0% found this document useful (0 votes)
216 views36 pages

Chint Ats

This document provides contact information for CHINT Electrics locations across various regions including Europe, North America, Latin America, West Asia & Africa, and Asia Pacific. It also provides an overview of CHINT Group, noting that it is a large Chinese enterprise operating in the power equipment industry with over 30,000 employees. The document discusses CHINT's certifications, patents, awards, and goals to become a world-famous brand contributing to industrial power through innovation.

Uploaded by

walter
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
216 views36 pages

Chint Ats

This document provides contact information for CHINT Electrics locations across various regions including Europe, North America, Latin America, West Asia & Africa, and Asia Pacific. It also provides an overview of CHINT Group, noting that it is a large Chinese enterprise operating in the power equipment industry with over 30,000 employees. The document discusses CHINT's certifications, patents, awards, and goals to become a world-famous brand contributing to industrial power through innovation.

Uploaded by

walter
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

Europe

Italy Spain
CHINT Electrics Europe S.R.L. CHINT Electrics S.L.
Add: Via A. Pacinotti 28, 30033 Noale (VE) Add: Calle José Echegaray, Num 8.Parque Empresarial Las Rozas
Tel: 0039 335 6265 032 Edificio 3, Planta 1º, Oficina 3.C.P: 28232 Las Rozas (Madrid)
E-mail: [email protected] Tel: 0034 91 636 59 98
Fax: 0034 91 645 95 82
E-mail: [email protected]

Czech Republic Russia


NOARK Electric Europe s.r.o. ООО «Чинт Электрик»
Add:Sezemická 2757/2, 193 00 Prague Адрес: РФ, 109089, г. Москва, ул. Угрешская, д.2, стр.3, оф.17
Tel: +420 226 203 120 Тел.: +7 495 665 6340
Email: [email protected] Факс: +7 495 665 6340
www.noark-electric.eu Email: [email protected]

North America Latin America


United States Brazil
NOARK Electric (USA) Inc. CHINT Electrics South America Ltd
Add: 2188 Pomona Blvd., Pomona, CA 91767 Add: Av. Paulista, 1765 - Edifício Scarpa-Conj.22
Tel: 626-330-7007 Bela Vista –CEP 01311-200-São Paulo- SP
Fax: 626-330-8035 Tel: 0055-11-3266-7654
E-mail: [email protected] E-mail: [email protected][email protected]
na.noark-electric.com

West Asia & Africa Asia Pacific


U.A.E China
CHINT West Asia & Africa FZE Zhejiang CHINT Electrics Co.,Ltd
Add: Office NO. LB182406, P.O.Box:263174, Jebel Ali, Dubai, Add (Shanghai):Bldg.2, No.3255 Sixian Road, Songjiang 201614 P.R.China
United Arab Emirates Tel: 0086-21-67777706
Tel: 00971-48848286 Fax: 0086-21-67777777-88225
Fax: 00971-48848287 E-mail: [email protected][email protected]
E-mail: [email protected]

ZHEJIANG CHINT ELECTRICS CO.,LTD.


Add: No. 1, CHINT Road, CHINT Industrial Zone, North Baixiang, The Next Reliable Choice
CHINT No EN K05

Yueqing, Zhejiang, 325603, P.R.China


Tel: +86-4001177797
Fax: +86-577-62775769 62871811
E-mail: [email protected]
Website: http://next.chint.com/ Jun. 2019

CHINT Electric All Rights Reserved Recycle Paper Printed

Specifications and technical data are subject to change without notice.


Automatic Transfer Switching Equipment
Please contact us to confirm relevant information on ordering
CHINT·Empower the World
Founded in 1984, CHINT Group is a well-known enterprise in Chinese industrial electric
appliance and new energy sectors. With total assets of over 60 billion RMB and more than 30
thousand employees, the company is running business that covers the power equipment
industrial chain including power generation, storage, transmission, transformation,
distribution, and consumption. The company is also operating in the fields of urban rail traffic,
energy equipment manufacturing, new energy storage materials, Energy Internet, investment
& financing platform, and business incubator. The products have been sold to over 130
countries and regions around the world, and have entered main component markets in
Europe, Asia, Middle East, and Africa.

CHINT ranks among top 500 private enterprises in China for a few consecutive years, and the
amount of tax payable can be regarded as a model for the manufacturing enterprises in
Wenzhou. Zhejiang CHINT Electric Appliance Corporation under CHINT Group is a
well-known enterprise in China's low voltage electrical appliance industry, and also A-share
listed company. CHINT Solar has built over a hundred photovoltaic power stations around the
world, it is an influential power station investor and operator in domestic private enterprises.

CHINT has always following the policies of innovation-driven industrial development. Among
all competitors, it passed ISO9001 quality system certification, ISO 14001 environment system
certification, and OHSAS18001 occupational health safety management certification. The
group also holds China Compulsory Certificate (CCC), international CB safety certificate, US UL
certificate, Finland FI certificate, Belgium CEBEC certificate, Netherland KEMA certificate, and
Germany VDE certificate. The group now owns over 1000 domestic and foreign patents, and
has participated in establishment and revision of over 120 industrial standards. Its HV and LV
electric appliances and photovoltaic inverters won Germany Red Dot Award. CHINT led
development of critical manufacturing equipment PECVD, LPCVD, and MOCVD for China's
silicon based thin film photovoltaic cells, which has significantly improved semiconductor
equipment manufacturing level in China.

The group has won a number of awards including China Industrial Award, National Quality
Management Award, China Excellent Private Science & Technology Enterprise, China Top Ten
Machinery Manufacturers with Core Competitiveness, China Top Ten Leading Private
Enterprises with Independent Innovation Capabilities, China Contract-Fulfilling and
Trustworthy Enterprise, National Advanced Private Enterprise for Employment and Social
Security, and China Charity Award.

In the future, CHINT will march towards the targets of creating world famous brands and
contributing to an industrial power. It will focus on building the Energy Internet and becoming
a smart energy developer and operator. The group will make great efforts to implement three
policies: globalization, M&A and integration, and smart manufacturing. Four platforms will be
created, including scientific innovation and industrial incubation platform, online industrial and
civil Internet of Things platform, online & offline supply chain interaction platform, and
investment & financing and payment platform. Four industrial clusters will also be developed,
including smart electrical system solution industrial cluster for smart grid, industrial
automation information cluster for smart cities, clean energy, environment protection, and
energy conservation industrial cluster for smart micro-grid, high-tech material information
technology and high-end equipment industrial cluster for smart manufacturing, and Internet
of Things IT and smart home industrial group for smart business.
Dual protection for key The Next Reliable Choice
electrical power
Newest Automatic Transfer Switching
Automatic Transfer
Equipment series product Switching Equipment
Precise switching, worriless power utilization
Isolated lock, safe and efficient repair and maintenance
It has a disconnected position and can be reliably used for fire control linkage and high
sensitive anti-load; the padlock can prevent false operation in maintenance.

