CyberPower UM OR2200LCDRT2U
CyberPower UM OR2200LCDRT2U
CyberPower UM OR2200LCDRT2U
This manual contains important instructions that must be followed during installation and maintenance of the UPS and batteries. Please read and 3. LCD module display
follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or High resolution and intelligent LCD display
operate your UPS. shows all the UPS information using icons and
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive messages. For more information please review
contaminants. (Please see specifications for acceptable temperature and humidity range). the “Definitions for Illuminated LCD Indicators”
CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. Turn off and unplug the unit before section below.
servicing the batteries. There are no user serviceable parts inside except for the battery. 4. LCD function selection switch
CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. The switch can be used to select the LCD
CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not display contents including input/output voltage
grounded. If you need to de-energize this equipment, turn off and unplug the unit. and estimated run time, etc.
CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer 5. Battery and Surge Protected Outlet
component. The unit has eight batteries powered/surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of
CAUTION! Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, your equipment during a power failure. (DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or
ANSI/NFPA 75. other large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in and damage the unit.)
accordance with the National Electric Code, ANSI/NFPA 70. 6. AC Input Power Cord
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical Heavy-duty power cord.
applications. DO NOT use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or 7. Output Circuit Breaker
patient care. Resettable circuit breakers provide output optimal overload protection.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation 8. Input Circuit Breaker
from the aquarium can cause the unit to short out. Resettable circuit breakers provide input optimal overload protection.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or electric shock, do not use the unit on any transportation 9. USB Port
such as airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out. The USB port allows connection and communication between the computer and the UPS unit.
10. Communication Protection Ports
INSTALLING YOUR UPS SYSTEM Communication protection ports will protect any standard modem, fax, telephone line, network or Ethernet connection (RJ11/RJ45).
11. Wiring Fault Indicator (red)
INTRODUCTION This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If
Thank you for selecting a CyberPower Systems UPS product. This UPS is designed to provide unsurpassed power protection, operation and this is illuminated, disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The unit will
performance during the lifetime of the product. not provide surge protection without being plugged into a grounded and properly wired wall outlet.
UNPACKING 12. Coax/Cable/DSS Surge Protection
Inspect the UPS upon receipt. The box should contain the following: The Coax/Cable/DSS surge protection ports will protect any cable modem, CATV converter, or DSS receiver.
(a) UPS unit (b) User’s manual (c) Rack mount brackets (d) Stands (e)Telephone cable (f) Serial cable (DB-9) (g) USB A+B type cable 13. Serial Port I (Primary)
OVERVIEW The serial port allows connection and communication between the UPS and the computer.
The OR1500LCDRT2U/OR2200LCDRT2U provides complete power protection from utility power 14. Serial Port II (Dry Contact)
that isn't always consistent. The OR1500LCDRT2U/OR2200LCDRT2U features surge protection Dry contact produces information for equipment that can utilize dry contact signals.
against power surges and maintenance free batteries for long lasting battery backup during power 15. SNMP/HTTP Network Slot
outages. In addition to ensuring consistent power to your computer system and the Remove the cover panel to install an optional RMCARD to remotely monitor and manage your UPS over a network.
OR1500LCDRT2U/OR2200LCDRT2U also includes software that will automatically save your open REPLACING THE BATTERY
files and shutdown your computer system during a utility power loss. Replacement of batteries located in an OPERATOR ACCESS AREA.
AUTOMATIC VOLTAGE REGULATOR When replacing batteries, replace with the same number of the following battery: CyberPower / RB1270X4J for the OR1500LCDRT2U,
The OR1500LCDRT2U/OR2200LCDRT2U stabilizes inconsistent utility power voltage to nominal CyberPower / RB1290X4L for the OR2200LCDRT2U.
levels that are safe for equipment. Inconsistent utility power may be damaging to important data files CAUTION! Risk of Energy Hazard, 24V, maximum 18 Ampere-hour battery. Before replacing batteries, remove conductive jewelry such as
and hardware, but with Automatic Voltage Regulation (AVR), damaging voltage levels are corrected chains, wrist watches, and rings. High energy conducted through these materials could cause severe burns.
to safe levels. AVR automatically increases low utility power and decreases high utility power to a consistent CAUTION! Do not dispose of batteries in a fire. The batteries may explode.
and safe 110/120 volts. CAUTION! Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING
Ensure that the equipment plugged into the outlets does not exceed the UPS unit’s rated capacity TO LOCAL REGULATIONS.
