Technical Service Manual: Rooftop Package
Technical Service Manual: Rooftop Package
Technical Service Manual: Rooftop Package
DM13-01.01.15en
Rooftop package
Models:
MRBT-062C(H/E)WN1-R
MRBT-075C(H/E)WN1-R
MRBT-085C(H/E)WN1-R
MRBT-100C(H/E)WN1-R
MRBT-150C(H/E)WN1-R
MRBT-175C(H/E)WN1-R
MRBT-200C(H/E)WN1-R
MRBT-300C(H/E)WN1-R
R410a Tropical Rooftop Package Unit 50Hz
Contents
1. Product List ........................................................................................................................ 2
2. External Appearance .......................................................................................................... 2
3. Nomenclature ..................................................................................................................... 3
4. Features .............................................................................................................................. 4
5. List of Functions................................................................................................................. 7
6. Specifications ..................................................................................................................... 9
7. Dimensional Drawings ..................................................................................................... 19
8. Wiring Diagrams ............................................................................................................... 25
9. Performance Data ............................................................................................................. 48
10. Electrical Data ............................................................................................................... 57
11. Parameter and Pressure Chart for Air Volume .......................................................... 59
12. Refrigerant Cycle Diagram .......................................................................................... 68
13. Operation Limit ............................................................................................................. 70
14. Installation..................................................................................................................... 72
15 Wired Controller ............................................................................................................ 79
16. Error Code ..................................................................................................................... 86
17. Accessories .................................................................................................................. 94
18. Maintenance and Upkeep ............................................................................................ 94
Appendix : ........................................................................................................................... 97
※ Manufacture reserves the right to discontinue, or change at any time, specifications or designs without
notices and without incurring obligations.
1
R410a Tropical Rooftop Package Unit 50Hz
1. Product List
2. External Appearance
6.2&7.5Ton
5 Ton
2
R410a Tropical Rooftop Package Unit 50Hz
30 Ton
3. Nomenclature
M R C T – 062 C W N1 - R
Power supply
D: 220v, 60Hz, 3Ph
R: 380~400v, 50Hz, 3Ph
Refrigerate type
N1: R410A
Wired controller
Function mode
C: Cooling only
E: Electric heater and Cooling
H: Cooling and heating
Cooling capacity (6.2ton)
XX: MBtu/h
XXX: ton
Working condition
Omit for T1 condition
T: T3 condition
Air outlet way
B: optional two air outlet ways: side and bottom
C: one air outlet way: side
D: one air outlet way: bottom
Rooftop package
Midea
3
R410a Tropical Rooftop Package Unit 50Hz
4. Features
The reinforced anticorrosion by using galvanization armor plate and coated with man-composed paint.
The appearance is stylish and be easy for maintenance.
(Has been passed 1000 hours salt spray test)
3.2 Condenser
By using high-efficient thin wing, the condenser has high-efficient heat exchanger, the energy waste
decreases greatly.
3.3 Evaporator
By using the high-efficient, super thin wing and inner grooved copper pipe, the evaporators get the
higher capacity and the lower noise level.
3.4 The heat insulation of indoor unit
The heat insulation of indoor unit can availably decrease heat loss.
3.5 The control and refrigerant cycle system
There are two independent refrigerant cycle systems, the capacity output is adjusted automatically by
4
R410a Tropical Rooftop Package Unit 50Hz
different demand, save energy when one control system is in running according to low capacity output.
4. Optional collocation
The air-conditioner designed for high temperature can run, despite the ambient temperature reaches up
to 52℃(125℉).
Large air volume from the air inlet is forced ventilating by the condenser fan.
The installation is fast and low cost with the easy installation and ready operation.
Flanges are prepared at the supply and return duct connections so that they can reduce duct connection
work at site.
Flange
Noise and vibration have been effectively reduced by adopting new style hermetic compressor. The
centrifugal fan and fan casing are optimum shaped for efficient and low noise operation.
5. Cabinet
5.1 Sloped drain pan and drain pipe.
5.2 Cabinets have forklift and lifting holes for easy transportation.
5.3 Cabinets have fresh air function, and the filter can be washable.
5
R410a Tropical Rooftop Package Unit 50Hz
Decorative
protective coil
guard
Compressor
contactor
Low voltage
terminal block
6. Optional supply/return airflow design, from side or bottom, It could be flexibly applied to
multi-position. The rooftop and ground installation are optional.
7. Certificate of compressor
6
R410a Tropical Rooftop Package Unit 50Hz
5. List of Functions
A. General
Packaged cooling or combination heating and cooling units suitable for mounting on the roof or ground.
The packaged unit consists of scroll compressors, evaporator coil, condenser coil, control wiring and
interconnecting piping- all factory assembled and mounted on heavy gauge G-90 galvanized steel sheet
press formed base, ready for field connection to utilities and ducts. The packaged unit is of rigid
construction with holes provided in the base rails for overhead rigging. The unit is provided with an integral
weather resistant control panel.
B. Unit enclosure
Panels are of heavy gauge, G-90 galvanized steel sheet with removable access panels, completely
weatherized for outdoor installation and properly reinforced and brazed. Panels and access door are
provided for inspection and access for all internal parts. Enclosures are provided with adequately
reinforced points of support for setting in the unit. Steel sheet panels are zinc-coated and galvanized by the
hot dip process of lock forming quality conforming to ASTM A 653 commercial weight G-90, followed by
baked on electrostatic polyester dry powder coat paint, on all external panel.
C. Compressor
Compressors are scroll for all the models. They are provided with all the standard controls and accessories
necessary for safe operation. These are equipped with internal motor protector; factory installed crank case
heater and rubber vibration isolator for quiet and efficient operation.
F. Evaporator fan
Evaporator fan is of centrifugal forward-curved blade design capable of handling total required CFM and
static pressure in the low and the medium ranges. Casings are made of galvanized steel. Blower motors
are of open drip proof type (totally enclosed types are optional) and conform to NEMA MG-1 and MG-2.
7
R410a Tropical Rooftop Package Unit 50Hz
Blower motor is mounted on adjustable base and secured by locking device. Pillow block bearing are
selected for at 200,000 hours average life at design operating conditions. Shaft is turned, ground and
polished from solid steel. Fans and pulleys are keyed to shaft and designed for continuous operation at
maximum motor horse power and fan speed. All rotating components and assemblies are statically and
dynamically balanced and every unit is vibration tested before shipment from the factory.
G. Electronic thermostats
General information: A dedicated electronic thermostat is supplied with unit controls as standard. This
thermostat controls one or two stage heating and cooling applications. The thermostat normally displays
room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also
allows you to select continuous fan operation, or have the fan on intermittent operation with the equipment.
It also displays the status of unit, thus providing maximum information for the end user.
8
R410a Tropical Rooftop Package Unit 50Hz
6. Specifications
Nominal ton (Ton) 5 6.2 6.2 6.2
ESP Pa 70 60 60 60
Performance
EER 1 Btu/h/W 10.4 9.7 9.7 9.7
Number of rows 4 2 2 2
Number of circuits 12 10 10 10
Quantity 1 1 1 1
Motors quantity 1 1 1 1
Quantity 1 1 1 1
Compressor
Model ZP67KCE-TFD-522 SH090A4ALC SH090A4ALC SH090A4ALC
9
R410a Tropical Rooftop Package Unit 50Hz
Capacity Btu/h 55000 76090 76090 76090
Number of rows 3 3 3 3
Quantity 1 1 1 1
Motors quantity 1 1 1 1
Outdoor sound level(sound pressure level ) dB(A) 62.9 70.3 70.3 70.3
Controller Wired controller type Wired controller Wired controller Wired controller Wired controller
Quantity Pieces 1 2 2 2
Filter
mm 410 X 495 X 25 447 X 885 X 10 447 X 885 X 10 447 X 885 X 10
Size (W×H×D)
inch 16.1X19.5X1 17.6 X34.8 X0.4 17.6 X34.8 X0.4 17.6 X34.8 X0.4
10
R410a Tropical Rooftop Package Unit 50Hz
Nominal
(Ton) 7.5 7.5 7.5 8.5 8.5
ton
Model MRBT-075CWN1-R MRCT-075EWN1-R MRBT-075HWN1-R MRBT-085CWN1-R MRCT-085EWN1-R
1 KW 26 26 26 30 30
flow
ESP (High Pa 60 60 60 75 75
Performance speed)
EER 1 Btu/h/W 9.7 9.7 9.7 9.8 9.8
Number of rows 2 2 2 3 3
Number of circuits 10 10 10 18 18
Quantity 1 1 1 1 1
Motors quantity 1 1 1 1 1
Quantity 1 1 1 1 1
11
R410a Tropical Rooftop Package Unit 50Hz
Input KW 8.472 8.472 8.472 9.462 9.462
Rated load Amps
A 16.7 16.7 16.7 20.7 20.7
(RLA)
Locked rotor
A 142 142 142 142 142
Amps(LRA)
Refrigerant oil ml 3000 3000 3000 3300 3300
charge
Number of rows 3 3 3 3 3
height inch 55.3 X38.1 55.3 X38.1 55.3 X38.1 68.8X34.6 68.8X34.6
Number of circuits 21 21 21 20 20
Quantity 1 1 1 1 1
Motors quantity 1 1 1 1 1
volume
Refrigerant Control Capillary Capillary Capillary Capillary Capillary
Controller Wired controller Wired controller Wired controller Wired controller Wired controller
mm 1630X1065X1068 2165X1021X1335
Net(W×H×D)
inch 64.2 X 41.9 X 42 85.2 X 40.2 X 52.6
Dimensions
mm 1700X1110X1160 2220X1140X1415
Packing(W×H×D)
inch 66.9 X 43.7 X 45.7 87.4 X 44.9 X 55.7
Quantity Pieces 2 2 2 2 2
Filter
mm 447 X 885 X 10 447 X 885 X 10 447 X 885 X 10 566 X 814 X 10 566 X 814 X 10
Size (W×H×D)
inch 17.6 X34.8 X0.4 17.6 X34.8 X0.4 17.6 X34.8 22.3 X 32X0.4 22.3 X 32X0.4
12
R410a Tropical Rooftop Package Unit 50Hz
Indoor fan air flow (High CFM 3600 4030 4030 4030 6150
speed)
ESP Pa 75 75 75 75 90
Performance
EER 1 Btu/h/W 9.8 10.2 10.2 10.2 9.7
Number of rows 3 3 3 3 3
Quantity Pieces 1 1 1 1 1
Quantity Pieces 1 1 1 1 2
13
R410a Tropical Rooftop Package Unit 50Hz
Input KW 9.462 10.862 10.862 10.862 8.472
Number of rows 3 3 3 3 3
Quantity Pieces 1 1 1 1 2
Controller Wired controller Wired controller Wired controller Wired controller Wired controller
Quantity Pieces 2 2 2 2 2
Filter
mm 566 X 814 X 10 566 X 814 X 10 566 X 814 X 10 566 X 814 X 10 900 X 815 X 12.5
Size (W×H×D)
inch 22.3 X 32X0.4 22.3 X 32X0.4 22.3 X 32X0.4 22.3 X 32X0.4 35.4 X32 X 0.5
Note:
The data are based on the following conditions:
Cooling: (1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46°C(114°F) DB.
