TECHNICAL SERVICE MANUAL

Rooftop package

Models:
MRBT-062C(H/E)WN1-R
MRBT-075C(H/E)WN1-R
MRBT-085C(H/E)WN1-R
MRBT-100C(H/E)WN1-R
MRBT-150C(H/E)WN1-R
MRBT-175C(H/E)WN1-R
MRBT-200C(H/E)WN1-R
MRBT-300C(H/E)WN1-R
R410a Tropical Rooftop Package Unit 50Hz

Contents
1. Product List ........................................................................................................................ 2
2. External Appearance .......................................................................................................... 2
3. Nomenclature ..................................................................................................................... 3
4. Features .............................................................................................................................. 4
5. List of Functions................................................................................................................. 7
6. Specifications ..................................................................................................................... 9
7. Dimensional Drawings ..................................................................................................... 19
8. Wiring Diagrams ............................................................................................................... 25
9. Performance Data ............................................................................................................. 48
10. Electrical Data ............................................................................................................... 57
11. Parameter and Pressure Chart for Air Volume .......................................................... 59
12. Refrigerant Cycle Diagram .......................................................................................... 68
13. Operation Limit ............................................................................................................. 70
14. Installation..................................................................................................................... 72
15 Wired Controller ............................................................................................................ 79
16. Error Code ..................................................................................................................... 86
17. Accessories .................................................................................................................. 94
18. Maintenance and Upkeep ............................................................................................ 94
Appendix : ........................................................................................................................... 97

※ Manufacture reserves the right to discontinue, or change at any time, specifications or designs without
notices and without incurring obligations.

1
R410a Tropical Rooftop Package Unit 50Hz

1. Product List

Nominal Capacity Model Power Supply


Refrigerant
Ton Model Name Function V, ph, Hz
5 MRBT-60CWN1-R Cooling + EAH(Optional) 380-415V 3N~50Hz
6.2 MRBT-062CWN1-R Cooling
6.2 MRCT-062EWN1-R Cooling + EAH
6.2 MRBT-062HWN1-R Heating & Cooling
7.5 MRBT-075CWN1-R Cooling
7.5 MRCT-075EWN1-R Cooling +EAH
7.5 MRBT-075HWN1-R Heating & Cooling
8.5 MRBT-085CWN1-R Cooling
8.5 MRCT-085EWN1-R Cooling +EAH
8.5 MRBT-085HWN1-R Heating & Cooling
10 MRBT-100CWN1-R Cooling
10 MRCT-100EWN1-R Cooling +EAH R410A
380-400V 3N~50Hz
10 MRBT-100HWN1-R Heating & Cooling
15 MRBT-150CWN1-R Cooling
15 MRCT-150EWN1-R Cooling +EAH
15 MRBT-150HWN1-R Heating & Cooling
17.5 MRBT-175CWN1-R Cooling
17.5 MRCT-175EWN1-R Cooling +EAH
17.5 MRBT-175HWN1-R Heating & Cooling
20 MRBT-200CWN1-R Cooling
20 MRCT-200EWN1-R Cooling +EAH
20 MRBT-200HWN1-R Heating & Cooling
30 MRCT-300HWN1-R Heating & Cooling
Note: EAH- Electric Auxiliary Heater

2. External Appearance
6.2&7.5Ton
5 Ton

8.5&10 Ton 15&17.5&20 Ton

2
R410a Tropical Rooftop Package Unit 50Hz

30 Ton

3. Nomenclature

M R C T – 062 C W N1 - R
Power supply
D: 220v, 60Hz, 3Ph
R: 380~400v, 50Hz, 3Ph
Refrigerate type
N1: R410A
Wired controller
Function mode
C: Cooling only
E: Electric heater and Cooling
H: Cooling and heating
Cooling capacity (6.2ton)
XX: MBtu/h
XXX: ton
Working condition
Omit for T1 condition
T: T3 condition
Air outlet way
B: optional two air outlet ways: side and bottom
C: one air outlet way: side
D: one air outlet way: bottom

Rooftop package
Midea

3
R410a Tropical Rooftop Package Unit 50Hz

4. Features

1. The adoption of anticorrosive-box

The reinforced anticorrosion by using galvanization armor plate and coated with man-composed paint.
The appearance is stylish and be easy for maintenance.
(Has been passed 1000 hours salt spray test)

2. The adoption of credible protection system

2.1 The protection of compressor


High-pressure protection, low-pressure protection, compressor‟s
current protection and so on.The series‟ protectors can ensure
compressor operating normally.
It adopts independent system, except for protection of sequence
and wired controller output, any related protection to its
corresponding compressor. Once a compressor protection
energized, the corresponding compressor will stop, the others
working still.
2.2 Fan motor
The fan motors for evaporator have over-heat protection and over-current protection function. The fan
motors for condenser have the temperature controller protection function.

3. Energy saving design

3.1 High efficiency compressor


Using professional compressor, heat exchanger and optimum connection pipe, the compressor can
startup under low power input. Provide maximum reliability, efficiency and quiet
operation.
Two refrigerant circuits on larger units (above 12.5ton) provide efficient part load
performance.
Standard low and high pressure safety switches.
Well compressor control
Compressor staging is controlled directly by the control temperature. When the
control temperature is warmer than the cooling set point, cooling is staged up;
when the control temperature is cooler than the cooling set point, cooling is
staged down. However, a stage change can only occur when the control
temperature is outside the dead band. Staging is constrained by an inter-stage
delay timer. These constraints protect the compressors from short cycling while
eliminating temperature variations near the diffusers.

3.2 Condenser
By using high-efficient thin wing, the condenser has high-efficient heat exchanger, the energy waste
decreases greatly.
3.3 Evaporator
By using the high-efficient, super thin wing and inner grooved copper pipe, the evaporators get the
higher capacity and the lower noise level.
3.4 The heat insulation of indoor unit
The heat insulation of indoor unit can availably decrease heat loss.
3.5 The control and refrigerant cycle system
There are two independent refrigerant cycle systems, the capacity output is adjusted automatically by
4
R410a Tropical Rooftop Package Unit 50Hz
different demand, save energy when one control system is in running according to low capacity output.

4. Optional collocation

4.1 Operation in high temperature

The air-conditioner designed for high temperature can run, despite the ambient temperature reaches up
to 52℃(125℉).

4.2 Strong air flow

Large air volume from the air inlet is forced ventilating by the condenser fan.

4.3 Minimum installation arrangement

The installation is fast and low cost with the easy installation and ready operation.

4.4 Pre-drilled duct flange

Flanges are prepared at the supply and return duct connections so that they can reduce duct connection
work at site.

Flange

4.5 Quiet operation

Noise and vibration have been effectively reduced by adopting new style hermetic compressor. The
centrifugal fan and fan casing are optimum shaped for efficient and low noise operation.

5. Cabinet
5.1 Sloped drain pan and drain pipe.
5.2 Cabinets have forklift and lifting holes for easy transportation.
5.3 Cabinets have fresh air function, and the filter can be washable.

Fresh air inlet

5.4 External pressure gauge ports.


With the gauge ports mounted externally, an accurate diagnostic of system operation
can be performed quickly and easily without disrupting airflow.
5.5 Durable construction.
Weather-resistant construction with capped seams and sloped top panels.
G90 galvanized heavy gauge plate conforming to ASTM-A-653, Zinc content of
galvanized plate is 275 g/m2 .

5
R410a Tropical Rooftop Package Unit 50Hz

Electric heater assembly (optional)


Condenser fan motor

Highly efficient enhanced copper


tube/Aluminum fin outdoor coil

Highly efficient enhanced


copper tube / aluminum fin
indoor coil

Decorative
protective coil
guard

Compressor
contactor

Low voltage
terminal block

Blower motor with


slide-out blower assembly

Compressor Heavy gauge removable


base rails
5ton

6. Optional supply/return airflow design, from side or bottom, It could be flexibly applied to
multi-position. The rooftop and ground installation are optional.

Cover panel Cover panel


Cover panel of horizontal Cover panel of horizontal
of horizontal air return of horizontal air return
air supply air supply

7. Certificate of compressor

The compressors have CE certified, UL certified.

6
R410a Tropical Rooftop Package Unit 50Hz

5. List of Functions

5.1 Standard specifications

A. General
Packaged cooling or combination heating and cooling units suitable for mounting on the roof or ground.
The packaged unit consists of scroll compressors, evaporator coil, condenser coil, control wiring and
interconnecting piping- all factory assembled and mounted on heavy gauge G-90 galvanized steel sheet
press formed base, ready for field connection to utilities and ducts. The packaged unit is of rigid
construction with holes provided in the base rails for overhead rigging. The unit is provided with an integral
weather resistant control panel.

B. Unit enclosure
Panels are of heavy gauge, G-90 galvanized steel sheet with removable access panels, completely
weatherized for outdoor installation and properly reinforced and brazed. Panels and access door are
provided for inspection and access for all internal parts. Enclosures are provided with adequately
reinforced points of support for setting in the unit. Steel sheet panels are zinc-coated and galvanized by the
hot dip process of lock forming quality conforming to ASTM A 653 commercial weight G-90, followed by
baked on electrostatic polyester dry powder coat paint, on all external panel.

C. Compressor
Compressors are scroll for all the models. They are provided with all the standard controls and accessories
necessary for safe operation. These are equipped with internal motor protector; factory installed crank case
heater and rubber vibration isolator for quiet and efficient operation.

D. Air-cooled condensing section


1. The air-cooled condensing section is enclosed within the unit housing and consists of condenser coil,
fan(s) electric motor(s) and inherently protected compressor(s). Inner grooved copper tubes with wall
thickness of 0.3mm, mechanically bonded to enhanced louvered aluminum fins are standard for all
condenser coils. As an option, enhanced coated aluminum fins may be provided. Tube support sheets are
galvanized steel, formed to provide structural strength.
2. Fans are propeller type, direct driven, upward discharge and provided with fan grille mounted on the
casing.
3. Motors are totally enclosed air-over type with class F insulation. Inherent thermal protection is automatic
reset type.

E. Evaporator coil section


1. All cooling coils are of enhanced louvered fins and inner grooved copper tubes with wall thickness of
0.3mm, mechanically bonded to aluminum fins. As option, enhanced coated aluminum fins may be
provided. Tube support sheets are galvanized steel, formed to provide structural strength.
2. Drainage pan: An insulated drainage pan made of G-90 galvanized steel is provided, for additional
corrosion protection.
3. Insulation: Insulation is supplied in adequate density and thickness for all units to prevent condensation
from forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against
deterioration and erosion from air currents.

F. Evaporator fan
Evaporator fan is of centrifugal forward-curved blade design capable of handling total required CFM and
static pressure in the low and the medium ranges. Casings are made of galvanized steel. Blower motors
are of open drip proof type (totally enclosed types are optional) and conform to NEMA MG-1 and MG-2.

7
R410a Tropical Rooftop Package Unit 50Hz
Blower motor is mounted on adjustable base and secured by locking device. Pillow block bearing are
selected for at 200,000 hours average life at design operating conditions. Shaft is turned, ground and
polished from solid steel. Fans and pulleys are keyed to shaft and designed for continuous operation at
maximum motor horse power and fan speed. All rotating components and assemblies are statically and
dynamically balanced and every unit is vibration tested before shipment from the factory.

G. Electronic thermostats
General information: A dedicated electronic thermostat is supplied with unit controls as standard. This
thermostat controls one or two stage heating and cooling applications. The thermostat normally displays
room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also
allows you to select continuous fan operation, or have the fan on intermittent operation with the equipment.
It also displays the status of unit, thus providing maximum information for the end user.

5.2 Electric auxiliary heater


Electric auxiliary heaters are the resistance open coil type and conform to the requirements of UL 573 or
equivalent. Electrical characteristics, kW capacities and number of stages are as indicated. Airflow
switches, fusible links and overheat limit thermostats are provided to shut-off power in case of airflow
failure/overheat. Electric heater kit is installed as an externally mounted kit at the supply opening.

5.3 Standard features/options/accessories


Option Accessory
Description Standard features
(factory installed) (field installed)
Horizontal discharge ◆
Compressor crankcase heaters ◆
Evaporator fan-belt driven ◆
Evaporator fan motor-ODP type(TEFC type optional) ◆
Condenser fan-direct drive, propeller type(Except 5ton) ◆
Condenser fan-direct drive, axial type(Only 5ton) ◆
Condenser fan motor-totally enclosed air-over type ◆
Electric auxiliary heater ◆ ◆
Filter, Nylon(Thickness 10&12.5mm, except 5ton) ◆
Filter, aluminum(Thickness 25mm) ◆
Compressor overload protection ◆
Low &high pressure switch ◆
Cooling & heating thermostat ◆
Condenser fan guard ◆
Condenser coil guard ◆
Wired controller KJR-12B ◆
Wired controller KJR-23B ◆
Wired controller KJR-25B ◆
Drainage pipe ◆
Drainage outlet ◆
Snap ring ◆

8
R410a Tropical Rooftop Package Unit 50Hz

6. Specifications
Nominal ton (Ton) 5 6.2 6.2 6.2

Model MRBT-60CWN1-R MRBT-062CWN1-R MRCT-062EWN1-R MRBT-062HWN1-R

Btu/h 59000 75000 75000 75000


Cooling Capacity (1)
KW 17 22 22 22

Power Input (1) KW 5.6 7.7 7.7 7.7


Cooling
Btu/h 51200 65000 65000 65000
Cooling Capacity (2)
KW 15 19 19 19

Power Input (2) KW 6.7 8.6 8.6 8.6

Btu/h - - 47800 89000


Heating Capacity
Heating KW - - 14 26

Power Input KW - - 14 7.6

Capacity steps % 0/100 0/100 0/100 0/100

Power supply V/PH/Hz 380-415V/3/50 380-400/3/50 380-400/3/50 380-400/3/50

Max. input consumption


Electrical data KW 8.1 10.9 10.9 11.3
(Except EAH)

Max. current A 18 20.1 20.1 21

Indoor fan air flow (High


CFM 1800 2600 2600 2600
speed)

ESP Pa 70 60 60 60
Performance
EER 1 Btu/h/W 10.4 9.7 9.7 9.7

EER 2 Btu/h/W 7.6 7.5 7.5 7.5

COP Btu/h/W / / / 11.6

Number of rows 4 2 2 2

mm 1.6 1.6 1.6 1.6


Fin spacing
inch 1/16 1/16'' 1/16'' 1/16''

mm 7.94 7.94 7.94 7.94


Indoor Coil Tube diameter
inch 3/8 5/16'' 5/16'' 5/16''

mm 837×704 880X847 880X847 880X847


Coil length X height
inch 32.9x27.7 34.6x33.3 34.6x33.3 34.6x33.3

Number of circuits 12 10 10 10

Type FC centrifugal FC centrifugal FC centrifugal FC centrifugal

Quantity 1 1 1 1

mm 282 254 254 254


Diameter(Width)
inch 11.1 10 10 10

Indoor fan Drive type Direct Belt Belt Belt

Motors quantity 1 1 1 1

Motor model YDK550-4E YFD90L-4-1.5 YFD90L-4-1.5 YFD90L-4-1.5

Motor output KW 0.55 1.5 1.5 1.5

Motor rpm r/min 948 1400 1400 1400

Type Scroll Scroll Scroll Scroll

Quantity 1 1 1 1
Compressor
Model ZP67KCE-TFD-522 SH090A4ALC SH090A4ALC SH090A4ALC

Brand Copeland Danfoss Danfoss Danfoss

9
R410a Tropical Rooftop Package Unit 50Hz
Capacity Btu/h 55000 76090 76090 76090

Input KW 5.2 7.185 7.185 7.185

Rated load Amps (RLA) A 11.8 14.3 14.3 14.3

Locked rotor Amps(LRA) A 74.0 20 20 20

Refrigerant oil charge ml 1656 3000 3000 3000

Number of rows 3 3 3 3

mm 1.3 1.6 1.6 1.6


Fin spacing
inch 1/16 1/16" 1/16" 1/16"

mm 7.94 7.94 7.94 7.94


Tube diameter
Outdoor Coil inch 5/16" 5/16" 5/16" 5/16"
(outer2124/middle2
mm 074/inner2024) X 1404X968 1404X968 1404X968
Coil length X height 756
(outer83.6/middle81
inch 55.3 X38.1 55.3 X38.1 55.3 X38.1
.7/inn9.7er7) X 29.8
Number of circuits 16 21 21 21

Type Axial fan Propeller Propeller Propeller

Quantity 1 1 1 1

mm 600 650 650 650


Diameter(Width)
inch 23.62 25.6 25.6 25.6

Outdoor Fan Drive type direct Direct Direct Direct

Motors quantity 1 1 1 1

Motor model YDK230-6G-6 YS600-6P YS600-6P YS600-6P

Motor output KW 0.23 0.6 0.6 0.6

Motor rpm r/min 915 930 930 930

Outdoor sound level(sound pressure level ) dB(A) 62.9 70.3 70.3 70.3

Type R410A R410A R410A R410A

Refrigerant Refrigerant volume kg 5 5.2 5.2 5.2

Refrigerant Control Piston Capillary Capillary Capillary

Controller Wired controller type Wired controller Wired controller Wired controller Wired controller

Operation temp ℃ 17~30 17~30 17~30 17~30

Outdoor ambient Cooling ℃ 18~52 18~52 18~52 18~52

temp Heating ℃ - - - -10~24

mm 1920X840X1068 1630X1065X1068 1630X1065X1068 1630X1065X1068


Net(W×H×D)
inch 75.6X33.1X42 64.2 X 41.9 X 42 64.2 X 41.9 X 42 64.2 X 41.9 X 42
Dimensions
mm 1955X870X1085 1700X1110X1160 1700X1110X1160 1700X1110X1160
Packing(W×H×D)
inch 77X34.3X42.7 66.9 X 43.7 X 45.7 66.9 X 43.7 X 45.7 66.9 X 43.7 X 45.7

Net weight kg(Ibs) 230(507) 315(694.4) 323(712) 320(705.4)


Weight
Gross weight kg(Ibs) 234(516) 335(738.5) 343(756) 340(749.6)

Type Nylon Nylon Nylon Nylon

Quantity Pieces 1 2 2 2
Filter
mm 410 X 495 X 25 447 X 885 X 10 447 X 885 X 10 447 X 885 X 10
Size (W×H×D)
inch 16.1X19.5X1 17.6 X34.8 X0.4 17.6 X34.8 X0.4 17.6 X34.8 X0.4

