5 2013 Edition
2013 Edition
© 2014 Reliable Automatic Sprinkler Co., Inc. 3 © 2014 Reliable Automatic Sprinkler Co., Inc. 4
Commodity Classification Commodity Classification Test
NFPA 13
2016 Edition
Issue Date: 5/26/2015
(or 8/20/2015 if someone files an appeal)
© 2014 Reliable Automatic Sprinkler Co., Inc. 11 © 2014 Reliable Automatic Sprinkler Co., Inc. 12
New Protection Options 1. K25 ESFR & Vertical Barriers
© 2014 Reliable Automatic Sprinkler Co., Inc. 13 © 2014 Reliable Automatic Sprinkler Co., Inc. 14
© 2014 Reliable Automatic Sprinkler Co., Inc. 15 © 2014 Reliable Automatic Sprinkler Co., Inc. 16
NFPA 13 NFPA 13
Chapter 21 Chapter 21
Alternative Sprinkler System Designs for Storage Criteria (Section A21.2)
Requires series of large scale fire tests Number of operated sprinklers
• High clear/low clear No sustained combustion at the outer edges of
• Ignition location relative to sprinklers the target arrays
Number of sprinklers used in the design must based No sustained combustion at the far end of the
on the worst-case result obtained in the full-scale main test array
fire test series increased by a minimum of 50% No sprinklers should operate at the outer edges
• Minimum of 12 sprinklers for standard coverage of the installed sprinkler system
• 768 sf (71,3m2) minimum operating area 1000°F (538°C) maximum 1 minute average
steel temperature measured above the fire
© 2014 Reliable Automatic Sprinkler Co., Inc. 17 © 2014 Reliable Automatic Sprinkler Co., Inc. 18
Test A: Setup
Test Program High Clearance
Test A Test B Test C
Ignited Between 2
Storage Arrangement Double Row Rack Sprinklers
Nom. Storage Height 20 ft (6,0m) 35 ft (10,7m) 30 ft (9,1m)
Ceiling Height 40 ft (12,2m)
Commodity Polystyrene Meat Trays on Hardwood Pallets
Vertical Barriers
Material Metal Metal 3/8 inch Plywood
Horizontal distance ~16 ft (4,9m) ~16 ft (4,9m) ~16 ft (4,9m)
Transverse Flue Spaces Blocked Open Open
Aisle Width 8 ft (2,4m)
Sprinkler ESFR K25.2 Intermediate Temperature at 60 psi (4,1bar)
Ignition Location Between 2 Sprinklers Under 1 Sprinkler
© 2014 Reliable Automatic Sprinkler Co., Inc. 19 © 2014 Reliable Automatic Sprinkler Co., Inc. 20
Test A: Damage
Results Summary
Test A Test B Test C
Nom. Storage Height (ft) 20 (6,0m) 35 (10,7m) 30 (9,1m)
Transverse Flue Spaces Blocked Open Open
Ignition Location Between 2 Sprinklers Under 1 Sprinkler
No. of Sprinklers Operated 6 7 7
First – Last (min:sec) 0:44 – 3:21 0:48 – 2:28 0:47 – 1:28
Max. 1 minute avg. steel 117 (47,2C) 134 (56,7C) 127 (52,8C)
temperature (°F)
Ignition of Target None
Extent of Fire Travel on 1 bay beyond 1 pallet position 1 pallet position
Main Array barrier beyond barrier beyond barrier
© 2014 Reliable Automatic Sprinkler Co., Inc. 21 © 2014 Reliable Automatic Sprinkler Co., Inc. 22
© 2014 Reliable Automatic Sprinkler Co., Inc. 23 © 2014 Reliable Automatic Sprinkler Co., Inc. 24
NFPA 13 Criteria
2. K8+ In-Rack & Horizontal Barriers
Vertical Barriers
3/8-inch (10mm) plywood, 3/8-inch particle board,
Alternative protection to supplement overhead
22 gauge metal (0,7mm), or equivalent sprinkler system
Max. 16-1/2 ft ( 5,0m) between barriers
Permitted for Group A plastics and Class I-IV
Max.124 sf (11,5m2)of storage between barriers and commodity
aisles
Similar to:
Extend through longitudinal flue space
FM Global Scheme 8-9A
Commodity may extend nominally 4 inches (0,1m)
past barrier into aisle NFPA 13 (2013) Section 17.1.5.7 for solid
Barrier must extended from max. of 4 inches (0,1m) shelves
above floor to top of storage Prior combustible liquids tests
© 2014 Reliable Automatic Sprinkler Co., Inc. 25 © 2014 Reliable Automatic Sprinkler Co., Inc. 26
© 2014 Reliable Automatic Sprinkler Co., Inc. 27 © 2014 Reliable Automatic Sprinkler Co., Inc. 28
In-Rack Sprinklers Single Row Racks
K8.0 or larger
Quick-response
Ceiling or in-rack
Model GL112
K11.2
Pendent & Upright
Spray Sprinklers
© 2014 Reliable Automatic Sprinkler Co., Inc. 29 © 2014 Reliable Automatic Sprinkler Co., Inc. 30
© 2014 Reliable Automatic Sprinkler Co., Inc. 31 © 2014 Reliable Automatic Sprinkler Co., Inc. 32
K25 EC In-Rack & Horizontal
3.
