Energies 14 04823 v3
Energies 14 04823 v3
Energies 14 04823 v3
Article
Efficiency Comparison of DC and AC Coupling Solutions for
Large-Scale PV+BESS Power Plants
Francesco Lo Franco 1 , Antonio Morandi 1, *, Pietro Raboni 2 and Gabriele Grandi 1
Abstract: In large-scale photovoltaic (PV) power plants, the integration of a battery energy storage
system (BESS) permits a more flexible operation, allowing the plant to support grid stability. In
hybrid PV+BESS plants, the storage system can be integrated by using different power conversion
system (PCS) layouts and different charge–discharge strategies. In the AC-coupling layout, the BESS
is connected to the ac-side of the system through an additional inverter. In the DC-coupling layout,
the BESS is connected to the dc-side, with or without a dedicated dc–dc converter, and no additional
inverter is needed. Referring to a 288 MWp PV plant with a 275 MWh BESS, this paper compares the
PCS efficiency between AC- and DC-coupling solutions. The power injected into the grid is obtained
considering providing primary power-frequency regulation services. A charging and discharging
strategy of the BESS is proposed to ensure cyclic battery energy shifting. The power flows in the
different components of the system that are obtained under realistic operating conditions, and total
energy losses and annual average efficiency are calculated accordingly. Finally, results show a higher
efficiency of DC-coupling compared to the AC-coupling layout.
Citation: Lo Franco, F.; Morandi, A.;
Raboni, P.; Grandi, G. Efficiency Keywords: battery energy storage system (BESS); photovoltaic; power conversion system (PCS);
Comparison of DC and AC Coupling renewable energy sources (RES); solar plus storage sizing; grid-connected PV plant
Solutions for Large-Scale PV+BESS
Power Plants. Energies 2021, 14, 4823.
https://doi.org/10.3390/en14164823
1. Introduction
Academic Editors: Woojin Choi and
Grid-connected PV plants are non-dispatchable energy sources that are controlled
Teuvo Suntio
in order to inject the maximum available power into the grid. Due to their operating
characteristics, PV plants cannot usually provide the control and regulation services that
Received: 26 May 2021
Accepted: 2 August 2021
conventional sources can do and, moreover, can impact the voltage and the stability of the
Published: 7 August 2021
electrical system [1–3]. For example, in PV plants with sizes up to hundreds of MW, the
unstable weather can cause deep power dips and high ramp-rate [4]. Therefore, the system
Publisher’s Note: MDPI stays neutral
operator employs power from programmable sources (generally thermal plants using
with regard to jurisdictional claims in
pollutant sources) to control the system’s operation and preserve the grid stability. The
published maps and institutional affil- integration of a battery energy storage system permits a more flexible operation of the PV
iations. plants with a much-reduced impact on safe grid operation [5]. A typical PV+BESS power
plant, in fact, consists of multiple PV arrays, power electronic converters, and storage
units which can contribute to grid stability and reliability through sophisticated grid-
friendly controls [6,7], thus supplementing (or even replacing in the long term) conventional
Copyright: © 2021 by the authors.
generators [8]. In particular, the development of advanced power controls can enable PV
Licensee MDPI, Basel, Switzerland.
to become a provider of a wide range of grid services, including spinning reserves, load
This article is an open access article
following, voltage support, ramping control, frequency response, and variability smoothing.
distributed under the terms and The BESS allows decoupling the PV power from the power that the plant injects into the
conditions of the Creative Commons grid. It is hence possible to modulate the grid power without reducing the generated PV
Attribution (CC BY) license (https:// power, or to keep constant the power injection to the grid even if the PV availability drops.
creativecommons.org/licenses/by/ Possible support functions that a hybrid PV+BESS plant can provide to the grid without
4.0/). involving curtailment of the PV generation are described, among others, in [9–18].
2. The Case Study: A 288 MW PV Plant with 92.2 MW/275.2 MWh Integrated BESS
A 288 MW power PV plant with a 92.2 MW/275.2 MWh battery storage capacity
is introduced in this section as a case study. The general characteristics of the plant are
discussed in the following. The typical size of PV inverters usually employed in large
hybrid PV plants is up to 5 MW. The DC voltage of the inverter is generally in the range
of 900 Vdc –1500 Vdc (PV side), and the output AC voltage is in the range of 400 Vac ÷
690 Vac [30] Large-scale PV plants reach the size of hundreds of MW by using multiple
inverters and PV generator modules. In this reference case study, the low voltage (LV) AC
output of more inverters is connected to a single multi-winding transformer that steps up
the voltage to the medium voltage (MV) level, in the range of 15,000 Vac –20,000 Vac . The
transformer may consist of one single grid-side winding with four secondary windings
connected to the inverters. A containerized solution was used: the PCS container involves
one single multi-winding transformer and four PV inverters. In Figure 1a, the schematic
of the 288 MWp PV plant used as a case study is shown. The plant is made of 80 PCS
containers. Each PCS includes four inverters modules with a 900 kVA rating, connected
to the multi-winding transformer. Both the inverters and the transformer are three-phase.
Different architectures can be considered for integrating the 92.2 MW/275.2 MWh BESS
system in the PV power plant, which is analyzed in detail in the following. However,
no matter the solution chosen, maintaining the modular approach is essential for the
correct design, assembling, operation, and maintenance of the power plant. For this reason,
the total BESS capacity of 92.2 MW/275.2 MWh is subdivided into 320 (4 × 80) battery
modules with 288 kW/860 kWh rating, to be individually coupled with the 900 kW PV
modules via the power converters. The BESS can consist of various battery cell technologies.
Popular battery technologies include Lithium-ion (Li-ion), Lead–Acid (PbA), and Nickel–
Metal Hydride (Ni–MH) [31]. Among these, Li-ion batteries have become the prevailing
technology used in large BESS [32], as the system described in this paper, due to the higher
energy density, the higher round trip efficiency, the longer life span, the fast response time,
and the decrease in cost seen in recent years [33–35].