Shipping Qty'Per 20'/40'/40'HQ Pieces 12/24/36 12/28/28 12/28/28 12/28/28


Note:
The data are based on the following conditions:
Cooling: (1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46°C(114°F) DB.
Heating and Power input: Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB; - Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) DB
Electrical data: Indoor Temperature 32°C(90°F) DB / 24°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB

10
R410a Tropical Rooftop Package Unit 50Hz

Nominal
(Ton) 7.5 7.5 7.5 8.5 8.5
ton
Model MRBT-075CWN1-R MRCT-075EWN1-R MRBT-075HWN1-R MRBT-085CWN1-R MRCT-085EWN1-R

Cooling Capacity Btu/h 89000 89000 89000 103000 103000

1 KW 26 26 26 30 30

Power Input 1 KW 9.2 9.2 9.2 10.4 10.4


Cooling
Cooling Capacity Btu/h 80100 80100 80100 91450 91450

2 KW 23.5 23.5 23.5 26.8 26.8

Power Input 2 KW 10.7 10.7 10.7 11.9 11.9

Btu/h - 47800 102000 - 71700


Heating Capacity
Heating KW - 14 30 - 21

Power Input KW - 14 8.8 - 21

Capacity steps % 0/100 0/100 0/100 0/100 0/100

Power supply V/PH/Hz 380-400/3/50 380-400/3/50 380-400/3/50 380-400/3/50 380-400/3/50


Electrical
Max. input KW 13 13 13 14 14
data
consumption
Max. current A 25 25 24 26.3 26.3
(Except EAH)
Indoor fan air CFM 2900 2900 2900 3600 3600

flow
ESP (High Pa 60 60 60 75 75

Performance speed)
EER 1 Btu/h/W 9.7 9.7 9.7 9.8 9.8

EER 2 Btu/h/W 7.5 7.5 7.5 7.7 7.7

COP Btu/h/W / / 11.6 / /

Number of rows 2 2 2 3 3

mm 1.6 1.6 1.6 1.4 1.4


Fin spacing
inch 1/16'' 1/16'' 1/16'' 1/18'' 1/18''

mm 7.94 7.94 7.94 7.94 7.94


Indoor Coil Tube diameter
inch 5/16'' 5/16'' 5/16'' 5/16'' 5/16''

Coil length X mm 880X847 880X847 880X847 1117X792 1117X792

height inch 34.6x33.3 34.6x33.3 34.6x33.3 44 X31.2 44 X31.2

Number of circuits 10 10 10 18 18

Type FC centrifugal FC centrifugal FC centrifugal FC centrifugal FC centrifugal

Quantity 1 1 1 1 1

mm 254 254 254 305 305


Diameter(Width)
inch 10 10 10 12 12

Indoor fan Drive type Belt Belt Belt Belt Belt

Motors quantity 1 1 1 1 1

Motor model YFD90L-4-1.5 YFD90L-4-1.5 YFD90L-4-1.5 YFD90L-4-1.5 YFD90L-4-1.5

Motor output KW 1.5 1.5 1.5 1.5 1.5

Motor rpm r/min 1400 1400 1400 1400 1400

Type Scroll Scroll Scroll Scroll Scroll

Quantity 1 1 1 1 1

Model SH105A4ALC SH105A4ALC SH105A4ALC SH120A4ALC SH120A4ALC


Compressor
Brand Danfoss Danfoss Danfoss Danfoss Danfoss

Capacity Btu/h 91500 91500 91500 102200 102200

11
R410a Tropical Rooftop Package Unit 50Hz
Input KW 8.472 8.472 8.472 9.462 9.462
Rated load Amps
A 16.7 16.7 16.7 20.7 20.7
(RLA)
Locked rotor
A 142 142 142 142 142
Amps(LRA)
Refrigerant oil ml 3000 3000 3000 3300 3300
charge
Number of rows 3 3 3 3 3

mm 1.6 1.6 1.6 1.6 1.6


Fin spacing
inch 1/16" 1/16" 1/16" 1/16" 1/16"

mm 7.94 7.94 7.94 7.94 7.94


Outdoor Coil Tube diameter
inch 5/16" 5/16" 5/16" 5/16" 5/16"

Coil length X mm 1404X968 1404X968 1404X968 1748X880 1748X880

height inch 55.3 X38.1 55.3 X38.1 55.3 X38.1 68.8X34.6 68.8X34.6

Number of circuits 21 21 21 20 20

Type Propeller Propeller Propeller Propeller Propeller

Quantity 1 1 1 1 1

mm 650 650 650 700 700


Diameter(Width)
inch 25.6 25.6 25.6 27.6 27.6

Outdoor Fan Drive type Direct Direct Direct Direct Direct

Motors quantity 1 1 1 1 1

Motor model YS600-6P YS600-6P YS600-6P YS1100-6 YS1100-6

Motor output KW 0.6 0.6 0.6 1.1 1.1

Motor rpm r/min 930 930 930 940 940

Outdoor sound level(sound dB(A) 70.3 70.3 70.3 72.2 72.2

pressure level ) Type R410A R410A R410A R410A R410A

Refrigerant Refrigerant kg 5.6 5.6 6 6.5 6.5

volume
Refrigerant Control Capillary Capillary Capillary Capillary Capillary

Controller Wired controller Wired controller Wired controller Wired controller Wired controller

Operation temp ℃ 17~30 17~30 17~30 17~30 17~30

Outdoor Cooling ℃ 18~52 18~52 18~52 18~52 18~52

ambient temp Heating ℃ - - -10~24 - -

mm 1630X1065X1068 2165X1021X1335
Net(W×H×D)
inch 64.2 X 41.9 X 42 85.2 X 40.2 X 52.6
Dimensions
mm 1700X1110X1160 2220X1140X1415
Packing(W×H×D)
inch 66.9 X 43.7 X 45.7 87.4 X 44.9 X 55.7

Net weight kg(Ibs) 315(694.4) 323(712) 380(837.7) 445(981) 455(1003)


Weight
Gross weight kg(Ibs) 335(738.5) 343(756) 390(859.8) 458(1009.7) 468(1031.7)

Type Nylon Nylon Nylon Nylon Nylon

Quantity Pieces 2 2 2 2 2
Filter
mm 447 X 885 X 10 447 X 885 X 10 447 X 885 X 10 566 X 814 X 10 566 X 814 X 10
Size (W×H×D)
inch 17.6 X34.8 X0.4 17.6 X34.8 X0.4 17.6 X34.8 22.3 X 32X0.4 22.3 X 32X0.4

Shipping Qty'Per Pieces 12/28/28 12/28/28 X0.4


12/28/28 8/16/16 8/16/16
Note: 20'/40'/40'HQ
The data are based on the following conditions:
Cooling: (1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46°C(114°F) DB.
Heating and Power input: Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB; - Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) DB
Electrical data: Indoor Temperature 32°C(90°F) DB / 24°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB

12
R410a Tropical Rooftop Package Unit 50Hz

Nominal ton (Ton) 8.5 10 10 10 15

Model MRBT-085HW MRBT-100CW MRCT-100EW MRBT-100HW MRBT-150CWN1-R

N1-R N1-R N1-R N1-R

Btu/h 103000 120000 120000 120000 180000


Cooling Capacity 1
KW 30 35 35 35 53

Power Input 1 KW 10.4 11.8 11.8 11.8 18.6


Cooling
Btu/h 91450 97000 97000 97000 158700
Cooling Capacity 2
KW 26.8 31.4 31.4 31.4 46.5

Power Input 2 KW 11.9 13.1 13.1 13.1 21.3

Btu/h 120000 - 71700 126000 -


Heating Capacity
Heating KW 35 - 21 37 -

Power Input KW 10.1 - 21 10.9 -

Capacity steps % 0/100 0/100 0/100 0/100 0/50/100

Power supply V/PH/Hz 380-400/3/50 380-400/3/50 380-400/3/50 380-400/3/50 380-400/3/50

Max. input consumption KW 14 17.7 17.7 17 27


Electrical data
(Except EAH)

Max. current A 27.5 30 30 31 53

Indoor fan air flow (High CFM 3600 4030 4030 4030 6150

speed)

ESP Pa 75 75 75 75 90
Performance
EER 1 Btu/h/W 9.8 10.2 10.2 10.2 9.7

EER 2 Btu/h/W 7.7 8.2 8.2 8.2 7.5

COP Btu/h/W 11.6 / / 11.6 /

Number of rows 3 3 3 3 3

mm 1.4 1.4 1.4 1.4 1.4


Fin spacing
inch 1/18'' 1/18'' 1/18'' 1/18'' 1/18''

mm 7.94 7.94 7.94 7.94 7.94


Indoor Coil Tube diameter
inch 5/16'' 5/16'' 5/16'' 5/16'' 5/16''

mm 1117X792 1117X792 1117X792 1117X792 1607X880


Coil length X height
inch 44 X31.2 44 X31.2 44 X31.2 44 X31.2 63.3X346.

Number of circuits 18 18 18 18 10+10

Type FC centrifugal FC centrifugal FC centrifugal FC centrifugal FC centrifugal

Quantity Pieces 1 1 1 1 1

mm 305 305 305 305 383


Diameter(Width)
inch 12 12 12 12 15

Indoor fan Drive type Belt Belt Belt Belt Belt

Motors quantity Pieces 1 1 1 1 1

Motor model YFD90L-4-1.5 YFD90L-4-1.5 YFD90L-4-1.5 YFD90L-4-1.5 YFD132S-4-5.5

Motor output KW 1.5 1.5 1.5 1.5 5.5

Motor rpm r/min 1400 1400 1400 1400 1440

Type Scroll Scroll Scroll Scroll Scroll

Quantity Pieces 1 1 1 1 2

Compressor Model SH120A4ALC SH140A4ALC SH140A4ALC SH140A4ALC SH105A4ALC

Brand Danfoss Danfoss Danfoss Danfoss Danfoss

Capacity Btu/h 102200 119000 119000 119000 91500

13
R410a Tropical Rooftop Package Unit 50Hz
Input KW 9.462 10.862 10.862 10.862 8.472

Rated load Amps (RLA) A 20.7 21.4 21.4 21.4 16.7

Locked rotor Amps(LRA) A 142 147 147 147 156

Refrigerant oil charge ml 3300 3300 3300 3300 3000

Number of rows 3 3 3 3 3

mm 1.6 1.6 1.6 1.6 1.6


Fin spacing
inch 1.6 1/16" 1/16" 1/16" 1/16"

mm 7.94 7.94 7.94 7.94 7.94


Outdoor Coil Tube diameter
inch 5/16" 5/16" 5/16" 5/16" 5/16"

mm 1748X880 1748X880 1748X880 1748X880 2179X1100


Coil length X height
inch 68.8X34.6 68.8X34.6 68.8X34.6 68.8X34.6 85.8X43.3

Number of circuits 20 20 20 20 12+12

Type Propeller Propeller Propeller Propeller Propeller

Quantity Pieces 1 1 1 1 2

mm 700 700 700 700 650


Diameter(Width)
inch 27.6 27.6 27.6 27.6 25.6

Outdoor Fan Drive type Direct Direct Direct Direct Direct

Motors quantity Pieces 1 1 1 1 2

Motor model YS1100-6 YS1100-6 YS1100-6 YS1100-6 YS600-6P

Motor output KW 1.1 1.1 1.1 1.1 0.6 X 2

Motor rpm r/min 940 940 940 940 930

Outdoor sound level dB(A) 72.2 72.2 72.2 72.2 72.4

(sound pressure level )

Type R410A R410A R410A R410A R410A

Refrigerant Refrigerant volume kg 6.8 6.7 6.7 7.5 5.8 X 2

Refrigerant Control Capillary Capillary Capillary Capillary Capillary

Controller Wired controller Wired controller Wired controller Wired controller Wired controller

Operation temp ℃ 17~30 17~30 17~30 17~30 17~30

Outdoor Cooling ℃ 18~52 18~52 18~52 18~52 18~52

ambient temp Heating ℃ -10~24 - - -10~24 -

mm 2165X1021X1335 2230 X1245X1824


Net(W×H×D)
inch 85.2 X 40.2 X 52.6 87.8 X 71.8 X 49
Dimensions
mm 2220X1140X1415 2236 X1300X1855
Packing(W×H×D)
inch 87.4 X 44.9 X 55.7 88 X 51.2 X 73

Net weight kg(Ibs) 450(990) 445(981) 455(1003) 450(992) 710/ (1565.3)


Weight
Gross weight kg(Ibs) 463(1018.6) 458(1009.7) 468(1031.7) 463(1020.7) 730(1609.3)

Type Nylon Nylon Nylon Nylon Nylon

Quantity Pieces 2 2 2 2 2
Filter
mm 566 X 814 X 10 566 X 814 X 10 566 X 814 X 10 566 X 814 X 10 900 X 815 X 12.5
Size (W×H×D)
inch 22.3 X 32X0.4 22.3 X 32X0.4 22.3 X 32X0.4 22.3 X 32X0.4 35.4 X32 X 0.5

Shipping Qty'Per 20'/40'/40'HQ Pieces 8/16/16 8/16/16 8/16/16 8/16/16 3/6/12

Note:
The data are based on the following conditions:
Cooling: (1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46°C(114°F) DB.
Heating and Power input: Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB; - Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) DB
Electrical data: Indoor Temperature 32°C(90°F) DB / 24°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB

14
R410a Tropical Rooftop Package Unit 50Hz

Nominal ton (Ton) 15 15 17.5 17.5

Model MRCT-150EWN1-R MRBT-150HWN1-R MRBT-175CWN1-R MRCT-175EWN1-R

Btu/h 180000 180000 205000 205000


Cooling Capacity 1
KW 53 53 60 60

Power Input 1 KW 18.6 18.6 20 20


Cooling
Btu/h 158700 158700 176500 176500
Cooling Capacity 2
KW 46.5 46.5 51.7 51.7

Power Input 2 KW 21.3 21.3 23.5 23.5

Btu/h 102400 191000 - 102400


Heating Capacity
Heating KW 30 56 - 30

Power Input KW 30 17.5 - 30

Capacity steps % 0/50/100 0/50/100 0/50/100 0/50/100

Power supply V/PH/Hz 380-400/3/50 380-400/3/50 380-400/3/50 380-400/3/50

Max. input consumption KW 27 27 29 29


Electrical data
(Except EAH)

Max. current A 53 45 65 65

Indoor fan air flow (High 6150 6150 7311 7311


CFM
speed)

ESP Pa 90 90 90 90
Performance
EER 1 Btu/h/W 9.7 9.7 10.2 10.2

EER 2 Btu/h/W 7.5 7.5 7.5 7.5

COP Btu/h/W / 11 / /

Number of rows 3 3 3 3

mm 1.4 1.4 1.4 1.4


Fin spacing
inch 1/18'' 1/18'' 1/18'' 1/18''

mm 7.94 7.94 7.94 7.94


Indoor Coil Tube diameter
inch 5/16'' 5/16'' 5/16'' 5/16''

mm 1607X880 1607X880 1607X880 1607X880


Coil length X height
inch 63.3X346. 63.3X346. 63.3X346. 63.3X346.

Number of circuits 10+10 10+10 10+10 10+10

Type FC centrifugal FC centrifugal FC centrifugal FC centrifugal

Quantity Pieces 1 1 1 1

mm 383 383 383 383


Diameter(Width)
inch 15 15 15 15

Indoor fan Drive type Belt Belt Belt Belt

Motors quantity 1 1 1 1

Motor model YFD132S-4-5.5 YFD132S-4-5.5 YFD132S-4-5.5 YFD132S-4-5.5

Motor output KW 5.5 5.5 5.5 5.5

Motor rpm r/min 1440 1440 1440 1440

Type Scroll Scroll Scroll Scroll

Quantity Pieces 2 2 2 2

Model SH105A4ALC SH105A4ALC SH120A4ALC SH105A4ALC


Compressor
Brand Danfoss Danfoss Danfoss Danfoss

Capacity Btu/h 91500 91500 102200 102200

Input KW 8.472 8.472 9.462 9.462

15
R410a Tropical Rooftop Package Unit 50Hz
Rated load Amps (RLA) A 16.7 16.7 20.7 20.7

Locked rotor Amps(LRA) A 156 156 142 142

Refrigerant oil charge ml 3000 3000 3300 3300

Number of rows 3 3 3 3

mm 1.6 1.6 1.6 1.6


Fin spacing
inch 1/16" 1/16" 1/16" 1/16"

mm 7.94 7.94 7.94 7.94


Outdoor Coil Tube diameter
inch 5/16" 5/16" 5/16" 5/16"

mm 2179X1100 2179X1100 2179X1100 2179X1100


Coil length X height
inch 85.8X43.3 85.8X43.3 85.8X43.3 85.8X43.3

Number of circuits 12+12 12+12 12+12 12+12

Type Propeller Propeller Propeller Propeller

Quantity Pieces 2 2 2 2

mm 650 650 650 650


Diameter(Width)
inch 25.6 25.6 25.6 25.6

Outdoor Fan Drive type Direct Direct Direct Direct

Motors quantity Pieces 2 2 2 2

Motor model YS600-6P YS600-6P YS1100-6 YS1100-6

Motor output KW 0.6 X 2 0.6 X 2 1.3 X 2 1.3 X 2

Motor rpm r/min 930 930 940 940

Outdoor sound level(sound pressure level ) dB(A) 72.4 72.4 72.4 72.4

Type R410A R410A R410A R410A

Refrigerant Refrigerant volume kg 5.8 X 2 6.5 X 2 5.2X 2 5.2 X 2

Refrigerant Control Capillary Capillary Capillary Capillary

Controller Wired controller Wired controller Wired controller Wired controller

Operation temp ℃ 17~30 17~30 17~30 17~30

Outdoor ambient Cooling ℃ 18~52 18~52 18~52 18~52

temp Heating ℃ - -10~24 - -

Net(W×H×D) mm 2230 X1245X1824 2230 X1245X1824 2230 X1245X1824 2230 X1245X1824

inch 87.8 X 71.8 X 49 87.8 X 71.8 X 49 87.8 X 71.8 X 49 87.8 X 71.8 X 49


Dimensions
Packing(W×H×D) mm 2236 X1300X1855 2236 X1300X1855 2236 X1300X1855 2236 X1300X1855

inch 88 X 51.2 X 73 88 X 51.2 X 73 88 X 51.2 X 73 88 X 51.2 X 73

Net weight kg(Ibs) 720/ (1609.3) 730/ (1609.3) 710/ (1565.3) 720/ (1609.3)
Weight
Gross weight kg(Ibs) 740(1653.4) 750(1653.4) 730(1609.3) 740(1653.4)