Heating and Power input: Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB; - Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) DB
Electrical data: Indoor Temperature 32°C(90°F) DB / 24°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB
14
R410a Tropical Rooftop Package Unit 50Hz
Max. current A 53 45 65 65
ESP Pa 90 90 90 90
Performance
EER 1 Btu/h/W 9.7 9.7 10.2 10.2
COP Btu/h/W / 11 / /
Number of rows 3 3 3 3
Quantity Pieces 1 1 1 1
Motors quantity 1 1 1 1
Quantity Pieces 2 2 2 2
15
R410a Tropical Rooftop Package Unit 50Hz
Rated load Amps (RLA) A 16.7 16.7 20.7 20.7
Number of rows 3 3 3 3
Quantity Pieces 2 2 2 2
Outdoor sound level(sound pressure level ) dB(A) 72.4 72.4 72.4 72.4
Net weight kg(Ibs) 720/ (1609.3) 730/ (1609.3) 710/ (1565.3) 720/ (1609.3)
Weight
Gross weight kg(Ibs) 740(1653.4) 750(1653.4) 730(1609.3) 740(1653.4)
Quantity Pieces 2 2 2 2
Filter
mm 900 X 815 X 12.5 900 X 815 X 12.5 900 X 815 X 12.5 900 X 815 X 12.5
Size (W×H×D)
inch 35.4 X32 X 0.5 35.4 X32 X 0.5 35.4 X32 X 0.5 35.4 X32 X 0.5
Note:
The data are based on the following conditions:
Cooling: (1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46°C(114°F) DB.
Heating and Power input: Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB; - Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) DB
Electrical data: Indoor Temperature 32°C(90°F) DB / 24°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB
16
R410a Tropical Rooftop Package Unit 50Hz
Number of rows 3 3 3 3 3
circuitsrcuits
Type FC centrifugal FC centrifugal FC centrifugal FC centrifugal FC centrifugal
Quantity Pieces 1 1 1 1 1
Quantity Pieces 2 2 2 2 2
17
R410a Tropical Rooftop Package Unit 50Hz
Input KW 9.462 10.862 10.862 10.862 13.732
Rated load Amps A 20.7 21.4 21.4 21.4 27.6
(RLA)
Locked rotor A 142 147 147 147 197
Amps(LRA)
Refrigerant oil ml 3300 3300 3300 3300 3600
charge
Number of rows 3 4 4 4 4
circuitsrcuits
Type Propeller Propeller Propeller Propeller Propeller
Quantity Pieces 2 2 2 2 2
Controller Wired controller Wired controller Wired controller Wired controller Wired controller
Quantity Pieces 2 3 3 3 3
Filter
mm 900 X 815 X 12.5 640 X 1008 X 640 X 1008 X 640 X 1008 X 12.5 1492 X 640 X 12.5
Size (W×H×D) 12.5 12.5
inch 35.4 X32 X 0.5 25.2 X39.7 X 25.2 X39.7 X 0.5 25.2 X39.7 X 0.5 59 X26 X 0.5
0.5
Shipping Qty'Per Pieces 3/6/12 2/4/8 2/4/8 2/4/8 2/4/4
20'/40'/40'HQ
Note:
The data are based on the following conditions:
Cooling: (1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46°C(114°F) DB.
Heating and Power input: Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB; - Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) DB
Electrical data: Indoor Temperature 32°C(90°F) DB / 24°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB
18
R410a Tropical Rooftop Package Unit 50Hz
7. Dimensional Drawings
7.1 5ton
19
R410a Tropical Rooftop Package Unit 50Hz
7.2 6.2&7.5ton
20
R410a Tropical Rooftop Package Unit 50Hz
7.3 8.5&10ton
21
R410a Tropical Rooftop Package Unit 50Hz
7.4 15&17.5ton
22
R410a Tropical Rooftop Package Unit 50Hz
7.5 20ton
23
R410a Tropical Rooftop Package Unit 50Hz
7.6 30ton
294
120
888
Control electric heater box access panel 120
870
18
1656
14
2
Drain connection hole
83
9
Maintain orifice for air supply motor 142
27 9
53 17
Control and comperssor access panel 870
2157
Hole for control wires 99
7 13
5 142 820
Hole for power wires
Hole for other purpose
Hole for bottom installation 16-15×20
142
324
870
2157
678
8. Wiring Diagrams
8.1 5ton
MRBT-60CWN1-R
25
R410a Tropical Rooftop Package Unit 50Hz
8.2 6.2ton
MRBT-062CWN1-R
26
R410a Tropical Rooftop Package Unit 50Hz
MRCT-062EWN1-R
27
R410a Tropical Rooftop Package Unit 50Hz
MRBT-062HWN1-R
28
R410a Tropical Rooftop Package Unit 50Hz
8.3 7.5ton
MRBT-075CWN1-R
29
R410a Tropical Rooftop Package Unit 50Hz
MRCT-075EWN1-R
30
R410a Tropical Rooftop Package Unit 50Hz
MRBT-075HWN1-R
31
R410a Tropical Rooftop Package Unit 50Hz
8.4 8.5ton
MRBT-085CWN1-R
32
R410a Tropical Rooftop Package Unit 50Hz
MRCT-085EWN1-R
33
R410a Tropical Rooftop Package Unit 50Hz
MRBT-085HWN1-R
34
R410a Tropical Rooftop Package Unit 50Hz
8.5 10ton
MRBT-100CWN1-R
35
R410a Tropical Rooftop Package Unit 50Hz
MRCT-100EWN1-R
36
R410a Tropical Rooftop Package Unit 50Hz
MRBT-100HWN1-R
37
R410a Tropical Rooftop Package Unit 50Hz
8.6 15ton
MRCT-150CWN1-R
38
R410a Tropical Rooftop Package Unit 50Hz
MRCT-150EWN1-R
39
R410a Tropical Rooftop Package Unit 50Hz
MRBT-150HWN1-R
40
R410a Tropical Rooftop Package Unit 50Hz
8.7 17.5ton
MRBT-175CWN1-R
41
R410a Tropical Rooftop Package Unit 50Hz
MRCT-175EWN1-R
42
R410a Tropical Rooftop Package Unit 50Hz
MRBT-175HWN1-R
43
R410a Tropical Rooftop Package Unit 50Hz
8.8 20ton
MRBT-200CWN1-R
44
R410a Tropical Rooftop Package Unit 50Hz
MRCT-200EWN1-R
45
R410a Tropical Rooftop Package Unit 50Hz
MRBT-200HWN1-R
46
R410a Tropical Rooftop Package Unit 50Hz
8.9 30ton
MRCT-300HWN1-R
47
R410a Tropical Rooftop Package Unit 50Hz
9. Performance Data
Ent DB (℉) 75 80 85 90
SHC
Notes:
1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
48
R410a Tropical Rooftop Package Unit 50Hz
9.2 Cooling capacity for 6.2Ton:
Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 73.9 75.3 76.8 78.4 75.6 77.1 78.6 80.2 77.0 78.5 80.1 81.7
61
SHC 65.5 71.3 74.6 77.1 69.4 71.5 74.4 78.1 72.9 76.4 79.1 80.6
TGC 81.1 82.8 84.4 86.1 81.8 83.4 85.1 86.8 82.3 83.9 85.6 87.4
85 67
SHC 49.1 61.4 72.3 81.5 50.3 62.4 74.6 84.7 51.4 64.1 76.7 85.3
TGC 83.9 85.6 87.3 89.0 84.1 85.8 87.5 89.3 84.4 86.1 87.7 89.5
73
SHC 31.6 42.9 52.7 63.5 32.0 46.4 53.6 63.8 32.4 48.0 54.3 65.0
TGC 68.5 69.9 71.3 72.8 70.5 71.9 73.4 74.8 72.2 73.6 75.1 76.6
61
SHC 61.2 66.5 68.7 72.2 63.6 67.1 70.7 73.4 70.9 72.0 73.8 75.6
TGC 73.7 75.2 77.4 79.8 74.1 75.6 77.9 80.2 78.9 83.0 85.4 86.2
95 67
SHC 47.6 60.6 73.2 77.3 49.7 63.5 76.8 77.8 51.7 66.1 80.0 81.1
Ambient Temperature(°F)
TGC 83.2 84.9 86.6 88.3 83.5 85.2 86.9 88.6 83.4 85.1 86.8 88.5
73
SHC 30.6 43.3 54.2 65.4 31.1 44.0 55.5 67.0 31.6 47.0 56.6 68.6
TGC 63.0 64.2 65.5 66.8 64.7 66.0 67.4 68.7 66.3 67.7 69.0 70.4
61
SHC 60.2 61.3 64.6 66.3 63.7 64.7 65.9 68.0 64.4 66.5 67.9 69.8
TGC 73.0 74.5 76.0 77.5 74.3 75.8 77.3 78.9 75.4 76.9 78.4 80.0
105
67
SHC 45.4 56.0 71.9 76.4 47.6 62.0 76.7 78.1 49.8 65.3 76.2 78.2