The schematic of the modularized PV+BESS solution is shown in Figure 1b. In
Figure 1a,b PCCPlant denotes the point of common coupling (PCC) of the total plant, and
PCCCont. [i ] (with i ∈ [1:80]) denotes the PCC of the single PCS container. Similarly, it is
possible to define the PCC of the single PV module (a) or the PCC of the hybrid PV+BESS
module (b). The point of common coupling of the module is denoted with PCC Module [i, j]
2021, 14, 4823 4 of 22
The schematic of the modularized PV+BESS solution is shown in Figure 1b. In Figure 1a,b
𝑃𝐶𝐶
Energies 2021, 14, 4823 denotes the point of common coupling (PCC) of the total plant, and 𝑃𝐶𝐶 . 𝑖
4 of 22
(with 𝑖 ∈ [1:80]) denotes the PCC of the single PCS container. Similarly, it is possible to
define the PCC of the single PV module (a) or the PCC of the hybrid PV+BESS module (b).
The point of common coupling of the module is denoted with 𝑃𝐶𝐶 𝑖, 𝑗 in Figure
in Figure 1a,b, where i refers to the container’s number and j is the module’s number
1a,b, where i refers to the container’s number and j is the module’s number (𝑗 ∈ [1:4]).
(j ∈ [1:4]).
(a)
(b)
Figure 1. (a) A modular
Figure 1.288
(a)MWp PV power
A modular plant made
288 MWp of 80plant
PV power separate
madePCS, each
of 80 including
separate PCS,4 each
PV including 4 PV
inverter modulesinverter
with a 900 kVA rating. (b) Modular integration of the 92.2 MW/275.2 MWh BESS
modules with a 900 kVA rating. (b) Modular integration of the 92.2 MW/275.2 MWh BESS
into the 288 MW PV plant.
into the 288 MW PV plant.
(a) (b)
(c)
Figure 2.
Figure 2. Possible
Possible coupling
coupling architecture
architecturefor
forPV
PVand
andBESS
BESSmodules:
modules:(a)
(a)AC-coupling;
AC-coupling;(b)
(b)DC-coupling/BESS-side;
DC-coupling/BESS-side; (c)
(c) DC-
DC-
coupling/PV-side.
coupling/PV-side.
Table1.1. Data
Table Data of
of the
the case
casestudy
studyof
ofPV+BESS
PV+BESS plant
plant components
components in
in Figure
Figure 2.
2.
SingleModule
Single Module Total Plant(320
Total Plant (320Modules)
Modules)
Layout AC DC–BESS DC–PV AC DC–BESS DC–PV
Layout AC DC–BESS DC–PV AC DC–BESS DC–PV
PV [MW] 0.900 0.900 0.900 288 288 288
PV [MW] 0.900 0.900 0.900 288 288 288
BESS (energy)
BESS (energy) [MWh]
[MWh] 0.860
0.860 0.860
0.860 0.860
0.860 275.2
275.2 275.2
275.2 275.2
275.2
BESS
BESS (power)
(power) [MW]
[MW] 0.288
0.288 0.288
0.288 0.288
0.288 92.2
92.2 92.2
92.2 92.2
92.2
transf.
transf. [MVA]
[MVA] 1.200
1.200 1.200
1.200 1.200
1.200 384
384 384
384 384
384
BESS-transf.
BESS-transf. [MVA]
[MVA] 0.400
0.400 -- -- 128
128 -- --
inverter [MVA] 0.900 0.900 0.900 288 288 288
inverter [MVA] 0.900 0.900 0.900 288 288 288
BESS-inverter [MVA] 0.288 - - 92.2 - -
BESS-inverter
dc–dc conv. [MVA]
[MW] 0.288
- -
0.288 -
0.900 92.2
- 92.2- -
288
dc–dc conv. [MW] - 0.288 0.900 - 92.2 288
3.1. AC-Coupling
3.1. AC-Coupling
The AC-coupling architecture employs two distinct inverters for connecting a PV and
a BESSThemodule,
AC-coupling architecture
as is shown employs
in Figure two distinct
2a. Both inverters
inverters for connecting
are connected to the aPCCPV and
Cont.
a BESS module, as is shown in Figure 2a. Both inverters are connected
using two winding (per phase) transformers. The PV inverter sets the MPPT operation and. to the 𝑃𝐶𝐶
using two
conveys thewinding
power to(perthe phase)
ac-side transformers.
unidirectionally. TheThe
PVBESS
inverter sets the
converter MPPTthe
controls operation
battery
power flows operating in the inverter or the rectifier mode. It is worth noting that duethe
and conveys the power to the ac-side unidirectionally. The BESS converter controls to
battery
the power
use of flows operating
two separate inverter in the inverter
systems, or the rectifier
this configuration mode.
allows It isaworth
both notingBESS
distributed that
due to the
system, whichuse can
of two separate
be used inverter
for the systems,
modular this configuration
configuration of the wholeallows
plant,both a distrib-
as discussed
uted
in thisBESS
paper,system,
and awhich can be used
concentrated for where
system the modular configuration
the overall BESS power of the whole plant,
is conveyed in
as discussed
unique point,in thiscan
that paper,
evenandbe fara concentrated systemFor
from the PV plant. where
thesethe overallthe
reasons, BESS
BESSpower
in theis
conveyed in unique point, that can even be far from the PV plant.
AC-coupling could be designed with different modularity, such as 80 PCS containers ofFor these reasons, the
1.15 MW/3.44 MWh each.
3.2. DC-Coupling/BESS-Side
The DC coupling architecture with the dc–dc converter on the battery side (DC-
coupling/BESS-side in brief) only employs one inverter per module, as is shown in
Figure 2b. A dc–dc converter connects the battery module to the dc bus. The inverter
Energies 2021, 14, 4823 6 of 22
controls the power conveyed to the converter’s PCC (ac-side), regulating the current from
the bus-dc. The dc–dc converter manages the bus-dc voltage to allow the PV to work
in MPPT conditions, and it must allow the bidirectional power flow from BESS to PCC
(battery discharging) and from PCC to BESS (battery charging). This architecture only
applies to distributed storage systems because the BESS module must be connected to the
dc-side of each PV inverter.
