
Sensible, kW (MBH) 13 (44.4) 14.4 (49.3) 21.3 (72.6) 23.3 (79.4) 25.8 (88.2)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.3 (3.4) 9.2 (4.1) 14.6 (10.2) 15.9 (11.9) 16.6 (3.4)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 14.7 (50.1) 16.1 (55.1) 24.3 (83.1) 26.2 (89.6) 29.2 (99.5)
High Flow
Sensible, kW (MBH) 13.5 (45.9) 14.9 (50.8) 21 (71.6) 22.9 (78) 26.7 (91.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 12.6 (7.4) 13.9 (8.8) 20.9 (19.6) 22.5 (22.6) 25.2 (7.4)
Total, kW (MBH) 12.7 (43.3) 13.9 (47.5) 23 (78.6) 24.9 (84.9) 25.2 (86)
Med Flow
Sensible, kW (MBH) 12.2 (41.7) 13.5 (46) 20.2 (69.1) 22.1 (75.2) 24.2 (82.7)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.7 (3.7) 9.6 (4.5) 15.8 (11.9) 17.2 (13.7) 17.4 (3.7)
Total, kW (MBH) 10 (34.1) 11.1 (37.9) 21 (71.6) 22.8 (77.8) 19.8 (67.6)
Low Flow
Sensible, kW (MBH) 10 (34.1) 11.1 (37.9) 19 (64.9) 20.8 (70.8) 19.8 (67.6)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.8 (1.6) 6.4 (2.1) 12.0 (7.2) 13.1 (8.4) 11.6 (1.6)

38
CeilAiR ENGINEERING MANUAL

Chilled Water Air Handler Cooling Capacities, 14−35 kW (Con’t)


Model OHS- 048-C 060-C 072-C 084-C 120-C
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 22.1 (75.6) 24.2 (82.5) 35.3 (120.4) 38.1 (130) 44.1 (150.5)
High Flow
Sensible, kW (MBH) 18.1 (61.7) 20 (68.1) 27.4 (93.6) 29.9 (102.2) 35.9 (122.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 18.9 (15.5) 20.7 (18.3) 30.2 (38.4) 32.6 (44.1) 37.8 (15.5)
Total, kW (MBH) 20.5 (70.1) 22.6 (77.2) 33.5 (114.2) 36.1 (123.2) 40.9 (139.4)
Med Flow
Sensible, kW (MBH) 17.3 (58.9) 19.2 (65.4) 26.6 (90.7) 29 (98.9) 34.3 (117.2)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 14.1 (8.9) 15.5 (10.7) 23.0 (23.3) 24.8 (26.7) 28.2 (8.9)
Total, kW (MBH) 18.9 (64.4) 22.3 (76.1) 31.8 (108.6) 34.4 (117.2) 37.5 (128.1)
Low Flow
Sensible, kW (MBH) 16.4 (55.9) 18.2 (62.1) 25.8 (88) 28.1 (96) 32.6 (111.1)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 10.8 (5.5) 11.9 (6.6) 18.2 (15.1) 19.6 (17.4) 21.6 (5.5)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 16.8 (57.2) 18.4 (62.8) 27.3 (93.1) 29.5 (100.5) 33.4 (113.8)
High Flow
Sensible, kW (MBH) 15.6 (53.1) 17.2 (58.8) 24 (81.9) 26.2 (89.3) 31 (105.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 14.4 (9.4) 15.9 (11.2) 23.4 (24.1) 25.3 (27.8) 28.8 (9.4)
Total, kW (MBH) 14.9 (50.8) 16.4 (55.9) 26.2 (89.3) 28.2 (96.1) 29.6 (101)
Med Flow
Sensible, kW (MBH) 14.4 (49.2) 15.9 (54.4) 23.3 (79.7) 25.4 (86.7) 28.6 (97.6)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 10.2 (5.0) 11.3 (6.0) 18.0 (14.9) 19.4 (17.2) 20.4 (5.0)
Total, kW (MBH) 12.4 (42.3) 13.7 (46.9) 24.7 (84.2) 26.7 (91.1) 24.6 (83.9)
High Flow
Sensible, kW (MBH) 12.4 (42.3) 13.7 (46.9) 22.4 (76.5) 24.4 (83.4) 24.6 (83.9)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 7.1 (2.6) 7.9 (3.1) 14.1 (9.6) 15.3 (11.1) 14.2 (2.6)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 13.2 (44.9) 14.6 (49.7) 23.4 (79.7) 25 (85.3) 26.1 (89.1)
High Flow
Sensible, kW (MBH) 13.2 (44.9) 14.6 (49.7) 22.1 (75.4) 23.9 (81.7) 26.1 (89.1)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.3 (6.0) 12.5 (7.3) 20.0 (18.2) 21.4 (20.6) 22.6 (6.0)
Total, kW (MBH) 11.7 (39.9) 13 (44.2) 19.6 (66.8) 21.4 (73) 23.2 (79.1)
Med Flow
Sensible, kW (MBH) 11.7 (39.9) 13 (44.2) 19.6 (66.8) 21.4 (73) 23.2 (79.1)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.1 (3.2) 9.0 (3.9) 13.4 (8.8) 14.8 (10.5) 16.2 (3.2)
Total, kW (MBH) 10 (34) 11.1 (37.8) 17.7 (60.4) 19.3 (65.9) 19.7 (67.3)
Low Flow
Sensible, kW (MBH) 10 (34) 11.1 (37.8) 17.7 (60.4) 19.3 (65.9) 19.7 (67.3)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.7 (1.6) 6.4 (2.0) 10.2 (5.3) 11.1 (6.3) 11.4 (1.6)

39
CeilAiR ENGINEERING MANUAL

Chilled Water 42 °F EWT Cooling Capacities

Model OHS- 012-C 018-C 024-C 032-C 040-C


Gross Cooling Capacities - kW (MBH) for 42 °F Chilled Water Entering the Cooling Coil
80 °F DB / 67 °F WB
Total, kW (MBH) 7.7 (26.3) 10.5 (35.7) 11.9 (40.6) 13.6 (46.5) 17.4 (59.3)
High Flow
Sensible, kW (MBH) 4.9 (16.8) 6.9 (23.4) 7.9 (27.1) 9.2 (31.4) 12 (41)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 6.6 (25.0) 8.9 (43.9) 10.1 (55.8) 11.6 (29.8) 14.8 (47.2)

Med Flow Total, kW (MBH) 7.2 (24.6) 9.8 (33.5) 11.2 (38.2) 12.8 (43.7) 16.3 (55.8)
(10 °F Sensible, kW (MBH) 4.7 (16) 6.6 (22.5) 7.6 (26) 8.8 (30) 11.5 (39.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.9 (14.8) 6.7 (25.8) 7.6 (32.9) 8.7 (17.6) 11.1 (27.7)
Total, kW (MBH) 6.6 (22.7) 9.1 (31.2) 10.5 (35.8) 11.8 (40.4) 15.3 (52.3)
Low Flow
(12 °F Sensible, kW (MBH) 4.4 (15.2) 6.3 (21.4) 7.3 (24.9) 8.3 (28.5) 11 (37.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.8 (9.1) 5.2 (16.1) 6.0 (20.8) 6.7 (10.9) 8.7 (17.6)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 5.7 (19.5) 7.8 (26.8) 9 (30.6) 10.3 (35.2) 13.2 (45.2)
High Flow
Sensible, kW (MBH) 4.2 (14.4) 6 (20.3) 6.9 (23.6) 8 (27.1) 10.5 (35.8)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.9 (14.5) 6.7 (25.9) 7.6 (33.2) 8.8 (17.9) 11.3 (28.4)

Med Flow Total, kW (MBH) 5.2 (17.9) 7.3 (24.8) 8.4 (28.6) 9.5 (32.5) 12.4 (42.3)
(10 °F Sensible, kW (MBH) 4 (13.6) 5.7 (19.4) 6.6 (22.5) 7.5 (25.7) 10 (34.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.6 (8.2) 5.0 (15.1) 5.7 (19.3) 6.5 (10.2) 8.5 (16.7)

Low Flow Total, kW (MBH) 4.8 (16.4) 6.7 (22.9) 7.8 (26.7) 8.8 (29.9) 11.4 (39.1)
(12 °F Sensible, kW (MBH) 3.8 (12.9) 5.4 (18.4) 6.3 (21.4) 7.1 (24.4) 9.5 (32.5)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.8 (5.0) 3.8 (9.2) 4.4 (11.9) 5.0 (6.3) 6.5 (10.2)
72 °F DB / 60 °F WB
Total, kW (MBH) 4.7 (16.1) 6.6 (22.4) 7.5 (25.8) 8.7 (29.6) 11.2 (38.4)
High Flow
Sensible, kW (MBH) 3.8 (13) 5.4 (18.5) 6.3 (21.5) 7.2 (24.6) 9.6 (32.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.1 (10.4) 5.7 (19.0) 6.4 (24.0) 7.4 (13.0) 9.6 (21.0)

MedFlow Total, kW (MBH) 4.3 (14.8) 6.1 (20.7) 7 (23.9) 7.9 (27.1) 10.4 (35.4)
(10 °F Sensible, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6 (20.4) 6.8 (23.2) 9.1 (31)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.0 (5.9) 4.2 (10.8) 4.8 (14.0) 5.4 (7.4) 7.1 (12.1)

Low Flow Total, kW (MBH) 4 (13.5) 5.6 (19) 6.4 (22) 7.3 (24.9) 9.5 (32.5)
(12 °F Sensible, kW (MBH) 3.4 (11.6) 4.8 (16.5) 5.7 (19.3) 6.4 (21.9) 8.5 (29.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.4) 3.2 (6.6) 3.7 (8.6) 4.2 (4.5) 5.4 (7.3)

40
CeilAiR ENGINEERING MANUAL

Chilled Water 42 °F EWT Cooling Capacities


Model OHS- 048-C 060-C 072-C 084-C 120-C
Gross Cooling Capacities - kW (MBH) for 42 °F Chilled Water Entering the Cooling Coil
80 °F DB / 67 °F WB
Total, kW (MBH) 28.2 (96.3) 30.7 (104.8) 45 (153.4) 48.5 (165.4) 56.2 (191.9)
High Flow
Sensible, kW (MBH) 19 (64.7) 20.8 (71.1) 29.1 (99.3) 31.6 (107.9) 37.7 (128.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 24.0 (24.2) 26.2 (28.4) 38.3 (59.6) 41.3 (68.6) 42.0 (24.2)

Med Flow Total, kW (MBH) 26.3 (89.7) 28.7 (97.8) 42.4 (144.6) 45.6 (155.7) 52.3 (178.6)
(10 °F Sensible, kW (MBH) 18.1 (61.7) 19.9 (67.9) 27.9 (95.3) 30.3 (103.5) 35.9 (122.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 17.9 (14.1) 19.6 (16.6) 28.9 (35.7) 31.2 (41.0) 35.8 (14.1)

Low Flow Total, kW (MBH) 23.8 (81.3) 17.5 (59.6) 39.7 (135.6) 42.9 (146.3) 47.5 (162)
(12 °F Sensible, kW (MBH) 17 (57.9) 18.8 (64.2) 26.7 (91.3) 29.1 (99.3) 33.7 (115.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.6 (8.4) 15.0 (10.1) 22.6 (22.7) 24.5 (26.3) 27.2 (8.4)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 21.1 (72.1) 23.2 (79.1) 33.9 (115.7) 36.5 (124.7) 42.1 (143.5)
High Flow
Sensible, kW (MBH) 16.5 (56.2) 18.2 (62.1) 25.2 (86.1) 27.5 (93.7) 32.7 (111.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 18.1 (14.3) 19.9 (17.1) 28.9 (35.8) 31.2 (41.1) 36.2 (14.3)

Med Flow Total, kW (MBH) 19.1 (65.3) 21.1 (72) 31.9 (108.8) 34.3 (117.1) 38.1 (129.9)
(10 °F Sensible, kW (MBH) 15.5 (52.8) 17.2 (58.6) 24.3 (82.8) 26.4 (90) 30.7 (104.9)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.1 (7.9) 14.5 (9.6) 21.8 (21.4) 23.5 (24.5) 26.2 (7.9)

Low Flow Total, kW (MBH) 17.3 (58.9) 19.1 (65.2) 29.7 (101.5) 32.3 (110.2) 34.3 (117.1)
(12 °F Sensible, kW (MBH) 14.5 (49.4) 16.1 (55) 23.2 (79.2) 25.4 (86.6) 28.8 (98.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 9.9 (4.7) 11.0 (5.7) 17.0 (13.6) 18.5 (15.8) 19.8 (4.7)
72 °F DB / 60 °F WB
Total, kW (MBH) 17.6 (59.9) 19.3 (65.9) 28.7 (97.8) 30.9 (105.3) 34.9 (119.2)
High Flow
Sensible, kW (MBH) 14.9 (50.8) 16.5 (56.3) 23 (78.6) 25.1 (85.5) 29.6 (101)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 15.1 (10.2) 16.6 (12.3) 24.5 (26.4) 26.4 (30.3) 30.2 (10.2)

MedFlow Total, kW (MBH) 15.8 (53.9) 17.4 (59.5) 27 (92) 29.1 (99.2) 31.4 (107.1)
(10 °F Sensible, kW (MBH) 13.9 (47.5) 15.4 (52.7) 22.2 (75.6) 24.1 (82.4) 27.6 (94.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 10.8 (5.6) 12.0 (6.8) 18.5 (15.8) 20.0 (18.2) 21.6 (5.6)
Total, kW (MBH) 13.9 (47.4) 15.3 (52.2) 24.9 (84.9) 27 (92.2) 27.6 (94.1)
Low Flow
(12 °F Sensible, kW (MBH) 12.8 (43.5) 14.1 (48.2) 21.1 (71.9) 23 (78.5) 25.3 (86.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.0 (3.2) 8.8 (3.8) 14.2 (9.9) 15.5 (11.4) 16.0 (3.2)

