Instrumentation and Measurements
Instrumentation and Measurements
EE-218
1- INTRODUCTION
1.1 - Feedback Control.
1.2 - Levels of Control Engineering
1.3 - Process-Control Principles.
3- MEASUREMENT OF PRESSURES.
3.1 - Pressure Principles
3.2 - Pressure Units
3.3 - Absolute Pressure and Gauge pressure.
3.4 - Methods of Pressure Measurement.
4- MEASUREMENT OF LEVEL.
4.1 - Methods of Level Measurement.
5- MEASUREMENT OF TEMPERATURE.
5.1 - Units.
5.2 - Expansion Thermometers.
5.3 - Methods of Temperature Measurements.
6- MEASUREMENT OF FLOW.
6.1 - Units.
6.2 - Methods of Flow Measurements.
7- MEASUREMENT OF VISCOSITY.
7.1- Introduction.
7.2 - Methods of Viscosity Measurements.
1- INTRODUCTION
1-1 Feed-back Control
Automation (
) is used in many engineering systems. It is used to improve
(
) the operation of devices( ) to do functions ( ) that can never
be done by human operator (
) because of the required:
• Speed ( ), Precision ( ), Power ( ) and economical operation
( !"# ).
Modern ($ ) automation started with the invention (% & ) of steam engine.
Example of early automatic control mechanism is the speed governor (
'), as
shown in figure (1.1).
Set point
Fuel (steam)
To engine
Most early automatic control systems were self-operating ( ( !)), which means that
there is no external source of power (*+,& ) is required to drive (!"#) the
controller. A simple example is the float-controlled valve ( -) * -.
'
) to
control the water level, as shown in figure (1.2).
In modern controllers, we use electrical, hydraulic or pneumatic transmission (!) of
signals to control the process.
Float Output
Valve
Supply
• Advantages of Automation
a- Fuel saving “due to efficient operation” (!"# 01' * 2-).
b- Reduced maintenance, because of efficient operation and timely warning of
defects. (!* 3-. ( - !"# 01' !+)
c- Personal saving, less number of individual ( 2 ) is required () 2-).
c- Improved environment ( !"# 4-), watch keeping in a comfortable
() control rooms.
e- Increased safety, the degree of human error is less
.!5 #. 6*&
5 3
• Disadvantages
1- Increase first costs.(- 4' )
a- Extra components ( 7-').
b- More sophisticated ( &), reliable (!* !+) and expensive (,8)
components and devices (5) are employed (
& ).
c- Skilled persons ( !) are required to install (9') and test (.& ) the
components.
d- High degree of design work (! - ,+ 7 ).
2- Increased running costs(!"# 4 ), as extra () costs are
involved to provide(: 71;5)
a- Power required to operate the controls.
b- Staff education costs ((
+) 4'.
c- Extra maintenance (2; = ) may be required.
/
1.2 Levels of Control Engineering
>
1.2.4 Computer System for Ship Applications ()
A ship may be provided with computer, which performs (9
-) many functions
such as:-
- Automatic control of the engine room.
- Navigation (. ).
- Cargo handling (# !- )(load master).
- Ship management…(1 )..etc.
Qin
h
H
Qout
B
The human measures the actual level h in the sight glass and compares () it with
the set point H. if h > H, the human opens the valve to increase the output flow Qo, the
water level h lowers till (,) h =H. If h < H, the human closes the valve to decrease
the output flow Qo, and allow the level h to rise till h =H. So by continuous monitoring
( . ) of the sight glass the human can bring (!) ?*) the water level h to
shown in figure (1.4), the human is replaced by (F+ !) the following devices:-
- Sensor: To measure the water level and generates (,*)) a signal S that represents
- Controller: It compares the set point H with the actual level h and generates a control
signal u to change the valve opening via an actuator.
- Actuator: Is connected to the valve by a mechanical link.
Qin
Sensor Controller
h Actuator
H
Qouti
E
1.3.4 Process Control Block Diagram (
' -,- **& ).
- Error detector: (6*& 4#') A part of the controller to compare the set point H
- Actuator: ((1 ) The final control element, the device ( ) that has a direct
(#. $6) on the process and changes the controlled variable to bring it to
Sensor
Feedback signal
G
2 SPECIFICATIONS OF MEASURING INSTRUMENTS
(J 5 71 -)
2.1 Introduction to Instrumentation
measure the process variables. The measured value is indicated () as a signal, which
variable to the desired value. System variables that may be measured are pressure,
temperature, level, flow, viscosity, position, velocity …etc.
The instrument used has to be accurate (:), sensitive (J), reliable (!* !+)
and capable (,+) to operate for long time in the marine environment (. 4- ).
Namely (!$), vibration ( @ ), salt (-+ ), corrosive atmosphere (!'K ,+ -)
- Sensor : ()#) It detects (4#') the system controlled variable (temperature) and
produces a signal proportional to (? 9) it, this signal may be:
- Transducer (# !-) It changes the signal received (!.) from the sensor into an
I
2.2.1 Units
Two systems of units are commonly (!) ?0#) used:
COMPARISON
M
Example 2.1. Find the number of feet in 5.7 m
1m = 3.28 feet 5.7 x 3.28 = 18.698 = 18.7 ft.
2
m = 2
= 0 . 062 slugs
32 . 17 ft / s
1 kg
∴ m = 0.062× = 0.062 (14.59 −) = 0.905kg
0.0685 slug
Giga G 109
Mega M 106
Kilo k 103
Centi C 10-2
Mili m 10-3
Micro µ 10-6
Nano n 10-9
Pico p 10-12
Femto f 10-15
Example 2. 4. Express the time 0.0000215 sec. and the power 3,781,000,000 watt
in standard prefixes.
0. 0000215 = 2, 1.5 x 10-6 = 21.5 µ sec.
