Danfoss 2 Ps

KP pressure switches are used in refrigeration and air conditioning systems to protect against low suction or high discharge pressures. They can be used to start and stop compressors and fans. KP switches have a single-pole double-throw contact and are available in IP30, IP44, and IP55 enclosures. They are designed to be reliable, compact, and resistant to vibration and shock.

Uploaded by

Roshan Jaiswal
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views

Danfoss 2 Ps

KP pressure switches are used in refrigeration and air conditioning systems to protect against low suction or high discharge pressures. They can be used to start and stop compressors and fans. KP switches have a single-pole double-throw contact and are available in IP30, IP44, and IP55 enclosures. They are designed to be reliable, compact, and resistant to vibration and shock.

Uploaded by

Roshan Jaiswal
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Data Sheet

Pressure switch
Type KP

KP pressure switchs are for use in refrigeration


and air conditioning systems to give protection
against excessively low suction pressure or
excessively high discharge pressure.

KP pressure switches are also used for starting


and stopping refrigeration compressors and
fans on air-cooled condensers.

A KP pressure switch can be connected directly


to a single-phase AC motor of up to approx. 2
kW or installed in the control circuit of DC
motors and large AC motors.

KP pressure switches are fitted with a single-


pole double-throw (SPDT) switch. The position
of the switch is determined by the pressure
switch setting and the pressure at the
connector. KP pressure switches are available in
IP30, IP44 and IP55 enclosures.

Features:
• Ultra-short bounce time thanks to snap-
action function (reduces wear to a minimum
and increases reliability)
• Manual trip function (electrical contact
function can be tested without the use of
tools)
• Types KP6, KP7, KP17 and KP47 with fail-safe
double bellows element
• Vibration and shock resistant
• Compact design
• Fully welded bellows element
• High reliability both electrically
and mechanically

AI213186439478en-001203
Pressure switch, Type KP

Product specification

Technical data
Table 1: Technical data
Features Values
Ambient temperature -40 – 65 °C (80 °C for max. 2 hours)
Ambient temperature (PED approved units) -25 – 65 °C (80 °C for max. 2 hours)
Media temperature (1) -50 – 100 °C
LP: PS / MWP = 17 bar
KP 4, KP 47 (LP side): PS / MWP = 21.5 bar
Max. working pressure
KP17, KP47 and KP7BS (HP side):PS / Mwp=32 bar
KP 6: PS / MWP = 46.5 bar
LP: Pe = 20 bar
KP 4, KP 47 (LP side): Pe = 24 bar
Max. test pressure
HP: Pe = 35 bar
KP 6: Pe = 46.5 bar
AC1 =16 A, 400 V
Alternating current AC3 = 16 A, 400 V
Contact load
AC15 = 10 A, 400 V
Direct current DC13 = 12 W, 220 V control current
solid / stranded 0.75 – 2.5 mm2
Wire dimensions flexible, without ferrules 0.7 – 2.5 mm2
flexible, with ferrules 0.5 – 1.5 mm2
Tightening torque max. 2 Nm
Rated impulse voltage 4 kV
Pollution degree 3
Short circuit protection, fuse 16 A
Insulation 400 V
Enclosure IP30 / IP44 / IP55

(1)
The media temperature can be out of ambient temperature range under necessary condition that temperature inside KP must be kept in
ambient temperature range.

Cable connection
The cable entry can be used for 6 – 14 mm dia. cables. A Pg 13.5 screwed cable entry can also be used for 6 – 14 mm
cable.With 8 – 16 mm cable a standard Pg 16 screwed cable entry can be used.

Enclosure
IP30 to EN 60529 / IEC 60529
Enclosure IP30 is obtained when the units without top cover are mounted on a flat surface or bracket. The bracket
must be fixed to the unit so that all unused holes are covered.

IP44 to EN 60529 / IEC 60529


Enclosure IP44 is obtained when the units with top cover are mounted on a flat surface or bracket. The bracket must
be fixed to the unit so that all unused holes are covered.

KP pressure switches with auto reset are supplied with top cover. For KP pressure switches with manual reset, the
top cover must be separately ordered (code no. 060-109766 for single pressure switches and code no.
060-109866 for dual pressure switches).