TGC 80.6 82.2 83.8 85.5 81.8 83.4 85.1 86.8 82.2 83.8 85.5 87.2
73
SHC 28.9 42.6 55.5 66.7 30.0 44.2 56.9 68.5 30.4 45.2 58.3 70.7
TGC 56.9 58.0 59.1 60.3 59.1 60.2 61.4 62.7 61.0 62.2 63.5 64.7
61
SHC 51.8 54.4 57.2 58.5 56.9 58.5 60.1 61.9 59.5 60.2 62.3 64.1
TGC 66.4 67.8 69.1 70.5 63.1 65.0 66.3 68.3 69.0 70.3 71.8 73.2
115
67
SHC 42.7 55.8 66.3 69.5 44.9 59.4 61.2 63.0 47.1 63.0 69.5 72.4
TGC 72.8 74.2 75.7 77.3 78.6 80.2 81.8 83.4 79.2 80.8 82.4 84.0
73
SHC 27.9 41.0 53.7 66.1 28.5 42.6 56.4 69.6 29.0 44.4 58.7 72.7
TGC 52.2 53.2 54.2 55.3 54.2 55.3 56.4 57.5 55.9 57.1 58.2 59.4
61
SHC 47.5 49.9 52.5 53.6 52.2 53.6 55.1 56.9 54.6 55.3 57.1 58.8
TGC 60.9 62.2 63.4 64.6 62.2 63.5 64.7 66.0 63.3 64.6 65.8 67.1
125
67
SHC 39.2 51.3 60.8 63.7 41.2 54.5 63.7 65.7 43.2 57.8 63.7 66.4
TGC 66.8 68.1 69.5 70.8 72.1 73.5 75.1 76.5 72.7 74.1 75.6 77.1
73
SHC 25.6 37.6 49.3 60.7 26.1 39.1 51.7 63.9 26.7 40.8 53.9 66.7
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
49
R410a Tropical Rooftop Package Unit 50Hz
9.3 Cooling capacity for 7.5Ton:
Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 82.5 84.2 85.8 87.5 87.3 89 90.8 92.6 89.3 91.1 92.9 94.8
61
SHC 72.7 80.4 85.3 87.5 77.4 84.3 88.2 91.1 82 84.5 87.9 92.3
TGC 94.8 96.7 98.6 100.6 95.9 97.8 99.8 101.8 96.7 98.6 100.6 102.6
85 67
SHC 55.6 68.8 81.8 94.3 58 72.6 85.4 96.3 59.5 73.8 83.2 100.1
TGC 98.6 100.6 102.6 104.6 99.2 101.2 103.2 105.2 99.4 101.4 103.4 105.5
73
SHC 36.8 51 62 72.4 37.3 50.7 62.3 75.1 37.8 54.8 63.3 75.4
TGC 78.6 80.2 81.8 83.4 81 82.6 84.3 86 83.3 85 86.7 88.4
61
SHC 69.6 75.6 78 81.4 72.3 78.6 81.2 85.3 75.2 79.3 83.5 86.7
TGC 85.6 87.3 89.1 90.8 87.1 89 96.6 98 91.4 96.2 98.1 99.8
95 67
SHC 53.9 67.7 81.6 86.2 56.3 71.6 86.5 91.3 58.7 75 90.8 92
Ambient Temperature(°F)
TGC 97.8 99.8 101.8 103.8 98.3 100.3 102.3 104.3 98.7 100.7 102.7 104.7
73
SHC 35.7 50.2 62.3 74.5 36.2 51.2 64.1 77.3 36.8 52 65.6 79.2
TGC 72.1 73.5 75 76.5 74.4 75.9 77.4 79 76.5 78 79.6 81.2
61
SHC 66.4 68.3 71.3 73.2 71.2 72.4 76.3 78.4 75.3 76.5 77.9 80.4
TGC 84.4 86.1 87.8 89.6 86.3 88 89.8 91.6 87.8 89.6 91.3 93.2
105
67
SHC 51 65 79.2 86.3 53.7 66.2 85 90.3 56.3 73.3 90.6 92.3
TGC 95.3 97.2 99.2 101.1 95.2 97.1 99 101 96.7 98.6 100.6 102.6
73
SHC 34.2 48.9 64.2 76.8 34.1 50.4 65.6 78.8 35.4 52.2 67.2 80.9
TGC 65.3 66.6 67.9 69.3 67.2 68.5 69.9 71.3 69.8 71.2 72.6 74.1
61
SHC 63.2 64.6 66.4 68.6 61.2 64.3 67.6 69.1 67.3 69.1 71 73.2
TGC 76.7 78.2 79.8 81.4 78.5 80.1 81.7 83.3 80.1 817 83.3 85
115
67
SHC 47.8 62.1 75.4 80.2 50.5 66 78.3 82.1 53.1 70.2 82.1 84.6
TGC 90.8 92.6 94.5 96.4 86 87.7 89.5 91.3 92.9 94.8 96.7 98.6
73
SHC 32.4 46.3 61.2 76.4 33 48.4 63.5 78.1 33.7 50.4 66.6 82.3
TGC 59.9 61.1 62.3 63.6 61.7 62.9 64.1 65.4 64 65.3 66.6 68
61
SHC 58 59.3 60.9 62.9 56.1 59 62 63.4 61.7 63.4 65.1 67.2
TGC 70.4 71.8 73.2 74.7 72 73.5 74.9 76.4 73.5 75 76.5 78
125
67
SHC 43.9 57 69.2 73.6 46.3 60.6 71.8 75.3 48.7 64.4 75.3 77.6
TGC 83.3 85 86.7 88.4 78.9 80.5 82.1 83.7 85.2 86.9 88.7 90.4
73
SHC 29.7 42.5 56.1 70.1 30.3 44.4 58.3 71.7 30.9 46.2 61.1 75.5
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
50
R410a Tropical Rooftop Package Unit 50Hz
9.4 Cooling capacity for 8.5Ton:
Air Flow CFM 3000 3300 3600
Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 91.6 95.5 99.3 102.4 96.5 100.7 104.5 107.8 98.6 102.8 106.7 110.2
61
SHC 71.4 82.1 90.1 94.9 76.8 88.1 96.6 101.7 80.8 92.8 101.7 107.1
TGC 101.4 103.2 104.7 105.6 106.7 108.6 110.2 111.4 109 110.9 112.5 113.7
85 67
SHC 54.1 67.9 81.7 90.6 58.1 72.8 87.7 97.3 61.2 76.6 92.3 102.6
TGC 103.2 104.8 106.4 107.7 108.6 109.5 111.2 113.5 112.4 114.1 115.8 117.1
73
SHC 23.9 44.5 61.6 74.9 25.8 48.3 67.9 86.1 27.2 56.3 74.6 97.8
TGC 88.5 92.3 95.8 99.0 93.1 97.1 100.8 104.2 95.1 99.2 102.9 106.3
61
SHC 72.6 83.2 91.7 96.3 78.2 89.8 98.6 103.7 82.4 94.6 98.1 102.1
TGC 97.8 99.6 101.0 102.3 99.8 101.8 104.3 105.4 101.1 103.0 105.5 107.7
95 67
Ambient Temperature(°F)
SHC 55.2 68.7 83.4 92.4 59.2 74.3 89.4 99.8 62.4 78.1 94.1 104.5
Entering Wet Bulb(°F)
TGC 104.1 106 107.5 109.1 110.7 111.8 112.9 114.1 113.2 114.6 116.3 118.7
73
SHC 26.4 55.2 67.8 88.9 26.1 48.9 69.8 82.3 30.8 67.2 94.3 106.7
TGC 83.7 87.5 90.8 93.8 88.1 91.9 95.4 98.5 90.1 93.8 97.4 100.6
61
SHC 69.7 80.0 87.7 92.3 74.7 85.8 94.1 98.5 78.7 90.4 93.5 96.5
TGC 92.6 94.2 95.8 97.1 97.4 99.1 100.5 101.7 99.5 101.2 102.7 103.8
105 67
SHC 52.8 66.1 79.5 88.4 56.6 70.8 86.1 98.3 59.6 74.7 89.9 99.8
TGC 94.5 96.1 97.8 99.4 104.1 105.6 107.2 108.6 106.9 108.3 109.7 111.2
73
SHC 23.3 44.7 59.8 72.6 82.3 87.1 90.6 99.8 31.2 67.4 98.6 106.8
TGC 78.3 81.6 84.7 87.6 82.3 86.1 89.6 92.3 84.1 87.7 92.1 94.0
61
SHC 67.2 77.1 83.5 86.6 72 82.7 89.1 92.0 75.8 87.1 91.0 92.7
TGC 76.5 78.1 79.3 80.6 81 82.6 84.0 85.4 89.9 91.6 95.4 99.5
115 67
SHC 50.9 63.7 76.7 85.2 54.5 68.7 82.3 94.6 57.4 71.9 86.6 96.2
TGC 95.1 96.4 97.8 99.8 97.8 99.3 101.4 103.6 99.9 101.3 103.4 105.2
73
SHC 22.5 41.8 57.7 70.5 28.3 53.2 89.1 101.6 32.1 68.4 98.9 103.6
TGC 71.2 74.2 77.0 79.6 74.8 78.3 81.5 83.9 76.5 79.7 83.7 85.5
61
SHC 61.1 70.1 76.8 78.5 65.5 75.2 81.0 83.6 68.9 79.2 82.7 84.3
TGC 78.6 80.1 81.2 82.4 82.7 84.2 85.5 86.7 84.5 86.0 87.3 88.3
125 67
SHC 46.3 57.9 69.7 77.5 49.5 62.5 74.8 86.0 52.2 65.4 78.7 87.5
TGC 86.5 87.6 88.9 90.7 88.9 90.3 92.2 94.2 90.8 92.1 94.0 95.6
73
SHC 20.5 38.0 52.5 64.1 25.7 48.4 81.0 92.4 29.2 62.2 89.9 94.2
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
Heating capacity for 8.5Ton:
Net Capacities(kW)-3600 CFM
Peak Net Heating(kW) at Indicated Dry Bulb(℉) Peak Total Power(KW) at Indicated Dry Bulb(℉)
Outdoor Temp(℉) 70% RH
59 68 75.2 80.6 59 68 75.2 80.8
5 18.7 17.6 17.2 16.9 8.6 8.8 9.2 9.7
10.4 20.1 19.3 18.9 18.7 8.8 8.9 9.4 9.9
15.8 21.4 20.8 20.6 20.6 8.9 9.1 9.6 10.1
21.2 22.4 21.8 21.6 21.3 9.0 9.3 9.9 10.3
26.6 23.7 23.4 23.2 22.8 9.1 9.6 10.1 10.5
32 25.5 25.2 24.8 24.5 9.2 9.8 10.3 10.8
37.4 29.4 29.1 28.7 28.3 9.4 10.0 10.5 11.0
44.6 35.4 35.0 33.0 32.8 9.7 10.2 10.7 11.2
48.2 38.5 38.0 37.7 37.3 9.9 10.4 10.9 11.5
53.6 40.9 42.3 42.1 41.7 10.1 10.6 11.1 11.7
59 44.1 43.4 43.1 42.7 10.3 10.9 11.4 12.1
64.4 46.7 45.9 45.4 45.0 10.5 11.1 11.7 12.3
69.8 50.1 49.1 48.4 47.8 10.9 11.4 11.9 12.5
75.2 53.0 51.6 50.7 50.1 11.1 11.6 12.2 12.8
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.