3,781,000,000 = 3.781 x 109 w = 3.781 Gw
N
2.2.2 Standards
Two standards are used in control systems, for electric systems we use a range of
electric current, and for pneumatic systems we use a range of pressure. These signals
are used to transmit variable information (" 7-+) ! ) to and from the control
room, for example as shown in figure (2.1). Current is used to transmit measured
variable to the control room, and air pressure is used to transmit feedback signal ( #=
I 4- 20 mA I
Sensor to
Sensor current V
converter
I to V
I I
Plant Control room
P p V
Valve Actuator
V to P
Current signal
The most common ( & $' ) transmitting signal is 4 to 20 m A.
Sensor to R
Sensor current I
converter
RL (0-1000 Ω )
Note:
Current is used instead of (
.) voltage because the system is then less dependent on
(O+ !5) the load and the line resistance as shown in figure (2.2).
Example 2.5
A temperature range 20 o C ÷ 120 o C is represented by 4 to 20 mA. What current will
results from 66 o C?. What temperature does 6.5 mA represents?
Solution
Develop a linear equation between temperature and current
I = m T + Io
We have two point of this linear relation I
20 oC 120 oC
IO
4 mA 20mA
T
Pneumatic signals
The range of the Pneumatic signals for SI and English units is as following:
SI units 20 ÷ 100 KPa (0.2÷ 1 bar)
English units 3 ÷ 15 psi
2.2.3 Definitions (4))
(1) Error:
The error is most important quantity in control system. It is the difference between
the actual and the measured value.
Device
x Input K y output
The region (* ) between the maximum and the minimum limits (- ) of the
Solution
The transfer function error will be (± 0.01) (5m V/°C) = ± 0.05m V/°C.
The transfer function range is 4.95 to 5.05 m V/ °C.
(4) Span
The difference between the upper & lower range.
e.g. Range 20 to 200 psi Span = 180 psi
Range 50 to 150 volt Span = 100 volt
/
(5) Accuracy
This term expresses (
.)) the closeness (9) of the device reading with the
true value. Accuracy is expressed in several forms (1+& !'#6..) ).
i- Measured variable: the accuracy is ± 2 º C in some temperature measurement.
Thus there would be an inaccuracy of ± 2 º C in any value of temperature measured.
ii- Percentage of the instrument Full-scale (FS) reading: Thus an accuracy of
± 0.5% FS in a 5-volt full-scale range meter would mean the inaccuracy in any
measurement is ± 0.025 volts.
iii- Percentage of instrument Span: Thus, an accuracy of ± 3% of pressure range
20 to 50 psi the accuracy would be (± 0.03) (50 -20) = ± 0.9 psi.
iv- Percentage of the actual reading. Thus, for a ± 2% of a voltmeter reading. For a
reading of 2 volts, we would have an inaccuracy of ± 0.02 x 2 = ± 0.04 volts.
Example 2.7
(a) ± 0.5% FS, (b) ± 0.75% of span, and (c) ± 0.8% of reading.
What is the possible temperature in each case? ( !' ,2 + ,@ ).
Solution
Using the given definitions, we find:
a. Error = (± 0.05) (250 o C) = ± 1.25 o C.
The actual temperature is 53.75 or 56.25 ° C.
b. Error = (± 0.0075) (250 – 20) ° C = ± 1.725 ° C.
The actual temperature 53.275 or 56.725 ° C.
c. Error = (± 0.008) (55 °C) = ± 0.44 °C.
The actual temperature is 54.56 °C or 55.44 °C.
Example 2. 8.
Suppose (
5 D1.) a reading of 27.5 mV results from the sensor used in example (2.6),
where the transfer function range is 4.95 to 5.05 mV/ °C. Find the temperature that
provides (9.) this reading.
>
Solution
Because the range of transfer function is 4.95 to 5.05 mV/ °C, the possible temperature
for the reading of 27.5 mV is:
1
(27.5m V) = 5.56°C
4.95 mV/ °C
1
(27.5m V) = 5.45°C
5.05 mV/ °C
(6) Sensitivity
Is a measure of the instrument output change to the input change. The value of the
sensitivity is generally indicated by ( #) the transfer function. Thus, when a
temperature transducer (") transfer function 5 mV/ ° C, the sensitivity is 5 mV/ °C.
Windings
The resolution is the minimum measurable value of the input variable. A good
example is a wire-wound potentiometer, where the slider ( )اmoves across
windings to vary ( و#ا$%) resistance. If one turn of the winding = ∆ R ohms,
minimum resistance change is ∆ R, we say that the potentiometer resolution is ∆ R. This
is often expressed as ( ك#( ) # #)#) percentage of the full-scale range.
B
Example 2.10
A force is measured in a range of 0 to 150 N with a resolution of 0.1% FS. Find the
smallest change in force that can be measured.
Solution
Because smallest change in force that can be measured = the resolution = 0.1% FS
Example 2.11
A sensor has a transfer function of 5 V/ °C. Find the required voltage resolution of the
signal conditioning if a temperature resolution of 0.2 °C is required.
Solution
A temperature change of 0.2 ° C will result in a voltage change of:
5 mV/ °C x (0.2 °C) = 1.0 m V
Thus, the resolution of the signal conditioning circuit is 1.0 m V.
The relation ( . P) ) between the output and the input of the measuring device must
be linear that is (,).), for each value of the input variable there is only one value of
R = m T + Ro (2.1)
Where
T = measured input.
m = slope of straight line.
Ro = measured value at T = 0.
R = measured output.
E
Example 2.12
A sensor resistance changes linearly from 100 to 180 Ω as temperature changes from
20 ° C to 120 ° C. find a linear equation relating resistance and temperature.
Solution
Using equation (1.2) as a guide, the desired equation would be of the form:
R = m T + Ro
To find the two constants. m and Ro , substituting in (* +%#) equation.
100 Ώ = (20 o C) m + Ro
180 Ώ = (120 o C) m + Ro R(output)
Subtracting (-% د# ح ا/) the two equations.
