CONSULTANT : Al Omro
CONTRACTOR : HAWAZEN AL JAZEERA
PROJECT : College Maintenance
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : RABWAI
DATE: 10/22/2013
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1794.5 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 1899.40 3/4" 0.00 1794.50 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 30.00 1/2" 130.00 1664.50 92.76 85 100 ±6
WT.OF FILTER AFTER TEST gm 33.60 3/8" 348.90 1445.60 80.56 78 83 -
WT. OF AGG. AFTER TEST gm 1794.50 No. 4 814.30 980.20 54.62 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1798.10 No. 10 1149.00 645.50 35.97 30 42 ±5
WT. OF LOSS AGGREGATES gm 101.30 No. 40 1459.00 335.50 18.70 14 25 ±4
BITUMEN. BY WT. OF MIX % 5.33 No. 80 1610.40 184.10 10.26 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. % 5.33 No. 200 1708.00 86.50 4.82 3 7 ±2
SPECIFICATIONS FOR BWC % 4.0 - 6.0 PAN
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS: Need Futher Adjustment Sieve No. 40

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 93 85 100
3/8" 950 2.977724 2.10 81 64 73
70 #4 475 2.676694 1.80 55 46 60
# 10 200 2.30103 1.43 36 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 19 14 25


50 # 80 18 1.255273 0.38 10 8 16
# 200 7.5 0.875061 0.00 4.8 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector


‫بسم اهلل الرحمن الرحيم‬
‫المملكة العربية السعودية‬
‫وزارة الشئون البلدية والقروية‬
‫أمانة منطقة الحدود الشمالية‬
CONSULTANT : Al Omro
CONTRACTOR : Khaleed Al Nhady
PROJECT : Road Maintenance
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : Tariq Malik Faisal Near Post Office (S1)
DATE: May 06,2013
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1700.6 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 1799.70 3/4" 0.00 1700.60 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 31.10 1/2" 0.00 1700.60 100.00 85 100 ±6
WT.OF FILTER AFTER TEST gm 35.20 3/8" 289.00 1411.60 83.01 78 83 -
WT. OF AGG. AFTER TEST gm 1700.60 No. 4 676.40 1024.20 60.23 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1704.70 No. 10 1154.90 545.70 32.09 30 42 ±5
WT. OF LOSS AGGREGATES gm 95.00 No. 40 1479.00 221.60 13.03 14 25 ±4
BITUMEN. BY WT. OF MIX % 5.28 No. 80 1548.60 152.00 8.94 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. % 5.28 No. 200 1591.00 109.60 6.44 3 7 ±2
SPECIFICATIONS FOR BWC % 4.0 - 6.0 PAN
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS: Need Futher Adjustment Sieve No. 40

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 100 85 100
3/8" 950 2.977724 2.10 83 64 73
70 #4 475 2.676694 1.80 60 46 60
# 10 200 2.30103 1.43 32 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 13 14 25


50 # 80 18 1.255273 0.38 9 8 16
# 200 7.5 0.875061 0.00 6.4 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector Consultant QA/QC Baladiah


‫بسم اهلل الرحمن الرحيم‬
‫المملكة العربية السعودية‬
‫وزارة الشئون البلدية والقروية‬
‫أمانة منطقة الحدود الشمالية‬
CONSULTANT : Al Omro
CONTRACTOR : Khaleed Al Nhady
PROJECT : Road Maintenance
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : Tariq Malik Faisal Near Post Office Opposit side
DATE: June 11,2013
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1749.1 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 1843.20 3/4" 0.00 1749.00 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 20.80 1/2" 0.00 1749.00 100.00 85 100 ±6
WT.OF FILTER AFTER TEST gm 23.50 3/8" 330.90 1418.10 81.08 78 83 -
WT. OF AGG. AFTER TEST gm 1749.10 No. 4 689.90 1059.10 60.55 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1751.80 No. 10 1069.30 679.70 38.86 30 42 ±5
WT. OF LOSS AGGREGATES gm 91.40 No. 40 1369.30 379.70 21.71 14 25 ±4
BITUMEN. BY WT. OF MIX % 4.96 No. 80 1504.60 244.40 13.97 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. % 4.96 No. 200 1689.00 60.00 3.43 3 7 ±2
SPECIFICATIONS FOR BWC % 4.0 - 6.0 PAN
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS: Need Futher Adjustment Sieve No. 40