3.3. DC-Coupling/PV-Side
The DC coupling architecture with the dc–dc converter on the PV side (DC-coupling/
PV-side in brief) is shown in Figure 2c. It only employs one inverter connecting the storage
module to the module’s PCC. The PV strings are connected to the dc-link through a dc–dc
converter. The dc–dc converter manages the PV voltage to work in MPPT conditions;
meanwhile, the inverter manages the power supplied to the PCC and, consequently, the
battery power. This architecture only applies to distributed storage systems because the
BESS module must be connected to the dc side of each inverter.
Figure
Figure 3.3.PV
PVfacility
facilitydroop
droopcharacteristic
characteristic
forfor PFR
PFR inin Puerto
Puerto Rico
Rico (PREPA).
(PREPA).
The
The considered
considered daily
daily profile
profile of frequency
of frequency with
with a 1-min
a 1-min resolution
resolution is shown
is shown in Figure
in Figure 4a.
4a. The percentage occurrence of different frequency values obtained from
The percentage occurrence of different frequency values obtained from the daily data the daily data
ofof
Figure4a4aisisshown
Figure shownininFigure
Figure 4b.InInboth
4b. boththese
thesegraphs,
graphs,the
thekey
keyfrequency
frequencyvalues
valuesofofthe
thedroop
droop
characteristic are pointed out: the nominal frequency ( f n ); the deadband limits ( f 1 and f 2 );
the frequency thresholds where the regulating power reaches the bounds ( f 3 and f 4 ).
Figure 5 shows an example of the PFR power profile of the plant during about 2 h,
obtained according to the PFR droop characteristic of Figure 3 and the frequency data of
Figure 4a. Referring to the left-axis of Figure 5a, the black line is the available PV power
PPV . The black dotted line represents the base power, which is 90% of the available PPV
power. Based on the frequency excursion, the PCC power may deviate from the base value
providing up- and down-reserve, thus creating the output power profile reported with
the blue line in Figure 5a (named PPCC ). The grey line in Figure 5a depicts the minimum
admissible value of PPCC that is equal to 80% of PPV .
Energies 2021, 14, 4823 8 of 22
Figure 5 shows an example of the PFR power profile of the plant during about 2 h,
obtained according to the PFR droop characteristic of Figure 3 and the frequency data of
Figure 4a. Referring to the left-axis of Figure 5a, the black line is the available PV power
𝑃𝑃𝑃𝑃𝑃𝑃 . The black dotted line represents the base power, which is 90% of the available 𝑃𝑃𝑃𝑃𝑃𝑃
power. Based on the frequency excursion, the PCC power may deviate from the base value
providing up- and down-reserve, thus creating the output power profile reported with
the blue line in Figure 5a (named 𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃 ). The grey line in Figure 5a depicts the minimum
admissible value of 𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃 that is equal to 80% of 𝑃𝑃𝑃𝑃𝑃𝑃 .
Since the probability distribution of frequency (see Figure 4b) is practically symmet-
rical with respect to the nominal value, the average output power profile of the plant is
coincident with the base power of 90% of 𝑃𝑃𝑃𝑃𝑃𝑃 , as confirmed in Figure 5. This means that
about 10% of the energy generated is not transferred to the grid. This surplus energy is
stored in the battery. As a result, the BESS is charged during daytime hours. Furthermore,
since
(a) according to Figure 4b, the probability of occurrence (b) of an under-frequency event
with 𝑓𝑓 < 𝑓𝑓4 is very low; the PCC instant power is always lower than 100% of the PV
Figure
Figure5.5.Result
Resultof
ofPFR
PFRon
onthe plant’s
power.
the plant’s power
This flows.
implies
power (a)
(a)on
flows.that, the
theleft
leftaxis:
according
on toblack—100%
axis: Equation
black—100% (1), 𝑃𝑃𝑉
ofofa ; dot black—𝑃
Pcontinuous
PV ; dot black—P power (90%
flowofof
base (90%
𝑏𝑎𝑠𝑒 𝑃P𝑃𝑉
always );
PV ); oc-
blue—𝑃 ; grey—80% of 𝑃
blue—PPCC ; grey—80% of Pcurs ; on the right axis: red—BESS power. (b) on the left axis: grid frequency with an over- (blue
𝑃𝐶𝐶 𝑃𝑉
PV ; ontoward
the righttheaxis:
battery
red—BESSduringpower.
day hours. Theleft
(b) on the red linegrid
axis: (right axis) ofwith
frequency Figure 5a shows
an over- (blue the
area) and under-frequency (light-blue area) occurrences. On the right axis, the battery power profile (red) and the battery
area) and under-frequency resulting
(light-bluebattery power flow. Figure 5b shows the role of the energy storage during the
area) occurrences. On the right axis, the battery power profile (red) and the battery
“base” power (black). The red area depicts the provided upward energy reserve, and the yellow area depicts the
daytime
“base” power (black). The red
downward reserve. PFR
area depicts operation
the provided ofupward
the plant. Thereserve,
energy base power
and thesetsyellowa battery power
area depicts thevalue
downwardthat does
reserve. not depend on the grid frequency and is given by 𝑃𝑃𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏 − 𝑃𝑃𝑃𝑃𝑃𝑃 (10% of PV availability,
black
4.2. line). In case
Discharging of under-frequency
Strategy of the BESS occurrence, the power absorbed by the storage sys-
Since the probability distribution of frequency (see Figure 4b) is practically symmet-
tem (red line) decreases. On the other hand, in over-frequency conditions, the charging
ricalAs with previously
respect to shown,
the nominal due value,
to thethe fact that the
average output lowerpower bound f4 of
profile the plant
of the droop is
battery power increase according to the PFR droop curve. The PFR operation could also
characteristics,
coincident with corresponding
the base power to 100%
of 90% ofofPVPPVpower conveyed in
, as confirmed to the grid,
Figure 5.isThis
verymeans
seldomly that
be obtained without a BESS by reducing and modulating the PV generation but to the
reached,
about 10% theofBESS is charged
the energy duringisdaytime
generated hours. Atodischarge
not transferred the grid. strategy
This surplus mustenergy
then beis
expense of MPPT operation. However, by introducing a storage system, the PV+BESS
planned for allowing the battery to operate in cyclic conditions.
stored in the battery. As a result, the BESS is charged during daytime hours. Furthermore, In this paper, we assume
plant is capable of providing both up- and down-reserve without modulating the PV
that
sinceinaccording
the evening,to Figureand 4b,in the
particular
probabilityduring sunset hours,
of occurrence of an the batteries startevent
under-frequency the
power, maximizing the exploitation of the PV source (MPPT operation is assured).
discharging
with f < f 4 is process
very low; to deliver
the PCCthe stored
instant energy
power to thelower
is always grid. than
This 100%
process is generally
of the PV power.