80 Ώ = (100 o C) m m = 0.8 Ω / o C RO
Then, from the first equation we find
100 Ώ = (20 o C) (0.8 Ώ/ o C) + Ro Ro = 84 Ώ
The equation relating resistance and temperature is: T(input)
R = 0.8 T + 84
Statistics (70 =)
The average value is important in process control. For example, to control the
temperature in a process. The temperature might be measured in 10 locations, the
average tempperature is calculated and used in the control loop.
The arithmetic mean of a set (-) of n values, x1, x2, x3, ……, xn is defined by the
equation:
x 1 + x 2 + x 3 + ......... + xn
x = (2 . 2 )
n
Where:
x= arithmetic mean.
n= number of measurements.
G
x1, x2, …, x n measured values.
We use the symbol ∑ to represent a sum of numbers.
x=
∑x 1
(2 .3 )
n
Where:
∑xi symbol for a sum of the values x1, x2,… xn
It is insufficient (,2' 8) to know the value of the arithmetic mean of a set of
measurements to interpret the measurements properly ( *. 7
.)+),
it is necessary to know something about how the values are spread out (!- #) about
the mean value. ASlthough (
5
8) the mean value of the set (50, 40, 30, 70) is 47.5
and the mean value of the set ( 5, 150, 21, 14 ) is also 47.5, the second group of
numbers is obviously (T; -
) far more spread ( # $' 5) out about the mean
value 47.5 as shown in figure (2.4).
47.5
0 10 20 30 40 50 60 70 80 90 100
47.5
0 5 14 21 30 40 50 60 70 80 90 100 10 20 30 40 150
Figure (2.4) The values spread out about the mean value.
The standard deviation is a measure of this spread.
Given a set of n values x1, x2…., xn, the standard deviation is defined according to the
equation:
I
d 2
+ d 2
+ d 32 + ..... + d 2
σ = 1 2 n
n − 1
Where:
d 1 = x1 − x
d 2 = x 2 − x
d n = x n − x
σ = ∑ d i2
n − 1 (2.5)
Of course, the larger the standard deviation, the more spread out the numbers from the
mean value.
The standard deviation of the previous measurements:
For the measurements 50, 40, 30, 70. the mean value is 47.5
And the standard deviation is (50− 47.5)2 + (40− 47.5)2 + (30− 47.5)2 + (20− 47.5)2 / 3
6.25+ 56.25 . + 306.25+ 506.25= 21.47
Example 2.14
If the readings of an unknown coil were 20, 21, 22, 19, 18 Henry. Find the actual
value of the coil.
Solution:
20 + 21 + 22 + 19 + 18
Arithmetic mean L = 5
= 20 Henry
Arithmetic mean L = 20 H.
The deviations generally will be d = L - L
d1 = L1 - L = 20 - 20 = 0
d2 = L2 - L = 21 - 20 = 1
d3 = L3 - L = 22 - 20 = 2 L
M
d4 = L4 - L = 19 - 20 = -1
d5 = L5 - L = 18 - 20 = -2
N
3- PRESSURE MEASUREMENT
The measurement and control of fluid pressure is common in industrial processes.
3.1 Pressure Principles
F
The Pressure is defined as the force exerted per unit area P=
A
• Gas pressure:
Is the force per unit area exerted on the walls of the container that holds it.
• Liquid pressure:
Is the force per unit area exerted on the container it contained, (greatest on the bottom
and zero on a top). The pressure is static when the fluid is not in motion, when the fluid
moves, its pressure is dynamic pressure.
3.3 Absolute Pressure and Gauge Pressure (Head pressure)
- Absolute pressure
Is the pressure relative to the complete vaccum.
- Gauge pressure:
It is the plant pressure relative to atmosphere.
Absolute pressure
Gauge pressure
Atmosphere pressure
due to the atmosphere
of the gas.
Complete vacum (zero pressure)
i.e.
weight of liquid volum × ρ × g ρ ghA
P = = = = ρ gh
Area A A
Where:
P Pressure Pascal
ρ Specific density kg / m3
g Gravity constant 9.8 m / s2
h Head of liquid meter
h
Example 3.1
Pressure = ρ g h
a) 101.325 =13600 x 9.81x h hhg= 0.76 m
b) 101.325 =1000 x 9.81x h hw= 10.33 m
Example 3.2
A tank holds water (= F.) with a depth 7 feet. What is the pressure at the tank bottom
In order to display the pressure value, two approaches (9-+5) are used:
A - Manometers
U- type manometer
A manometer is the simplest device for measuring static pressure, as shown in
figure (3.2), the fluid used may be water or mercury.
The difference in level h is an indication of (,+#) the gauge pressure Pg.
Pat
P1
Scale
J - h
Datum
L
A a
/
Volume decrease = AL = Volume increase = ah.
ah
AL = ah L=
A
ah
Pressure in right limb (
% ( ) P = ρg ( h +L) = ρg ( h + )
A
a
The main equation of manometer is: P = ρgh ( 1+ )
A
Several types of manometers are used which are easy to use and more sensitive, such as:
• Well type manometer.
• Inclined type manometer.
Scale Pat
P1
A a
Notes:
* When the 2nd limb is open it measures the gauge pressure.
* It is filled with water for low pressure measurements.
* It is filled with mercury for high pressures measurements.
In this type a small pressure difference can be read more accurately. In this case the
scale is increased for a given head as shown in figure (3.4).
>
P1
P2
h
L Datum
∆h
θ
Figure (3.4) Inclined -Type Manometer
h = L sin θ
P2 - P1 = ρ.g.h = ρ.g L sin θ
Example 3.3
The left hand limb of a U – tube mercury manometer is connected to a static airflow
pressure 102 KPa. The right hand limb of the manometer is open to the atmosphere.