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 100 85 100
3/8" 950 2.977724 2.10 81 64 73
70 #4 475 2.676694 1.80 61 46 60
# 10 200 2.30103 1.43 39 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 22 14 25


50 # 80 18 1.255273 0.38 14 8 16
# 200 7.5 0.875061 0.00 3.4 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector Consultant QA/QC Baladiah


‫بسم اهلل الرحمن الرحيم‬
‫المملكة العربية السعودية‬
‫وزارة الشئون البلدية والقروية‬
‫أمانة منطقة الحدود الشمالية‬
CONSULTANT : Al Omro
CONTRACTOR : Khaleed Al Nhady
PROJECT : Road Maintenance
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : Tariq Malik Faisal Near Post Office Opposit side
DATE: June 12,2013
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1759.2 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 1851.00 3/4" 0.00 1759.00 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 22.30 1/2" 0.00 1759.00 100.00 85 100 ±6
WT.OF FILTER AFTER TEST gm 24.20 3/8" 302.10 1456.90 82.83 78 83 -
WT. OF AGG. AFTER TEST gm 1759.20 No. 4 679.90 1079.10 61.35 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1761.10 No. 10 1058.40 700.60 39.83 30 42 ±5
WT. OF LOSS AGGREGATES gm 89.90 No. 40 1389.80 369.20 20.99 14 25 ±4
BITUMEN. BY WT. OF MIX % 4.86 No. 80 1510.90 248.10 14.10 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. % 4.86 No. 200 1668.20 90.80 5.16 3 7 ±2
SPECIFICATIONS FOR BWC % 4.0 - 6.0 PAN
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS: Need Futher Adjustment Sieve No. 40

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 100 85 100
3/8" 950 2.977724 2.10 83 64 73
70 #4 475 2.676694 1.80 61 46 60
# 10 200 2.30103 1.43 40 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 21 14 25


50 # 80 18 1.255273 0.38 14 8 16
# 200 7.5 0.875061 0.00 5.2 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector Consultant QA/QC Baladiah


‫بسم اهلل الرحمن الرحيم‬
‫المملكة العربية السعودية‬
‫وزارة الشئون البلدية والقروية‬
‫أمانة منطقة الحدود الشمالية‬
CONSULTANT : Al Omro
CONTRACTOR : Khaleed Al Nhady
PROJECT : Road Maintenance
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : Tariq Malik Faisal Near Post Office Opposit side
DATE:
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1436.9 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 1507.80 3/4" 0.00 1436.90 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 22.50 1/2" 0.00 1436.90 100.00 85 100 ±6
WT.OF FILTER AFTER TEST gm 23.10 3/8" 259.90 1177.00 81.91 78 83 -
WT. OF AGG. AFTER TEST gm 1436.90 No. 4 659.50 777.40 54.10 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1437.50 No. 10 908.60 528.30 36.77 30 42 ±5
WT. OF LOSS AGGREGATES gm 70.30 No. 40 1208.50 228.40 15.90 14 25 ±4
BITUMEN. BY WT. OF MIX % 4.66 No. 80 1284.60 152.30 10.60 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. % 4.66 No. 200 1372.80 64.10 4.46 3 7 ±2
SPECIFICATIONS FOR BWC % 4.0 - 6.0 PAN
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS: Need Futher Adjustment Sieve No. 40

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 100 85 100
3/8" 950 2.977724 2.10 82 64 73
70 #4 475 2.676694 1.80 54 46 60
# 10 200 2.30103 1.43 37 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 16 14 25