IP55 to EN 60529 / IEC 60529


IP55 is obtained when the KP pressure switches are mounted in an IP55 enclosure, (code no. 060-033066 for single
pressure switches and code no. 060-035066 for dual pressure switches). IP55 enclosure has to be ordered
separately.

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 2


Pressure switch, Type KP

Contact systems
Table 2: Low and high pressure
Low pressure (LP) High pressure (HP)

Table 3: Dual pressure


Dual pressure (LP/HP) Dual pressure (LP/HP) Dual pressure (HP/HP)

Materials in contact with the medium


Table 4: Materials in contact with the medium
Type Material
Tinbronze, no. CW452K, EN 1652
KP 1, KP 2, KP 4, KP 5, KP 6, KP 7, KP 15, KP 17 and KP 47
Nickel plated free cutting steel, no. 1.0737 / 1.0718, EN 10277
Stainless steel 18/8, no. 1.4306, EN 10088-2
Free cutting steel, no. 1.0737, EN 10277
Cold forming steel, no. 1.0338, EN 10139
KP 1A, KP 5A, KP 6A, KP 7A and KP 15A only Steel, no 1.0308, EN 10305
Free cutting steel, no. 1.0715, EN10277
Free cutting steel, no. 1.0718, EN 10277
Aluminium, no. AW-3005, EN 573

Terminology
Reset
1. Manual (Min. / Max.) reset:
Units with manual reset can only be reset during operation by activation of the reset button.
2. Automatic reset:
After operational stop, these units reset automatically.
3. Convertible reset:
Units with optional reset can be activated by automatic and/or manual reset

Permissible working pressure


The permissible working pressure is determined by the pressure that can be safely allowed in the refrigerating
system or any of the units within it.

Test pressure
The test pressure is the pressure used in strength tests and/or leakage tests on refrigerating systems or individual
parts in systems. The test pressure is designated Pe.

“Snap function”
A certain contact force is maintained until irrevocable “snap” is initiated. The time during which the contact force
approaches zero is thus limited to a very few milliseconds. Therefore contact bounce cannot occur as a result of, for
example, slight vibrations, before the cut-out point. Contact systems with “Snap function” will change over even
when micro-welds are created between the contacts during cut-in. A very high force is created during cut-out to
separate the contacts. This force immediately shears off all the welds. Thus the cut-out point of the unit remains very
accurate and completely independent of the magnitude of the current load.

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 3


Pressure switch, Type KP

Setting
Pressure switches with automatic reset – LP: Set the LP start pressure on the "CUT-IN" scale (range scale). One
rotation of the low pressure spindle ∼ 0.7 bar.Set the LP differential on the "DIFF" scale. One rotation of the
differential spindle ∼ 0.15 bar.The LP stop pressure is the LP start pressure minus the differential.

 NOTE:
The LP stop pressure must be above absolute vacuum (Pe = -1 bar)!

If with low stop pressure the refrigeration compressor will not stop, check to ensure that the differential value has
not been set too high!

Pressure switches with automatic reset – HP: Set the HP pressure on the “CUT-OUT” scale. One rotation of the HP
spindle ∼ 2.3 bar. Set the HP differential on the “DIFF” scale. One rotation of the differential spindle ∼ 0.3 bar. The
HP start pressure is the HP stop pressure minus the differential.

Start and stop pressures for both the LP and HP sides of the system should always be checked with an accurate
pressure gauge.

Pressure switches with manual reset Set the stop pressure on “CUT-OUT” scale (range scale).

Low pressure switches can be manually reset when the pressure is equal to the stop pressure plus the differential.
High pressure switches can be manually reset when the pressure is equal to the stop pressure minus the differential.

Design
Table 5: Design
Pressure switch, type KP KP 1, KP 2, KP 5

KP 15 Capillary tube for KP 1A, KP 5A and KP 15A


MK

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 4


Pressure switch, Type KP

1. Low pressure setting spindle, (LP) 11. HP connection


2. Differential setting spindle 12. Switch
3. Main arm 13. Terminals
5. High pressure setting spindle, (HP) 14. Earth terminal
7. Main spring 15. Cable entry
8. Differential spring 16. Tumbler
9. Bellows 18. Locking plate
10. LP connection 30. Reset button

The switch in the KP has a snap-action function where the bellows move only when the cut-in or cut-out value is
reached.

The bellows are connected to the low or high pressure side of the system through connection (10) or (11).