Barriers
Conventional vs. N-RACK-ECTM
Conventional In-Rack Sprinkler N-RACK-ECTM
New concept for in-rack sprinkler protection
Supported by full-scale fire testing at UL
Not in NFPA 13
Patent Pending
© 2014 Reliable Automatic Sprinkler Co., Inc. 35 © 2014 Reliable Automatic Sprinkler Co., Inc. 36
Exposed Expanded Group A plastics
Double-Row Racks
Horizontal
barriers at 20 ft
(6,0m) intervals
for EEP
© 2014 Reliable Automatic Sprinkler Co., Inc. 37 © 2014 Reliable Automatic Sprinkler Co., Inc. 38
Rack Storage of
Exposed Expanded Group A Plastics
Ceiling Sprinklers
K-16.8 ESFR @ 50 psi (3,4bar)
In-Rack Sprinklers
212° F (100C) K-25.2 EC Pendent @ 30 psi (2,0bar)
C-C 2,5m
© 2014 Reliable Automatic Sprinkler Co., Inc. 39 © 2014 Reliable Automatic Sprinkler Co., Inc. 40
Damage
© 2014 Reliable Automatic Sprinkler Co., Inc. 41 © 2014 Reliable Automatic Sprinkler Co., Inc. 42
Results Applications
Extent of fire spread: 1 bay from ignition Protection for high hazard commodities
Ignition of target: No Existing buildings with increase in hazard
1-min avg. Steel Temp: 102°F (38,9C) classification
Ceiling sprinklers operated: 1 Buildings taller than 48 ft (14,6m)
In-Rack sprinklers operated: 2 Areas with limited water supplies
Water savings
© 2014 Reliable Automatic Sprinkler Co., Inc. 43 © 2014 Reliable Automatic Sprinkler Co., Inc. 44
The Future of Storage
80’/120’
60’/90’
40’/60’
20’/30’
© 2014 Reliable Automatic Sprinkler Co., Inc. 45 © 2014 Reliable Automatic Sprinkler Co., Inc. 46
Summary
New options to protect Exposed Expanded
Group A plastics
Option Sprinkler Barriers Max. Ceiling In-Rack Water
(Interval) Height Sprinklers Demand
Storage
1 K25 ESFR Vertical 40 ft N/A 2,350+ gpm
(16-1/2 ft) (12,2m) (8,896lpm)
(5,0m)
2 K8+ QR Horizontal Unlimited Yes 480+ gpm
(12 ft) Repeat ~5 per level per (1,817lpm)
(3,7m) protection bay in a DRR
Definitions
Commodities
Michael Billstroem
Director of International Technical Services
The Reliable Automatic Sprinkler Co., Inc.
Definitions Definitions
¾ Encapsulation ¾ Encapsulated
• A method of packaging consisting of a plastic sheet
completely enclosing the sides and top of a pallet
load containing a combustible commodity.
Combustible commodities individually wrapped and
stored exposed in a pallet load are encapsulated.
Totally noncombustible commodities on wood pallets
enclosed by plastic sheet are not considered
encapsulated.
Banding (wrapping the sides only) is not considered
encapsulation.
Holes or voids greater than 50% on the top are not
encapsulated
Does not apply to plastic enclosed packages inside a
large, non-plastic enclosed container.
Definitions Definitions
¾ Non Encapsulated ¾ Expanded Plastics
(Foamed or Cellular)
• Plastics in which the
density is reduced by
the presence of
numerous small
cavities (cells),
interconnecting or not,
dispersed throughout
their mass
Definitions
¾ Exposed Plastics
• Plastics not in packaging or
coverings that absorb water
or appreciably retard the
burning hazard of the
commodity. (Paper wrapped or
encapsulated, or both, should
be considered exposed).
¾ Free Flowing Plastics
• Plastics that fall out of their
containers during a fire, fill
flue spaces and create a
smothering effect on the fire.