50 # 80 18 1.255273 0.38 11 8 16
# 200 7.5 0.875061 0.00 4.5 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector Consultant QA/QC Baladiah


‫بسم اهلل الرحمن الرحيم‬
‫المملكة العربية السعودية‬
‫وزارة الشئون البلدية والقروية‬
‫أمانة منطقة الحدود الشمالية‬
CONSULTANT : Al Omro
CONTRACTOR : Khaleed Al Nhady
PROJECT : Road Maintenance
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : MALIK SAUD ROAD ( STA.(0+840-1+205)R/S
DATE:
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1901.1 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 2002.50 3/4" 0.00 1901.10 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 25.20 1/2" 0.00 1901.10 100.00 85 100 ±6
WT.OF FILTER AFTER TEST gm 23.90 3/8" 366.00 1535.10 80.75 78 83 -
WT. OF AGG. AFTER TEST gm 1901.10 No. 4 798.80 1102.30 57.98 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1899.80 No. 10 1206.70 694.40 36.53 30 42 ±5
WT. OF LOSS AGGREGATES gm 102.70 No. 40 1575.70 325.40 17.12 14 25 ±4
BITUMEN. BY WT. OF MIX % 5.13 No. 80 1709.10 192.00 10.10 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. 0 5.13 No. 200 1854.80 46.30 2.44 3 7 ±2
SPECIFICATIONS FOR BWC 0 4.0 - 6.0 PAN
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS: Need Futher Adjustment Sieve No. 40

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 100 85 100
3/8" 950 2.977724 2.10 81 64 73
70 #4 475 2.676694 1.80 58 46 60
# 10 200 2.30103 1.43 37 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 17 14 25


50 # 80 18 1.255273 0.38 10 8 16
# 200 7.5 0.875061 0.00 2.4 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector Consultant QA/QC Baladiah


‫بسم اهلل الرحمن الرحيم‬
‫المملكة العربية السعودية‬
‫وزارة الشئون البلدية والقروية‬
‫أمانة منطقة الحدود الشمالية‬
CONSULTANT : Al Omro
CONTRACTOR : Khaleed Al Nhady
PROJECT : Road Maintenance
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : MALIK SAUD ROAD ( STA.0+463-0+840)R/S
DATE:
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1587.0 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 1669.00 3/4" 0.00 1587.00 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 24.60 1/2" 0.00 1587.00 100.00 85 100 ±6
WT.OF FILTER AFTER TEST gm 22.70 3/8" 368.90 1218.10 76.75 78 83 -
WT. OF AGG. AFTER TEST gm 1587.00 No. 4 720.90 866.10 54.57 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1585.10 No. 10 980.90 606.10 38.19 30 42 ±5
WT. OF LOSS AGGREGATES gm 83.90 No. 40 1292.50 294.50 18.56 14 25 ±4
BITUMEN. BY WT. OF MIX % 5.03 No. 80 1409.00 178.00 11.22 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. % 5.03 No. 200 1499.00 88.00 5.55 3 7 ±2
SPECIFICATIONS FOR BWC % 4.0 - 6.0 PAN
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS: Need Futher Adjustment Sieve No. 40

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 100 85 100
3/8" 950 2.977724 2.10 77 64 73
70 #4 475 2.676694 1.80 55 46 60
# 10 200 2.30103 1.43 38 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 19 14 25


50 # 80 18 1.255273 0.38 11 8 16
# 200 7.5 0.875061 0.00 5.5 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector Consultant QA/QC Baladiah