41
CeilAiR ENGINEERING MANUAL

Chilled Water 50 °F EWT Cooling Capacities


Model OHS- 012-C 018-C 024-C 032-C 040-C
Gross Cooling Capacities - kW (MBH) for 50 °F Chilled Water Entering the Cooling Coil
80 °F DB / 67 °F WB
Total, kW (MBH) 5.1 (17.3) 7 (23.7) 7.9 (27.1) 9.2 (31.6) 11.8 (40.3)
High Flow
Sensible, kW (MBH) 3.8 (13) 5.4 (18.4) 6.3 (21.4) 7.2 (24.7) 9.5 (32.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.4 (11.6) 6.0 (20.6) 6.8 (26.0) 7.9 (14.5) 10.1 (22.7)

Med Flow Total, kW (MBH) 4.7 (15.9) 6.5 (22.1) 7.4 (25.4) 8.5 (29.1) 10.8 (36.8)
(10 °F Sensible, kW (MBH) 3.6 (12.3) 5.2 (17.6) 6 (20.5) 6.9 (23.5) 9.2 (31.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.2 (6.5) 4.5 (12.0) 5.1 (15.3) 5.8 (8.2) 7.6 (13.4)
Total, kW (MBH) 4.3 (14.6) 6 (20.4) 6.9 (23.7) 7.8 (26.8) 10.3 (35.1)
Low Flow
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.8) 5.8 (19.6) 6.5 (22.3) 8.7 (29.8)
(12 °F ΔTw
Flow Rate, GPM (Pressure Drop, ftH2O) 2.5 (4.0) 3.4 (7.4) 4.0 (9.7) 4.5 (5.1) 5.9 (8.3)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 3.5 (12.1) 4.9 (16.7) 5.6 (19.2) 6.6 (22.4) 8.4 (28.8)
High Flow
Sensible, kW (MBH) 3.2 (11) 4.6 (15.6) 5.3 (18.2) 6.1 (20.9) 8.1 (27.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.1 (6.1) 4.2 (10.9) 4.8 (14.0) 5.7 (7.8) 7.2 (12.3)
Total, kW (MBH) 3.2 (10.9) 4.4 (14.9) 5 (17) 5.8 (19.9) 6.9 (23.4)
Med Flow
(10 °F Sensible, kW (MBH) 3 (10.3) 4.2 (14.4) 4.9 (16.7) 5.7 (19.3) 6.9 (23.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.2 (3.3) 3.0 (5.8) 3.4 (7.4) 4.0 (4.2) 4.8 (5.7)

High Flow Total, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4)
(12 °F Sensible, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.5 (1.3) 2.1 (2.9) 2.4 (3.9) 2.6 (1.7) 3.5 (3.1)
72 °F DB / 60 °F WB
Total, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5)
High Flow
Sensible, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.5) 3.2 (6.6) 3.7 (8.7) 4.1 (4.3) 5.5 (7.3)

Med Flow Total, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6)
(10 °F Sensible, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.6 (1.6) 2.3 (3.5) 2.7 (4.6) 2.9 (2.1) 3.8 (3.7)

High Flow Total, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3)
(12 °F Sensible, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.1 (0.7) 1.6 (1.6) 1.9 (2.3) 2.0 (0.8) 2.6 (1.7)
(Note: The above Cooling capacities @ standard ft3/min and ESP as shown on page 34, Evaporator Blower/Motor.)

42
CeilAiR ENGINEERING MANUAL

Chilled Water 50 °F EWT Cooling Capacities


Model OHS- 048-C 060-C 072-C 084-C 120-C
Gross Cooling Capacities - kW (MBH) for 50 °F Chilled Water Entering the Cooling Coil
80 °F DB / 67 °F WB

Total, kW (MBH) 18.8 (64.2) 20.5 (69.8) 30.1 (102.6) 32.5 (110.9) 37.4 (127.6)
High Flow
Sensible, kW (MBH) 15 (51.2) 16.5 (56.4) 22.8 (77.6) 24.8 (84.8) 29.8 (101.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 16.1 (11.4) 17.6 (13.4) 25.7 (28.3) 27.9 (32.7) 32.2 (11.4)

Med Flow Total, kW (MBH) 17.2 (58.7) 19 (64.8) 28.3 (96.4) 30.5 (104) 34.2 (116.7)
(10 °F Sensible, kW (MBH) 14.2 (48.5) 15.8 (53.9) 22 (74.9) 23.9 (81.7) 28.2 (96.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.8 (6.4) 13.1 (7.8) 19.4 (16.9) 21.0 (19.5) 23.6 (6.4)

Low Flow Total, kW (MBH) 15.5 (52.9) 17.1 (58.5) 26.7 (91) 28.7 (97.9) 30.8 (105)
(12 °F Sensible, kW (MBH) 13.3 (45.5) 14.8 (50.5) 21.2 (72.4) 23.1 (78.8) 26.5 (90.3)
ΔTw
Flow Rate, GPM (Pressure Drop, ftH2O) 8.9 (3.8) 9.9 (4.6) 15.3 (10.9) 16.4 (12.5) 17.8 (3.8)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 12.8 (43.6) 13.3 (45.4) 22.1 (75.5) 23.7 (80.9) 25.3 (86.5)
High Flow
Sensible, kW (MBH) 12.4 (42.4) 13.3 (45.4) 19.9 (67.8) 21.6 (73.6) 24.7 (84.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.0 (5.6) 11.5 (6.1) 19.0 (16.3) 20.4 (18.6) 22.0 (5.6)

Med Flow Total, kW (MBH) 10.6 (36.1) 11.7 (40) 21 (71.7) 22.3 (76.3) 20.9 (71.4)
(10 °F Sensible, kW (MBH) 10.6 (36.1) 11.7 (40) 19.2 (65.4) 20.7 (70.6) 20.9 (71.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 7.3 (2.7) 8.2 (3.3) 14.4 (9.9) 15.4 (11.2) 14.6 (2.7)

High Flow Total, kW (MBH) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
(12 °F Sensible, kW (MBH) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.1 (1.2) 5.7 (1.6) 9.2 (4.4) 10.0 (5.1) 10.2 (1.2)
72 °F DB / 60 °F WB
Total, kW (MBH) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
High Flow
Sensible, kW (MBH) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.5 (3.5) 9.5 (4.3) 14.1 (9.5) 15.4 (11.1) 17.0 (3.5)

Med Flow Total, kW (MBH) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
(10 °F Sensible, kW (MBH) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.7 (1.6) 6.4 (2.0) 10.0 (5.1) 11.0 (6.0) 11.4 (1.6)

High Flow Total, kW (MBH) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
(12 °F Sensible, kW (MBH) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.6 (0.5) 4.1 (0.7) 7.0 (2.7) 7.7 (3.2) 7.2 (0.5)
(Note: The above Cooling capacities @ standard ft /min and ESP as shown on page 35, Evaporator Blower/Motor.)
3

43
CeilAiR ENGINEERING MANUAL

Electrical Data (FLA / MCA / MFS)


1. Electrical data is based on standard performance and component selection per the Technical Specifications/Performance
Capacity section of this document. Please consult your local sales representative for “special” equipment electrical data.
2. Electrical data is the same for horizontal and standard discharge cabinets.
3. High Static Pressure Belt-Drive Option - Electrical data in the pages to follow are based on standard CFMs and external
static pressures. Please consult your local sales representative for component and electrical rating data for this option.
4. Current draws in the following tables are specified as:
FLA = Full Load Amps
MCA = Minimum Circuit Amps (wire size amps)
MFS = Maximum Fuse Size

44
CeilAiR ENGINEERING MANUAL

DX Air, Water, and Glycol Cooled

With Condensate Pump (OHS-012 − OHS-060 AS)


OHS-012-AS OHS-018-AS OHS-024-AS OHS-032-AS OHS-040-AS OHS-048-AS OHS-060-AS
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING and CONDENSATE PUMP ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 12.9 18.4 25.0 16.0 21.5 30.0 18.7 26.9 40.0 21.1 30.2 45.0 22.4 31.5 45.0 N/A N/A
277/1/60 10.4 15.9 20.0 12.2 17.0 25.0 14.1 21.0 30 17.0 24.3 35.0 18.1 25.4 35.0 N/A N/A
208/3/60 N/A N/A 15.5 19.2 25 17.1 23.8 35.0 18.4 25.1 35.0 N/A N/A
460/3/60 N/A N/A 7.1 9.5 15 7.9 11.7 15.0 8.6 12.4 15.0 N/A N/A
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT, with or without Humidifier
208/1/60 34.3 45.2 50.0 37.4 48.2 50.0 40.1 53.6 60.0 42.5 56.9 60.0 43.8 58.2 60.0 N/A N/A
277/1/60 28.5 38.5 40.0 30.3 39.7 40.0 32.2 43.7 50.0 35.1 46.9 50.0 36.2 48.0 50.0 N/A N/A
208/3/60 N/A N/A 27.9 34.7 40.0 29.5 39.3 45.0 30.8 40.6 45.0 N/A N/A
460/3/60 N/A N/A 13.4 17.4 20.0 14.2 19.6 20.0 14.9 20.3 25.0 N/A N/A
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 21.1 26.6 35.0 24.2 29.7 40.0 26.9 35.0 50.0 29.3 38.4 50.0 30.6 39.7 50.0 N/A N/A
277/1/60 16.5 22.0 30.0 18.3 23.1 30.0 20.2 27.1 35.0 23.1 30.4 40.0 24.2 31.5 45.0 N/A N/A
208/3/60 N/A N/A 23.7 27.4 35.0 25.3 32.0 40.0 26.6 33.3 45.0 N/A N/A
460/3/60 N/A N/A 10.8 13.2 15.0 11.6 15.4 20.0 12.3 16.1 20.0 N/A N/A

-
Without Condensate Pump (OHS-012 − OHS-060 AS)
OHS-012-AS OHS-018-AS OHS-024-AS OHS-032-AS OHS-040-AS OHS-048-AS OHS-060-AS
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 11.7 17.2 25.0 14.8 20.3 30.0 17.5 25.6 40.0 19.9 29.0 45.0 21.2 30.3 45.0 N/A N/A
277/1/60 9.2 14.7 20.0 11.0 15.8 20.0 12.9 19.8 30.0 15.8 23.1 35.0 16.9 24.2 35.0 N/A N/A
208/3/60 N/A N/A 14.3 18.0 25.0 15.9 22.6 30.0 17.2 23.9 35.0 N/A N/A
460/3/60 N/A N/A 6.6 8.9 15.0 7.4 11.2 15.0 8.1 11.9 15.0 N/A N/A
COOLING and ELECTRIC REHEAT/HEAT, with or without Humidifier (No Condensate Pump)
208/1/60 33.1 44.0 45.0 36.2 47.0 50.0 38.9 52.4 60.0 41.3 55.7 60.0 42.6 57 60.0 N/A N/A
277/1/60 27.3 37.3 40.0 29.1 38.5 40.0 31.0 42.5 50.0 33.9 45.7 50.0 35.0 46.8 50.0 N/A N/A
208/3/60 N/A N/A 26.7 33.5 35.0 28.3 38.1 45.0 29.6 39.4 45.0 N/A N/A
460/3/60 N/A N/A 12.9 16.8 20.0 13.7 19.1 20.0 14.4 19.8 20.0 N/A N/A
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 19.9 25.4 30.0 23.0 28.5 35.0 25.7 33.8 45.0 28.1 37.2 50.0 29.4 38.5 50.0 N/A N/A
277/1/60 15.3 20.8 25.0 17.1 21.9 30.0 19.0 25.9 35.0 21.9 29.2 40.0 23.0 30.3 40.0 N/A N/A
208/3/60 N/A N/A 22.5 26.2 35.0 24.1 30.8 40.0 25.4 32.1 40.0 N/A N/A
460/3/60 N/A N/A 10.3 12.6 15.0 11.1 14.9 20.0 11.8 15.6 20.0 N/A N/A

45
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-012 − OHS-024 / AR, W, G)


OHS-012-AR, W and G OHS-018-AR, W and G OHS-024-AR, W and G
Model FLA (OEM Rated) FLA (OEM Rated) FLA (OEM Rated)
MCA MFS MCA MFS MCA MFS
AR W G AR W G AR W G
COOLING and CONDENSATE PUMP ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 10.0 8.6 10.4 15.5 20.0 11.8 10.1 12.3 17.3 25.0 14.5 11.9 15.4 22.6 35.0
277/1/60 8.6 7.6 8.9 14.1 20.0 9.3 8.0 9.7 14.1 20.0 11.2 9.3 11.8 18.1 30.0
208/3/60 N/A N/A 11.3 9.9 11.8 15.0 20.0
460/3/60 N/A N/A 5.4 4.8 5.6 7.8 15.0
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 31.0 30.0 31.8 42.3 45.0 33.2 31.5 33.7 44.0 45.0 35.9 33.3 36.8 49.4 50.0
277/1/60 26.7 25.7 27.0 36.8 40.0 27.4 26.1 27.8 36.8 40.0 29.3 27.4 29.9 40.8 45.0
208/3/60 N/A N/A 23.7 22.3 24.2 30.5 35.0
460/3/60 N/A N/A 11.7 11.1 11.9 15.7 20.0
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 18.2 16.8 18.6 23.7 30.0 20.0 18.3 20.5 25.5 35.0 22.7 20.1 23.6 30.9 45.0
277/1/60 14.7 13.7 15.0 20.2 25.0 15.4 14.1 15.8 20.2 25.0 17.3 15.4 17.9 24.2 35.0
208/3/60 N/A N/A 19.5 18.1 20.0 23.2 30.0
460/3/60 N/A N/A 9.1 8.5 9.3 11.5 15.0
COOLING,CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 31.4 30.0 31.8 42.3 45.0 33.2 31.5 33.7 44.0 45.0 35.9 33.3 36.8 49.4 50.0
277/1/60 26.7 25.7 27.0 36.8 40.0 27.4 26.1 27.8 36.8 40.0 29.3 27.4 29.9 40.8 45.0
208/3/60 N/A N/A 23.7 22.3 24.2 30.5 35.0
460/3/60 N/A N/A 11.7 11.1 11.9 15.7 20.0