(Powder, pellets, flakes or
random-packed small objects)
Standard Commodities for Testing
Definitions
¾ High Piled Storage
• Solid-piled, palletized, rack storage, bin
box, and shelf storage in excess of 12 feet
Class 2 Class 3 Class 4 in height.
¾ Miscellaneous Storage
Cartoned
onedd Cartoned Exposed • Storage that does not exceed 12 feet and is
incidental to another occupancy group.
Unexp
Unexxxp.
xp
p. Expanded Expanded Storage shall not constitute more than 10
Group A Group A Group A percent of the building area or 4000 ft² of
sprinklered area whichever is greater.
Storage shall not exceed 1000 ft² per pile
Each pile shall be separated by 25 feet from
other piles
Classifications based on NFPA 13
Images © 2013 UL LLC. All rights reserved.
Used with permission.
Definitions Definitions
¾ Pallets
¾ Pallets
• Conventional Pallet – a material handling
aid designed to support a unit load with
openings to provide access for material
handling devices.
• Plastic Pallet – Any portion consisting of
plastic
• Reinforced Plastic Pallet – A plastic pallet
incorporating a secondary reinforcing
material (such as steel or fiberglass) within
the pallet.
• Slave Pallet – A special pallet captive to a
material handling system.
• Wood Pallet – A pallet constructed entirely
of wood with metal fasteners.
Definitions Definitions
¾ Closed Array ¾ Shelf Storage
• Storage arrangement where air • Storage on structures up to and including 30
movement in the pile is restricted in. deep and separated by aisles at least 30 in.
because of 6 in. or less vertical wide.
flues. ¾ Back to Back Shelf Storage
¾ Open Array • Two solid or perforated shelves up to 30 in. in
depth, not exceeding a total depth of 60 in.,
• Storage arrangement where air separated by a longitudinal vertical barrier
movement in the pile is enhanced such as plywood, particleboard, sheet metal,
because of 6 in. or larger vertical or equivalent, with a maximum 0.25 in.
flues. diameter penetrations and no longitudinal flue
space and a maximum storage height of 15 ft.
¾ Bin Box Storage
• Storage in a five-sided wood, metal,
¾ Solid-Piled Storage
or cardboard boxes with open face • Storage of commodities stacked on each other
on the aisles. with no pallets or aides. Piles can be stable or
unstable.
Definitions Definitions
¾ Rack ¾ Double Row Rack
• Any combination of • Racks less than or equal to 12 ft. in depth or single row
vertical, horizontal, racks placed back to back not exceeding 12 ft.
and diagonal structural
members that support
stored materials or
commodities.
¾ Single Row Rack
• Racks that have no
longitudinal flue space
and that have a depth
up to 6 ft. in width with
aisles of at least 3.5 ft.
between loads on
racks.
Definitions Definitions
¾ Multiple Row Flow Through Rack Portable Rack
Racks
• Racks greater
than 12 ft. in
depth or
single or
double row
racks
separated by
aisles less
than 3.5 ft.
wide having
an overall
width greater
than 12 ft.
Definitions Definitions
¾ Open Rack ¾ Solid Shelving
• Racks without shelving or with shelves in racks that are fixed in • Fixed in place, slatted, wire mesh, or other type of shelves located
place with shelves having a solid surface and a shelf equal to or within racks. The area is defined by an aisle or flue space on all
less than 20 ft² or with shelves having wire mesh, slatted surface, four sides. Solid shelves having an area equal to or less than 20 ft²
or other material with openings representing the horizontal area of shall be defined as open racks. Shelves of wire mesh, slats, or
rack members and where the flue spaces are maintained. other materials more than 50% open shall be defined as open
racks.
Definitions Definitions
¾ Longitudinal Flue
Space
¾ Horizontal Barrier
• The space between • A solid barrier in the horizontal position
rows of storage
perpendicular to the covering the entire rack, including all flue
direction of loading spaces at certain height increments to
with a width not
exceeding 24 in. prevent vertical fire spread.
between storage.
¾ Transverse Flue ¾ Bulkhead
Space • A vertical barrier across the rack.
• The space between
rows of storage
parallel to the
¾ Roof Height
direction of loading. • The distance between the floor and the
underside of the roof deck within the
storage area.
Definitions Definitions
¾ Pyramid Tire Storage
¾ Laced Tire • On-floor storage in which
Storage tires are formed into a
pyramid for stability
• Tires stored ¾ On Side Tire Storage
where the • Tires stored horizontally
sides of the or flat.
tires overlap, ¾ On-Tread Tire Storage
creating a • Tires stored vertically or
woven or laced on their treads.
appearance.
Definitions Definitions
Typical Open Portable Rack Typical Palletized Portable Rack