RTT20
RTT20
RTT20
February 2016
RTT20
I/A Series® Temperature Transmitter
Installation, Configuration, Operation,
Calibration, and Maintenance
Style A
MI 020-453 – February 2016
2
Contents
Figures ........................................................................................................................................... 5
Tables ............................................................................................................................................ 7
1. Introduction .............................................................................................................................. 9
General Description ....................................................................................................................9
Transmitter Identification..........................................................................................................10
Reference Documents ...............................................................................................................10
Standard Specifications..............................................................................................................11
Operating Conditions .........................................................................................................11
Functional Specifications......................................................................................................11
Physical Specifications ..........................................................................................................15
Electrical Certification Rating ...................................................................................................15
Electrical Safety Specifications ..............................................................................................15
ATEX Warning.....................................................................................................................17
IECEx Warning....................................................................................................................17
FM and CSA Warnings ........................................................................................................17
ATEX Compliance Documents ............................................................................................17
CENELEC Compliance Documents ....................................................................................18
IECEx Compliance Documents ...........................................................................................18
2. Installation .............................................................................................................................. 19
Unpacking ................................................................................................................................19
Transmitter Mounting...............................................................................................................19
DIN Rail Mount ..................................................................................................................20
Pipe or Surface Mount..........................................................................................................20
Surface Mount without Bracket............................................................................................20
Bare Sensor Mount...............................................................................................................21
Thermowell Mount ..............................................................................................................21
Mounting Basic Transmitter in Old Style Housing ...............................................................21
Positioning Transmitter to View Optional Indicator..................................................................22
Cover Lock................................................................................................................................22
Transmitter Wiring ...................................................................................................................23
Power Supply Requirements for HART Transmitters............................................................23
Conduit Drainage ................................................................................................................24
Hazardous Locations ............................................................................................................24
Sensor Connections and Wiring ...........................................................................................26
3
MI 020-453 – February 2016 Contents
Loop Wiring.........................................................................................................................29
Grounding (Earthing) ..........................................................................................................34
HART Multidrop Communication ......................................................................................34
3. Operation................................................................................................................................ 37
4. Configuration.......................................................................................................................... 39
Configurable Parameters ...........................................................................................................39
Parameter Descriptions .............................................................................................................44
Indicator/Configurator..............................................................................................................47
Configuration Procedure ......................................................................................................49
5. Calibration .............................................................................................................................. 51
Trimming 4 to 20 mA Output ..................................................................................................51
Input Calibration ......................................................................................................................52
N-Point Calibration ..................................................................................................................52
Custom Curve Calibration ........................................................................................................53
6. Maintenance............................................................................................................................ 55
Troubleshooting Problems.........................................................................................................55
Replacement of Integrally Mounted Sensor ...............................................................................59
Replacement of Basic Transmitter..............................................................................................59
4
Figures
1 Transmitter Identification....................................................................................................10
2 DIN Rail Mount.................................................................................................................20
3 Pipe or Surface Mount ........................................................................................................20
4 Surface Mount without Bracket (Rear View) .......................................................................20
5 Bare Sensor Mount..............................................................................................................21
6 Thermowell Mount.............................................................................................................21
7 Locating New Holes in Existing Mounting Plate.................................................................22
8 Cover Lock..........................................................................................................................23
9 Recommended Conduit Routing ........................................................................................24
10 Single RTD Wiring .............................................................................................................26
11 Dual RTD Wiring...............................................................................................................27
12 Thermocouple or Voltage Wiring........................................................................................29
13 Typical Transmitter Wiring to an I/A Series System.............................................................31
14 Voltage and Load Limits......................................................................................................31
15 Typical Transmitter Wiring with a 4 to 20 mA Output .......................................................33
16 Wiring Several 4 to 20 mA Transmitters to a Common Power Supply.................................33
17 Typical Multidrop Network.................................................................................................34
18 3-Line Indicator ..................................................................................................................48
19 Addition of Indicator/Configurator.....................................................................................48
20 Indicator Configurator Flowchart........................................................................................50
21 4 to 20 mA Output Calibration Setup ................................................................................51
22 Input Calibration Setup ......................................................................................................52
5
MI 020-453 – February 2016 Figures
6
Tables
1 Reference Documents .........................................................................................................10
2 Operating Conditions .........................................................................................................11
3 Input Types .........................................................................................................................13
4 Range Limits, Maximum Span, and Accuracy (a) ................................................................14
5 Electrical Safety Specifications.............................................................................................16
6 RTT20 with Intelligent Output (Code- D).........................................................................40
7 RTT20 with HART Output (Code- D) ..............................................................................41
8 RTT20 with 4 to 20 mA Output (Code-I)..........................................................................43
7
MI 020-453 – February 2016 Tables
8
1. Introduction
General Description
The RTT20 I/A Series Temperature Transmitter is a microprocessor-based, two-wire device for
converting various mV and ohm type sensors into a linear 4 to 20 mA or digital output. A
standard two-wire system provides a nominal 24 V dc power to the transmitter and also carries
the output signal to a receiver tied into the loop wiring. There are three different output types
with communications capabilities as follows:
Output Code -I: 4 to 20 mA without remote communications
Output Code -T: 4 to 20 mA output with HART communication
Output Code -D: 4 to 20 mA or FoxCom™ digital communication
The microprocessor-based transmitter was designed for easy installation in a wide variety of
applications. The major differences between the three output types is in communications. The
optional 1-Line and 3-Line Indicator/Configurators are designed to enable the user to locally
reconfigure any transmitter database. A single indicator can be easily moved from one transmitter
to another. No tools are required to install or remove it. Simply plug it in and make the desired
adjustments to the transmitter. Then remove it and move on to the next transmitter. The 4 to
20 mA transmitter (Output Code -I) can only be adjusted using these Indicator/Configurators
because there is no remote communications capability. Whenever the local
Indicator/Configurators are used for reconfigurations, the loop must be put in manual. As a safety
feature, the output will be held at the last value until the transmitter is returned to the operational
mode.
The HART and FoxCom protocol transmitters have an internal modem to enable the database to
be remotely reranged or reconfigured as follows:
HART protocol – with a HART Communicator or a Foxboro PC-based configurator.
FoxCom protocol – with a PC-Based Configurator and/or from an I/A Series system.
All of the remote configurators can communicate with the transmitter from any wiring
termination point in the loop. This allows the transmitter to be installed in hazardous locations or
areas which are not at grade level. The configurator can only be used in an area for which it is
rated. Communication between the remote configurator and the transmitter is based upon the
Frequency Shift Keying (FSK) technique. Since the FSK tones do not add any current to the two-
wire system, reading transmitter data does not interfere with the output signal. When new
configuration data is being downloaded into the transmitter, however, the output is interrupted
and the loop must therefore be put in manual. The transmitter with FoxCom protocol can also be
digitally integrated into an I/A Series System and reconfigured with any of the system
workstations, eliminating the need for the separate configurator.