Type Nylon Nylon Nylon Nylon

Quantity Pieces 2 2 2 2
Filter
mm 900 X 815 X 12.5 900 X 815 X 12.5 900 X 815 X 12.5 900 X 815 X 12.5
Size (W×H×D)
inch 35.4 X32 X 0.5 35.4 X32 X 0.5 35.4 X32 X 0.5 35.4 X32 X 0.5

Shipping Qty'Per 20'/40'/40'HQ Pieces 3/6/12 3/6/12 3/6/12 3/6/12

Note:
The data are based on the following conditions:
Cooling: (1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46°C(114°F) DB.
Heating and Power input: Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB; - Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) DB
Electrical data: Indoor Temperature 32°C(90°F) DB / 24°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB

16
R410a Tropical Rooftop Package Unit 50Hz

Nominal ton (Ton) 17.5 20 20 20 30

Model MRBT-175HWN1 MRBT-200CW MRCT-200EWN1 MRBT-200HWN1- MRCT-300HWN1


-R N1-R -R R -R
Btu/h 180000 240000 240000 240000 331000
Cooling Capacity
(1)
KW 53 70 70 70 97

Power Input (1) KW 18.6 23.6 23.6 23.6 33


Cooling
Btu/h 158700 210000 210000 210000 299600
Cooling Capacity
(2)
KW 51.7 61.4 61.4 61.4 87.8

Power Input (2) KW 23.5 27.7 27.7 27.7 40.1

Btu/h 191000 - 133100 256000 358000


Heating Capacity
Heating KW 67 - 39 75 105

Power Input KW 19.8 - 39 23.4 34.8

Capacity steps % 0/50/100 0/50/100 0/50/100 0/50/100 0/50/100

Power supply V/PH/Hz 380-400/3/50 380-400/3/50 380-400/3/50 380-400/3/50 380-400/3/50


Electrical Max. input KW 29 36 36 36 49
data consumption
(Except EAH)
Max. current A 65 66 66 75 86.5
Indoor fan air flow CFM 7311 8400 8400 8400 12000
(High speed)
ESP Pa 90 100 100;; 100 250
Performan
EER 1 Btu/h/W 10.2 10.1 10.1 10.1 10
ce
EER 2 Btu/h/W 7.5 7.6 7.6 7.6 7.5

COP Btu/h/W 11.5 / / 11 10.3

Number of rows 3 3 3 3 3

mm 1.4 1.6 1.6 1.6 1.5


Fin spacing
inch 1/18'' 1/16'' 1/16'' 1/16'' 1/16''

mm 7.94 7.94 7.94 7.94 7


Indoor Coil Tube diameter
inch 5/16'' 5/16'' 5/16'' 5/16'' 9/32''

Coil length X mm 1607X880 1882X1012 1882X1012 1882X1012 1882X1428

height inch 63.3X346. 74.1X39.8 74.1X39.8 74.1X39.8 74.1X56.2

Number of circuits 10+10 11+12 11+12 11+12 17+17

circuitsrcuits
Type FC centrifugal FC centrifugal FC centrifugal FC centrifugal FC centrifugal

Quantity Pieces 1 1 1 1 1

mm 383 452 452 452 500


Diameter(Width)
inch 15 17.8 17.8 17.8 19.7

Indoor fan Drive type Belt Belt Belt Belt Belt

Motors quantity Pieces 1 1 1 1 1

Motor model YFD132S-4-5.5 YFD132S-4-5.5 YFD132S-4-5.5 YFD132S-4-5.5 Y(2)132M-4-7.5

Motor output KW 5.5 5.5 5.5 5.5 7.5

Motor rpm r/min 1440 1440 1440 1440 1440

Type Scroll Scroll Scroll Scroll Scroll

Quantity Pieces 2 2 2 2 2

Compress Model SH120A4ALC SH140A4ALC SH140A4ALC SH140A4ALC SH184A4ALC


or
Brand Danfoss Danfoss Danfoss Danfoss Danfoss

Capacity Btu/h 102200 119000 119000 119000 152426

17
R410a Tropical Rooftop Package Unit 50Hz
Input KW 9.462 10.862 10.862 10.862 13.732
Rated load Amps A 20.7 21.4 21.4 21.4 27.6
(RLA)
Locked rotor A 142 147 147 147 197
Amps(LRA)
Refrigerant oil ml 3300 3300 3300 3300 3600
charge
Number of rows 3 4 4 4 4

mm 1.6 1.6 1.6 1.6 1.5


Fin spacing
inch 1/16" 1/16" 1/16" 1/16" 1/16"

mm 7.94 7.94 7.94 7.94 7


Outdoor
Tube diameter
Coil
inch 5/16" 5/16" 5/16" 5/16" 9/32"

Coil length X mm 2179X1100 2650X1100 2650X1100 2650X1100 2650X1512

height inch 85.8X43.3 104.3X43.3 104.3X43.3 104.3X43.3 104.3X59.5

Number of circuits 12+12 11+12 11+12 11+12 12+12

circuitsrcuits
Type Propeller Propeller Propeller Propeller Propeller

Quantity Pieces 2 2 2 2 2

mm 650 750 750 750 750


Diameter(Width)
inch 25.6 29.5 29.5 29.5 29.5
Outdoor
Drive type Direct Direct Direct Direct Direct
Fan
Motors quantity Pieces 2 2 2 2 2

Motor model YS1100-6 YS1500-6 YS1500-6 YS1500-6 YS1500-6

Motor output KW 1.3 X 2 1.5 X 2 1.5 X 2 1.5 X 2 1.5 X 2

Motor rpm r/min 940 910 910 910 910


Outdoor sound level dB(A) 72.4 74.2 74.2 74.2 75.4
(sound pressure level )
Type R410A R410A R410A R410A R410A

Refrigerant Refrigerant kg 5.6 X 2 8.1 X 2 8.1 X 2 8.8 X 2 9.4 X 2


volume
Refrigerant Control Capillary Capillary Capillary Capillary Capillary

Controller Wired controller Wired controller Wired controller Wired controller Wired controller

Operation temp ℃ 17~30 17~30 17~30 17~30 17~30

Outdoor Cooling ℃ 18~52 18~52 18~52 18~52 18~52


ambient
temp Heating ℃ -10~24 - - -10~24 -10~24

mm 2230 2753 2753 2753 2753


Net(W×H×D) X1245X1824 X1245X2157 X1245X2157 X1245X2157 X1674X2157
inch 87.8 X 71.8 X 49 108.4 X 49 X 108.4 X 49 X 108.4 X 49 X 84.9 108.4 X 65.9 X
Dimensions 84.9 84.9 84.8
mm 2236 2755 2755 2755 2755
Packing X1300X1855 X1300X2180 X1300X2180 X1300X2180 X1690X2180
(W×H×D) 108.5X51.2 108.5X51.2
inch 88 X 51.2 X 73 108.5X51.2 X85.8 108.5X66.5 X85.8
X85.8 X85.8
Net weight kg(Ibs) 730/ (1609.3) 925(2039.2) 940(2072.3) 940(2072.3) 1110(2447.1)
Weight
Gross weight kg(Ibs) 750(1653.4) 940(2072.3) 955(2105.4) 955(2105.4) 1130(2491.2)

Type Nylon Nylon Nylon Nylon Nylon

Quantity Pieces 2 3 3 3 3
Filter
mm 900 X 815 X 12.5 640 X 1008 X 640 X 1008 X 640 X 1008 X 12.5 1492 X 640 X 12.5
Size (W×H×D) 12.5 12.5
inch 35.4 X32 X 0.5 25.2 X39.7 X 25.2 X39.7 X 0.5 25.2 X39.7 X 0.5 59 X26 X 0.5
0.5
Shipping Qty'Per Pieces 3/6/12 2/4/8 2/4/8 2/4/8 2/4/4
20'/40'/40'HQ
Note:
The data are based on the following conditions:
Cooling: (1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46°C(114°F) DB.
Heating and Power input: Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB; - Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) DB
Electrical data: Indoor Temperature 32°C(90°F) DB / 24°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB

18
R410a Tropical Rooftop Package Unit 50Hz

7. Dimensional Drawings
7.1 5ton

19
R410a Tropical Rooftop Package Unit 50Hz
7.2 6.2&7.5ton

20
R410a Tropical Rooftop Package Unit 50Hz
7.3 8.5&10ton

21
R410a Tropical Rooftop Package Unit 50Hz
7.4 15&17.5ton

22
R410a Tropical Rooftop Package Unit 50Hz
7.5 20ton

23
R410a Tropical Rooftop Package Unit 50Hz
7.6 30ton

294

120
888
Control electric heater box access panel 120
870

1 5 12 Filter access door


Hole for electric heater power wires 65
2
26
Horizontal supply opening 6 Fresh air
52
2
144
Horizontal return opening 55

18

1656

14
2
Drain connection hole
83
9
Maintain orifice for air supply motor 142

27 9
53 17
Control and comperssor access panel 870
2157
Hole for control wires 99
7 13
5 142 820
Hole for power wires
Hole for other purpose
Hole for bottom installation 16-15×20
142
324
870
2157
678

862 917 730 135


2693
2753 24
R410a Tropical Rooftop Package Unit 50Hz

8. Wiring Diagrams

8.1 5ton
MRBT-60CWN1-R

25
R410a Tropical Rooftop Package Unit 50Hz

8.2 6.2ton
MRBT-062CWN1-R

26
R410a Tropical Rooftop Package Unit 50Hz

MRCT-062EWN1-R

27
R410a Tropical Rooftop Package Unit 50Hz

MRBT-062HWN1-R

28
R410a Tropical Rooftop Package Unit 50Hz

8.3 7.5ton
MRBT-075CWN1-R

29
R410a Tropical Rooftop Package Unit 50Hz

MRCT-075EWN1-R

30
R410a Tropical Rooftop Package Unit 50Hz

MRBT-075HWN1-R

31
R410a Tropical Rooftop Package Unit 50Hz

8.4 8.5ton
MRBT-085CWN1-R

32
R410a Tropical Rooftop Package Unit 50Hz

MRCT-085EWN1-R

33
R410a Tropical Rooftop Package Unit 50Hz

MRBT-085HWN1-R

34
R410a Tropical Rooftop Package Unit 50Hz

8.5 10ton
MRBT-100CWN1-R

35
R410a Tropical Rooftop Package Unit 50Hz

MRCT-100EWN1-R

36
R410a Tropical Rooftop Package Unit 50Hz

MRBT-100HWN1-R

37
R410a Tropical Rooftop Package Unit 50Hz

8.6 15ton

MRCT-150CWN1-R

38
R410a Tropical Rooftop Package Unit 50Hz

MRCT-150EWN1-R

39
R410a Tropical Rooftop Package Unit 50Hz

MRBT-150HWN1-R

40
R410a Tropical Rooftop Package Unit 50Hz

8.7 17.5ton

MRBT-175CWN1-R

41
R410a Tropical Rooftop Package Unit 50Hz

MRCT-175EWN1-R

42
R410a Tropical Rooftop Package Unit 50Hz

MRBT-175HWN1-R

43
R410a Tropical Rooftop Package Unit 50Hz

8.8 20ton

MRBT-200CWN1-R

44
R410a Tropical Rooftop Package Unit 50Hz

MRCT-200EWN1-R

45
R410a Tropical Rooftop Package Unit 50Hz

MRBT-200HWN1-R

46
R410a Tropical Rooftop Package Unit 50Hz

8.9 30ton

MRCT-300HWN1-R

47
R410a Tropical Rooftop Package Unit 50Hz

9. Performance Data

9.1 Cooling capacity for 5Ton:

Air Flow CFM 1800

Ent DB (℉) 75 80 85 90

TGC 63.6 66.8 72.8 75


61
SHC 46.8 48.1 51.7 53.2

TGC 65.7 69 74.5 76.7


75 67
SHC 47.3 49 52.9 54.5

TGC 67.4 70.7 76.4 78.3


73
SHC 47.8 50.2 54.2 55.7

TGC 59.6 62.6 68.2 70.3


61
SHC 42.9 45.1 49.1 50.6

TGC 61.5 64.6 69.7 71.8


85 67
SHC 44.3 46.5 50.2 51.7

TGC 63 66.2 71.5 73.3


73
45.4 47.7 51.5 52.8
Ambient Temperature(℉)

SHC

TGC 55.5 58.3 63 64.8


61
Entering Wet Bulb(℉)

SHC 41.1 43.1 46.6 48

TGC 57.1 60 65 66.9


95 67
SHC 41.7 44 47.2 48.8

TGC 58.7 61.7 66.6 68.3


73
SHC 42.9 45 48.6 49.8

TGC 51.6 54.2 59 60.8


61
SHC 39.7 41.7 45.5 46.8

TGC 53.2 55.9 60.3 62.2


105 67
SHC 40.4 42.5 45.9 47.2

TGC 54.6 57.3 61.9 63.4


73
SHC 40.9 43 46.4 47.6

TGC 47.4 49.7 54.2 55.8


61
SHC 38.8 39.3 42.8 44.1

TGC 48.8 51.2 55.7 57.4


115 67
SHC 39 39.8 43.7 45.4

TGC 49.9 52.4 57.1 58.6


73
SHC 39.4 41.4 45.1 46.2

Notes:

1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.

2. TGC=Total Gross Capacity. (Unit: MBtu/h).

3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).

48
R410a Tropical Rooftop Package Unit 50Hz
9.2 Cooling capacity for 6.2Ton:

Air Flow CFM 2400 2600 2800

Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90

TGC 73.9 75.3 76.8 78.4 75.6 77.1 78.6 80.2 77.0 78.5 80.1 81.7
61
SHC 65.5 71.3 74.6 77.1 69.4 71.5 74.4 78.1 72.9 76.4 79.1 80.6

TGC 81.1 82.8 84.4 86.1 81.8 83.4 85.1 86.8 82.3 83.9 85.6 87.4
85 67
SHC 49.1 61.4 72.3 81.5 50.3 62.4 74.6 84.7 51.4 64.1 76.7 85.3

TGC 83.9 85.6 87.3 89.0 84.1 85.8 87.5 89.3 84.4 86.1 87.7 89.5
73
SHC 31.6 42.9 52.7 63.5 32.0 46.4 53.6 63.8 32.4 48.0 54.3 65.0

TGC 68.5 69.9 71.3 72.8 70.5 71.9 73.4 74.8 72.2 73.6 75.1 76.6
61
SHC 61.2 66.5 68.7 72.2 63.6 67.1 70.7 73.4 70.9 72.0 73.8 75.6

TGC 73.7 75.2 77.4 79.8 74.1 75.6 77.9 80.2 78.9 83.0 85.4 86.2
95 67
SHC 47.6 60.6 73.2 77.3 49.7 63.5 76.8 77.8 51.7 66.1 80.0 81.1
Ambient Temperature(°F)

Entering Wet Bulb(°F)

TGC 83.2 84.9 86.6 88.3 83.5 85.2 86.9 88.6 83.4 85.1 86.8 88.5
73
SHC 30.6 43.3 54.2 65.4 31.1 44.0 55.5 67.0 31.6 47.0 56.6 68.6

TGC 63.0 64.2 65.5 66.8 64.7 66.0 67.4 68.7 66.3 67.7 69.0 70.4
61
SHC 60.2 61.3 64.6 66.3 63.7 64.7 65.9 68.0 64.4 66.5 67.9 69.8

TGC 73.0 74.5 76.0 77.5 74.3 75.8 77.3 78.9 75.4 76.9 78.4 80.0
105
67
SHC 45.4 56.0 71.9 76.4 47.6 62.0 76.7 78.1 49.8 65.3 76.2 78.2

TGC 80.6 82.2 83.8 85.5 81.8 83.4 85.1 86.8 82.2 83.8 85.5 87.2
73
SHC 28.9 42.6 55.5 66.7 30.0 44.2 56.9 68.5 30.4 45.2 58.3 70.7

TGC 56.9 58.0 59.1 60.3 59.1 60.2 61.4 62.7 61.0 62.2 63.5 64.7
61
SHC 51.8 54.4 57.2 58.5 56.9 58.5 60.1 61.9 59.5 60.2 62.3 64.1

TGC 66.4 67.8 69.1 70.5 63.1 65.0 66.3 68.3 69.0 70.3 71.8 73.2
115
67
SHC 42.7 55.8 66.3 69.5 44.9 59.4 61.2 63.0 47.1 63.0 69.5 72.4

TGC 72.8 74.2 75.7 77.3 78.6 80.2 81.8 83.4 79.2 80.8 82.4 84.0
73
SHC 27.9 41.0 53.7 66.1 28.5 42.6 56.4 69.6 29.0 44.4 58.7 72.7

TGC 52.2 53.2 54.2 55.3 54.2 55.3 56.4 57.5 55.9 57.1 58.2 59.4
61
SHC 47.5 49.9 52.5 53.6 52.2 53.6 55.1 56.9 54.6 55.3 57.1 58.8

TGC 60.9 62.2 63.4 64.6 62.2 63.5 64.7 66.0 63.3 64.6 65.8 67.1
125
67
SHC 39.2 51.3 60.8 63.7 41.2 54.5 63.7 65.7 43.2 57.8 63.7 66.4

TGC 66.8 68.1 69.5 70.8 72.1 73.5 75.1 76.5 72.7 74.1 75.6 77.1
73
SHC 25.6 37.6 49.3 60.7 26.1 39.1 51.7 63.9 26.7 40.8 53.9 66.7

Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).

Heating capacity for 6.2Ton:


Net Capacities(kW)-2600 CFM
Outdoor
Temp(°F) Peak Net Heating(kW) at Indicated Dry Bulb(°F) Peak Total Power (kW) at Indicated Dry Bulb(°F)
70% RH
59 68 75.2 80.6 59 68 75.2 80.6
23 15.7 15.2 14.8 14.3 6.0 6.3 6.5 6.7
26.6 17.4 16.9 16.4 15.9 6.3 6.6 6.8 7.0
32 19.3 18.8 18.2 17.7 6.7 6.9 7.2 7.4
37.4 22.8 22.1 21.4 20.8 7.0 7.3 7.5 7.8
44.6 26.8 26.0 25.2 24.5 7.4 7.6 7.9 8.2
48.2 28.7 27.8 27.0 26.2 7.5 8.3 8.8 9.3
53.6 30.4 29.5 28.6 27.7 7.8 8.7 9.1 9.7
59 32.2 31.3 30.3 29.4 7.9 8.9 9.3 9.9
64.4 34.1 33.1 32.1 31.2 8.2 9.0 9.6 10.2
69.8 36.2 35.1 34.1 33.0 8.3 9.2 9.7 10.2
75.2 38.3 37.2 36.1 35.0 8.5 9.3 10.1 10.4
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.