To exploit the BESS capacity, it is necessary to ensure cyclic working conditions, in
referred
This implies to asthat,
energy shiftingto(ES).
according Equation (1), a continuous power flow always occurs toward
which the batteries must be completely charged and discharged during a 24-h cycle. A
The scheduling
the battery during day of the power
hours. The that
redtheline
BESS should
(right axis)supply
of Figure during the energy
5a shows shifting
the resulting
discharge strategy for the battery must then be planned after daily hours, which restores
depends
battery power on different factors,
flow. Figure such as
5b shows thethe
roleBESS
of the and PV size,
energy storagetheduring
PCC load profile, PFR
the daytime the
the initial SOC value at the beginning of the next day. This discharge strategy, which is
operation of the plant. The base power sets a battery power
seasonal and daily irradiance, and, finally, the type of services that the plant provides. In value that does not depend
obtained
on the systems by frequency
grid assuming that the battery provides
Pbase −ofPPV ramp rate support during blacksunsetline).
hours,
power where aand is given
substantial by
amount (10%
solar of PV
source isavailability,
installed, the amount of In
iscase
discussed
ofthat in the next subsection.
under-frequency occurrence, the power absorbed
power must be generated from programmable sourcesby the storage
(mainly thermal system
power(red line)
plants)
decreases.
rapidly On theduring
increases other hand,
sunsetinand over-frequency
reaches the peak conditions, the charging hours.
in the mid-evening batteryAs power
it is
increase
shown in according to thethe
[39], the higher PFR droop curve.
penetration The power,
of solar PFR operationthe higher could also be
the ramp rateobtained
of the
without a BESSpower
programmable by reducing
duringand modulating
sunset hours. Thisthe PV generation (which
phenomenon but to the expense to
is referred of as
MPPT
the
operation. However, by introducing a storage system, the
“duck curve” due to the power profile resembling a duck’s silhouette) is typical in electric PV+BESS plant is capable of
systems with high penetration of RES. The excessive ramp rate of thermal power requires
the inefficient operation of thermal power plants at reduced power and is mitigated by
operating the PV+BESS power plant in energy shifting mode, that is, discharging the
battery during evening hours.
To assure appropriate operation, lifetime, and safety, a minimum and maximum
Energies 2021, 14, 4823 9 of 22
providing both up- and down-reserve without modulating the PV power, maximizing the
exploitation of the PV source (MPPT operation is assured).
To exploit the BESS capacity, it is necessary to ensure cyclic working conditions, in
which the batteries must be completely charged and discharged during a 24-h cycle. A
discharge strategy for the battery must then be planned after daily hours, which restores
the initial SOC value at the beginning of the next day. This discharge strategy, which is
obtained by assuming that the battery provides ramp rate support during sunset hours, is
discussed in the next subsection.
SOC (24) ∼
= SOC (0) ∼
= SOCmin (2)
where SOC (24) is the SOC at time t = 24 : 00 and SOC (0) is the SOC value 24 h before,
that is, at t = 0 : 00. Since the allowed SOC range is between 20% and 90%, the maximum
energy ( EB ), which could be stored in the BESS and supplied to the grid during evening
hours, is 70% of EBmax (EB = 192 MWh). The trapezoidal power profile shown in Figure 6a
is assumed for the scheduled BESS power during the evening energy shifting (discharge).
In particular, constant power is scheduled from 19:00 to 20:00, while downward power
rate is applied after 20:00 and the same upward ramp rate is applied to start around 18:00
(t ESstart ) for reaching the planned power, thus generating the trapezoidal profile shown.
The area under the BESS power curve represents the energy EB(supplied) supplied to the
grid. It is worth pointing out that the curve of Figure 6a holds under the assumption that
SOC (t ESstart ) = SOCmax . In case that SOC (t ESstart ) < SOCmax the scheduled battery power
is scaled by a factor k ∈ [0 : 1] defined as:
(a) (b)
(c) (d)
Figure6.6.Reference
Figure Referencepower
powerflows:
flows:(a)
(a)PV
PVpower
powerprofile
profile(black)
(black)and
andbattery
batteryscheduled
scheduledpower
powerfor
forenergy
energyshifting
shiftingoperation
operation
(red) with k = 1; (b) PV power and PCC power demand (red) obtained by PFR and ES operating; (c) Battery power flow,
(red) with k = 1; (b) PV power and PCC power demand (red) obtained by PFR and ES operating; (c) Battery power flow,
daytime charging (negative power) and evening discharging (positive power); (d) battery SOC profile.
daytime charging (negative power) and evening discharging (positive power); (d) battery SOC profile.
Figure 6b shows the power flows of the hybrid plant during three consecutive spring
days with different irradiance obtained according to the criteria depicted above. The
shifting effect of the delivered power is evident from the plots of Figure 6c,d, showing the
battery power and SOC profiles, respectively. Finally, the SOC’s plot (Figure 6d) confirms
the cyclic operation of the battery.
Figure
Figure 7.
7. Power
Power efficiency
efficiency of the PCS
of the PCS components:
components: Inverters and dc–dc
Inverters and dc–dc converters.
converters. The efficiencies
The efficiencies
are functions of the normalized rating power.
are functions of the normalized rating power.
The intrinsic efficiency of the battery storage (i.e., at the cell terminals) is not considered
in this calculation. Of course, this leads to an overestimation of the overall system’s
efficiency. However, since the power flow of batteries is the same for all the considered
layouts, this does not affect the results of the comparison in terms of energy losses that
occur in the PCSs. However, for more details, Appendix A provides efficiency comparisons
of the three layouts, including the round-trip battery losses.