The design of the KP gives the following advantages:


• high contact load
• ultra-short bounce time
• high resistance to pulsation
• vibration resistance up to 4 g in the range 0 – 1000 Hz
• long mechanical and electrical life

Table 6: Design
KP 7W, flare KP 7W, solder
MK

MK.FW

KP 7BS
MK

30
1 25

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 5


Pressure switch, Type KP

1 Pressure setting spindle 18 Locking plate


2 Differential setting spindle 25 Int. reset arm
3 Main arm 30 Ext. reset button
15 Cable entry

Types KP1, KP1A, KP2, KP4, KP6, KP6A, KP7, KP17 and KP47 units with designation W, B or S have been tested and
approved by TÜV, Rheinland in accordance with EN 12263.

Types KP6, KP6A, KP7, KP17 and KP47 have a double bellows: an outer bellows and a regulating bellows. When
system pressure exceeds the set value, the KP will automatically stop the plant. The double bellows system prevents
loss of charge in the event of bellows rupture.

A rupture in the inner bellows will cause the control cut-out pressure to fall about 3 times less the set value, thus the
refrigeration plant compressor will stop.

A rupture in the outer bellows will cause the control cut-out pressure to fall to about 3 bar under the set value, thus
providing a fail-safe function.

Versions with designation W or AW cut in again automatically when the pressure has fallen to the set value minus
the differential.

Versions with designation B or AB can be cut in manually with the external reset button when the pressure in KP1
has increased 0.7 bar above set value and in KP6 and KP7 has fallen 4 bar under the set value.

Versions with designation S or AS can be cut in manually with the internal reset arm when the pressure has fallen 4
bar under the set value.

All KP pressure switches, including those which are PED-approved, operate independently of changes in the
ambient temperature around the control housing. Therefore the set cut-out pressure and differential are held
constant provided the permissible ambient temperatures are not exceeded.

Dimensions [in] and weight [lb]


Table 7: Pressure switchess with flare connection
KP 1, KP 2, KP 4, KP 5, KP 6, KP 7B, KP 7S and KP 7W KP15, KP17W and KP47W
84 44
122 44
60-306.16
Danfoss
61
61

28 – 32
28 – 30
28 – 30

=12

=12

Table 8: M10 × 0.75 connection


KP 1A, KP 2A and KP 5A KP 15A, KP 7AS and KP 7ABS
84 44
60-303.19
Danfoss

122 44
60-305.12
Danfoss
61

61
25 – 29

=12
25

=12

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 6


Pressure switch, Type KP

Table 9: Solder connection


KP 1, KP 2, KP 5, KP 7B, KP 7S and KP 7W KP 15, 1 KP 7W
84 44
122 44
61

61
112 – 114

112 – 116
112 – 114

Figure 1: KP with top cover


122 44
7
61
28 – 30

28 – 32

=12

Net weight:
KP 1, KP 2, KP4, KP 5, KP 6 and KP 7: approx. 0.3 kg
KP 15, KP 17, KP 47 and KP 7BS: approx. 0.5 kg
KP 1A and KP 5A: approx. 0.3 kg
KP 15A and KP 7ABS: approx. 0.5 kg

Table 10: IP55 enclosure


IP55 enclosure IP55 enclosure for dual types

Figure 2: Weld nipple for KP-A

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 7


Pressure switch, Type KP

Ordering

Figure 3: KP

For complete list of approved refrigerants, visit www.products.danfoss.com and search for individual code numbers,
where refrigerants are listed as part of technical data.

Table 11: For R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R448A, R449A, R450A, R452A, R507A, R513A and
selected A2L refrigerants: R455A, R454C, R1234yf, R1234yz, R1234ze
Low pressure (LP) High pressure (HP) Reset Code no.
High Contact Connection
Pressure Type Regulating Differential Regulating Differential Low
pressure system 1/4 in. 6 1/4 in. ODF 6 mm ODF
range [bar] ∆p [bar] range [bar] ∆p [bar] pressure LP
HP mm flare solder solder
060-110166 060-111266 060-111066
Low KP 1 -0.2 – 7.5 0.7 – 4.0 – – Auto – SPDT (1)(4) (4) (4)

060-114166
Low KP 1 -0.2 – 7.5 0.7 – 4.0 – – Auto – SPDT (2)(4)
– –

060-110366
Low KP 1 -0.9 – 7.0 0.7 – – Man. (Min.) – SPDT (1)
060-111166 060-110966