Small size, convenient in installation, intensive and efficient use of space Intelligent control, integration of multifunction
The product adopts the modular design and has a small size; the controller can be installed With optional communication function, various modes of conversion, and settable time and
in integrated or split type. voltage parameters, it can be flexibly and conveniently used.

Strong adaptability in the environment with big temperature difference,


PC grade for dedicated use, stable and reliable product performance reliable operation in extreme environment
Full plastic insulation enclosure and excellent electric properties can ensure reliable power It can be used in the ambient temperature of -25°C~70°C to meet the use requirements in
supply to important loads. different applications.
Contents
NXZ Series Automatic Transfer Switching Equipment
Introduction P-01

Type selection guidance P-02

Functions and characteristics P-03

Connection of body and controller P-08

Overall and installation dimension P-12

NXZ(H)B/NXZ(H)M Series Automatic Transfer Switching Equipment


Introduction P-14

Type selection guidance P-15

Functions and characteristics P-17

Connection of body and controller P-23

Overall and installation dimension P-29


NXZ Series Automatic Transfer Switching Equipment

Introduction
Scope of Application

● NXZ series Automatic Transfer Switching Equipment is applicable to the three-


phase four-wire duplicate supply power grid of AC 50Hz, rated voltage 400V/415V
and below, and rated current up to 630A . It can automatically connect one or
several load circuits from one power source to the other to ensure the normal
power supply for the load circuit.
● This product is applicable to industrial and commercial power use places, high-
rise buildings, and residential houses.

Applicable standards

● Product standard
IEC 60947-1.
IEC 60947-6-1.
● Standards for use in extreme environment
IEC 60068-2-1. (Low Temperature)
IEC 60068-2-2. (High Temperature)
IEC 60068-2-30. (Cyclic Damp Heat)
IEC 60068-2-11. (Salt mist)
● Certification :CB、CE、KEMA

Normal working conditions

+2000m
+40℃
+40℃

-5℃ -5℃
Grade III

● Ambient temperature
-5°C~+40°C; Users can custom-tailor relevant product to be used in the environment of -
25°C~+70°C, and use the product according to the temperature compensation table.
● Sea level elevation
Equal to 2000m or below; if it needs to work above 2000m altitude, it shall be used
according to the table of capacity reduction of different altitudes.
● Atmospheric conditions
The relative humidity shall not exceed 50% when the surrounding air temperature is
+40°C; the relative humidity can be higher when the temperature is lower; the average
monthly maximum relative humidity in the wettest month is 90%, and the average
monthly minimum temperature shall be +20°C. Special measures may be necessary in
cases of occasional condensation due to variations in temperature.
● Pollution degree: class 3
● Installation category
Installation category of the switching equipment of main circuit is category IV.
Installation category of auxiliary circuit is category III.
Installation category of conversion controller is category II.
● Utilization category: AC-33B
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC 61000-4-2) Level 2
Radio-frequency electromagnetic field-radiated electromagnetic field immunity (IEC
61000-4-3) Level 3,
Fast transient bursts (IEC 61000-4-4) Level 3,
Surges (IEC 61000-4-5) Level 3,
Radio-frequency electromagnetic field-conducted immunity (IEC 61000-4-6) Level 3,
Radiation grade (CISPR11) grade B,

01 >> Empower the World


NXZ Series Automatic Transfer Switching Equipment

Model definition and description

NXZ - 125 / 4 A 100A

Product code Frame current code Pole code Controller code Rated current code

NXZ: series 125A 3: 3 pole A: standard type 80A、100A、125A、


automatic transfer 250A 4: 4 pole B: intelligent type 160A、200A、250A、
switching equipment 630A 315A、320A、400A、
(PC grade) 500A、630A

Type selection example:


NXZ-125/4A 125A: To order an Automatic Transfer Switching Equipment of which the frame current is 125A, number of poles is 4P, rated current is
125A, with a standard controller
Note: when the controller is installed in split type, the split wire needs to be ordered separately.

Comparison Table of Frame Current and Rated Current

Rated current (A) 80 100 125 160 200 250 315 320 400 500 630

125

Frame current (A) 250

630

Structural Features of the Automatic Transfer Switching Equipment

2
11

4 10

6 7 8

1 Terminal on the normal supply side 7 Handle

2 Terminal on the alternative supply side 8 Switching-off/switching-on indicator

3 Trade mark 9 QR Code

4 Display and operation module of the controller 10 Manual/electric dial switch

5 Terminal on the load side 11 Controller processing module

6 Nameplate

Empower the World >> 02


NXZ Series Automatic Transfer Switching Equipment

Functions and characteristics


Technical parameters of NXZ (Class PC )

Model NXZ-125 NXZ-250 NXZ-630

Electrical characteristics

Frame current (A) 125 250 630

Rated current (A) 80,100,125 160,200,250 315,320,400,500,630

Rated operational voltage Ue (V) 400/415 50Hz

Rated insulation voltage Ui (V) AC800

Rated impulse withstand voltage Uimp (kV) 8

Utilization category AC-33B

Number of poles 3P/4P

Rated conditional short-circuit current Iq (kA) 100

Rated short-circuit making capacity Icm (kA) 20 30 50

Rated short time withstand current Icw/0.2s (kA) 10 10 25

Contact transfer time (S) 0.6×(1±50%) 1×(1±10%) 1.5×(1±10%)

Operating transfer time (S) 1.2×(1±10%) 2.1×(1±10%) 3.3×(1±10%)

Mechanical endurance (times) 8500 7000 3000

Electrical endurance (times) 1500 1000 1000

Overall dimension

Width x height x depth (mm) 245×130×126 295×175×175 430×272×230

Controller characteristics

Controller model A type (standard), B type (intelligent)

Installation mode Integrated, split

Rated control power supply voltage Us (V) 230/240 50/60Hz

Control voltage range 85%~110%Ue

03 >> Empower the World


NXZ Series Automatic Transfer Switching Equipment

Parameters of controller

Model
A type (standard) B type (intelligent)
Function

Manual/automatic transfer

Main contact positions

Normal position

Alternative position

Off-position

Automatic control

Normal supply of monitoring Phase failure/loss of voltage, undervoltage, overvoltage fault Phase failure/loss of voltage, undervoltage, overvoltage fault