During the daily operation of the PV+BESS plant, different power flows can occur
between PV, grid, and BESS, regardless of the layout of the PCS. However, as it can be
deduced from Figure 2, the number of conversion stages involved in the power flows
depend on the PCS’s layout. For example, when power flows from PV to PCC, the AC-
coupling and the DC-coupling/BESS side layouts involve two conversion stages (inverter
and transformer), whereas the DC-coupling/PV-side involves three conversion stages
(dc–dc converter, inverter, and transformer) and is less efficient. On the other hand,
Energies 2021, 14, 4823 12 of 22
when power flows from BESS to PCC, the less efficient layout is the DC-coupling/BESS
side coupling because it presents one conversion stage more than the others. Similarly,
different conversion stage number and efficiency is obtained for the three layouts when
the power flow from PV to BESS is considered (in this case the worst-performing layout
is the AC-coupling since it involves two converters and two transformers). The count of
the conversion stages and the efficiency for each layout, and the different power flows are
resumed in Table 2.
Table 2. Power efficiency and conversion stages based on power flow directions, where ηinvPV and ηinvB are the efficiencies
of the PV and BESS inverter, ηTPV and ηTB are the efficiencies of the PV and BESS transformers for the AC coupling layout.
On the other hand, ηinv is the inverter efficiency, ηdcdc is the dc–dc converter efficiency and ηT is the transformer efficiency
for both DC-coupling layouts.
The daily energy loss EL for each layout can be calculated based on the power losses
PL (t) during plant’s operation as follows.
Z 24
EL = PL (t)dt (5)
0
where PL is given by the difference between the input and output power of the conversion
stage. The input and output power of each conversion stage is shown in Figure 8.
For the three layouts. Based on the symbols of Figure 8a, the power flows and energy
losses of the AC-coupling layout are expressed by:
Z 24 Z 24
EL = ( PPV − PPVac )dt + | PB − PBac |dt (6)
0 0
(
(ηinvB ηTB ) · PB , discharging
PBac = 1 (7)
ηinvB ηTB · PB , charging
Table 2. Power efficiency and conversion stages based on power flow directions, where 𝜂𝜂𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖 and
𝜂𝜂𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖 are the efficiencies of the PV and BESS inverter, 𝜂𝜂 𝑇𝑇𝑇𝑇𝑇𝑇 and 𝜂𝜂 𝑇𝑇𝑇𝑇 are the efficiencies of the PV
and BESS transformers for the AC coupling layout. On the other hand, 𝜂𝜂𝑖𝑖𝑖𝑖𝑖𝑖 is the inverter effi-
ciency, 𝜂𝜂𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 is the dc–dc converter efficiency and 𝜂𝜂 𝑇𝑇 is the transformer efficiency for both DC-
Energies 2021, 14, 4823 13 of 22
coupling layouts.
(a)
(b)
(c)
Figure 8. PowerFigure
flows8.that involve
Power flowsthe
thatthree different
involve layouts:
the three (a) layouts:
different AC coupling;
(a) AC(b) DC-cou-
coupling; (b) DC-coupling/
pling/BESS-side; (c) DC-coupling/PV-side.
BESS-side; (c) DC-coupling/PV-side.
Figure
Figure9.9.Delivered
Deliveredgrid
gridpower
powerof
ofthe
thethree
threedifferent
differentlayouts
layoutsduring
duringone
one typical
typical summer
summer day.
day.
AAsubstantial
substantial difference indeedexists
difference indeed existsininterms
termsofofloss
loss and
and overall
overall efficiency,
efficiency, which
which can
can be appreciated
be appreciated by aby a more
more careful
careful analysis
analysis of theofresults.
the results. The battery
The battery powerpower of eachoflayout
each
layout
duringduring the simulated
the simulated 24 h is24 h is shown
shown in Figurein Figure
10a. The 10a. The corresponding
corresponding profile profile
of SOCof is
SOC
shown is shown in 10b.
in Figure Figure
The10b. Thepower
overall overallloss
power
(MW),loss (MW),
i.e., i.e.,occurring
the loss the loss inoccurring in all
all conversion
conversion stages,inisFigure
stages, is shown shown10c.
in Figure 10c. The corresponding
The corresponding energy loss energy
(MWh) lossis (MWh) is finally
finally shown in
shown in Figure 10d.
Figure 10d.
ItItcan
canbe
be seen
seen from
from Figure
Figure 10c
10c that during the
that during the daytime,
daytime, thethe DC-coupling/BESS-side
DC-coupling/BESS-side
layout
layoutshows
showsless
lessloss
losscompared
comparedto tothe
theAC-coupling
AC-couplingdue dueto tothe
thereduced
reducedconversion
conversionstagesstages
(1 versus 4) involving the power flow from PV to the battery. As a result, a higher SOC,
corresponding to higher stored energy, is reached with the DC–BESS layout during daytime
(see Figure 10b). On the other hand, during the evening hours, the energy only flows from
the battery to the grid, and the DC-coupling/BESS-side presents the highest losses due to
one more conversion stage. However, avoided losses of the AC-coupling during discharge
(two versus three converter stages) are less than increased losses during charge (four
versus one converter stages); hence lower overall energy losses are obtained with the
DC-coupling/BESS during the day cycle as it can be seen in Figure 10d.
The worst performing layout in terms of losses is the DC-coupling/PV-side, as can
be seen from the plots in Figure 11. This layout is, along with the AC coupling, the
most efficient during energy shifting in the evening hours (battery discharge) since it only
presents two conversion stages. However, the amount of energy involved in the energy
shifting is only about 10% of the daily PV energy. The main of the energy, which is 90% of
the PV energy, follow the PV-to-grid path and involves three conversion stage (compared
to two conversion stage only for the other two layouts), thus production the highest overall
losses shown in Figure 10b,c.
efficient during energy shifting in the evening hours (battery discharge) since it only pre-
sents two conversion stages. However, the amount of energy involved in the energy shift-
ing is only about 10% of the daily PV energy. The main of the energy, which is 90% of the
PV energy, follow the PV-to-grid path and involves three conversion stage (compared to
Energies 2021, 14, 4823 two conversion stage only for the other two layouts), thus production the highest overall
15 of 22
(a) (b)
(c) (d)
Figure 10.