The microprocessor-based transmitter has been designed to accept a wide variety of mV and
resistive sensors:
9
MI 020-453 – February 2016 1. Introduction
♦ Thermocouples
♦ RTDs (2, 3 or 4 wire)
♦ Millivolt dc sources
♦ Resistive Sensors (Ohms measurement)
♦ Dewpoint Sensors (Foxboro Model 2781)
The input and output characteristics are determined by the configuration information loaded into
the transmitter at the factory. This configuration can be easily changed using the
Indicator/Configurators or any of the various remote configurators.
Transmitter Identification
See Figure 1 for typical transmitter data plate contents. For a complete explanation of the Model
Number code, see PL 008-659.
NOTE
Figure 1 shows a typical data plate. For a recapitulation of the specific information
that applies to each agency certification, see “Electrical Certification Rating” on
page 15.
DATA PLATE
Reference Documents
This document contains information on installation, configuration, operation, calibration, and
maintenance of the RTT20 Transmitter. Additional information about the transmitter and the
remote configurators are contained in the documents listed in Table 1.
Table 1. Reference Documents
Document Description
MI 020-460 Operation, Calibration, and Configuration Using a HART Communicator
MI 020-484 HART Model 275 Communicator Messages
MI 020-495 PC20 Intelligent Transmitter Configurator
MI 020-501 PC50 Intelligent Field Device Tool (Installation and Parts List)
MI 020-504 PC50 Intelligent Field Device Tool (Operation Using HART Protocol)
MI 020-505 PC50 Intelligent Field Device Tool (Operation Using FoxCom Protocol)
PL 008-659 Parts List - RTT20 I/A Series Temperature Transmitter
DP 020-460 Dimensional Print - I/A Series Temperature Transmitter
10
1. Introduction MI 020-453 – February 2016
Standard Specifications
Operating Conditions
Table 2. Operating Conditions
Reference Operating
Influence Conditions Normal Operating Conditions
Ambient Conditions
Without Integral Display 24 ±2°C (75 ±3°F) -40 to +85°C (-40 to +185°F)
With Integral Display 24 ±2°C (75 ±3°F) -29 to +70°C (-20 to +158°F)
Relative Humidity 50 ±10% 0 to 100% (noncondensing)
Supply Voltage 30 ±0.5 V dc 12 to 42 V dc
Vibration 0 m/s2 (0 g) 30 m/s2 (3 g) maximum(a)
Functional Specifications
Input Types and Range Limits See Table 4.
Span Limits Minimum: 5°C (10°F).
Maximum: See Table 4.
Output Types 4 to 20 mA.
4 to 20 mA with HART communication.
4 to 20 mA or FoxCom digital communication.
Two-Wire Transmitter The same two wires are used for input power, output signal, and remote
communication.
Input Response Time With minimum damping, the 90% response time for an 80% input step is
1.2 seconds.
Electronic Damping 4 to 20 mA Version: 1.2 seconds
.
HART Version: Damping is set as a floating decimal point value between 0
and 32 seconds.
11
MI 020-453 – February 2016 1. Introduction
Supply Voltage
1304
Requirements and External Loop
RMAX = 43.5 (Vs-12)
Load Limitations 1200
1000
Maximum loop resistance (ohms)
X)
800
MA
(R
AD
LO
600
UM
XIM
MA
400
250
200
0
0 5 10 15 20 25 30 35 40
12 42
Supply voltage (Vs), V dc
NOTES:
1. MINIMUM LOAD WITH HART COMMUNICATOR OR PC-BASED CONFIGURATOR
CONNECTED IS 250 Ω.
2. CONNECTING A PC-BASED CONFIGURATOR OR HART COMMUNICATOR WHILE
OPERATING BELOW THE MINIMUM SPECIFIED LOAD MAY CAUSE COMMUNICA-
TION PROBLEMS.
12
1. Introduction MI 020-453 – February 2016
Dual Sensors
13
MI 020-453 – February 2016 1. Introduction
14
1. Introduction MI 020-453 – February 2016
Physical Specifications
Basic Transmitter Polycarbonate with molded ryton terminal block.
Screw terminals of nickel over copper-plated steel.
Mounting Options Option Code Bracket Hardware
Mounting Set -M1 Epoxy-Coated Steel Plated Steel
Stainless Steel -M2 Stainless Steel Stainless
Mounting Set Steel
DIN Rail Hardware -D1 Aluminum and Plastic Plated Steel
Enclosure Construction Housing: Epoxy-coated, low-copper aluminum or 316 ss.
Union coupling (thermowell only): zinc plated steel or 316 ss.
Environmental Protection Housing: NEMA 4X, IP66.
Approximate Mass Basic Transmitter Package: 0.13 kg (0.28 lb).
Aluminum Pipe or Surface Mount Housing: 1.47 kg (3.25 lb).
316 ss Pipe or Surface Mount Housing: 3.25 kg (7.25 lb).
3-Line Indicator: Add 0.06 kg (0.13 lb).
Housing Connections (2) 1/2 NPT (see note below)
NOTE
Housings with optional PG 13.5 connections are available except in transmiters that
are certified for explosionproof/flameproof installations.
! DANGER
To prevent possible explosions and to maintain explosionproof, dust-ignitionproof
protection, observe applicable wiring practices. Plug any unused conduit opening
with a metal pipe plug, which engages a minimum of five full threads.
! WARNING
To maintain IEC IP66 and NEMA Type 4X protection, any unused conduit opening
must be plugged with a metal plug. In addition, the threaded housing cover must be
installed. Hand tighten cover as much as possible so that the O-ring is fully captured.
15
MI 020-453 – February 2016 1. Introduction
16
1. Introduction MI 020-453 – February 2016
ATEX Warning
! WARNING
Do not open while energized.
IECEx Warning
! WARNING
Do not open when energized or when an explosive atmosphere may be present.
! WARNING
Substitution of components may impair intrinsic safety.
! WARNING
Keep cover tight while circuits are alive.
17
MI 020-453 – February 2016 1. Introduction
18
2. Installation
The following material provides information and procedures for installing the RTT20
Transmitter. For dimensional information, refer to DP 020-460.
NOTE
Use a suitable thread sealant on all connections.
! CAUTION
Bare sensor or thermowell mounting to the 316 ss housing should not be used in high
vibration areas.
Unpacking
Upon receipt, inspect the package for any sign of damage that may have occurred in shipping.
Immediately report any shipping damage to the shipping agent/carrier. The carrier may not honor
any claims unless all shipping material is retained for examination. After examining the packaging
and removing the contents, save the carton and packaging material in the event the transmitter
needs to be returned for any reason.