060-112066 060-112366
Low KP 2 -0.2 – 5.0 0.5 – 1.5 – – Auto – SPDT (1)(4)
– (4)

060-117166 060-117966 060-117766


High KP 5 – – 8 – 32 1.8 – 6.0 – Auto SPDT (1)(4) (4) (4)

060-117366
High KP 5 – – 8 – 32 3 – Man. (Max.) SPDT (1)
060-118066 –

SPDT + LP 060-124166 060-125466


Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Auto –
signal (4) (4)

SPDT + LP 060-124366
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Man. (Max.) – –
signal (1)

SPDT + LP 060-114866
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Man. (Max.) – –
signal (2)

SPDT + LP 060-124566
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4 Man. (Min.) Man. (Max.) – –
signal (1)

SPDT + LP
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4 Conv.(3) Conv.(3) 060-126166 – –
signal
SPDT + LP
060-126566 060-129966
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Auto and HP sig- (1)(4) (4) –
nal
SPDT + LP
060-126466 060-128466
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Man. (Max.) and HP sig- (1) (1) –
nal
SPDT + LP
060-115466 060-001066
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Conv.(3) Conv.(3) and HP sig- (4) (4) –
nal
SPDT + LP
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4 Conv.(3) Conv.(3) and HP sig- 060-122066 – –
nal

(1)
Available in Asia market with code 060-xxxx91
(2)
Pressure switches with gold-plated contacts
(3)
Conv.: optional automatic or manual reset
(4)
Enclosure IP44

For complete list of approved refrigerants, visit www.products.danfoss.com and search for individual code numbers,
where refrigerants are listed as part of technical data.

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 8


Pressure switch, Type KP

Table 12: For R717, R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507A,
R513A and selected A2L refrigerants : R455A, R454C, R1234yf, R1234yz, R1234ze
Low pressure (LP) High pressure (HP) Reset Code no.
Connection
Contact
Pressure Type Regulating Differential Regulating Differential Low High system 1 m cap.
range [bar] ∆p [bar] range [bar] ∆p [bar] pressure LP pressure HP M10 × 0.75 tube with
M10 × 0.75
060-116266 060-116066
Low KP 1A -0.2 – 7.5 0.7 – 4.0 – – Auto – SPDT (1) (2)

Low KP 1A -0.9 – 7.0 0.7 – – Man. (Min.) – SPDT – 060-116166


High KP 5A – – 8 – 32 1.8 – 6.0 – Auto SPDT – 060-123066
060-115366
High KP 5A – – 8 – 32 3 – Man. (Max.) SPDT (1) 060-123166

SPDT + LP
Dual KP 15A -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Auto 060-129566 060-129366
and HP signal
SPDT + LP
Dual KP 15A -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Man. (Max.) 060-129666 060-129466
and HP signal
SPDT + LP
Dual KP 15A -0.9 – 7.0 0.7 8 – 32 4 Conv. (3) Conv. (3) – 060-128366
signal

(1)
Available in Asia market with code 060-xxxx91
(2)
Enclosure IP44
(3)
Conv.: optional automatic or manual reset

Pressure switches PED 2014/68/EU approved; EN 12263


For complete list of approved refrigerants, visit www.products.danfoss.com and search for individual code numbers,
where refrigerants are listed as part of technical data.

Table 13: For R22, R134a, R404A, R407A, R407C, R407F, R410A(for KP6W, KP6B), R422B, R422D, R438A, R448A, R449A, R450A,
R452A, R507A, R513A and selected A2L refrigerants: R455A, R454C, R1234yf, R1234yz, R1234ze
Low pressure (LP) High pressure (HP) Reset Code no.
Contact Connection
Pressure Type (1)
Regulating Differential Regulating Differential Low High system 1/4 in. 6 mm 6 mm ODF
range [bar] ∆p [bar] range [bar] ∆p [bar] pressure LP pressure HP
flare solder
060-110166 060-111066
Low KP 1 -0.2 – 7.5 0.7 – 4.0 – – Auto – SPDT (2)(3) (3)

060-110366
Low KP 1 -0.9 – 7 0.7 – – Man. (Min.) – SPDT (2)
060-110966

060-112066 060-112366
Low KP 2 -0.2 – 5 0.5 – 1.5 – – Auto – SPDT (2)(3) (3)