51
R410a Tropical Rooftop Package Unit 50Hz
9.5 Cooling capacity for 10Ton:
Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 110.9 113.1 115.4 117.7 113.8 116.1 118.4 120.8 116.5 118.8 121.2 123.6
61
SHC 96.8 98.7 100.7 102.7 103.2 105.3 107.4 109.5 109.2 111.4 113.6 115.9
TGC 123.4 125.9 128.4 131 124.6 127.1 129.6 132.2 125.7 128.2 130.8 133.4
85 67
SHC 73.2 92 108.3 124.8 75.6 94.3 112.8 128.5 78 97.3 116.5 130.4
TGC 127.9 130.5 133.1 135.7 128.3 130.9 133.5 136.2 128.6 131.2 133.8 136.5
73
SHC 47.7 64.9 79.6 95.3 48.3 65.8 81.2 96.7 49 72.1 82.4 98.4
TGC 102.8 104.9 107 109.1 105.9 108 110.2 112.4 108.9 111.1 113.3 115.6
61
SHC 92.7 94.6 96.4 98.4 99.2 101.2 103.2 105.3 105.4 107.5 109.7 111.9
TGC 116.7 117 118.5 121 119.5 121 123.5 126 124 126 128.7 132.3
95 67
Ambient Temperature(°F)
SHC 70.8 89.8 108.6 123.4 74.3 94.8 114 124.3 77.4 99.3 120.3 128.4
Entering Wet Bulb(°F)
TGC 126.8 129.3 131.9 134.6 127.1 129.6 132.2 134.9 127.8 130.4 133 135.6
73
SHC 46.3 65.4 81.5 97.8 47.2 66.7 84.3 101.9 47.5 67.6 85.8 104.7
TGC 94.5 96.4 98.3 100.3 97.8 99.8 101.8 103.8 99.8 101.8 103.8 105.9
61
SHC 88.6 90.4 92.2 94 95.2 97.1 99 101 93.4 95.3 97.2 99.1
TGC 110.3 112.5 114.8 117.1 112.9 115.2 117.5 119.8 114.6 116.9 119.2 121.6
105 67
SHC 67.6 86.4 105.9 115.6 71.3 92.1 113.7 117.9 74.2 98.3 115.5 117.6
TGC 123.8 126.3 128.8 131.4 124.6 127.1 129.6 132.2 125.2 127.7 130.3 132.9
73
SHC 44.3 63.2 81 98.3 45.2 65.6 85.3 103.7 45.7 67.5 86.9 106.8
TGC 86.3 88 89.8 91.6 89.2 91 92.8 94.7 92.3 94.1 96 97.9
61
SHC 84.6 86.3 88 89.8 86.2 87.9 89.7 91.5 90.2 92 93.8 95.7
TGC 101.3 103.3 105.4 107.5 103.2 107 107.4 109.5 105.6 107.7 109.9 112.1
115 67
SHC 63.5 83.2 102.1 104.1 67.3 88.2 105.3 107.4 70.8 94.1 107.3 110.5
TGC 119.2 121.6 124 126.5 120.1 122.5 125 127.5 120.8 123.2 125.7 128.2
73
SHC 42.2 61.3 80.1 98.7 42.9 64.1 84.3 104.1 43.7 66.8 87.9 109.3
TGC 78.5 80 81.6 83.3 81.1 82.7 84.4 86.1 83.9 85.6 87.8 89
61
SHC 76.9 78.4 80 81.6 78.4 79.9 81.5 83.2 82 83.6 85.3 87
TGC 92.1 93.9 95.8 97.7 93.8 97.9 98.2 99.6 96 98.1 99.9 101.9
125 67
SHC 57.7 75.6 92.8 94.7 61.2 80.2 95.7 97.6 64.4 85.5 97.7 100.5
TGC 108.4 110.5 112.7 115 109.2 111.4 113.6 115.9 109.8 112 114.3 116.5
73
SHC 38.4 55.7 72.8 89.7 39 58.3 76.6 94.6 39.7 60.7 79.9 99.4
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
52
R410a Tropical Rooftop Package Unit 50Hz
9.6 Cooling capacity for 15Ton:
Air Flow CFM 5500 6000 6500
Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 163.6 165.6 172.9 182.7 168 171.6 179 188.7 169.9 174.2 185.1 193.6
61
SHC 131.5 155.8 166 175.3 138.7 165.6 173.6 183 146.1 167.2 177.7 185.9
TGC 183.3 185.5 187.6 190.2 188.7 190 191.1 192.4 191 192.5 193.6 195.1
85 67
SHC 104.7 127.8 149.8 172.9 109.3 132.7 157.1 180.2 111.2 136.4 162 187.6
TGC 193.6 197.3 199.8 202.2 195.8 198.5 202.2 204.5 198.3 201 203.3 205.8
73
SHC 72.2 96.8 117 136.4 73.6 99 119.6 138.6 74.9 99.9 121.6 143.7
TGC 153.4 157.1 164.5 175.4 155.3 162 171.7 181.4 160.8 164.5 176.6 186.3
61
SHC 125.3 149.8 159.5 170.1 132.7 157.1 166.6 176 140.1 159.5 171.3 180.8
TGC 171.7 174.2 176.6 180.2 179 180 182.7 183.9 185.1 186.5 187.7 188.7
95 67
Ambient Temperature(°F)
SHC 99.9 123 146.1 169.2 104.1 129 153.5 179 108.1 132.8 160.8 186.3
Entering Wet Bulb(°F)
TGC 188.8 191.1 193.5 196.1 190.2 192.2 195.2 198.5 191.9 194.3 196.8 198
73
SHC 69 93.1 114.8 135.2 70.5 96.3 117.8 140.1 71.8 97.9 120.7 143.7
TGC 142.7 146.4 153.8 166.1 147.6 151.3 163.6 171 150.1 156.2 169.7 180.8
61
SHC 119.6 140.5 147.6 159.4 127.9 145.2 157 164.1 135.3 151.5 164.6 173.2
TGC 163.6 166.1 169.7 171 164.8 168.5 173.4 175.9 173.4 175.9 178.4 180.8
105 67
SHC 94.6 118.1 141.3 165.7 109 124.2 149.8 170.6 102.6 130.3 157.1 175.4
TGC 185.7 187 188.2 189.4 188.2 189.4 190.7 193.1 190.7 191.9 193.1 194.3
73
SHC 65.6 89.2 111.7 132.8 67 92.3 115.5 138.9 68.3 95.3 118.6 142.4
TGC 130.4 135.3 147.6 159.9 134.1 141.5 153.8 166.1 137.8 140.4 150.9 172.2
61
SHC 114.5 131.2 143.2 155.1 121.6 135.8 147.6 159.4 127.9 136.2 146.9 167
TGC 153.8 156.2 157.4 160.9 155 158.7 161.1 163.6 163.6 166.1 169.7 174
115 67
SHC 98.4 113.4 136.5 159.9 103.3 119.9 145.1 163.6 108.2 125.5 151.3 168.8
TGC 173.4 175.9 178.4 179.6 178.4 180.8 182 183.3 182 183.3 184.5 185.7
73
SHC 62.1 85.6 108.9 131.6 63.5 89.8 113.2 136.5 66.4 92.3 118.1 143.9
TGC 125.4 130.1 141.9 152.1 128.9 136 147.8 159.7 132.5 140.7 153.8 165.6
61
SHC 110.1 126.2 137.7 147.5 117 131.9 143.4 154.9 13 136.5 149.1 160.6
TGC 147.8 150.2 151.4 153.8 149 152.6 154.9 157.3 157.3 159.7 163.2 167.1
125 67
SHC 94.6 109 131.3 153.8 99.3 115.3 139.6 152.6 104.1 120.6 145.5 162.1
TGC 166.8 169.1 171.5 172.7 171.5 173.9 175 176.2 175 176.2 177.4 178.6
73
SHC 59.7 82.3 104.7 126.5 61 86.3 108.8 131.3 63.9 88.7 113.5 138.4
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.
