STULZ CeilAir Engineering Manual
STULZ CeilAir Engineering Manual
Engineering Manual
Ceiling Mounted Precision Air Conditioners/Air Handlers
3.5-35 kW / 60 Hz
CeilAiR ENGINEERING MANUAL
Notice
This document contains information protected by copyright. All rights are reserved. The owner of the equipment
for which this manual is written may photocopy the contents of this manual for internal use only. No part of this
document may be photocopied, reproduced, or translated into another language for use by anyone other than the
owner of the equipment for which this manual is written without the prior written consent of STULZ Air Technology
Systems, Inc. (STULZ).
This document contains confidential and proprietary information of STULZ Air Technology Systems, Inc.
Distributing or photo- copying this document for external distribution is in direct violation of U.S. copyright laws
and is strictly prohibited without the express written consent of STULZ.
Unpublished — rights reserved under the copyright laws of the United States and of other countries. Other
brands and tradenames are trademarks of their respective owners.
Copyright 2018 by STULZ Air Technology Systems, Inc. Printed in the United States of America.
All rights reserved.
iii
CeilAiR ENGINEERING MANUAL
Table Of Contents
DX Dual Compressor with Free Cooling - Self-Contained
DX Dual Compressor- Split Air Cooled Remote w/
Glycol Cooling Capacities, 14−35 kW ............................. 27
Condenser Technical Data, 14–35 kW .............................. 7
DX with Alternate Water Source Cooling Capacities,
DX Dual Compressor- Split Air Cooled Remote w/
3.5−17.5 kW............................................................................ 28
Condenser Technical Data, 14−35 kW (Cont) ................. 8
DX with Alternate Water Source Cooling Capacities,
DX - Split Air Cooled w/Condensing Unit Technical
14−35 kW................................................................................. 29
Data, 3.5−17.5 kW .................................................................. 9
Alternate Water Source 42 °F EWT Cooling
DX Dual Compressor - Split Air Cooled w/Condensing
Capacities ................................................................................... 30
Unit Technical Data, 14−35 kW .........................................10
Alternate Water Source 42 °F EWT Cooling
DX- Self-Contained Water Cooled Technical Data,
Capacities ................................................................................... 31
3.5−17.5 kW ............................................................................11
Alternate Water Source 50 °F EWT Cooling
DX Dual Compressor - Self-Contained Water Cooled
Capacities ................................................................................... 32
Technical Data, 14−35 kW ..................................................12
Alternate Water Source 50 °F EWT Cooling
DX - Self-Contained Glycol Cooled Technical Data,
Capacities ................................................................................... 33
3.5−17.5 kW ............................................................................13
Chilled Water Models ............................................................... 34
DX Dual Compressor - Self-Contained Glycol Cooled
Technical Data, 14−35 kW ..................................................14 Chilled Water Air Handler Technical Data,
3.5−10.5 kW............................................................................ 34
DX - Self-Contained Air Cooled (AS) 3.5 - 10.5 kW /
Split Air Cooled Cooling Capacities, 3.5–17.5 kW ......15 Chilled Water Air Handler Technical Data,
14−35 kW................................................................................. 35
DX Dual Compressor- Split Air Cooled Remote w/
Condenser Cooling Capacities, 14−35 kW ...................15 Chilled Water Air Handler Cooling Capacities,
3.5−12 kW................................................................................ 36
DX - Split Air Cooled w/Condensing Unit Cooling
Capacities, 3.5−17.5 kW .....................................................16 Chilled Water Air Handler Cooling Capacities,
3.5−12 kW (Con’t) .................................................................. 37
DX Dual Compressor - Split Air Cooled w/Condensing
Unit Cooling Capacities, 14−35 kW .................................16 Chilled Water Air Handler Cooling Capacities,
14−35 kW................................................................................. 38
DX- Self-Contained Water Cooled Cooling Capacities,
3.5−17.5 kW ............................................................................17 Chilled Water Air Handler Cooling Capacities,
14−35 kW (Con’t) ................................................................... 39
DX Dual Compressor - Self-Contained Water Cooled
Cooling Capacities, 14−35 kW ..........................................17 Chilled Water 42 °F EWT Cooling Capacities ................. 40
Chilled Water 42 °F EWT Cooling Capacities ................. 41
iii
CeilAiR ENGINEERING MANUAL
Chilled Water 50 °F EWT Cooling Capacities ................. 42 With Condensate Pump (OHS-048 −
Chilled Water 50 °F EWT Cooling Capacities ................. 43 OHS-120 C) .............................................................................. 55
Without Condensate Pump (OHS-048 −
Electrical Data (FLA / MCA / MFS) ........................ 43 OHS-120 C) .............................................................................. 55
DX Air, Water, and Glycol Cooled ............................................. 45
Dimensional Data and Installation Drawings ........ 57
With Condensate Pump (OHS-012 −
OHS-060 AS)............................................................................ 45 Physical Data and Connection Sizes ...................................... 58
Without Condensate Pump (OHS-012 − Air Cooled Systems ...................................................................... 60
OHS-060 AS)............................................................................ 45 DX Air Handling Units .................................................................. 64
With Condensate Pump (OHS-012 − Water/Glycol Systems ................................................................ 66
OHS-024 / AR, W, G) ............................................................. 45 Chilled Water Systems ................................................................ 70
Without Condensate Pump (OHS-012 − OHS-024 /
AR, W, G) ..................................................................................... 46 CeilAiR Product Guide Specifications ................... 72
With Condensate Pump (OHS-032 − OHS-060 / AR, SUMMARY .......................................................................................... 72
W, G) ............................................................................................. 46 Design Requirements ...................................................................... 72
Without Condensate Pump (OHS-032 − OHS-060 / Quality Assurance ............................................................................. 72
AR, W, G) ..................................................................................... 47
Cabinet ................................................................................................. 72
With Condensate Pump (OHS-048 − OHS-120 DAR,
Air Flow Patterns ............................................................................... 72
DW, DG) ....................................................................................... 48
“Ductless” Spot Cooler (Models OHS-012
Without Condensate Pump (OHS-048 − OHS-120
thru 040-( ) only) ........................................................................... 72
DAR, DW, DG)............................................................................ 47
Ducted Evaporator (Available on all model sizes) ............... 72
With Condensate Pump (OHS-012 − OHS-032
AHU) ............................................................................................. 49 Air Filtration ......................................................................................... 72
Without Condensate Pump (OHS-012 − OHS-032 Mechanical Components................................................................ 72
AHU) ............................................................................................. 49 Blowers/Motors ................................................................................ 72
With Condensate Pump (OHS-040 − Direct Drive Systems ................................................................... 72
OHS-060 AHU) ........................................................................ 50 Belt Driven Systems .................................................................... 72
Without Condensate Pump (OHS-040 − OHS-060 Refrigeration System ....................................................................... 72
AHU) ............................................................................................. 49
Scroll Compressor........................................................................ 72
With Condensate Pump (OHS-048 − OHS-120
Evaporator Coil. ............................................................................. 73
DAHU) ......................................................................................... 51
Air Cooled Heat Rejection ......................................................... 73
Without Condensate Pump (OHS-048 − OHS-120
DAHU) ......................................................................................... 51 Water Cooled Heat Rejection ....................................................... 73
DX Free Cooling and Alternate Water Source .................... 51 Chilled Water System .................................................................. 73
With Condensate Pump (OHS-012 − OHS-024 HAR, Chilled Water Control Valve ......................................................... 73
HW, HG) ...................................................................................... 51 Overflow Safety Float Switch ........................................................ 73
Without Condensate Pump (OHS-012 − OHS-024 Remote Start/Stop .......................................................................... 73
HAR, HW, HG) ........................................................................... 51 Electrical System .............................................................................. 73
With Condensate Pump (OHS-032 − OHS-060 HAR, A-Tech-1.1 Controller...................................................................... 74
HW, HG) ...................................................................................... 52
E2 Series Controller .............................................................................. 74
Without Condensate Pump (OHS-032 − OHS-060
Field Configurable ........................................................................ 74
HAR, HW, HG) ........................................................................... 52
Password Protection ....................................................................... 74
With Condensate Pump (OHS-048 − OHS-120 DAR,
DW, DG) ....................................................................................... 53 Restorable Parameters/Factory Defaults ........................... 74
Without Condensate Pump (OHS-048 − OHS-120 Timer Feature ................................................................................ 74
DAR, DW, DG)............................................................................ 53 A/C Grouping pLAN Operation ............................................... 74
Chilled Water ................................................................................. 54 Remote BMS ...................................................................................... 75
With Condensate Pump (OHS-012 − OHS-040 C) ... 54 Alarms .............................................................................................. 75
Without Condensate Pump (OHS-012 − E2 Constant Contact .................................................................... 75
OHS-040 C) .............................................................................. 54
iv
CeilAiR ENGINEERING MANUAL
v
CeilAiR ENGINEERING MANUAL
Nomenclature
OHS-XXX-XX-XX
Nominal
System Capacity in Configuration Options
1,000’s of
BTU/Hr
AWS = Alternate Water
AHU = Air Handling Unit
Source FC = Free
AR = Air-Cooled Remote
OHS = 012, 018, 024, D( ) = Dual Circuit Cooling
032, (Split) AS = Air-Cooled
CeilAiR H( ) = Horizontal LP = Low Profile
040, 048, 060, Self-Contained C =
Overhead 072, Discharge (“H- Configuration SF =
System 084, 120 Series”) Chilled Water System
Same-Face Air Pattern
G = Glycol-Cooled SP = Special
W = Water Cooled
Configuration *
OHS 040 H G FC
STULZ Condensers and Condensing Units are documented in our Heat Rejection Engineering Manual.
STULZ Pump Packages and Drycoolers are documented in our Glycol Systems Engineering Manual.
vi
CeilAiR ENGINEERING MANUAL
1
CeilAiR ENGINEERING MANUAL
2
CeilAiR ENGINEERING MANUAL
3
CeilAiR ENGINEERING MANUAL
4
CeilAiR ENGINEERING MANUAL
This section contains technical specifications and performance/capacity data tables for the different CeilAiR cooling systems
available from STULZ:
• DX - Air Cooled/Water Cooled/Glycol Cooled Models
• DX with Free Cooling and DX with Alternate Water Source Models
• Chilled Water Models
5
CeilAiR ENGINEERING MANUAL
DX - Self-Contained Air Cooled (AS) 3.5 – 10.5 kW / Split Air Cooled (AR) Technical Data, 3.5–17.5 kW
Model OHS- 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-AR
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 5 5 5 5 5 10 10
Optional Heater, kW N/A N/A N/A N/A N/A N/A N/A
Hot Gas Reheat
Total Capacity, kW (MBH) 3.3 (11.4) 5 (17) 6.2 (21.2) 7.5 (25.7) 9.1 (30.9) 14.5 (49.3) 15.9 (54.2)
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 6.1 (20.7) 9.5 (32.4) 10.2 (34.9) 14.8 (50.4) 16.2 (55.3) 28.5 (97.1) 32.6 (111.2)
Flow rate, GPM 1 2 2 3 3 4 5
Pressure Drop, ftH2O-Coil 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 3.5 (12) 5.3 (18) 7 (24) 9.4 (32) 11.7 (40) 14.1 (48) 17.6 (60)
Condensate, lb/hr 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 2–5 2-5 2-5 2-5 2-5 4-10 4-10
Power Input, kW 1.7 1.7 1.7 1.7 1.7 3.4 3.4
Standard Control Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Nominal Horsepower, hp 1/4 1/4 1/4 1/3 1/2 1 1 1/2
Rated Airflow ft /min @ inH2O ESP
3
500 @ 0.3 750 @ 0.3 900 @ 0.3 1000 @ 0.3 1415 @ 0.3 2200 @ 0.5 2500 @ 0.5
Standard Drive Method Direct Direct Direct Direct Direct Belt Belt
Optional Drive Method Belt Belt Belt Belt Belt N/A N/A
-
6
CeilAiR ENGINEERING MANUAL
NOTES:
Compressor is integral to the OHS-( )-AS Self-Contained Unit.
Refer to the STULZ Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and
Indoor Air Cooled Condensers used with OHS-( )-()AR Split Systems.