Without Condensate Pump (OHS-012 − OHS-024 / AR, W, G)


OHS-012-AR, W and G OHS-018-AR, W and G OHS-024-AR, W and G
Model FLA (OEM Rated) FLA (OEM Rated) FLA (OEM Rated)
MCA MFS MCA MFS MCA MFS
AR W G AR W G AR W G
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 8.8 7.4 9.2 14.3 20.0 10.6 8.9 11.1 16.1 25.0 13.3 10.7 14.2 21.5 35.0
277/1/60 7.4 6.4 7.7 12.9 20.0 8.1 6.8 8.5 12.9 20.0 10.0 8.1 10.6 16.9 25.0
208/3/60 N/A N/A 10.1 8.7 10.6 13.8 20.0
460/3/60 N/A N/A 4.9 4.3 5.1 7.3 15.0
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 30.2 28.8 30.6 41.1 45.0 32.0 30.3 32.5 42.8 45.0 34.7 32.1 35.6 48.2 50.0
277/1/60 25.5 24.5 25.8 35.5 40.0 26.2 24.9 26.6 35.5 40.0 28.1 26.2 28.7 39.5 45.0
208/3/60 N/A N/A 22.5 21.1 23.0 29.3 35.0
460/3/60 N/A N/A 11.2 10.6 11.4 15.1 20.0
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 17.0 15.6 17.4 22.5 30.0 18.8 17.1 19.3 24.3 30.0 21.5 18.9 22.4 29.6 40.0
277/1/60 13.5 12.5 13.8 19.0 25.0 14.2 12.9 14.6 19.0 25.0 16.1 14.2 16.7 23.0 35.0
208/3/60 N/A N/A 18.3 16.9 18.8 22.0 30.0
460/3/60 N/A N/A 8.6 8.0 8.8 10.9 15.0
COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 30.2 28.8 30.6 41.1 45.0 32.0 30.3 32.5 42.8 45.0 34.7 32.1 35.6 48.2 50.0
277/1/60 25.5 24.5 25.8 35.5 40.0 26.2 24.9 26.6 35.5 40.0 28.1 26.2 28.7 39.5 45.0
208/3/60 N/A N/A 22.5 21.1 23.0 29.3 35.0
460/3/60 N/A N/A 11.2 10.6 11.4 15.1 20.0

46
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-032 − OHS-060 / AR, W, G)


OHS-032-AR, W and G OHS-040-AR, W and G OHS-048-AR, W and G OHS-060-AR, W and G
Model FLA (OEM Rated) FLA (OEM Rated) FLA (OEM Rated) FLA (OEM Rated)
MCA MFS MCA MFS MCA MFS MCA MFS
AR W G AR W G AR W G AR W G
COOLING and CONDENSATE PUMP ONLY, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 16.9 14.2 17.7 26.0 40.0 18.2 15.5 19.0 27.3 40.0 N/A N/A
277/1/60 14.1 11.8 14.8 21.4 35.0 15.2 12.9 15.9 22.5 35.0 N/A N/A
208/3/60 12.9 11.5 13.3 19.6 30.0 14.2 12.8 14.6 20.9 30.0 18.1 15.6 18.9 26.5 40.0 23.8 20.5 24.8 30.4 45.0
460/3/60 6.2 5.5 6.4 10.0 15.0 6.9 6.2 7.1 10.7 15.0 9.1 7.9 9.5 12.5 20.0 10.9 9.5 11.3 14.8 20.0
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 38.3 35.6 39.1 52.7 60.0 39.6 36.9 40.4 54.0 60.0 N/A N/A
277/1/60 32.2 29.9 32.9 44.0 50.0 33.3 31.0 34.0 45.1 50.0 N/A N/A
208/3/60 25.3 23.9 25.7 35.1 40.0 26.6 25.2 27.0 36.4 45.0 42.8 40.3 43.6 57.4 60.0 48.5 45.2 49.5 61.3 70.0
460/3/60 12.5 11.8 12.7 17.9 20.0 13.2 12.5 13.4 18.6 20.0 21.7 20.5 22.1 28.3 30.0 23.5 22.1 23.9 30.6 35.0
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 25.1 22.4 25.9 34.2 50.0 26.4 23.7 27.2 35.5 50.0 N/A N/A
277/1/60 20.2 17.9 20.9 27.5 40.0 21.3 19.0 22.0 28.6 40.0 N/A N/A
208/3/60 21.1 19.7 21.5 27.8 35.0 22.4 21.0 22.8 29.1 40.0 34.4 31.9 35.2 42.8 50.0 40.1 36.8 41.1 46.7 60.0
460/3/60 9.9 9.2 10.1 13.7 20.0 10.6 9.9 10.8 14.4 20.0 16.5 15.3 16.9 19.9 25.0 18.3 16.9 18.7 22.2 30.0
COOLING,CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 38.3 35.6 39.1 52.7 60.0 39.6 36.9 40.4 54.0 60.0 N/A N/A
277/1/60 32.2 29.9 32.9 44.0 50.0 33.3 31.0 34.0 45.1 50.0 N/A N/A
208/3/60 25.3 23.9 25.7 35.1 40.0 26.6 25.2 27.0 36.4 45.0 42.8 40.3 43.6 57.4 60.0 48.5 45.2 49.5 61.3 70.0
460/3/60 12.5 11.8 12.7 17.9 20.0 13.2 12.5 13.4 18.6 20.0 21.7 20.5 22.1 28.3 30.0 23.5 22.1 23.9 30.6 35.0

Without Condensate Pump (OHS-032 − OHS-060 / AR, W, G)


OHS-032-AR, W and G OHS-040-AR, W and G OHS-048-AR, W and G OHS-060-AR, W and G
Model FLA (OEM Rated) FLA (OEM Rated) FLA (OEM Rated) FLA (OEM Rated)
MCA MFS MCA MFS MCA MFS MCA MFS
AR W G AR W G AR W G AR W G
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 15.7 13.0 16.5 24.8 40.0 17.0 14.3 17.8 26.1 40.0 N/A N/A
277/1/60 12.9 10.6 13.6 20.2 30.0 14.0 11.7 14.7 21.3 35.0 N/A N/A
208/3/60 11.7 10.3 12.1 18.4 30.0 13.0 11.6 13.4 19.7 30.0 16.9 14.4 17.7 25.3 40.0 22.6 19.3 23.6 29.2 45.0
460/3/60 5.7 5.0 5.9 9.5 15.0 6.4 5.7 6.6 10.2 15.0 8.6 7.4 9.0 12.0 15.0 10.4 9.0 10.8 14.3 20.0
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 37.1 34.4 37.9 51.5 60.0 38.4 35.7 39.2 52.8 60.0 N/A N/A
277/1/60 31.0 28.7 31.7 42.8 50.0 32.1 29.8 32.8 43.9 50.0 N/A N/A
208/3/60 24.1 22.7 24.5 33.9 40.0 25.4 24.0 25.8 35.2 40.0 41.6 39.1 42.4 56.2 60.0 47.3 44.0 48.3 60.1 70.0
460/3/60 12.0 11.3 12.2 17.4 20.0 12.7 12.0 12.9 18.1 20.0 21.2 20.0 21.6 27.7 30.0 23.0 21.6 23.4 30.0 35.0
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 23.9 21.2 24.7 33.0 50.0 25.2 22.5 26.0 34.3 50.0 N/A N/A
277/1/60 19.0 16.7 19.7 26.3 40.0 20.1 17.8 20.8 27.4 40.0 N/A N/A
208/3/60 19.9 18.5 20.3 26.6 35.0 21.2 19.8 21.6 27.9 35.0 33.2 30.7 34.0 41.6 50.0 38.9 35.6 39.9 45.5 60.0
460/3/60 9.4 8.7 9.6 13.2 15.0 10.1 9.4 10.3 13.9 20.0 16.0 14.8 16.4 19.4 25.0 17.8 16.4 18.2 21.7 30.0
COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 37.1 34.4 37.9 51.5 60.0 38.4 35.7 39.2 52.8 60.0 N/A N/A
277/1/60 31.0 28.7 31.7 42.8 50.0 32.1 29.8 32.8 43.9 50.0 N/A N/A
208/3/60 24.1 22.7 24.5 33.9 40.0 25.4 24.0 25.8 35.2 40.0 41.6 39.1 42.4 56.2 60.0 47.3 44.0 48.3 60.1 70.0
460/3/60 12.0 11.3 12.2 17.4 20.0 12.7 12.0 12.9 18.1 20.0 21.2 20.0 21.6 27.7 30.0 23.0 21.6 23.4 30.0 35.0

47
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-048 − OHS-120 DAR, DW, DG)


OHS-048-DAR, DW and DG OHS-072-DAR, DW and DG OHS-084-DAR, DW and DG OHS-120-DAR, DW and DG
Model FLA (OEM rated) FLA (OEM rated) FLA (OEM rated) FLA (OEM rated)
MCA MFS MCA MFS MCA MFS MCA MFS
DAR DW DG DAR DW DG DAR DW DG DAR DW DG
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 19.3 16.5 20.3 24.5 30 22.9 201.1 23.7 33.3 45 31.4 27.4 32.6 46.7 60 45.5 38.9 47.5 53.9 70
460/3/60 9.1 7.9 9.5 12.6 15 11.8 10.4 12.2 17.8 20 15.9 13.9 16.5 21.7 25 20.3 17.5 21.1 25.8 30
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 36.3 35.2 37.1 46.5 50 39.3 37.9 39.7 52.2 60 44.5 42.5 45.1 60.5 70 52.7 49.4 53.7 65.5 70
460/3/60 18.3 17.7 18.5 23.8 25 20.2 19.5 20.4 27.2 30 22.5 21.5 22.8 29.6 30 25.4 24 25.8 32.5 35
COOLING, CONDENSATE PUMP, HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 35.6 32.8 36.6 40.8 45 37.1 34.3 37.9 47.5 50 45.6 41.6 46.8 60.9 70 59.7 53.1 61.7 68.1 80
460/3/60 16.5 15.3 16.9 20 25 18.2 16.8 18.6 24.2 30 22.3 20.3 22.9 28.1 35 26.7 23.9 27.5 32.2 40
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 36.6 35.2 37.1 46.5 50 39.3 37.9 39.7 52.2 60 45.6 42.5 46.8 60.9 70 59.7 53.1 61.7 68.1 80
460/3/60 18.3 17.7 18.5 23.8 25 20.2 19.5 20.4 27.2 30 22.5 21.5 22.9 29.6 35 26.7 24 27.5 32.5 40

Without Condensate Pump (OHS-048 − OHS-120 DAR, DW, DG)


OHS-048-DAR, DW and DG OHS-072-DAR, DW and DG OHS-084-DAR, DW and DG OHS-120-DAR, DW and DG
Model FLA (OEM rated) FLA (OEM rated) FLA (OEM rated) FLA (OEM rated)
MCA MFS MCA MFS MCA MFS MCA MFS
DAR DW DG DAR DW DG DAR DW DG DAR DW DG
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 18.1 15.3 19.1 23.3 30 21.7 18.9 22.5 32.1 40 30.2 26.2 31.4 45.5 60 44.3 37.7 46.3 52.7 70
460/3/60 8.6 7.3 8.9 12.1 15 11.3 9.9 11.7 17.3 20 15.4 13.4 16 21.2 25 19.8 17 20.6 25.3 30
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 35.4 34 35.9 45.3 50 38.1 36.7 38.5 51 60 43.3 41.3 43.9 59.3 70 51.5 48.2 52.5 64.3 70
460/3/60 17.8 17.2 18 23.3 25 19.7 19 19.9 26.7 30 22 21 22.3 29 30 24.9 23.5 25.3 31.9 35
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 34.4 31.6 35.4 39.6 45 35.9 33.1 36.7 56.3 50 44.4 40.4 45.6 59.7 70 58.5 51.9 60.5 66.9 80
460/3/60 16 14.8 16.4 19.5 20 17.7 16.3 18.1 23.7 30 21.8 19.8 22.4 27.6 35 26.2 23.4 27 31.7 40
COOLING and ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 35.4 34 35.9 45.3 50 38.1 36.7 38.5 51 60 44.4 41.3 45.6 59.7 70 58.5 51.9 60.5 66.9 80
460/3/60 17.8 17.2 18 23.3 25 19.7 19 19.9 26.7 30 22 21 22.4 29 35 26.2 23.5 27 31.9 40

48
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-012 − OHS-032 AHU)