Figure 10. Typical
Typicalsummer
summerday
daysimulation
simulation result:
result: (a)(a) battery
battery power
power profiles,
profiles, (b) (b) battery
battery SOC;SOC; (c) overall
(c) overall system
system power
power loss,
loss, (d) overall system energy loss.
(d) overall system energy loss.
The PV
The PV power
power data
data used
usedininthis
thisstudy
studyare
areobtained
obtainedbybya aone-year
one-yearmeasurement
measurement with
with a
a one-minuteresolution
one-minute resolutionfrom
froma apower
powerplant
plantlocated
locatedininCentral
CentralAmerica
AmericaThe Theimpact
impact ofof the
the
different daily
different daily and
and seasonal
seasonal irradiance
irradiance conditions
conditions on
on the
the system’s
system’s loss,
loss, and
and efficiency
efficiency isis
evaluated in the following. In Figure 11, the grid power (Figure 11a,b) and
evaluated in the following. In Figure 11, the grid power (Figure 11a,b) and the battery SOCthe battery
SOC (Figure
(Figure 11c,d)11c,d)
of theofthree
the three different
different layouts
layouts during
during one one
week week in two
in two different
different periods
periods of
of the
the year
year areare shown.
shown. TheThe figure
figure confirms
confirms the cyclic
the cyclic operation
operation of theofbattery
the battery
duringduring all
all days,
regardless of the available PV power. The energy losses of the three different layouts are
also shown in Figure 11e,f.
It can be seen that the DC-coupling/BESS-side remains the best performing layout in
terms of loss and efficiency in all irradiance conditions. In particular, the total energy loss
of the DC-coupling/BESS-side in a summer week is about 470 MWh, while 23 MWh (4.9%)
and 110 MWh (23.4%) more losses are obtained for the AC-coupling and DC-coupling/PV-
side layouts, respectively. The winter week simulation follows a similar trend, with
310 MWh total energy loss for the DC-coupling/BESS-side, 14 MWh (4.5%) more losses for
the AC-coupling, and 72 MWh (22.2%) more losses for DC-coupling/PV-side.
To allow a quantitative comparison of the performance of the three systems in all
operating conditions, the values (MWh) of the PV energy, PCC energy, BESS energy,
and total energy loss are reported in Table 3 for three days with different irradiance
conditions: the low-irradiance condition (in which the PV produces 779.8 MWh in total), the
mean-irradiance condition (with the PV producing 1957.9 MWh), and the high-irradiance
condition (with the PV producing 2398.1 MWh).
It can be seen that the DC-coupling/BESS-side remains the best performing layout in
terms of loss and efficiency in all irradiance conditions. In particular, the total energy loss
of the DC-coupling/BESS-side in a summer week is about 470 MWh, while 23 MWh (4.9%)
and 110 MWh (23.4%) more losses are obtained for the AC-coupling and DC-coupling/PV-
Energies 2021, 14, 4823 side layouts, respectively. The winter week simulation follows a similar trend, with 310
16 of 22
MWh total energy loss for the DC-coupling/BESS-side, 14 MWh (4.5%) more losses for the
AC-coupling, and 72 MWh (22.2%) more losses for DC-coupling/PV-side.
(a) (b)
(c) (d)
(e) (f)
Figure 11. Power and SOC profiles for the three different layouts during typical summer and winter weeks. (a) grid power
Figure 11. Power and SOC profiles for the three different layouts during typical summer and winter weeks. (a) grid power
during summer week, (b) grid power during winter week, (c) battery SOC during summer week, (d) battery SOC during
during summer week, (b) grid power during winter week, (c) battery SOC during summer week, (d) battery SOC during
winter week, (e) total energy loss during summer week, (f) total energy loss during a winter week.
winter week, (e) total energy loss during summer week, (f) total energy loss during a winter week.
Finally, the annual energy loss and efficiency obtained by simulating an operating
time of one year are shown in Figure 12a,b, respectively. The one-year analysis confirms
the trend reported by the one-day and weekly simulations. The most efficient layout
is the DC-coupling/BESS-side, which presents 21.48 GWh of losses per year and has
an average annual efficiency of 97.02%. The losses of the AC-coupling are 22.67 GWh
per year (+1190 MWh), corresponding to an annual average efficiency of 96.86%. The
worst performing layout is the DC-coupling/PV-side with 26.26 GWh losses per year
(+4780 MWh) and annual average efficiency of 96.34%.
Table 3. Energy values (MWh) refer to the system’s elements. The results consider three different
initial PV conditions: low, mean, and high irradiance.
Low-Irradiance Mean-Irradiance High-Irradiance
AC DC/BESS DC/PV AC DC/BESS DC/PV AC DC/BESS DC/PV
𝐸𝐸𝑃𝑃𝑃𝑃 779.8 1957.9 2398.1
Energies 2021, 14, 4823 17 of 22
𝐸𝐸𝑃𝑃𝑃𝑃𝑃𝑃 753.6 754.9 747.6 1894.2 1897.4 1884.3 2312.0 2316.5 2300.5
Δ𝐸𝐸𝐵𝐵 −1.6 −0.9 −1.2 −2.2 −1.5 −1.8 −12.5 −11.4 −10.8
𝐸𝐸𝐿𝐿 24.5 23.9 31.01 61.5 58.9 71.7 73.6 79.1 86.7
η 96.8% 96.9% 96.0% 96.8% 97.0% 96.3% 96.9% 97.1% 96.4%
Table 3. Energy values (MWh) refer to the system’s elements. The results consider three different initial PV conditions: low,
mean, and high irradiance.