Transmitter Mounting
The basic transmitter can be mounted on a DIN rail or to a flat surface. The transmitter in a field
housing can be pipe mounted, surface mounted, mounted directly to a bare sensor, or thermowell
mounted. See Figures 2 through 6. For extremely high process temperatures, a remote mounted
sensor is recommended. Also, the mounting stability can influence how the sensor is attached to
the transmitter. If the process vessel is highly insulated and the thermowell has considerable
lagging, a remote mounted transmitter attached to a 50 mm (2 inch) pipe is recommended.
When mounting the transmitter, take into account the necessary room to remove the cover if you
wish to use the indicators or remote configurators at the transmitter. The housing can be
mounted in any position. The module can be rotated in 90 degree increments to align the
optional indicator for easy viewing.
19
MI 020-453 – February 2016 2. Installation
64.8
2.55
55.9
2.20
mm
inch
20
2. Installation MI 020-453 – February 2016
Thermowell Mount
LAGGING
PROCESS UNION
COUPLER
WELL
INSULATION
FILLER
21
MI 020-453 – February 2016 2. Installation
0.164-32 UNC-2B
2 HOLES 16.5
0.650
33.0 mm
1.300 inch
! CAUTION
Do not over-tighten the mounting screws.
Cover Lock
A housing cover lock is provided as standard with certain agency certifications and as part of the
Custody Transfer Lock and Seal option.
To lock the cover on the housing, screw the cover onto the housing as far as possible, place the
clamp as shown below and tighten the clamp screw. Insert the seal wire through the clamp and
crimp the seal if applicable.
22
2. Installation MI 020-453 – February 2016
EXTERNAL
GROUNDING
SCREW
CLAMP
SCREW SEAL WIRE
Transmitter Wiring
Your transmitter must be installed to meet all local installation regulations, such as hazardous
location requirements and electrical wiring codes. Persons involved in the installation must be
trained in these code requirements. To maintain agency certification, your transmitter must also
be installed in accordance with the agency requirements.
! WARNING
On transmitters with Housing Code L, M, S, T, W, and Y. to maintain IEC IP66 and
NEMA Type 4X protection, any unused conduit opening must be plugged with a
metal plug. In addition, the threaded housing cover must be installed. Hand tighten
cover as much as possible so that the O-ring is fully captured.
NOTE
It is recommended to use transient/surge protection in installations prone to high
levels of electrical transients and surges.
The ripple and noise specifications prevent direct interference with the HART signals. The
impedance limit ensures that HART signals recognize the power supply as a low impedance path,
and prevents inadvertent coupling of multiple HART loops when powered from a common
power supply. (The resistance of output fuses, if any, must be included when measuring this
value.) The power supply voltage limits are determined by the instruments in the loop, and not by
requirements of HART protocol.
23
MI 020-453 – February 2016 2. Installation
Conduit Drainage
The transmitter is completely sealed to resist moisture. However, improper routing of conduit for
the power or sensor wires can allow moisture to collect inside the housing and provide
conductivity paths between the various screw terminals. This can cause errors until the housing is
dried out. Therefore it is preferable to run conduit below the transmitter as shown in Figure 9. If
you must run conduit above the transmitter, a conduit seal at the housing is advisable.
TRANSMITTER
TO SENSOR
LOOP WIRING
DRAIN
In extremely humid environments where the conduit cannot be installed with recommended
conduit drains as shown in Figure 9, It is recommended to install a poured conduit seal at the
conduit entries of the housing. This will eliminate the conduit moisture from entering the
housing. Make sure to use a silicone sealing compound at all threaded connections between the
poured seal and the transmitter housing.
One manufacturer of poured conduit seals is Cooper Industries, Crouse-Hinds Division (Phone
315-477-7000 in U.S.A.).
Description Part Number
Connection for 1/2 inch conduit thread EYS 116
Sealing Compound CHICO A3
Fiber Fill CHICO X4
Hazardous Locations
General
When using the RTT20 transmitter in a hazardous location, care must be taken to ensure proper
installation practices per the applicable agency requirements. The housing was designed for
explosionproof installations. In addition, the basic transmitter is available for intrinsically safe and
nonincendive operation. Each transmitter and housing has a label indicating the hazardous
location approvals. To maintain the certified rating, the transmitter must be installed per the
applicable code requirements.
24
2. Installation MI 020-453 – February 2016
! WARNING
The following information can only be considered as general information and the user
is responsible for proper installation in hazardous areas per the applicable agency
codes and guidelines.
25
MI 020-453 – February 2016 2. Installation
– +
1 4
2 3
2-WIRE RTD 3-WIRE RTD
1 4 1 4
2 3 2 3
RED
RED WHT
RED WHT
JUMPER JUMPER
GRN WHT
BLK
Three and four wire RTDs are compensated up to 40 Ω for each lead. This is approximately equal
to 1220 m (4000 ft) of 20 gauge wire. The total resistance including the RTD and the two lead
wires is:
180 mV 0.180 V
-------------------- = ------------------------ = 600 Ω
0.3 mA 0.0003 A
Therefore, if a platinum RTD is used to measure a maximum temperature of 1292 °F (700 °C),
the RTD resistance is 345 Ω and the maximum permissible lead wire resistance (for both leads
combined) is:
600 Ω – 345 Ω = 255 Ω
You may calculate the maximum permissible lead wire resistance for other RTD applications in a
similar manner.
For a single 2-wire RTD, the extension leads are in series with the sensing portion of the RTD, so
lead length should be minimized. If the distance between the transmitter and sensor is “long”,
change the RTD to a 3- or 4-wire RTD.
The “lead length” errors associated with two-wire RTDs are:
26
2. Installation MI 020-453 – February 2016
RED 2 3
WHT RED
WHT
JUMPER
RTD #1 RTD #2
For dual RTD measurements (not available with convention Output Code -I), the RTDs can only
be 2-wire. The RTT20 cannot have dual 3- or 4-wire RTDs. Also, the 2-wire RTDs must be the
same type and the extension lead resistance will be added to the RTD measurement, creating an
error. For dual measurements, it is recommended to hold the extension to an absolute minimum
to avoid errors.
The local 1-line and 3-line indicators do not have the ability to configure the transmitter for dual
RTDs (remote configurator must be used). The dual RTD choices are:
♦ Difference
♦ Average
♦ Independent (HART version only)
! CAUTION
After sales release of the product, it was discovered that the Redundant operation does
not work properly. If RTD #1 fails, the output will switch automatically to RTD #2,
only if RTD #1 fails shorted. If RTD #1 fails open, the output goes to failsafe
conditions. Therefore, this selection is removed from the remote configurator
software.