OHS-012-AHU OHS-018-AHU OHS-024-AHU OHS-032-AHU
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 3.9 4.9 15 3.9 4.9 15 3.9 4.9 15 4.6 5.8 15
277/1/60 3 3.8 15 3 3.8 15 3 3.8 15 3.5 4.4 15
208/3/60 3.9 4.9 15 3.9 4.9 15 3.9 4.9 15 4.6 5.8 15
460/3/60 2 2.6 15 2 2.6 15 2 2.6 15 2 2.6 15
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 25.3 31.6 35 25.3 31.6 35 25.3 31.6 35 26 32.5 35
277/1/60 21.1 26.4 30 21.1 26.4 30 21.1 26.4 30 21.6 27 30
208/3/60 16.3 20.4 25 16.3 20.4 25 16.3 20.4 25 17 21.3 25
460/3/60 8.3 10.4 15 8.3 10.4 15 8.3 10.4 15 8.3 10.4 15
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 12.1 15.1 20 12.1 15.1 20 12.1 15.1 20 12.8 16 20
277/1/60 9.1 11.4 15 9.1 11.4 15 9.1 11.4 15 9.6 12 15
208/3/60 12.1 15.1 20 12.1 15.1 20 12.1 15.1 20 12.8 16 20
460/3/60 5.7 7.2 15 5.7 7.2 15 5.7 7.2 15 5.7 7.2 15
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 33.5 41.9 45 33.5 41.9 45 33.5 41.9 45 34.2 42.8 45
277/1/60 27.2 34 35 27.2 34 35 27.2 34 35 27.7 34.6 35
208/3/60 24.5 30.6 35 24.5 30.6 35 24.5 30.6 35 25.2 31.5 35
460/3/60 12 15.1 20 12 15.1 20 12 15.1 20 12 15.1 20

Without Condensate Pump (OHS-012 − OHS-032 AHU)


OHS-012-AHU OHS-018-AHU OHS-024-AHU OHS-032-AHU
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15
277/1/60 1.8 2.3 15 1.8 2.3 15 1.8 2.3 15 2.3 2.9 15
208/3/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15
460/3/60 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 24.1 30.1 35 24.1 30.1 35 24.1 30.1 35 24.8 31 35
277/1/60 19.9 24.9 25 19.9 24.9 25 19.9 24.9 25 20.4 25.5 30
208/3/60 15.1 18.9 20 15.1 18.9 20 15.1 18.9 20 15.8 19.8 20
460/3/60 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15
277/1/60 7.9 9.9 15 7.9 9.9 15 7.9 9.9 15 8.4 10.5 15
208/3/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15
460/3/60 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 32.3 40.4 45 32.3 40.4 45 32.3 40.4 45 33 41.3 45
277/1/60 26 32.5 35 26 32.5 35 26 32.5 35 26.5 33.1 35
208/3/60 23.3 29.1 30 23.3 29.1 30 23.3 29.1 30 24 30 35
460/3/60 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15

49
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-040 − OHS-060 AHU)


OHS-040-AHU OHS-048-AHU OHS-060-AHU
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 5.9 7.4 15 N/A N/A
277/1/60 4.6 5.8 15 N/A N/A
208/3/60 5.9 7.4 15 5.1 6.4 15 6.3 7.9 15
460/3/60 2.7 3.4 15 2.6 3.3 15 3.4 4.3 15
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 27.3 34.1 35 N/A N/A
277/1/60 22.7 28.4 30 N/A N/A
208/3/60 18.3 22.9 25 29.8 37.3 40 31 38.8 40
460/3/60 9 11.3 15 15.2 19.1 20 16 20.1 25
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 14.1 17.6 20 N/A N/A
277/1/60 10.7 13.4 15 N/A N/A
208/3/60 14.1 17.6 20 21.4 26.8 30 22.6 28.3 30
460/3/60 6.4 8.1 15 10 12.6 15 10.8 13.6 15
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 35.5 44.4 45 N/A N/A
277/1/60 28.8 36 40 N/A N/A
208/3/60 26.5 33.1 35 46.1 57.6 60 47.3 59.1 60
460/3/60 12.7 15.9 20 22.6 28.3 30 23.4 29.3 30

Without Condensate Pump (OHS-040 − OHS-060 AHU)


OHS-040-AHU OHS-048-AHU OHS-060-AHU
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 4.7 5.9 15 N/A N/A
277/1/60 3.4 4.3 15 N/A N/A
208/3/60 4.7 5.9 15 3.9 4.9 15 5.1 6.4 15
460/3/60 2.1 2.6 15 2.2 2.8 15 2.9 3.6 15
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 26.1 32.6 35 N/A N/A
277/1/60 21.5 26.9 30 N/A N/A
208/3/60 17.1 21.4 25 28.6 35.8 40 29.8 37.3 40
460/3/60 8.4 10.5 15 14.8 18.5 20 15.5 19.4 20
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 12.9 16.1 20 N/A N/A
277/1/60 9.5 11.9 15 N/A N/A
208/3/60 12.9 16.1 20 20.2 25.2 30 21.4 26.8 30
460/3/60 5.8 7.3 15 9.6 12 15 10.3 12.9 15
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 34.3 42.9 45 N/A N/A
277/1/60 27.6 34.5 35 N/A N/A
208/3/60 25.3 31.6 35 44.9 56.1 60 46.1 57.6 60
460/3/60 12.1 15.1 20 22.2 27.8 30 22.9 28.6 30

50
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-048 − OHS-120 DAHU)


OHS-048-DAHU OHS-072-DAHU OHS-084-DAHU OHS-120-DAHU
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 4.5 5.6 15 6.3 7.9 15 8.2 10.3 15 10.5 13.1 15
460/3/60 2.3 2.9 15 3.4 4.3 15 3.9 4.9 15 5.3 6.7 15
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 29.2 36.5 40 31 38.8 40 32.9 41.1 45 35.2 44 45
460/3/60 14.9 18.6 20 16 20.1 25 16.5 20.7 25 17.9 22.4 25
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 20.8 26 30 20.5 25.6 30 22.4 28 30 24.7 30.9 35
460/3/60 9.7 12.1 15 9.8 12.3 15 10.3 12.9 15 11.7 14.7 15
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 45.5 56.9 60 45.2 56.5 60 47.1 58.9 60 49.4 61.8 70
460/3/60 22.3 27.9 30 22.4 28.1 30 22.9 28.7 30 24.3 30.4 35

Without Condensate Pump (OHS-048 − OHS-120 DAHU)


OHS-048-DAHU OHS-072-DAHU OHS-084-DAHU OHS-120-DAHU
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 3.3 4.1 15 5.1 6.4 15 7 8.8 15 9.3 11.6 20
460/3/60 1.8 2.2 15 2.9 3.6 15 3.4 4.3 15 4.8 6 15
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 28 35 40 29.8 37.3 40 31.7 39.6 40 34 42.5 45
460/3/60 14.4 17.9 20 15.5 19.4 20 16 20 25 17.4 21.8 25
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 19.6 24.5 25 19.3 24.1 25 21.2 26.5 30 23.5 29.4 30
460/3/60 9.1 11.4 15 9.3 11.6 15 9.8 12.3 15 11.2 14 15
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 44.3 55.4 60 44 55 60 45.9 57.4 60 48.2 60.3 70
460/3/60 21.8 27.2 30 21.9 27.4 30 22.4 28 30 23.8 29.8 30

51
CeilAiR ENGINEERING MANUAL

DX Free Cooling and Alternate Water Source

With Condensate Pump (OHS-012 − OHS-024 HAR, HW, HG)


OHS-012-HAR, HW and HG - OHS-018-HAR, HW and HG - OHS-024-HAR, HW and HG -
AWS or FC AWS or FC AWS or FC
Model
FLA (OEM rated) FLA (OEM rated) FLA (OEM rated)
MCA MFS MCA MFS MCA MFS
HAR HW HG HAR HW HG HAR HW HG
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 10.3 8.9 10.7 15.8 25 11.3 9.6 11.8 16.8 25 14.9 12.3 15.8 23 35
277/1/60 9.4 8.4 9.7 14.9 20 9.4 8.1 9.8 14.4 20 11.9 10 12.5 18.8 30
208/3/60 N/A N/A 11.2 9.8 11.7 14.9 20
460/3/60 N/A N/A 5.2 4.6 5.4 7.6 15
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 31.7 30.3 32.1 42.6 45 32.7 31 33.2 43.5 45 36.3 33.7 37.2 49.8 50
277/1/60 27.5 26.5 27.8 37.5 40 27.5 26.2 27.9 36.8 40 30 28.1 30.6 41.5 45
208/3/60 N/A N/A 23.6 22.2 24.1 30.4 35
460/3/60 N/A N/A 11.5 10.9 11.7 15.5 20
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 18.5 17.1 18.9 24 30 19.5 17.8 20 25 35 23.1 20.5 24 31.3 45
277/1/60 15.5 14.5 15.8 21 25 15.5 14.2 15.9 20.3 25 18 16.1 18.6 24.9 35
208/3/60 N/A N/A 19.4 18 19.9 23.1 30
460/3/60 N/A N/A 8.9 8.3 9.1 11.3 15
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 31.7 30.3 32.1 42.6 45 32.7 31 33.2 43.5 45 36.3 33.7 37.2 49.8 50
277/1/60 27.5 26.5 27.8 37.5 40 27.5 26.2 27.9 36.8 40 30 28.1 30.6 41.5 45
208/3/60 N/A N/A 23.6 22.2 24.1 30.4 35
460/3/60 N/A N/A 11.5 10.9 11.7 15.5 20

Without Condensate Pump (OHS-012 − OHS-024 HAR, HW, HG)


OHS-012-HAR, HW and HG - OHS-018-HAR, HW and HG - OHS-024-HAR, HW and HG -
AWS or FC AWS or FC AWS or FC
Model
FLA (OEM rated) FLA (OEM rated) FLA (OEM rated)
MCA MFS MCA MFS MCA MFS
HAR HW HG HAR HW HG HAR HW HG
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 9.1 7.7 9.5 14.6 20 10.1 8.4 10.6 15.6 25 13.7 11.1 14.6 21.9 35
277/1/60 8.2 7.2 8.5 13.7 20 8.2 6.9 8.6 13 20 10.7 8.8 11.3 17.6 25
208/3/60 N/A N/A 10 8.6 10.5 13.7 20
460/3/60 N/A N/A 4.7 4.1 4.9 7 15
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 30.5 29.1 30.9 41.4 45 31.5 29.8 32 42.3 45 35.1 32.5 36 48.6 50
277/1/60 26.3 25.3 26.6 36.3 40 26.3 25 26.7 35.7 40 28.8 26.9 29.4 40.3 45
208/3/60 N/A N/A 22.4 21 22.9 29.2 35
-

460/3/60 N/A N/A 11 10.4 11.2 14.9 15


COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 17.3 15.9 17.7 22.8 30 18.3 16.6 18.8 23.8 30 21.9 19.3 22.8 30 45
277/1/60 14.3 13.3 14.4 19.8 25 14.3 13 14.7 19.1 25 16.8 14.9 17.4 23.7 35
208/3/60 N/A N/A 18.2 16.8 18.7 21.9 30
460/3/60 N/A N/A 8.4 7.8 8.6 10.8 15
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 30.5 29.1 30.9 41.4 45 31.5 29.9 32 42.3 45 35.1 32.5 36 48.6 50
277/1/60 26.3 25.3 26.6 36.3 40 26.3 25 26.7 35.7 40 28.8 26.9 29.4 40.3 45
208/3/60 N/A N/A 22.4 21 22.9 29.2 35
460/3/60 N/A N/A 11 10.4 11.2 14.9 15

52
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-032 − OHS-060 HAR, HW, HG)


OHS-032-HAR, HW and HG - OHS-040-HAR, HW and HG - OHS-048-AR, W and G - OHS-060 AR, W and G -
AWS or FC AWS or FC AWS or FC AWS or FC
Model FLA (OEM rated) FLA (OEM rated) FLA (OEM rated) FLA (OEM rated)
MCA MFS MCA MFS MCA MFS MCA MFS
HAR HW HG HAR HW HG AR W G AR W G

COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 18.6 15.9 19.4 27.7 40 18.6 15.9 19.4 27.7 40 N/A N/A
277/1/60 15.8 13.5 16.5 23.1 35 15.8 13.5 16.5 23.1 35 N/A N/A
208/3/60 13.4 12 13.8 20.1 30 13.4 12 13.8 20.1 30 19.3 16.8 20.1 27.7 40 25.7 22.4 26.7 32.3 50

-
460/3/60 6.8 6.1 7 10.6 15 6.8 6.1 7 10.6 15 9.9 8.7 10.3 13.3 20 11.4 10 11.8 15.3 20
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 40 37.3 40.8 54.4 60 40 37.3 40.8 54.4 60 N/A N/A
277/1/60 33.9 31.6 34.6 45.7 50 33.9 31.6 34.6 45.7 50 N/A N/A
208/3/60 25.8 24.4 26.2 35.6 40 25.8 24.4 26.2 35.6 40 44 41.5 44.8 58.6 60 50.4 47.1 51.4 63.2 70
460/3/60 13.1 12.4 13.3 18.5 20 13.1 12.4 13.3 18.5 20 22.5 21.3 22.9 29.1 30 24 22.6 24.4 31.1 35
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 26.8 24.1 27.6 35.9 50 26.8 24.1 27.6 35.9 50 N/A N/A
277/1/60 21.9 19.6 22.6 29.2 40 21.9 19.6 22.6 29.2 40 N/A N/A
208/3/60 21.6 20.2 22 28.3 40 21.6 20.2 22 28.3 40 35.6 33.1 36.4 44 60 42 38.7 43 48.6 60
460/3/60 10.5 9.8 10.7 14.3 20 10.5 9.8 10.7 14.3 20 17.3 16.1 17.7 20.7 25 18.8 17.4 19.2 22.7 30
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 40 37.3 40.8 54.4 60 40 37.3 40.8 54.4 60 N/A N/A
277/1/60 33.9 31.6 34.6 45.7 50 33.9 31.6 34.6 45.7 50 N/A N/A
208/3/60 25.8 24.4 26.2 35.6 40 25.8 24.4 26.2 35.6 40 44 41.5 44.8 58.6 60 50.4 47.1 51.4 63.2 70
460/3/60 13.1 12.4 13.3 18.5 20 13.1 12.4 13.3 18.5 20 22.5 21.3 22.9 29.1 30 24 22.6 24.4 31.1 35