060-440166
Low KP 4 -0.2 – 7.5 0.7 – 4.0 – – Auto – SPDT (3)

060-519066
High KP 6W – – 8 – 42 4 – 10 – Auto SPDT (3)

High KP 6B – – 8 – 42 4 – Man. (Max.) SPDT 060-519166 –


060-119066 060-120366
High KP 7W – – 8 – 32 4 – 10 – Auto SPDT (3) (3)

High KP 7B – – 8 – 32 4 – Man. (Max.) SPDT 060-119166 –


060-119266
High KP 7S – – 8 – 32 4 – Man. (Max.) SPDT (3)

Man. (Max.)
Dual KP 7BS – – 8 – 32 4 – SPST 060-120066 –
Man. (Max.)
SPDT + LP 060-127566 060-127666
Dual KP 17W -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Auto
and HP signal (3) (3)

SPDT+ LP sig- 060-126766


Dual KP 17W -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Auto –
nal (3)

Dual KP 17B -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Man. (Max.) SPDT 060-126866 060-127466
SPDT + LP 060-539766
Dual KP 17WB -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Conv.(5) –
and HP signal (3)(4)

SPDT + LP 060-470366
Dual KP47WB -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Conv.(5) –
and HP signal (3)(4)

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 9


Pressure switch, Type KP

(1)
W = PSH (pressure switch), B = PZH (pressure switch with ext. reset), S = PZHH (pressure switch with int. reset)
(2)
Available in Asia market with code 060-xxxx91
(3)
Enclosure IP44
(4)
Factory setting: LP side: Range 1 bar Pe, Diff. 1 bar; HP side: Range 18 bar Pe, Diff. 4 bar fixed
(4)
Factory setting: LP side: Range 1 bar Pe, Diff. 1 bar; HP side: Range 18 bar Pe, Diff. 4 bar fixed
(5)
Conv.: optional automatic or manual reset
(5)
Conv.: optional automatic or manual reset

For complete list of approved refrigerants, visit www.products.danfoss.com and search for individual code numbers,
where refrigerants are listed as part of technical data.

Table 14: For R717, R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507A,
R513A and selected A2L refrigerants: R455A, R454C, R1234yf, R1234yz, R1234ze
Low pressure (LP) High pressure (HP) Reset Code no.
Connection
Contact
Pressure Type Regulating Differential Regulating Differential Low High system 1 m cap.
range [bar] ∆p [bar] range [bar] ∆p [bar] pressure LP pressure HP M10 × 0.75 tube with
M10 × 0.75
060-116266 060-116066
Low KP 1A -0.2 – 7.5 0.7 – 4.0 – – Auto – SPDT (1) (2)

Low KP 1A 0.9 – 7 Fixed 0.7 – – Man. (Min.) – SPDT – 060-116166


Man. (Max.)
Dual KP 7ABS – – 8 – 32 Fixed 4 – SPST – 060-120566
Man. (Max.)

(1)
Available in Asia market with code 060-xxxx91
(2)
Enclosure IP44

Use with A2L refrigerants (R455A, R454C, R1234yf, R1234yz, R1234ze)


 CAUTION:
While using A2L refrigerants the following safety requirements should be followed

Safety requirements

1. KP pressure switches shall only be employed in the units/systems which comply with the requirements for
charge limits and requirements for avoiding ignition sources of IEC 60335-2-24, IEC 60335-2-40, IEC 60335-2-89,
ISO 5149, EN378-1 or equivalent
2. Applying the overload on the KPs must be prevented. If by any chance it was damaged, the system / unit shall be
stopped and KP shall be replaced as necessary
3. Electrostatic discharge protection and Electrical leakage protection shall be surely implemented by grounding or
other measures
4. Only trained personnel are authorized to handle flammable refrigerants systems and may do the installation,
maintenance and exchange of the switch by using appropriate tools
5. It is recommended to regularly check the function of KP switch
6. The KP pressure switches shall be used as built-in devices that cannot be accessible from outside and protected
against mechanical impact
7. The KPs shall be installed in water free environment. In addition, protection of the KP switches against corrosion
shall be taken into consideration when using them in corrosive environment
8. Cables shall not be in contact with sharp edges. The cables shall be connected with adequate stress relieve in
order to prevent that pulling forces can be carried thorough the cable to the terminal
9. In the event of pressure pulsation in the system, where switch is connected, these must be effectively dumped to
prevent failure of the bellows. The cycle frequency of KP switch shall be kept as low as possible
10. The KP switches shall not be installed in places where high level of vibration is present