53
R410a Tropical Rooftop Package Unit 50Hz
9.7 Cooling capacity for 17.5Ton:
Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 187.6 189.9 198.3 209.5 192.6 196.8 205.3 216.4 194.8 199.7 212.2 222.0
61
SHC 150.8 178.7 190.3 201.0 159.0 189.9 199.1 209.8 167.5 191.7 203.8 213.2
TGC 210.2 212.7 215.1 218.1 216.4 217.9 219.1 220.6 219.0 220.7 222.0 223.7
85 67
SHC 120.1 146.5 171.8 198.3 125.3 152.2 180.1 206.6 127.5 156.4 185.8 215.1
TGC 222.0 226.2 229.1 231.9 224.5 227.6 231.9 234.5 227.4 230.5 233.1 236.0
73
SHC 82.8 111.0 134.2 156.4 84.4 113.5 137.1 158.9 85.9 114.6 139.4 164.8
TGC 175.9 180.1 188.6 201.1 178.1 185.8 196.9 208.0 184.4 188.6 202.5 213.6
61
SHC 143.7 171.8 182.9 195.0 152.2 180.1 191.0 201.8 160.6 182.9 196.4 207.3
TGC 196.9 199.7 202.5 206.6 205.3 206.4 209.5 210.9 212.2 213.9 215.2 216.4
95 67
SHC 114.6 141.0 167.5 194.0 119.4 147.9 176.0 205.3 124.0 152.3 184.4 213.6
TGC 216.5 219.1 221.9 224.9 218.1 220.4 223.8 227.6 220.0 222.8 225.7 227.0
73
SHC 79.1 106.8 131.6 155.0 80.8 110.4 135.1 160.6 82.3 112.3 138.4 164.8
Ambient Temperature(°F)
TGC 163.6 167.9 176.4 190.5 169.2 173.5 187.6 196.1 172.1 179.1 194.6 207.3
Entering Wet Bulb(°F)
61
SHC 137.1 161.1 169.2 182.8 146.7 166.5 180.0 188.2 155.1 173.7 188.7 198.6
TGC 187.6 190.5 194.6 196.1 189.0 193.2 198.8 201.7 198.8 201.7 204.6 207.3
105 67
SHC 108.5 135.4 162.0 190.0 125.0 142.4 171.8 195.6 117.6 149.4 180.1 201.1
TGC 212.9 214.4 215.8 217.2 215.8 217.2 218.7 221.4 218.7 220.0 221.4 222.8
73
SHC 75.2 102.3 128.1 152.3 76.8 105.8 132.4 159.3 78.3 109.3 136.0 163.3
TGC 149.5 155.1 169.2 183.4 153.8 162.3 176.4 190.5 158.0 161.0 173.0 197.5
61
SHC 131.3 150.4 164.2 177.8 139.4 155.7 169.2 182.8 146.7 156.2 168.4 191.5
TGC 176.4 179.1 180.5 183.4 177.7 182.0 184.7 187.6 187.6 190.5 194.6 199.5
115 67
SHC 112.8 130.0 156.5 183.4 118.5 137.5 166.4 187.6 124.1 143.9 173.5 193.6
TGC 198.8 201.7 204.6 205.9 204.6 207.3 208.7 210.2 208.7 210.2 211.6 212.9
73
SHC 71.2 98.2 124.9 150.9 72.8 103.0 129.8 156.5 76.1 105.8 135.4 165.0
TGC 143.8 149.2 162.7 174.4 147.8 155.9 169.5 183.1 151.9 161.3 176.4 189.9
61
SHC 126.2 144.7 157.9 169.1 134.2 151.2 164.4 177.6 141.0 156.5 171.0 184.2
TGC 169.5 172.2 173.6 176.4 170.9 175.0 177.6 180.4 180.4 183.1 187.1 191.6
125 67
SHC 100.4 125.0 150.6 176.4 113.5 132.2 160.1 175.0 119.4 138.3 166.8 185.9
TGC 191.3 193.9 196.7 198.0 196.7 199.4 200.7 202.0 200.7 202.0 203.4 204.8
73
SHC 68.5 94.4 120.1 145.1 69.9 99.0 124.8 150.6 73.3 101.7 130.1 158.7
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
Outdoor Temp(℉) 70% RH Peak Net Heating(kW) at Indicated Dry Bulb(℉) Peak Total Power(KW) at Indicated Dry Bulb(℉)
59 68 75.2 80.6 59 68 75.2 80.8
5 35.6 33.5 32.8 32.3 15.6 17.2 18.2 19.2
10.4 38.4 36.7 36.0 35.6 15.9 17.5 18.3 19.5
15.8 40.7 39.6 39.2 39.2 16.2 17.6 18.5 19.9
21.2 42.7 41.4 41.0 40.6 16.3 17.9 18.9 20.2
26.6 45.2 44.5 44.2 43.4 16.5 18.0 19.2 20.6
32 48.6 47.9 47.2 46.7 16.6 18.3 19.5 20.7
37.4 56.0 55.4 54.6 53.9 17.0 18.6 19.9 21.0
44.6 68.5 67.0 62.9 62.5 17.6 19.8 20.6 21.7
48.2 73.3 72.4 71.6 70.9 18.3 20.3 21.6 22.9
53.6 77.8 80.5 80.2 79.4 19.0 21.2 22.4 23.7
59 83.9 82.7 82.1 81.2 19.5 21.7 22.9 24.3
64.4 88.9 87.4 86.4 85.7 20.0 22.3 23.6 24.7
69.8 95.4 93.5 92.2 91.0 20.3 22.6 23.7 25.0
75.2 100.8 98.2 96.5 95.4 20.9 22.9 24.6 25.4
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.
54
R410a Tropical Rooftop Package Unit 50Hz
9.8 Cooling capacity for 20Ton:
Ent DB (°F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 216.1 218.7 228.5 241.3 222.0 226.7 236.4 249.3 224.4 230.1 244.6 255.8
61
SHC 173.7 205.9 221.6 234.1 183.3 218.7 229.3 241.8 193.1 223.2 237.2 248.1
TGC 242.1 245.1 247.8 251.2 249.3 251.1 252.5 254.2 252.4 254.3 255.8 257.7
85 67
SHC 138.3 168.8 197.9 228.5 144.5 175.3 207.5 238.1 146.9 180.2 214.0 247.8
TGC 255.8 260.7 263.9 267.2 258.7 262.3 267.2 270.2 262.0 265.5 268.6 271.9
73
SHC 95.4 127.9 154.5 180.2 97.2 130.8 158.0 183.1 99.0 132.0 160.7 189.8
TGC 202.6 207.5 217.3 231.7 205.2 214.0 226.9 239.7 212.4 217.3 233.4 246.2
61
SHC 165.6 197.9 210.7 224.8 175.3 205.5 217.8 230.1 185.1 210.7 226.3 238.8
TGC 226.9 230.1 233.4 238.1 236.4 240.0 241.3 242.9 244.6 246.4 248.0 249.3
95 67
Ambient Temperature(°F)
SHC 132.0 162.5 193.1 223.6 137.5 170.5 202.8 236.4 142.8 175.5 212.4 246.2
Entering Wet Bulb(°F)
TGC 249.4 252.5 255.6 259.0 251.2 254.0 257.9 262.3 253.5 256.8 260.0 261.6
73
SHC 91.2 123.0 151.6 178.6 93.1 127.2 155.7 185.1 94.9 129.4 159.4 189.8
TGC 188.5 193.4 203.1 219.4 195.0 199.9 216.1 225.9 198.3 206.4 224.3 238.9
61
SHC 158.0 187.6 197.0 212.8 169.0 193.9 209.6 219.1 178.8 200.2 217.5 231.7
TGC 216.1 219.4 224.3 225.9 217.8 222.6 229.1 232.4 229.1 232.4 235.6 238.9
105 67
SHC 125.0 156.0 186.7 218.9 144.0 164.1 197.9 209.1 135.5 172.1 207.5 238.9
TGC 245.4 247.0 248.6 250.3 248.6 250.3 251.9 255.1 251.9 253.5 255.1 256.8
73
SHC 86.6 117.8 147.6 175.5 88.6 122.0 152.6 183.5 90.2 125.9 156.7 188.2
TGC 172.3 178.8 195.0 211.3 177.1 186.9 203.1 219.4 182.0 193.4 211.3 227.5
61
SHC 151.3 173.4 189.2 204.9 160.7 181.3 197.0 212.8 169.0 187.6 204.9 220.7
TGC 203.1 206.4 208.0 211.3 204.8 209.6 212.9 216.1 216.1 219.4 224.3 227.5
115 67
SHC 130.0 149.8 180.4 211.3 136.5 158.4 191.8 216.1 143.0 165.8 199.9 227.5
TGC 229.1 232.4 235.6 237.3 235.6 238.9 240.5 242.1 240.5 242.1 243.8 245.4
73
SHC 82.1 113.1 143.8 173.9 83.9 118.6 149.5 180.4 87.8 121.9 156.0 190.1
TGC 162.5 168.6 184.0 199.3 167.1 176.3 191.6 207.0 171.6 182.4 199.3 214.6
61
SHC 147.2 163.6 178.4 193.3 151.6 171.0 185.9 200.7 159.4 177.0 193.3 208.2
TGC 191.6 194.7 196.2 210.3 193.2 197.8 200.8 203.9 203.9 207.0 211.6 214.6
125 67
SHC 122.6 141.3 170.2 189.3 128.8 149.5 180.9 199.8 134.9 156.4 188.6 210.3
TGC 216.2 219.2 222.3 223.8 222.3 225.4 226.9 228.4 226.9 228.4 230.0 231.5
73
SHC 77.4 106.7 135.7 164.0 79.1 111.9 141.0 170.2 82.8 115.0 147.2 179.4
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
55
R410a Tropical Rooftop Package Unit 50Hz
9.9 Cooling capacity for 30Ton:
Air Flow(CFM) 11000 12000 13000
Ent DB (F) 75 80 85 90 75 80 85 90 75 80 85 90
TGC 289.0 292.9 307.0 326.0 297.5 304.5 318.8 337.6 301.2 309.5 330.6 347.0
61
SHC 231.3 278.2 298.0 315.9 245.2 297.2 312.7 324.8 259.5 300.3 320.6 336.4
TGC 327.1 331.4 335.4 340.5 337.6 340.1 342.2 344.7 342.0 344.9 347.0 349.9
85 67
SHC 179.4 224.1 266.6 311.3 188.3 233.6 280.8 325.4 192.0 240.7 290.2 319.7
TGC 347.0 354.2 359.0 363.7 351.3 356.5 363.7 368.1 356.1 361.3 365.8 370.6
73
SHC 116.6 164.2 203.2 240.7 119.3 168.4 208.3 245.0 121.8 170.2 212.1 254.8
TGC 269.3 276.5 290.8 311.8 273.0 313.2 304.7 323.4 283.6 290.8 314.2 332.9
61
SHC 219.3 266.6 285.4 305.9 233.6 276.0 299.1 317.3 247.9 285.4 308.2 326.6
TGC 315.0 319.8 324.5 331.4 329.1 331.0 336.3 338.6 340.9 343.6 345.9 347.9
95 67
SHC 170.2 214.8 259.5 304.1 230.3 278.4 301.8 313.1 233.0 249.8 293.9 319.2
TGC 337.8 342.2 346.8 351.9 340.5 344.3 350.1 356.5 343.7 348.4 353.2 355.5
73
SHC 110.4 157.0 199.0 238.4 113.3 163.2 204.8 247.9 115.8 166.3 210.4 254.8
Ambient Temperature( F)