Without Condensate Pump (OHS-032 − OHS-060 HAR, HW, HG)


OHS-032-HAR, HW and HG - OHS-040-HAR, HW and HG - OHS-048-AR, W and G - OHS-060 AR, W and G -
AWS or FC AWS or FC AWS or FC AWS or FC
Model
FLA (OEM rated) FLA (OEM rated) FLA (OEM rated) FLA (OEM rated)
MCA MFS MCA MFS MCA MFS MCA MFS
HAR HW HG HAR HW HG AR W G AR W G
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 17.4 14.7 18.1 26.5 40 17.4 14.7 18.2 26.5 40 N/A N/A
277/1/60 14.6 12.3 15.3 21.9 35 14.6 12.3 15.3 21.9 35 N/A N/A
208/3/60 12.2 10.8 12.6 18.9 30 12.2 10.8 12.6 18.9 30 18.1 15.6 18.9 26.5 40 24.5 21.2 25.5 31.1 50
460/3/60 6.3 5.6 6.5 10.1 15 6.3 5.6 6.5 10.1 15 9.4 8.2 9.8 12.8 20 10.9 9.5 11.3 14.8 20
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 38.8 36.1 39.6 53.2 60 38.8 36.1 39.6 53.2 60 N/A N/A
277/1/60 32.7 30.4 33.4 44.5 50 32.7 30.4 33.4 44.5 50 N/A N/A
208/3/60 24.6 23.2 25 34.4 40 24.6 23.2 25 34.4 40 42.8 40.3 43.6 57.4 60 49.2 45.9 50.2 62 70
460/3/60 12.6 11.9 12.8 18 20 12.6 11.9 12.8 18 20 22 20.8 22.4 28.5 30 23.5 22.1 23.9 30.5 35
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 25.6 22.9 26.4 34.7 50 25.6 22.9 26.4 34.7 50 N/A N/A
277/1/60 20.7 18.4 21.4 28 40 20.7 18.4 21.4 28 40 N/A N/A
208/3/60 20.4 19 20.8 27.1 35 20.4 19 20.8 27.1 35 34.4 31.9 35.2 42.8 50 40.8 37.5 41.8 47.4 60
460/3/60 10 9.3 10.2 13.8 20 10 9.3 10.2 13.8 20 16.8 15.6 17.2 20.2 25 18.3 16.9 18.7 22.2 30
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 38.8 36.1 39.6 53.2 60 38.8 36.1 39.6 53.2 60 N/A N/A
277/1/60 32.7 30.4 33.4 44.5 50 32.7 30.4 33.4 44.5 50 N/A N/A
208/3/60 24.6 23.2 25 34.4 40 24.6 23.2 25 34.4 40 42.8 40.3 43.6 57.4 60 49.2 45.9 50.2 62 70
460/3/60 12.6 11.9 12.8 18 20 12.6 11.9 12.8 18 20 22 20.8 22.4 28.5 30 23.5 22.1 23.9 30.5 35

53
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-048 − OHS-120 DAR, DW, DG)


OHS-048-DAR, DW and DG - OHS-072-DAR, DW and DG - OHS-084-DAR, DW and DG - OHS-120-DAR, DW and DG -
AWS or FC AWS or FC AWS or FC AWS or FC
Model
FLA (OEM rated) FLA (OEM rated) FLA (OEM rated) FLA (OEM rated)
MCA MFS MCA MFS MCA MFS MCA MFS
DAR DW DG DAR DW DG DAR DW DG DAR DW DG
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 19.9 17.1 20.9 25.1 30 24.8 22 25.6 35.2 45 33.7 29.7 34.9 49 60 50.3 43.7 52.3 58.7 70
460/3/60 9.4 8.2 9.8 13 15 12.3 10.9 12.7 18.3 20 17.3 15.3 17.9 23.1 30 22.2 19.4 23 27.7 35
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidififier)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 37.2 35.8 37.7 47.1 50 41.2 39.8 41.6 54.1 60 46.8 44.8 47.4 62.8 70 57.5 54.2 58.5 70.3 80
460/3/60 18.6 18 18.8 24.1 25 20.7 20 20.9 27.7 30 23.9 22.9 24.2 31 35 27.3 25.9 27.7 34.4 40
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 36.2 33.4 37.2 41.4 50 39 36.2 39.8 49.4 60 47.9 43.9 49.1 63.2 80 64.5 57.9 66.5 72.9 90
460/3/60 16.8 15.6 17.2 20.4 25 18.7 17.3 19.1 24.7 30 23.7 21.7 24.3 29.5 35 28.6 25.8 29.4 34.1 40
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 37.2 35.8 37.7 47.1 50 41.2 39.8 41.6 54.1 60 47.9 44.8 49.1 63.2 80 64.5 57.9 66.5 72.9 90
460/3/60 18.6 18 18.8 24.1 25 20.7 20 20.9 27.7 30 23.9 22.9 24.3 31 35 28.6 25.9 29.4 34.4 40

Without Condensate Pump (OHS-048 − OHS-120 DAR, DW, DG)


OHS-048-DAR, DW and DG - OHS-072-DAR, DW and DG - OHS-084-DAR, DW and DG - OHS-120-DAR, DW and DG -
AWS or FC AWS or FC AWS or FC AWS or FC
Model
FLA (OEM rated) FLA (OEM rated) FLA (OEM rated) FLA (OEM rated)
MCA MFS MCA MFS MCA MFS MCA MFS
DAR DW DG DAR DW DG DAR DW DG DAR DW DG
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 18.7 15.9 19.7 23.9 30 23.6 20.8 24.4 34 45 32.5 28.5 33.7 47.8 60 49.1 42.5 51.1 57.4 70
460/3/60 8.9 7.7 9.3 12.4 15 11.8 10.4 12.2 17.8 20 16.8 14.8 17.4 22.6 30 21.7 18.9 22.5 27.2 35
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 36 34.6 36.5 45.9 50 40 38.6 40.4 52.9 60 45.6 43.6 46.2 61.6 70 56.3 53 57.3 69.1 80
460/3/60 18.1 17.5 18.3 23.6 25 20.2 19.5 20.4 27.2 30 23.4 22.4 23.7 30.4 35 26.8 25.4 27.2 33.8 35
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 N/A N/A N/A N/A
-

277/1/60 N/A N/A N/A N/A


208/3/60 35 32.2 36 40.2 45 37.8 35 38.6 48.2 60 46.7 42.7 47.9 62 70 63.3 56.7 65.3 71.7 90
460/3/60 16.3 15.1 16.7 19.9 20 18.2 16.8 18.6 24.2 30 23.2 21.2 23.8 29 35 28.1 25.3 28.9 33.6 40
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A
208/3/60 36 34.6 36.5 45.9 50 40 38.6 40.4 52.9 60 46.7 43.6 47.9 62 70 63.3 56.7 65.3 71.7 90
460/3/60 18.1 17.5 18.3 23.6 25 20.2 19.5 20.4 27.2 30 23.4 22.4 23.8 30.4 35 28.1 25.4 28.9 33.8 40

54
CeilAiR ENGINEERING MANUAL

Chilled Water

With Condensate Pump (OHS-012 − OHS-040 C)


OHS-012-C OHS-018-C OHS-024-C OHS-032-C OHS-040-C
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 3.9 4.9 15 3.9 4.9 15 3.9 4.9 15 4.6 5.8 15 5.9 7.4 15
277/1/60 3 3.8 15 3 3.8 15 3 3.8 15 3.5 4.4 15 4.6 5.8 15
208/3/60 3.9 4.9 15 3.9 4.9 15 3.9 4.9 15 4.6 5.8 15 5.9 7.4 15
460/3/60 2 2.6 15 2 2.6 15 2 2.6 15 2 2.6 15 2.7 3.4 15
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 25.3 31.6 35 25.3 31.6 35 25.3 31.6 35 26 32.5 35 27.3 34.1 35
277/1/60 21.1 36.4 30 21.1 36.4 30 21.1 36.4 30 21.6 27 30 22.7 28.4 30
208/3/60 16.3 20.4 25 16.3 20.4 25 16.3 20.4 25 17 21.3 25 18.3 22.9 25
460/3/60 8.3 10.4 15 8.3 10.4 15 8.3 10.4 15 8.3 10.4 15 9 11.3 15
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 12.1 15.1 20 12.1 15.1 20 12.1 15.1 20 12.8 16 20 14.1 17.6 20
277/1/60 9.1 11.4 15 9.1 11.4 15 9.1 11.4 15 9.6 12 15 10.7 13.4 15
208/3/60 12.1 15.1 20 12.1 15.1 20 12.1 15.1 20 12.8 16 20 14.1 17.6 20
460/3/60 5.7 7.2 15 5.7 7.2 15 5.7 7.2 15 5.7 7.2 15 6.4 8.1 15
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 33.5 41.9 45 33.5 41.9 45 33.5 41.9 45 34.2 42.8 45 35.5 44.4 45
277/1/60 27.2 34 35 27.2 34 35 27.2 34 35 27.7 34.6 35 28.8 36 40
208/3/60 24.5 30.6 35 24.5 30.6 35 24.5 30.6 35 25.2 31.5 35 26.5 33.1 35

460/3/60 12 15.1 20 12 15.1 20 12 15.1 20 12 15.1 20 12.7 15.9 20

-
Without Condensate Pump (OHS-012 − OHS-040 C)
OHS-012-C OHS-018-C OHS-024-C OHS-032-C OHS-040-C
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 4.7 5.9 15
277/1/60 1.8 2.3 15 1.8 2.3 15 1.8 2.3 15 2.3 2.9 15 3.4 4.3 15
208/3/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 4.7 5.9 15
460/3/60 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 2.2 2.8 15
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 24.1 30.1 35 24.1 30.1 35 24.1 30.1 35 24.8 31 35 26.1 32.6 35
277/1/60 19.9 24.9 25 19.9 24.9 25 19.9 24.9 25 20.4 25.5 30 21.5 26.9 30
208/3/60 15.1 18.9 20 15.1 18.9 20 15.1 18.9 20 15.8 19.8 20 17.1 21.4 25
460/3/60 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 8.5 10.6 15
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 12.9 16.1 20
277/1/60 7.9 9.9 15 7.9 9.9 15 7.9 9.9 15 8.4 10.5 15 9.5 11.9 15
208/3/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 12.9 16.1 20
460/3/60 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 5.9 7.4 15
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 32.3 40.4 45 32.3 40.4 45 32.3 40.4 45 33 41.3 45 34.3 42.9 45
277/1/60 26 32.5 35 26 32.5 35 26 32.5 35 26.5 33.1 35 27.6 34.5 35
208/3/60 23.3 29.1 30 23.3 29.1 30 23.3 29.1 30 24 30 35 25.3 31.6 35
460/3/60 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 12.2 15.3 20

55
CeilAiR ENGINEERING MANUAL

With Condensate Pump (OHS-048 − OHS-120 C)


OHS-048-C OHS-060-C OHS-072-C OHS-084-C OHS-120-C
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 N/A N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A N/A
208/3/60 5.1 6.4 15 6.3 7.9 15 6.3 7.9 15 8.2 10.3 15 10.5 13.1 20
460/3/60 2.6 3.3 15 3.4 4.3 15 3.4 4.3 15 3.9 4.9 15 5.3 6.7 15
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 N/A N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A N/A
208/3/60 29.8 37.3 40 31 38.8 40 31 38.8 40 32.9 41.1 45 35.2 44 45
460/3/60 15.2 19.1 20 16 20.1 25 16 20.1 25 16.5 20.7 25 17.9 22.4 25
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 N/A N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A N/A
208/3/60 21.4 26.8 30 22.6 28.3 30 20.5 25.6 30 22.4 28 30 24.7 30.9 35
460/3/60 10 12.6 15 10.8 13.6 15 9.8 12.3 15 10.3 12.9 15 11.7 14.7 15
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 N/A N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A N/A
208/3/60 46.1 57.6 60 47.3 59.1 60 45.2 56.5 60 47.1 58.9 60 49.4 61.8 70
460/3/60 22.6 28.3 30 23.4 29.3 30 22.4 28.1 30 22.9 28.7 30 24.3 30.4 35

Without Condensate Pump (OHS-048 − OHS-120 C)


OHS-048-C OHS-060-C OHS-072-C OHS-084-C OHS-120-C
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 N/A N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A N/A
208/3/60 3.9 4.9 15 5.1 6.4 15 5.1 6.4 15 7 8.8 15 9.3 11.6 20
460/3/60 2.1 2.6 15 2.9 3.6 15 2.9 3.6 15 3.4 4.3 15 4.8 6 15
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 N/A N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A N/A
208/3/60 28.6 35.8 40 29.8 37.3 40 29.8 37.3 40 31.7 39.6 40 34 42.5 45
460/3/60 14.7 18.4 20 15.5 19.4 20 15.5 19.4 20 16 20 25 17.4 21.8 25
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 N/A N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A N/A
208/3/60 20.2 25.2 30 21.4 26.8 30 19.3 24.1 25 21.2 26.5 30 23.5 29.4 30
460/3/60 9.5 11.9 15 10.3 12.9 15 9.3 11.6 15 9.8 12.3 15 11.2 14 15
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 N/A N/A N/A N/A N/A
277/1/60 N/A N/A N/A N/A N/A
208/3/60 44.9 56.1 60 46.1 57.6 60 44 55 60 45.9 57.4 60 48.2 60.3 70
460/3/60 22.1 27.6 30 22.9 28.6 30 21.9 27.4 30 22.4 28 30 23.8 29.8 30

56
CeilAiR ENGINEERING MANUAL

Dimensional Data and Installation Drawings

The sections that follow present the following information:

• Unit Net Weights (lbs) Table


• Refrigerant Connection Sizes Table
• Air Cooled Systems Dimensional Drawings
• DX Air Handling Units Dimensional Drawings
• Water / Glycol Cooled Systems Dimensional Drawings
• Chilled Water Systems Dimensional Drawings

57
CeilAiR ENGINEERING MANUAL

Physical Data and Connection Sizes


Unit Net Weights (lb)

(Cooling Only. Please see notes, given in lb.)