Given that: Patm=101 KPa, ρHg = 13600 kg / m3 and ρw = 1000 kg / m3.
a) What is the height difference in the U – tube limbs ? Calculate the height difference,
if the mercury is replaced by water.
b) If the U- tube is replaced by an inclined manometer at an angle 20o and the liquid is
water. What is the reading on the manometer scale?
Solution
a) Pair = Patm + ρ.g.h
As this pressure is too small to measure accurately, the mercury is replaced by water.
1.02 x 105 =1.01x 105 + 1000 x 9.81 hw hw = 0.102 m = 102 mm
This height can be measured accurately.
B
B- By Acting on Elastic Area
Most pressure sensors used in process control, converts (!-) the pressure into a
mechanical displacement ( =) using elastic area, then this displacement is converted
to a pointer (#) movement via a link (! - % () , quadrant (J ?.) and a gear
(J) arrangement as shown in figure (3.5). The elastic element can be Bourdon tube,
diaphragm, bellows or capsules.
the pressure to displacement. The tube is made of stainless steel or phosphoric bronze to
stand corrosion (!'K - 5 + !." 9+ - 5 -1-1 -.
) ).
Bourdon tube is coiled in different shapes C, spiral (,-+) or helical ( ) shapes.
Scale
Bourdon tube
Moving end
Gear
Quadrant Link
Fixed end
P
Measured pressure
Advantages Disadvantage
High accuracy Susceptibility to shocks
Low cost Variations
Simple structure Susceptibility to hystresis
Wide range
E
The Diaphragm
A diaphragm likes a spring and therefore it extends until (, ) a force is
developed (- -) to balance the pressure difference force.
A pressure P1 and P2 are applied on the sides of a diaphragm, the net force (+ - )
is F = (P1 -P2) A
Where
A diaphragm area m2
P1, P2 pressure N/m2
P1 > P2
Link
P1 P2
The Bellows
It is made of phosphoric bronze & stainless steel. The device converts the pressure
difference into mechanical displacement, much like the diaphragm, except that the
bellows displacement is much more straight - line expansion (0%1 23 * )! د.
Bellows are more sensitive and accurate than Bourdon tubes.
Bellows
P1 Link
P2
The Capsules
Capsules are much more sensitive and accurate than any other type (0.1% accuracy,
while it is 0.5 % for Bourdon tube, the pressure is applied from outside the capsules,
while the capsules are evacuated and sealed ( ' ). When measuring the differential
pressure, applied from out side, other pressure from inside it
G
Gear Scale
Quadrant
Evacuated space
N.O.
Scale Spring
N.C.
Compressor
L1
Micro switch
Stopper L2
Bellows
Measure pressure
I
Pressure Continuous Control (negative Feed-back Control)
To keep the pressure at a certain preset value ( ) is very important in the
industrial processes, namely chemical, medical or food processes. In order to implement
this type of pressure control (
'
%- (@ (1-), a device called “Sensor” is
employed (
&) to measure and generate a signed proportional to this pressure. This
signal may be electrical current in the range 4 -20 mA or pneumatic pressure in the
range 3 -15 psi .
Generally, the sensor is composed (
-') of two parts:
Elastic element (
), which converts the pressure into mechanical
displacement, such as Bourdon tube, Diaphragm, Bellows, Capsules etc., as shown in
figure (3.10).
Pressure Signal
Elastic Element Transducer
4 -20 mA
Bourdon tube Potienomter 3 -15 psi
Bellows LVDT 0.2 -1 bar
Diaphragm Pilot Valve 20-100 KPa
Capsules
This sensor uses a Bourdon tube as the elastic element and LVDT as the transducer.
The pressure causes a mechanical displacement of the free end of C- type Bourdon
tube, this will change the core position.
The LVDT operation. (Bourdon + LVDT page 272 Dally)
The schematic diagram is as shown in figure (3.12). When the pressure is zero, the
core is in the middle position between the two coils, the voltage across the two coils are
the same but of opposite sign, the LVDT output voltage Vout = V1 - V2 = 0.
When a pressure applied, the core moves up, its linkage (*. ) with coil 1 is greater
than coil 2, hence V1>V2 and the output Voltage Vout is proportional to the applied
pressure.
M
Note: Commercial LVDT can sense a displacement of 2 mm. It is reliable (!* !+),
stable and excellent for static or quasi static (7.$ F.# - 5 7.$) pressure measurement, its
limit freq. ≤ 10 HZ.
Secondary
Winding 1
Core
Vout =V1- V2
Supply
Core displacement
Primary
winding Secondary
Winding 2
This type is used for low and middle pressure range measurements 0 -30,000 psi.
The design of the SG must be very long to give a large enough resistance, it is made of
foil (fine wire), so that it does not resist the applied strain, it also must responds to strain
(. $ 6) only in one direction as shown in figure (3.13).
The normal SG resistance is 60, 120, 240, 350, 500 and 1000 Ω.
The resistance and volume of the strain gauge wire before applying the measured
pressure are given by:
ρ Lo
R o =
A o
∴ volum V = L o A o = ( L o + ∆ L )( A o − ∆ A )
Where:
Because both length and area have changed, the resistance will also change.
/N
L o+ ∆L Lo + ∆L
R =ρ =ρ
Ao − ∆ A L o Ao / Lo + ∆ L
(L + ∆ L )2 ρ
( )
R = ρ o = L 2o + 2 L o ∆ L + ∆ L 2
Lo Ao Lo Ao
ρLo
2
2 Lo∆L ∆ L2
R = (1 + + )
Lo Ao L 2o L 2o
Lo ∆L ∆L
R = ρ 1 + 2 = R o 1 + 2
Ao Lo Lo
∆L
∆R = 2Ro
L
∆ L
This means that the stain convents directly into a resistance change
L
Sensitive Direction
R1 R2 Dummy SG
+
Dummy SG Active SG
R3 R4
Applied force
Figure (3.13) Strain Gauge Connection Diagram.