O
TGC 248.6 255.8 270.1 293.9 258.1 265.3 289.0 303.3 262.9 274.7 300.8 322.3
61
SHC 208.3 248.7 262.4 285.2 224.3 257.7 280.6 294.3 238.6 269.9 295.3 311.9
TGC 289.0 293.9 300.8 303.3 291.4 298.5 308.0 312.8 308.0 312.8 317.6 322.3
105 67
SHC 159.9 205.4 250.2 297.4 187.8 217.1 266.6 306.9 175.4 228.9 280.8 316.1
TGC 331.8 334.3 336.6 338.9 336.6 338.9 341.4 346.1 341.4 343.7 346.1 348.0
73
SHC 103.9 149.5 193.0 233.8 106.6 155.5 200.3 245.6 109.1 161.3 206.3 252.3
TGC 234.8 244.3 268.1 291.9 242.0 256.3 280.1 303.9 249.2 254.2 274.5 315.7
61
SHC 198.4 230.7 253.9 276.9 212.1 239.6 262.4 285.2 224.3 238.3 251.0 289.9
TGC 290.1 294.7 297.0 301.9 292.4 299.6 302.2 309.0 309.0 313.9 320.8 329.1
115 67
SHC 192.9 221.9 266.5 291.0 202.3 234.4 283.2 287.0 216.8 250.3 290.1 294.0
TGC 308.0 312.8 317.6 320.0 317.6 322.3 324.6 327.1 324.6 327.1 329.4 331.8
73
SHC 97.1 142.5 187.6 231.5 102.8 150.6 195.9 240.9 105.4 155.5 205.4 255.2
TGC 215.2 224.3 247.1 266.8 221.9 235.7 258.5 281.5 228.9 244.8 270.1 292.9
61
SHC 189.9 201.0 223.2 242.2 203.2 232.0 254.3 276.5 214.8 230.9 255.3 285.5
TGC 258.5 263.1 265.4 270.1 260.8 267.8 272.2 276.9 276.9 281.5 288.3 295.8
125 67
SHC 146.4 187.8 230.9 254.4 168.4 199.9 246.9 262.1 178.3 210.2 258.3 286.4
TGC 295.2 299.7 304.3 306.6 304.3 308.9 311.1 313.4 311.1 313.4 315.7 318.0
73
SHC 92.4 136.1 179.4 221.6 95.0 143.9 187.4 230.9 100.6 148.5 196.5 244.6
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. TGC=Total Gross Capacity. (Unit: MBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: MBtu/h).
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.
56
R410a Tropical Rooftop Package Unit 50Hz
Model Power Supply Compressor Evaporator fan motor Condenser fan motor
MCA TOCA MFA STC RNC IPT Qty RNC IPT Qty RNC IPT Qty
MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A) STC: Starting Current (A)
RNC: Running Current (A) IPT: Input (kW)
Note:
1. The item with ※ power supply: 380-415V/3Ph/50Hz(Tolerance:342V-440V);
2. The starting current is indicated for each compressor motor.
3. The maximum currents of the compressor can be estimated as follows.
One compressor unit Two compressor unit
Max. IPT×: Compressor power input from the performance table at the expected maximum condition
STC, IPT, RNC: Compressor data from the above table
11. The data in the compressor motor column shall indicate the respective values of the refrigeration cycle.
57
R410a Tropical Rooftop Package Unit 50Hz
58
R410a Tropical Rooftop Package Unit 50Hz
11.1 Model:5ton
Air flow (CFM) 1920 1872 1831 1800 1795 1749 1701 1649 1598 1536
Brake power (kW) 0.7782 0.7634 0.752 0.742 0.7417 0.73 0.716 0.7015 0.687 0.67
Fan speed (rpm) 846 881 914 944 948 975 1006 1036 1067 1096
59
R410a Tropical Rooftop Package Unit 50Hz
11.2 Model:6.2ton
Air flow (CFM) 2853 2754 2632 2602 2522 2413 2310 2236 2108
Brake power (kW) 1.51 1.4 1.36 1.34 1.2 1.14 1.09 1.05 0.98
Fan speed (rpm) 1068 1072 1077 1077 1080 1082 1085 1089 1091
250
Static pressure(Pa)
225
200
175
150
125
100
75
50
25
0
2200 2300 2400 2500 2600 2700 2800 2900 3000 3100
Air volume(CFM)
60
R410a Tropical Rooftop Package Unit 50Hz
11.3 Model: 7.5Ton
Air flow (CFM) 3240 3149 2996 2941 2886 2782 2664 2540 2411
Brake power (kW) 1.83 1.78 1.70 1.66 1.63 1.58 1.53 1.47 1.41
Fan speed (rpm) 1260 1265 1268 1271 1274 1277 1281 1285 1287
250
Static pressure(Pa)
225
200
175
150
125
100
75
50
25
0
2500 2600 2700 2800 2900 3000 3100 3200 3300 3400
Air volume(CFM)
61
R410a Tropical Rooftop Package Unit 50Hz
Air flow (CFM) 3940 3785 3612 3451 3302 3130 2955 2759
Brake power (kW) 1.88 1.81 1.73 1.66 1.59 1.51 1.43 1.35
Fan speed (rpm) 933 937 939 944 946 949 952 953
250
Static pressure(Pa)
225
200
175
150
125
100
75
50
25
0
2800 3000 3200 3400 3600 3800 4000 4200 4400 4600
Air volume(CFM)
62
R410a Tropical Rooftop Package Unit 50Hz
Air flow (CFM) 4298 4156 3929 3756 3579 3382 3218 3020
Brake power (kW) 2.18 2.1 2.02 1.96 1.86 1.79 1.71 1.62
Fan speed (rpm) 1000 1004 1006 1011 1014 1016 1020 1021
225
200
175
150
125
100
75
50
25
0
2800 3000 3200 3400 3600 3800 4000 4200 4400 4600
Air volume(CFM)
Fig.7-4
Parameter table for outdoor unit air volume:
Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)
63
R410a Tropical Rooftop Package Unit 50Hz
Air flow (CFM) 7209 6675 6575 6400 6150 6044 5639 5227
Brake power (kW) 5.11 4.85 4.71 4.65 4.45 4.32 4.08 3.82
Fan speed (rpm) 1029 1029 1030 1031 1031 1032 1033 1034
225
200
175
150
125
100
75
50
25
0
5200 5450 5700 5950 6200 6450 6700 6950 7200 7450
Air volume(CFM)
64
R410a Tropical Rooftop Package Unit 50Hz
Static pressure (Pa) 0 25 50 75 100 125 150 175 200 225 250 275 300
Air flow (CFM) 7858 7712 7546 7392 7271 7091 6977 6836 6680 6534 6354 6178 6020
Brake power (kW) 5.76 5.66 5.57 5.36 5.3 5.14 5.05 4.88 4.78 4.67 4.55 4.37 4.12
Fan speed (rpm) 1019 1020 1020 1021 1022 1022 1023 1024 1025 1025 1026 1027 1030
270
240
210
180
150
120
90
60
30
0
6200 6400 6600 6800 7000 7200 7400 7600 7800 8000
Air volume(CFM)
65
R410a Tropical Rooftop Package Unit 50Hz
Air flow (CFM) 9296 8782 8452 8289 8179 7826 7388 6955 6555
Brake power (kW) 5.86 5.73 5.59 5.44 5.50 5.27 4.98 4.66 4.32
Fan speed (rpm) 818 819 819 820 820 821 822 823 825
270
240
210
180
150
120
90
60
30
0
6800 7100 7400 7700 8000 8300 8600 8900 9200 9500
Air volume(CFM)
66
R410a Tropical Rooftop Package Unit 50Hz
Static pressure (Pa) 150 175 200 225 250 275 300 325 350
Air flow (CFM) 14664 14464 14119 13743 13230 12729 12365 11957 11489
Brake power (kW) 8.91 8.59 8.30 8.01 7.71 7.40 7.07 6.74 6.39
Fan speed (rpm) 775 775 776 777 778 779 780 782 782
460
420
380
340
300
260
220
180
140
9500 10000 10500 11000 11500 12000 12500 13000 13500 14000 14500
Air volume(CFM)
67
R410a Tropical Rooftop Package Unit 50Hz
T3
Condenser
Capillary
High pressure
switch
TP Evaporator
T2
T3
Condenser
High pressure Four way valve
Capillary
switch
TP Evaporator
Low pressure switch
Comp
T2
68
R410a Tropical Rooftop Package Unit 50Hz
T3
High pressure
switch
T3
TP Condenser
Capillary
Capillary
High pressure
switch
Comp
TP T2
T2
Evaporator
Cooling and Heating type:
T3
Capillary
TP Evaporator
TP Low pressure T2
Low switch
Comp
pressure
switch
Comp
T2
69
R410a Tropical Rooftop Package Unit 50Hz
Standard
operation
Temperature
Outdoor temperature Indoor temperature
Model
Cooling mode 18℃~52℃ 17℃~30℃
With auxiliary electric heater models -- 17℃~30℃
70
R410a Tropical Rooftop Package Unit 50Hz
55 Cooling mode
50
45
Outdoor temperature(℃ DB)
40
Standard
35 operation
30
25
20
15
10 17 30
Indoor temperature(℃ WB)
Temperature
Outdoor temperature Indoor temperature
Mode
Cooling mode 18℃~52℃ 17℃~30℃
Heating mode
25
Outdoor temperature(℃ DB)
20
15
10 Standard
operation
5
0
-5 10 17 30
-10
Indoor temperature(℃ WB)
Temperature
Outdoor temperature Indoor temperature
Mode
71
R410a Tropical Rooftop Package Unit 50Hz
14. Installation
14.1 Lifting
Rigging cables should have adequate capability to resist 3 times weight of unit. Before lift, please check and
ensure that hooks are holding tightly to unit and lifting angles are no less than 60°.