(1500VA/900W for OR1500LCDRT2U, 2000VA/1320W for OR2200LCDRT2U). If the rated capacities of the BATTERY REPLACEMENT PROCEDURE:
unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to
trip.
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, to ensure the battery’s maximum charge
capacity, it is recommended that you charge the battery for at least 8 hours. Your UPS is equipped with an
auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically charge
whether the UPS is turned on or off.
2. With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals 1. Remove the right side front panel. 2. Remove four screws from battery compartment cover 3. Disconnect the black and red cable
requiring battery backup into the battery power supplied outlets. DO NOT plug a laser printer, paper and remove the cover completely off the unit.
shredder, copier, space heater, vacuum, sump pump or other large electrical devices into the “Battery
and Surge Protected Outlets”. The power demands of these devices may overload and damage the
unit.
3. To protect a fax, phone or modem, connect a telephone cable or network cable from the wall jack outlet to
the IN jack of the UPS. Connect a telephone cable or network cable from the OUT jack of the UPS to a fax
machine, telephone, modem, or network devices.
4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air 4. Insert the new battery pack. Assemble the 5. Install the replacement batteries by connecting the
conditioner, copier, etc…). The warranty prohibits the use of extension cords, outlet strips, and surge strips. screws, cover, cable and front panel in the red and the black wire to the same color wires
reverse sequence of above steps. from the battery pack.
5. Press the power switch to turn the unit on. The Power On indicator light will illuminate and the unit will “beep”. Recharge the unit for at least 8 hours to ensure
the UPS performs expected runtime.
If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this,
turn the UPS off and unplug at least one piece of equipment from the battery power supplied outlets. Make REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sell lead-acid batteries
sure the circuit breaker is depressed and then turn the UPS on. collect used batteries for recycling, as required by local regulations.
6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
7. To store the UPS for an extended period, cover it and store with the battery fully charged. While in storage, recharge the battery every three
months to ensure battery life.
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
8. Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility.
9. Professional Rack Mount UPS provides one serial port, one dry contact and one USB port to allow connection and communication between
the UPS and computers or equipment. USB port and Serial Port l (Primary) allow the simultaneous shutdown of two computer systems. Serial
®
port ll produces the basic information for the equipment that can utilize a dry contact ups. The Primary computers (with PowerPanel
Business Edition installed) are the computers that you will use to control the UPS and make any changes to the operation of the UPS. When
®
there is a power failure, the computer which connects to Primary port will start to shut down after a user controlled delay. PowerPanel
Business Edition will save and close any open files to shutting the system down.
Connect the USB / serial cable to the UPS unit and an open
2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have
The USB / serial cable is not information on all applicable insurance or other resources of recovery/payment that are available to the Initial Customer and
USB / serial port on the back of the computer. You must
connected.
use the cable that came with the unit. Request a Claim Number.
The USB / serial cable is connected Check the back of the computer for an additional USB / 3. You must provide a dated purchase receipt (or other proof of the original purchase) for the Cyber Power unit and connected
PowerPanel® Business Edition is
to the wrong port. serial port. Move the cable to this port. equipment. You also need to provide a description of the damage to your connected equipment.
inactive (all icons are gray). Shutdown your computer and turn the UPS off. Wait 10 4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the
The unit is not providing battery
seconds and turn the UPS back on. This should reset the damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the
power.
unit. shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and
The serial cable is not the cable that Please use the serial cable that came with the unit for the shipment, and you must pay the cost of the repair estimate.
came with the unit. software. How Long Do I Have To Make A Claim?
Additional troubleshooting information can be found under “Support” at www.cyberpower.com All claims must be made within ten days of the occurrence.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product.