∆R / R
Strain .Gauge . Factor GF =
strain
In the following table, an example of the Strain Gauge Factor G.F values of some
materials.
/
The bridge output voltage Vout = Va -Vb
Vs R3 V s R4
Va = and Vb =
R1 + R3 R2 + R4
R3 R4
Vout = Va − Vb = Vs −
R1 + R3 R2 + R4
Let the resistances are R1= R2= R3= R4= R0
The measured pressure P =0 Pa
No change occurs in the strain gauge resistance i.e R4 = R0
R0 R0
Vout = Va − Vb = Vs − = 0 volt
R
0 + R 0 R 0 + R 0
Vs
Vout = − strain × G.F
4
This output voltage is also called the offset voltage.
Example:
A strain gauge of 350 Ω with a gauge factor G.F =2.03 is used in a Wheatstone bridge.
A strain of 1450 µ m/m is applied. Find the voltage offset if the supply voltage Vs=10 v.
Solution:
Given: Ro = 350 Ω
G.F. = 2.03
Strain = 1450 µ m/m
Vs=10 v
The offset voltage is:
Vs 10 −6
Vout = − strain × G.F = − x1450 x10 × 2.03 = − 0.00735875v = −7.35875 mv
4 4
/
(iii) Piezo Electric Crystal
Piezo Electric Phenomina, when a Piezo electric materials, such as quartz or barium
titanate, when a crystal of these materials are subjected to (ض%! #) a pressure, a
charges polarization occurs (ت#9: ب#/%ث اﺱ9) on the crystal surfaces, and when the
crystal surfaces are coated (/$!) with metal electrodes (?ب ﻥ#/A )أ, we obtain an
output voltage as shown in figure (3.14). The output voltage is: q=VC
Where:
C Capacitance of the crystal.
q Charge developed on the crystal surface.
V Output voltage.
The se crystals are used in the following application: Sonar, Microphone and piezo fans.
+
Metal-coated plates
++++++++++++
Crystal ---------------- Vout
– _
The elastic member output displacement acts on the pilot value such that the
pneumatic pressure output is proportional to the applied pressure.
A Bourdon tube free end is connected to a valve in pneumatic system, which enables it
to control the air supply pressure as shown in figure (3.15) and figure (3.16).
Air supply
//
Bourdon Tube
Free end
Fixed end
Measured pressure P
closes the gap of the nozzle. A higher current produces higher force and hence higher
pressure. The position of the flapper relative to (! ..) the nozzle are designed such
x1 x2
Lever
b c
Nozzle Pivot
Force F
Bellows
P2
Air supply
P2
15psi
15psi
Force
/>
4 LEVEL MEASUREMENTS
Liquid level measurements are commonly employed in several marine
applications such as steam drum water boilers, tanks of fuel, oil etc.
The level measurement may be classified as: level display, level ON-OFF control and
level continuous control.
o Level display
A - Sight glass:
The tank, equipped with a sight glass with a float, such that the liquid in the tank can
be seen directly. As show in figure (4.1).
Sight glass
Float
This is a simple and reliable (!* !+) method for measuring the level of water, oil
and fuel in ship tanks.
A dip tube is inserted (J" ) in the tank, air under pressure is adjusted to be slightly
greater than the hydrostatic pressure at the end of the dip tube which is equal to ρgh, so
that a bubbles (72) will go out from the tube, in this case the air pressure indicated by
the pressure gauge Pg will equal to ρgh, where h is the liquid level as shown in figure
(4.2).
Note:
The gauge can be calibrated ()) to read level, volume or height of the liquid in the
tank.
/B
Dip tube
Rota meter
Air supply
Pressure gauge
Air valve
C -Whessoe tank gauge: This is a mechanical method used during loading, unloading
and ballasting operations to provide continuous level display on ship board. It consists
of stainless steel tape ( *# ) with a float at its end, while the float moves up and down,
it causes the rotation of the drum spindle which drives( - 9.) an AC transmitter
motor which generate (-) an electric signal, this signal is measured to display the
level.
Repeater
Spindle
Cable
Deck Alarm
Guide
Note: In marine applications, a tape with load and white scale is used also to measure
the fuel level in (heavy oil storage tank).
/E
o ON-OFF Level Control (Level Switch)
To control-alarm the liquid level between maximum and minimum levels, a level
switch is used. It consists of:
- Micro switch equipped with (9 -) permanent magnet of same polarity.
The micro switch has two set of contacts (7P
-), as shown
in figure (4.4).
i- Normally close contact NC, through which a pump is fed to fill the tanks.
ii- Normally opened contact NO, when the level reaches its maximum value the
float changes the state of the micro switch, the NO contact feeds the alarm circuit
and the pump stops.
This technique is used in level control in the tanks of boilers, purifiers and slugs oil
separators.
sensor may be mechanical, electrical, and ultrasonic or using the principle of pressure
measurement if the density of liquid is known.
/G
Mechanical:
The float is connected by a linkage to potentiometer or LVDT core as shown in
figure (4.5). Using LVDT is more accurate.
LDVT output
Electrical:
In this case, two concentric (' ) cylinders are contained in a liquid tank.
This device acts like two capacitors in parallel, one with dielectric constant of air (≈ 1)
and the other with that of the liquid. Thus the variation (") of liquid level causes the
To AC bridge
R Cair
Tank shell
concentric AC supply
cylinders
R Cliquid
Rectifier
Oil Separator
7 ! 2 Output signal
/I
Where:
K = Dielectric constant
Ultrasonic:
The use of ultrasonic to measure level is favored (!;1) because it does not involve
(!# ) placing any device in the tank also no moving parts. This technique may be
/M
Signal
Conditioning
Transmitter Receiver
a- External b- Internal
Example 4.2. For the outer type ultrasonic level system shown below, find the liquid
level given that:
* h + d = 2m
T R
* The time t = 2 X 10-3 sec.
* The speed of signal is 350 m/sec.