Cloth material or hard-paper should be padded in the contact place between unit and rigging cable. Rigging
cable should be entwined a round at the hook for prevent danger by cable slip because of weight unbalance.
During lifting, anyone forbidden lingering under the lifting unit.
72
R410a Tropical Rooftop Package Unit 50Hz
0.5m
1m
Overhead air
Overhead air 1m Clearance≥3m 1m
0.6mClearance≥1.55m 0.3m
0.8m
1m
For 5ton For 6.2ton and above
For roof top applications using a field fabricated frame and ducts, according to the following procedure:
1) The frame must be located and secured by bolting or welding to the roof. Flashing is required.
2) The hole in the roof must be prepared in advance of installing the unit.
3) Secure the ducts to the roof.
4) Place the unit on the frame or roof curb.
5) Secure the unit to the frame or roof curb.
6) Insulate any ductwork outside of the structure with at least two (2) inches of insulation and then
weatherproof. There must be a weatherproof seal where the duct enters the structure.
7) Complete the installation according to the instructions.
Typical rooftop application with frame:
73
R410a Tropical Rooftop Package Unit 50Hz
74
R410a Tropical Rooftop Package Unit 50Hz
75
R410a Tropical Rooftop Package Unit 50Hz
Typical ground level application:
Drain pan
A B
Drain commutator
6.2&7.5&8.5&10&15&17.5&20ton:
76
R410a Tropical Rooftop Package Unit 50Hz
14.6 Ductwork
Supply and return air flanges are provided on the roof curb for easy duct installation. All ductwork must be run
and attached to the curb before the unit is set into place.
Follow these guidelines for ductwork construction:
1) Connections to the unit should be made with three-inch canvas connectors to minimize noise and vibration
transmission.
2) Elbows with turning vanes or splitters are recommended to minimize air noise and resistance.
3) The first elbow in the ductwork leaving the unit should be no closer than two feet from the unit, to minimize
noise and resistance.
77
R410a Tropical Rooftop Package Unit 50Hz
14.7 Wiring provision
Field wiring
The units are internally wired at the factory according to generally accepted electrical technology.
Main power wiring to the unit control wiring between the control center and the unit, and earth wiring are
required in the field.
5Ton 6.2&7.5&8.5&10Ton 15&17.5&20Ton
Required components
The following components are required: main power fuse, conduit coupling, and field supplied room
thermostat.
Wire and fuse size should be selected in accordance with national standard, taking the designed maximum
current shall be the total of the compressor maximum current, condenser fan motor current and evaporator
fan motor current (refer to “electrical data”).
The wire size between the room thermostat and the unit should be determined according to the following
table, because the 24V power source is applied to the control circuit.
78
R410a Tropical Rooftop Package Unit 50Hz
15 Wired Controller
KJR-12B/DP (T)-E
1. SAFETY PRECAUTIONS
The following contents are stated on the product and the operation manual, including usage, precautions
against personal harm and property loss, and the methods of using the product correctly and safely. After fully
understanding the following contents (identifiers and icons), read the text body and observe the following
rules.
Identifier description
79
R410a Tropical Rooftop Package Unit 50Hz
2. SUMMARIZE
Usage condition:
○1 . Power supply: 5V DC.
3. FUNCTION SUMMARY
Main function:
○1 . Connecting to indoor unit by A, B, C, D, E terminal;
○3 . LCD display.
80
R410a Tropical Rooftop Package Unit 50Hz
5. INSTALLATION METHOD
When a wired controller is needed, a small 5-way terminal should be added, fix an infrared emitter with
gumwater near the receiver on the switch board. Connect its anode and cathode to A and B, and +5V, GND,
RUN to C, D, E on the switch board.
① Mode button:
When press this button, the operation mode change as the following sequence:
Remark: For the cooling only model, the heating mode is skipped.
② Timer on button :
Press this button, timer on function is active. Then every press, the time increase 0.5h, after 10h, 1h increase
after each press. If cancel this Function, just set it to "0.0".
③ Timer off button:
Press this button, timer off function is active. Then every press, the time increase 0.5h, after 10h, per 1h
increase after each press. If cancel this function, just set it to "0.0".
④ Follow me button:
When under cool, heat and auto mode, press this button, follow me function is active. Press again, this
function is ineffective.
⑤ Electrical heater button :
If press this button in heat mode, electrical heater function become ineffective.
81
R410a Tropical Rooftop Package Unit 50Hz
⑥ Reset button(hidden):
Use a 1mm stick to press in the little hole , then the current setting is canceled . The wired controller will enter
into original state.
⑦ON/OFF button:
When in off state, press this button, the indicator is on, the wire controller enter into on state, and send
setting information to in door PCB. When in on state, press this button, the indicator is off, and send
instruction. If timer on or timer off has been set, it cancel this setting then send instruction to stop the
machine.
⑧ Adjust button ▲:
Set indoor temperature up. If press and hold on, it will increase at 1 degree per 0.5 second.
⑨ Adjust button ▼ :
Set indoor temperature down. If press and hold on, it will decrease at 1degree per 0.5 second.
⑩ Swing button:
First pressing: start swing function; second pressing: stop swing. (Match to some model with swing function).
○
11 Economy operation button:
Press this button, the indoor unit operates in economy mode, press it again, exit this mode (it may be
ineffective for some models)
○
12 Fan speed button:
Press this button consecutively, the fan speed will circle as follow:
○
13 Lock button (hidden):
When you push the LOCK button, all current settings are locked in and the wire controller does not accept
any operation except that of the LOCK button. Use the lock mode when you want to prevent setting from
being changed accidentally or play fully. Push the LOCK button again when you want to cancel the LOCK
mode.
7. USING METHOD
AUTOMATIC OPERATION
Connect to power, indoor operation lamp flash.
○1 . Press "MODE" button, select " AUTO " ;
○2 . Press the button "▲" and "▼", set temperature you want, generally it is among 17℃~30℃;
○3 . Press " ON/OFF" button, operation lamp is on, the air-conditioner work in auto mode, indoor fan is auto,
and can not be changed. Auto is displayed on LCD. Press " ON/OFF" button again to stop.
○4 . Economy operation is valid in auto mode.
○4 . Press "ON/OFF" button, indoor unit operation lamp on, it works in selected mode. Press "ON/OFF" button
DRY OPERATION
82
R410a Tropical Rooftop Package Unit 50Hz
○1 . Press " MODE " button, select " DRY " mode.
○3 . Press " ON/OFF " button, indoor unit operation lamp on, it works in dry mode. Press ON/OFF button again,
it stops to work.
○4 . In dry mode, economy operation and fan speed are ineffective.
TIMER SETTING
Timer on only:
○1 . Press " TIME ON " button, it display "SET" on LCD, and display " H " and "ON" , it is waiting for timer on
setting.
○2 . Press " timer " on button repeatedly to adjust time setting.
○3 . If press this button and hold on, the time will increase at 0.5h, after 10h, it increases at 1h.
○4 . After setting 0.5 second, the wire controller send timer on information, it is finished.
setting.
○2 . Press "TIME OFF" button repeatedly to adjust time setting.
○3 . If press this button and hold on, the time will increase at 0.5h, after 10h, it increases at 1h.
○4 . After setting 0.5 second, the wire controller send timer off information, it is finished.
○
1 . Set timer on time as the corresponding step1 and 2.
○
2 . Set timer off time as the corresponding step1 and 2.
○
3 . Timer off time must be longer than timer on time.
○
4 . 0.5 second after setting, the wire controller send information, the setting is finished.
CHANGE TIMER
If there is a timer of changing time to be need, press corresponding button to revise it. If cancel timer, change
time to 0.0.
NOTE: The timer time is relative time, that is delay after setting time ( i, e: setting time is 8:05 A,M). So when
timer is set, the standard time can not be adjusted.