TECHNICAL SPECIFICATIONS If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if
CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund
to you the full purchase price you paid for the Product (purchase receipt showing price paid is required).
Model OR1500LCDRT2U OR2200LCDRT2U If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the
connected equipment. We will repair or replace the equipment that was damaged because of the failure of our Product or pay you
Capacity 1500VA / 900W 2000VA / 1320W
the fair market value (NOT REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or
another a third-party valuation guide, or eBay, craigslist, or other source to establish that amount. Our maximum liability is limited to
Nominal Input Voltage 120Vac
$300,000 for the OR1500LCDRT2U and OR2200LCDRT2U.
Input Frequency 50/60 Hz +/- 3 Hz(Auto-sensing) Who Pays For Shipping?
We pay when we send items to you; you pay when you send items to us.
On-Battery Output Voltage 120Vac +/- 10% What isn’t covered by the warranty?
1. This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any
On-Battery Output Wave Form Simulated Sine Wave
data that is lost as a result of the failure or the restoration of data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product
Operating Temperature + 32°F to 104° F / 0° C to 40° C
or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or
Operating Relative Humidity 0 to 90% non-condensing maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums,
medical or life support devices, etc.
Size (W x H x D) 17.2" x 3.5" x 15.7" What are the Limitations?
The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.
Net Weight 48.4 lbs / 21.9 kg 52.7 lbs / 23.9 kg
1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired
and grounded outlets (including compliance with electrical and safety codes of the most current electrical code), without the use
Typical Battery Recharge Time 8 hours from total discharge
of any adapters or other connectors.
Typical Battery Life 3 to 6 years, depending on number of discharge/recharge cycles 2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be
directly connected to the Product and not “daisy-chained” together in serial fashion with any extension cords, another Product
Recommended Battery Sealed Maintenance Free Lead Acid Battery or device similar to the Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty.
3. The Product and equipment connected to it must have been used properly in a suitable and proper environment and in
Safety Approvals UL1778 / CSAC22.2 No.107, FCC DOC Class B
conformance with any license, instruction manual, or warnings provided with the Product and the equipment connected to it.
4. The Product must have been used at all times within the limitations on the Product’s VA capacity.
SYSTEM FUNCTIONAL BLOCK DIAGRAM The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses
EMI Surge from lightning or other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence
Input Filter Suppressor AVR Output
will be deemed outside the rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or
Undertake Any Liability in Any Event for Any of the Following:
Charger 1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
AC/DC Inverter
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and
Normal Mode code-compliant 120 volt power lines in the United States and Canada; transients, surges or spikes on standard telephone land
Battery Mode
lines, PBX telephone equipment lines or Base 10T Ethernet lines, when properly installed and connected. (This exclusion
Battery
applies, for example, to fluctuations in data transmission or reception, by CATV or RF transmission or fluctuations, or by
transients in such transmission.)
SAFETY COMPLIANCE STATEMENT 3. Damage from any circumstance described as excluded above with respect to the Product.
FCC COMPLIANCE STATEMENT 4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the
product or the Connected Equipment.
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired 5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee.
operation. CyberPower excludes any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC loss of property [EXCEPT FOR (AND ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This
benefits regarding "Connected Equipment" under this Warranty], loss of profits, business interruption, or loss of information or
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a data. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by above limitation may not apply to you.
turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver. environments requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected. directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical
- Consult the dealer or an experienced radio/TV technician for help
or life support device (collectively, "High Risk Activities"). CyberPower expressly disclaims any express or implied warranty of
Important: Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to
fitness for High Risk Activities or with aquariums. CyberPower does not authorize use of any Product in any High Risk Activities
operate the equipment.
or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT.
CANADIAN COMPLIANCE STATEMENT Where Can I Get More Information?
CAN ICES-3 (B)/NMB-3(B) The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
CyberPower is the warrantor under this Limited Warranty.
. For further information please feel free to contact CyberPower at CyberPower Systems (USA), Inc. 4241 12th Ave E., STE 400,
Shakopee, MN 55379; call us at (877) 297-6937; or send us an e-mail message at [email protected].
All rights reserved. Reproduction without permission is prohibited.