Finally, the annual energy loss and efficiency obtained by simulating an operating
Low-Irradianceof one year are shownMean-Irradiance
time in Figure 12a,b, respectively. The one-year analysis confirms
High-Irradiance
the trend reported by the one-day and weekly simulations. The most efficient layout is the
AC DC/BESS DC/PV AC DC/BESS DC/PV AC DC/BESS DC/PV
DC-coupling/BESS-side, which presents 21.48 GWh of losses per year and has an aver-
EPV 779.8age annual efficiency of 97.02%. The losses of the AC-coupling are2398.1
1957.9 22.67 GWh per year
EPCC 753.6 754.9 747.6 1894.2 1897.4 1884.3 2312.0 2316.5 2300.5
(+1190 MWh), corresponding to an annual average efficiency of 96.86%. The worst per-
∆EB −1.6 −0.9 −1.2 −2.2 −1.5 −1.8 −12.5 −11.4 −10.8
EL 24.5 23.9forming 31.01
layout is the
61.5DC-coupling/PV-side
58.9 with 26.2673.6
71.7 GWh losses
79.1per year86.7
(+4780
η 96.8% 96.9%MWh) and annual average
96.0% 96.8% efficiency
97.0% of 96.34%.
96.3% 96.9% 97.1% 96.4%
(a) (b)
Figure12.
Figure 12.Comparison
Comparisonofoftotal
totalenergy
energylosses
lossesininone
oneyear
year(a)
(a)and
andannual
annualefficiency
efficiency(b)
(b)for
forthe
thethree
threedifferent
differentlayouts.
layouts.
Aspointed
As pointedoutoutininthetheprevious
previousdiscussion,
discussion,thetheefficiency
efficiencyofofthethelayouts
layoutsisisaffected
affectedby by
theamount
the amountof of energy
energy involving
involving the the BESS
BESScompared
comparedtotothe theavailable
availablePV PVenergy.
energy.Below,
Below, an
anefficiency
efficiencycomparison
comparison of of
thethe
three
threelayouts
layoutsis is
carried
carriedout, considering
out, considering different ratios
different be-
ratios
tween the
between theBESS
BESSenergy
energyand andPV PVenergy.
energy.InInparticular,
particular,thetheprevious
previousone-year
one-yearsimulation
simulationis
isrun,
run,considering
consideringthe thesame
samebattery
battery capacity
capacity of
of 275 MWh, for
275 MWh, for different
different values
valuesof ofthe
thePVPV
plantrating
plant rating(MWp),
(MWp),and andefficiency
efficiencyisiscalculated
calculatedasasa afunction
functionofofthe the BESS/PVratio,
BESS/PV ratio,which
which
isisdefined
definedasasthethepercentage
percentageamount amountofofdaily
dailyenergy
energyoperated
operatedby bythe
thebattery
battery(70%
(70%ofofthe
the
nominalcapacity)
nominal capacity) andandthethe daily
daily PV generated
PV generated energy.
energy. The same
The same irradiance
irradiance conditions,
conditions, same
same frequency
frequency profile, profile, same deadband
same deadband (± 0.012
(±0.012 Hz), Hz), and
and same same thresholds
frequency frequency (thresholds
±0.3 Hz)
(±0.3 Hz) are considered for calculating the PCC power according to the PFR method in
are considered for calculating the PCC power according to the PFR method described de-
scribed4.1.
Section in Section
The same 4.1.bounds
The same bounds
of the of theSOC
allowable allowable
intervalSOC(20% interval (20%are
and 90%) and 90%)
also are
used.
Onalso
theused.
otherOn the other
hand, the drop hand, thePFR
of the dropisof the PFRbased
changed is changed
on the based on thePV
considered considered
plant ratingPV
plant rating
(MWp) (MWp) that
for ensuring for ensuring
the allowed thatstorage
the allowed
capacitystorage
of thecapacity
battery of the battery
is fully is fully
exploited in
all considered cases. In other words, the higher the battery capacity with respect to the
average daily PV production (the higher BESS/PV ratio), the higher the regulating power
(in the percentage of the PV power) that the plant can provide.
The assumed settings of the PFR in all the considered cases are resumed in Table 4.
Table 4 also includes the reference case discussed above (275 MWh/288 MWp). It is
noteworthy that the size considered for the PCSs is scaled according to the PV power, so to
leave the efficiency of each conversion system unchanged. The average annual efficiency
obtained for the different BESS/PV ratios of Table 4 is shown in Figure 13. The results
show that under low BESS/PV ratios, the difference in terms of total efficiency between
the AC-coupling and the DC-coupling/BESS-side decreases (while their overall efficiency
slightly increases). These two layouts approximately present the same losses and efficiency
value if BESS/PV ≤ 5%. The gap of efficiency of the AC-coupling layout with respect to
the DC-coupling/BESS-side constantly increases with increasing the BESS/PV ratio. For
the BESS/PV ratios of around 20%, both DC-coupling layouts present higher efficiency
than AC-coupling (the latter becomes even less efficient than the DC-coupling/PV-side).
the AC-coupling and the DC-coupling/BESS-side decreases (while their overall efficiency
slightly increases). These two layouts approximately present the same losses and effi-
ciency value if BESS/PV ≤ 5%. The gap of efficiency of the AC-coupling layout with respect
to the DC-coupling/BESS-side constantly increases with increasing the BESS/PV ratio. For
Energies 2021, 14, 4823 the BESS/PV ratios of around 20%, both DC-coupling layouts present higher efficiency
18 of 22
than AC-coupling (the latter becomes even less efficient than the DC-coupling/PV-side).
Table 4. The setting of the primary frequency reserve operation for different BESS/PV ratios. In all
Table 4. The setting of the primary frequency reserve operation for different BESS/PV ratios. In all
cases, the same energy capacity (275 MWh of nominal capacity) is considered while the PV rating
cases, the same energy capacity (275 MWh of nominal capacity) is considered while the PV rating
changes.
changes.
PV Rating PV Energy BESS/PV PFR 𝑷𝑷𝒃𝒃𝒃𝒃𝒃𝒃𝒃𝒃 PFR Reserve
[MWp]
PV Rating [MWh/Day]
PV Energy [%]
BESS/PV [%
PFRofPbase
𝑷𝑷𝑷𝑷𝑷𝑷 ] [% Reserve
PFR of 𝑷𝑷𝑷𝑷𝑷𝑷 ]
[MWp] [MWh/Day] [%] [% of PPV ] [% of PPV ]
550 3916 5 95 ±5
550
288 3916
1958 5
9.8 95
90 ± 5
±10
288 1958 9.8 90 ±10
275
275 1869
1869 10
10 90
90 ±±10
10
183
183 1305
1305 15.3
15.3 85
85 ±±15
15
137
137 979
979 20.4
20.4 80
80 ±±20
20
Figure13.