83
R410a Tropical Rooftop Package Unit 50Hz
15.2 Optional wired controller:
KJR-23B KJR-25B
R G Y (C ) R G Y W (C ) R G Y B ( C )
5 -termi na l
KJR -1 2B Gro up ON
BROW N SW3
A 1 CN7
RED
B
YELLOW
WHITE
Y ELLOW MAINCONTROLBOARD
RED
C CN9
GREEN
BL ACK
D CN36
WH ITE
E
R G Y (C) XT2
TOTHEWIREDCONTROLLER
84
R410a Tropical Rooftop Package Unit 50Hz
For Cooling+EAH Units
5 -termi na l
KJR -1 2B Gro up ON
BROW N SW3
A 1 CN7
RED
B
YELLOW
WHITE
BLUE
CN9 MAINCONTROLBOARD
RED
Y ELLOW
C
BL ACK
D CN36 GREEN
WH ITE
E
R G Y W(C) XT2
TOTHEWIREDCONTROLLER
5 -termi na l
KJR -1 2B Gro up ON
BROW N SW3
A 1 CN7
RED
B
YELLOW
WHITE
BLUE
CN9 MAINCONTROLBOARD
RED
Y ELLOW
C
BL ACK
D CN36 GREEN
WH ITE
E
R G Y W(C) XT2
TOTHEWIREDCONTROLLER
Remark:
Two stage capacity output controlling is optional.
85
R410a Tropical Rooftop Package Unit 50Hz
Normal Standby --
Protection Protection for Hi./Lo. Pressure or exhaust temp. (System 1) P4 Auto reset
Protection Protection for Hi./Lo. Pressure or exhaust temp. (System 1) P5 Auto reset
Protection Protection for High temperature of the outdoor condenser P8 Auto reset
Normal Standby --
Protection Protection for Hi./Lo. Pressure or exhaust temp. in sys. A P4 Comprehensive protection in sys. A
Protection Protection for Hi./Lo. Pressure or exhaust temp. in sys. B P5 Comprehensive protection in sys. B
Protection T2 evaporator Hi-temperature protection stop outdoor unit fan P6 Auto reset
Protection T2 evaporator Hi- temperature protection then stop outdoor unit fan and compressor P7 Auto reset
86
R410a Tropical Rooftop Package Unit 50Hz
16.2 Troubleshooting
For 5ton
○
1 E0:Compressor phase sequence error or phase default
○
2 E1:Outdoor coil temp. sensor T3 default.
Yes No
87
R410a Tropical Rooftop Package Unit 50Hz
○
3 E9:Indoor coil temp. sensor T2 default.
(Indoor temp. and Pipe Temp. Sensor Resistance Value Table, see Appendix 2 )
No
Yes
Replace the temp. sensor,
Replace the main board.
detect it again.
○
4 When E2,E5,E6 or EA displays, please check the wired nameplate, if the terminals of T2_1、T2_2、
T3_2、T4 are connected as short circuit. If no, please connect all as short circuit, unless replace main
board.
○
5 Eb: Wired controller output error.(Only for KJR-23B or KJR-25B).
○
6 P0:Compressor over current protection.(The over current protection value is 16A)
○
7 P3:Comprehensive protection for outdoor fan
Yes
Detect by multimeter if
No Replace three-phase
three-phase protector COM
protector, detect it again.
and NO exist current circuit.
Yes
88
R410a Tropical Rooftop Package Unit 50Hz
○
8 P4:Protection for Hi./Lo. Pressure or exhaust temp. (High pressure protection value:4.4MPa, High
Yes
Yes
○
9 Indoor fan motor don’t work.
Yes
Yes
○
10 Outdoor fan motor don’t work.
Detect if there exist power supply from No Replace the main board.
main board to outdoor fan.
Yes
Yes
89
R410a Tropical Rooftop Package Unit 50Hz
For 6.2ton and above
Yes
No
Detect if the voltage of the fan on PCB Replace T2 sensor or check if exist
No
Yes
If the indoor fan contactor is close. Detect if the fuse on PCB is burned off.
Yes No Yes No
Replace motor. Replace contactor. Replace fuse. Check if the secondary voltage
transformer is normal.
Yes No
90
R410a Tropical Rooftop Package Unit 50Hz
○
2 Compressor don’t run (All wires connection are correct and reliable, if power supplier is required
Yes No
close. off.
Yes No Yes No
Yes No
Replace Replace
PCB. transformer.
○
3 T3 temp sensor error.
Yes No
○
4 Check if the low pressure protection is normal.
Yes No
91
R410a Tropical Rooftop Package Unit 50Hz
○
5 Outdoor fan motor don’t run.
Yes No
If the outdoor fan motor contactor is Detect if the fuse on PCB is burned off.
close.
Yes No Yes No
Yes No
○
6 Four ways valve don’t work.
Yes No
Replace four way valve or coil. Detect if the fuse on PCB is burned off.
Yes No
Yes No
Replace Replace
PCB. transformer.
92
R410a Tropical Rooftop Package Unit 50Hz
○
7 Condenser high temperature protection
No
Check: There is air or nitrogen in system (air comes from the incomplete
vacuum drying, and nitrogen is caused by directly pressurizing to ball
valve), symptom: Pressure value of high/low is high, discharge and suction Yes
temperature is high, current is large, there may be abnormal noise in
compressor, pressure gauge is jittering. Remove the problem
No
93
R410a Tropical Rooftop Package Unit 50Hz
17. Accessories
Model A
6.2 Ton 328mm
7.5 Ton 328mm
8.5Ton 395mm
10 Ton 395mm
15 Ton 576mm
17.5 Ton 576mm
20 Ton 525mm
30Ton 925mm
Note:At least 1m flame resistant layer must be laid at the end of the air duct internal surface.
Regulating belt of rate of tension, inner fan Refer to the following Fig. fixed bolt of electric motor‟s supporting
slide was loosened, following electric motor was droved, belt of rate of tension will begin change.
94
R410a Tropical Rooftop Package Unit 50Hz
NOTE:The belt which is too tight or too loose may generate noise and be harmful to the unit.
Dismantle the air filter.
Twist of screws and up the plate that is gets out.
Upon loose the filter-baffle-plate, the filter could be pulled out along the supporting slot.
5ton
7.5&10&15&20ton
Screw
Filter
Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust
accumulation is too heavy, please use soft brush and mild detergent to clean it and dry out in cool
place).
95
R410a Tropical Rooftop Package Unit 50Hz
CAUTION:
Do not operate the unit without the evaporator fan access panel in place. Reinstall the access panel
after performing any maintenance. Operating the unit without the access panel may result in severe
personal injury or death.
96
R410a Tropical Rooftop Package Unit 50Hz
Appendix :
1. Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (6.2ton and above)
97
R410a Tropical Rooftop Package Unit 50Hz
2. Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (5ton)
Temp Resistance(KΩ) Resist.tol (%) Temp.tol(℃)
98
R410a Tropical Rooftop Package Unit 50Hz
29 8.621 8.337 8.055 3.41 3.38 0.77 0.74
30 8.252 7.972 7.695 3.51 3.47 0.80 0.77
31 7.900 7.625 7.353 3.61 3.57 0.83 0.79
32 7.566 7.296 7.029 3.70 3.66 0.85 0.82
33 7.247 6.982 6.721 3.80 3.74 0.88 0.84
34 6.944 6.684 6.428 3.89 3.83 0.91 0.87
35 6.656 6.401 6.150 3.98 3.92 0.93 0.90
36 6.381 6.131 5.886 4.08 4.00 0.96 0.93
37 6.119 5.874 5.634 4.17 4.09 0.98 0.95
38 5.870 5.630 5.395 4.26 4.17 1.01 0.98
39 5.631 5.397 5.167 4.34 4.26 1.03 1.01
40 5.404 5.175 4.951 4.43 4.34 1.06 1.03
41 5.188 4.964 4.745 4.52 4.42 1.09 1.06
42 4.982 4.763 4.549 4.60 4.50 1.12 1.09
43 4.785 4.571 4.362 4.69 4.58 1.14 1.12
44 4.596 4.387 4.183 4.77 4.66 1.17 1.14
45 4.417 4.213 4.014 4.85 4.74 1.19 1.17
46 4.246 4.046 3.851 4.93 4.81 1.22 1.20
47 4.082 3.887 3.697 5.02 4.89 1.25 1.23
48 3.925 3.735 3.550 5.10 4.97 1.28 1.25
49 3.776 3.590 3.409 5.18 5.04 1.30 1.28
50 3.632 3.451 3.274 5.25 5.12 1.33 1.30
51 3.495 3.318 3.146 5.33 5.19 1.35 1.33
52 3.363 3.191 3.023 5.41 5.26 1.41 1.36
53 3.237 3.069 2.905 5.49 5.34 1.43 1.38
54 3.116 2.952 2.793 5.56 5.41 1.46 1.41
55 3.001 2.841 2.685 5.64 5.48 1.48 1.44
56 2.890 2.734 2.582 5.71 5.55 1.51 1.46
57 2.784 2.632 2.484 5.79 5.62 1.54 1.49
58 2.682 2.534 2.390 5.86 5.69 1.56 1.52
59 2.585 2.440 2.299 5.93 5.76 1.59 1.54
60 2.491 2.350 2.213 6.01 5.83 1.62 1.57
61 2.401 2.264 2.130 6.08 5.90 1.64 1.60
62 2.315 2.181 2.051 6.15 5.96 1.67 1.62
63 2.233 2.102 1.975 6.22 6.03 1.70 1.65
64 2.154 2.026 1.903 6.29 6.10 1.72 1.68
65 2.077 1.953 1.833 6.36 6.16 1.75 1.70
66 2.004 1.883 1.766 6.42 6.23 1.77 1.73
67 1.934 1.816 1.702 6.49 6.29 1.80 1.76
68 1.867 1.752 1.641 6.56 6.35 1.83 1.78
69 1.802 1.690 1.582 6.62 6.41 1.85 1.81
70 1.740 1.631 1.525 6.69 6.48 1.88 1.84
71 1.680 1.574 1.471 6.75 6.54 1.91 1.86
72 1.622 1.519 1.419 6.82 6.60 1.93 1.89
73 1.567 1.466 1.369 6.88 6.66 1.96 1.92
74 1.514 1.416 1.321 6.94 6.71 1.98 1.94
75 1.463 1.367 1.275 7.00 6.77 2.01 1.97
99