27
MI 020-453 – February 2016 2. Installation
! CAUTION
Do not ground the shielding at both the transmitter and the sensor under any
circumstances.
Other Recommendations:
♦ Do not run sensor extension wires in the same conduit as the 4 to 20 mA loop wires
or power cable
♦ Twist wires together to improve noise resistance
♦ Make the extension wires the same length (without splices)
♦ Periodically check terminations at each end to ensure that terminal screws are tight
and that no significant surface corrosion as developed.
The above items are recommendations, not absolute requirements. The primary issues, when
using extension wire to connect a 4- or 4-wire RTD sensor to the RTT20 Transmitter are:
♦ To make a secure wire to terminal connection with minimal contact resistance
♦ To make the wires the same length with no added splices or interconnections between
the sensor terminals and the transmitter
♦ To protect the wires from picking up environmental noise by using proper shielding.
28
2. Installation MI 020-453 – February 2016
2 3
JUMPER
1 4
2 3 +
2 3
+ –
+ –
T/C 2
JUMPER
+
T/C 1 JUMPER
Thermocouple extension wire must be the same type as the thermocouple used. It is
recommended that extension wires should be twisted with an overall shield to avoid extraneous
noise pickup. The shield should be grounded at the sensor.
Loop Wiring
Wiring a Transmitter to an I/A Series System
The RTT20 temperature transmitter can be wired to various Fieldbus Modules (FBMs) of an
I/A Series System as follows:
29
MI 020-453 – February 2016 2. Installation
! CAUTION
1. All devices attached to an FBM 43 or FBM 44 must be configured for the same output
(DIGITAL or 4-20 mA).
2. Make sure that Device Name parameter is configured the same as the letterbug used for
that channel in the I/A Series system, or verify that it is set to its default description,
DevNam, before installation.
NOTE
An I/A Series system can also receive an analog signal from a transmitter configured
4-20 mA and attached to an FBM01, 04, 201, or 204. However, it cannot communicate
digitally with the transmitter using this analog signal.
Transmitter power is supplied by the FBM. The maximum total resistance for each transmitter loop
varies with the FBM. The maximum recommended length for field wire is 600 m (2000 ft). However,
the maximum total resistance must be taken into consideration. For example, if the maximum total
loop resistance allowed is 420 Ω and an intrinsically safe barrier with a resistance of 200 Ω is used, the
maximum resistance left for receivers in the loop and wire resistance is 220 Ω.
1. Remove the cover from the transmitter housing.
2. Run signal wires (0.50 mm2 or 20 AWG, typical) through one of the transmitter conduit
connections as shown in Figure 13. Use twisted pair to protect the digital output and/or
remote communications from electrical noise. Screened (shielded) cable may be required in
some locations.
NOTE
Do not run transmitter wires in same conduit as mains (ac power) wires.
3. If shielded cable is used, earth (ground) the shield at the field enclosure only. Do not ground
the shield at the transmitter.
4. Plug unused conduit connection with the metal plug provided (or equivalent). To maintain
specified explosionproof and dust-ignitionproof protection, plug must engage a minimum
of five full threads.
5. Connect the signal wires to the transmitter “+” and “–” terminal screws.
6. Reinstall the cover on the transmitter housing.
7. To connect the transmitter signal wires to the I/A Series system, refer to applicable I/A Series
system instructions.
30
2. Installation MI 020-453 – February 2016
ATMOSPHERE NOT TO
EXCEED HAZARDOUS I/A Series
CONDITIONS SPECIFIED SYSTEM
ON TRANSMITTER ENCLOSURE
DATA PLATE. TO
ADDITIONAL
TRANSMITTERS
CONDUIT
(a)
CONNECTION TRANSMITTER
2000
)
OUTPUT LOAD, Ω
AX
M
(R
1500 NOTE:
AD
Configurator is 250 Ω.
UM
IM
1000
AX
M
OPERATING
AREA
500
SEE NOTE
0 20 30 40
42
12 SUPPLY VOLTAGE (V ), V dc
S
31
MI 020-453 – February 2016 2. Installation
! CAUTION
Connecting a PC-Based Configurator, or HART Communicator while operating
below the specified minimum load may cause output disturbances and/or
communication problems.
Even though the transmitter has various filters to reduce or eliminate electrical noise, the power
supply should have less than 2% ripple.
To wire one or more transmitters to a power supply, proceed with the following steps.
1. Remove the cover from the transmitter housing.
2. Run signal wires (0.50 mm2 or 20 AWG, typical) through one of the transmitter
conduit connections as shown in Figure 15. Use twisted pair to protect the 4 to
20 mA output and/or remote communications from electrical noise. Maximum
recommended length for signal wires is 1800 m (6000 ft). Screened (shielded) cable
may be required in some locations.
NOTE
Do not run transmitter wires in same conduit as mains (ac power) wires.
3. Connect the power supply and receiver loop wires to the transmitter “+” and “–”
terminal screws.
4. Connect receivers (such as controllers, recorders, indicators) in series with power
supply and transmitter as shown in Figure 15.
5. Reinstall the cover onto the transmitter housing.
6. If wiring additional transmitters to the same power supply, repeat Steps 1 through 5
for each additional transmitter. The setup with multiple transmitters connected to a
single power supply is shown in Figure 16.
7. The remote configurator can be connected in the loop (subject to hazardous location
restrictions) as shown in Figure 15 and Figure 16.
32
2. Installation MI 020-453 – February 2016
+
+
POWER
INDICATOR SUPPLY
-
PC-BASED -
CONFIGURATOR
OR HART
C0MMUNICATOR + -
CONTROLLER
OR RECORDER
NOTES:
POWER
SUPPLY
(a)
(a) (a)
+ – + – + –
33
MI 020-453 – February 2016 2. Installation
Grounding (Earthing)
The transmitter will operate with the loop wiring floating or grounded. If the loop wiring is
grounded, the preferred method is to ground the negative lead close to the power supply. Never
ground the loop at more than one point.
The transmitter is an isolated device, so the sensor wiring can be grounded. If a grounded
thermocouple is used, that will be the one ground point for the sensor wiring.
Shielded cable around the loop wiring should be grounded at the power supply and floating
(ungrounded) at the transmitter. Do not ground the loop shield to the transmitter
Shielded cable around the sensor wiring should be grounded at the sensor, not at the transmitter.
The electronic module is not metallic and therefore does not need to be grounded. For certain
installations, a ground screw inside the housing is provided. For certain electrical safety
certifications, an external ground screw is provided (see Figure 8 for location).
BELL 202
HOST
MODEM
LOAD
POWER
SUPPLY RTT20-T RTT20-T RTT20-T
34
2. Installation MI 020-453 – February 2016
The HART Communicator or the PC-Based Configurator can operate, configure, and calibrate
the RTT20-T in the same way as it can a RTT20-T in a standard point-to-point installation.