-
DX Dual Compressor- Split Air Cooled Remote w/ Condenser Technical Data, 14–35 kW
Model OHS- 048-DAR 072-DAR 084-DAR 120-DAR
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Hot Gas Reheat
Total Capacity, kW (MBH) 6.2 (21.2) 9.5 (32.3) 10.9 (37.2) 14.8 (50.5)
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.8 (50.4) 28.7 (97.9) 29.3 (99.8) 38.2 (130.5)
Flow rate, GPM 3 3 3 10
Pressure Drop, ftH2O-Coil 0.3 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.1 (48) 21.1 (72) 26.4 (90) 35.2 (120)
Condensate, lb/hr 50 75 94 125
Control Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 3/4 1 1/2 2 3
Rated Airflow, ft /min @ inH2O ESP
3
1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 4 4 4
7
CeilAiR ENGINEERING MANUAL
DX Dual Compressor- Split Air Cooled Remote w/ Condenser Technical Data, 14−35 kW (Cont)
Model OHS- 048-DAR 072-DAR 084-DAR 120-DAR
Face Area, ft 2
4.1 6.7 6.7 10
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
Input per Compressor, kW 2.1 2.8 3.8 5.0
Total Heat of Rejection, kW (MBH) 18.5 (63.3) 25.4 (86.6) 32.3 (110.2) 45 (153.4)
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant
Liquid Line OD, in. 3/8 1/2 1/2 1/2
Quantity 2 2 2 2
Hot Gas Line OD, in. 5/8 5/8 7/8, 7/8
Quantity 2 2 2 2
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 420 450 510 580
8
CeilAiR ENGINEERING MANUAL
Refer to the STULZ Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensers
9
CeilAiR ENGINEERING MANUAL
DX Dual Compressor - Split Air Cooled w/Condensing Unit Technical Data, 14−35 kW
Model OHS- 048-DAHU 072-DAHU 084-DAHU 120-DAHU
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Hot Water Reheat / Heat - Reheat rated @ 180 °F Entering Water Temperature, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.8 (50.4) 28.7 (97.9) 29.3 (99.8) 38.2 (130.5)
Flow rate, GPM 3 3 3 10
Pressure Drop, ftH2O-Coil 0.3 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized
Steam Reheat / Heat - nominally Reheat rated @ 5 psi Steam, EAT = 72 °F DB
Total Capacity, kW (MBH) 14.1 (48) 21.1 (72) 26.4 (90) 35.2 (120)
Condensate, lb/hr 50 75 94 125
Control Motorized Motorized Motorized Motorized
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 3/4 1 1/2 2 3
Rated Airflow, ft /min @ inH2O ESP
3
1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant
Suction Line OD, in. 3/4 7/8 7/8 7/8
Quantity 2 2 2 2
Liquid Line OD, in. 3/8 1/2 1/2 1/2
Quantity 2 2 2 2
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4
Physical Size (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 320 350 410 480
10
CeilAiR ENGINEERING MANUAL
11
CeilAiR ENGINEERING MANUAL
12
CeilAiR ENGINEERING MANUAL
13
CeilAiR ENGINEERING MANUAL
14
CeilAiR ENGINEERING MANUAL
DX - Self-Contained Air Cooled (AS) 3.5 - 10.5 kW / Split Air Cooled Cooling Capacities, 3.5–17.5 kW
Model OHS- 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-AR
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft /min and ESP ratings)
3
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 4.1 (14) 5.7 (19.5) 7.5 (25.7) 9.6 (32.8) 10.5 (35.8) 17.6 (60) 19.3 (66)
Sensible, kW (MBH) 3.1 (10.6) 4.5 (15.2) 5.7 (19.5) 6.9 (23.4) 8.2 (28) 14 (47.7) 15.4 (52.4)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 3.7 (12.7) 5.3 (18) 6.9 (23.6) 8.8 (30) 9.6 (32.7) 16.1 (55) 17.7 (60.5)
Sensible, kW (MBH) 3.1 (10.6) 4.5 (15.4) 5.6 (19) 6.7 (22.9) 8 (27.4) 13.8 (47) 15.1 (51.6)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 3.5 (12) 5 (17.2) 6.6 (22.5) 8.4 (28.5) 9.1 (31.1) 15.4 (52.4) 16.9 (57.6)
Sensible, kW (MBH) 3 (10.4) 4.4 (15.1) 5.4 (18.6) 6.6 (22.4) 7.8 (26.7) 13.5 (46) 14.8 (50.6)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 3.9 (13.4) 5.5 (18.9) 7.2 (24.6) 9.2 (31.3) 10.2 (34.7) 16.9 (57.7) 18.6 (63.4)
Sensible, kW (MBH) 3.5 (11.8) 5 (17) 6.1 (20.9) 7.3 (24.9) 9.1 (30.9) 15.3 (52.1) 16.8 (57.3)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6.7 (23) 8.5 (28.9) 9.4 (32.1) 15.7 (53.4) 17.2 (58.6)
Sensible, kW (MBH) 3.3 (11.4) 4.8 (16.4) 6 (20.5) 7 (23.9) 8.7 (29.7) 14.7 (50.3) 16.2 (55.3)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.4 (11.6) 4.9 (16.7) 6.4 (22) 8 (27.4) 8.9 (30.5) 14.9 (50.9) 16.4 (55.8)
Sensible, kW (MBH) 3.3 (11.1) 4.7 (16.1) 5.9 (20.1) 6.9 (23.6) 8.5 (29) 14.4 (49.2) 15.8 (54.1)
DX Dual Compressor- Split Air Cooled Remote w/ Condenser Cooling Capacities, 14−35 kW
Model OHS- 048-DAR 072-DAR 084-DAR 120-DAR
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 15.8 (53.7) 21.7 (73.9) 27 (92.1) 38.2 (130.4)
Sensible, kW (MBH), kW (MBH) 12 (40.9) 18.2 (62.1) 20.8 (71.1) 28.7 (98)
75 ° F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 14.4 (49.3) 19.8 (67.6) 24.6 (84) 35 (119.6)
Sensible, kW (MBH), kW (MBH) 11.8 (40.3) 18 (61.5) 20.8 (70.8) 28.2 (96.2)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 13.8 (47) 18.8 (64.3) 23.4 (79.8) 33.2 (113.4)
Sensible, kW (MBH) 11.6 (39.5) 17.6 (60.2) 20.4 (69.6) 27.7 (94.6)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 15.1 (51.6) 20.7 (70.7) 25.7 (87.7) 36.6 (124.9)
Sensible, kW (MBH) 13 (44.3) 20 (68.1) 23.2 (79.1) 31.2 (106.5)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 14 (47.9) 19.2 (65.6) 23.7 (80.8) 33.9 (115.5)
Sensible, kW (MBH) 12.6 (42.8) 18.8 (64.1) 22.3 (76.2) 30.1 (102.9)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 13.4 (45.6) 18.4 (62.8) 22.5 (76.7) 32.2 (110)
Sensible, kW (MBH) 12.3 (42) 18.1 (61.9) 21.6 (73.7) 29.6 (100.9)
15
CeilAiR ENGINEERING MANUAL
Total, kW (MBH) 3.7 (12.7) 5.3 (18) 6.9 (23.6) 8.9 (30.4) 9.9 (33.8) 16.1 (55) 17.7 (60.5)
Sensible, kW (MBH) 3.1 (10.6) 4.5 (15.4) 5.6 (19) 7.1 (24.2) 8.6 (29.3) 13.8 (47) 15.1 (51.6)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 3.5 (12) 5 (17.2) 6.6 (22.5) 8.5 (29) 9.5 (32.3) 15.4 (52.4) 16.9 (57.6)
Sensible, kW (MBH) 3 (10.4) 4.4 (15.1) 5.4 (18.6) 6.9 (23.7) 8.4 (28.5) 13.5 (46) 14.8 (50.6)
80 °F DB / 65°F WB, 45% RH
Total, kW (MBH) 3.9 (13.4) 5.5 (18.9) 7.2 (24.6) 9.3 (31.7) 10.3 (35.1) 16.9 (57.7) 18.6 (63.4)
Sensible, kW (MBH) 3.5 (11.8) 5 (17) 6.1 (20.9) 8.1 (27.6) 9.8 (33.4) 15.3 (52.1) 16.8 (57.3)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6.7 (23) 8.6 (29.5) 9.6 (32.8) 15.7 (53.4) 17.2 (58.6)
Sensible, kW (MBH) 3.3 (11.4) 4.8 (16.4) 6 (20.5) 7.7 (26.3) 9.2 (31.5) 14.7 (50.3) 16.2 (55.3)
72°F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 3.4 (11.6) 4.9 (16.7) 6.4 (22) 8.3 (28.2) 9.2 (31.4) 14.9 (50.9) 16.4 (55.8)
Sensible, kW (MBH) 3.3 (11.1) 4.7 (16.1) 5.9 (20.1) 7.5 (25.6) 8.9 (30.5) 14.4 (49.2) 15.8 (54.1)
DX Dual Compressor - Split Air Cooled w/Condensing Unit Cooling Capacities, 14−35 kW
Model OHS- 048-DAHU 072-DAHU 084-DAHU 120-DAHU
Net DX Cooling Capacity - kW (MBH), (includes standard DX evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °FWB, 50% RH
Total, kW (MBH) 15.8 (53.7) 21.7 (73.9) 27 (92.1) 38.2 (130.4)
Sensible, kW (MBH) 12 (40.9) 18.2 (62.1) 20.8 (71.1) 28.7 (98)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 14.4 (49.3) 19.8 (67.6) 24.6 (84) 35 (119.6)
Sensible, kW (MBH) 11.8 (40.3) 18 (61.5) 20.8 (70.8) 28.2 (96.2)
72 °F DB/ 60 °F WB, 50% RH
Total, kW (MBH) 13.8 (47) 18.8 (64.3) 23.4 (79.8) 33.2 (113.4)
Sensible, kW (MBH) 11.6 (39.5) 17.6 (60.2) 20.4 (69.6) 27.7 (94.6)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 15.1 (51.6) 20.7 (70.7) 25.7 (87.7) 36.6 (124.9)
Sensible, kW (MBH) 13 (44.3) 20 (68.1) 23.2 (79.1) 31.2 (106.5)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 14 (47.9) 19.2 (65.6) 23.7 (80.8) 33.9 (115.5)
Sensible, kW (MBH) 12.6 (42.8) 18.8 (64.1) 22.3 (76.2) 30.1 (102.9)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 13.4 (45.6) 18.4 (62.8) 22.5 (76.7) 32.2 (110)
Sensible, kW (MBH) 12.3 (42) 18.1 (61.9) 21.6 (73.7) 29.6 (100.9)
16
CeilAiR ENGINEERING MANUAL
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 4.8 (16.4) 6.2 (21.1) 8.2 (28) 10.4 (35.6) 11.5 (39.1) 18.8 (64.3) 20.7 (70.7)
Sensible, kW (MBH) 3.4 (11.7) 4.7 (16) 6 (20.5) 7.2 (24.6) 8.6 (29.5) 14.4 (49.2) 15.9 (54.1)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 4.4 (14.9) 5.7 (19.3) 7.5 (25.8) 9.6 (32.7) 10.5 (35.8) 17.2 (58.8) 19 (64.7)
Sensible, kW (MBH) 3.3 (11.3) 4.6 (15.6) 5.9 (20.1) 7.1 (24.3) 8.4 (28.8) 14.2 (48.6) 15.7 (53.4)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 4.1 (14) 5.4 (18.4) 7.2 (24.6) 9.1 (31.2) 10 (34.1) 16.4 (56.1) 18.1 (61.7)
Sensible, kW (MBH) 3.2 (11.1) 4.8 (16.4) 5.8 (19.7) 7 (23.8) 8.2 (28.1) 14 (47.6) 15.3 (52.3)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 4.6 (15.6) 6 (20.4) 7.9 (26.8) 10 (34.2) 10.9 (37.4) 18.1 (61.6) 19.9 (67.7)
Sensible, kW (MBH) 3.6 (12.4) 5.2 (17.6) 6.4 (21.8) 7.7 (26.3) 9.3 (31.6) 15.7 (53.6) 17.3 (59)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 4.2 (14.4) 5.6 (19) 7.3 (24.9) 9.3 (31.6) 10.3 (35.1) 16.7 (57.1) 18.4 (62.8)
Sensible, kW (MBH) 3.6 (12.3) 5 (17) 6.2 (21.1) 7.4 (25.4) 9 (30.6) 15.2 (51.8) 16.7 (57)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 4 (13.6) 5.3 (18.1) 6.9 (23.7) 8.8 (30.1) 9.8 (33.5) 16 (54.5) 17.5 (59.8)
Sensible, kW (MBH) 3.5 (12) 4.9 (16.7) 6.1 (20.7) 7.3 (24.8) 8.9 (30.5) 14.9 (50.8) 16.4 (55.9)
17
CeilAiR ENGINEERING MANUAL
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 15 (51.3) 20.6 (70.2) 25.6 (87.4) 36.3 (124)
Sensible, kW (MBH) 11.6 (39.7) 17.9 (61) 20.4 (69.5) 27.9 (95.3)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 13.7 (46.8) 18.8 (64.1) 23.3 (79.6) 33.1 (113)
Sensible, kW (MBH) 11.5 (39.2) 17.6 (60.2) 20.3 (69.4) 27.5 (93.9)
72 °F DB/ 60 °F WB, 50% RH
Total, kW (MBH) 13.1 (44.6) 17.9 (61) 22.2 (75.6) 31.5 (107.5)
Sensible, kW (MBH) 11.3 (38.4) 17.2 (58.5) 20 (68.1) 26.9 (91.9)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 14.4 (49.2) 19.7 (67.3) 24.3 (83.1) 34.8 (118.7)
Sensible, kW (MBH) 12.7 (43.3) 19.2 (65.4) 22.7 (77.4) 30.5 (104.1)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 13.3 (45.5) 18.4 (62.6) 22.5 (76.6) 32.1 (109.6)
Sensible, kW (MBH) 12.3 (41.8) 18.1 (61.8) 21.5 (73.4) 29.4 (100.4)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 12.7 (43.3) 17.5 (59.9) 21.4 (73.2) 30.5 (104.2)
Sensible, kW (MBH) 12 (41) 17.5 (59.6) 20.8 (71.1) 28.8 (98.4)
18
CeilAiR ENGINEERING MANUAL
19
CeilAiR ENGINEERING MANUAL
DX Dual Compressor with Free Cooling - Self-Contained Water Cooled Technical Data, 14−35 kW
Model OHS- 048-DW-FC 072-DW-FC 084-DW-FC 120-DW-FC
Flow Rates, Free Cooling Coil
Flow rate, GPM 12.7 17.5 22.2 30.8
Evaporator Blower / Motor, DX w/ Free Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1 1 1/2 2 3
Rated Airflow, ft3/min @ inH2O ESP 1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coils, (Both DX and Free Cooling Respectively) - Aluminum Fin, Copper Tube
DX Coil:
Rows 4 4 4 4
Face Area, ft 2
4.1 6.7 6.7 10.0
FC Coil:
Rows 4 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
Input per Compressor, kW 2.2 3 4.1 6
DX Water Cooled Condenser Data - Based on 0% glycol solution
Total Heat of Rejection, kW (MBH) 18.6 (63.5) 25.6 (87.4) 32.5 (110.8) 45.2 (154.1)
GPM @ 85 °F EWT 12.7 17.5 22.2 30.8
Pressure Drop, ftH2O-Total Unit 26.8 25.2 28.3 25.7
Type Coaxial Coaxial Coaxial Coaxial
DX-Head Pressure and Free Cooling Coil Control Valve Combinations
DX Head Pressure Valve Type - - - - - - -3-way, 150 psi DX Condenser Source Regulating Valve - field installed - - - - - - -
Free Cooling Valve - 3-way, Spring Actuated (Open/Close):
FC Valve Size, in. 1 1 1 1
Cv 7.0 14.0 14.0 14.0
Valve Pressure Rating, psi 300 400 400 400
Optional Valve Combos - Please refer to “Free Cooling System Valves” on page 74 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve
Combination Options.