Note: The sound speed 340 m/sec.
h+ d
Solution:
2d 2d
v= = 350 =
t 2 × 10− 3
∴ d = 0.35m ∴ h = 2-0.35 = 1.65m
Note:
For measuring liquid level it is also possible to use the known relation between the
pressure at the bottom of the tank and the liquid head and liquid density.
Pressure (P) =density (ρ) x level head(h)x(g).
Differential pressure transmitter cell D/P cell
An output pneumatic signal is obtained from the cell which is proportional to head of
liquid in the tank.
>N
5 - TEMPERATURE MEASUREMENTS
Industrial temperature regulation (
) is important and becomes more with the
advance (-*) of technology.
5.1 Units
The range between the freezing and boiling points of water at a pressure of one
atmosphere (101,3 KPa) is divided in different scales, Celsius scale, Fahrenheit scale
and Absolute scale.
- Celsius scale o C has 100 divisions between these points.
- Fahrenheit scale o F has 180 divisions between these points.
- Absolute scale (Kelvin) o K = o C + 273.15 o K
To convert from ( !-+) Fahrenheit scale to Celsius scale use the formula:
Note The temperature -273.15 value is the zero thermal energy, i.e. no molecular
vibration. ( Absolute zero)
Solution
a- T(o K ) = T(o C)+ 273.15 = 144.5 + 273.15 = 417.65 o K
b- T(o F) = 32 + (9/5) T (oC ) = 32 + (9/5) X 144.15 = 292.1o F
>
5.2 Expansion Thermometers ( 7 -$ )
In the expansion thermometers solids, liquids or gases are used as sensing elements.
VT = VO ( 1+β ∆T )
Where:
VT, Vo Volumes after and before expansion.
β Coefficient of volumetric expansion ( F9 د ا% ا#).
∆T Temperature change.
• Temperature display,
• ON -OFF control and
• Continuous control.
>
5.3 Methods of Temperature Measurements
Temperature Display
The temperature can be displayed:
• Locally (,);-) at the process by:
Bulb
Sensing head
Hg
>/
Remote temperature Display
There are 3 types, which can be used for remote display, alarm or temperature
control. All involve (,+ !#) the use of a bulb (W1 ) at the sensing end, and a
capillary tube ()# .-. 5 ) connecting the bulb to on elastic element (Bourdon tube,
Bellow, etc), which responds to pressure change due to temperature variation as shown
in figure (5.2).
Scale
Bourdon tube
Gear
Quadrant Link
>>
Temperature ON - OFF Control
Using a Bi-metal strip and micro switch to control temperature within upper- lower
limits. This type is applied to control the temperature of:
Iron (J.P -'), Air-condition, and Heaters.
Heater
Micro Supply
B Switch Alarm
A
Heater
Micro Supply
Switch Alarm
B
>B
1- Gas Filled Thermometer
A measuring bulb is filled with Helium, Nitrogen --- etc. Using the flapper nozzle
Differential Pressure (D/P) cell, the output of the sensor is a pneumatic signal. The
pressure of the gas in the bulb changes with temperature variation. An output pneumatic
pressure is obtained from the DIP cell proportional to this variation, as shown
in figure (5.4). The main disadvantage is that the gas can slowly diffuse through the
metal bulb (,) W1
9) with time.
The sensor consists of a resistant wire wounded around a mica frame. Operation
depends upon the change of the wire resistance when subjected to temperature change.
The resistance at a temperature T o C is given by:
RT = Ro ( 1 + α ∆T )
Where: ρ L
RT R=
A
RT Resistance at T o C. Nickel
o
Ro Resistance at 0 C.
Platinum
∆T Temperature change. Ro
α Temperature coefficient.
Temperature T o C.
>E
The wire may be of Platinum or Nickel, the wire diameter range: 0.02 to 0.8 mm.
The sensor output is taken via a wheat-stone bridge circuit as shown in figure (5.5).
o
The bridge is balanced at 0 C. When the temperature changes the value of RTD
resistance increases, and causes the bridge unbalance, an output voltage appears at the
output terminals (جMاف اO) أ, which is proportional to the temperature change.
A three wires sensor is used to compensate (- +%) the change of the connecting
wire resistance running in different ambient temperature ( P%M /9 ت ﺡارة#)درﺝ.
The RTD resistance element has a resistance = 100 Ω at zero degree o C.
The range is - 200 o C to 600 o C for Platinum.
The range is up to 1200 o C. for Tungsten.
The range is - 180 o C to 300 o C for Nickel.
R R
Output
+
Amplifier _
R
Insulator (Mica)
Platinum wire
Example 1.5
o
A platinum resistance thermometer has a resistance of 140.5 Ω at 100 C. If its
resistance becomes 305.3 Ω when it is in contact (R1S) with hot gas. Determine the
temperature of gas ( Temp. coeff. α = 0.0039 o C-1 )
Solution
RT=R1[1+ α ∆T ]
R2 − R1 305.3 − 140.5
∴TT − T1 = TT − 100 =
αR1 0.0039 x140.5
o
TT =100 + 300.756 =400.756 C
>G
3- Thermo-Couples T / C. (Discovered by See Beck in 1821)
If two wires of copper and iron are connected together and the junction is heated, an
electro motive force emf is generated, the current flows from copper (+) to iron (-) at
the hot end, as shown in figure (5.6).
B Iron ( - ) emf
Gauge linear
C
C Copper (+)
285
Temperature difference ToC
B
Terminals
C
Insulator
Hot junction
Figure (5.6) Thermocouple
The generated emf in the thermocouple given by the relation: E =K (Thot - Tcold)
Where:
E the generated emf.
K thermocouple sensitivity.
Thot,Tcold hot and cold temperatures.