OHS-( )-( ) 012 018 024 032 040 048 060 072 084 120
OHS-( )-AS 210 215 220 255 265 - - - - -
OHS-( )-AR 160 165 170 205 215 370 380 - - -
OHS-( )-HAR 185 190 195 230 240 - - - - -
OHS-( )-AHU 120 120 120 155 165 270 280 - - -
OHS-( )-HAHU 135 140 145 180 190 - - - - -
OHS-( )-DAR - - - - - 420 - 450 510 580
OHS-( )-DAHU - - - - - 320 - 350 410 480
OHS-( )-W 180 200 210 245 260 395 405 - - -
OHS-( )-HW 205 225 235 265 285 - - - - -
OHS-( )-DW - - - - - 440 - 470 550 625
OHS-( )-G 180 200 210 245 260 395 405 - - -
OHS-( )-HG 205 225 235 265 285 - - - - -
OHS-( )-DG - - - - - 440 - 470 550 625
OHS-( )-C 120 125 125 160 170 280 290 365 415 495
OHS-( )-HC 140 145 150 185 190 - - - - -
OHS-( )-( )-FC 245 265 275 300 310 500 510 570 660 745
OHS-( )-( )-AWS 225 230 235 270 280 460 470 550 610 705

Table Legend: Model Sizes

Note-1: Features/Options 012/040 048/060 048/120-D( )


Hyphen (‘-’) value means indicated unit not available in the indicated capac-
ity/configuration. Adding Features: Net Additions

Note-2: Steam Humidifier + 20 lb + 25 lb + 25 lb


Unit net weights shown above are for Cooling Only Evaporator units without
receivers. If Humidity Options (steam humidifier; electric, hot gas, hot water Electric Reheat + 15 lb + 25 lb + 25 lb
or steam reheat) and/or -30 °F flooded receiver(s) are applicable, please Hot Gas Reheat + 30 lb + 35 lb + 45 lb
add the approximate weights shown in the Model Sizes table on this page to Hot Water Reheat + 30 lb + 35 lb + 45 lb
the unit net weights. Steam Reheat + 30 lb + 35 lb + 45 lb

-30 °F Flooded + 30 lb + 50 lb + 100 lb


Condensate Pump + 10 lb + 10 lb + 10 lb
(Figures may vary if
receiver skid is used)

58
CeilAiR ENGINEERING MANUAL

Refrigerant Piping Connection Sizes


Refrigerant Piping Connection Sizes - Single Compressor / Circuit Systems
OHS-012-( ) OHS-018-( ) OHS-024-( ) OHS-032-( ) OHS-040-( ) OHS-048-( ) OHS-060-( )
Model
“A” “B” “C” “A” “B” “C” “A” “B” “C” “A” “B” “C” “A” “B” “C” “A” “B” “C” “A” “B” “C”
OHS-( )-AR ---- 3/8 1/2 ---- 3/8 1/2 ---- 3/8 5/8 ---- 1/2 5/8 ---- 1/2 7/8 ---- 1/2 7/8 ---- 1/2 7/8
OHS-( )-AHU 5/8 3/8 ---- 3/4 3/8 ---- 3/4 3/8 ---- 3/4 1/2 ---- 7/8 1/2 ---- 7/8 1/2 ---- 7/8 1/2 ----

Refrigerant Piping Connection Sizes -


Dual Compressor / Circuit Systems
Sizes given are per circuit O.D.
OHS-048-( ) OHS-072-( ) OHS-084-( ) OHS-120-( )
Model
“A” “B” “C” “A” “B' “C” “A” “B” “C” “A” “B” “C”
OHS-( )-DAR ---- 3/8 5/8 ---- 1/2 5/8 ---- 1/2 7/8 ---- 1/2 7/8
OHS-( )-DAHU 3/4 3/8 ---- 7/8 1/2 ---- 7/8 1/2 ---- 7/8 1/2 ----

Legend:
Notes:
“A” = Suction Line, inches OD Copper
Note-1:-------- means connection type not applicable to this unit configuration.
“B” = Liquid Line, inches OD Copper
“C” = Hot Gas, inches OD Copper Note-2: Dimensions shown represent the “pipe connection size” only. For
information detailing the sizing of the interconnecting refrigerant and water lines,
please refer to the CeilAiR Installation, Operation and Maintenance Manual.

Source Water/Glycol Connection Sizes


Source Water / Glycol Piping Connection Sizes
(Single Compressor / Single Circuit Systems)
012 018 024 032 040 048 060
Model
IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT
OHS-( )-W/G 5/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8
OHS-( )-W/G-FC 5/8 5/8 5/8 7/8 7/8 1-1/8 1-1/8

Chilled Water / Alternate Water Source Piping Connection Sizes


012 018 024 032 040 048 060
Model
IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT IN/OUT
OHS-( )-C and AWS 5/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8

048 072 084 120


Model
IN/OUT IN/OUT IN/OUT IN/OUT
OHS-( )-C and AWS. 1-1/8 1-1/8 1-1/8 1-3/8

Legend:

IN = Inlet Connection, inches OD Copper


OUT = Outlet Connection, inches OD Copper

59
CeilAiR ENGINEERING MANUAL

Air Cooled Systems

OHS-012 thru 032-AS


Self-Contained, Air Cooled
DIMENSIONAL DATA (in.)
(“Ductless” Spot Cooler)
MODEL “A” “B” “C” “D”
OHS-012, 018,and 024-AS 20.38 15.5 5.50 18.0
OHS-032-AS 26.38 21.5 10.50 23.0

DIMENSIONAL DATA (in.)


MODEL “A” “B” “C” “D” “E” “F” OHS-012 thru 032-AS Self-Con-
OHS-012, 018,and 024-AS 20.38 15.5 5.75 18.0 19.75 16.13 tained, Air Cooled (“Ducted” Evap
OHS-032-AS 26.38 21.5 10.88 23.0 15.63 19.75 - Direct Driven)

Air Cooled (“Ductless” Spot


Cooler)

60
CeilAiR ENGINEERING MANUAL

OHS-040-HAS Self-Contained, Air


Cooled (“Ducted” Version - Direct
Driven)

DIMENSIONAL DATA (in.) OHS-012 thru 032-AR Remote


MODEL “A”
Air Cooled, Evaporator (“Ductless”
OHS-012, 018,and 024-AR. 20.38
Spot Cooler)
OHS-032-AR 26.38

OHS-012 thru 032-AR Remote DIMENSIONAL DATA (in.)


MODEL “A” “B” “E” “F”
Air Cooled, Evaporator (“Ducted”
OHS-012, 018 and 024-AR 20.38 15.5 19.75 16.13
Version - Direct Driven) OHS-032-AR 26.38 21.5 15.63 19.75

61
CeilAiR ENGINEERING MANUAL

OHS-040-AR Remote Air Cooled,


Evaporator (“Ductless” Spot Cooler)

DIMENSIONAL DATA (in.)


MODEL “A” “B” “C” “L” “M”
OHS-012 thru 040-HAR Remote Air
OHS-012, 018, and see see see Cooled, Evaporator “H-Series Ducted Ver-
20.0 16.0
024-HAR note note note sion” (040 - Direct Driven) and (012/040
see see see
OHS-032- and 040-HAR 24.0 20.0
note note note - Belt Driven)
OHS-040-HAR, @ 0.3 in.
24.0 20.0 6.62 11.38 10.5
ESP (direct drive blower)

Note: Consult your local Sales Represen-


tative for blower outlet dimensional data for
“High-Static Pressure Blower Option”.

DIMENSIONAL DATA (in.)


OHS-048 thru 060-AR Remote MODEL “C” “L” “M”
Air Cooled, Evaporator (Ducted OHS-040 and 060-AR 6.62 11.38 13.12
Only)

62
CeilAiR ENGINEERING MANUAL

OHS-048 thru 084-DAR Remote Air Cooled, DIMENSIONAL DATA (in.)


Evaporator (DUAL Compressors) MODEL “C” “L” “M”
OHS-048-DAR 6.62 11.38 13.12
OHS-072 and 084-DAR 7.62 13.44 15.62

DIMENSIONAL DATA (in.)


MODEL “C” “L” “M”
OHS-120-DAR Remote Air Cooled,
OHS-120-DAR 7.25 13.44 15.62
Evaporator (DUAL Compressors)

63
CeilAiR ENGINEERING MANUAL

OHS-012 thru 040-AHU DX - Air


DX Air Handling Units
Handling Unit (“Ductless” Spot
Cooler)
DIMENSIONAL DATA (in.)
MODEL “A”

OHS-012, 018, and 024-AHU 20.7

OHS-032 and 040-AR 26.7

DIMENSIONAL DATA (in.) OHS-012 thru 040-AHU DX - Air


MODEL “A” “B” “E” “F” Handling Unit (“Ducted Version” -
OHS-012, 018, and 024-AHU 20.7 15.5 19.88 15.75 Direct Driven)
OHS-032 and 040-AHU 26.7 21.5 15.75 19.88

DIMENSIONAL DATA (in.)

OHS-012 thru 040-HAHU DX - MODEL “A” “E” “F” “C” “L” “M”

“H-Series”, Air Handling Unit (“Ducted OHS-012, 018, and 024-AHU 20.0 19.75 15.63
see
note
see
note
see
note
Version” - Belt Driven) see see see
OHS-032 and 040-AHU 24.0 19.75 19.75
note note note

Note: Consult your local Sales Repre-


sentative for blower outlet dimensional
data for “High-Static Pressure Blower
Option”.

64
CeilAiR ENGINEERING MANUAL

DIMENSIONAL DATA (in.)


MODEL “C” “L” “M”
OHS-048 thru 060-AHU DX - Air OHS-048 and 060-AHU 6.62 11.38 13.12
Handling Unit (Ducted Only)

DIMENSIONAL DATA (in.)


OHS-048 thru 084-DAHU DUAL
Model “C” “L” “M” Circuit, DX - Air Handling Unit (Ducted
OHS-048-DAHU 6.62 11.38 13.12 Only)
OHS-072 and 084-AHU 7.62 13.44 15.62

DIMENSIONAL DATA (in.)


OHS-120-DAHU DUAL Circuit, DX - MODEL
Std ft3/min @ 0.5” ESP
“C” “L” “M”
Air Handling Unit (Ducted Only)
OHS-120-DAHU 7.38 13.5 15.69

65
CeilAiR ENGINEERING MANUAL

Water/Glycol Systems

OHS-012 thru 032-W / G Self-Con- DIMENSIONAL DATA (in.)


MODEL “A”
tained, Water/Glycol Cooled (“Duct-
OHS-012, 018 and 024 W/G 20.4
less” Spot Cooler)
OHS-032-W/G 26.4

DIMENSIONAL DATA (in.)


MODEL “A” “B” “E” “F”
OHS-012 thru 032-W / G Self-Con-
OHS-012, 018 and 024-W/G 20.4 15.5 19.75 16.13 tained, Water/Glycol Cooled (“Ducted
OHS-032-W/G 26.4 21.5 15.63 19.75 Version” - Direct Drive)

OHS-040-W / G Self-Contained,
Water/Glycol Cooled (“Ductless”
Spot Cooler)

66
CeilAiR ENGINEERING MANUAL

DIMENSIONAL DATA (in.)


OHS-012 thru 040-HW / HG and optional
MODEL “A” “B” “C” “L” “M”
OHS-012 thru 040-HW/HG-FC “H-Series
OHS-012, 018, and 024- see see see
Ducted Version” (040 - Direct Driven) and HW/HG (and HW/HG-FC)
20.0 16.0
note note note
(012/040 - Belt Driven) OHS-032, and 040-HW/HG
24.0 20.0
see see see
(and HW/HG-FC) note note note
OHS-040-HW/G @ 0.3” ESP
24.0 20.0 6.62 11.38 10.5
(Direct-Drive Blower)

Note: Consult your local Sales Representative


for blower outlet dimensional data for “High-
Static Pressure Blower Option”.

DIMENSIONAL DATA (in.)


MODEL “C” “L” “M”
OHS-048 thru 060-W / G and
OHS-048 and 060-W/G 6.62 11.38 13.12 optional OHS-048 thru 060-W/G-
see see FC Self-Contained, Water/Glycol
OHS-048 and 060-W/G-FC see note
note note Cooled (Ducted Only)

Note: Consult your local Sales Representative


for blower outlet dimensional data for “High-
Static Pressure Blower Option”.

67
CeilAiR ENGINEERING MANUAL

DIMENSIONAL DATA (in.)


MODEL “C” “L” “M”
OHS-048 thru 084-DW / DG and optional OHS-048-DW/DG 6.62” 11.38” 13.19”
W/DG-FC Self-Contained, Water/ Glycol OHS-072-084-DW/DG 7.62” 13.5” 15.69”
Cooled (DUAL Compressors) OHS-048/084-DW/DG-FC see note see note see note

Note: Consult your local Sales Represen-


tative for blower outlet dimensional data for
“High-Static Pressure Blower Option”.