49
R410a Tropical Rooftop Package Unit 50Hz
9.3 Cooling capacity for 7.5Ton:

Air Flow CFM 2800 3000 3200

Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90

TGC 82.5 84.2 85.8 87.5 87.3 89 90.8 92.6 89.3 91.1 92.9 94.8
61
SHC 72.7 80.4 85.3 87.5 77.4 84.3 88.2 91.1 82 84.5 87.9 92.3

TGC 94.8 96.7 98.6 100.6 95.9 97.8 99.8 101.8 96.7 98.6 100.6 102.6
85 67
SHC 55.6 68.8 81.8 94.3 58 72.6 85.4 96.3 59.5 73.8 83.2 100.1

TGC 98.6 100.6 102.6 104.6 99.2 101.2 103.2 105.2 99.4 101.4 103.4 105.5
73
SHC 36.8 51 62 72.4 37.3 50.7 62.3 75.1 37.8 54.8 63.3 75.4

TGC 78.6 80.2 81.8 83.4 81 82.6 84.3 86 83.3 85 86.7 88.4
61
SHC 69.6 75.6 78 81.4 72.3 78.6 81.2 85.3 75.2 79.3 83.5 86.7

TGC 85.6 87.3 89.1 90.8 87.1 89 96.6 98 91.4 96.2 98.1 99.8
95 67
SHC 53.9 67.7 81.6 86.2 56.3 71.6 86.5 91.3 58.7 75 90.8 92
Ambient Temperature(°F)

Entering Wet Bulb(°F)

TGC 97.8 99.8 101.8 103.8 98.3 100.3 102.3 104.3 98.7 100.7 102.7 104.7
73
SHC 35.7 50.2 62.3 74.5 36.2 51.2 64.1 77.3 36.8 52 65.6 79.2

TGC 72.1 73.5 75 76.5 74.4 75.9 77.4 79 76.5 78 79.6 81.2
61
SHC 66.4 68.3 71.3 73.2 71.2 72.4 76.3 78.4 75.3 76.5 77.9 80.4

TGC 84.4 86.1 87.8 89.6 86.3 88 89.8 91.6 87.8 89.6 91.3 93.2
105
67
SHC 51 65 79.2 86.3 53.7 66.2 85 90.3 56.3 73.3 90.6 92.3

TGC 95.3 97.2 99.2 101.1 95.2 97.1 99 101 96.7 98.6 100.6 102.6
73
SHC 34.2 48.9 64.2 76.8 34.1 50.4 65.6 78.8 35.4 52.2 67.2 80.9

TGC 65.3 66.6 67.9 69.3 67.2 68.5 69.9 71.3 69.8 71.2 72.6 74.1
61
SHC 63.2 64.6 66.4 68.6 61.2 64.3 67.6 69.1 67.3 69.1 71 73.2

TGC 76.7 78.2 79.8 81.4 78.5 80.1 81.7 83.3 80.1 817 83.3 85
115
67
SHC 47.8 62.1 75.4 80.2 50.5 66 78.3 82.1 53.1 70.2 82.1 84.6

TGC 90.8 92.6 94.5 96.4 86 87.7 89.5 91.3 92.9 94.8 96.7 98.6
73
SHC 32.4 46.3 61.2 76.4 33 48.4 63.5 78.1 33.7 50.4 66.6 82.3

TGC 59.9 61.1 62.3 63.6 61.7 62.9 64.1 65.4 64 65.3 66.6 68
61
SHC 58 59.3 60.9 62.9 56.1 59 62 63.4 61.7 63.4 65.1 67.2

TGC 70.4 71.8 73.2 74.7 72 73.5 74.9 76.4 73.5 75 76.5 78
125
67
SHC 43.9 57 69.2 73.6 46.3 60.6 71.8 75.3 48.7 64.4 75.3 77.6

TGC 83.3 85 86.7 88.4 78.9 80.5 82.1 83.7 85.2 86.9 88.7 90.4
73
SHC 29.7 42.5 56.1 70.1 30.3 44.4 58.3 71.7 30.9 46.2 61.1 75.5

Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).

Heating capacity for 7.5Ton:


Net Capacities(kW)-3000 CFM
Outdoor Temp(℉) 70% Peak Net Heating(kW) at Indicated Dry Bulb(℉) Peak Total Power(KW) at Indicated Dry Bulb(℉)
RH 59 68 75.2 80.6 59 68 75.2 80.8
5 14.9 14.0 13.7 13.4 6.9 7.6 8.0 8.5
10.4 16.0 15.3 15.0 14.9 7.1 7.7 8.1 8.6
15.8 17.0 16.5 16.4 16.4 7.1 7.8 8.2 8.8
21.2 17.8 17.3 17.1 16.9 7.2 7.9 8.3 8.9
26.6 18.8 18.5 18.4 18.1 7.3 8.0 8.5 9.1
32 20.3 20.0 19.7 19.4 7.4 8.1 8.6 9.2
37.4 23.3 23.1 22.7 22.4 7.5 8.3 8.8 9.3
44.6 30.3 30 29.6 29.2 7.8 8.8 9.1 9.6
48.2 30.5 30.2 29.9 29.6 8.1 9.0 9.5 10.1
53.6 32.4 33.5 33.4 33.1 8.4 9.4 9.9 10.5
59 35.0 34.4 34.2 33.8 8.6 9.6 10.1 10.7
64.4 37.1 36.4 36.0 35.7 8.9 9.8 10.4 11.0
69.8 39.8 38.9 38.4 37.9 9.0 10.0 10.5 11.0
75.2 42.0 40.9 40.2 39.8 9.2 10.1 10.9 11.3
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.

50
R410a Tropical Rooftop Package Unit 50Hz
9.4 Cooling capacity for 8.5Ton:
Air Flow CFM 3000 3300 3600

Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 91.6 95.5 99.3 102.4 96.5 100.7 104.5 107.8 98.6 102.8 106.7 110.2
61
SHC 71.4 82.1 90.1 94.9 76.8 88.1 96.6 101.7 80.8 92.8 101.7 107.1
TGC 101.4 103.2 104.7 105.6 106.7 108.6 110.2 111.4 109 110.9 112.5 113.7
85 67
SHC 54.1 67.9 81.7 90.6 58.1 72.8 87.7 97.3 61.2 76.6 92.3 102.6
TGC 103.2 104.8 106.4 107.7 108.6 109.5 111.2 113.5 112.4 114.1 115.8 117.1
73
SHC 23.9 44.5 61.6 74.9 25.8 48.3 67.9 86.1 27.2 56.3 74.6 97.8
TGC 88.5 92.3 95.8 99.0 93.1 97.1 100.8 104.2 95.1 99.2 102.9 106.3
61
SHC 72.6 83.2 91.7 96.3 78.2 89.8 98.6 103.7 82.4 94.6 98.1 102.1
TGC 97.8 99.6 101.0 102.3 99.8 101.8 104.3 105.4 101.1 103.0 105.5 107.7
95 67
Ambient Temperature(°F)

SHC 55.2 68.7 83.4 92.4 59.2 74.3 89.4 99.8 62.4 78.1 94.1 104.5
Entering Wet Bulb(°F)

TGC 104.1 106 107.5 109.1 110.7 111.8 112.9 114.1 113.2 114.6 116.3 118.7
73
SHC 26.4 55.2 67.8 88.9 26.1 48.9 69.8 82.3 30.8 67.2 94.3 106.7
TGC 83.7 87.5 90.8 93.8 88.1 91.9 95.4 98.5 90.1 93.8 97.4 100.6
61
SHC 69.7 80.0 87.7 92.3 74.7 85.8 94.1 98.5 78.7 90.4 93.5 96.5
TGC 92.6 94.2 95.8 97.1 97.4 99.1 100.5 101.7 99.5 101.2 102.7 103.8
105 67
SHC 52.8 66.1 79.5 88.4 56.6 70.8 86.1 98.3 59.6 74.7 89.9 99.8
TGC 94.5 96.1 97.8 99.4 104.1 105.6 107.2 108.6 106.9 108.3 109.7 111.2
73
SHC 23.3 44.7 59.8 72.6 82.3 87.1 90.6 99.8 31.2 67.4 98.6 106.8
TGC 78.3 81.6 84.7 87.6 82.3 86.1 89.6 92.3 84.1 87.7 92.1 94.0
61
SHC 67.2 77.1 83.5 86.6 72 82.7 89.1 92.0 75.8 87.1 91.0 92.7
TGC 76.5 78.1 79.3 80.6 81 82.6 84.0 85.4 89.9 91.6 95.4 99.5
115 67
SHC 50.9 63.7 76.7 85.2 54.5 68.7 82.3 94.6 57.4 71.9 86.6 96.2
TGC 95.1 96.4 97.8 99.8 97.8 99.3 101.4 103.6 99.9 101.3 103.4 105.2
73
SHC 22.5 41.8 57.7 70.5 28.3 53.2 89.1 101.6 32.1 68.4 98.9 103.6
TGC 71.2 74.2 77.0 79.6 74.8 78.3 81.5 83.9 76.5 79.7 83.7 85.5
61
SHC 61.1 70.1 76.8 78.5 65.5 75.2 81.0 83.6 68.9 79.2 82.7 84.3
TGC 78.6 80.1 81.2 82.4 82.7 84.2 85.5 86.7 84.5 86.0 87.3 88.3
125 67
SHC 46.3 57.9 69.7 77.5 49.5 62.5 74.8 86.0 52.2 65.4 78.7 87.5
TGC 86.5 87.6 88.9 90.7 88.9 90.3 92.2 94.2 90.8 92.1 94.0 95.6
73
SHC 20.5 38.0 52.5 64.1 25.7 48.4 81.0 92.4 29.2 62.2 89.9 94.2

Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
Heating capacity for 8.5Ton:
Net Capacities(kW)-3600 CFM
Peak Net Heating(kW) at Indicated Dry Bulb(℉) Peak Total Power(KW) at Indicated Dry Bulb(℉)
Outdoor Temp(℉) 70% RH
59 68 75.2 80.6 59 68 75.2 80.8
5 18.7 17.6 17.2 16.9 8.6 8.8 9.2 9.7
10.4 20.1 19.3 18.9 18.7 8.8 8.9 9.4 9.9
15.8 21.4 20.8 20.6 20.6 8.9 9.1 9.6 10.1
21.2 22.4 21.8 21.6 21.3 9.0 9.3 9.9 10.3
26.6 23.7 23.4 23.2 22.8 9.1 9.6 10.1 10.5
32 25.5 25.2 24.8 24.5 9.2 9.8 10.3 10.8
37.4 29.4 29.1 28.7 28.3 9.4 10.0 10.5 11.0
44.6 35.4 35.0 33.0 32.8 9.7 10.2 10.7 11.2
48.2 38.5 38.0 37.7 37.3 9.9 10.4 10.9 11.5
53.6 40.9 42.3 42.1 41.7 10.1 10.6 11.1 11.7
59 44.1 43.4 43.1 42.7 10.3 10.9 11.4 12.1
64.4 46.7 45.9 45.4 45.0 10.5 11.1 11.7 12.3
69.8 50.1 49.1 48.4 47.8 10.9 11.4 11.9 12.5
75.2 53.0 51.6 50.7 50.1 11.1 11.6 12.2 12.8
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.

51
R410a Tropical Rooftop Package Unit 50Hz
9.5 Cooling capacity for 10Ton:

Air Flow CFM 3800 4000 4200

Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90

TGC 110.9 113.1 115.4 117.7 113.8 116.1 118.4 120.8 116.5 118.8 121.2 123.6
61
SHC 96.8 98.7 100.7 102.7 103.2 105.3 107.4 109.5 109.2 111.4 113.6 115.9

TGC 123.4 125.9 128.4 131 124.6 127.1 129.6 132.2 125.7 128.2 130.8 133.4
85 67
SHC 73.2 92 108.3 124.8 75.6 94.3 112.8 128.5 78 97.3 116.5 130.4

TGC 127.9 130.5 133.1 135.7 128.3 130.9 133.5 136.2 128.6 131.2 133.8 136.5
73
SHC 47.7 64.9 79.6 95.3 48.3 65.8 81.2 96.7 49 72.1 82.4 98.4

TGC 102.8 104.9 107 109.1 105.9 108 110.2 112.4 108.9 111.1 113.3 115.6
61
SHC 92.7 94.6 96.4 98.4 99.2 101.2 103.2 105.3 105.4 107.5 109.7 111.9

TGC 116.7 117 118.5 121 119.5 121 123.5 126 124 126 128.7 132.3
95 67
Ambient Temperature(°F)

SHC 70.8 89.8 108.6 123.4 74.3 94.8 114 124.3 77.4 99.3 120.3 128.4
Entering Wet Bulb(°F)

TGC 126.8 129.3 131.9 134.6 127.1 129.6 132.2 134.9 127.8 130.4 133 135.6
73
SHC 46.3 65.4 81.5 97.8 47.2 66.7 84.3 101.9 47.5 67.6 85.8 104.7

TGC 94.5 96.4 98.3 100.3 97.8 99.8 101.8 103.8 99.8 101.8 103.8 105.9
61
SHC 88.6 90.4 92.2 94 95.2 97.1 99 101 93.4 95.3 97.2 99.1

TGC 110.3 112.5 114.8 117.1 112.9 115.2 117.5 119.8 114.6 116.9 119.2 121.6
105 67
SHC 67.6 86.4 105.9 115.6 71.3 92.1 113.7 117.9 74.2 98.3 115.5 117.6

TGC 123.8 126.3 128.8 131.4 124.6 127.1 129.6 132.2 125.2 127.7 130.3 132.9
73
SHC 44.3 63.2 81 98.3 45.2 65.6 85.3 103.7 45.7 67.5 86.9 106.8

TGC 86.3 88 89.8 91.6 89.2 91 92.8 94.7 92.3 94.1 96 97.9
61
SHC 84.6 86.3 88 89.8 86.2 87.9 89.7 91.5 90.2 92 93.8 95.7

TGC 101.3 103.3 105.4 107.5 103.2 107 107.4 109.5 105.6 107.7 109.9 112.1
115 67
SHC 63.5 83.2 102.1 104.1 67.3 88.2 105.3 107.4 70.8 94.1 107.3 110.5

TGC 119.2 121.6 124 126.5 120.1 122.5 125 127.5 120.8 123.2 125.7 128.2
73
SHC 42.2 61.3 80.1 98.7 42.9 64.1 84.3 104.1 43.7 66.8 87.9 109.3

TGC 78.5 80 81.6 83.3 81.1 82.7 84.4 86.1 83.9 85.6 87.8 89
61
SHC 76.9 78.4 80 81.6 78.4 79.9 81.5 83.2 82 83.6 85.3 87

TGC 92.1 93.9 95.8 97.7 93.8 97.9 98.2 99.6 96 98.1 99.9 101.9
125 67
SHC 57.7 75.6 92.8 94.7 61.2 80.2 95.7 97.6 64.4 85.5 97.7 100.5

TGC 108.4 110.5 112.7 115 109.2 111.4 113.6 115.9 109.8 112 114.3 116.5
73
SHC 38.4 55.7 72.8 89.7 39 58.3 76.6 94.6 39.7 60.7 79.9 99.4

Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).

Heating capacity for 10Ton:


Net Capacities(kW)-4000 CFM
Outdoor Temp(℉) 70% Peak Net Heating(kW) at Indicated Dry Bulb(℉) Peak Total Power(KW) at Indicated Dry Bulb(℉)
RH 59 68 75.2 80.6 59 68 75.2 80.8
5 19.8 18.6 18.2 17.9 9.2 10.1 10.7 11.3
10.4 21.3 20.4 20 19.8 9.4 10.3 10.8 11.5
15.8 22.6 22 21.8 21.8 9.5 10.4 10.9 11.7
21.2 23.7 23 22.8 22.5 9.6 10.5 11.1 11.9
26.6 25.1 24.7 24.5 24.1 9.7 10.6 11.3 12.1
32 27 26.6 26.2 25.9 9.8 10.8 11.5 12.2
37.4 31.1 30.8 30.3 29.9 10 11 11.7 12.4
44.6 37.8 37 36.3 35.7 10.4 10.9 11.9 12.8
48.2 40.7 40.2 39.8 39.4 10.8 12 12.7 13.5
53.6 43.2 44.7 44.5 44.1 11.2 12.5 13.2 14
59 46.6 45.9 45.6 45.1 11.5 12.8 13.5 14.3
64.4 49.4 48.5 48 47.6 11.8 13.1 13.9 14.6
69.8 53 51.9 51.2 50.5 12 13.3 14 14.7
75.2 56 54.5 53.6 53 12.3 13.5 14.5 15
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.