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4 1/4
Source Water In/Out OD, in. 1 1/8 1 1/8 1 3/8 1 3/8
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Physical Size - (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 550 570 660 745
20
CeilAiR ENGINEERING MANUAL
21
CeilAiR ENGINEERING MANUAL
DX Dual Compressor with Free Cooling - Self-Contained Glycol Cooled Technical Data, 14−35 kW
Model OHS- 048-DG-FC 072-DG-FC 084-DG-FC 120-DG-FC
Flow Rates, Free Cooling Coil
Flow Rate, GPM 13.7 18.7 23.8 33.0
Evaporator Blower / Motor, DX w/ Free Cooling - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Nominal Horsepower, hp 1 1 1/2 2 3
Rated Airflow, ft3/min @ inH2O ESP 1800 @ 0.5 3000 @ 0.5 3350 @ 0.5 4400 @ 0.5
Drive Method Belt Belt Belt Belt
Evaporator Coils, (Both DX and Free Cooling Respectively) - Aluminum Fin, Copper Tube
DX Coil:
Rows 4 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
FC Coil:
Rows 4 4 4 4
Face Area, ft2 4.1 6.7 6.7 10.0
Reheat/Heat (Optional) - Performance Capacities Include Motor Heat
Electric Reheat / Heat - kW values are nominal
Standard Heater, kW 10 10 10 10
Optional Heater, kW N/A 15 15 15
Humidification (Optional) - Electrode Steam Canister Humidifier with Adjustable Output
Steam Output, lb/hr 4-10 4-15 4-15 4-15
Power Input, kW 3.4 5.1 5.1 5.1
Standard Control Cycling Cycling Cycling Cycling
Compressor - Heat pump duty rated, HCFC Ozone Safe R-407C
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
Input per Compressor, kW 2.2 3 4.1 5.3
DX Glycol Condenser Data - Based on 40% ethylene glycol solution
Total Heat of Rejection, kW (MBH) 18.1 (61.8) 24.7 (84.4) 31.5 (107.6) 43.7 (149.2)
GPM @ 110 °F EGT 13.7 18.7 23.8 33.0
Pressure Drop, ftH2O-Total Unit 37.8 34.8 41.0 29.5
Type Coaxial Coaxial Coaxial Coaxial
DX-Head Pressure and Free Cooling Coil Control Valve Combinations
DX Head Pressure Regulating Valves:
DX Head Pressure Type - - - - - - - - - - -3-way, 150 psi DX Condenser Source Regulating Valve - field installed - - - - - - - - - - -
Free Cooling Valve - 3-way, Spring Actuated (Open/Close):
FC Valve Size, in. 1 1 1 1
Cv 7.0 14.0 14.0 14.0
Valve Pressure Rating, psi 300 400 400 400
Optional Valve Combos - Please refer to “Free Cooling System Valves” on page 74 for Higher Pressure Rated and Modulating (0-10 Vdc) Valve Combi-
nation Options
Connection Sizes - Copper
Humidifier Inlet OD, in. 1/4 1/4 1/4
Source Glycol In/Out OD, in. 1 1/8 1 1/8 1 3/8 1 3/8
Filters - 1 in. deep throwaway
Nominal Size, in. 16×20 20×20 20×20 24×24
Quantity 2 2 2 2
Physical Size - (Please refer to “Dimensional Data and Installation Drawings” on page 57 for detailed dimensional data.)
Approximate Weight, lb 550 570 660 745
See the Glycol Pump/Drycooler Engineering Manual for drycooler data, optional 105 °F amb. selections, and optional glycol pump packages.
22
CeilAiR ENGINEERING MANUAL
23
CeilAiR ENGINEERING MANUAL
24
CeilAiR ENGINEERING MANUAL
DX Dual Compressor with Free Cooling - Self-Contained Water Cooled Cooling Capacities, 14−35 kW
Model OHS- 048-DW-FC 072-DW-FC 084-DW-FC 120-DW-FC
Net DX Cooling Capacity - kW (MBH), (includes standard DX w/ FC evaporator motor heat @ std ft3/min and ESP ratings)
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 16.8 (57.2) 23.2 (79.2) 28.9 (98.8) 40.8 (139.2)
Sensible, kW (MBH) 12.4 (42.3) 18.7 (63.8) 21.6 (73.7) 29.8 (101.7)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 15.4 (52.6) 21.3 (72.5) 26.5 (90.5) 37.4 (127.7)
Sensible, kW (MBH) 12.2 (41.6) 18.5 (63.2) 21.3 (72.8) 29.3 (100)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 14.7 (50.1) 20.2 (69) 25.2 (86.1) 35.6 (121.6)
Sensible, kW (MBH) 12 (40.8) 18.2 (62) 20.9 (71.4) 28.7 (98)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 16.1 (54.9) 22.2 (75.8) 27.6 (94.3) 39.1 (133.3)
Sensible, kW (MBH) 13.4 (45.7) 20.6 (70.4) 23.8 (81.2) 32.3 (110.1)
75 °F DB / 61 °F WB, 45% RH
Total, kW (MBH) 14.9 (51) 20.6 (70.2) 25.5 (87.1) 36.2 (123.5)
Sensible, kW (MBH) 12.9 (44.2) 19.8 (67.7) 23.1 (78.7) 31.2 (106.3)
72 °F DB / 58.5 °F WB, 45% RH
Total, kW (MBH) 14.2 (48.6) 19.6 (66.8) 24.3 (82.8) 34.5 (117.6)
Sensible, kW (MBH) 12.7 (43.4) 19.1 (65.2) 22.7 (77.3) 30.6 (104.3)
FREE-COOLING CAPACITY - kW (MBH) @ 45°F Entering Water Temperature, 0% Glycol Solution
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 19.1 (65) 33.6 (114.5) 37.9 (129.5) 45.7 (155.8)
Sensible, kW (MBH) 13.8 (47.2) 24.2 (82.7) 27.2 (92.9) 33.4 (114)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 15.2 (51.7) 27.2 (92.8) 30.4 (103.8) 36.4 (124)
Sensible, kW (MBH) 12.6 (42.9) 22.3 (75.9) 24.8 (84.7) 30.4 (103.8)
72 °F D B / 60 °F WB, 50% RH
Total, kW (MBH) 13.1 (44.7) 23.8 (81.3) 26.6 (90.6) 31.4 (107.3)
Sensible, kW (MBH) 11.7 (39.9) 20.8 (71) 23.2 (79.2) 28.3 (96.5)
80 °F DB /65 °F WB, 45% RH
Total, kW (MBH) 17.7 (60.5) 31.8 (108.7) 35.7 (121.7) 42.6 (145.4)
Sensible, kW (MBH) 14.7 (50) 26 (88.5) 29 (98.9) 35.5 (121.2)
75°FDB/61°FWB, 45% RH
Total, kW (MBH) 14.4 (49) 26.3 (89.8) 29.2 (99.7) 34.5 (117.9)
Sensible, kW (MBH) 13.2 (44.9) 23.6 (80.4) 26.2 (89.4) 31.9 (108.8)
72°FDB/58.5°FWB, 45% RH
Total, kW (MBH) 12.3 (42) 23.1 (78.9) 25.5 (87.2) 29.6 (100.9)
Sensible, kW (MBH) 12.1 (41.4) 22 (75.1) 24.4 (83.4) 29.4 (100.3)
25
CeilAiR ENGINEERING MANUAL
26
CeilAiR ENGINEERING MANUAL
DX Dual Compressor with Free Cooling - Self-Contained Glycol Cooling Capacities, 14−35 kW
Model OHS- 048-DG-FC 072-DG-FC 084-DG-FC 120-DG-FC
Net DX Cooling Capacity - kW (MBH), (includes standard DX w/ FC evaporator motor heat @ std ft /min and ESP ratings)
3
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 15 (51.3) 20.6 (70.2) 25.6 (87.4) 36.3 (124)
Sensible, kW (MBH) 11.6 (39.7) 17.9 (61) 20.4 (69.5) 27.9 (95.3)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 13.7 (46.8) 18.8 (64.1) 23.3 (79.6) 33.1 (113)
Sensible, kW (MBH) 11.5 (39.2) 17.6 (60.2) 20.3 (69.4) 27.5 (93.9)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 13.1 (44.6) 17.9 (61) 22.2 (75.6) 31.5 (107.5)
Sensible, kW (MBH) 11.3 (38.4) 17.2 (58.5) 20 (68.1) 26.9 (91.9)
80 °F DB / 65 °F WB, 45% RH
Total, kW (MBH) 14.4 (49.2) 19.7 (67.3) 24.3 (83.1) 34.8 (118.7)
Sensible, kW (MBH) 12.7 (43.3) 19.2 (65.4) 22.7 (77.4) 30.5 (104.1)
75 °F DB / 61°F WB, 45% RH
Total, kW (MBH) 13.3 (45.5) 18.4 (62.6) 22.5 (76.6) 32.1 (109.6)
Sensible, kW (MBH) 12.3 (41.8) 18.1 (61.8) 21.5 (73.4) 29.4 (100.4)
72 °F DB / 58.5°F WB, 45% RH
Total, kW (MBH) 12.7 (43.3) 17.5 (59.9) 21.4 (73.2) 30.5 (104.2)
Sensible, kW (MBH) 12 (41) 17.5 (59.6) 20.8 (71.1) 28.8 (98.4)
FREE-COOLING CAPACITY - kW (MBH) @ 45°F Entering Glycol Temperature, 40% Ethylene Glycol Solution
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 15.9 (54.1) 26.1 (89) 31.1 (106) 35.1 (119.7)
Sensible, kW (MBH) 12.5 (42.7) 21.2 (72.4) 24.4 (83.3) 29.1 (99.4)
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 12.7 (43.3) 21.2 (72.3) 25.2 (85.8) 28.1 (95.7)
Sensible, kW (MBH) 11.4 (39.1) 19.5 (66.7) 22.5 (76.7) 26.6 (90.9)
72 °F DB / 60°F WB, 50% RH
Total, kW (MBH) 10.9 (37.3) 18.3 (62.4) 21.9 (74.6) 24.1 (82.1)
Sensible, kW (MBH) 10.6 (36.2) 18.1 (61.8) 20.9 (71.4) 24.1 (82.1)
80 °F DB / 65°F WB, 45% RH
Total, kW (MBH) 14.9 (50.8) 24.9 (85) 29.5 (100.8) 32.9 (112.3)
Sensible, kW (MBH) 13.4 (45.7) 22.9 (78.1) 26.3 (89.7) 31.2 (106.3)
75 °F DB / 61°F WB, 45% RH
Total, kW (MBH) 11.7 (39.9) 20 (68.4) 23.9 (81.7) 27.1 (92.4)
Sensible, kW (MBH) 11.7 (39.9) 20 (68.4) 23.9 (81.7) 27.1 (92.4)
72 °F DB / 58.5°F WB, 45% RH
Total, kW (MBH) 10.6 (36.3) 18 (61.3) 21 (71.5) 24.3 (82.8)
Sensible, kW (MBH) 10.6 (36.3) 18 (61.3) 21 (71.5) 24.3 (82.8)
27
CeilAiR ENGINEERING MANUAL
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.6) 5.7 (19.3) 6.5 (22.1) 8.6 (29.4) 13.4 (45.6) 14.8 (50.5)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.4 (7.5) 4.7 (13.6) 5.5 (17.8) 6.3 (9.5) 8.1 (15.4) 12.6 (7.4) 13.9 (8.8)