DIMENSIONAL DATA (in.)


MODEL “C” “L” “M” OHS-120-DW / DG Self-Contained,
OHS-120-DW/DG 7.25 13.5 15.69 Water/Glycol Cooled (DUAL Compressors)

68
CeilAiR ENGINEERING MANUAL

DIMENSIONAL DATA (in.)


OHS-120-DW / DG-FC
MODEL “C” “L” “M”
“FREE-COOLING Version”
OHS-120-DW/DG-FC 7.62 13.5 15.69
Self-Contained, Water/Glycol
Cooled (DUAL Compressors)

69
CeilAiR ENGINEERING MANUAL

OHS-012 thru 040-C Chilled Chilled Water Systems


DIMENSIONAL DATA (in.)
Water System (“Ductless” Spot MODEL “A”
Cooler) OHS-012-, 018, and 024-C, in. 20.7
OHS-032 and 040-C, in. 26.7

DIMENSIONAL DATA (in.)


MODEL “A” “B” “E” “F” OHS-012 thru 040-C Chilled Water
OHS-012, 018, and 024-C 20.4 15.5 19.75 15.63 System (“Ducted Version” - Direct
OHS-032, and 040-C 26.4 21.5 15.63 19.75 Driven)

DIMENSIONAL DATA (in.)


OHS-012 thru 040-HC “H-Series”, MODEL “A” “E” “F” “C” “L” “M”
Chilled Water System (“Ducted OHS-012, 018, and 024-HC 20.0 19.75 15.63
SEE SEE SEE
NOTE NOTE NOTE
Version” - Belt Driven)
SEE SEE SEE
OHS-032 and 040-HC 24.0 19.75 19.75
NOTE NOTE NOTE

Note: Consult your local Sales Represen-


tative for blower outlet dimensional data
for “High-Static Pressure Blower Option”.

70
CeilAiR ENGINEERING MANUAL

OHS-048 thru 060-C Chilled


Water System (“Ducted” - Belt
Driven)

DIMENSIONAL DATA (in.)


MODEL “C” “L” “M”
OHS-048 and 060-C 6.62 11.38 13.12

DIMENSIONAL DATA (in.)


MODEL “C” “L” “M” OHS-072 thru 084-C Chilled Water
OHS-072 and 084-C 7.62 13.5 15.69 System (“Ducted” - Belt Driven)

DIMENSIONAL DATA (in.)


OHS-120-C Chilled Water System MODEL “C” “L” “M”
(“Ducted” - Belt Driven) OHS-120-C 7.38 13.5 15.7

71
CeilAiR ENGINEERING MANUAL

STULZ CeilAiR Series Ducted Evaporator (Available on all model


3.5 – 35 kW Single/Dual Circuit sizes)
The air conditioner shall be provided with evaporator supply and
Ceiling Mounted return air duct connections.
Precision Air Conditioners Air Filtration
Summary The air conditioning unit shall have a drop out, 1 in. deep,
Class 2 (per UL Standard 900) filter easily accessed through
This specification describes requirements for a precision
the hinged return grille. The filter shall have a rating of at least
environmental control system. The STULZ CeilAiR ceiling- 80% average arrestance as measured by ASHRAE Standard
mounted air conditioning system shall provide precision 52-76 test method.
temperature and/or humidity control for computer rooms or
rooms containing communications or other highly sensitive heat Mechanical Components
load equipment where continuous 24 hour a day, 365 days a
year air conditioning is required. The units are designed with a Blowers/Motors
wide range of options to handle all precision cooling
Direct Drive Systems
applications. The blower shall be direct driven with double width, double
inlet housing and forward curved blades. The blower shall be
Design Requirements dynamically and statically balanced to minimize vibration and
The system shall be a ceiling mounted supplemental air operate in the Class I range.
conditioner. The air conditioner shall be fully accessible in-place The evaporator motor shall be factory wired for the correct
through easily removable side access panels. speed to produce the specified air quantity. The motor shall
have internal overload protection.
Quality Assurance
Belt Driven Systems
The manufacturer shall maintain a set of international standards The blower shall be belt driven with a double width, double inlet
of quality management to ensure product quality. Prior to housing and forward curved blades and permanently lubricated
shipment each system shall be subject to a complete ball bearings sized for an average 100,000 hours of service
operational and functional testing based on predefined life. The blowers shall be dynamically and statically balanced to
procedures. The air conditioner manufacturer shall be ISO minimize vibration and operate in the Class I range. The blower
shall have an adjustable base for belt tensioning and a locking
9001:2015 certified.
system to prevent the motors from moving. Motor drive sheave
shall have an adjustable pitch to change the speed of the
Cabinet blower. The motor shall be 1,725 RPM and shall have overload
The cabinet and access panels shall be fabricated from protection and a minimum NEMA service factor of 1.15.
aluminum for corrosion protection and to minimize the system’s
weight. The panels shall be lined with 2 lb/ft2 high density sound REFRIGERATION SYSTEM
and thermal insulation and sealed with self-extinguishing
gasketing conforming to NFPA 90A and 90B. All piping and components contained within the
refrigeration system shall be rated for use with R407C
refrigerant. The refrigeration circuit shall include, as a
Air Flow Patterns minimum, a refrigerant dryer/strainer, sight glass with
“Ductless” Spot Cooler (Models OHS-012 moisture detector, thermal expansion valve, evaporator coil,
thru 040-( ) only) compressor, high-pressure switch with manual reset, and low-
The air conditioner shall be designed for installation in a standard pressureswitch with automatic reset.
2 ft x 4 ft ceiling grid for ductless supply and return evaporator Scroll Compressor
air through a factory provided bottom supply and return filter
grille. The compressor shall be a high efficiency, high reliability, low
noise scroll compressor. The compressor shall be complete
with internal vibration isolation, internal thermal overloads,
internal pressure relief valve, internal discharge gas vibration
eliminator, and external vibration mounting isolation.

72
CeilAiR ENGINEERING MANUAL

Dual Compressor System Free-Cooling Systems (Optional)


(Models OHS-( )-D()) DX Water/Glycol Cooled systems with Free-Cooling shall be
provided with the following standard DX head pressure and
The air conditioner shall be a dual scroll compressor system with Free-Cooling valve combination:
two independent refrigeration circuits to provide 50% capacity
unloading, as well as component redundancy. DX Valves – 3-way, 150 psig
The air conditioner shall be provided with a 2-stage temperature FC Valve – 3-way, 300 psig
controller with microprocessor-based control logic for automatic Alternate Water Source Systems (Optional)
staging.
The alternate water source cooling shall be controlled by the
Evaporator Coil following standard and optional control valves:
The evaporator coil shall be constructed of seamless drawn 2- way, 150 psig (Standard)
copper tubes, mechanically bonded to tempered aluminum fins 3- way, 350 psig (Optional)
with enhanced design for maximum heat transfer and mounted 3- way, 400 psig (Optional)
in a sloped stainless-steel condensate drain pan. The coil shall be A 2/3-way modulating AWS cooling control valve shall be
designed for a maximum of 500 ft/min face velocity. factory installed. Precision cooling control shall be
Air Cooled Heat Rejection accomplished via an analog control signal to the proportionally
actuating control valve.
0 °F, Fan Cycling / Fan Speed
The air-cooled system shall incorporate a low ambient fan
Chilled Water Systems
cycling / fan speed head pressure control. The pressure control Chilled Water Cooling Coil
shall be for year-round air conditioning system operation down to
The coil shall be constructed of seamless drawn copper
0 °F DB minimum ambient air temperature.
tubes, mechanically bonded to tempered aluminum fins with
-20°F Variable Fan Speed Control enhanced fin design for maximum heat transfer and mounted
The air-cooled system shall incorporate a low ambient, variable in a sloped stainless-steel condensate drain pan. The coil shall
speed fan, head pressure control. The pressure control shall be be designed for a maximum of 500 ft./min. face velocity. The
for year-round air conditioning system operation down to - water circuit shall be designed to distribute water into the
20°F DB minimum ambient air temperature. entire coil face area. Manual air bleed vents and drain ports
shall be factory installed.
-30°F Flooded Control
The air-cooled system shall incorporate a low ambient flooded
Chilled Water Control Valve
Cooling capacity shall be controlled by a factory-installed slowly
head pressure control. The pressure control shall be for year-
opening and slowly closing 2-way motorized control valve rated
round system operation down to -30°F DB minimum ambient air for a maximum 300 psi wwp.
temperature. Liquid refrigerant receivers with receiver liquid
sight glass and head pressure regulator valves (for flooded Overflow Safety Float Switch
condenser operation) shall be included. A condensate pan water level switch shall be incorporated to
shut the system down if a condensate overflow condition is
Water/Glycol Cooled Heat Rejection sensed.
Heat Exchanger Remote Start/Stop
Each evaporator refrigerant circuit shall be provided with a Included in the system’s electrical control circuit shall be a 2-
factory-installed single pass, counterflow configured, tube-in- pin terminal connection for remote start/stop of the CeilAiR air
tube coaxial condenser designed and tested for 450 psi wwp. conditioner by remote source.
2-Way, 150 psig Regulating Valve (Standard) Electrical System
Each refrigerant circuit’s head pressure shall be controlled by a
The electrical system shall conform to National Electrical Code
factory-installed 2-way water / glycol regulating valve rated for
requirements. The control circuit shall be 24 volts AC, wire in
150 psi wwp.
accordance with NEC Class II requirements. The control
circuit wire shall not be smaller than 18 AWG. All wiring shall
DX Water Cooled and Glycol Cooled systems are available with be neatly wrapped and routed in bundles. Each wire shall end
following standard and optional head pressure regulating control with a service loop and be securely fastened by an approved
valves: method. Each wire in the unit shall be numbered for ease of
2-way,150 psig (Standard) service tracing.
2-way, 350, 400 psig (Optional)
3-way, 150, 350, 400 psig (Optional)

73
CeilAiR ENGINEERING MANUAL
All electrically actuated components shall be easily accessible
from the front of the unit without reaching over exposed high
The controller shall receive inputs for measurable
voltage components or rotating parts. Each high voltage circuit
shall be individually protected by circuit breakers or manual control conditions (temperature, relative humidity, and
motor starters on all phases. The blower motor shall have thermal dew point) via return air or room mounted sensors. The
and short circuit protection. Line voltage and 24-volt control internal logic will then determine if the conditions
circuit wiring shall be routed in separate bundles. require cooling, humidification or dehumidification.
The electric box shall be positioned for service convenience and Control setpoints shall be established to maintain
shall include all the contactors, starters, fuses, circuit breakers, design conditions of the installation. The controller will
terminal boards and control transformer required for operation respond accordingly to changes in these conditions and
of the STULZ unit and shall allow for full service access. control the output/demand for the appropriate mode of
Controller operation until user defined conditions are achieved.
Field Configurable
A-Tech-1.1 Controller
The CeilAiR ceiling air conditioner shall be provided with a The program for the E² Series controller shall be field
STULZ slim-line, ultra-thin profile, 1-stage cool / 1-stage heat, configurable, so the operator can select control
remote wall mounted programmable digital microprocessor setpoints specific to the application. The operator
based controller. interface for the E² controller is provided via a door
Notes: mounted user interface
• The A-Tech-1.1 thermostat is standard on all single stage DX display panel. The display panel shall be a backlit LCD
and non-proportional chilled water systems. graphical display and function keys that give complete
• The A-Tech-1.2 thermostat is standard on all dual stage DX control and monitoring capability of the precision
systems. cooling system. The menu-driven interface shall provide
• A remote sensor (wired) is available on request. the ability to scroll through and enter various menu
screens.
A-Tech-1.1 Features: Password Protection
• Auto changeover for Heat/Cool Modes
Access to the Info Menu, Alarms Log, and the ability to
• Selectable °F or °C display
monitor room conditions shall be allowed without the
• Fan selector for continuous fan operation use of a password. Modifications to the control setpoints
• Built-in short cycle protection shall require the use of a password. The controller shall
• Internal switch to lock-out the keypad to prevent unauthorized be programmed to recognize predetermined security
tampering levels before allowing access to display screens
• Electronic calibration containing critical variables. Three secured menu levels
• 45 second fan purge after heating and cooling call (Control, Service and Factory) will support unique
• Day/Night button for user selectable alternate setpoint passwords that must be entered to access the menu
manual setback screens so only authorized personnel may perform
modifications to the settings.
E² Series Controller Restorable Parameters/Factory Defaults
General Upon initial start-up the system shall operate using the
The advanced microprocessor-based E² Series controller shall setpoints programmed by the factory. The customer
be equipped with flexible software capable of meeting the may enter new operating parameters in the Control
specific needs of the application. The setpoints shall be default menu and the system will then operate accordingly. The
and their ranges shall be easily viewed and adjusted from the new setpoints may be stored as, “Customer Default
user interface display. The program and operating parameters Setpoints”. The primary setpoints entered by thefactory
shall be permanently stored on a non-volatile system in the event remain stored in the controller’s memory as, “Factory
of power failure. Setpoints”. The setpoints for the system may be re-
adjusted in the Control menu at any time. If it becomes
The controller shall be designed to manage temperature and
necessary, the customer may restore the setpoints
relative humidity (RH) levels to a user defined setpoint via control
back to the Customer Default setpoint values or to the
output signals to the system.
original Factory (primary) setpoint values.

