Power System Protection Lectures - Feeder Protection
Power System Protection Lectures - Feeder Protection
by
Pratap Mysore, P.E.
Feeder Protection
Distribution system Protection
Feeder Circuit Configuration
❑ Four-Wire unigrounded-
❑Four-Wire Multigrounded neutral neutral System
System
2
Distribution system Protection
• Distribution voltages – 4 kV – 34.5 kV
• Mostly Radial
• Distributed generation is changing this assumption
Overcurrent protection
5
Fuse and Fuse cutout
Copyright@2015
Fuses
7
Expulsion Fuses
▪Typically Coordination is
done between same type
of fuse links
▪K type –supposed to
coordinate better with
8
Current limiting fuses
Application - indoor or confined places
Does not emit ionized particles
10
Sectionalizers
• Performs the function of automatic sectionalizing
• Does not have fault interrupting rating
• Counts the number of trips by the recloser and sectionalizes
(opens) during reclosing cycle (when the breaker is open).
11
Breakers and Overcurrent Relays
15
Feeder Relay Settings
• Based on the system strength, length of the feeder and the
rating of the feeder
• Short feeders in urban areas
• Long feeders in rural areas
16
Feeder Settings – Typical philosophy
• The system fault current on the low voltage side of a transformer (Source)
doesn’t vary much.
• The phase pick up – one half of the minimum phase to phase fault current at
the end of the feeder
• The ground pick up – one half of the minimum single line to ground fault
current at the end of the feeder
• Time dial coordinated to provide 15-25 cycles margin with downstream
protective devices
• If any one of these are not met, we need to install an interrupting device (fuse
or pole mounted recloser) at the location where we meet all the above
requirements. The installed device will be set to protect the remaining section
of the feeder.
17
Short Feeders with Strong System
• 15 kV Fuse cutouts are rated at 10,000A
• Typically the fault current at the exit of the substation is limited
to 10,000A
• The feeder conductor is rated for 560A (336)
• Feeder length – 5 miles
18
Feeder Settings
• Phase pick up is set to around 150% of the phase conductor rating
– 840A
• Ground overcurrent settings are typically set to 50% of the phase
pick up on strong systems – This allows field switching with
feeders loaded up to 75% of the feeder rating – 420A
20
Feeder Relay-Fuse
Coordination
▪Feeder overcurrent pick up - Ph-
840A, Ground – 420A
Close-in Phase to ground Fault
Fault current –9300A
22
Feeder Relay-Fuse
Coordination
▪Feeder overcurrent pick up - Ph- 8A,
Ground – 420A
Feeder end Three Phase Fault
Fault current –1779A
23
Feeder Relay-Fuse
Coordination
▪Feeder overcurrent pick up - Ph-
840A, Ground – 420A
Feeder end phase- Phase Fault
Fault current –1541A
24
Longer Feeders
26
Instantaneous Settings
• Feeder instantaneous settings – 85-90% of the fault current –
8300A
• The instantaneous setting – 0.5 miles on the feeder
28
Instantaneous settings on bus back up
relay
• Animal faults are common on distribution buses
• One shot reclose restores feeders for a temporary fault
• Could be set only if the feeder has instantaneous setting
29
Multiple Transformer Stations
• Two or three transformer stations
• Bus ties open or closed
• If fault currents at feeder exits exceed 10,000A, current limiting
reactors are used.
30
Overcurrent Relays in Multiple Transformer
Stations
• Settings are based on max. fault current
• With N.C. bus ties open, one shot reclose for bus faults will not
operate
• Distance relays are used especially in substations with feeder
31
Distribution Transformer
Feeder Coordination
32
Distribution Transformer
Feeder Coordination
33
Long Feeders with weaker
sources
• The relay has to clear faults at the end of the feeder
• The fault current/relay pick ratio of 2.0 can be used as a setting
philosophy.
• The phase pick up is usually set to 135-150% of the maximum
34
Rural Feeders
• Rural Electrification Administration (REA)
bulletin 61-2, “Guide for making a
sectionalizing study on Rural Electric Systems”
• Key points – Fault resistance of 40 ohms for
35
Other Features in Modern Relays
• Negative sequence overcurrent relays
• Use of Torque control with other protection elements are also
available.
36
Auto-Reclosing
• Reclosers have fixed (2 or 4 sec) time delays
with adjustable number of recloses (# of trips up
to 4)
• Substation relays - Settable
38