Example:
A Copper – Constantan T/ C was calibrated between 0 o C to 400 o C, the generated emf
is 20.68 mv at 400 o C (while the cold junction temperature at 0 o C).
a) Determine the correction (U9V%) ا, which must be made to the indicated emf if
the cold junction temperature is 25 o C.
b) If the indicated emf is 8.92 mv in the T / C circuit, determine the temperature of
the junction.
Solution
a) T/ C sensitivity =20.86 / (400) = 0.0517 mv / o C
Since the T/ C is calibrated at the cold junction at 0 o C and the T/ C is being used at
25 o C, then the correction which must be made between 0 o C and 25 o C is:
Ecorr. = 0.0517x25 o C =1.293 mV.
b) Indicated emf of the hot junction = 8.92 mv.
The temperature of the hot junction is 8.92 / 0.0517 = 172.53 o C.
>I
Since the cold junction at 25 o C, the hot junction temperature is: 172.53+25=197.53 o C
Range of temperature measurement of T/ C: Start from - 250 o C and with special alloys
( WX#){ )ﺱ90% Platinum, Rhodium and 10 %platinum), can reach 1400 o C, as shown
in the following table.
4 -Thermistors
In the semi-conductor device, electrons are bounded to each molecule -' )
(70.. When temperature increased, the valence electrons will get free of molecules
(70 ), and the semi-conductor material become conductor ( H.#5 T. -
>M
+ - - 7P - ), and its resistance decreases as temperature increases as shown in
20
0.2 mm
10
Protective glass
0
o
-2 0 0 25 50 75 100 T ( C)
o
Example 5.2: A thermistor has a constant β = 3140 K, and a resistance 1050 Ω at
o .
27 C At the measured temperature, the resistance is 2330 Ω find the measured
temperature T
Solution
Given : To = 300 o K, Ro = 1050 Ω, R = 2330 Ω
1 1
R = Ro β −
e
T To
1 1
∴ LnR − LnR = β −
T O
o
T
LnR − LnR 1 1 7 . 754 − 6 . 957 1 −3
o
+ = = + = 3 . 587 × 10
β TO T 3140 300
BN
Advantages
- Thermistor is strong and rugged (Y), so it is suitable for:
Disadvantages
- It has a wide range of resistance, but the range depends on the semi-conductor
material, hence depends on:
▪ Melting temperature of the semi-conductor material, the upper limit is 300 o C.
▪ Encapsulating materials (a$%( )اد اplastic, epoxy, Teflon), which protects the
sensor from environment ($:%وف اb). This material constrains (!) the upper
limit temperature.
▪ The sensor sensitivity decreases with higher temperatures, as the resistance of the
material is very small.
- The power dissipated must not exceed the specified ratings of thermistor ( (E اA#/ا
دة9 ا$:% اA#O ى%!S أنdF E(%1 ) ا.
5- Pyrometers:
The temperature is measured by using the radiations (ت#[#)ﻥS )اfrom the hot body,
(non contact thermometer), in the range of ultra violet, visible and infrared radiations.
The speed of response is very high (few micro seconds). There are 3 types of
Pyrometers:
i – Optical Pyrometers:
A very accurate method for measuring temperature between 600 and 3000 o C.
It measures the temperature by comparing the brightness of the hot body ( ن# رﻥ#
-3#1 ا01F ) اwith the known brightness of a lamp, (tungsten lamp).
By varying the brightness of the lamp so that it just disappears ( ن# * ح#)V ا%* P%M!
-3#1 ا01F ) اinto the hot body viewed through the lens. The temperature can be
measured from the meter reading. As shown in figure (5.8).
The main disadvantage is that it is limited to temperature > 700 o C only.
B
Eye piece Red glass Lamp Screen Objective lens Hot body
(Filter)
Source filament
Pyrometer filament
The the main parts of the pyrometer are as shown in figure (5.9).
The emitted radiation is focused ( # !آه0% e) ت ا##ﺵS )اon a RTD or T / C,
the temperature change is measured in the usual way as in the case of RTD and T / C..
This type of pyrometer can be used for automatic temperature control.
Mirror
Hot
Body
Meter
B
iii - Photo Electrical Pyrometer
This detector has a very high-speed response ( ﺱ ﺝا#F% )اﺱand can give a high
output volt / watt of radiation, it is also very useful in automatic control purposes.
Note:
Thermistor, RTD and TC. make direct contact with the source of heat. Pyrometers
does not make direct contact with the source of heat.
B/
6 FLOW MEASUREMENTS
depends on the plant and the fluid used. For air-craft, the fuel meter must
be compact (
') and not affected by the craft orientation ( ?;-. $6 -
!'K O+ -). On the other hand in marine applications, the heavy fuel
flow meter is used, where the heavy fuel may be corrosive and contains
foreign matters (90 -#). Also factors such as (!$ ! -) range, accuracy,
meters:
6.1 Units
Unit
Parameter SI
English
Volume flow rate m3/hr ft3/ hr
Flow velocity m / min. ft
/min.
B>
The flow velocity is given by V = Q / A
Where:
V flow velocity ( m / min ).
Q volume flow rate ( m3/min).
A cross– sectional area of the pipe (m2).
The Mass flow rate is given by M = ρ Q
Where:
M mass flow rate (Kg/ hr).
ρ mass density (Kgm3).
- Pipe size.
- Pipe friction (- ,2 Y' ).
(9-$ T*).
BB
This type is used in flow applications of both liquids and gases. Many
devices are classified as Obstruction flow sensor such as: Rota-meter,
mechanical turbine and electrical turbine flow meters.
1- Rota-meter:
A commonly used variable area flow meter (to maintain steady pressure
difference (7.$ *"; :2 ,+ 2 ). The fluid enters the vertically placed
tapered tube (.- .-.5), causes the float to move upwards.
The position of the float on a scale indicates ( .) the flow rate, as shown
in figure (6.1).
Float stop
Scale Float
Float stop
Flow inlet
Advantages:
- Direct visual display of the flow on a linear scale.
- Range from 0.1 liter / min. to several hundred liter / min.