NOTE
RTT20 Transmitters are set to address 0 at the factory, allowing them to operate in the
standard point-to-point manner with a 4 to 20 mA output signal. To activate
multidrop communication, the transmitter address must be changed to a number
from 1 to 15. This change deactivates the 4 to 20 mA analog output.
35
MI 020-453 – February 2016 2. Installation
36
3. Operation
In normal operation, the RTT20 Transmitter continuously receives input signals from RTDs,
thermocouples, ohms sensors, or dc mV sources and transmits a linear 4 to 20 mA dc or FoxCom
digital output signal. The 4 to 20 mA output and configurable parameters can be displayed via a
PC-Based Configurator or HART Communicator and the optional 3-Line
Indicator/Configurator.
The optional indicators can be configured to display the output in any one of five different ways
as follows:
EGUs = displays the measured value (temperature)
% = displays the percent of output based upon the calibrated range
mA = displays the mA output value between 4 and 20 mA
EGU and mA = alternates between the EGU and mA value
% and EGU = alternates between the % and the EGU
The 1-Line Indicator displays the output on its 4-digit display. It also automatically displays
alternating flashing messages “FAIL” and “SAFE” to denote a sensor or transmitter fault. An
indication of -999 or 9999 indicates that the output has exceeded the limits of the display.
The 3-Line Indicator displays the output on the first line of its display. The second line of this
indicator is an 11-segment bargraph that displays readings in percent of calibrated range.
Temperatures outside the calibrated range are indicated by a left-pointing (underrange) or right-
pointing (overrange) arrow. The third line displays seven character user configurable tag
information. It also automatically displays the following fault messages:
♦ 9999.9°C (or F) on the first line of the display to denote that the temperature exceeds
the limit of the display. The third line will read DFAIL.
♦ Alternating flashing messages “FAIL” and “SAFE” on the third line of the display to
denote a sensor or transmitter fault.
When a sensor or transmitter fault occurs and the problem has been corrected, the output
automatically resumes normal operation. On the HART version, the power supply must be cycled
if the Failsafe Reset is configured as Latched.
NOTE
The RTT20 Transmitter performs multiple sensor and transmitter validity checks.
Under certain startup and power conditions, the transmitter with HART
communications can take longer to complete those tasks than the alotted ‘startup
time’. This momentarily trips the sensor failure diagnostics bit. Therefore, if you have
a transmitter with HART protocol and are using the Historical Diagnostics data bit, it
is recommended that you perform a ‘Clear Historical Data' function through a
HART Communicator or PC-Based Configurator.
37
MI 020-453 – February 2016 3. Operation
38
4. Configuration
The RTT20 Transmitters are programmed internally with the characteristics of all the sensor
types that can be attached. Configuration is therefore simplified to selecting a few operating
parameters.
The RTT20 Transmitter may be configured before or after installation in the field. It may be
useful to configure the transmitter on the bench before installation to ensure that all the
configurable parameters are configured correctly for each application. To configure the
transmitter on the bench:
1. Connect the transmitter to a 24 V dc power supply (see Figure 14 for allowable power
supply voltage and output load limitations).
2. Make sure there is a load of at least 200 Ω in the loop for output code -D and 250 Ω
for output code -T to ensure proper communications (not required with output
code -I).
3. If the transmitter is not supplied with an integral sensor, attach the sensor to be used
to the proper screws (see Figures 10 and 12). The transmitter can be configured
without a sensor on the bench. However, if this is done and the FAILSAFE parameter
is not configured for OFF, the transmitter reports a failure.
4. Review all of the configurable parameters and change any as required using the
optional Indicator/Configurator or applicable remote configurator.
If the transmitter is to be configured in the field, proceed with the installation (loop wiring, sensor
wiring, and mechanical installation), and then review the configurable parameters and reconfigure
as required.
Configurable Parameters
The RTT20 Transmitter is microprocessor based. All adjustments to the transmitter can only be
performed via the integral or remote configurators.
NOTE
Remote configurators can only be used with the HART and Intelligent versions. The
4 to 20 mA version (Output Code -I) does not contain a modem, so remote
communications are not available. Therefore, all adjustments can be performed with
the 1- or 3-line integral indicators only.
There are no mechanical jumpers, potentiometers, or switches that are normally part of an analog
type transmitter. The following pages list all of the configurable parameters and the factory
default for each of the three different output types. The factory default values have been
customized if the transmitter was ordered with optional feature -C1 or -C2. The tables also show
which parameters are configurable with the integral vs. remote configurators. Following the tables
is an explanation for each parameter.
39
MI 020-453 – February 2016 4. Configuration
40
4. Configuration MI 020-453 – February 2016
Integ. Remote
Parameter Capability Factory Default Indic. Config. Applic. Req.
Descriptors
Tag Number 8 characters max Per S.O. No Yes ______
Tag Name (Description) 16 characters max Tag Name No Yes ______
Message 32 characters max Blank No Yes ______
Output
EGUs C, F, K, R, mV, ohms Note 1 Yes Yes ______
Linearization Mode EGU/Dewpoint EGU No Yes ______
Burst Mode On/Off Off No Yes ______
Multidrop Address 0 to 16 0 No Yes ______
Input
Input Type RTD, T/C, mV, Ω, spec per Model Code Yes Yes ______
Lower Range Value (LRV) per Model Code Note 1 Yes Yes ______
Upper Range Value(URV) per Model Code Note 1 Yes Yes ______
Cold Junction Internal, External, Fixed, Internal No Yes ______
Disabled
Cold Junction EGU C, F C No Yes ______
For RTD Measurement Only
Number of Sensors Single or Dual Single No Yes ______
For Single RTD 2,3, or 4 wire 3 wire Yes Yes ______
For Dual 2 wire RTD Avg, Diff, or Indep per order No Yes ______
For Dual 3 or 4 wire RTD Not Available
Other
Sensor Fault Detection On/Off On Yes Yes ______
Failsafe On/Off On Yes Yes ______
Failsafe Value Note 2 21.00 mA No Yes ______
Failsafe Reset Auto/Latched Auto No Yes ______
Power Supply Freq. (Hz) 50/60 60 No Yes ______
Power Supply Filter Standard/High High No Yes ______
Damping 0 to 32 seconds 0 No Yes ______
Sensor Validation 0.25 to 10.0 seconds 0.5 No Yes ______
Intelligent Smoothing 0 to 30 seconds 10 No Yes ______
3-Line Indicator/Configurator ______
Push Buttons Enable or Disable Enable No Yes ______
41
MI 020-453 – February 2016 4. Configuration
Configurable with
Display (Top line) Note 3 EGU No Yes ______
Display (Bottom line) 7 characters max FOXBORO No Yes ______
Configuration Language Eng, Fr, Ger, Span English Yes Yes ______
NOTES:
1. Transmitter configured for 0 to 100 Deg C if calibrated range is not provided.
2. The mA failsafe value is user configurable between 3.6 and 3.8 mA for downscale failsafe or between 20.75 and 23.0 mA for
upscale failsafe. Factory default is 3.6 mA for downscale failsafe or 21.00 mA for upscale.