‫بسم اهلل الرحمن الرحيم‬
‫المملكة العربية السعودية‬
‫وزارة الشئون البلدية والقروية‬
‫أمانة منطقة الحدود الشمالية‬
CONSULTANT : Al Omro
CONTRACTOR : Khaleed Al Nhady
PROJECT : Road Maintenance
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : MALIK SAUD ROAD ( STA.0+00-0+463)R/S
DATE:
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1427.9 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 1505.70 3/4" 0.00 1427.90 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 22.50 1/2" 0.00 1427.90 100.00 85 100 ±6
WT.OF FILTER AFTER TEST gm 25.60 3/8" 366.00 1061.90 74.37 78 83 -
WT. OF AGG. AFTER TEST gm 1427.90 No. 4 722.50 705.40 49.40 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1431.00 No. 10 964.90 463.00 32.43 30 42 ±5
WT. OF LOSS AGGREGATES gm 74.70 No. 40 1192.70 235.20 16.47 14 25 ±4
BITUMEN. BY WT. OF MIX % 4.96 No. 80 1262.30 165.60 11.60 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. % 4.96 No. 200 1351.30 76.60 5.36 3 7 ±2
SPECIFICATIONS FOR BWC % 4.0 - 6.0 PAN
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS: Need Futher Adjustment Sieve No. 40

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 100 85 100
3/8" 950 2.977724 2.10 74 64 73
70 #4 475 2.676694 1.80 49 46 60
# 10 200 2.30103 1.43 32 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 16 14 25


50 # 80 18 1.255273 0.38 12 8 16
# 200 7.5 0.875061 0.00 5.4 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector Consultant QA/QC Baladiah


CONTRACTOR : Khaleed Al Nhady
PROJECT : AR AR COLLEGE MENTAINANCE
DESCRIPTION : Bituminous Wearing Course - Class B
LOCATION : AR AR COLLEGE
DATE: September 24,2013
QUANTITATIVE EXTRACTION OF BITUMEN (ASTM 2172)

EXTRACTION TEST MECHANICAL ANALYSIS OF AGGREGATE (AASHTO T-30)

TOTAL WT. OF AGGREGATES = 1794.5 gm


CUMM. CUM.
ASTM PASSING MOMRA
SAMPLE No. No. A B
SIEVES
RETAINED PASSING
% Specs
Tol.
gms. gms.
WT. OF SAMPLE MIX gm 1899.10 3/4" 0.00 1794.50 100.00 100 ±6
WT.OF FILTER BEFORE TEST gm 30.00 1/2" 0.00 1794.50 100.00 85 100 ±6
WT.OF FILTER AFTER TEST gm 33.60 3/8" 103.50 103.50 5.77 78 83 -
WT. OF AGG. AFTER TEST gm 1794.50 No. 4 603.90 707.40 39.42 46 60 ±6
TOTAL WT. OF AGGREGATES gm 1798.10 No. 10 443.10 1150.50 64.11 30 42 ±5
WT. OF LOSS AGGREGATES gm 101.00 No. 40 401.10 1551.60 86.46 14 25 ±4
BITUMEN. BY WT. OF MIX % 5.32 No. 80 119.10 1670.70 93.10 8 16 ±3
EXTR. AVG. BIT. BY WT. OF MIX. % 5.32 No. 200 54.10 1724.80 96.12 3 7 ±2
SPECIFICATIONS FOR BWC % 4.0 - 6.0 PAN 7.90 1732.7
JMF TOLERANCE LIMIT % 5.5±0.40 WASH

REMARKS:

100 1.5" 3810 3.580925 2.71

1" 2540 3.404834 2.53


90
3/4" 1900 3.278754 2.40 100 100 100
80 1/2" 1250 3.09691 2.22 100 85 100
3/8" 950 2.977724 2.10 6 64 73
70 #4 475 2.676694 1.80 39 46 60
# 10 200 2.30103 1.43 64 30 42
60
% PASSING

# 40 42.5 1.628389 0.75 86 14 25


50 # 80 18 1.255273 0.38 93 8 16
# 200 7.5 0.875061 0.00 96.1 3 7.0
SIEVE SIZE
mms LOG Specs
LOG-NEGATIVE MAX.
40

30

20

10

0
200 # 80 # 40 # 10 # 4# "3/8 "1/2 "3/4

SIEVE SIZE/NO. (LOG)

Contractor Materials Inspector