Total, kW (MBH) 3.6 (12.4) 5 (17.2) 5.8 (19.7) 6.7 (22.7) 8.6 (29.4) 12.6 (43) 13.8 (47.2)
Med Flow
Sensible, kW (MBH) 3.2 (11.1) 4.6 (15.7) 5.3 (18.2) 6.1 (20.9) 8.1 (27.6) 12.1 (41.3) 13.4 (45.7)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.5 (4.2) 3.5 (7.7) 4.0 (10.0) 4.6 (5.4) 6.0 (8.6) 8.7 (3.7) 9.6 (4.5)
Total, kW (MBH) 3.3 (11.1) 4.5 (15.3) 5.1 (17.5) 5.9 (20.1) 7.6 (25.8) 9.9 (33.8) 11 (37.6)
Low Flow
Sensible, kW (MBH) 3 (10.3) 4.2 (14.5) 4.9 (16.7) 5.6 (19.2) 7.4 (25.1) 9.9 (33.8) 11 (37.6)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.9 (2.2) 2.6 (4.5) 3.0 (5.7) 3.4 (3.1) 4.4 (4.9) 5.8 (1.6) 6.4 (2.1)
28
CeilAiR ENGINEERING MANUAL
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 20.7 (70.5) 39.3 (134.1) 42.3 (144.4) 48.9 (166.9)
High Flow
Sensible, kW (MBH) 14.4 (49.3) 26.6 (90.8) 28.9 (98.7) 34.5 (117.9)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 17.6 (43.1) 33.5 (46.3) 36.1 (53.2) 41.8 (18.6)
Total, kW (MBH) 19.3 (65.8) 36.8 (125.6) 39.6 (135.1) 45.1 (154)
Med Flow
Sensible, kW (MBH) 13.8 (47.2) 25.5 (87) 27.7 (94.6) 32.9 (112.2)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.2 (25.1) 25.2 (27.5) 27.1 (31.5) 31.0 (10.7)
Total, kW (MBH) 18 (61.5) 34.4 (117.4) 37.1 (126.6) 40.8 (139.3)
Low Flow
Sensible, kW (MBH) 13.2 (45.2) 24.4 (83.4) 26.6 (90.8) 30.9 (105.5)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 10.4 (15.8) 19.6 (17.4) 21.2 (20.1) 23.4 (6.4)
7 5°F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 15.2 (51.9) 29 (99.1) 31.3 (106.7) 35.7 (121.9)
High Flow
Sensible, kW (MBH) 12.5 (42.7) 23 (78.5) 25.1 (85.5) 29.8 (101.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.0 (24.6) 24.8 (26.9) 26.8 (30.8) 30.8 (10.6)
Total, kW (MBH) 14.2 (48.4) 27.3 (93.3) 29.5 (100.6) 32.1 (109.7)
Med Flow
Sensible, kW (MBH) 1.2 (4) 22.2 (75.7) 24.2 (82.4) 27.9 (95.3)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 9.8 (14.5) 18.8 (16.1) 20.3 (18.5) 22.2 (5.8)
Total, kW (MBH) 13.1 (44.6) 25.6 (87.3) 27.8 (94.8) 28.6 (97.6)
Low Flow
Sensible, kW (MBH) 11.3 (38.7) 21.3 (72.6) 23.3 (79.4) 25.8 (88.2)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 7.6 (8.9) 14.6 (10.2) 15.9 (11.9) 16.6 (3.4)
2 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 12.6 (43.2) 24.3 (83.1) 26.2 (89.6) 29.2 (99.5)
High Flow
Sensible, kW (MBH) 11.3 (38.7) 21 (71.6) 22.9 (78) 26.7 (91.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.0 (17.8) 20.9 (19.6) 22.5 (22.6) 25.2 (7.4)
Total, kW (MBH) 11.6 (39.5) 23 (78.6) 24.9 (84.9) 25.2 (86)
Med Flow
Sensible, kW (MBH) 10.7 (36.4) 20.2 (69.1) 22.1 (75.2) 24.2 (82.7)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.0 (10.0) 15.8 (11.9) 17.2 (13.7) 17.4 (3.7)
Total, kW (MBH) 10.3 (35) 21 (71.6) 22.8 (77.8) 19.8 (67.6)
Low Flow
Sensible, kW (MBH) 9.8 (33.4) 19 (64.9) 20.8 (70.8) 19.8 (67.6)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 6.0 (5.7) 12.0 (7.2) 13.1 (8.4) 11.6 (1.6)
29
CeilAiR ENGINEERING MANUAL
Med Flow Total, kW (MBH) 7.2 (24.6) 9.8 (33.5) 11.2 (38.2) 12.8 (43.7) 16.3 (55.8)
(10 °F Sensible, kW (MBH) 4.7 (16) 6.6 (22.5) 7.6 (26) 8.8 (30) 11.5 (39.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.9 (14.8) 6.7 (25.8) 7.6 (32.9) 8.7 (17.6) 11.1 (27.7)
Low Flow Total, kW (MBH) 6.6 (22.7) 9.1 (31.2) 10.5 (35.8) 11.8 (40.4) 15.3 (52.3)
(12 °F Sensible, kW (MBH) 4.4 (15.2) 6.3 (21.4) 7.3 (24.9) 8.3 (28.5) 11 (37.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.8 (9.1) 5.2 (16.1) 6.0 (20.8) 6.7 (10.9) 8.7 (17.6)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 5.7 (19.5) 7.8 (26.8) 9 (30.6) 10.3 (35.2) 13.2 (45.2)
High Flow
Sensible, kW (MBH) 4.2 (14.4) 6 (20.3) 6.9 (23.6) 8 (27.1) 10.5 (35.8)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.9 (14.5) 6.7 (25.9) 7.6 (33.2) 8.8 (17.9) 11.3 (28.4)
Med Flow Total, kW (MBH) 5.2 (17.9) 7.3 (24.8) 8.4 (28.6) 9.5 (32.5) 12.4 (42.3)
(10 °F Sensible, kW (MBH) 4 (13.6) 5.7 (19.4) 6.6 (22.5) 7.5 (25.7) 7.1 (24.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.6 (8.2) 5.0 (15.1) 5.7 (19.3) 6.5 (10.2) 8.5 (16.7)
Total, kW (MBH) 4.8 (16.4) 6.7 (22.9) 7.8 (26.7) 8.8 (29.9) 11.4 (39.1)
High Flow
Sensible, kW (MBH) 3.8 (12.9) 5.4 (18.4) 6.3 (21.4) 7.1 (24.4) 9.5 (32.5)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.8 (5.0) 3.8 (9.2) 4.4 (11.9) 5.0 (6.3) 6.5 (10.2)
72 °F DB / 60 °F WB
Total, kW (MBH) 4.7 (16.1) 6.6 (22.4) 7.5 (25.8) 8.7 (29.6) 11.2 (38.4)
High Flow
Sensible, kW (MBH) 3.8 (13) 5.4 (18.5) 6.3 (21.5) 7.2 (24.6) 9.6 (32.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.1 (10.4) 5.7 (19.0) 6.4 (24.0) 7.4 (13.0) 9.6 (21.0)
Med Flow Total, kW (MBH) 4.3 (14.8) 6.1 (20.7) 7 (23.9) 7.9 (27.1) 10.4 (35.4)
(10 °F Sensible, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6 (20.4) 6.8 (23.2) 9.1 (31)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.0 (5.9) 4.2 (10.8) 4.8 (14.0) 5.4 (7.4) 7.1 (12.1)
High Flow Total, kW (MBH) 4 (13.5) 5.6 (19) 6.4 (22) 7.3 (24.9) 9.5 (32.5)
(12 °F Sensible, kW (MBH) 3.4 (11.6) 4.8 (16.5) 5.7 (19.3) 6.4 (21.9) 8.5 (29.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.4) 3.2 (6.6) 3.7 (8.6) 4.2 (4.5) 5.4 (7.3)
(Note: The above Cooling capacities @ standard ft3/min and ESP as shown on page 23, Evaporator Blower/Motor.)
30
CeilAiR ENGINEERING MANUAL
Med Flow Total, kW (MBH) 26.3 (89.7) 28.7 (97.8) 42.4 (144.6) 45.6 (155.7) 52.3 (178.6)
(10 °F Sensible, kW (MBH) 18.1 (61.7) 19.9 (67.9) 27.9 (95.3) 30.3 (103.5) 35.9 (122.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 17.9 (14.1) 19.6 (16.6) 28.9 (35.7) 31.2 (41.0) 35.8 (14.1)
Low Flow Total, kW (MBH) 23.8 (81.3) 17.5 (59.6) 39.7 (135.6) 42.9 (146.3) 47.5 (162)
(12 °F Sensible, kW (MBH) 17 (57.9) 18.8 (64.2) 26.7 (91.3) 29.1 (99.3) 33.7 (115.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.6 (8.4) 15.0 (10.1) 22.6 (22.7) 24.5 (26.3) 27.2 (8.4)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 21.1 (72.1) 23.2 (79.1) 33.9 (115.7) 36.5 (124.7) 42.1 (143.5)
High Flow
Sensible, kW (MBH) 16.5 (56.2) 18.2 (62.1) 25.2 (86.1) 27.5 (93.7) 32.7 (111.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 18.1 (14.3) 19.9 (17.1) 28.9 (35.8) 31.2 (41.1) 36.2 (14.3)
Med Flow Total, kW (MBH) 19.1 (65.3) 21.1 (72) 31.9 (108.8) 34.3 (117.1) 38.1 (129.9)
(10 °F Sensible, kW (MBH) 15.5 (52.8) 17.2 (58.6) 24.3 (82.8) 26.4 (90) 30.7 (104.9)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.1 (7.9) 14.5 (9.6) 21.8 (21.4) 23.5 (24.5) 26.2 (7.9)
Total, kW (MBH) 17.3 (58.9) 19.1 (65.2) 29.7 (101.5) 32.3 (110.2) 34.3 (117.1)
High Flow
Sensible, kW (MBH) 14.5 (49.4) 16.1 (55) 23.2 (79.2) 25.4 (86.6) 28.8 (98.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 9.9 (4.7) 11.0 (5.7) 17.0 (13.6) 18.5 (15.8) 19.8 (4.7)
72 °F DB / 60 °F WB
Total, kW (MBH) 17.6 (59.9) 19.3 (65.9) 28.7 (97.8) 30.9 (105.3) 34.9 (119.2)
High Flow
Sensible, kW (MBH) 14.9 (50.8) 16.5 (56.3) 23 (78.6) 25.1 (85.5) 29.6 (101)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 15.1 (10.2) 16.6 (12.3) 24.5 (26.4) 26.4 (30.3) 30.2 (10.2)
Med Flow Total, kW (MBH) 15.8 (53.9) 17.4 (59.5) 27 (92) 29.1 (99.2) 31.4 (107.1)
(10 °F Sensible, kW (MBH) 13.9 (47.5) 15.4 (52.7) 22.2 (75.6) 24.1 (82.4) 27.6 (94.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 10.8 (5.6) 12.0 (6.8) 18.5 (15.8) 20.0 (18.2) 21.6 (5.6)
High Flow Total, kW (MBH) 13.9 (47.4) 15.3 (52.2) 24.9 (84.9) 27 (92.2) 27.6 (94.1)
(12 °F Sensible, kW (MBH) 12.8 (43.5) 14.1 (48.2) 21.1 (71.9) 23 (78.5) 25.3 (86.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.0 (3.2) 8.8 (3.8) 14.2 (9.9) 15.5 (11.4) 16.0 (3.2)
(Note: The above Cooling capacities @ standard ft3/min and ESP as shown on page 23, Evaporator Blower/Motor.)