3. The indicator can be configured to display the output in any one of five different ways as follows:
EGUs = displays the measured value (temperature)
% = displays the percent of output based upon the calibrated range
mA = displays the mA output value between 4 and 20 mA
EGU and mA = alternates between the EGU and mA value
% and EGU = alternates between the % and the EGU
42
4. Configuration MI 020-453 – February 2016
Input
Input Type RTD, T/C, mV, Ω Note 4 _________
Special or Custom Curve Not Available (Use Output Code -D or -T)
Lower Range Value (LRV) per Model Code Note 1 _________
Upper Range Value (URV) per Model Code Note 1 _________
Other
Sensor Fault Detection On/Off On _________
Failsafe On/Off On
Fail Safe Direction Up (21 mA) or Down (3.6 Up _________
mA)
3-Line Indicator/Configurator
Configuration Language English, German, French, English
Spanish _________
NOTES:
1. Transmitter is configured for 0 to 100 Deg C if calibrated range is not provided.
2. The mA failsafe value is user configurable for Output Codes -D and -T between 3.6 and 3.8 mA for downscale failsafe or
between 20.75 and 23.0 mA for upscale failsafe. Factory default is 21.00 mA for upscale and 3.6 mA for downscale failsafe.
3. The 1-line indicator and the top line of the 3-line indicator for Output Code -D and -T can be configured to display the output
in any one of five different ways, as follows:
EGUs = displays the measured value (temperature)
% = displays the percent of output based upon the calibrated range
mA = displays the mA output value between 4 and 20 mA
EGU and mA = alternates between the EGU and mA values
% and mA = alternates between the % and mA values
4. Input: Types limited to the following:
RTD Pt 100 DIN/IRC
Pt 100 SAMA
T/C Types B, C, E, J, K, L, N, R, S, T, U
mV
Ohm
NOTE
Adjustments to the transmitter with 4 to 20 mA output (Code -I) can only be
performed using the 3-line LCD Indicator/Configurator. Remote communication is
available with -D and -T transmitters.
43
MI 020-453 – February 2016 4. Configuration
Parameter Descriptions
To help guide you through the configuration of the transmitter, the following is a brief
description of the configurable parameters. Please remember that not all parameters are applicable
to all three different types of outputs, and not all parameters are configurable from the integral
Indicator/Configurators.
Output
Output This parameter is applicable to the Intelligent output version only. The output is
configurable for 4 to 20 mA output or digital. Digital is used only when the output is to be
digitally integrated to I/A Series System through FBM18, 39, 43, 44, or 46. When
configured for digital output, communications between the transmitter and the control
system occur at 10 times per second.
Engineering Configurable to C, F, K, or R for thermocouple or RTD sensors. If the input is configured for
Unit (EGU) mV or ohms, the engineering units should be mV or ohms, respectively.
Linearization Configurable for EGU or Dewpoint. This parameter should be set to EGU to make the
Mode output linear with temperature. It should be configured for Dewpoint only when the output
wants to be linear with Dewpoint (for example, when using Foxboro 2781 Dewpoint sensor
as the input).
Burst Mode Applicable to HART output version only. In the Off position, digital communications over the
HART network occur at 2 times per second. This parameter should be turned On only if the
transmitter is communicating digitally to a HART compatible control system and the
multidrop address is set to 0. When in the Burst mode, it provides faster digital
communications (approx 3 times per second) from the transmitter to the host control
system. Burst mode cannot be used with multidrop wiring.
Multidrop Address Applicable to HART output version only. The default of 0 allows the transmitter to operate in
the standard point-to-point, two wire 4 to 20 mA mode. If the transmitter is to be multidrop
wired, the address must be changed to a number from 1 to 15. All transmitters installed in
a multidrop node must have a different multidrop address, and Burst mode must be
configured Off. With multidrop operation, the analog current value will be fixed at 4 mA. A
maximum of 15 transmitters can be multidropped (networked) over a single pair of wires.
For intrinsically safe applications, the maximum number of transmitters per multidrop node
is 3 or 4, depending upon the barrier used. However, the HART Communication
Foundation does not recommend multidrop installations for intrinsically safe applications.
44
4. Configuration MI 020-453 – February 2016
Input
Input Configurable for all popular RTDs and thermocouples. When an RTD is selected, you must
also select whether it is a 2-, 3-, or 4-wire sensor (Measurement Mode). Can also be
configured for various mV or ohms sources.
! CAUTION
In the Input selection area, there are multiple special selections, namely Special
T/C, Special RTD, and Special Input. These selections are only used when the
factory installs a nonstandard sensor curve into the transmitter. They must not be
selected when the user is trying to implement a Custom Curve. Refer to the
Custom Curve portion of the Calibration menu.
Measurement Selected to match the number of wires coming from the sensor (2-, 3-, or 4-wire).
Mode
Lower Range Value This is the measurement value corresponding to the 4 mA point. This value can be
(LRV) electronically changed without the need for calibration equipment.
or Zero
Upper Range Value This is the measurement value corresponding to the 20 mA point This value can be
(URV) electronically changed without the need for calibration equipment.
or Full Scale
Cold Junction The cold junction reference is used with thermocouple input and FoxCom or HART Output
(code –T) only. The junction can be programmed for Internal, External, Fixed, or Disabled.
! CAUTION
Incorrect thermocouple measurements will result if the cold junction settings do
not match the installed transmitter. “Fixed” or “Disabled” should only be used
during diagnostic evaluation or calibration.
Cold Junction (EGU) The engineering units that are displayed on the remote configurators for the cold junction
temperature can be configured for F or C. Used with thermocouple input only.
45
MI 020-453 – February 2016 4. Configuration
Other
Sensor Fault The transmitter checks for sensor problems every three seconds. If configured for ON and
Detection or Sensor a fault is detected, the output goes to the configured failsafe condition. If configured for
Failsafe OFF, the output will not be forced to the failsafe value when a sensor fault is detected.
Failsafe (mA output If the transmitter detects an internal fault or a sensor fault (when configured for ON), the
only) mA will be driven to the failsafe value.
Failsafe Value or When the Failsafe is turned On and a fault is detected, the output will be driven below 4 mA
Failsafe Report or above 20 mA. On the 4 to 20 mA version (Code-I), the values are set at 3.6 and 21 mA.