52
R410a Tropical Rooftop Package Unit 50Hz
9.6 Cooling capacity for 15Ton:
Air Flow CFM 5500 6000 6500

Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90

TGC 163.6 165.6 172.9 182.7 168 171.6 179 188.7 169.9 174.2 185.1 193.6
61
SHC 131.5 155.8 166 175.3 138.7 165.6 173.6 183 146.1 167.2 177.7 185.9

TGC 183.3 185.5 187.6 190.2 188.7 190 191.1 192.4 191 192.5 193.6 195.1
85 67
SHC 104.7 127.8 149.8 172.9 109.3 132.7 157.1 180.2 111.2 136.4 162 187.6

TGC 193.6 197.3 199.8 202.2 195.8 198.5 202.2 204.5 198.3 201 203.3 205.8
73
SHC 72.2 96.8 117 136.4 73.6 99 119.6 138.6 74.9 99.9 121.6 143.7

TGC 153.4 157.1 164.5 175.4 155.3 162 171.7 181.4 160.8 164.5 176.6 186.3
61
SHC 125.3 149.8 159.5 170.1 132.7 157.1 166.6 176 140.1 159.5 171.3 180.8

TGC 171.7 174.2 176.6 180.2 179 180 182.7 183.9 185.1 186.5 187.7 188.7
95 67
Ambient Temperature(°F)

SHC 99.9 123 146.1 169.2 104.1 129 153.5 179 108.1 132.8 160.8 186.3
Entering Wet Bulb(°F)

TGC 188.8 191.1 193.5 196.1 190.2 192.2 195.2 198.5 191.9 194.3 196.8 198
73
SHC 69 93.1 114.8 135.2 70.5 96.3 117.8 140.1 71.8 97.9 120.7 143.7

TGC 142.7 146.4 153.8 166.1 147.6 151.3 163.6 171 150.1 156.2 169.7 180.8
61
SHC 119.6 140.5 147.6 159.4 127.9 145.2 157 164.1 135.3 151.5 164.6 173.2

TGC 163.6 166.1 169.7 171 164.8 168.5 173.4 175.9 173.4 175.9 178.4 180.8
105 67
SHC 94.6 118.1 141.3 165.7 109 124.2 149.8 170.6 102.6 130.3 157.1 175.4

TGC 185.7 187 188.2 189.4 188.2 189.4 190.7 193.1 190.7 191.9 193.1 194.3
73
SHC 65.6 89.2 111.7 132.8 67 92.3 115.5 138.9 68.3 95.3 118.6 142.4

TGC 130.4 135.3 147.6 159.9 134.1 141.5 153.8 166.1 137.8 140.4 150.9 172.2
61
SHC 114.5 131.2 143.2 155.1 121.6 135.8 147.6 159.4 127.9 136.2 146.9 167

TGC 153.8 156.2 157.4 160.9 155 158.7 161.1 163.6 163.6 166.1 169.7 174
115 67
SHC 98.4 113.4 136.5 159.9 103.3 119.9 145.1 163.6 108.2 125.5 151.3 168.8

TGC 173.4 175.9 178.4 179.6 178.4 180.8 182 183.3 182 183.3 184.5 185.7
73
SHC 62.1 85.6 108.9 131.6 63.5 89.8 113.2 136.5 66.4 92.3 118.1 143.9

TGC 125.4 130.1 141.9 152.1 128.9 136 147.8 159.7 132.5 140.7 153.8 165.6
61
SHC 110.1 126.2 137.7 147.5 117 131.9 143.4 154.9 13 136.5 149.1 160.6

TGC 147.8 150.2 151.4 153.8 149 152.6 154.9 157.3 157.3 159.7 163.2 167.1
125 67
SHC 94.6 109 131.3 153.8 99.3 115.3 139.6 152.6 104.1 120.6 145.5 162.1

TGC 166.8 169.1 171.5 172.7 171.5 173.9 175 176.2 175 176.2 177.4 178.6
73
SHC 59.7 82.3 104.7 126.5 61 86.3 108.8 131.3 63.9 88.7 113.5 138.4

Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).

Heating capacity for 15Ton:


Net Capacities(kW)-6000 CFM
Outdoor Temp(℉) Peak Net Heating(kW) at Indicated Dry Bulb(℉) Peak Total Power(KW) at Indicated Dry Bulb(℉)
70% RH 59 68 75.2 80.6 59 68 75.2 80.8
5 29.7 27.9 27.3 26.9 13.8 15.2 16.1 17.0
10.4 32.0 30.6 30.0 29.7 14.1 15.5 16.2 17.3
15.8 33.9 33.0 32.7 32.7 14.3 15.6 16.4 17.6
21.2 35.6 34.5 34.2 33.8 14.4 15.8 16.7 17.9
26.6 37.7 37.1 36.8 36.2 14.6 15.9 17.0 18.2
32 40.5 39.9 39.3 38.9 14.7 16.2 17.3 18.3
37.4 46.7 46.2 45.5 44.9 15.0 16.5 17.6 18.6
44.6 56.7 56 54.3 53.7 15.6 17.5 18.2 19.2
48.2 61.1 60.3 59.7 59.1 16.2 18.0 19.1 20.3
53.6 64.8 67.1 66.8 66.2 16.8 18.8 19.8 21.0
59 69.9 68.9 68.4 67.7 17.3 19.2 20.3 21.5
64.4 74.1 72.8 72.0 71.4 17.7 19.7 20.9 21.9
69.8 79.5 77.9 76.8 75.8 18.0 20.0 21.0 22.1
75.2 84.0 81.8 80.4 79.5 18.5 20.3 21.8 22.5

Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.

53
R410a Tropical Rooftop Package Unit 50Hz
9.7 Cooling capacity for 17.5Ton:

Air Flow CFM 6800 7300 7600

Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90

TGC 187.6 189.9 198.3 209.5 192.6 196.8 205.3 216.4 194.8 199.7 212.2 222.0
61
SHC 150.8 178.7 190.3 201.0 159.0 189.9 199.1 209.8 167.5 191.7 203.8 213.2

TGC 210.2 212.7 215.1 218.1 216.4 217.9 219.1 220.6 219.0 220.7 222.0 223.7
85 67
SHC 120.1 146.5 171.8 198.3 125.3 152.2 180.1 206.6 127.5 156.4 185.8 215.1

TGC 222.0 226.2 229.1 231.9 224.5 227.6 231.9 234.5 227.4 230.5 233.1 236.0
73
SHC 82.8 111.0 134.2 156.4 84.4 113.5 137.1 158.9 85.9 114.6 139.4 164.8

TGC 175.9 180.1 188.6 201.1 178.1 185.8 196.9 208.0 184.4 188.6 202.5 213.6
61
SHC 143.7 171.8 182.9 195.0 152.2 180.1 191.0 201.8 160.6 182.9 196.4 207.3

TGC 196.9 199.7 202.5 206.6 205.3 206.4 209.5 210.9 212.2 213.9 215.2 216.4
95 67
SHC 114.6 141.0 167.5 194.0 119.4 147.9 176.0 205.3 124.0 152.3 184.4 213.6

TGC 216.5 219.1 221.9 224.9 218.1 220.4 223.8 227.6 220.0 222.8 225.7 227.0
73
SHC 79.1 106.8 131.6 155.0 80.8 110.4 135.1 160.6 82.3 112.3 138.4 164.8
Ambient Temperature(°F)

TGC 163.6 167.9 176.4 190.5 169.2 173.5 187.6 196.1 172.1 179.1 194.6 207.3
Entering Wet Bulb(°F)

61
SHC 137.1 161.1 169.2 182.8 146.7 166.5 180.0 188.2 155.1 173.7 188.7 198.6

TGC 187.6 190.5 194.6 196.1 189.0 193.2 198.8 201.7 198.8 201.7 204.6 207.3
105 67
SHC 108.5 135.4 162.0 190.0 125.0 142.4 171.8 195.6 117.6 149.4 180.1 201.1

TGC 212.9 214.4 215.8 217.2 215.8 217.2 218.7 221.4 218.7 220.0 221.4 222.8
73
SHC 75.2 102.3 128.1 152.3 76.8 105.8 132.4 159.3 78.3 109.3 136.0 163.3

TGC 149.5 155.1 169.2 183.4 153.8 162.3 176.4 190.5 158.0 161.0 173.0 197.5
61
SHC 131.3 150.4 164.2 177.8 139.4 155.7 169.2 182.8 146.7 156.2 168.4 191.5

TGC 176.4 179.1 180.5 183.4 177.7 182.0 184.7 187.6 187.6 190.5 194.6 199.5
115 67
SHC 112.8 130.0 156.5 183.4 118.5 137.5 166.4 187.6 124.1 143.9 173.5 193.6

TGC 198.8 201.7 204.6 205.9 204.6 207.3 208.7 210.2 208.7 210.2 211.6 212.9
73
SHC 71.2 98.2 124.9 150.9 72.8 103.0 129.8 156.5 76.1 105.8 135.4 165.0

TGC 143.8 149.2 162.7 174.4 147.8 155.9 169.5 183.1 151.9 161.3 176.4 189.9
61
SHC 126.2 144.7 157.9 169.1 134.2 151.2 164.4 177.6 141.0 156.5 171.0 184.2

TGC 169.5 172.2 173.6 176.4 170.9 175.0 177.6 180.4 180.4 183.1 187.1 191.6
125 67
SHC 100.4 125.0 150.6 176.4 113.5 132.2 160.1 175.0 119.4 138.3 166.8 185.9

TGC 191.3 193.9 196.7 198.0 196.7 199.4 200.7 202.0 200.7 202.0 203.4 204.8
73
SHC 68.5 94.4 120.1 145.1 69.9 99.0 124.8 150.6 73.3 101.7 130.1 158.7

Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).

Heating capacity for 17.5Ton:


Net Capacities(kW)-7300 CFM

Outdoor Temp(℉) 70% RH Peak Net Heating(kW) at Indicated Dry Bulb(℉) Peak Total Power(KW) at Indicated Dry Bulb(℉)
59 68 75.2 80.6 59 68 75.2 80.8
5 35.6 33.5 32.8 32.3 15.6 17.2 18.2 19.2
10.4 38.4 36.7 36.0 35.6 15.9 17.5 18.3 19.5
15.8 40.7 39.6 39.2 39.2 16.2 17.6 18.5 19.9
21.2 42.7 41.4 41.0 40.6 16.3 17.9 18.9 20.2
26.6 45.2 44.5 44.2 43.4 16.5 18.0 19.2 20.6
32 48.6 47.9 47.2 46.7 16.6 18.3 19.5 20.7
37.4 56.0 55.4 54.6 53.9 17.0 18.6 19.9 21.0
44.6 68.5 67.0 62.9 62.5 17.6 19.8 20.6 21.7
48.2 73.3 72.4 71.6 70.9 18.3 20.3 21.6 22.9
53.6 77.8 80.5 80.2 79.4 19.0 21.2 22.4 23.7
59 83.9 82.7 82.1 81.2 19.5 21.7 22.9 24.3
64.4 88.9 87.4 86.4 85.7 20.0 22.3 23.6 24.7
69.8 95.4 93.5 92.2 91.0 20.3 22.6 23.7 25.0
75.2 100.8 98.2 96.5 95.4 20.9 22.9 24.6 25.4
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.

54
R410a Tropical Rooftop Package Unit 50Hz
9.8 Cooling capacity for 20Ton:

Air Flow CFM 7700 8400 9000

Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90

TGC 216.1 218.7 228.5 241.3 222.0 226.7 236.4 249.3 224.4 230.1 244.6 255.8
61
SHC 173.7 205.9 221.6 234.1 183.3 218.7 229.3 241.8 193.1 223.2 237.2 248.1

TGC 242.1 245.1 247.8 251.2 249.3 251.1 252.5 254.2 252.4 254.3 255.8 257.7
85 67
SHC 138.3 168.8 197.9 228.5 144.5 175.3 207.5 238.1 146.9 180.2 214.0 247.8

TGC 255.8 260.7 263.9 267.2 258.7 262.3 267.2 270.2 262.0 265.5 268.6 271.9
73
SHC 95.4 127.9 154.5 180.2 97.2 130.8 158.0 183.1 99.0 132.0 160.7 189.8

TGC 202.6 207.5 217.3 231.7 205.2 214.0 226.9 239.7 212.4 217.3 233.4 246.2
61
SHC 165.6 197.9 210.7 224.8 175.3 205.5 217.8 230.1 185.1 210.7 226.3 238.8

TGC 226.9 230.1 233.4 238.1 236.4 240.0 241.3 242.9 244.6 246.4 248.0 249.3
95 67
Ambient Temperature(°F)

SHC 132.0 162.5 193.1 223.6 137.5 170.5 202.8 236.4 142.8 175.5 212.4 246.2
Entering Wet Bulb(°F)

TGC 249.4 252.5 255.6 259.0 251.2 254.0 257.9 262.3 253.5 256.8 260.0 261.6
73
SHC 91.2 123.0 151.6 178.6 93.1 127.2 155.7 185.1 94.9 129.4 159.4 189.8

TGC 188.5 193.4 203.1 219.4 195.0 199.9 216.1 225.9 198.3 206.4 224.3 238.9
61
SHC 158.0 187.6 197.0 212.8 169.0 193.9 209.6 219.1 178.8 200.2 217.5 231.7

TGC 216.1 219.4 224.3 225.9 217.8 222.6 229.1 232.4 229.1 232.4 235.6 238.9
105 67
SHC 125.0 156.0 186.7 218.9 144.0 164.1 197.9 209.1 135.5 172.1 207.5 238.9

TGC 245.4 247.0 248.6 250.3 248.6 250.3 251.9 255.1 251.9 253.5 255.1 256.8
73
SHC 86.6 117.8 147.6 175.5 88.6 122.0 152.6 183.5 90.2 125.9 156.7 188.2

TGC 172.3 178.8 195.0 211.3 177.1 186.9 203.1 219.4 182.0 193.4 211.3 227.5
61
SHC 151.3 173.4 189.2 204.9 160.7 181.3 197.0 212.8 169.0 187.6 204.9 220.7
TGC 203.1 206.4 208.0 211.3 204.8 209.6 212.9 216.1 216.1 219.4 224.3 227.5
115 67
SHC 130.0 149.8 180.4 211.3 136.5 158.4 191.8 216.1 143.0 165.8 199.9 227.5
TGC 229.1 232.4 235.6 237.3 235.6 238.9 240.5 242.1 240.5 242.1 243.8 245.4
73
SHC 82.1 113.1 143.8 173.9 83.9 118.6 149.5 180.4 87.8 121.9 156.0 190.1
TGC 162.5 168.6 184.0 199.3 167.1 176.3 191.6 207.0 171.6 182.4 199.3 214.6
61
SHC 147.2 163.6 178.4 193.3 151.6 171.0 185.9 200.7 159.4 177.0 193.3 208.2
TGC 191.6 194.7 196.2 210.3 193.2 197.8 200.8 203.9 203.9 207.0 211.6 214.6
125 67
SHC 122.6 141.3 170.2 189.3 128.8 149.5 180.9 199.8 134.9 156.4 188.6 210.3
TGC 216.2 219.2 222.3 223.8 222.3 225.4 226.9 228.4 226.9 228.4 230.0 231.5
73
SHC 77.4 106.7 135.7 164.0 79.1 111.9 141.0 170.2 82.8 115.0 147.2 179.4

Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).

Heating capacity for 20Ton:


Net Capacities(kW)-8400 CFM
Outdoor Temp(℉) Peak Net Heating(kW) at Indicated Dry Bulb(℉) Peak Total Power(KW) at Indicated Dry Bulb(℉)
70% RH 59 68 75.2 80.6 59 68 75.2 80.8
5 39.6 37.2 36.4 35.8 18.4 20.2 21.4 22.6
10.4 42.6 40.8 40.0 39.6 18.8 20.6 21.6 23.0
15.8 45.2 44.0 43.6 43.6 19.0 20.8 21.8 23.4
21.2 47.4 46.0 45.6 45.0 19.2 21.0 22.2 23.8
26.6 50.2 49.4 49.0 48.2 19.4 21.2 22.6 24.2
32 54.0 53.2 52.4 51.8 19.6 21.6 23.0 24.4
37.4 62.2 61.6 60.6 59.8 20.0 22.0 23.4 24.8
44.6 75.8 75 74.2 73.6 20.8 23.4 24.2 25.6
48.2 81.4 80.4 79.6 78.8 21.6 24.0 25.4 27.0
53.6 86.4 89.4 89.0 88.2 22.4 25.0 26.4 28.0
59 93.2 91.8 91.2 90.2 23.0 25.6 27.0 28.6
64.4 98.8 97.0 96.0 95.2 23.6 26.2 27.8 29.2
69.8 106.0 103.8 102.4 101.0 24.0 26.6 28.0 29.4
75.2 112.0 109.0 107.2 106.0 24.6 27.0 29.0 30.0
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.

55
R410a Tropical Rooftop Package Unit 50Hz
9.9 Cooling capacity for 30Ton:
Air Flow(CFM) 11000 12000 13000
Ent DB (F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 289.0 292.9 307.0 326.0 297.5 304.5 318.8 337.6 301.2 309.5 330.6 347.0
61
SHC 231.3 278.2 298.0 315.9 245.2 297.2 312.7 324.8 259.5 300.3 320.6 336.4
TGC 327.1 331.4 335.4 340.5 337.6 340.1 342.2 344.7 342.0 344.9 347.0 349.9
85 67
SHC 179.4 224.1 266.6 311.3 188.3 233.6 280.8 325.4 192.0 240.7 290.2 319.7
TGC 347.0 354.2 359.0 363.7 351.3 356.5 363.7 368.1 356.1 361.3 365.8 370.6
73
SHC 116.6 164.2 203.2 240.7 119.3 168.4 208.3 245.0 121.8 170.2 212.1 254.8
TGC 269.3 276.5 290.8 311.8 273.0 313.2 304.7 323.4 283.6 290.8 314.2 332.9
61
SHC 219.3 266.6 285.4 305.9 233.6 276.0 299.1 317.3 247.9 285.4 308.2 326.6
TGC 315.0 319.8 324.5 331.4 329.1 331.0 336.3 338.6 340.9 343.6 345.9 347.9
95 67
SHC 170.2 214.8 259.5 304.1 230.3 278.4 301.8 313.1 233.0 249.8 293.9 319.2
TGC 337.8 342.2 346.8 351.9 340.5 344.3 350.1 356.5 343.7 348.4 353.2 355.5
73
SHC 110.4 157.0 199.0 238.4 113.3 163.2 204.8 247.9 115.8 166.3 210.4 254.8
Ambient Temperature( F)
O

TGC 248.6 255.8 270.1 293.9 258.1 265.3 289.0 303.3 262.9 274.7 300.8 322.3
61
SHC 208.3 248.7 262.4 285.2 224.3 257.7 280.6 294.3 238.6 269.9 295.3 311.9
TGC 289.0 293.9 300.8 303.3 291.4 298.5 308.0 312.8 308.0 312.8 317.6 322.3
105 67
SHC 159.9 205.4 250.2 297.4 187.8 217.1 266.6 306.9 175.4 228.9 280.8 316.1
TGC 331.8 334.3 336.6 338.9 336.6 338.9 341.4 346.1 341.4 343.7 346.1 348.0
73
SHC 103.9 149.5 193.0 233.8 106.6 155.5 200.3 245.6 109.1 161.3 206.3 252.3
TGC 234.8 244.3 268.1 291.9 242.0 256.3 280.1 303.9 249.2 254.2 274.5 315.7
61
SHC 198.4 230.7 253.9 276.9 212.1 239.6 262.4 285.2 224.3 238.3 251.0 289.9
TGC 290.1 294.7 297.0 301.9 292.4 299.6 302.2 309.0 309.0 313.9 320.8 329.1
115 67
SHC 192.9 221.9 266.5 291.0 202.3 234.4 283.2 287.0 216.8 250.3 290.1 294.0
TGC 308.0 312.8 317.6 320.0 317.6 322.3 324.6 327.1 324.6 327.1 329.4 331.8
73
SHC 97.1 142.5 187.6 231.5 102.8 150.6 195.9 240.9 105.4 155.5 205.4 255.2
TGC 215.2 224.3 247.1 266.8 221.9 235.7 258.5 281.5 228.9 244.8 270.1 292.9
61
SHC 189.9 201.0 223.2 242.2 203.2 232.0 254.3 276.5 214.8 230.9 255.3 285.5
TGC 258.5 263.1 265.4 270.1 260.8 267.8 272.2 276.9 276.9 281.5 288.3 295.8
125 67
SHC 146.4 187.8 230.9 254.4 168.4 199.9 246.9 262.1 178.3 210.2 258.3 286.4
TGC 295.2 299.7 304.3 306.6 304.3 308.9 311.1 313.4 311.1 313.4 315.7 318.0
73
SHC 92.4 136.1 179.4 221.6 95.0 143.9 187.4 230.9 100.6 148.5 196.5 244.6
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).