74
CeilAiR ENGINEERING MANUAL
Timer Feature Optional Features
The timer shall enable a setup of an operating schedule to
STULZ CeilAiR standard features can be deleted and/or
automatically scale back or shut down the air conditioner during
substituted with optional features to allow you the flexibility to
low demand or unoccupied periods. This is an energy saving
select the configuration best suited for your application.
feature to create an operating schedule tailored to the needs of
the building. An evening (night-setback) schedule may also be
created to enable the system to operate at night with relaxed
Mechanical Options
temperature/humidity setpoints and offsets. Full-Floating, Hot Gas Bypass
A/C Grouping pLAN Operation (Optional) (Models OHS-( )-()AHU/RCU-() only)
Multiple STULZ CeilAiR system controllers shall be able to be
The CeilAiR ceiling A/C shall incorporate a full floating hot gas
connected (grouped) to a pLAN local network, allowing the
bypass system to provide modulation of the unit’s cooling
communication of data and information from each controller to a
capacity and evaporator coil freeze protection under low load
central control terminal or Lead controller. The Lead controller
conditions.
display screens can be used to monitor and adjust group control
variables for the individual system controllers. Each E² Snap-Acting, Hot Gas Bypass
controller connected to the pLAN network shall be identified (Models OHS-()-AR, W and G only)
with its own unique address. Multiple STULZ CeilAiR systems
The STULZ CeilAiR ceiling mounted air conditioning system
consisting of up to eight STULZ precision air conditioners
shall incorporate a snap-acting hot-gas bypass system to
equipped with like controllers may be controlled and monitored
provide modulation of the unit’s cooling capacity and
via the E² series controller. With multiple STULZ CeilAiR systems
evaporator coil freeze protection under low load conditions.
each unit can selectively be configured as Active to operate as a
primary A/C, Capacity Assist for staged operation, or as High Static Pressure Belt-Drive Blowers
Standby to come online for a failed air conditioning unit to
The CeilAiR ceiling air conditioner shall be provided with a high
ensure continuous availability. The controller may also be
static pressure belt-driven evaporator blower to provide
configured to rotate units with timed duty cycling to promote
standard unit airflow.
equal run-time and assure that each STULZ CeilAiR system,
within the rotating group, is operationally exercised on a periodic (Note: Due to the probable change in standard unit blower motor
timed basis. horsepower for the High Static Belt-Drive Blower option, please
consult your local STULZ sales representative for the following
Remote BMS Interface (Optional) unit specification changes: Blower Motor Horsepower, Net
The E² series controller shall incorporate a communication Cooling Capacity, Electrical Data, Discharge Blower Data
interface port that can be field connected to a Building
Unit Air Flow Rate (ft3/min) will match values shown in the
Management System via Modbus, BACnet MS/TP, SNMP,
Performance Data tables for each respective unit model.)
HTTP, or BACnet over ETHERNET/IP as configured by the
factory. A controller interfaced to a network must be configured Low Entering Condenser Water Kit
for BMS communication.
For Water/Glycol systems that require entering condenser
Alarms water temperatures from 45°F to 65°F, the system provides
Alarm conditions shall activate a red LED indicator that a factory installed in-line liquid refrigerant receiver to help
backlights the alarm function key. As an option, an alarm reduce the negative effect the low condenser source can have
condition may also be enunciated by an audible alarm signal. An on the evaporator. A compressor crankcase heater is
alarm is acknowledged by pressing the alarm key. This calls up standard with this option. (Compressor Sound Jackets are not
alarm display screens that provides a text message detailing the available with this option due to the crankcase heater).
alarm conditions. After an alarm condition is corrected, the alarm Steam Generating Humidifier
can be cleared by pressing the alarm key.
The humidifier shall be a self-contained atmospheric steam
E² Constant Contact (Optional) generator. The humidifier assembly shall include an integral fill
The control package shall include a STULZ Constant Contact cup, fill and drain valves, disposable steam cylinder and
short-term power supply for the E² Series Controller to allow associated piping. The humidifier shall be equipped with an
the controller to manage the power transfer switch from one auto-adaptive control system to optimize water conductivity,
primary power source to another while maintaining control automatic drain and flush cycles, minimize energy waste
communications with an active monitoring system. The E² and maximize cylinder life. The humidifier shall have output
Constant Contact shall permit a minimum of one-minute ride between 20% and 100% of rated capacity. The unit shall
through period. include draw in water tempering to ensure the drain water
does not exceed 140°F during operation.

75
CeilAiR ENGINEERING MANUAL
Dehumidification Cycle DX extruded aluminum heat sink and solid-state logic system
The system shall be a refrigeration-based dehumidification to provide close dry bulb temperature control.
mode. Moisture is condensed on the cooling coil and
discharged through the condensate drain. Reheat (electric, hot Low Profile Condensate Pump
gas, steam or hot water) shall be used to offset sensible cooling A Low-Profile condensate pump designed for limited height
during the dehumidification cycle. ceiling plenum installation shall be factory provided for
automatic removal of condensate and humidifier flush water
Dehumidification Cycle CW (if applicable). The condensate pump shall be field installed as
The system shall be provided with a dehumidification control a standard.
mode. The chilled water valve shall be opened to allow chilled The Low-Profile condensate pump can be factory installed as
water flow during a dehumidification demand. Moisture is an option on models OHS-012/040-AS, AHU, AR, W, G and
condensed on the cooling coil and discharged through the C.
condensate drain. Reheat (electric, hot water) shall be provided
All-Metal Condensate Pump
to offset sensible cooling during the dehumidification cycle.
A heavy-duty All-Metal condensate pump shall be provided for
Electric Reheat/Heat automatic removal of condensate and humidifier flush water (if
applicable).
A factory mounted and wired low-watt density, electric resistance
The pump shall be constructed with a cast aluminum reservoir
heater shall be included to provide automatic sensible reheating
and impeller; aluminum reservoir cover and impeller chamber
during the dehumidification cycle and automatic heating mode.
cover; stainless steel fasteners and a stainless-steel motor
Electric heaters shall be provided with miniature shaft. The condensate pump meets most local codes for
thermal/magnetic circuit breakers that shall protect each certification as a “plenum rated” pump. The condensate pump
ungrounded conductor. Also included will be one automatic shall be field installed only.
reset and one manual reset over-temperature safety device (pilot The condensate pump shall be specifically designed to operate
duty). with the higher condensate temperatures caused by the flush
and drain cycle of the electrode canister humidifiers.
Hot Gas Reheat
(Models OHS-()-AS, AR, W and G only) Dual Overflow Safety Switches
In addition to the standard condensate pan overflow safety
A factory-installed copper tube, aluminum-fin hot gas reheat coil
float(s), the condensate pump shall include an internal overflow
and valve shall be provided for automatic sensible reheating safety float switch which, when wired to the A/C’s remote stop/
mode during dehumidification cycle is provided. Hot compressor start terminals, shall open the A/C’s control circuit, thereby
discharge gas shall be diverted from the condenser to the hot gas shutting the A/C down in the event of a condensate overflow.
reheat coil providing energy-free sensible reheating.
Air Filtration
Hot Water Reheat/Heat CeilAiR ceiling A/C’s are available with the following standard
(F1) and optional (F2 and F3) high efficiency IAQ-conscious
A factory-installed, copper tube, aluminum-fin heat/
filtration:
reheat coil and 2-way control valve shall be provided to
F1: 1 in., 20% effective filtration (standard) F2:
control the flow of hot water for automatic sensible
reheating mode during the dehumidification cycle and 2 in., 30% effective filtration
automatic heating mode as required. F3: 2 in., 30% plus 4 in., 60% for 95% effective filtration
(includes field-installed filter box for 4 in. filter)
Steam Reheat/Heat
Air Pattern Type Filters Available
A factory installed copper tube, aluminum fin
heat/reheat coil and 2-way control valve shall be Direct Drive012/040
provided to control the flow of steam for automatic w/ Spot Cooler: F1
sensible reheating mode during the dehumidification
w/ Ducted Return: F1, F2 (n/a 024)
cycle and automatic heating mode as required.
Belt-Drive Units
Note: Steam trap and steam piping specialties shall be
provided by others, not STULZ w/ Ducted Return: F1, F2 and F3

SCR Fired Reheat (Requires Filter ratings are based on dust spot efficiency ratings per
ASHRAE Test Standard 52-76.
E²controller)
Note: F2 and F3 optional filters create additional static pressure
The electric heat/reheat shall be controlled through a and may require the High Static Pressure Belt-Drive Option.
“Zero Firing” Silicon Controlled Rectifier (SCR) with an Please consult your local Sales Representative for details.

76
CeilAiR ENGINEERING MANUAL

Smoke Detection
Note: Three phase power supply is a standard
A photo-electric smoke detector shall be factory installed and
feature on models OHS-048 and larger units.
wired in the return air section of the STULZ CeilAiR air
conditioning system. The photo-electric detector shall include 277/1/60 Power Supply
built-in circuitry that performs a functional test of all detection (Models OHS-012 thru-040)
circuits at least once every 40 seconds without the need for A main power distribution block shall be located in the
generating smoke. The UL-listed velocity range shall be 0-3000 air conditioner’s electric box for single point power
fpm. The air conditioner will shut down upon sensing smoke in connection to a 277/1/60 power supply source. All
the return air stream. system components (motor, heater and humidifier, if
applicable) shall be rated for operation with a 277/1/60
Firestat power supply. 277V to 208V main power step-down
The STULZ CeilAiR system shall be provided with a factory transformers shall not be required.
wired and mounted firestat. The firestat shuts down the air
Fast-delivery orders sometimes require the OHS
conditioner upon sensing a high return air temperature.
system be shipped from stock as 208/1/60. In those
cases, 277/1/60 applications are provided with a field-
Remote Water Detector-Spot Type
installed 277-to-208V step-down transformer.
A remote single point water/leak detector shall be factory
supplied and shall ship separately for field installation. Upon Main Power Service Switch
sensing a water leak, the normally closed water detector control The main power service switch shall be the NEMA 3R or
circuit shall open, thereby shutting down the STULZ CeilAiR NEMA-12 non-fused type, depending on the OHS model
water producing components. selected. The disconnect switch shall have a lockable
handle.
Remote Water Detector-Dual Spot Type
Field installed main power service switches shall be the
A dual remote single point water/leak detector shall be factory standard option, however, switches can be optionally
supplied and shall ship separately for field installation. Upon factory mounted on select CeilAiR systems. Factory
sensing a water leak, the normally closed water detector control mounting of disconnect switches is not available on
circuit shall open, thereby shutting down the STULZ CeilAiR models OHS-012, 018, 024 and 032-AS incorporating
water producing components. the “Ducted” Evaporator Connection option.
Remote Water Detector-Strip Type
A 20 ft. remote strip/cable type water/leak detector shall be Air-Side Economizer Controls
provided for remote field installation. In addition to the 20 ft. The STULZ CeilAiR system controller shall be equipped
sensing cable, a 24-volt water detector power module shall with a unique air-side economization mode for
require field mounting and wiring to the factory provided terminal applications using outdoor air-side economizing.
connection. Upon sensing a water leak, the normally closed The STULZ Air-Side economizer control package shall
water detector control circuit shall open, thereby shutting down include an outdoor temperature and humidity sensor,
the STULZ CeilAiR water producing components. remote space return air sensor, and supply air sensor for
proper control during economizer operation.
Compressor Sound Jacket
(Air Cooled 0 °F OHS-()-AS and Water/Glycol Cooled Only) Individual discrete analog output signals (0-10 VDC) are
available to allow control of the external outdoor air
The compressor shall be provided with an acoustical sound
intake damper and exhaust relief provisions. Control
jacket (shipped loose). Each sound jacket shall have a snap settings shall be included for both temperature and
closure system for ease of removing and re-installation during humidity properties of the outdoor air. A damper signal
maintenance. The sound jacket shall have a Noise Reduction lockout shall be included if the outdoor air conditions
Coefficient NRC of 85 per ASTM C-423 and a Sound Trans- reaches user adjustable limits.
mission Loss STC of 11 per ASTM E-90. The economizing damper signal shall allow a minimum
Electrical Options output setting for minimum outside air control to meet
ventilation requirements.
Three Phase Power Supply
(Available on OHS-024, 032 and 040-() units.)
Compressor, (belt-drive blower motor and electric heat/reheat
if applicable) shall be three phase in lieu of standard single
phase. All other components (5/10 lb humidifier and direct drive
motor(s)) shall be single phase, with each leg of power supply
balanced as closely as possible.

77
CeilAiR ENGINEERING MANUAL

Alternate Water Source


To use building chilled water supply when available as the
primary cooling cycle, with compressor, cooling as a
backup, an Alternate Water Source cooling cycle is
provided.
The air conditioner has two cooling systems:
Primary Mode
The primary mode of cooling is a chilled water/glycol
circuit with alternate water source cooling coil and 3-way
modulating (0-10 Vdc) control valve rated for300 psig.
w.w.p.
Secondary/Backup Mode
The controller microprocessor’s Alternate Water Source
program algorithm analyzes input data from factory
provided water inlet temperature, and return room air
temperature, and relative humidity sensors. Based on this
data, the controller automatically controls the sequencing
of the primary AWS chilled water to and from the
secondary/ backup compressor DX mode of operation. If
chilled water is available, the system operates like a chilled
water unit, without the compressor operating. When the
water temperature is too high, or the water flow rate is not
sufficient, the air conditioner automatically switches to the
compressor, DX refrigerant cycle.
Code Conformance
The supplied system shall be with the following
compliance approvals:

CETL US listed to UL 1995 (2011 Ed. 4)


CSA C22.2 No. 236 (2011 Ed. 4)

78
CeilAiR ENGINEERING MANUAL

North American Headquarters


STULZ Air Technology Systems, Inc.
1572 Tilco Drive | Frederick, MD 21704
301.620.2033 | Fax: 301.662.5487 | [email protected]
Technical Support: 888.529.1266

www.stulz-usa.com

QE-OHS0023B- Feb. 2018 © STULZ Air Technology Systems, Inc. - Specifications subject to change without notice.