Alternative supply of monitoring Phase failure/loss of voltage, undervoltage, overvoltage fault Phase failure/loss of voltage, undervoltage, overvoltage fault

Automatically transfer and restore operation

Automatically transfer and nonautomatically restore operation

Grid-grid

Grid-generator

Phase failure/loss of voltage transfer

Under voltage transfer

Over voltage transfer

Delay adjustable

Transfer delay 0s~300s adjustable 0s~300s adjustable

Return delay 0s~300s adjustable 0s~300s adjustable

Generator control

Fire control linkage

Indication

Switching-on/switching-off/Off-position indication

Normal/alternative supply indication

Parameter setting indication

Others

Communication function -

Display module LED LCD

Empower the World >> 04


NXZ Series Automatic Transfer Switching Equipment

Functions and characteristics

Operation interface of the display module of controller Figure 1

1 2 3 4 10 12 11

Automatic Manual Setting Generator startup Fire-fighting startup



Ua V
Normal Alternative
Normal

Switching-on Overvoltage

5 Switching-off
Ub S
Undervoltage
Uc Hz
-
Ua V Off-position
Alternative

Switching-on Overvoltage
6 Switching-off
Ub S
Undervoltage Automatic
Setting
Uc Hz Manual

7 9 8

1. Indication of automatic/manual operation mode


2. Setting status indication
3. Indication of the startup signal of generator
4. Indication of start of the fire control linkage function
5. Display area of the status parameters of normal supply: Display the voltage parameters and Transfer delay time of normal supply in working state; display the
setting item parameters in setting state;
6. Display area of the status parameters of alternative supply: Display the voltage parameters and return delay time of alternative supply in working state; display the
setting item parameters in setting state;
7. Setting button (press this button to enter the parameter setting menu of the controller);
8. Automatic/manual transfer mode selector button: used for selection of automatic/manual transfer mode in normal working state; used for save and exit in setting
state;
9. Off-position button: under the manual control mode, any one of the two power supply is normal, press this button to make automatic transfer switching equipment
on off-position; Under setting mode, this button is used to decrease value in parameter setting;
10. Normal supply transfer button: under the manual control mode, the switch is on alternative position, press this button to switch on normal supply; under setting
mode, this button is used for pageup in parameter setting;
11. Alternative supply transfer button: under the manual control mode, the switch is on normal position, press this button to switch on alternative supply; under
setting mode, this button is used for pagedown in parameter setting;
12. + button:Under setting mode, this button is used for increase value in parameter setting.

05 >> Empower the World


NXZ Series Automatic Transfer Switching Equipment

Figure 2
Parameter setting of the display module of controller

Automatic Automatic
Normal

Normal
Switch Ua V Switch Ua V
ing-on ing-on
Alternative

Alternative
Ua V Ua V
Switchi Switchi
ng-off ng-off

Setting Setting

Automatic Automatic
Setting Setting
Manual Setting of under-voltage switching value of normal Manual

V
supply; press to increase; press to decrease V

1 1

Automatic Automatic
Setting Setting
Manual
Setting of over-voltage switching value of normal Manual
Setting of correspondence address; press to
V
supply; press to increase; press to decrease increase; press to decrease
2 2

Automatic Automatic
Setting Setting
Manual
Setting of transfer delay time; press to Manual
Odd-even parity check setting, 0: no parity check;
increase; press to decrease 1: odd parity check; 2: even parity check;
s
3 3

Automatic Setting Automatic Setting


Setting of under-voltage switching value of
Manual Manual Setting of baud rate 1:2400 2:4800 3:9600
alternative supply; press to increase;
V
4:19200 5:38400
press to decrease
4 4

Automatic
Setting
Manual
Setting of over-voltage switching value of
alternative supply; press to increase;
V
press to decrease
5

Automatic
Setting
Manual
Setting of return delay time; press to increase;
press to decrease
s
6

Automatic Setting
Manual
Setting of generator startup delay time; press
to increase; press to decrease
s
7

Automatic
Setting
Manual Setting of generator stop delay time; press
to increase; press to decrease
s
8

Setting of switching mode; press keys to


Automatic Setting change the switching mode. (It's power grid-power
Manual
grid automatically transfer and restore operation
when the final bit is 0; automatically transfer and
s
9 nonautomatically restore operation when it's 1;
and power grid-generator when it's 2.)

Note: The functional parameters of the display module and communication module are set as follows:
Setting of under-voltage switching value: Default to 187V, user-settable 160V~200V;
Setting of over-voltage switching value: Default to 263V, user-settable 240V~290V;
Transfer delay setting:Default to 5s, user-settable 0s~300s;
Return delay setting: Default to 5s, user-settable 0s~300s;
Generator startup delay setting:Default to 5s, user-settable 0s~300s;
Generator stop delay setting: Default to 5s, user-settable 0s~300s;
Switching and power source mode:Default setting: automatically transfer and restore operation (grid - grid), and user can set automatically
transfer and nonautomatically restore operation (grid - grid), automatically transfer and restore operation (grid - power generation)..
Default parameter setting for communication function: address: 1; Baud rate: 9600bps; parity check bit: odd parity; data bit: 8; stop bit: 1
■ Buttons:
Press setup key to enter the setting interface when the controller is working. Press " "" " to page up or down the setting menu. Press
manual/automatic key to exit from the setting menu. Press " "" " to revise the parameters.
Parameter setting of communication function (note: please ask for the communication agreement from our after-service staff)

Empower the World >> 06


NXZ Series Automatic Transfer Switching Equipment

Functions and characteristics


Figure 3
Controller action flow

Normal operation of
normal power supply

Normal operation of Failure of normal power supply


normal power supply T3

Failure of normal power supply


T1 Generator startup

Disconnection of Generator output reaching set value


Normal operation of normal power supply T1
normal power supply

Failure of normal power supply Switch to alternative supply Disconnection of


T1 normal power supply

Connection of Switch to alternative supply


Disconnection of alternative supply
normal power supply
Recovery of normal supply
Connection of
Switch to alternative supply
alternative supply

Connection of Recovery of normal supply


Connection of alternative supply T2
alternative supply
Failure of alternative supply Disconnection of
Recovery of normal supply
T2 alternative supply
T2

Disconnection of Switch to normal supply


Disconnection of alternative supply
alternative supply

Switch to normal supply Connection of


Switch to normal supply normal supply

Connection of Connection of normal supply


Connection of normal supply T4
normal supply
Generator standstill

Automatically transfer and restore operation (power Automatically transfer and nonautomatically restore operation Automatically transfer and restore operation (power
grid-power grid) work flow diagram of controller (power grid-power grid) work flow diagram of controller grid-generator) work flow diagram of controller

I: Normal supply II: Alternative supply


T1: Transfer delay time, normal supply fault, time before disconnection of I;
T2: Return delay time, normal supply recovered, time before disconnection of II;
T3: Generator startup delay time: 0s~300s, adjustable
T4: Generator standstill delay time: 0s~300s, adjustable

Padlocking function

● Padlock apertureΦ5~Φ8 (mm)

Figure 4

① The product is on off-position. Put the yellow ② Pull out the limiting member and lock it.
toggle switch on the manual position.