Heating capacity for 30Ton:


Net Capacities(kW)-12000 CFM
Outdoor Temp(°F) Peak Net Heating(kW) at Indicated Dry Bulb(°F) Peak Total Power (kW) at Indicated Dry Bulb(°F)
70% RH
59 68 75.2 80.6 59 68 75.2 80.8
5 59.4 55.8 54.6 53.8 27.6 30.4 32.2 34
10.4 64 61.2 60 59.4 28.2 31 32.4 34.6
15.8 67.8 66 65.4 65.4 28.6 31.2 32.8 35.2
21.2 71.2 69 68.4 67.6 28.8 31.6 33.4 35.8
26.6 75.4 74.2 73.6 72.4 29.2 31.8 34 36.4
32 81 79.8 78.6 77.8 29.4 32.4 34.6 36.6
37.4 93.4 92.4 91 89.8 30 33 35.2 37.2
44.6 107.4 105.0 104.8 104.2 31.2 34.8 36.4 38.4
48.2 122.2 120.6 119.4 118.2 32.4 36 38.2 40.6
53.6 129.6 134.2 133.6 132.4 33.6 37.6 39.6 42
59 139.8 137.8 136.8 135.4 34.6 38.4 40.6 43
64.4 148.2 145.6 144 142.8 35.4 39.4 41.8 43.8
69.8 159 155.8 153.6 151.6 36 40 42 44.2
75.2 168 163.6 160.8 159 37 40.6 43.6 45

Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.

56
R410a Tropical Rooftop Package Unit 50Hz

10. Electrical Data

10.1 Electrical Data


380-400V/3Ph/50Hz(Tolerance:342V-440V)

Model Power Supply Compressor Evaporator fan motor Condenser fan motor

MCA TOCA MFA STC RNC IPT Qty RNC IPT Qty RNC IPT Qty

※ MRBT-60CWN1-R 19.75 21.5 25 74 11.8 5.2 1 3.5 0.8 1 1.5 0.35 1

MRBT-062CWN1-R 23 29 38 98 14.3 7.185 1 3.7 1.5 1 1.7 0.6 1

MRCT-062EWN1-R 23 29 38 98 14.3 7.185 1 3.7 1.5 1 1.7 0.6 1

MRBT-062HWN1-R 23 29 38 98 14.3 7.185 1 3.7 1.5 1 1.7 0.6 1

MRBT-075CWN1-R 26 32 42 142 16.4 8.47 1 3.7 1.9 1 1.7 0.85 1

MRCT-075EWN1-R 26 32 42 142 16.4 8.47 1 3.7 1.9 1 1.7 0.85 1

MRBT-075HWN1-R 26 32 42 142 16.4 8.47 1 3.7 1.9 1 1.7 0.85 1

MRBT-085CWN1-R 32 39 53 142 20.7 9.5 1 3.4 1.66 1 3.5 1.02 1

MRCT-085EWN1-R 32 39 53 142 20.7 9.5 1 3.4 1.66 1 3.5 1.02 1

MRBT-085HWN1-R 32 39 53 142 20.7 9.5 1 3.4 1.66 1 3.5 1.02 1

MRBT-100CWN1-R 33 40 55 147 29.5 10.8 1 3.7 1.9 1 2.7 1.3 1

MRCT-100EWN1-R 33 40 55 147 29.5 10.8 1 3.7 1.9 1 2.7 1.3 1

MRBT-100HWN1-R 33 40 55 147 29.5 10.8 1 3.7 1.9 1 2.7 1.3 1

MRBT-150CWN1-R 56 67 89 110 32.8 16.8 2 9.2 4.65 1 1.7 0.85 2

MRCT-150EWN1-R 56 67 89 110 32.8 16.8 2 9.2 4.65 1 1.7 0.85 2

MRBT-150HWN1-R 56 67 89 110 32.8 16.8 2 9.2 4.65 1 1.7 0.85 2

MRBT-175CWN1-R 66 79 108 142 20.7 9.5 2 10.3 5.3 1 2.7 1.3 2

MRCT-175EWN1-R 66 79 108 142 20.7 9.5 2 10.3 5.3 1 2.7 1.3 2

MRBT-175HWN1-R 66 79 108 142 20.7 9.5 2 10.3 5.3 1 2.7 1.3 2

MRBT-200CWN1-R 72 85 115 140 42.8 21.6 2 11.8 5.5 1 3.3 1.7 2

MRCT-200EWN1-R 72 85 115 140 42.8 21.6 2 11.8 5.5 1 3.3 1.7 2

MRBT-200HWN1-R 72 85 115 140 42.8 21.6 2 11.8 5.5 1 3.3 1.7 2

MRCT-300HWN1-R 91 109 146 197 55.2 27.4 2 13 7.0 1 6.5 3.4 2

MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A) STC: Starting Current (A)
RNC: Running Current (A) IPT: Input (kW)
Note:
1. The item with ※ power supply: 380-415V/3Ph/50Hz(Tolerance:342V-440V);
2. The starting current is indicated for each compressor motor.
3. The maximum currents of the compressor can be estimated as follows.
One compressor unit Two compressor unit

Max. current RNC×Max. IPT×/IPT RNC×Max. IPT×/IPT

Max. instantaneous current STC STC+RNC×0.5×Max. IPT×/IPT

Max. IPT×: Compressor power input from the performance table at the expected maximum condition
STC, IPT, RNC: Compressor data from the above table
11. The data in the compressor motor column shall indicate the respective values of the refrigeration cycle.

Voltage imbalance between phases to be <2%.

57
R410a Tropical Rooftop Package Unit 50Hz

10.2 Motor protection class


Compressor Indoor fan motor Indoor coil Outdoor fan motor Outdoor coil
Model
Motor protection Insulation class Safe class Pressure Insulation class Safe class Pressure

MRBT-60CWN1-R IOP F IPX0 250psi B IPX4 450psi

MRBT-062CWN1-R IOP F IP54 250psi F IP54 450psi

MRCT-062EWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-062HWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-075CWN1-R IOP F IP54 250psi F IP54 450psi

MRCT-075EWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-075HWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-085CWN1-R IOP F IP54 250psi F IP54 450psi

MRCT-085EWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-085HWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-100CWN1-R IOP F IP54 250psi F IP54 450psi

MRCT-100EWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-100HWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-150CWN1-R IOP F IP54 250psi F IP54 450psi

MRCT-150EWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-150HWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-175CWN1-R IOP F IP54 250psi F IP54 450psi

MRCT-175EWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-175HWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-200CWN1-R IOP F IP54 250psi F IP54 450psi

MRCT-200EWN1-R IOP F IP54 250psi F IP54 450psi

MRBT-200HWN1-R IOP F IP54 250psi F IP54 450psi

MRCT-300HWN1-R IOP F IP54 250psi F IP44 450psi

IOP: Internal overload protector

58
R410a Tropical Rooftop Package Unit 50Hz

11. Parameter and Pressure Chart for Air Volume

11.1 Model:5ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 0 25 50 70 75 100 125 150 175 200

Air flow (CFM) 1920 1872 1831 1800 1795 1749 1701 1649 1598 1536

Brake power (kW) 0.7782 0.7634 0.752 0.742 0.7417 0.73 0.716 0.7015 0.687 0.67

Fan speed (rpm) 846 881 914 944 948 975 1006 1036 1067 1096

Parameter table for outdoor unit air volume:

Static pressure Air flow Brake power Fan speed


Model
(Pa) (CFM) (kW) (rpm)

5Ton 0 4114 0.345 1080

59
R410a Tropical Rooftop Package Unit 50Hz
11.2 Model:6.2ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 0 25 50 60 75 100 125 150 175

Air flow (CFM) 2853 2754 2632 2602 2522 2413 2310 2236 2108

Brake power (kW) 1.51 1.4 1.36 1.34 1.2 1.14 1.09 1.05 0.98

Fan speed (rpm) 1068 1072 1077 1077 1080 1082 1085 1089 1091

250
Static pressure(Pa)

225

200

175

150

125

100

75

50

25

0
2200 2300 2400 2500 2600 2700 2800 2900 3000 3100

Air volume(CFM)

Parameter table for outdoor unit air volume:


Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)

0 5880 0.78 900

6.2Ton 10 5647 0.79 889

20 5411 0.80 875

60
R410a Tropical Rooftop Package Unit 50Hz
11.3 Model: 7.5Ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 0 20 50 60 75 100 125 150 175

Air flow (CFM) 3240 3149 2996 2941 2886 2782 2664 2540 2411

Brake power (kW) 1.83 1.78 1.70 1.66 1.63 1.58 1.53 1.47 1.41

Fan speed (rpm) 1260 1265 1268 1271 1274 1277 1281 1285 1287

Curve diagram of static pressure, air flow volume:

250
Static pressure(Pa)

225

200

175

150

125

100

75

50

25

0
2500 2600 2700 2800 2900 3000 3100 3200 3300 3400

Air volume(CFM)

Parameter table for outdoor unit air volume:


Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)

0 5880 0.78 900

7.5Ton 10 5647 0.79 889

20 5411 0.80 875

61
R410a Tropical Rooftop Package Unit 50Hz

11.4 Model: 8.5Ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 0 25 50 75 100 125 150 175

Air flow (CFM) 3940 3785 3612 3451 3302 3130 2955 2759

Brake power (kW) 1.88 1.81 1.73 1.66 1.59 1.51 1.43 1.35

Fan speed (rpm) 933 937 939 944 946 949 952 953

Curve diagram of static pressure, air flow volume:

250
Static pressure(Pa)

225

200

175

150

125

100

75

50

25

0
2800 3000 3200 3400 3600 3800 4000 4200 4400 4600

Air volume(CFM)

Parameter table for outdoor unit air volume:


Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)

0 7060 0.78 935

8.5Ton 10 6765 0.79 926

20 6471 0.80 918

62
R410a Tropical Rooftop Package Unit 50Hz

11.5 Model: 10Ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 0 25 50 75 100 125 150 175

Air flow (CFM) 4298 4156 3929 3756 3579 3382 3218 3020

Brake power (kW) 2.18 2.1 2.02 1.96 1.86 1.79 1.71 1.62

Fan speed (rpm) 1000 1004 1006 1011 1014 1016 1020 1021

Curve diagram of static pressure, air flow volume:


250
Static pressure(Pa)

225

200

175

150

125

100

75

50

25

0
2800 3000 3200 3400 3600 3800 4000 4200 4400 4600

Air volume(CFM)
Fig.7-4
Parameter table for outdoor unit air volume:
Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)

0 7060 0.78 935

10Ton 10 6765 0.79 926

20 6471 0.80 918

63
R410a Tropical Rooftop Package Unit 50Hz

11.6 Model: 15Ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 0 50 75 90 125 150 200 250

Air flow (CFM) 7209 6675 6575 6400 6150 6044 5639 5227

Brake power (kW) 5.11 4.85 4.71 4.65 4.45 4.32 4.08 3.82

Fan speed (rpm) 1029 1029 1030 1031 1031 1032 1033 1034

Curve diagram of static pressure, air flow volume:


250
Static pressure(Pa)

225

200

175

150

125

100

75

50

25

0
5200 5450 5700 5950 6200 6450 6700 6950 7200 7450

Air volume(CFM)

Parameter table for outdoor unit air volume:


Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)

0 11000 0.78×2 935

15Ton 10 9800 0.79×2 926

20 9600 0.80×2 918

64
R410a Tropical Rooftop Package Unit 50Hz

11.7 Model: 17.5Ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 0 25 50 75 100 125 150 175 200 225 250 275 300

Air flow (CFM) 7858 7712 7546 7392 7271 7091 6977 6836 6680 6534 6354 6178 6020

Brake power (kW) 5.76 5.66 5.57 5.36 5.3 5.14 5.05 4.88 4.78 4.67 4.55 4.37 4.12

Fan speed (rpm) 1019 1020 1020 1021 1022 1022 1023 1024 1025 1025 1026 1027 1030

Curve diagram of static pressure, air flow volume:


300
Static pressure(Pa)

270

240

210

180

150

120

90

60

30

0
6200 6400 6600 6800 7000 7200 7400 7600 7800 8000

Air volume(CFM)

Parameter table for outdoor unit air volume:


Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)

0 11000 0.78×2 935

17.5Ton 10 9800 0.79×2 926

20 9600 0.80×2 918

65
R410a Tropical Rooftop Package Unit 50Hz

11.8 Model: 20Ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 25 50 75 100 125 150 200 250 300

Air flow (CFM) 9296 8782 8452 8289 8179 7826 7388 6955 6555

Brake power (kW) 5.86 5.73 5.59 5.44 5.50 5.27 4.98 4.66 4.32

Fan speed (rpm) 818 819 819 820 820 821 822 823 825

Curve diagram of static pressure, air flow volume:


300
Static pressure(Pa)

270

240

210

180

150

120

90

60

30

0
6800 7100 7400 7700 8000 8300 8600 8900 9200 9500

Air volume(CFM)

Parameter table for outdoor unit air volume:


Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)

0 14000 1.3×2 940

20Ton 10 13500 1.4×2 938

20 13100 1.5×2 930

66
R410a Tropical Rooftop Package Unit 50Hz

11.9 Model: 30Ton

Parameter table for indoor unit air volume:

Static pressure (Pa) 150 175 200 225 250 275 300 325 350

Air flow (CFM) 14664 14464 14119 13743 13230 12729 12365 11957 11489

Brake power (kW) 8.91 8.59 8.30 8.01 7.71 7.40 7.07 6.74 6.39

Fan speed (rpm) 775 775 776 777 778 779 780 782 782

Curve diagram of static pressure, air flow volume:


500
Static pressure(Pa)

460

420

380

340

300

260

220

180

140
9500 10000 10500 11000 11500 12000 12500 13000 13500 14000 14500

Air volume(CFM)

Parameter table for outdoor unit air volume:


Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)

0 14000 1.3×2 940

30Ton 10 13500 1.4×2 938

20 13100 1.5×2 930

67
R410a Tropical Rooftop Package Unit 50Hz

12. Refrigerant Cycle Diagram


12.1 5,6.2,7.5,8.5,10 ton:
Cooling,Cooling+EAH type

T3

Condenser

Capillary
High pressure
switch

TP Evaporator

Low pressure switch


Comp

T2

Cooling and Heating type:

T3

Condenser
High pressure Four way valve
Capillary

switch

TP Evaporator
Low pressure switch
Comp

T2

TP: Compressor discharge temperature sensor in system


T2: Indoor coil temperature sensor in system
T3: Outdoor coil temperature sensor in system

68
R410a Tropical Rooftop Package Unit 50Hz

12.2 15,17.5,20,30 ton:

Cooling, Cooling+EAH type

T3

High pressure
switch
T3
TP Condenser

Capillary

Capillary
High pressure
switch
Comp

Low pressure switch

TP T2

Low pressure switch


Comp

T2

Evaporator
Cooling and Heating type:

T3

Four way valve Four way T3


High pressure High pressure valve
switch switch Condenser
Capillary

Capillary

TP Evaporator
TP Low pressure T2
Low switch
Comp

pressure
switch
Comp

T2

TP: Compressor discharge temperature sensor in system A and B


T2: Indoor coil temperature sensor in system A and B
T3: Outdoor coil temperature sensor in system A and B

69
R410a Tropical Rooftop Package Unit 50Hz

13. Operation Limit

13.1 Cooling only and cooling with auxiliary heater


Cooling only and
cooling only with auxiliary heater
Outdoor temperature(℃ DB)

Standard
operation

Indoor temperature(℃ WB)

Temperature
Outdoor temperature Indoor temperature
Model
Cooling mode 18℃~52℃ 17℃~30℃
With auxiliary electric heater models -- 17℃~30℃

70
R410a Tropical Rooftop Package Unit 50Hz

13.2 Cooling and heating

55 Cooling mode
50

45
Outdoor temperature(℃ DB)

40
Standard
35 operation
30

25

20

15

10 17 30
Indoor temperature(℃ WB)

Temperature
Outdoor temperature Indoor temperature
Mode
Cooling mode 18℃~52℃ 17℃~30℃

Heating mode
25
Outdoor temperature(℃ DB)

20

15

10 Standard
operation
5

0
-5 10 17 30

-10
Indoor temperature(℃ WB)

Temperature
Outdoor temperature Indoor temperature
Mode

Heating mode -10℃~24℃ 17℃~30℃

71
R410a Tropical Rooftop Package Unit 50Hz

14. Installation

14.1 Lifting
Rigging cables should have adequate capability to resist 3 times weight of unit. Before lift, please check and
ensure that hooks are holding tightly to unit and lifting angles are no less than 60°.
Cloth material or hard-paper should be padded in the contact place between unit and rigging cable. Rigging
cable should be entwined a round at the hook for prevent danger by cable slip because of weight unbalance.
During lifting, anyone forbidden lingering under the lifting unit.

15.2 Service Space


1. The recommended clearances for single-unit installations are illustrated in following Fig.
These minimum requirements are not only an important consideration when determining unit placement, but
they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency. 2.
Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation or
the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be
reviewed with a local engineer.