31
CeilAiR ENGINEERING MANUAL
Med Flow Total, kW (MBH) 4.7 (15.9) 6.5 (22.1) 7.4 (25.4) 8.5 (29.1) 10.8 (36.8)
(10 °F Sensible, kW (MBH) 3.6 (12.3) 5.2 (17.6) 6 (20.5) 6.9 (23.5) 9.2 (31.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.2 (6.5) 4.5 12.0 () 5.1 (15.3) 5.8 (8.2) 7.6 (13.4)
Total, kW (MBH) 4.3 (14.6) 6 (20.4) 6.9 (23.7) 7.8 (26.8) 10.3 (35.1)
Low Flow
(12 °F Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.8) 5.8 (19.6) 6.5 (22.3) 8.7 (29.8)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.5 (4.0) 3.4 (7.4) 4.0 (9.7) 4.5 (5.1) 5.9 (8.3)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 3.5 (12.1) 4.9 (16.7) 5.6 (19.2) 6.6 (22.4) 8.4 (28.8)
High Flow
Sensible, kW (MBH) 3.2 (11) 4.6 (15.6) 5.3 (18.2) 6.1 (20.9) 8.1 (27.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.1 (6.1) 4.2 (10.9) 4.8 (14.0) 5.7 (7.8) 7.2 (12.3)
Med Flow Total, kW (MBH) 3.2 (10.9) 4.4 (14.9) 5 (17) 5.8 (19.9) 6.9 (23.4)
(10 °F Sensible, kW (MBH) 3 (10.3) 4.2 (14.4) 4.9 (16.7) 5.7 (19.3) 6.9 (23.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.2 (3.3) 3.0 (5.8) 3.4 (7.4) 4.0 (4.2) 4.8 (5.7)
Total, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4)
High Flow
Sensible, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.5 (1.3) 2.1 (2.9) 2.4 (3.9) 2.6 (1.7) 3.5 (3.1)
72 °F DB / 60 °F WB
Total, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5)
High Flow
Sensible, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.5) 3.2 (6.6) 3.7 (8.7) 4.1 (4.3) 5.5 (7.3)
Med Flow Total, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6)
(10 °F Sensible, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.6 (1.6) 2.3 (3.5) 2.7 (4.6) 2.9 (2.1) 3.8 (3.7)
High Flow Total, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3)
(12 °F Sensible, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.1 (0.7) 1.6 (1.6) 1.9 (2.3) 2.0 (0.8) 2.6 (1.7)
(Note: The above Cooling capacities @ standard ft /min and ESP as shown on page 23, Evaporator Blower/Motor.)
3
32
CeilAiR ENGINEERING MANUAL
Med Flow Total, kW (MBH) 17.2 (58.7) 19 (64.8) 28.3 (96.4) 30.5 (104) 34.2 (116.7)
(10 °F Sensible, kW (MBH) 14.2 (48.5) 15.8 (53.9) 22 (74.9) 23.9 (81.7) 28.2 (96.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.8 (6.4) 13.1 (7.8) 19.4 (16.9) 21.0 (19.5) 23.6 (6.4)
Low Flow Total, kW (MBH) 15.5 (52.9) 17.1 (58.5) 26.7 (91) 28.7 (97.9) 30.8 (105)
(12 °F Sensible, kW (MBH) 13.3 (45.5) 14.8 (50.5) 21.2 (72.4) 23.1 (78.8) 26.5 (90.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.9 (3.8) 9.9 (4.6) 15.3 (10.9) 16.4 (12.5) 17.8 (3.8)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 12.8 (43.6) 13.3 (45.4) 22.1 (75.5) 23.7 (80.9) 25.3 (86.5)
High Flow
Sensible, kW (MBH) 12.4 (42.4) 13.3 (45.4) 19.9 (67.8) 21.6 (73.6) 24.7 (84.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.0 (5.6) 11.5 (6.1) 19.0 (16.3) 20.4 (18.6) 22.0 (5.6)
Med Flow Total, kW (MBH) 10.6 (36.1) 11.7 (40) 21 (71.7) 22.3 (76.3) 20.9 (71.4)
(10 °F Sensible, kW (MBH) 10.6 (36.1) 11.7 (40) 19.2 (65.4) 20.7 (70.6) 20.9 (71.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 7.3 (2.7) 8.2 (3.3) 14.4 (9.9) 15.4 (11.2) 14.6 (2.7)
Total, kW (MBH) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
High Flow
Sensible, kW (MBH) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.1 (1.2) 5.7 (1.6) 9.2 (4.4) 10.0 (5.1) 10.2 (1.2)
72 °F DB / 60 °F WB
Total, kW (MBH) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
High Flow
Sensible, kW (MBH) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.5 (3.5) 9.5 (4.3) 14.1 (9.5) 15.4 (11.1) 17.0 (3.5)
Med Flow Total, kW (MBH) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
(10 °F Sensible, kW (MBH) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.7 (1.6) 6.4 (2.0) 10.0 (5.1) 11.0 (6.0) 11.4 (1.6)
Total, kW (MBH) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
High Flow
(12 °F Sensible, kW (MBH) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.6 (0.5) 4.1 (0.7) 7.0 (2.7) 7.7 (3.2) 7.2 (0.5)
(Note: The above Cooling capacities @ standard ft3/min and ESP as shown on page 23, Evaporator Blower/Motor.)
33
CeilAiR ENGINEERING MANUAL
34
CeilAiR ENGINEERING MANUAL
35
CeilAiR ENGINEERING MANUAL
36
CeilAiR ENGINEERING MANUAL
37
CeilAiR ENGINEERING MANUAL
80 °F DB / 67 °F WB, 50% RH
Total, kW (MBH) 24.6 (83.8) 26.7 (91.1) 39.3 (134.1) 42.3 (144.4) 48.9 (166.9)
High Flow
Sensible, kW (MBH) 17.4 (59.3) 19.1 (65.3) 26.6 (90.8) 28.9 (98.7) 34.5 (117.9)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 20.9 (18.6) 22.8 (21.9) 33.5 (46.3) 36.1 (53.2) 41.8 (18.6)
Total, kW (MBH) 22.7 (77.4) 24.9 (84.8) 36.8 (125.6) 39.6 (135.1) 45.1 (154)
Med Flow
Sensible, kW (MBH) 16.5 (56.4) 18.3 (62.4) 25.5 (87) 27.7 (94.6) 32.9 (112.2)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 15.5 (10.7) 17.1 (12.7) 25.2 (27.5) 27.1 (31.5) 31.0 (10.7)
Total, kW (MBH) 20.5 (70) 22.6 (77.2) 34.4 (117.4) 37.1 (126.6) 40.8 (139.3)
Low Flow
Sensible, kW (MBH) 53.1) 17.3 (58.9) 24.4 (83.4) 26.6 (90.8) 30.9 (105.5)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.7 (6.4) 13.0 (7.7) 19.6 (17.4) 21.2 (20.1) 23.4 (6.4 )
75 °F DB / 62.5 °F WB, 50% RH
Total, kW (MBH) 18 (61.3) 19.8 (67.5) 29 (99.1) 31.3 (106.7) 35.7 (121.9)
High Flow
Sensible, kW (MBH) 15 (51.2) 16.6 (56.8) 23 (78.5) 25.1 (85.5) 29.8 (101.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 15.4 (10.6) 17.0 (12.7) 24.8 (26.9) 26.8 (30.8) 30.8 (10.6)
Total, kW (MBH) 16.2 (55.2) 17.9 (61.1) 27.3 (93.3) 29.5 (100.6) 32.1 (109.7)
Med Flow
Sensible, kW (MBH) 14.1 (48) 15.6 (53.3) 22.2 (75.7) 24.2 (82.4) 27.9 (95.3)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.1 (5.8) 12.4 (7.1) 18.8 (16.1) 20.3 (18.5) 22.2 (5.8)
Total, kW (MBH) 14.4 (49.2) 15.9 (54.4) 25.6 (87.3) 27.8 (94.8) 28.6 (97.6)
Low Flow
Sensible, kW (MBH) 13 (44.4) 14.4 (49.3) 21.3 (72.6) 23.3 (79.4) 25.8 (88.2)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.3 (3.4) 9.2 (4.1) 14.6 (10.2) 15.9 (11.9) 16.6 (3.4)
72 °F DB / 60 °F WB, 50% RH
Total, kW (MBH) 14.7 (50.1) 16.1 (55.1) 24.3 (83.1) 26.2 (89.6) 29.2 (99.5)
High Flow
Sensible, kW (MBH) 13.5 (45.9) 14.9 (50.8) 21 (71.6) 22.9 (78) 26.7 (91.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 12.6 (7.4) 13.9 (8.8) 20.9 (19.6) 22.5 (22.6) 25.2 (7.4)
Total, kW (MBH) 12.7 (43.3) 13.9 (47.5) 23 (78.6) 24.9 (84.9) 25.2 (86)
Med Flow
Sensible, kW (MBH) 12.2 (41.7) 13.5 (46) 20.2 (69.1) 22.1 (75.2) 24.2 (82.7)
(10 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.7 (3.7) 9.6 (4.5) 15.8 (11.9) 17.2 (13.7) 17.4 (3.7)
Total, kW (MBH) 10 (34.1) 11.1 (37.9) 21 (71.6) 22.8 (77.8) 19.8 (67.6)
Low Flow
Sensible, kW (MBH) 10 (34.1) 11.1 (37.9) 19 (64.9) 20.8 (70.8) 19.8 (67.6)
(12 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.8 (1.6) 6.4 (2.1) 12.0 (7.2) 13.1 (8.4) 11.6 (1.6)
38
CeilAiR ENGINEERING MANUAL
39
CeilAiR ENGINEERING MANUAL
Med Flow Total, kW (MBH) 7.2 (24.6) 9.8 (33.5) 11.2 (38.2) 12.8 (43.7) 16.3 (55.8)
(10 °F Sensible, kW (MBH) 4.7 (16) 6.6 (22.5) 7.6 (26) 8.8 (30) 11.5 (39.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.9 (14.8) 6.7 (25.8) 7.6 (32.9) 8.7 (17.6) 11.1 (27.7)
Total, kW (MBH) 6.6 (22.7) 9.1 (31.2) 10.5 (35.8) 11.8 (40.4) 15.3 (52.3)
Low Flow
(12 °F Sensible, kW (MBH) 4.4 (15.2) 6.3 (21.4) 7.3 (24.9) 8.3 (28.5) 11 (37.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.8 (9.1) 5.2 (16.1) 6.0 (20.8) 6.7 (10.9) 8.7 (17.6)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 5.7 (19.5) 7.8 (26.8) 9 (30.6) 10.3 (35.2) 13.2 (45.2)
High Flow
Sensible, kW (MBH) 4.2 (14.4) 6 (20.3) 6.9 (23.6) 8 (27.1) 10.5 (35.8)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.9 (14.5) 6.7 (25.9) 7.6 (33.2) 8.8 (17.9) 11.3 (28.4)
Med Flow Total, kW (MBH) 5.2 (17.9) 7.3 (24.8) 8.4 (28.6) 9.5 (32.5) 12.4 (42.3)
(10 °F Sensible, kW (MBH) 4 (13.6) 5.7 (19.4) 6.6 (22.5) 7.5 (25.7) 10 (34.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.6 (8.2) 5.0 (15.1) 5.7 (19.3) 6.5 (10.2) 8.5 (16.7)
Low Flow Total, kW (MBH) 4.8 (16.4) 6.7 (22.9) 7.8 (26.7) 8.8 (29.9) 11.4 (39.1)