Communication function

● Modbus protocol; RS485 interface.

07 >> Empower the World


NXZ Series Automatic Transfer Switching Equipment

Mode of connection of the main part and controller

Product incoming mode: upper incoming

Figure 5

Normal supply bus-bar


Alternative supply bus-bar

Wiring error of N pole may cause the


controller to be burnt!

Wire of the
main circuit

Phase sequence of the power


source shall be correct.

Load bus-bar

Installation mode: vertical or horizontal

Product wiring

Figure 6

Normal supply I Alternative supply II Normal supply I Alternative supply II


1 3 5 N 1 3 5 N 1 3 5 N 1 3 5 N

Main
circuit

3P 4P

Empower the World >> 08


NXZ Series Automatic Transfer Switching Equipment

Mode of connection of the main part and controller


Figure 7
Wire connection

≥Φ
c
≥Φ ≤a
c ≤b
≤a
≤b

Unit: mm

a b c

NXZ-125 8 21.5 6

NXZ-250 10 27.5 8

NXZ-630 15 43 12

Figure 8
Split type installation of the display module (cabinet)

1 2 3 4 2 points

ST2.9
2 points
0.8N·m

6 2 nuts 7
5

2 screws

M3

Note: The nuts are mounted with fastening 0.9N·m


screws on the back.

09 >> Empower the World


NXZ Series Automatic Transfer Switching Equipment

Wiring of signal and control terminal

A type controller Figure 9

Indication of Indication of
normal state alternative state

101 102 103 201 202 203 FUSE 5×20 FUSE 5×20

Indication of standby state


101

Indication of normal state


201

Active VC230V output

Active VC230V output


102 202
103 203
Power source signal

Power source signal


alternative null line
Switching signal

Switching signal

301 +
Normal null line

Auxiliary source
501

Generator control

Passive output
DC24V

302 - 502
503
401

Passive input

Fire-fighting control
402

Split-type interface
403

Passive output
404
Active AC230V/0.5A
Users can connect corresponding terminal
based on requirements.

Generation startup control

Auxiliary Fire-fighting
source signal

301 302 401 402 403 404 501 502 503


Passive contact
Passive output
Passive input

DC24V/0.5A

Note: the dotted line is the circuit inside the controller.

B type controller Figure 10

FUSE 5×20 FUSE 5×20


RS485

A+ B- GND
Indication of standby state
Indication of normal state

101 201
Active VC230V output

Active VC230V output

102 202
103 A+ B- GND 203
RS485
Auxiliary source

301 + 501
Generator control

Passive output

DC24V
Note: The signal and controller terminal wiring 302 - 502
of B type controller is same with A type 503
Passive input

401
controller, and B type controller has
Fire-fighting control

402
Split-type interface

communication terminal wiring.


403
Passive output

404

Empower the World >> 10


NXZ Series Automatic Transfer Switching Equipment

Mode of connection of the main part and controller

Typical application Figure 11

Used in power grid-generator mode; it can be unconnected, but the Connected to the upper computer (RS485)
generator startup delay is 0s by default.

Normal null line 101 201 Alternative null line


A+ B- GND
Normal supply 102 202 Alternative supply

Normal switching 103 203 Alternative e switching


Normal supply is normal, To the remote port
of generator
+ 301 501
contact of controller
State of the internal
DC24V
- 302 502

503
To the fire control room 401

402

403

404

Terminals 401 and 402 can only be connected with passive signals; if the fire-fighting Only used in power grid-generator mode; it can be
signal is an active signal, it shall be switched over by a relay, and the normally open connected or unconnected with the generator based
contact of the relay can then be connected to the controller. When product is on on requirement. When the normal supply is failure,
off-positionl, terminals 403 and 404 will be connected . After the fire-fighting signal 502 and 503 will be connected.
is cancelled, press any key of the controller, and it will return to the normal operation
state.

11 >> Empower the World


NXZ Series Automatic Transfer Switching Equipment

Overall and installation dimension


Figure 12
Product overall and installation dimension

H(max)

A(max) H3
H2
A1 H1
F
E
B(max)

常用
+ 备用

-
D
B1

双分
自动
设置
手动

2×Φd
L
H4

Unit: mm

Product code A A1 B B1 D E F G L H H1 H2 H3 H4 d

NXZ-125 245 229.5 130 220 113 21.5 30 4.5 5.5 126 21 71 107.5 21 4.5

NXZ-250 295 275 175 304 152 27.5 35 6 8 175 29 99 146 29 6

NXZ-630 430 400 272 461 240 43 58 9 13 230 41 131 192 41 9

Hole size of the product installation plate Figure 13

4XΦd
M

Unit: mm

Product code C M d

NXZ-125 229.5 113 4.5

NXZ-250 275 152 6

NXZ-630 400 240 9

Empower the World >> 12


NXZ Series Automatic Transfer Switching Equipment

Overall and installation dimension


Figure 14
Overall dimension of split type module (unit: mm)

29 8

54

109

127

Figure 15
Size of the installation cabinet of split type module (unit: mm)

111~112

2XΦ3.5
55~56

127

13 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

Introduction

Scope of application

● NXZ(H)B/NXZ(H)M Series Automatic Transfer Switching Equipment is applicable to three-


phase four-wire duplicate supply grid of AC 50/60Hz, rated voltage 400V/415V and
below, rated current 800A, and can switch one or several load circuits from one power
source to the other to ensure the normal power supply of the load circuit.
● This product is applicable to industrial and commercial power use places, high-rise
buildings, and residential houses.