For 6.2ton and above

72
R410a Tropical Rooftop Package Unit 50Hz

0.5m

1m
Overhead air
Overhead air 1m Clearance≥3m 1m
0.6mClearance≥1.55m 0.3m
0.8m

1m
For 5ton For 6.2ton and above

15.3 Rooftop -- units

For roof top applications using a field fabricated frame and ducts, according to the following procedure:
1) The frame must be located and secured by bolting or welding to the roof. Flashing is required.
2) The hole in the roof must be prepared in advance of installing the unit.
3) Secure the ducts to the roof.
4) Place the unit on the frame or roof curb.
5) Secure the unit to the frame or roof curb.
6) Insulate any ductwork outside of the structure with at least two (2) inches of insulation and then
weatherproof. There must be a weatherproof seal where the duct enters the structure.
7) Complete the installation according to the instructions.
Typical rooftop application with frame:

73
R410a Tropical Rooftop Package Unit 50Hz

Typical rooftop application with frame:

74
R410a Tropical Rooftop Package Unit 50Hz

14.4 Ground Level -- Horizontal Units


For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit
must be level on the pad. The pad must not come in contact with the structure. Be sure the outdoor portion of
the supply and return air ducts are as short as possible.
Installation according to the following procedure:
1) Place the unit on the pad.
2) Attach the supply and return air ducts to the unit.
3) Insulate any ductwork outside of the structure with at least 2 inches of insulation and weatherproof. There
must be a weatherproof seal where the duct enters the structure.
4) Complete the installation according to the instructions.

75
R410a Tropical Rooftop Package Unit 50Hz
Typical ground level application:

14.5 Installation of condensate drain piping


5ton:

Drain pan

A B
Drain commutator

Drain connector tube

Removable Condensate Drain Pan


And Removal Procedure

6.2&7.5&8.5&10&15&17.5&20ton:

Outer diameter:28 mm/1.1 inch

Inner diameter:21 mm/0.83 inch

76
R410a Tropical Rooftop Package Unit 50Hz

14.6 Ductwork

1. Attaching horizontal ductwork to unit


1) All conditioned air ductwork should be insulated to minimize heating and cooling duct losses. Use a
minimum of two (2) inches of insulation with a vapor barrier. The outside ductwork must be weatherproofed
between the unit and the building.
2) When attaching ductwork to a horizontal unit, provide a flexible watertight connection to prevent noise
transmission from the unit to the ducts. The flexible connection must be indoors and made out of heavy
canvas.
Note:
Do not draw the canvas taut between the solid ducts.

2. Attaching down flow ductwork to roof curb

Supply and return air flanges are provided on the roof curb for easy duct installation. All ductwork must be run
and attached to the curb before the unit is set into place.
Follow these guidelines for ductwork construction:
1) Connections to the unit should be made with three-inch canvas connectors to minimize noise and vibration
transmission.
2) Elbows with turning vanes or splitters are recommended to minimize air noise and resistance.
3) The first elbow in the ductwork leaving the unit should be no closer than two feet from the unit, to minimize
noise and resistance.

77
R410a Tropical Rooftop Package Unit 50Hz
14.7 Wiring provision

Field wiring

The units are internally wired at the factory according to generally accepted electrical technology.

Required field wiring

Main power wiring to the unit control wiring between the control center and the unit, and earth wiring are
required in the field.
5Ton 6.2&7.5&8.5&10Ton 15&17.5&20Ton

Required components

The following components are required: main power fuse, conduit coupling, and field supplied room
thermostat.

Wire and fuse size selection for main power source.

Wire and fuse size should be selected in accordance with national standard, taking the designed maximum
current shall be the total of the compressor maximum current, condenser fan motor current and evaporator
fan motor current (refer to “electrical data”).

Wire size between room thermostat and unit.

The wire size between the room thermostat and the unit should be determined according to the following
table, because the 24V power source is applied to the control circuit.

78
R410a Tropical Rooftop Package Unit 50Hz

15 Wired Controller

15.1 Standard wired controller: KJR-12B/DP (T)-E

KJR-12B/DP (T)-E
1. SAFETY PRECAUTIONS
The following contents are stated on the product and the operation manual, including usage, precautions
against personal harm and property loss, and the methods of using the product correctly and safely. After fully
understanding the following contents (identifiers and icons), read the text body and observe the following
rules.
Identifier description

79
R410a Tropical Rooftop Package Unit 50Hz
2. SUMMARIZE
Usage condition:
○1 . Power supply: 5V DC.

○2 . Operation temperature: -15℃-+43℃.

○3 . Operation humidity: 40%-90%, RH.

3. FUNCTION SUMMARY
Main function:
○1 . Connecting to indoor unit by A, B, C, D, E terminal;

○2 . Button setting action mode.

○3 . LCD display.

○4 . Timer for rest time.

4. NAME AND FUCTION OF INDICATORS ON THE CONTROLLER

① Operation mode indication:


When press " MODE " button, the following mode can be selected in circle. Auto→Cool →Dry→Heat→
Fan only→Auto. For cooling only model,heat mode is skipped.
② Timer :
When adjust setting on time or only on time is set, the "ON" is lighted.
When adjust setting off time or only off time is set, the "OFF" is lighted. If both „on‟ and „off‟ timer are set, both
the "ON" and "OFF" are lighted.
③ Follow me function:
There is a temperature sensor inside the wire controller, after setting temperature, it will compare the two
temperatures, and the space of wire controller will be
the same as setting temperature. It is available under cooling, heating, auto mode.
④ ON/OFF indication :
When it is on, the icon display, otherwise it is extinguished.
⑤ Fan speed indication :
There are four fan modes : low, middle, high, auto. For some models, no middle fan then the middle fan is
seen as high speed.
⑥ Lock:
When the " LOCK " button is pressed, the icon appear and other buttons is unable, press again, the icon
disappear.
⑦ Temperature display zone:
Generally it displays setting temperature, it can be adjusted by press temperature button ▲ and ▼. But in
fan mode, no display here.

80
R410a Tropical Rooftop Package Unit 50Hz
5. INSTALLATION METHOD

When a wired controller is needed, a small 5-way terminal should be added, fix an infrared emitter with
gumwater near the receiver on the switch board. Connect its anode and cathode to A and B, and +5V, GND,
RUN to C, D, E on the switch board.

6. NAME AND OPERATION OF THE BUTTON ON THE WIRE CONTROLLER

① Mode button:

When press this button, the operation mode change as the following sequence:

Remark: For the cooling only model, the heating mode is skipped.
② Timer on button :
Press this button, timer on function is active. Then every press, the time increase 0.5h, after 10h, 1h increase
after each press. If cancel this Function, just set it to "0.0".
③ Timer off button:
Press this button, timer off function is active. Then every press, the time increase 0.5h, after 10h, per 1h
increase after each press. If cancel this function, just set it to "0.0".
④ Follow me button:
When under cool, heat and auto mode, press this button, follow me function is active. Press again, this
function is ineffective.
⑤ Electrical heater button :
If press this button in heat mode, electrical heater function become ineffective.
81
R410a Tropical Rooftop Package Unit 50Hz
⑥ Reset button(hidden):
Use a 1mm stick to press in the little hole , then the current setting is canceled . The wired controller will enter
into original state.
⑦ON/OFF button:
When in off state, press this button, the indicator is on, the wire controller enter into on state, and send
setting information to in door PCB. When in on state, press this button, the indicator is off, and send
instruction. If timer on or timer off has been set, it cancel this setting then send instruction to stop the
machine.
⑧ Adjust button ▲:
Set indoor temperature up. If press and hold on, it will increase at 1 degree per 0.5 second.
⑨ Adjust button ▼ :
Set indoor temperature down. If press and hold on, it will decrease at 1degree per 0.5 second.
⑩ Swing button:
First pressing: start swing function; second pressing: stop swing. (Match to some model with swing function).


11 Economy operation button:

Press this button, the indoor unit operates in economy mode, press it again, exit this mode (it may be
ineffective for some models)


12 Fan speed button:

Press this button consecutively, the fan speed will circle as follow:


13 Lock button (hidden):

When you push the LOCK button, all current settings are locked in and the wire controller does not accept
any operation except that of the LOCK button. Use the lock mode when you want to prevent setting from
being changed accidentally or play fully. Push the LOCK button again when you want to cancel the LOCK
mode.

7. USING METHOD

AUTOMATIC OPERATION
Connect to power, indoor operation lamp flash.
○1 . Press "MODE" button, select " AUTO " ;

○2 . Press the button "▲" and "▼", set temperature you want, generally it is among 17℃~30℃;

○3 . Press " ON/OFF" button, operation lamp is on, the air-conditioner work in auto mode, indoor fan is auto,

and can not be changed. Auto is displayed on LCD. Press " ON/OFF" button again to stop.
○4 . Economy operation is valid in auto mode.

COOL/HEAT/FAN MODE OPERATION


○1 . Press "MODE" button, select "COOL", "HEAT" or "FAN ONLY" mode.

○2 . Press temperature adjust button to select setting temp..

○3 . Press "FAN SPEED" button to select high/mid/low/auto.

○4 . Press "ON/OFF" button, indoor unit operation lamp on, it works in selected mode. Press "ON/OFF" button

again, it stops to work.


Remark: When in fan mode, no temperature can be set.

DRY OPERATION

82
R410a Tropical Rooftop Package Unit 50Hz
○1 . Press " MODE " button, select " DRY " mode.

○2 . Press temperature adjust button to select setting temp.

○3 . Press " ON/OFF " button, indoor unit operation lamp on, it works in dry mode. Press ON/OFF button again,

it stops to work.
○4 . In dry mode, economy operation and fan speed are ineffective.

TIMER SETTING

Timer on only:
○1 . Press " TIME ON " button, it display "SET" on LCD, and display " H " and "ON" , it is waiting for timer on

setting.
○2 . Press " timer " on button repeatedly to adjust time setting.

○3 . If press this button and hold on, the time will increase at 0.5h, after 10h, it increases at 1h.

○4 . After setting 0.5 second, the wire controller send timer on information, it is finished.

Timer off only:


○1 . Press "TIME OFF " button, it display "SET" on LCD, and display " H " and ON, it is waiting for timer on

setting.
○2 . Press "TIME OFF" button repeatedly to adjust time setting.

○3 . If press this button and hold on, the time will increase at 0.5h, after 10h, it increases at 1h.

○4 . After setting 0.5 second, the wire controller send timer off information, it is finished.

TIMER ON AND TIMER OFF BOTH


1 . Set timer on time as the corresponding step1 and 2.


2 . Set timer off time as the corresponding step1 and 2.


3 . Timer off time must be longer than timer on time.


4 . 0.5 second after setting, the wire controller send information, the setting is finished.

CHANGE TIMER

If there is a timer of changing time to be need, press corresponding button to revise it. If cancel timer, change
time to 0.0.

NOTE: The timer time is relative time, that is delay after setting time ( i, e: setting time is 8:05 A,M). So when
timer is set, the standard time can not be adjusted.

8. TECHNICAL INDICATION AND REQUIREMENT

EMC and EMI comply with the CE certification requirements.

83
R410a Tropical Rooftop Package Unit 50Hz
15.2 Optional wired controller:

KJR-23B: For cooling only and cooling with auxiliary heater


KJR-25B: For Cooling and heating

KJR-23B KJR-25B

15.3 Field wiring

To connect wired controller


For Cooling Units F o r C o o l i n g + E A H UF
noi trs H e a t i n g & c o o l i n g U n i t s

R G Y (C ) R G Y W (C ) R G Y B ( C )

Dial code setting


The wired controller KJR-12B can be used when the SW3 is on “on”, if the SW3 is on „1”, the wired cotroller
KJR-23B or KJR-25B can be used. After setting, please shut off the power supply and then power on it again,
otherwise, the new settings function will be invalid.
For Cooling Units

5 -termi na l
KJR -1 2B Gro up ON
BROW N SW3
A 1 CN7
RED
B
YELLOW

WHITE

Y ELLOW MAINCONTROLBOARD
RED

C CN9
GREEN

BL ACK
D CN36
WH ITE
E
R G Y (C) XT2

TOTHEWIREDCONTROLLER

84
R410a Tropical Rooftop Package Unit 50Hz
For Cooling+EAH Units

5 -termi na l
KJR -1 2B Gro up ON
BROW N SW3
A 1 CN7
RED
B

YELLOW

WHITE
BLUE
CN9 MAINCONTROLBOARD

RED
Y ELLOW
C
BL ACK
D CN36 GREEN
WH ITE
E
R G Y W(C) XT2

TOTHEWIREDCONTROLLER

For Cooling+EAH Units

5 -termi na l
KJR -1 2B Gro up ON
BROW N SW3
A 1 CN7
RED
B
YELLOW

WHITE
BLUE
CN9 MAINCONTROLBOARD
RED
Y ELLOW
C
BL ACK
D CN36 GREEN
WH ITE
E
R G Y W(C) XT2

TOTHEWIREDCONTROLLER

Remark:
Two stage capacity output controlling is optional.

85
R410a Tropical Rooftop Package Unit 50Hz

16. Error Code

16.1 Error Code for 5ton


Type Content Code Remarks

Normal Standby --

Normal Constraint cooling On

Normal Run 10.

Error Compressor phase sequence error or phase default E0 Manual reset

Error Outdoor coil temp. sensor T3-1 default E1 Manual reset

Error Outdoor coil temp. sensor T3-2 default E2 Manual reset

Error Indoor coil temp. sensor T2-1 default E5 Manual reset

Error Indoor coil temp. sensor T2-2 default E6 Manual reset

Error Indoor temp. sensor T1 error E9 Manual reset

Error Outdoor ambient temp. sensor T4 error EA Manual reset

Error Wired controller output error Eb Manual reset

Protection Over current protection P0 Auto reset

Protection Comprehensive protection for outdoor fan P3 Auto reset

Protection Protection for Hi./Lo. Pressure or exhaust temp. (System 1) P4 Auto reset

Protection Protection for Hi./Lo. Pressure or exhaust temp. (System 1) P5 Auto reset

Protection Protection for High temperature of the outdoor condenser P8 Auto reset

Error code for 6.2ton and above


Type Content Code Remarks

Normal Standby --

Normal Constraint cool On

Normal Run 10.

Error Compressor phase sequence error or phase default E0 Manual reset

Error Outdoor coil temp. sensor in sys. A error E1 Manual reset

Error Outdoor coil temp. sensor in sys. B error E2 Manual reset

Error Indoor coil temp. sensor in sys. A error E5 Manual reset

Error Indoor coil temp. sensor in sys. B error E6 Manual reset

Error Indoor temp. sensor error E9 Manual reset

Error Outdoor ambient temp. sensor error EA Manual reset

Error Wire controller output error Eb Manual reset

Protection Overcurrent protection in sys. A P0 Auto reset

Protection Overcurrent protection in sys. B P1 Auto reset

Protection Overcurrent protection for indoor fan P2 Auto reset

Protection Comprehensive protection for outdoor fan P3 Auto reset

Protection Protection for Hi./Lo. Pressure or exhaust temp. in sys. A P4 Comprehensive protection in sys. A

Protection Protection for Hi./Lo. Pressure or exhaust temp. in sys. B P5 Comprehensive protection in sys. B

Protection T2 evaporator Hi-temperature protection stop outdoor unit fan P6 Auto reset

Protection T2 evaporator Hi- temperature protection then stop outdoor unit fan and compressor P7 Auto reset

Protection Protection for condenser Hi-temp. in sys. A P8 Auto reset

Protection Protection for condenser Hi-temp. in sys. B P9 Auto reset

Protection Anti-freezing protection for evaporator in sys. A Pc Auto reset

Protection Anti-freezing protection for evaporator in sys. B Pd Auto reset

Protection Defrosting dF Auto reset

86
R410a Tropical Rooftop Package Unit 50Hz
16.2 Troubleshooting

For 5ton

Item Content Error code


1 Compressor phase sequence error or phase default E0

2 Outdoor coil temp. sensor T3-1 default E1

3 Outdoor coil temp. sensor T3-2 default E2

4 Indoor coil temp. sensor T2-1 default E5

5 Indoor coil temp. sensor T2-2 default E6

6 Indoor temp. sensor T1 error E9

7 Outdoor ambient temp. sensor T4 error EA

8 Wired controller output error Eb

9 Over current protection P0

10 Comprehensive protection for outdoor fan P3

11 Protection for Hi./Lo. Pressure or exhaust temp. P4


1 E0:Compressor phase sequence error or phase default

Detect if the voltage of 5p wire joint


between A, B and C is normal.
No
Yes
Cut off power supply, replace the
power wire, inspect again.
Detect if the main board voltage
between A, B and C is normal.
No
Yes
Cut off power supply, exchange the
Cut off power supply, exchange wire from main power supply to main
freely two wires between A, B and board. Power on again, retesting.
C. Power on again, if the main
board display E0.
No
Yes
OK.

Replace the main board.


2 E1:Outdoor coil temp. sensor T3 default.

Detect if the temp. sensor is normal.

Yes No

Replace the temp. sensor, detect


Replace the main board.
it again.

87
R410a Tropical Rooftop Package Unit 50Hz


3 E9:Indoor coil temp. sensor T2 default.

(Indoor temp. and Pipe Temp. Sensor Resistance Value Table, see Appendix 2 )

Detect if the temp. sensor is normal.

No
Yes
Replace the temp. sensor,
Replace the main board.
detect it again.


4 When E2,E5,E6 or EA displays, please check the wired nameplate, if the terminals of T2_1、T2_2、

T3_2、T4 are connected as short circuit. If no, please connect all as short circuit, unless replace main
board.


5 Eb: Wired controller output error.(Only for KJR-23B or KJR-25B).

Avoid three conditions as following:


1) The wired controller output signal has Y, no G.
2) The wired controller output signal has W, no G.
3) The wired controller output signal has Y and W, no G.


6 P0:Compressor over current protection.(The over current protection value is 16A)

Detect B phase current, if the current


value is over the setting value.
No
Yes
Replace the main board.

The main board display P0, normal.


7 P3:Comprehensive protection for outdoor fan

Detect if the three-phase No The main board display P3,


protector display is normal. normal.

Yes

Detect by multimeter if
No Replace three-phase
three-phase protector COM
protector, detect it again.
and NO exist current circuit.

Yes

Replace the main board.

88
R410a Tropical Rooftop Package Unit 50Hz


8 P4:Protection for Hi./Lo. Pressure or exhaust temp. (High pressure protection value:4.4MPa, High

pressure protection value:0.14MPa;air discharge temp. protection value: 130℃ above)

When P4 display, detect Hi/Lo pressure testing


point by pressure gauge and discharge point temp. No The main board display P4 is
by thermometer. Conform if all testing values are
normal.
normal.