On the HART and Intelligent versions, the milliamp failsafe current is adjustable between
3.6 and 3.8 mA for downscale and between 20.75 and 23.00 mA for upscale failsafe.
Failsafe Reset When a transmitter or sensor fault occurs and the problem has been corrected, the output
will return to normal operation if configured to AUTO. If configured for LATCHED, the power
supply will have to be turned off and back on before the transmitter will resume normal
operation. This parameter is applicable to HART output (code -T) only,
Power Supply Freq Should be set to the ac frequency of the power supply, either 50 or 60 Hz.
Power Supply This parameter helps eliminate noise originating from the power supply. This should always
Filter be set to HIGH. Set to STD only if you require extremely fast response with the damping
value set for 0 seconds.
Damping The basic transmitter has a response time of approximately 1.2 seconds for a 90%
response to an 80% input step. For processes which have temperature swings that are
beyond the Intelligent Smoothing band, and require a damped output, increase the
damping to a higher value. The damping is selectable between 0 and 30 seconds. Before
increasing the damping, it is suggested that you increase the Intelligent Smoothing time
and the Sensor Validation time to the maximum before increasing the damping value.
Sensor Adjustable between 0 and 10 seconds. This is the lag time that the microprocessor holds
Validation and compares the input to past inputs. If the value does not match the pattern determined
by three different filters, that value is discarded rather than used as a measurement.
Increasing the sensor validation time eliminates spikes due to input (sensor) noise.
! CAUTION
Under certain noisy electrical conditions, the output of a
Code -D transmitter may exhibit a short duration spike when
configured for 0.0 seconds. The configurator software is
being revised to 0.25 seconds minimum sensor validation
time. 0.0 seconds is not recommended on any transmitter
used in a control loop. This is not a problem with
conventional output Code -I and HART output (Code -T)
transmitters.
Intelligent Smoothing Any process or electrical noise is eliminated by a digital filtering algorithm and is smoothed
by averaging the input over an adjustable time period. The averaging time can be set
between 0 and 30 seconds. The Intelligent smoothing action is bypassed with 0 seconds,
or maximized with 30 seconds. When the input changes quickly, the smoothing band is
exceeded and the output tracks the input, temporarily bypassing the smoothing action.
Once the input settles at a new value, the filtering algorithm is automatically reactivated,
eliminating noise and producing an accurate and stable output. The smoothing band is
approximately ±0.6 ohms or ±0.5 mV, depending upon input configuration (RTD vs. T/C),
and is not adjustable. Therefore at a 100°C measurement, the intelligent smoothing band is
approximately ±2°C for an RTD or ±8°C for a thermocouple.
Calibrators The 6-character field can be used to designate who calibrated the transmitter. It can also
Initials be used to insert the date of last calibration (Jun 96, for example).
46
4. Configuration MI 020-453 – February 2016
3-Line Indicator/Configurator
Pushbuttons Configurable to Enable or Disable from the 3-line indicator/configurator. Disable would be
selected for security reasons only if you do not want anyone to reconfigure the transmitter from
the integral Indicator. Note that this is set in the transmitter, not the 3-line indicator/configurator.
Therefore, if a transmitter has the pushbuttons disabled, it is disabled for any indicator. This is
not a configurable parameter on the 4 to 20 mA output version (Output Code -I), because the
transmitter can be reconfigured only through the Indicator.
Display The top line of the 3-line indicator can be configured to display the output in any one of five
different ways as follows:
EGUs = displays the measured value (temperature
% = displays the percent of output based upon the calibrated range)
mA = displays the mA output value between 4 and 20 mA
EGU and mA = alternates between the EGU and mA value
% and EGU = alternates between the % and the EGU
The indicator pushbuttons are not active when the display is configured in the alternating mode
with software Rev 1. The pushbuttons are active with transmitter software Rev. 2 or later.
Display Normally configured to the plant tag number, such as TT301B.
(Bottom line)
Configuration The configuration language used by the 3-line indicator can be configured to English, French,
Language Spanish or German.
Indicator/Configurator
An optional 3-Line Indicator/Configurator can be added to your transmitter or moved from
transmitter to transmitter. See Figure 18.
In normal mode, the 3-Line Indicator displays the output on the first line of its display. In
configuration mode, it displays configuration values. (When configured for mV input, the display
goes blank with inputs exceeding 99 mV.) The second line of this indicator is an 11-segment
bargraph that displays readings in percent of calibrated range. Temperatures outside the calibrated
range are indicated by a left-pointing (underrange) or right-pointing (overrange) arrow. The third
line displays seven character user configurable tag information in normal mode.
In normal operating mode, the 3-Line Indicator also automatically displays the following fault
messages:
♦ 9999.9°C (or F) on the first line of the display to denote that the temperature exceeds
the limit of the display. The third line will read DFAIL.
♦ Alternating flashing message “FAIL” and “SAFE” on the third line of the display to
denote a sensor or transmitter fault.
47
MI 020-453 – February 2016 4. Configuration
Changing the configuration with the Indicator/Configurator is similar to setting the time on a
digital watch. The transmitter steps through a menu of parameters in response to the NEXT/NO
and ENTER/YES buttons on the indicator faceplate. See Tables 6 through . Whenever the
buttons are being used to reconfigure a transmitter, if neither button is pressed during a 2-minute
period, the transmitter returns to normal operation. Also, if the power is interrupted for more
than 10 seconds in the configuration mode, the transmitter returns to normal operation.
Press the NEXT/NO button to move to the next item in the menu structure or to answer “No” to
a prompt question. Press the ENTER/YES button to accept or enter an item or to answer “Yes” to
a prompt question.
48
4. Configuration MI 020-453 – February 2016
Configuration Procedure
1. Connect a 24 V dc power supply to the transmitter. Observe correct polarity of the
power supply and transmitter connections.
2. Turn on the power supply and wait until the display is functional (typically 5 to
8 seconds).
3. Following the configurator flowchart (Figure 20), use the NEXT/NO button to go to
the first parameter to be reconfigured and press ENTER/YES. Continue to follow the
flowchart to configure your transmitter. Note that the flowchart shows both a four-
digit code and text in each box. The code is displayed on a 1-Line Indicator and an
abbreviated form of the text on the third line of a 3-Line Indicator.
NOTE
Not all parameters are configurable using the 1- and 3-line indicator/configurators.
The menu selections allow the most common changes to be implemented. For all
other parameters, a remote configurator must be used.