Applicable standards

● Product standard
IEC 60947-1.
IEC 60947-6-1.
● Standards for use in extreme environment
IEC 60068-2-1. (Low Temperature)
IEC 60068-2-2. (High Temperature)
IEC 60068-2-30. (Cyclic Damp Heat)
IEC 60068-2-11. (Salt mist)

Normal working conditions

+2000m
+40℃
+40℃

-5℃ -5℃
Grade III

● Ambient temperature
-5°C~+40°C; Users can custom-tailor relevant product to be used in the environment of -
25°C~+70°C, and use the product according to the temperature compensation table.
● Sea level elevation
Equal to 2000m or below; if it needs to work above 2000m altitude, it shall be used
according to the table of capacity reduction of different altitudes.
● Atmospheric conditions
The relative humidity shall not exceed 50% when the surrounding air temperature is
+40°C; the relative humidity can be higher when the temperature is lower; the average
monthly maximum relative humidity in the wettest month is 90%, and the average
monthly minimum temperature shall be +20°C. Special measures may be necessary in
cases of occasional condensation due to variations in temperature.
● Pollution degree: class 3

Salt

Dual tripping

● Installation category
Installation category of the switching equipment of main circuit is category IV.
Installation category of auxiliary circuit is category III.
Installation category of conversion controller is category II.
● Utilization category:
NXZB: AC-33iB
NXZ (H) B: AC-33B
NXZ (H) M: AC-33B
● Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC 61000-4-2) Level 2
Radio-frequency electromagnetic field-radiated electromagnetic field immunity (IEC
61000-4-3) Level 3,
Fast transient bursts (IEC 61000-4-4) Level 3,
Surges (IEC 61000-4-5) Level 3,
Radio-frequency electromagnetic field-conducted immunity (IEC 61000-4-6) Level 3,
Radiation grade (CISPR11) grade B,

Empower the World >> 14


NXZ(H)B、NXZ(H)M Series ATS

Model definition and description

NXZB-63 (Class CB )

NXZB - 63 H / 4 A T C 63

Frame Breaking Controller Tripping Rated


Product code Pole Function code
current code capacity code code type code current code

NXZB: series 63A S:6kA 3: 3 poles A: standard Empty: no C: C type 10A、16A、


automatic H:10kA 4: 4 poles type communication D: D type 20A、25A、
transfer C: intelligent function 32A、40A、
switching type T: 50A、63A
equipment communication
function

Type selection example:


NXZB-63H/4C C63:To order a class CB automatic transfer switching equipment, the frame current is 63A, number of poles is 4P, the breaking
capability is 10kA, rated current is 63A, the tripping type is C type, with an intelligent controller (C type).

NXZM (Class CB)

NXZM - 250 H / 4 A 2 160A

Frame Breaking Controller Rated


Product code Pole Function code
current code capacity code code current code

NXZM: 63A、125A、 S: standard 3: 3 poles A: standard Empty: power 10A~800A


automatic 160A、250A、 H: higher 4: 4 poles type distribution
transfer 320A、400A、 B: intelligent protection
switching 630A、800A type 2: generator
equipment protection

Type selection example:


NXZM-250H/4A 160A:To order a class CB automatic transfer switching equipment, the frame current is 250A, number of poles is 4P, H breaking
capability, rated current is 160A, with a standard controller (A type) and generator protection.

Comparison Table of Frame Current and Rated Current

Rated current (A) 10 16 25 32 40 50 63 80 100 125 160 180 200 225 250 315 320 350 400 500 630 700 800

63

125

160

Frame current 250


(A)
320

400

630

800

15 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

NXZHB-63 (Class PC)

NXZHB - 63 / 4 A T 63A

Frame Controller Rated


Product code Pole Function code
current code code current code

NXZHB: 63A 3: 3 poles A: standard Empty: no 16A、32A、63A


automatic 4: 4 poles type communication
transfer C: intelligent function
switching type T:
equipment communication
function

Type selection example:


NXZHB-63/4A 63A:To order a PC grade automatic transfer switching equipment, the frame current is 63A, number of poles is 4P, rated current is
63A, with a standard controller (A type).

NXZHM (Class PC )

NXZHM - 250 / 4 A 160A

Frame Controller Rated


Product code Pole
current code code current code

NXZHM: 63A、125A、 3: 3 poles A: standard 10A~800A


automatic 160A、250A、 4: 4 poles type
transfer 320A、400A、 B: intelligent
switching 630A、800A type
equipment

Type selection example:


NXZHM-250/4A 250A:To order a PC grade automatic transfer switching equipment, the frame current is 250A, number of poles is 4P, rated current
is 250A, with a standard controller (A type)

Comparison Table of Frame Current and Rated Current

Rated current (A) 10 16 25 32 40 50 63 80 100 125 160 180 200 225 250 315 320 350 400 500 630 700 800

63

125

160

Frame current 250


(A)
320

400

630

800

Empower the World >> 16


NXZ(H)B、NXZ(H)M Series ATS

Functions and characteristics

Technical parameters of NXZB-63 (class CB )

Model NXZB-63S NXZB-63H

Electrical characteristics    

Execution body NXB-63 NXB-63H

Frame current (A) 63 63

Rated current (A) 10,16,20,25,32,40,50,63 10,16,20,25,32,40,50,63

Rated operational voltage Ue (V) 400 400

Rated insulation voltage Ui (V) 500 500

Rated impulse voltage Uimp (kV) 4 4

Utilization category AC-33iB AC-33iB

Number of poles 3P、4P 3P、4P

Rated short-circuit making capacity Icm (kA) 9 17

Rated short-circuit breaking capacity Icn (kA) 6 10

Tripping curve type C、D C、D

Mechanical endurance (times) 10000 10000

Electrical endurance (times) 3000 3000

Controller characteristics

Controller model A type (standard), C type (intelligent)

Operating transfer time (s) 1.4×(1±10%)

Controller installation mode Built in

Rated control power source voltage Us(V) 230 50Hz

Control voltage range 85%Ue~110%Ue

Technical parameters of NXZM (class CB )

Model NXZM-63 NXZM-125 NXZM-160 NXZM-250 NXZM-320 NXZM-400 NXZM-630 NXZM-800

Electrical characteristics          
Execution body NXM-63 NXM-125 NXM-160 NXM-250 NXM-320 NXM-400 NXM-630 NXM-800

Frame current (A) 63 125 160 250 320 400 630 800

10,16,25, 63,80,100, 160,180,200, 160,180,200, 250,315, 400,500, 630,700,


Rated current (A) 125,160
32,40,50,63 125 225,250 225,250,320 350,400 630 800

Rated operational voltage Ue (V) 400/415 50Hz

Rated insulation voltage Ui (V) AC800 AC800 AC800 AC1000 AC1000 AC1000 AC1000 AC1000