Yes

Replace high/low pressure switch


Detect by multimeter if the high/low pressure No and air discharge temp. switch,
switch two sides and air discharge switch two
detect them again.
sides exist current circuit.

Yes

Replace the main board.


9 Indoor fan motor don’t work.

Detect if there exist current from main No


Replace the main board.
board to indoor fan.

Yes

Replace indoor fan capacitor, detect it No


Replace the indoor fan.
again, conform if the indoor fan works.

Yes

Remove the problem


10 Outdoor fan motor don’t work.

Detect if there exist power supply from No Replace the main board.
main board to outdoor fan.

Yes

Replace the capacitor of outdoor fan, No


Replace outdoor fan.
detect it again, if the outdoor fan work.

Yes

Remove the problem

89
R410a Tropical Rooftop Package Unit 50Hz
For 6.2ton and above

Item Content Error code


1 Indoor fan motor didn‟t run. --
2 Compressor didn‟t run. --
3 T3 temp sensor error. EA
4 Check if the low pressure protection is normal. --
5 Outdoor fan motor didn‟t run. --
6 Four ways valve didn‟t work. --
7 Condenser high temp protection. P8,P9

1 Indoor fan motor don’t run.



The first check if the power supplier is normal, if all wire connection terminal is loose, if the wired controller set
and wire connection are correct, operating as flow process after confirm.

If the heating mode is in preventing cold


state for a long time (Cooling mode will not
be considered)

Yes
No

Detect if the voltage of the fan on PCB Replace T2 sensor or check if exist

which corresponds to the interface is 208 ~ leakage in pipeline.

230V AC between CN6 of INFAN and N.

No
Yes

If the indoor fan contactor is close. Detect if the fuse on PCB is burned off.

Yes No Yes No

Replace motor. Replace contactor. Replace fuse. Check if the secondary voltage
transformer is normal.

Yes No

Replace PCB. Replace


transformer.

90
R410a Tropical Rooftop Package Unit 50Hz


2 Compressor don’t run (All wires connection are correct and reliable, if power supplier is required

range. If compressor don’t run, you can analysis as flowing)

Detect if the voltage of compressor which


corresponds to the interface on PCB is 208 ~
230V AC between CN6 of COMP1, COMP2
and N.

Yes No

If indoor fan motor contactor is Detect if the fuse on PCB is burned

close. off.

Yes No Yes No

Replace Replace Replace fuse. Check if the secondary voltage


compressor. contactor. transformer is normal.

Yes No

Replace Replace
PCB. transformer.

3 T3 temp sensor error.

Is the electric resistance of T3 answer for


Appendix 1?

Yes No

Replace PCB. Replace the T3 sensor.


4 Check if the low pressure protection is normal.

Check if the low pressure protection is normal


(The normal resistance is 0Ω).

Yes No

Replace PCB. 1:Check if the refrigerant in system is less.


2:Detect if system have blocked
3:Check if the four-valve is broken.
4:Detect if low-pressure switching ontology is bad,
replace the low-voltage switch.

91
R410a Tropical Rooftop Package Unit 50Hz


5 Outdoor fan motor don’t run.

Detect if the voltage of compressor which


corresponds to the interface on PCB is 208 ~ 230V
AC between CN6 of OFAN1,OFAN2 and N.

Yes No

If the outdoor fan motor contactor is Detect if the fuse on PCB is burned off.
close.

Yes No Yes No

Replace outdoor Replace Replace Check if the secondary voltage


fan motor. contactor. fuse. transformer is normal.

Yes No

Replace PCB. Replace


transformer.


6 Four ways valve don’t work.

Detect if the voltage is 208 ~ 230V AC


between CN28, CN29 and C on PCB.

Yes No

Replace four way valve or coil. Detect if the fuse on PCB is burned off.

Yes No

Replace Check if the secondary voltage


fuse. transformer is normal.

Yes No

Replace Replace
PCB. transformer.

92
R410a Tropical Rooftop Package Unit 50Hz


7 Condenser high temperature protection

Is the electric resistance of condenser high temp


sensor answer for Appendix 1?
No
Yes Replace the sensor

Check: Heat dispersion function of outdoor heat exchanger is unqualified:


For example, the heat exchanger is dirty, air-outlet and air-back line is
short-circuited, outdoor fan stops running or air speed is over-low, inlet
Yes
and outlet air is blocked in heat exchanger, etc.
Remove the problem

No

Check: There is air or nitrogen in system (air comes from the incomplete
vacuum drying, and nitrogen is caused by directly pressurizing to ball
valve), symptom: Pressure value of high/low is high, discharge and suction Yes
temperature is high, current is large, there may be abnormal noise in
compressor, pressure gauge is jittering. Remove the problem

No

Check: System liquid side pipeline is blocked, for example, pipe is


squashed or body of valve is blocked, or stop valve has not been opened
(this situation often happens under high-pressure protection firstly).
Yes

Remove the problem


No

Replace the Outdoor PCB.

93
R410a Tropical Rooftop Package Unit 50Hz

17. Accessories

18. Maintenance and Upkeep

Regular maintenance and upkeep


Some regular maintenance and upkeep have been carry on by user, includes: change the one-time dust filter,
clean casing, wash condenser and replace a new belt, as well as do some test for the equipment.

Model A
6.2 Ton 328mm
7.5 Ton 328mm
8.5Ton 395mm
10 Ton 395mm
15 Ton 576mm
17.5 Ton 576mm
20 Ton 525mm
30Ton 925mm

Note:At least 1m flame resistant layer must be laid at the end of the air duct internal surface.
Regulating belt of rate of tension, inner fan Refer to the following Fig. fixed bolt of electric motor‟s supporting
slide was loosened, following electric motor was droved, belt of rate of tension will begin change.

Method of belt tensioning using belt tension indicator


Calculate the deflection in mm on a basis of 16mm per meter of center distance
Center distance (m) ×16=deflection (mm).

94
R410a Tropical Rooftop Package Unit 50Hz

For required to deflection belt 16 mm per meter of span


Belt section Small pulley diameter Newton Kilogram-force
(mm) (N) (kgf)
SPA 80 to132 25 to 35 2.5 to 3.6
SPB 140 to 224 45 to 65 4.6 to 6.6

NOTE:The belt which is too tight or too loose may generate noise and be harmful to the unit.
Dismantle the air filter.
Twist of screws and up the plate that is gets out.
Upon loose the filter-baffle-plate, the filter could be pulled out along the supporting slot.
5ton

7.5&10&15&20ton

Screw

Filter

Return I lateral plate assemblies


Extraction board of filter

Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust
accumulation is too heavy, please use soft brush and mild detergent to clean it and dry out in cool
place).

95
R410a Tropical Rooftop Package Unit 50Hz

The air-in side should face up when using vacuum cleaner.


The air-in side should face down when using water.
CAUTION: Do not dry out the air filter under direct sunshine or with fire.

Re-install the air filter


Condenser coil
Unfiltered air circulates through the unit's condenser coil and can cause the coil's surface to
become clogged with dust, dirt, etc. To clean the coil, vertically (i.e., with the fins) stroke the coil
surface with a soft-bristled brush. Be sure to keep all vegetation away from the condenser coil area.

Maintenance performed by serviceman.


To keep your unit operating safely and efficiently, the manufacturer recommends that a qualified
serviceman check the entire system at least once each year and any other time that you feel one is
needed. Your serviceman should examine these areas of your unit:
Filters
Motors and drive system components
Economizer gaskets (for possible replacement)
Safety controls (for mechanical cleaning)
Electrical components and wiring (for possible replacement and connection tightness)
Condensate drain (for cleaning)
Unit duct connections (to see that they are physically sound and sealed to the unit casing)
Unit mounting support (for structural integrity)
The unit (for obvious unit deterioration)

CAUTION:
Do not operate the unit without the evaporator fan access panel in place. Reinstall the access panel
after performing any maintenance. Operating the unit without the access panel may result in severe
personal injury or death.

96
R410a Tropical Rooftop Package Unit 50Hz

Appendix :

1. Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (6.2ton and above)

℃ K Ohm ℃ K Ohm ℃ K Ohm ℃ K Ohm


-20 115.266 20 12.6431 60 2.35774 100 0.62973
-19 108.146 21 12.0561 61 2.27249 101 0.61148
-18 101.517 22 11.5000 62 2.19073 102 0.59386
-17 96.3423 23 10.9731 63 2.11241 103 0.57683
-16 89.5865 24 10.4736 64 2.03732 104 0.56038
-15 84.2190 25 10.000 65 1.96532 105 0.54448
-14 79.3110 26 9.55074 66 1.89627 106 0.52912
-13 74.5360 27 9.12445 67 1.83003 107 0.51426
-12 70.1698 28 8.71983 68 1.76647 108 0.49989
-11 66.0898 29 8.33566 69 1.70547 109 0.48600
-10 62.2756 30 7.97078 70 1.64691 110 0.47256
-9 58.7079 31 7.62411 71 1.59068 111 0.45957
-8 56.3694 32 7.29464 72 1.53668 112 0.44699
-7 52.2438 33 6.98142 73 1.48481 113 0.43482
-6 49.3161 34 6.68355 74 1.43498 114 0.42304
-5 46.5725 35 6.40021 75 1.38703 115 0.41164
-4 44.0000 36 6.13059 76 1.34105 116 0.40060
-3 41.5878 37 5.87359 77 1.29078 117 0.38991
-2 39.8239 38 5.62961 78 1.25423 118 0.37956
-1 37.1988 39 5.39689 79 1.21330 119 0.36954
0 35.2024 40 5.17519 80 1.17393 120 0.35982
1 33.3269 41 4.96392 81 1.13604 121 0.35042
2 31.5635 42 4.76253 82 1.09958 122 0.3413
3 29.9058 43 4.57050 83 1.06448 123 0.33246
4 28.3459 44 4.38736 84 1.03069 124 0.32390
5 26.8778 45 4.21263 85 0.99815 125 0.31559
6 25.4954 46 4.04589 86 0.96681 126 0.30754
7 24.1932 47 3.88673 87 0.93662 127 0.29974
8 22.5662 48 3.73476 88 0.90753 128 0.29216
9 21.8094 49 3.58962 89 0.87950 129 0.28482
10 20.7184 50 3.45097 90 0.85248 130 0.27770
11 19.6891 51 3.31847 91 0.82643 131 0.27078
12 18.7177 52 3.19183 92 0.80132 132 0.26408
13 17.8005 53 3.07075 93 0.77709 133 0.25757
14 16.9341 54 2.95896 94 0.75373 134 0.25125
15 16.1156 55 2.84421 95 0.73119 135 0.24512
16 15.3418 56 2.73823 96 0.70944 136 0.23916
17 14.6181 57 2.63682 97 0.68844 137 0.23338
18 13.9180 58 2.53973 98 0.66818 138 0.22776
19 13.2631 59 2.44677 99 0.64862 139 0.22231

97
R410a Tropical Rooftop Package Unit 50Hz
2. Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (5ton)
Temp Resistance(KΩ) Resist.tol (%) Temp.tol(℃)

(℃) Rmax R(t)Normal Rmin MAX(+) MIN(-) MAX(+) MIN(-)

-20 116.539 106.732 96.920 9.19 9.19 1.59 1.59


-19 110.231 100.552 91.451 9.63 9.05 1.57 1.57
-18 103.743 94.769 86.328 9.47 8.91 1.56 1.55
-17 97.673 89.353 81.525 9.31 8.76 1.54 1.54
-16 91.990 84.278 77.017 9.15 8.62 1.53 1.52
-15 86.669 79.521 72.788 8.99 8.47 1.51 1.50
-14 81.684 75.059 68.815 8.83 8.32 1.49 1.48
-13 77.013 70.873 65.083 8.66 8.17 1.47 1.47
-12 72.632 66.943 61.574 8.50 8.02 1.45 1.45
-11 68.523 63.252 58.274 8.33 7.87 1.44 1.43
-10 64.668 59.784 55.169 8.17 7.72 1.42 1.41
-9 61.048 56.524 52.246 8.00 7.57 1.40 1.39
-8 57.649 53.458 49.492 7.84 7.42 1.38 1.37
-7 54.456 50.575 46.899 7.67 7.27 1.35 1.35
-6 51.456 47.862 44.455 7.51 7.12 1.33 1.32
-5 48.636 45.308 42.150 7.35 6.97 1.31 1.30
-4 45.984 42.903 39.977 7.18 6.82 1.29 1.28
-3 43.490 40.638 37.927 7.02 6.67 1.27 1.26
-2 41.144 38.504 35.992 6.86 6.52 1.25 1.24
-1 38.935 36.492 34.165 6.70 6.38 1.23 1.21
0 36.857 34.596 32.440 6.53 6.23 1.21 1.19
1 34.898 32.807 30.810 6.38 6.09 1.18 1.17
2 33.055 31.120 29.271 6.22 5.94 1.16 1.15
3 31.317 29.528 27.815 6.06 5.80 1.14 1.12
4 29.681 28.026 26.440 5.90 5.66 1.12 1.10
5 28.138 26.608 25.140 5.75 5.52 1.10 1.08
6 26.682 25.268 23.909 5.60 5.38 1.07 1.06
7 25.310 24.003 22.745 5.45 5.24 1.05 1.03
8 24.016 22.808 21.644 5.30 5.10 1.03 1.01
9 22.794 21.678 20.601 5.15 4.97 1.01 0.99
10 21.641 20.610 19.614 5.00 4.83 0.99 0.97
11 20.553 19.601 18.680 4.86 4.70 0.96 0.94
12 19.525 18.646 17.794 4.71 4.57 0.94 0.92
13 18.554 17.743 16.955 4.57 4.44 0.92 0.90
14 17.636 16.888 16.160 4.43 4.31 0.90 0.88
15 16.769 16.079 15.406 4.29 4.19 0.88 0.85
16 15.949 15.313 14.691 4.15 4.06 0.86 0.83
17 15.174 14.588 14.014 4.02 3.94 0.84 0.81
18 14.442 13.902 13.372 3.89 3.81 0.81 0.79
19 13.748 13.251 12.762 3.75 3.69 0.79 0.76
20 13.093 12.635 12.183 3.62 3.57 0.77 0.74
21 12.471 12.050 11.634 3.50 3.46 0.75 0.72
22 11.883 11.496 11.112 3.37 3.34 0.73 0.70
23 11.327 10.971 10.617 3.25 3.23 0.71 0.68
24 10.800 10.473 10.147 3.12 3.11 0.69 0.66
25 10.300 10.000 9.700 3.00 3.00 0.67 0.63
26 9.848 9.551 9.255 3.11 3.10 0.69 0.66
27 9.418 9.125 8.834 3.21 3.19 0.72 0.69
28 9.010 8.721 8.434 3.31 3.29 0.75 0.71

98
R410a Tropical Rooftop Package Unit 50Hz
29 8.621 8.337 8.055 3.41 3.38 0.77 0.74
30 8.252 7.972 7.695 3.51 3.47 0.80 0.77
31 7.900 7.625 7.353 3.61 3.57 0.83 0.79
32 7.566 7.296 7.029 3.70 3.66 0.85 0.82
33 7.247 6.982 6.721 3.80 3.74 0.88 0.84
34 6.944 6.684 6.428 3.89 3.83 0.91 0.87
35 6.656 6.401 6.150 3.98 3.92 0.93 0.90
36 6.381 6.131 5.886 4.08 4.00 0.96 0.93
37 6.119 5.874 5.634 4.17 4.09 0.98 0.95
38 5.870 5.630 5.395 4.26 4.17 1.01 0.98
39 5.631 5.397 5.167 4.34 4.26 1.03 1.01
40 5.404 5.175 4.951 4.43 4.34 1.06 1.03
41 5.188 4.964 4.745 4.52 4.42 1.09 1.06
42 4.982 4.763 4.549 4.60 4.50 1.12 1.09
43 4.785 4.571 4.362 4.69 4.58 1.14 1.12
44 4.596 4.387 4.183 4.77 4.66 1.17 1.14
45 4.417 4.213 4.014 4.85 4.74 1.19 1.17
46 4.246 4.046 3.851 4.93 4.81 1.22 1.20
47 4.082 3.887 3.697 5.02 4.89 1.25 1.23
48 3.925 3.735 3.550 5.10 4.97 1.28 1.25
49 3.776 3.590 3.409 5.18 5.04 1.30 1.28
50 3.632 3.451 3.274 5.25 5.12 1.33 1.30
51 3.495 3.318 3.146 5.33 5.19 1.35 1.33
52 3.363 3.191 3.023 5.41 5.26 1.41 1.36
53 3.237 3.069 2.905 5.49 5.34 1.43 1.38
54 3.116 2.952 2.793 5.56 5.41 1.46 1.41
55 3.001 2.841 2.685 5.64 5.48 1.48 1.44
56 2.890 2.734 2.582 5.71 5.55 1.51 1.46
57 2.784 2.632 2.484 5.79 5.62 1.54 1.49
58 2.682 2.534 2.390 5.86 5.69 1.56 1.52
59 2.585 2.440 2.299 5.93 5.76 1.59 1.54
60 2.491 2.350 2.213 6.01 5.83 1.62 1.57
61 2.401 2.264 2.130 6.08 5.90 1.64 1.60
62 2.315 2.181 2.051 6.15 5.96 1.67 1.62
63 2.233 2.102 1.975 6.22 6.03 1.70 1.65
64 2.154 2.026 1.903 6.29 6.10 1.72 1.68
65 2.077 1.953 1.833 6.36 6.16 1.75 1.70
66 2.004 1.883 1.766 6.42 6.23 1.77 1.73
67 1.934 1.816 1.702 6.49 6.29 1.80 1.76
68 1.867 1.752 1.641 6.56 6.35 1.83 1.78
69 1.802 1.690 1.582 6.62 6.41 1.85 1.81
70 1.740 1.631 1.525 6.69 6.48 1.88 1.84
71 1.680 1.574 1.471 6.75 6.54 1.91 1.86
72 1.622 1.519 1.419 6.82 6.60 1.93 1.89
73 1.567 1.466 1.369 6.88 6.66 1.96 1.92
74 1.514 1.416 1.321 6.94 6.71 1.98 1.94
75 1.463 1.367 1.275 7.00 6.77 2.01 1.97