(12 °F Sensible, kW (MBH) 3.8 (12.9) 5.4 (18.4) 6.3 (21.4) 7.1 (24.4) 9.5 (32.5)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.8 (5.0) 3.8 (9.2) 4.4 (11.9) 5.0 (6.3) 6.5 (10.2)
72 °F DB / 60 °F WB
Total, kW (MBH) 4.7 (16.1) 6.6 (22.4) 7.5 (25.8) 8.7 (29.6) 11.2 (38.4)
High Flow
Sensible, kW (MBH) 3.8 (13) 5.4 (18.5) 6.3 (21.5) 7.2 (24.6) 9.6 (32.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 4.1 (10.4) 5.7 (19.0) 6.4 (24.0) 7.4 (13.0) 9.6 (21.0)
MedFlow Total, kW (MBH) 4.3 (14.8) 6.1 (20.7) 7 (23.9) 7.9 (27.1) 10.4 (35.4)
(10 °F Sensible, kW (MBH) 3.6 (12.3) 5.1 (17.5) 6 (20.4) 6.8 (23.2) 9.1 (31)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.0 (5.9) 4.2 (10.8) 4.8 (14.0) 5.4 (7.4) 7.1 (12.1)
Low Flow Total, kW (MBH) 4 (13.5) 5.6 (19) 6.4 (22) 7.3 (24.9) 9.5 (32.5)
(12 °F Sensible, kW (MBH) 3.4 (11.6) 4.8 (16.5) 5.7 (19.3) 6.4 (21.9) 8.5 (29.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.4) 3.2 (6.6) 3.7 (8.6) 4.2 (4.5) 5.4 (7.3)
40
CeilAiR ENGINEERING MANUAL
Med Flow Total, kW (MBH) 26.3 (89.7) 28.7 (97.8) 42.4 (144.6) 45.6 (155.7) 52.3 (178.6)
(10 °F Sensible, kW (MBH) 18.1 (61.7) 19.9 (67.9) 27.9 (95.3) 30.3 (103.5) 35.9 (122.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 17.9 (14.1) 19.6 (16.6) 28.9 (35.7) 31.2 (41.0) 35.8 (14.1)
Low Flow Total, kW (MBH) 23.8 (81.3) 17.5 (59.6) 39.7 (135.6) 42.9 (146.3) 47.5 (162)
(12 °F Sensible, kW (MBH) 17 (57.9) 18.8 (64.2) 26.7 (91.3) 29.1 (99.3) 33.7 (115.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.6 (8.4) 15.0 (10.1) 22.6 (22.7) 24.5 (26.3) 27.2 (8.4)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 21.1 (72.1) 23.2 (79.1) 33.9 (115.7) 36.5 (124.7) 42.1 (143.5)
High Flow
Sensible, kW (MBH) 16.5 (56.2) 18.2 (62.1) 25.2 (86.1) 27.5 (93.7) 32.7 (111.7)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 18.1 (14.3) 19.9 (17.1) 28.9 (35.8) 31.2 (41.1) 36.2 (14.3)
Med Flow Total, kW (MBH) 19.1 (65.3) 21.1 (72) 31.9 (108.8) 34.3 (117.1) 38.1 (129.9)
(10 °F Sensible, kW (MBH) 15.5 (52.8) 17.2 (58.6) 24.3 (82.8) 26.4 (90) 30.7 (104.9)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 13.1 (7.9) 14.5 (9.6) 21.8 (21.4) 23.5 (24.5) 26.2 (7.9)
Low Flow Total, kW (MBH) 17.3 (58.9) 19.1 (65.2) 29.7 (101.5) 32.3 (110.2) 34.3 (117.1)
(12 °F Sensible, kW (MBH) 14.5 (49.4) 16.1 (55) 23.2 (79.2) 25.4 (86.6) 28.8 (98.2)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 9.9 (4.7) 11.0 (5.7) 17.0 (13.6) 18.5 (15.8) 19.8 (4.7)
72 °F DB / 60 °F WB
Total, kW (MBH) 17.6 (59.9) 19.3 (65.9) 28.7 (97.8) 30.9 (105.3) 34.9 (119.2)
High Flow
Sensible, kW (MBH) 14.9 (50.8) 16.5 (56.3) 23 (78.6) 25.1 (85.5) 29.6 (101)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 15.1 (10.2) 16.6 (12.3) 24.5 (26.4) 26.4 (30.3) 30.2 (10.2)
MedFlow Total, kW (MBH) 15.8 (53.9) 17.4 (59.5) 27 (92) 29.1 (99.2) 31.4 (107.1)
(10 °F Sensible, kW (MBH) 13.9 (47.5) 15.4 (52.7) 22.2 (75.6) 24.1 (82.4) 27.6 (94.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 10.8 (5.6) 12.0 (6.8) 18.5 (15.8) 20.0 (18.2) 21.6 (5.6)
Total, kW (MBH) 13.9 (47.4) 15.3 (52.2) 24.9 (84.9) 27 (92.2) 27.6 (94.1)
Low Flow
(12 °F Sensible, kW (MBH) 12.8 (43.5) 14.1 (48.2) 21.1 (71.9) 23 (78.5) 25.3 (86.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.0 (3.2) 8.8 (3.8) 14.2 (9.9) 15.5 (11.4) 16.0 (3.2)
41
CeilAiR ENGINEERING MANUAL
Med Flow Total, kW (MBH) 4.7 (15.9) 6.5 (22.1) 7.4 (25.4) 8.5 (29.1) 10.8 (36.8)
(10 °F Sensible, kW (MBH) 3.6 (12.3) 5.2 (17.6) 6 (20.5) 6.9 (23.5) 9.2 (31.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.2 (6.5) 4.5 (12.0) 5.1 (15.3) 5.8 (8.2) 7.6 (13.4)
Total, kW (MBH) 4.3 (14.6) 6 (20.4) 6.9 (23.7) 7.8 (26.8) 10.3 (35.1)
Low Flow
Sensible, kW (MBH) 3.4 (11.7) 4.9 (16.8) 5.8 (19.6) 6.5 (22.3) 8.7 (29.8)
(12 °F ΔTw
Flow Rate, GPM (Pressure Drop, ftH2O) 2.5 (4.0) 3.4 (7.4) 4.0 (9.7) 4.5 (5.1) 5.9 (8.3)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 3.5 (12.1) 4.9 (16.7) 5.6 (19.2) 6.6 (22.4) 8.4 (28.8)
High Flow
Sensible, kW (MBH) 3.2 (11) 4.6 (15.6) 5.3 (18.2) 6.1 (20.9) 8.1 (27.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.1 (6.1) 4.2 (10.9) 4.8 (14.0) 5.7 (7.8) 7.2 (12.3)
Total, kW (MBH) 3.2 (10.9) 4.4 (14.9) 5 (17) 5.8 (19.9) 6.9 (23.4)
Med Flow
(10 °F Sensible, kW (MBH) 3 (10.3) 4.2 (14.4) 4.9 (16.7) 5.7 (19.3) 6.9 (23.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.2 (3.3) 3.0 (5.8) 3.4 (7.4) 4.0 (4.2) 4.8 (5.7)
High Flow Total, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4)
(12 °F Sensible, kW (MBH) 2.6 (8.7) 3.6 (12.4) 4.2 (14.4) 4.5 (15.4) 6 (20.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.5 (1.3) 2.1 (2.9) 2.4 (3.9) 2.6 (1.7) 3.5 (3.1)
72 °F DB / 60 °F WB
Total, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5)
High Flow
Sensible, kW (MBH) 2.6 (9) 3.7 (12.7) 4.3 (14.8) 4.8 (16.2) 6.3 (21.5)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 2.3 (3.5) 3.2 (6.6) 3.7 (8.7) 4.1 (4.3) 5.5 (7.3)
Med Flow Total, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6)
(10 °F Sensible, kW (MBH) 2.3 (7.9) 3.3 (11.3) 3.8 (13.1) 4.1 (14.1) 5.5 (18.6)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.6 (1.6) 2.3 (3.5) 2.7 (4.6) 2.9 (2.1) 3.8 (3.7)
High Flow Total, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3)
(12 °F Sensible, kW (MBH) 2 (6.7) 2.8 (9.6) 3.3 (11.1) 3.4 (11.5) 4.5 (15.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 1.1 (0.7) 1.6 (1.6) 1.9 (2.3) 2.0 (0.8) 2.6 (1.7)
(Note: The above Cooling capacities @ standard ft3/min and ESP as shown on page 34, Evaporator Blower/Motor.)
42
CeilAiR ENGINEERING MANUAL
Total, kW (MBH) 18.8 (64.2) 20.5 (69.8) 30.1 (102.6) 32.5 (110.9) 37.4 (127.6)
High Flow
Sensible, kW (MBH) 15 (51.2) 16.5 (56.4) 22.8 (77.6) 24.8 (84.8) 29.8 (101.6)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 16.1 (11.4) 17.6 (13.4) 25.7 (28.3) 27.9 (32.7) 32.2 (11.4)
Med Flow Total, kW (MBH) 17.2 (58.7) 19 (64.8) 28.3 (96.4) 30.5 (104) 34.2 (116.7)
(10 °F Sensible, kW (MBH) 14.2 (48.5) 15.8 (53.9) 22 (74.9) 23.9 (81.7) 28.2 (96.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.8 (6.4) 13.1 (7.8) 19.4 (16.9) 21.0 (19.5) 23.6 (6.4)
Low Flow Total, kW (MBH) 15.5 (52.9) 17.1 (58.5) 26.7 (91) 28.7 (97.9) 30.8 (105)
(12 °F Sensible, kW (MBH) 13.3 (45.5) 14.8 (50.5) 21.2 (72.4) 23.1 (78.8) 26.5 (90.3)
ΔTw
Flow Rate, GPM (Pressure Drop, ftH2O) 8.9 (3.8) 9.9 (4.6) 15.3 (10.9) 16.4 (12.5) 17.8 (3.8)
75 °F DB / 62.5 °F WB
Total, kW (MBH) 12.8 (43.6) 13.3 (45.4) 22.1 (75.5) 23.7 (80.9) 25.3 (86.5)
High Flow
Sensible, kW (MBH) 12.4 (42.4) 13.3 (45.4) 19.9 (67.8) 21.6 (73.6) 24.7 (84.2)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 11.0 (5.6) 11.5 (6.1) 19.0 (16.3) 20.4 (18.6) 22.0 (5.6)
Med Flow Total, kW (MBH) 10.6 (36.1) 11.7 (40) 21 (71.7) 22.3 (76.3) 20.9 (71.4)
(10 °F Sensible, kW (MBH) 10.6 (36.1) 11.7 (40) 19.2 (65.4) 20.7 (70.6) 20.9 (71.4)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 7.3 (2.7) 8.2 (3.3) 14.4 (9.9) 15.4 (11.2) 14.6 (2.7)
High Flow Total, kW (MBH) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
(12 °F Sensible, kW (MBH) 8.8 (30) 9.8 (33.4) 15.9 (54.3) 17.4 (59.3) 17.4 (59.3)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.1 (1.2) 5.7 (1.6) 9.2 (4.4) 10.0 (5.1) 10.2 (1.2)
72 °F DB / 60 °F WB
Total, kW (MBH) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
High Flow
Sensible, kW (MBH) 9.8 (33.6) 10.9 (37.2) 16.3 (55.6) 17.7 (60.5) 19.5 (66.4)
(8 °F ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 8.5 (3.5) 9.5 (4.3) 14.1 (9.5) 15.4 (11.1) 17.0 (3.5)
Med Flow Total, kW (MBH) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
(10 °F Sensible, kW (MBH) 8.2 (27.9) 9.1 (30.9) 14.5 (49.3) 15.8 (53.8) 16.1 (55.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 5.7 (1.6) 6.4 (2.0) 10.0 (5.1) 11.0 (6.0) 11.4 (1.6)
High Flow Total, kW (MBH) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
(12 °F Sensible, kW (MBH) 6.1 (20.9) 6.8 (23.4) 12.1 (41.4) 13.3 (45.3) 12 (41.1)
ΔTw)
Flow Rate, GPM (Pressure Drop, ftH2O) 3.6 (0.5) 4.1 (0.7) 7.0 (2.7) 7.7 (3.2) 7.2 (0.5)
(Note: The above Cooling capacities @ standard ft /min and ESP as shown on page 35, Evaporator Blower/Motor.)