Rated impulse voltage Uimp (kV) 8 12


Use type AC-33B

Number of poles 3P、4P

Rated short-circuit making S:52.5 S:52.5 S:73.5 S:73.5 S:73.5 S:105 S:105 S:105
capacity Icm (kA) H:105 H:105 H:105 H:105 H:105 H:143 H:143 H:165

Rated short-circuit breaking S:25 S:25 S:35 S:35 S:35 S:50 S:50 S:50
capacity Icn (kA)
H:50 H:50 H:50 H:50 H:50 H:65 H:65 H:75

Mechanical endurance (times) 10000 10000 8000 6000 6000 4000 4000 4000

Electrical endurance (times) 2000 2000 2000 2000 2000 1500 1500 1000

Controller characteristics

Controller model A type (standard), B type (intelligent)

Operating transfer (s) 2.8 ×(1±10%) 2.8 ×(1±10%) 3.3 ×(1±10%) 3.3 ×(1±10%) 3.3 ×(1±10%) 3.5 ×(1±10%) 3.5 ×(1±10%) 4 ×(1±10%)

Installation mode Integrated, split

Rated control power source


230/240 50Hz
voltage Ue(V)

Control voltage range 85%~110%Ue

17 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

Technical parameters of NXZHB-63 (class PC)

Model NXZHB-63

Electrical characteristics  

Frame current (A) 63

Rated current (A) 16,32,63A

Rated operational voltage Ue (V) 400

Rated insulation voltage Ui (V) 500

Rated impulse voltage Uimp (kV) 4

Utilization category AC-33B

Number of poles 3P、4P

Rated conditional short-circuit current Iq (kA) 100

Mechanical endurance (times) 10000

Electrical endurance (times) 1500

Controller characteristics  

Controller model A type (standard), C type (intelligent)

Operating transfer (s) 1.4×(1±10%)

Controller installation mode Built in

Rated control power source voltage Ue(V) 230 50Hz

Control voltage range 85%Ue~110%Ue

Technical parameters of NXZHM (class PC)

Model NXZHM-63 NXZHM-125 NXZHM-160 NXZHM-250 NXZHM-320 NXZHM-400 NXZHM-630 NXZHM-800

Electrical characteristics

Execution body NXHM-63 NXHM-125 NXHM-160 NXHM-250 NXHM-320 NXHM-400 NXHM-630 NXHM-800

Frame current (A) 63 125 160 250 320 400 630 800

10,16,25,32, 63,80, 160,180,200, 160,180,200, 250,315,350, 400,500, 630,700,


Rated current (A) 125,160
40,50,63 100,125 225,250 225,250,320 400 630 800

Rated operational voltage Ue (V) 400/415 50Hz z


Rated insulation voltage Ui (V) AC800 AC800 AC800 AC1000 AC1000 AC1000 AC1000 AC1000

Rated impulse voltage Uimp (kV) 8 12


Utilization category AC-33B

Number of poles 3P、4P 3P、4P 3P、4P 3P、4P 3P、4P 3P、4P 3P、4P 3P、4P

Rated conditional short-circuit


100 100 100 100 100 100 100 100
current Iq (kA)

Mechanical endurance (times) 10000 10000 8000 6000 6000 4000 4000 4000

Electrical endurance (times) 2000 2000 2000 2000 2000 1500 1500 1000

Controller characteristics

Controller model A type (standard), B type (intelligent)

Operating transfer (s) 2.8 ×(1±10%) 2.8 ×(1±10%) 3.3 ×(1±10%) 3.3 ×(1±10%) 3.3 ×(1±10%) 3.5 ×(1±10%) 3.5 ×(1±10%) 4 ×(1±10%)

Installation mode Integrated, split

Rated control power source


230/240 50Hz
voltage Us(V)

Control voltage range 85%~110%Ue

Empower the World >> 18


NXZ(H)B、NXZ(H)M Series ATS

Functions and characteristics

Functional parameters of NXZ (H) B controller

Model
A type (standard) C型(智能型)
Function

Manual/automatic transfer

Main contact positions

Normal position

Alternative position

Off-position

Automatic control

Normal supply of monitoring Phase failure/loss of voltage, undervoltage, overvoltage fault Phase failure/loss of voltage, undervoltage, overvoltage fault

Alternative supply of monitoring Phase failure/loss of voltage, undervoltage, overvoltage fault Phase failure/loss of voltage, undervoltage, overvoltage fault

Automatically transfer and restore operation

Grid-grid

Phase failure/loss of voltage transfer

Undervoltage transfer

Delay adjustable

Transfer delay 0s~30s adjustable 0s~30s adjustable

Return delay 0s~30s adjustable 0s~30s adjustable

Generator control Optional

Fire control linkage

Fire control feedback

Indication

Switching-on/switching-off/dual tripping indication

Normal/alternative supply indication

Parameter setting indication

Others

Communication function Optional Optional

Table of main functional parameters of NXZ (H) M controller

Model
A type (standard) B type (intelligent)
Function

Manual/automatic transfer

Main contact positions

Normal position

Alternative position

Off-position

Automatic control

Normal supply of monitoring Phase failure/loss of voltage, undervoltage, overvoltage fault Phase failure/loss of voltage, undervoltage, overvoltage fault

Alternative supply of monitoring Phase failure/loss of voltage, undervoltage, overvoltage fault Phase failure/loss of voltage, undervoltage, overvoltage fault

Automatically transfer and restore operation

Automatically transfer and nonautomatically restore operation

Grid-grid

Grid-generator

Phase failure/loss of voltage transfer

Undervoltage transfer

Overvoltage transfer

Delay adjustable

Transfer delay 0s~180s adjustable 0s~180s adjustable

Return delay 0s~180s adjustable 0s~180s adjustable

Generator control

Fire control linkage

Fire control feedback

Indication

Switching-on/switching-off/off-position

Normal/alternative supply indication

Parameter setting indication

Fault tripping indication

Others

Communication function Optional Optional

Display module LED LED

19 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

Functional description of NXZ (H) B

Figure 1

Ⅰ Ⅱ 1 Normal supply (red)


1 3 2 Normal switching-on (green)
3 Alternative supply (red)
ON ON 4 Alternative switching-on (green)
2 4 5 Transfer delay time setting (normal to alternative)
0 30 0 30
T1(S) T2(S) 6 Return time delay setting (alternative to normal)
5 6
7 Automatic/manual switching

Automatic Manual
7

Indicator light information

Product status ① ② ③ ④
Normal supply normal Normal on

Normal circuit breaker switched on Normal on

Alternative supply normal Normal on

Alternative breaker switched on Normal on

Transfer delay Flash

Return delay Flash

Normal circuit breaker tripped Flash Flash

Alternative breaker tripped Flash Flash

Product transfer fault Flash Flash

Fire control linkage Flash Flash

Lock system

● During line repair or fault-based maintenance, put the product on off-position, and then pull out the locking system of the handle, then lock it.
The lock hole diameter is Φ5.5.