Electrical rating for use with A2L refrigerants (R455A, R454C, R1234yf, R1234yz, R1234ze)
AC-3: 16 A / 250 V AC
AC-15: 10 A / 250 V AC

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 10


Pressure switch, Type KP

Table 15: Electrical rating


Voltage Current range Power factor (cos phi) Frequency
250V AC ≤ 4.0 A PF ≥ 0,400 50Hz/60Hz
250V AC > 4.0 to 6.0 A PF ≥ 0,594 50Hz/60Hz
250V AC > 6.0 to 16,0 A PF ≥ 0,780 50Hz/60Hz

Pressure switch setting with convertible reset


Table 16: Pressure switch setting with convertible reset

Low pressure Manual reset (1) Automatic reset Automatic reset Manual reset
High pressure Manual reset (1) Manual reset Automatic reset Automatic reset

(1)
Factory setting

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 11


Pressure switch, Type KP

Certificates, declarations, and approvals

The list contains all certificates, declarations, and approvals for this product type. Individual code number may have
some or all of these approvals, and certain local approvals may not appear on the list.

Some approvals may change over time. You can check the most current status at danfoss.com or contact your local
Danfoss representative if you have any questions.

Table 17: Certificates, declarations, and approvals


File name Document type Document topic Approval authority
01 202 PL-Q-11 0004 Quality - Assurance Certificate PED TÜV
01 202 641-B-19 0006-02 Pressure - Safety Certificate PED TÜV
17.20386.258 Marine - Safety Certificate Marine approval RMRS
LR 17-20047(E1) Marine - Safety Certificate Marine approval LR
FZ2015006584 Logo Printing Permission - CCC
ELE-086320XG-003 Marine - Safety Certificate Marine approval RINA
BV 03650-K0 BV Marine - Safety Certificate Marine approval BV
RU Д-DK.ГА02.В.03367 EAC Declaration EMC EAC
DNV GL TAA00001VZ Marine - Safety Certificate Marine approval DNV GL
RU C-DK.БЛ08.В.00063_18 Electrical - Safety Certificate EMC/LVEc EAC
UA.1O146.D.00075-19 UA Declaration EMCD/LVD LLC CDC EURO TYSK
UL E31024 Electrical - Safety Certificate - UL

CE-marked in accordance with:


• LVD 2014/35/EU (EN 60947-1, EN 60947-4-1, EN 60947-5-1)
• PED 2014/68/EU, category IV (EN 12263): KP 1, KP 2, KP 4, KP 6, KP 7, KP 17 and KP 47
• Underwriters Laboratories Inc., UL listed: excluding KP 4 and KP 47
• China Compulsory Certificate, CCC

Ship approvals
Det Norske Veritas and Germanischer Lloyd, DNV GL
Registro Italiano Navale, RINA
Bureau Veritas, BV
Lloyd’s Register, LR
Russian Maritime Register of Shipping, RMRS

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 12


Online support

Danfoss offers a wide range of support along with our products, including digital product information, software,
mobile apps, and expert guidance. See the possibilities below.

The Danfoss Product Store


The Danfoss Product Store is your one-stop shop for everything product related—no matter where
you are in the world or what area of the cooling industry you work in. Get quick access to essential
information like product specs, code numbers, technical documentation, certifications, accessories,
and more.
Start browsing at store.danfoss.com.

Find technical documentation


Find the technical documentation you need to get your project up and running. Get direct access to
our official collection of data sheets, certificates and declarations, manuals and guides, 3D models
and drawings, case stories, brochures, and much more.

Start searching now at www.danfoss.com/en/service-and-support/documentation.

Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specifically
designed to help engineers, installers, service technicians, and wholesalers better understand the
products, applications, industry topics, and trends that will help you do your job better.

Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.

Get local information and support


Local Danfoss websites are the main sources for help and information about our company and
products. Find product availability, get the latest regional news, or connect with a nearby expert—all
in your own language.

Find your local Danfoss website here: www.danfoss.com/en/choose-region.

© Danfoss | Climate Solutions | 2022.09 AI213186439478en-001203 | 13