0% found this document useful (0 votes)
37 views2 pages

PICKUP - QCM:: Test Module

The document summarizes the results of four protection relay tests - two for pickup and reset of overcurrent protection (PU OCR and RESET OCR), and two for pickup and reset of ground fault protection (PU GFR and RESET GFR). It provides the test module information, fault calculator parameters, generator settings, and binary input settings for each test. All four tests passed with a 100% pass rate.

Uploaded by

dwiki septian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views2 pages

PICKUP - QCM:: Test Module

The document summarizes the results of four protection relay tests - two for pickup and reset of overcurrent protection (PU OCR and RESET OCR), and two for pickup and reset of ground fault protection (PU GFR and RESET GFR). It provides the test module information, fault calculator parameters, generator settings, and binary input settings for each test. All four tests passed with a 100% pass rate.

Uploaded by

dwiki septian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PICKUP.

qcm:

Test Module
Name: OMICRON QuickCMC Version: 4.00
Test Start: 08-Feb-2022 11:19:10 Test End: 08-Feb-2022 11:23:51
User Name: Manager:
Company:

Test Results

Title: PU OCR

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct IR 2,650 A 0,00 ° 50,000 Hz
IS 2,650 A -120,00 ° 50,000 Hz
IT 2,650 A 120,00 ° 50,000 Hz

Generator Settings
IR 2,650A 0,00° +90°
IS 2,650A -120,00° IT
IT 2,650A 120,00°

IR
180° 0°

IS
3,0 A -90°

Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Title: RESET OCR

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct IR 2,550 A 0,00 ° 50,000 Hz
IS 2,550 A -120,00 ° 50,000 Hz
IT 2,550 A 120,00 ° 50,000 Hz

Generator Settings
IR 2,550A 0,00° +90°
IS 2,550A -120,00° IT
IT 2,550A 120,00°

IR
180° 0°

IS
3,0 A -90°

Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0
Title: PU GFR

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct IR 248,0 mA 0,00 ° 50,000 Hz
IS 0,00 A -120,00 ° 50,000 Hz
IT 0,00 A 120,00 ° 50,000 Hz

Generator Settings
IR 0,248A 0,00° +90°
IS 0,000A -120,00°
IT 0,000A 120,00°

IR
180° 0°

300,0 mA-90°

Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Title: RESET GFR

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct IR 241,0 mA 0,00 ° 50,000 Hz
IS 0,00 A -120,00 ° 50,000 Hz
IT 0,00 A 120,00 ° 50,000 Hz

Generator Settings
IR 0,241A 0,00° +90°
IS 0,000A -120,00°
IT 0,000A 120,00°

IR
180° 0°

300,0 mA-90°

Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Summary
4 tests passed, 0 tests failed, 0 tests not assessed 100,00% passed