- Accuracy ± 1 % of the maximum flow rate.
- Wide variety of fluids (!0 -
1+& % -5) including corrosive fluids can
be used.
BE
Disdvantages:
- The Rota-meter must be placed vertically.
- It is sensitive to pulsating (7.$ 8 –D.) flow.
A cast iron body with brass inner chamber (1 J +& 28),
a rotor with vans, spindle rotating in frictionless bearings ( -. - -
Y' ), the gearing mechanism ( - ) indicates the flow rate as
A low friction rotor, such that the rotation rate proportional to the flow
rate, the rotor is equipped with (9 - -;) ) a magnet. The rotor
BG
- ) is proportional to the fluid flow rate as shown in figure (6.3). The
figure shows a floating rotor type, to reduce friction (Y' !+), the AC
BI
Orifice plate
Flow
h
P
P
Pressure
Flow
A 1 & V1 A 2 & V2
Applying the Bernoulli theorem to deduce ([) the relation between
1
1
2
ρV1 + P1 =
2
ρV 22 + P2 potential energy = gh = cons .
2
(V 2
2
− V12 = ) 1
ρ
(P1 − P2 ) (1)
2 BM
A1
V 1 − V 1 2 = ρ (P1 − P2 )
A2
V 1 A1 = V 2 A 2 (2) continuity equation .
A1
∴V2 = V 1
A2
A 2
V1 2 1 − 1 = 2 (P − P )
A 2 2 (P − P ρ) 1 2
V1 = 1 2
A 12
ρ 2 − 1
A2
2 (P1 − P 2 )
Q = A1 A 2
(
ρ A 12 − A 22 )
Practically, the flow rate is much less than this value because of friction
and losses. Hence a discharge coefficient (cd) must be used. This
coefficient can be determined by calibration.
The mass flow rate is dm / dt
2 (P1 − P2 )
m& = ρ V = ρ A 1 A 2
(
ρ A 12 − A 22 )
The above equation can be written as:
m& = K ∆P
Where:
2
K = Cd ρ A1 A2 constan t
ρ ( A12 − A22 )
EN
This equation means that the flow rate is proportional to the square root
∆ P = P1 − P2
of the pressure difference.
Practically, the sensor is classified as a restriction meter and can be
implemented (H(1) using different constructions as shown in figure
(6.4).
Venturi tube flow meter is not commonly used, as it is more expensive.
Orifice tube flow meter (1 F-#- !'K+ D)), is simple and commonly
used (
& ?0#). Nozzle tube flow meter, needs shorter length
of a straight pipe, less susceptible to corrosion (!'K+ ; ! 5), unlike the
orifice type.
figure (6.5 )
such that: e = β .d .
Where:
e Potential difference.
E
β Magnetic flux density. (field strength)
d Pipe diameter.
V Velocity of flow.
Supply
Flux
Flow Magnetic flux
Stainless s.
(Platinum)
Electrodes
e
Flow V
E
Flow is to be to controlled from 20 gal/min to 150 gal/min. The flow is
measured using an orifice plate system. The orifice constant K = 119.5 gal
/min / (psi)1/2. A bellows measures the pressure with an LDVT, so that the
output is 1.8 volt/psi. Find the range of voltages that results from the given
flow range.
Solution.
20 gal/min ∆p = (20/119.5)2 = 0.028 psi
150 gal/min ∆p = (150/119.5)2 =1.5756 psi
The voltage range is:
0.028 × 1.8 = 0.0504 volt
1.5756 × 1.8 = 2.836 volt
E/
7 VISCOSITY MEASUREMENTS
7.1 Introduction
Viscosity is defined as internal friction (ك#E% )اﺡbetween the fluid layers or the
resistance of flow within the fluid. It is one of the major factors of energy dissipation in
fluid (gas) transportation in pipelines (d#ﻥi * اIX ا اP! ء#[ أA#/ اP 1X)أﺡ اا ا.
Also the study of viscosity is very important in the study of lubrication and wear’s
characteristics ( آj% واR%اص ا3 )دراﺱ اوﺝ ( دراﺱ.
In the discussion of flow measurement, we assume an ideal fluid, i. e. we
neglect the viscosity. We proved that the flow = K √ ∆P . In general
laminar flow, viscosity must be considered ( 9 ,.* :2 ,2 -
dV
Newton’s law of viscosity F = µ A
dx
Where:
dV
F Shear force F = µ A also called viscous drag
dx
force.
µ Coefficient of dynamic Viscosity N.sec/m2( Stoke)
dV
dx Velocity gradient ( ) (V meter / sec).
τ τ = A
Shear stress force between the fluid layer
F
N /m
2
A
V
Shear force F x
Vo
µ
ρ
E>
• Kinematic Viscosity: It is the ratio of dynamic viscosity to the fluid
density
• The viscosity increases as temperature decreases.
The following table shows the viscosity of some fluids at 20 o C.
Reynolds’s number
Experiments show that NR < 2000 Laminar flow motion.
NR >3000 Turbulence flow motion.
7.2 Methods of Viscosity Measurements.
Viscosity sensor
The viscosity is measured by forcing a small quantity of oil at a constant
rate (via a gear pump), through a capillary tube ()# .-.5 ) as
Outlet
Gear pump
EB (7.1) Visco-detector
Figure
Example 7.1.
In a capillary tube visco -meter, the tube diameter is 0.05 m, a shearing
force of 100 N is applied to the flow tube, if the velocity gradient is 5 sec-1,
the diameter of the capillary tube is 0.02 m , head of the tank is 0.8 m and
specific density ρ is 0.7 Kg / m3 . Determine the fluid
viscosity.
dv
Solution The shearing force F = µ A
dx
Π d 2
Π (0 . 05 )2
A = =
4 4
F 100 × 4
µ = = = 10185 . 91 kg / m . sec
A (dv / dx ) 25 Π × 10 − 4 × 5
EE