3
43
CeilAiR ENGINEERING MANUAL
44
CeilAiR ENGINEERING MANUAL
-
Without Condensate Pump (OHS-012 − OHS-060 AS)
OHS-012-AS OHS-018-AS OHS-024-AS OHS-032-AS OHS-040-AS OHS-048-AS OHS-060-AS
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 11.7 17.2 25.0 14.8 20.3 30.0 17.5 25.6 40.0 19.9 29.0 45.0 21.2 30.3 45.0 N/A N/A
277/1/60 9.2 14.7 20.0 11.0 15.8 20.0 12.9 19.8 30.0 15.8 23.1 35.0 16.9 24.2 35.0 N/A N/A
208/3/60 N/A N/A 14.3 18.0 25.0 15.9 22.6 30.0 17.2 23.9 35.0 N/A N/A
460/3/60 N/A N/A 6.6 8.9 15.0 7.4 11.2 15.0 8.1 11.9 15.0 N/A N/A
COOLING and ELECTRIC REHEAT/HEAT, with or without Humidifier (No Condensate Pump)
208/1/60 33.1 44.0 45.0 36.2 47.0 50.0 38.9 52.4 60.0 41.3 55.7 60.0 42.6 57 60.0 N/A N/A
277/1/60 27.3 37.3 40.0 29.1 38.5 40.0 31.0 42.5 50.0 33.9 45.7 50.0 35.0 46.8 50.0 N/A N/A
208/3/60 N/A N/A 26.7 33.5 35.0 28.3 38.1 45.0 29.6 39.4 45.0 N/A N/A
460/3/60 N/A N/A 12.9 16.8 20.0 13.7 19.1 20.0 14.4 19.8 20.0 N/A N/A
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 19.9 25.4 30.0 23.0 28.5 35.0 25.7 33.8 45.0 28.1 37.2 50.0 29.4 38.5 50.0 N/A N/A
277/1/60 15.3 20.8 25.0 17.1 21.9 30.0 19.0 25.9 35.0 21.9 29.2 40.0 23.0 30.3 40.0 N/A N/A
208/3/60 N/A N/A 22.5 26.2 35.0 24.1 30.8 40.0 25.4 32.1 40.0 N/A N/A
460/3/60 N/A N/A 10.3 12.6 15.0 11.1 14.9 20.0 11.8 15.6 20.0 N/A N/A
45
CeilAiR ENGINEERING MANUAL
46
CeilAiR ENGINEERING MANUAL
47
CeilAiR ENGINEERING MANUAL
48
CeilAiR ENGINEERING MANUAL
49
CeilAiR ENGINEERING MANUAL
50
CeilAiR ENGINEERING MANUAL
51
CeilAiR ENGINEERING MANUAL
52
CeilAiR ENGINEERING MANUAL
COOLING AND CONDENSATE PUMP only, with or without Hot Gas, Hot Water or Steam Reheat
208/1/60 18.6 15.9 19.4 27.7 40 18.6 15.9 19.4 27.7 40 N/A N/A
277/1/60 15.8 13.5 16.5 23.1 35 15.8 13.5 16.5 23.1 35 N/A N/A
208/3/60 13.4 12 13.8 20.1 30 13.4 12 13.8 20.1 30 19.3 16.8 20.1 27.7 40 25.7 22.4 26.7 32.3 50
-
460/3/60 6.8 6.1 7 10.6 15 6.8 6.1 7 10.6 15 9.9 8.7 10.3 13.3 20 11.4 10 11.8 15.3 20
COOLING, CONDENSATE PUMP, and ELECTRIC REHEAT/HEAT only, (No Humidifier)
208/1/60 40 37.3 40.8 54.4 60 40 37.3 40.8 54.4 60 N/A N/A
277/1/60 33.9 31.6 34.6 45.7 50 33.9 31.6 34.6 45.7 50 N/A N/A
208/3/60 25.8 24.4 26.2 35.6 40 25.8 24.4 26.2 35.6 40 44 41.5 44.8 58.6 60 50.4 47.1 51.4 63.2 70
460/3/60 13.1 12.4 13.3 18.5 20 13.1 12.4 13.3 18.5 20 22.5 21.3 22.9 29.1 30 24 22.6 24.4 31.1 35
COOLING, CONDENSATE PUMP, and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat)
208/1/60 26.8 24.1 27.6 35.9 50 26.8 24.1 27.6 35.9 50 N/A N/A
277/1/60 21.9 19.6 22.6 29.2 40 21.9 19.6 22.6 29.2 40 N/A N/A
208/3/60 21.6 20.2 22 28.3 40 21.6 20.2 22 28.3 40 35.6 33.1 36.4 44 60 42 38.7 43 48.6 60
460/3/60 10.5 9.8 10.7 14.3 20 10.5 9.8 10.7 14.3 20 17.3 16.1 17.7 20.7 25 18.8 17.4 19.2 22.7 30
COOLING, CONDENSATE PUMP, ELECTRIC REHEAT/HEAT and HUMIDIFIER
208/1/60 40 37.3 40.8 54.4 60 40 37.3 40.8 54.4 60 N/A N/A
277/1/60 33.9 31.6 34.6 45.7 50 33.9 31.6 34.6 45.7 50 N/A N/A
208/3/60 25.8 24.4 26.2 35.6 40 25.8 24.4 26.2 35.6 40 44 41.5 44.8 58.6 60 50.4 47.1 51.4 63.2 70
460/3/60 13.1 12.4 13.3 18.5 20 13.1 12.4 13.3 18.5 20 22.5 21.3 22.9 29.1 30 24 22.6 24.4 31.1 35
53
CeilAiR ENGINEERING MANUAL
54
CeilAiR ENGINEERING MANUAL
Chilled Water
-
Without Condensate Pump (OHS-012 − OHS-040 C)
OHS-012-C OHS-018-C OHS-024-C OHS-032-C OHS-040-C
Model
FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS FLA MCA MFS
COOLING ONLY, with or without Hot Gas, Hot Water or Steam Reheat (No Condensate Pump)
208/1/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 4.7 5.9 15
277/1/60 1.8 2.3 15 1.8 2.3 15 1.8 2.3 15 2.3 2.9 15 3.4 4.3 15
208/3/60 2.7 3.4 15 2.7 3.4 15 2.7 3.4 15 3.4 4.3 15 4.7 5.9 15
460/3/60 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 1.5 1.9 15 2.2 2.8 15
COOLING and ELECTRIC REHEAT/HEAT only, (No Humidifier and Condensate Pump)
208/1/60 24.1 30.1 35 24.1 30.1 35 24.1 30.1 35 24.8 31 35 26.1 32.6 35
277/1/60 19.9 24.9 25 19.9 24.9 25 19.9 24.9 25 20.4 25.5 30 21.5 26.9 30
208/3/60 15.1 18.9 20 15.1 18.9 20 15.1 18.9 20 15.8 19.8 20 17.1 21.4 25
460/3/60 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 7.8 9.8 15 8.5 10.6 15
COOLING and HUMIDIFIER only, with or without Hot Gas, Hot Water or Steam Reheat (No Electric Reheat/Heat and Condensate Pump)
208/1/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 12.9 16.1 20
277/1/60 7.9 9.9 15 7.9 9.9 15 7.9 9.9 15 8.4 10.5 15 9.5 11.9 15
208/3/60 10.9 13.6 15 10.9 13.6 15 10.9 13.6 15 11.6 14.5 15 12.9 16.1 20
460/3/60 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 5.2 6.5 15 5.9 7.4 15
COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER (No Condensate Pump)
208/1/60 32.3 40.4 45 32.3 40.4 45 32.3 40.4 45 33 41.3 45 34.3 42.9 45
277/1/60 26 32.5 35 26 32.5 35 26 32.5 35 26.5 33.1 35 27.6 34.5 35
208/3/60 23.3 29.1 30 23.3 29.1 30 23.3 29.1 30 24 30 35 25.3 31.6 35
460/3/60 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 11.5 14.4 15 12.2 15.3 20
55
CeilAiR ENGINEERING MANUAL
56
CeilAiR ENGINEERING MANUAL
57
CeilAiR ENGINEERING MANUAL
58
CeilAiR ENGINEERING MANUAL
Legend:
Notes:
“A” = Suction Line, inches OD Copper
Note-1:-------- means connection type not applicable to this unit configuration.
“B” = Liquid Line, inches OD Copper
“C” = Hot Gas, inches OD Copper Note-2: Dimensions shown represent the “pipe connection size” only. For
information detailing the sizing of the interconnecting refrigerant and water lines,
please refer to the CeilAiR Installation, Operation and Maintenance Manual.
Legend:
59
CeilAiR ENGINEERING MANUAL
60
CeilAiR ENGINEERING MANUAL
61
CeilAiR ENGINEERING MANUAL
62
CeilAiR ENGINEERING MANUAL
63
CeilAiR ENGINEERING MANUAL
OHS-012 thru 040-HAHU DX - MODEL “A” “E” “F” “C” “L” “M”
“H-Series”, Air Handling Unit (“Ducted OHS-012, 018, and 024-AHU 20.0 19.75 15.63
see
note
see
note
see
note
Version” - Belt Driven) see see see
OHS-032 and 040-AHU 24.0 19.75 19.75
note note note
64
CeilAiR ENGINEERING MANUAL
65
CeilAiR ENGINEERING MANUAL
Water/Glycol Systems
OHS-040-W / G Self-Contained,
Water/Glycol Cooled (“Ductless”
Spot Cooler)
66
CeilAiR ENGINEERING MANUAL
67
CeilAiR ENGINEERING MANUAL
68
CeilAiR ENGINEERING MANUAL
69
CeilAiR ENGINEERING MANUAL
70
CeilAiR ENGINEERING MANUAL
71
CeilAiR ENGINEERING MANUAL
72
CeilAiR ENGINEERING MANUAL
73
CeilAiR ENGINEERING MANUAL
All electrically actuated components shall be easily accessible
from the front of the unit without reaching over exposed high
The controller shall receive inputs for measurable
voltage components or rotating parts. Each high voltage circuit
shall be individually protected by circuit breakers or manual control conditions (temperature, relative humidity, and
motor starters on all phases. The blower motor shall have thermal dew point) via return air or room mounted sensors. The
and short circuit protection. Line voltage and 24-volt control internal logic will then determine if the conditions
circuit wiring shall be routed in separate bundles. require cooling, humidification or dehumidification.
The electric box shall be positioned for service convenience and Control setpoints shall be established to maintain
shall include all the contactors, starters, fuses, circuit breakers, design conditions of the installation. The controller will
terminal boards and control transformer required for operation respond accordingly to changes in these conditions and
of the STULZ unit and shall allow for full service access. control the output/demand for the appropriate mode of
Controller operation until user defined conditions are achieved.
Field Configurable
A-Tech-1.1 Controller
The CeilAiR ceiling air conditioner shall be provided with a The program for the E² Series controller shall be field
STULZ slim-line, ultra-thin profile, 1-stage cool / 1-stage heat, configurable, so the operator can select control
remote wall mounted programmable digital microprocessor setpoints specific to the application. The operator
based controller. interface for the E² controller is provided via a door
Notes: mounted user interface
• The A-Tech-1.1 thermostat is standard on all single stage DX display panel. The display panel shall be a backlit LCD
and non-proportional chilled water systems. graphical display and function keys that give complete
• The A-Tech-1.2 thermostat is standard on all dual stage DX control and monitoring capability of the precision
systems. cooling system. The menu-driven interface shall provide
• A remote sensor (wired) is available on request. the ability to scroll through and enter various menu
screens.
A-Tech-1.1 Features: Password Protection
• Auto changeover for Heat/Cool Modes
Access to the Info Menu, Alarms Log, and the ability to
• Selectable °F or °C display
monitor room conditions shall be allowed without the
• Fan selector for continuous fan operation use of a password. Modifications to the control setpoints
• Built-in short cycle protection shall require the use of a password. The controller shall
• Internal switch to lock-out the keypad to prevent unauthorized be programmed to recognize predetermined security
tampering levels before allowing access to display screens
• Electronic calibration containing critical variables. Three secured menu levels
• 45 second fan purge after heating and cooling call (Control, Service and Factory) will support unique
• Day/Night button for user selectable alternate setpoint passwords that must be entered to access the menu
manual setback screens so only authorized personnel may perform
modifications to the settings.
E² Series Controller Restorable Parameters/Factory Defaults
General Upon initial start-up the system shall operate using the
The advanced microprocessor-based E² Series controller shall setpoints programmed by the factory. The customer
be equipped with flexible software capable of meeting the may enter new operating parameters in the Control
specific needs of the application. The setpoints shall be default menu and the system will then operate accordingly. The
and their ranges shall be easily viewed and adjusted from the new setpoints may be stored as, “Customer Default
user interface display. The program and operating parameters Setpoints”. The primary setpoints entered by thefactory
shall be permanently stored on a non-volatile system in the event remain stored in the controller’s memory as, “Factory
of power failure. Setpoints”. The setpoints for the system may be re-
adjusted in the Control menu at any time. If it becomes
The controller shall be designed to manage temperature and
necessary, the customer may restore the setpoints
relative humidity (RH) levels to a user defined setpoint via control
back to the Customer Default setpoint values or to the
output signals to the system.
original Factory (primary) setpoint values.