49
MI 020-453 – February 2016 4. Configuration
ENTER/YES ENTER/YES
TRIM 4 mA? RAISE mA OUT? 9601 NEXT = + 9610
9600 LOWER mA OUT? 9602 NEXT = - 9620
ENTER/YES ENTER/YES
NEXT/NO
ENTER/YES ENTER/YES
TRIM 20 mA? RAISE mA OUT? 9701 NEXT = + 9710
9700 LOWER mA OUT? 9702 NEXT = - 9720
ENTER/YES ENTER/YES
NEXT/NO
THOUSN? X000
ENTER/YES ENTER/YES HUNDRD? 0X00
TRIM DISPLY? PLUS? 9801 00X0
TENS?
9800 MINUS? 9802 ONES? 000X
ENTER/YES ENTER/YES
TENTHS?
NEXT/NO
ENTER/YES ENGLISH
SELECT LANGUAGE? DEUTSCH
NOT APPLICABLE FRENCH
ENTER/YES ESPANOL
NEXT/NO
NEXT/NO
50
5. Calibration
The RTT20 Transmitter has an advanced self-calibration routine that greatly extends the time
between recalibrations. Every three seconds, the transmitter checks the zero and full scale output
against highly accurate and stable internal voltage signals that are referenced back to the factory
calibration stored in nonvolatile EEPROM memory. Any adjustments are made automatically
without interrupting the output signal.
The following sections display and describe procedures for transmitter calibration. Use test
equipment that is at least three times as accurate as the desired accuracy of the transmitter. Trimming
the 4 to 20 mA output is performed by setting the module to output either 4 or 20 mA, and then
comparing the loop current to a known standard. Input calibration is performed by simulating the
electrical behavior of the sensor with a known standard input device, then comparing the transmitter
output to the expected value.
Note that “Trimming 4 to 20 mA Output” is available on all three transmitter output types. “Input
Calibration” is only available on the Intelligent (-D) and HART (-T) output types.
Trimming 4 to 20 mA Output
If you have a 4 to 20 mA output, you may trim the output at 4 mA and 20 mA by connecting
a digital voltmeter and precision resister in the output loop (see Figure 21) and adjusting the output
in Configuration Mode. For the procedure using the integral indicator/configurator, see the
flowchart in Figure 20. For the procedure using a remote configurator, see MI 020-495 (PC20
Configurator), MI 020-501, 504, and 505 (PC50 Configurator), or MI 020-460 (HART
Communicator).
Negative adjustments (either 4 or 20 mA point, but not both) using Output Trim on the local
display or mA Cal on the remote configurators force the mA output to the maximum positive
current on a FoxCom transmitter (Output Code -D) with Rev 2 or earlier software. Do a Restore
Factory mA with the PC-Based Configurator and adjust the output with “1-point Cal”. Contact
Global Customer Support for a field upgrade kit. The “Output Trim/mA Cal” function works
correctly with transmitter software Rev 3 or later.
VOLTMETER POWER SUPPLY
51
MI 020-453 – February 2016 5. Calibration
Input Calibration
Connect the configured transmitter as shown in Figure 22. Sensor input connections to the
transmitter should be made per the diagrams shown in Figure 10 on page 26 (Single RTD),
Figure 11 on page 27 (Dual RTD), or Figure 12 on page 29 (Thermocouple or Voltage). Do not
use any sort of quick disconnect or clip connections on the sensor input connections since added
contact resistance can cause an inaccurate calibration.
Unless an N-point calibration is being performed, make sure that the Sensor Fault Detection is off
before taking calibration measurements. Interaction between the transmitter Sensor Fault
Detection and external calibration devices such as a millivolt current source can cause an
inaccurate calibration. After the calibration is completed, the Sensor Fault Detection can be
restored to its original configuration.
HART COMMUNICATOR
OR
PC-BASED CONFIGURATOR
N-Point Calibration
A computer-assisted 1-, 2-, 3-, or 5-point calibration may be performed with the PC-Based
Configurator. Note that the PC-Based Configurator automatically switches off the Sensor Fault
Detection, then automatically restores the Sensor Fault Detection to its pre-calibration settings.
Performing an N-Point Calibration overwrites any existing Input Calibration data contained in
the transmitter (see “Custom Curve Calibration”, which follows).
52
5. Calibration MI 020-453 – February 2016
NOTE
Since it is not possible to leave the default values in memory when performing a
custom input curve calibration, it is strongly recommended that the transmitter data
base, with the Number of Points = 0, be stored to a file prior to making drastic
changes in the calibration data.
! CAUTION
Calibrating data is stored in a single data array in the transmitter EEPROM.
Performing any calibration overwrites the existing calibration data. It is recommended
to save the transmitter database to a file before you recalibrate the transmitter.
53
MI 020-453 – February 2016 5. Calibration
54
6. Maintenance
The RTT20 Transmitter basic unit has no moving parts and is a completely sealed unit. If there is
a problem, refer to the following troubleshooting section for possible corrective actions. If you
cannot find any external problem, contact Global Customer Support representative or return the
transmitter for repair.
! CAUTION
The transmitter is completely sealed unit and cannot be repaired. Any attempt to
open the basic transmitter will void the warranty.
! DANGER
For nonintrinsically safe installations, to prevent a potential explosion in a Division 1
hazardous area, deenergize transmitter before you remove threaded housing cover.
Failure to comply with this warning could result in an explosion resulting in severe
injury or death.
Troubleshooting Problems
Normally, any problem activates a fault message on the optional indicators or remote
configurators, alerting the user that there is a problem. The following lists various problems and
corrective actions:
55
MI 020-453 – February 2016 6. Maintenance
56
6. Maintenance MI 020-453 – February 2016
No Output (0 mA)
♦ Check wiring for breaks.
♦ Make sure that there is at least 12 V dc at the transmitter loop wiring screws.
♦ Check wiring polarity.
Erratic Output
♦ Check for multiple grounds.
♦ Check for intermittent shorts or opens in the loop wiring.
Output Spike
♦ Under certain noisy electrical conditions, the output of a Code -D transmitter may
exhibit a short duration spike when configured for 0.0 seconds. The configurator
software is being revised to 0.25 seconds minimum sensor validation time. It is not
recommended to set 0.0 seconds on any transmitter used in a control loop. This is not
a problem with conventional output Code -I transmitters and output (Code -T)
transmitters.
57
MI 020-453 – February 2016 6. Maintenance
58
6. Maintenance MI 020-453 – February 2016
! CAUTION
When replacing housing cover, hand tighten it as much as possible so that O-ring is fully
captured.
! CAUTION
1. When replacing the two mounting screws, do not over-tighten.
2. When replacing housing cover, hand tighten it as much as possible so that O-ring is fully
captured.
59
MI 020-453 – February 2016
ISSUE DATES
JAN 2003 SEP 2004 FEB 2016
JUL 2003 SEP 2006
JAN 2004 FEB 2007
FEB 2004 APR 2008
Vertical lines to the right of text or illustrations indicate areas changed at last issue date.