ADDENDUM
The items listed in this addendum have changed to reflect product compliance with UL1741 First
Edition requirements. The changes only affect 120 VAC/60 Hz units using the SELL mode function
of the inverter/charger. The software revision has changed from 4.01 to 4.10.
General Information:
The inverter software has been redesigned to meet UL1741 First Edition requirements which
incorporates IEEE929 recommended practices. These requirements have altered voltage and
frequency operating windows and have added a 5 minute grid connect timer delay before selling
power. In addition to user utility interactive changes, the inverter has been approved to meet the
rigorous non-islanding and harmonics analyses initiated by UL1741.
The SELL voltage window is now nonadjustable and locked at 106132 VAC range, indicated by
the inverters LINE TIE LED ON. Any voltage limits programmed in SET INPUT LOWER/UPPER
LIMIT VAC menu item (located under MENU HEADING 11) for input AC1, are displayed, but ignored
when the SELL mode is selected.
The SELL frequency window is nonadjustable and locked at 59.360.5 Hz anytime the inverter
is in SELL mode. This is indicated by the LINE TIE LED ON. For any voltage or frequency condition
outside these specified operating windows, the inverter will disconnect and attempt to reconnect to
the grid when proper voltage and frequency conditions are detected (after a 5 minute wait period
elapses). The inverter will reset the 5 minute timer each time an out-of-bounds condition is detected,
during periods when the AC1 light is blinking or ON.
TRACE ENGINEERING 3
REV 4.10
Menu
976-0013-D-001
Changes in Manual:
Page-1, 5, 34, 39 and 119All references to software version 4.01 should now read 4.10.
Page 1 and 17The SW4024, SW4048 and SW5548 inverter models are UL listed to
UL1741-First Edition which incorporates IEEE929 recommended practices.
Labeling
Page 7 and 12The product rating labels have changed as shown below to reflect the UL listing:
270-0032-01-01
270-0033-01-01
270-0031-01-01
Mounting
The second paragraph under MOUNTING should read as follows:
Use 1/4" minimum bolts for mounting. The mounting must capable of supporting four times the
weight of the inverter...
When mounting to a vertical surface, such as a wall, ensure the inverter (or backing
material) is securely mounted to the wall studs for proper support.
Vertical wall mounting with proper access panels in place is the only UL approved
mounting method for fire prevention.
Menu Maps
The USER and SETUP menu have been updated to reflect the new software revision as follows:
Page 34USER MENU. The software revision shown under menu heading TRACE
ENGINEERING 3, menu item REVISION 4.01 is changed to REVISION 4.10.
An information file has been added to menu heading 11 and reads: IN SELL MODE AC1
INPUT VAC LIMITS FIXED AT 88% AND 110% OF NOMINAL.
Menu System
Page 39TRACE ENGINEERING (3) menu heading. The software revision has been updated
from 4.01 to 4.10.
Page 48The SET MAX CHARGE AMPS AC menu item, the range has been changed from
01 to 35 amps to 01 to 40 amps for the SW5548 model.
Page 54BATTERY SELLING (17) menu heading. The SET MAX SELL AMPS AC range has
been changed from 01 to 35 amps to 01 to 50 amps for SW5548 model.
Operation
Page 61 The following paragraph should be added to the UTILITY INTER-ACTIVE MODE
bulleted item: To meet agency approvals, SELL mode will sell power only between the locked
106132 volts AC range and 59.360.5 Hz range windows (120 VAC/60 Hz models only).
Page 83When in SELL mode, the SET INPUT LOWER LIMIT VAC is locked at 106 VAC and
sells power only when the AC output of the inverter is between 88 to 110% of nominal AC line
voltage.
Display Deletions
The following menu display items have been deleted for various reasons unrelated to UL
requirements.
Under the ERROR CAUSES 5 menu heading, menu item INVERTER BREAKER TRIPPED
has been deleted.
Under the GENERATOR MODE 2 menu heading, menu item GEN MAX RUN TIME ERROR
has been deleted.
Under the GENERATOR MODE 2 menu heading, all references to the GEN MAX RUN TIMER
have been deleted (i.e., IF GEN RUNS FOR MORE THAN MAX RUN TIME THEN ERROR).
Under GEN AUTO START SETUP 12 menu heading, all references to the GEN MAX RUN
TIMER have been deleted (i.e., SET MAXIMUM RUN TIME H:M 08:00 and SET MAX RUN TIME
TO 0 TO DEFEAT).
976-0013-D-002
*Trip time refers to the time between the abnormal conditions being applied and the inverter
ceasing to energize the utility line.
Islanding Protection
The non-islanding inverter protection features required by UL1741 ensures that the inverter
ceases to energize the utility line when the inverter is subjected to island conditions. As a result,
active control techniques have been incorporated into the SW inverter for detecting potential
dispersed-generation islands.
Over-current Protection
The Trace SW Series inverters also include over-current protection for the inverter system.
This protective system is used if the inverter attempts to power too large of a load or if the inverter
loses synchronization with the utility grid. This protective system is implemented with redundant
systems in analog hardware, microprocessor software and with a mechanical device (circuit
breaker). This insures the inverter is protected from damage and can not create an unsafe fault
condition to the utility or residence.