74
CeilAiR ENGINEERING MANUAL
Timer Feature Optional Features
The timer shall enable a setup of an operating schedule to
STULZ CeilAiR standard features can be deleted and/or
automatically scale back or shut down the air conditioner during
substituted with optional features to allow you the flexibility to
low demand or unoccupied periods. This is an energy saving
select the configuration best suited for your application.
feature to create an operating schedule tailored to the needs of
the building. An evening (night-setback) schedule may also be
created to enable the system to operate at night with relaxed
Mechanical Options
temperature/humidity setpoints and offsets. Full-Floating, Hot Gas Bypass
A/C Grouping pLAN Operation (Optional) (Models OHS-( )-()AHU/RCU-() only)
Multiple STULZ CeilAiR system controllers shall be able to be
The CeilAiR ceiling A/C shall incorporate a full floating hot gas
connected (grouped) to a pLAN local network, allowing the
bypass system to provide modulation of the unit’s cooling
communication of data and information from each controller to a
capacity and evaporator coil freeze protection under low load
central control terminal or Lead controller. The Lead controller
conditions.
display screens can be used to monitor and adjust group control
variables for the individual system controllers. Each E² Snap-Acting, Hot Gas Bypass
controller connected to the pLAN network shall be identified (Models OHS-()-AR, W and G only)
with its own unique address. Multiple STULZ CeilAiR systems
The STULZ CeilAiR ceiling mounted air conditioning system
consisting of up to eight STULZ precision air conditioners
shall incorporate a snap-acting hot-gas bypass system to
equipped with like controllers may be controlled and monitored
provide modulation of the unit’s cooling capacity and
via the E² series controller. With multiple STULZ CeilAiR systems
evaporator coil freeze protection under low load conditions.
each unit can selectively be configured as Active to operate as a
primary A/C, Capacity Assist for staged operation, or as High Static Pressure Belt-Drive Blowers
Standby to come online for a failed air conditioning unit to
The CeilAiR ceiling air conditioner shall be provided with a high
ensure continuous availability. The controller may also be
static pressure belt-driven evaporator blower to provide
configured to rotate units with timed duty cycling to promote
standard unit airflow.
equal run-time and assure that each STULZ CeilAiR system,
within the rotating group, is operationally exercised on a periodic (Note: Due to the probable change in standard unit blower motor
timed basis. horsepower for the High Static Belt-Drive Blower option, please
consult your local STULZ sales representative for the following
Remote BMS Interface (Optional) unit specification changes: Blower Motor Horsepower, Net
The E² series controller shall incorporate a communication Cooling Capacity, Electrical Data, Discharge Blower Data
interface port that can be field connected to a Building
Unit Air Flow Rate (ft3/min) will match values shown in the
Management System via Modbus, BACnet MS/TP, SNMP,
Performance Data tables for each respective unit model.)
HTTP, or BACnet over ETHERNET/IP as configured by the
factory. A controller interfaced to a network must be configured Low Entering Condenser Water Kit
for BMS communication.
For Water/Glycol systems that require entering condenser
Alarms water temperatures from 45°F to 65°F, the system provides
Alarm conditions shall activate a red LED indicator that a factory installed in-line liquid refrigerant receiver to help
backlights the alarm function key. As an option, an alarm reduce the negative effect the low condenser source can have
condition may also be enunciated by an audible alarm signal. An on the evaporator. A compressor crankcase heater is
alarm is acknowledged by pressing the alarm key. This calls up standard with this option. (Compressor Sound Jackets are not
alarm display screens that provides a text message detailing the available with this option due to the crankcase heater).
alarm conditions. After an alarm condition is corrected, the alarm Steam Generating Humidifier
can be cleared by pressing the alarm key.
The humidifier shall be a self-contained atmospheric steam
E² Constant Contact (Optional) generator. The humidifier assembly shall include an integral fill
The control package shall include a STULZ Constant Contact cup, fill and drain valves, disposable steam cylinder and
short-term power supply for the E² Series Controller to allow associated piping. The humidifier shall be equipped with an
the controller to manage the power transfer switch from one auto-adaptive control system to optimize water conductivity,
primary power source to another while maintaining control automatic drain and flush cycles, minimize energy waste
communications with an active monitoring system. The E² and maximize cylinder life. The humidifier shall have output
Constant Contact shall permit a minimum of one-minute ride between 20% and 100% of rated capacity. The unit shall
through period. include draw in water tempering to ensure the drain water
does not exceed 140°F during operation.
75
CeilAiR ENGINEERING MANUAL
Dehumidification Cycle DX extruded aluminum heat sink and solid-state logic system
The system shall be a refrigeration-based dehumidification to provide close dry bulb temperature control.
mode. Moisture is condensed on the cooling coil and
discharged through the condensate drain. Reheat (electric, hot Low Profile Condensate Pump
gas, steam or hot water) shall be used to offset sensible cooling A Low-Profile condensate pump designed for limited height
during the dehumidification cycle. ceiling plenum installation shall be factory provided for
automatic removal of condensate and humidifier flush water
Dehumidification Cycle CW (if applicable). The condensate pump shall be field installed as
The system shall be provided with a dehumidification control a standard.
mode. The chilled water valve shall be opened to allow chilled The Low-Profile condensate pump can be factory installed as
water flow during a dehumidification demand. Moisture is an option on models OHS-012/040-AS, AHU, AR, W, G and
condensed on the cooling coil and discharged through the C.
condensate drain. Reheat (electric, hot water) shall be provided
All-Metal Condensate Pump
to offset sensible cooling during the dehumidification cycle.
A heavy-duty All-Metal condensate pump shall be provided for
Electric Reheat/Heat automatic removal of condensate and humidifier flush water (if
applicable).
A factory mounted and wired low-watt density, electric resistance
The pump shall be constructed with a cast aluminum reservoir
heater shall be included to provide automatic sensible reheating
and impeller; aluminum reservoir cover and impeller chamber
during the dehumidification cycle and automatic heating mode.
cover; stainless steel fasteners and a stainless-steel motor
Electric heaters shall be provided with miniature shaft. The condensate pump meets most local codes for
thermal/magnetic circuit breakers that shall protect each certification as a “plenum rated” pump. The condensate pump
ungrounded conductor. Also included will be one automatic shall be field installed only.
reset and one manual reset over-temperature safety device (pilot The condensate pump shall be specifically designed to operate
duty). with the higher condensate temperatures caused by the flush
and drain cycle of the electrode canister humidifiers.
Hot Gas Reheat
(Models OHS-()-AS, AR, W and G only) Dual Overflow Safety Switches
In addition to the standard condensate pan overflow safety
A factory-installed copper tube, aluminum-fin hot gas reheat coil
float(s), the condensate pump shall include an internal overflow
and valve shall be provided for automatic sensible reheating safety float switch which, when wired to the A/C’s remote stop/
mode during dehumidification cycle is provided. Hot compressor start terminals, shall open the A/C’s control circuit, thereby
discharge gas shall be diverted from the condenser to the hot gas shutting the A/C down in the event of a condensate overflow.
reheat coil providing energy-free sensible reheating.
Air Filtration
Hot Water Reheat/Heat CeilAiR ceiling A/C’s are available with the following standard
(F1) and optional (F2 and F3) high efficiency IAQ-conscious
A factory-installed, copper tube, aluminum-fin heat/
filtration:
reheat coil and 2-way control valve shall be provided to
F1: 1 in., 20% effective filtration (standard) F2:
control the flow of hot water for automatic sensible
reheating mode during the dehumidification cycle and 2 in., 30% effective filtration
automatic heating mode as required. F3: 2 in., 30% plus 4 in., 60% for 95% effective filtration
(includes field-installed filter box for 4 in. filter)
Steam Reheat/Heat
Air Pattern Type Filters Available
A factory installed copper tube, aluminum fin
heat/reheat coil and 2-way control valve shall be Direct Drive012/040
provided to control the flow of steam for automatic w/ Spot Cooler: F1
sensible reheating mode during the dehumidification
w/ Ducted Return: F1, F2 (n/a 024)
cycle and automatic heating mode as required.
Belt-Drive Units
Note: Steam trap and steam piping specialties shall be
provided by others, not STULZ w/ Ducted Return: F1, F2 and F3
SCR Fired Reheat (Requires Filter ratings are based on dust spot efficiency ratings per
ASHRAE Test Standard 52-76.
E²controller)
Note: F2 and F3 optional filters create additional static pressure
The electric heat/reheat shall be controlled through a and may require the High Static Pressure Belt-Drive Option.
“Zero Firing” Silicon Controlled Rectifier (SCR) with an Please consult your local Sales Representative for details.
76
CeilAiR ENGINEERING MANUAL
Smoke Detection
Note: Three phase power supply is a standard
A photo-electric smoke detector shall be factory installed and
feature on models OHS-048 and larger units.
wired in the return air section of the STULZ CeilAiR air
conditioning system. The photo-electric detector shall include 277/1/60 Power Supply
built-in circuitry that performs a functional test of all detection (Models OHS-012 thru-040)
circuits at least once every 40 seconds without the need for A main power distribution block shall be located in the
generating smoke. The UL-listed velocity range shall be 0-3000 air conditioner’s electric box for single point power
fpm. The air conditioner will shut down upon sensing smoke in connection to a 277/1/60 power supply source. All
the return air stream. system components (motor, heater and humidifier, if
applicable) shall be rated for operation with a 277/1/60
Firestat power supply. 277V to 208V main power step-down
The STULZ CeilAiR system shall be provided with a factory transformers shall not be required.
wired and mounted firestat. The firestat shuts down the air
Fast-delivery orders sometimes require the OHS
conditioner upon sensing a high return air temperature.
system be shipped from stock as 208/1/60. In those
cases, 277/1/60 applications are provided with a field-
Remote Water Detector-Spot Type
installed 277-to-208V step-down transformer.
A remote single point water/leak detector shall be factory
supplied and shall ship separately for field installation. Upon Main Power Service Switch
sensing a water leak, the normally closed water detector control The main power service switch shall be the NEMA 3R or
circuit shall open, thereby shutting down the STULZ CeilAiR NEMA-12 non-fused type, depending on the OHS model
water producing components. selected. The disconnect switch shall have a lockable
handle.
Remote Water Detector-Dual Spot Type
Field installed main power service switches shall be the
A dual remote single point water/leak detector shall be factory standard option, however, switches can be optionally
supplied and shall ship separately for field installation. Upon factory mounted on select CeilAiR systems. Factory
sensing a water leak, the normally closed water detector control mounting of disconnect switches is not available on
circuit shall open, thereby shutting down the STULZ CeilAiR models OHS-012, 018, 024 and 032-AS incorporating
water producing components. the “Ducted” Evaporator Connection option.
Remote Water Detector-Strip Type
A 20 ft. remote strip/cable type water/leak detector shall be Air-Side Economizer Controls
provided for remote field installation. In addition to the 20 ft. The STULZ CeilAiR system controller shall be equipped
sensing cable, a 24-volt water detector power module shall with a unique air-side economization mode for
require field mounting and wiring to the factory provided terminal applications using outdoor air-side economizing.
connection. Upon sensing a water leak, the normally closed The STULZ Air-Side economizer control package shall
water detector control circuit shall open, thereby shutting down include an outdoor temperature and humidity sensor,
the STULZ CeilAiR water producing components. remote space return air sensor, and supply air sensor for
proper control during economizer operation.
Compressor Sound Jacket
(Air Cooled 0 °F OHS-()-AS and Water/Glycol Cooled Only) Individual discrete analog output signals (0-10 VDC) are
available to allow control of the external outdoor air
The compressor shall be provided with an acoustical sound
intake damper and exhaust relief provisions. Control
jacket (shipped loose). Each sound jacket shall have a snap settings shall be included for both temperature and
closure system for ease of removing and re-installation during humidity properties of the outdoor air. A damper signal
maintenance. The sound jacket shall have a Noise Reduction lockout shall be included if the outdoor air conditions
Coefficient NRC of 85 per ASTM C-423 and a Sound Trans- reaches user adjustable limits.
mission Loss STC of 11 per ASTM E-90. The economizing damper signal shall allow a minimum
Electrical Options output setting for minimum outside air control to meet
ventilation requirements.
Three Phase Power Supply
(Available on OHS-024, 032 and 040-() units.)
Compressor, (belt-drive blower motor and electric heat/reheat
if applicable) shall be three phase in lieu of standard single
phase. All other components (5/10 lb humidifier and direct drive
motor(s)) shall be single phase, with each leg of power supply
balanced as closely as possible.
77
CeilAiR ENGINEERING MANUAL
78
CeilAiR ENGINEERING MANUAL
www.stulz-usa.com
QE-OHS0023B- Feb. 2018 © STULZ Air Technology Systems, Inc. - Specifications subject to change without notice.
79