Figure 2

Empower the World >> 20


NXZ(H)B、NXZ(H)M Series ATS

Functions and characteristics

Functional description of NXZ (H) M

Figure 3
Operation interface of the display module of controller

1 2 20 21 22

Automatic Manual Automatically Nonautomatically Generator


restore restore 4
Switching-on V
Normal

5 S 9
Switching-off
Hz
3
Fault Setting A B C 10
6
Alternative

Switching-on V

7 S 11
Switching-off
Hz

Fire-fighting startup Communication Generator startup


12

8 13

23

19
Confirm Query

14 return
Setting
18

Normal Alternative Off-position

15 17

16

1 Indication of automatic operation mode;


2 Indication of manual operation mode;
3 Fault indication: This light will be on when switch fault or breaker tripping caused by load short circuit (class PC controller doesn’t have such
function);
4 The display area of voltage parameters of normal supply shows the voltage parameters of normal supply and the transfer delay time during working,
and shows the symbol in setting mode;
5 Indication of switching-on, switching-off for the normal supply; when normal supply is failure, indicator light of "normal" flash;
6 Setting status indication;
7 Indication of switching-on, switching-off for the alternative supply; when alternative is failure, indicator light of "alternative" flash;
8 Indication of startup of fire control linkage;
9 Voltage, time, and frequency unit for the normal supply ;
10 A, B. C phase;
11 Voltage, time, and frequency unit for the alternative supply;
12 The display area of voltage parameters of alternative supply shows the voltage parameters of alternative supply and the transfer delay time during
working, and shows the symbol in setting mode;
13 Indication of generator startup;
14 Confirm/return button: It means saving and exit in setting mode; It means returning to the normal working state in fire control linkage mode;
15 Normal supply switching button: On the manual control mode, if the normal supply is normal, press this button to compulsorily switch to normal
supply; On setting mode, this button is used for paging up;
16 Alternative supply switching button: On the manual control mode, if the alternative supply is normal, press this button to compulsorily switch to
alternative supply; On setting mode, this button is used for paging down;
17 Trip button: On the manual control mode, if any one of the two power sources is normal, press this button to switch to the switching-off position; On
setting mode, this button is used to decrease value in parameter setting;
18 Fault query button: when there is fault indication on the display screen, press this button to query the fault code ; On setting state, this button is
used to increase value in parameter setting;
19 Setting button: press this button to enter the parameter setting menu of the controller;
20 Indication of automatically transfer and restore operation mode;
21 Indication of automatically transfer and nonautomatically restore operation mode;
22 Indication of generator (automatically transfer and restore operation);
23 Indication of communication state.

21 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

Figure 4
Parameter setting of the display module of controller
Normal

Automatic
V
Switching-on

220
Alternative

A
V
220
Switching-off

Setting

Confirm

Return
A-1 Setting of under-voltage switching value of normal
Setting
V supply; press  to increase; press  to decrease.
1 187
Normal Alternative

Confirm

Return
A-2 Setting of over-voltage switching value of normal
Setting
V supply; press to increase; press  to decrease.
2
263
Normal Alternative

Confirm

Return
A-3 Setting of transfer delay time; press  to increase;
Setting
press to decrease.
3
005 s

Normal Alternative

Confirm

Return
A-4 Setting of under-voltage switching value of alternative
Setting
V supply; press  to increase; press to decrease.
4
187
Normal Alternative

Confirm

Return
A-5 Setting of over-voltage switching value of alternative
Setting
V supply; press  to increase; press to decrease.
5
263
Normal Alternative

Confirm

Return
A-6 Setting of return delay time; press  to increase;
Setting
press  to decrease.
6
005 s

Normal Alternative

Confirm

Return
A-7 Setting of generator startup delay time; press  to
Setting
increase; press  to decrease.
7
005 s

Normal Alternative

Confirm

Return
A-8 Setting of generator standstill delay time; press  to
Setting
increase; press  to decrease.
8
005 s

Normal Alternative

Confirm
Setting of switching mode; press   keys to change the switching mode.
Return
A-9 It's power grid-power grid automatically transfer and restore operation
Setting when it's 000, automatically transfer and nonautomatically restore operati

9
000 s on when it's 001, and power grid-generator when it's 002.

Normal Alternative

Confirm

Return
A-A Used for setting Modbus correspondence address,
Setting
range of setting 1-247;
10
3
Normal Alternative

Confirm

Return
A-C Used for setting Modbus communication baud rate,
Setting 0: 9.6 kbps; 1:19.2 kbps
11
0
Normal Alternative

Confirm

Return
A-E
Setting Remote locking: (ON/OFF), OFF by default

12
0

Operation interface for parameter setting of controller

1 Setting of under-voltage switching value: Default to 187V ;user-settable 160V-200V;


2 Setting of over-voltage switching value: Default to 263V ; user-settable 240V-290V;
3 Transfer delay setting: Default to 5s; user-settable 0s-180s;
4 Return delay setting: Default to 5s; user-settable 0s-180s;
5 Generator startup delay setting: Default to 5s; user-settable 0s-180s;
6 Generator standstill delay setting: Default to 5s; user-settable 0s-180s;
■ Note of buttons:
Pressure setup key when the controller is working, and the screen shows the parameter setting menu. Press “ ” “ ” in the setting menu to turn up or down.
Press "Confirm/return" key to exit from menu setting; press “ ” “ ” to revise parameter.

Empower the World >> 22


NXZ(H)B、NXZ(H)M Series ATS

Mode of connection of the main part and controller

Mode of connection of NXZB and NXZHB

● Product wiring
The incoming line is connected from the top of product; the outgoing line is connected from the bottom of product; the product can be installed
vertically or horizontally.
Wiring as follows. The power phase sequence shall be correct; in particular, N pole shall not be wrongly connected.
The connecting wire (electric cable) adopts single core Polyvinyl chloride (PVC) insulated conductor or copper bar of the equivalent effect. Advice
as follows:

Cross-sectional area of copper conductor

Safe ampacity (A) 20 25 32 40 50 63

Cross-sectional area of copper conductor (mm2) 2.5 4 6 10 10 16

Figure 5
3P product
Normal supply Alternative supply
1 3 5 1 3 5
Controller port

T1(S) T2(S)

Normal null line Alternative null line


(101 and 102, 201 and 202 have been
short connected internally, and need
to be connected with any wire externally.)

2.5N·m

Figure 6
4P product

Normal supply Alternative supply

1 3 5 N 1 3 5 N

Ⅰ Ⅱ

T1(S) T2(S)

2 4 6 N 2 4 6 N

2.5N·m

23 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

Signal and control terminal wiring

Figure 7

Null line of normal supply Null line of alternative supply


101 201
(101 and 102 are short connected internally) (201 and 202 are short connected internally)
102 202

Normal null line Normal null line


301 401
Normal supply Normal supply
302 402
Switching-on position Switching-on position
303 403

Generator control outputs passive signal. 501 601


Fire-fighting input shall be
Normal supply normal, 501 and 503 connected passive signal.
502 602
Normal supply fault, 502 and 503 connected
503 603
A type controller doesn’t have this module. 603/604 feedback function is optional.
604
GND 701

A+ 702
Communication function optional

(RS485) B- 703

Empower the World >> 24


NXZ(H)B、NXZ(H)M Series ATS

Mode of connection of the main part and controller

Mode of connection of NXZM and NXZHM

● Product incoming line mode: incoming line at the top of product; outgoing line at the bottom of product
● Installation mode: vertically or horizontally

Figure 8

Normal supply Alternative supply


bus-bar bus-bar

Load bus-bar

Product wiring

Figure 9
3P

Normal supply Alternative supply


1 3 5 1 3 5
Alternative supply N
Normal supply N

Directly connected to the external


201 202 terminal of the controller
It is forbidden to connect between
null line terminal 201 and 202 terminal

Figure 10
4P

Normal supply Alternative supply


1 3 5 N 1 3 5 N

Wiring error of N pole may cause the controller


to be burnt
Voltage sample line

Power bus

Phase sequence of the power source shall be correct.

25 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

Wire connection

Figure 11

≥Φc

≤a
≥Φc ≤b

≤a
≤b

Unit: mm

Product code a b c

6.5 14 5.5(≤63A)
MXZ(H)M-63、125
7.5 17 6.5(>63A)

MXZ(H)M-160 7.5 14.5 8.5

MXZ(H)M-250、320 10 23 8.5

MXZ(H)M-400、630 10.5 30.5 10.5

MXZ(H)M-800 15 43 14

Empower the World >> 26


NXZ(H)B、NXZ(H)M Series ATS

Mode of connection of the main part and controller


Figure 12
Installation of interphase barrier

Note: The interphase barrier for NXZ(H)M-160 is preassembled before deliver y.

Figure 13
Split type installation of the display module (cabinet door)

1 2 3

27 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

Signal and control terminal wiring

Figure 14

Only used in power grid-generator It is prohibited to connect between two pairs


mode; If there is no connection, the of terminals; otherwise, the controller will be burnt.
generator startup delay automatically
restores to 0s. Note: The output is
active AC230V/0.5A.

101 102 201 202 301 302 303 401 402 403
Trip signal

Switching signal

Trip signal

Switching signal
common port

common port
N1 N2
DC24V/0.5A
Normal
Spare

Auxiliary External neutral


power input wire to 3P

Communication interface Generator control Fire-fighting control (passive)


(RS485)
State of contact inside the controller Control input
when the normal
G A+ B-
supply is normal Feedback output
Common
port

701 702 703 601 602 603 501 502 503 504
connect to generator

Only used in power grid-generator


Terminals 501 and 502 can only be connected with passive
mode; connected with the generator
The remote port

signals; passive signals can be input after switchover by a relay.


based on required; when the normal
After fire-fighting is on off-position, terminals 503 and 504 will
supply is failure, 601 and 603 will be
be connected.
connected through.
For the automatic transfer switch under automatic operation
state, after the fire-fighting signals are cancelled, the toggle
switch shall be switched to "manual"; then press
"confirm/return" to return to the normal state;
For the automatic transfer switch under the manual operation
state, press "confirm/return" to return to the normal state.

Note: Type A controller has no fire-fighting feedback and generator control function.

Empower the World >> 28


NXZ(H)B、NXZ(H)M Series ATS

Overall and installation dimension

Overall and installation dimension of NXZB and NXZHB

Overall and installation dimension Figure 15


(the dimension of 3P product and 4P is the same)

248max 130max
229±0.36 112.5

Ⅰ Ⅱ

ON ON
0 30 0 30
T1(S) T2(S)

自动 手动
113±0.21
125max

R 5.5
5 16

Overall and installation dimension of NXZM and NXZHM

Figure 16
Overall and installation dimension

A2 Hmax
A1 H1
C
F G H2

101 102 201 202 301 302 303 401 402 403
请 沿 此 揭 开

- 24V + N1 N2
脱扣
备用 合闸 常用 脱扣 合闸
辅助电源输入 3P 外接 N线 公共端 信号 信号 公共端 信号 信号

通讯接口 发电机控制 消防控制(无源)


G A+ B- 控制输入 反馈输出

701 702 703 601 602 603 501 502 503 504
D
B1

B2
B

E N

Take 4p product as the example Unit: mm

A1 A2 E F H H1 H2
Product code B B1 B2 C D G M N
4P 3P
4P 3P 4P 3P S H S H S H

NXZ(H)M-63、125 300 312 240 230 223 267 220 12.5 0 51.5 64 25 178 190 151 161 47 56 9 17

NXZ(H)M-160 340 345 250 245 240 307 230 15 0 52 67 30 167 195 152 180 50 9 17

NXZ(H)M-250、320 390 393 250 367 240 357 230 17.5 0 60 77.5 35 181 216 155 190 49 50 9 17

NXZ(H)M-400、630 535 540 334 464 342 475 304 24 0 84 108 44 234 198 66 11 26

NXZ(H)M-800 660 663 344 477 344 600 314 29 0 106 135 58 228 203 68 11 26

Note: the dimension H is only for reference.

29 >> Empower the World


NXZ(H)B、NXZ(H)M Series ATS

Figure 17
Overall dimension of split type module (unit: mm)

64 17 4.5 60
105

101

Empower the World >> 30