Figure 13.Layout
Layoutefficiency
efficiencyas
asaafunction
functionof
ofthe
theBESS/PV
BESS/PV daily
daily energy
energy ratio.
ratio.
7.7.Conclusions
Conclusions
Theefficiency
The efficiencycomparison
comparison of of three
three different
different layouts
layouts of power
of power conversion
conversion systems
systems that
that can be used in large PV+BESS power plants providing primary frequency reserve and
can be used in large PV+BESS power plants providing primary frequency reserve and
energyshifting
energy shiftingservice
servicetotothe
thegrid
gridwaswascarried
carriedout.
out.TheTheproposed
proposedmethod
methodcan canbe
beapplied
applied
toPCS
to PCSwith
withdifferent
differentsizes,
sizes,power
powerratings,
ratings,and
andcomponents’
components’numbers.
numbers.AC-coupling
AC-couplingand and
DC-couplinglayouts
DC-coupling layoutswere
wereinvestigated,
investigated,and andaautility-scale
utility-scaleplant
plantwith
with288
288MWpMWpPV PVpower
power
and92.2
and 92.2MW/275.2
MW/275.2 MWh MWh of of total
total battery
battery capacity
capacity was
was considered
considered as
as aacase
casestudy.
study.The
The
power flows in the different components of the system were calculated underrealistic
power flows in the different components of the system were calculated under realistic
operatingconditions
operating conditionsand andtotal
totalenergy
energylosses,
losses,and
andannual
annualaverage
averageefficiency
efficiencywaswascalculated
calculated
accordingly. It was found that under the same input–output condition (irradiance,PFR,
accordingly. It was found that under the same input–output condition (irradiance, PFR,
and dispatching settings), the best performing PCS layout is DC-coupling with dc–dc
converter at the battery side, presenting an annual average efficiency of 97.02%, followed
by the AC-coupling presenting annual average efficiency of 96.86%. The worst performing
layout is the DC-coupling with dc–dc converter at the PV-side, with an annual average
efficiency of 96.34%. The different performances were related to the different number of
conversion stages involving the energy flow from PV to battery during PFR service in day
hours and from battery to grid during energy shifting in evening hours. It was also shown
that by increasing the storage capacity of the battery with respect to average daily PV
production, the losses of the AC coupling layout increase, and the advantage of adopting
the DC-coupling with dc–dc converter at the battery side becomes even greater.
Author Contributions: Conceptualization, F.L.F., A.M., P.R. and G.G.; methodology, F.L.F. and A.M.;
software, F.L.F.; validation, F.L.F., A.M., P.R. and G.G.; formal analysis, F.L.F., A.M., P.R. and G.G.;
investigation, F.L.F.; data curation, F.L.F., A.M., P.R. and G.G.; writing—original draft preparation,
F.L.F. and A.M.; writing—review and editing, F.L.F., A.M., P.R. and G.G.; visualization, F.L.F., A.M.
and P.R.; supervision, A.M., P.R. and G.G. All authors have read and agreed to the published version
of the manuscript.
Energies 2021, 14, 4823 19 of 22
Funding: This work was supported by the project ENERGYNIUS (ENERGY Networks Integration
for Urban Systems), funded by POR-FESR Region Emilia-Romagna (Italy) 2014–2020.
Data Availability Statement: The original contributions presented in the study are included in the
article material, further inquiries can be directed to the corresponding author.
Conflicts of Interest: The authors declare no conflict of interest.
Appendix A
The purpose of this work was to analyze and compare the losses that involve three
different power conversion system architectures in hybrid PV+BESS large power plants. Fo-
cusing on the PCS, the comparison was carried out considering the power flows converted
in each PCS’s element (dc–dc converter, dc–ac converter, and transformer). In fact, the PCS
is the only element of the power plant that changes among the three examined layouts. Of
course, without considering the battery round trip efficiency, an overestimation of the over-
all system’s efficiency is obtained. On the other hand, focusing only on the PCS efficiency
(without considering the battery’s one), it is possible to estimate and compare with more
accuracy and sensitivity the loss performance of the PCSs. Moreover, the BESS can consist
of different cell technologies, and accordingly, the round trip battery efficiency strongly
depends on the used chemistry. However, this appendix aims to provide an estimation
of the total efficiency, also considering the battery round trip losses in the calculation. For
these reasons, simulations were carried out, including the battery efficiency in the total
losses calculation.
Considering assuming a LiFePO technology, the battery efficiency data are provided
by the reference [44] and the reports in [34]. As shown in the reference documents, the
battery energy efficiency (ηB ) is defined as the ratio between discharge energy and charge
energy and depends on the charging–discharging rate. The annual average C-rate under
the operating condition of the plant is less than 0.1 C. Reference [44] reports the efficiency
from 4 C (ηB = 88%) down to 0.25 C (ηB = 98%), showing that the efficiency monotonically
increases when the C-rate decreases. The battery losses can be introduced in the calculation
of the layout’s efficiency. As shown in Figure A1, it is possible to consider the battery as
Energies 2021, 14, 4823 a system composed of an ideal subsystem and a subsystem that introduces the battery 20 of 22
conversion losses.
Figure A1.Power
A1.
Figure Powerflow
flowthat
thatinvolves the
involves battery
the considering
battery the
considering round
the trip
round conversion
trip losses.
conversion losses.
𝜂η 𝑃PBT, , charging.
𝑐ℎ𝑎𝑟𝑔𝑖𝑛𝑔.
(
Bch
PB𝑃 == 11 P , discharging. (A2)
(A2)
ηBdis 𝑃BT , 𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑖𝑛𝑔.
𝜂
where ηBch and ηBdis are the charging and discharging efficiency of the battery, PBT is the
where 𝜂 and 𝜂 are the charging and discharging efficiency of the battery, 𝑃 is
BESS power measured at the battery cell terminals, and PB is the power ideally measured
the BESS power measured at the battery cell terminals, and 𝑃 is the power ideally meas-
inside the cell, e.g., to the net of conversion losses during the charging. However, the
ured inside the cell, e.g., to the net of conversion losses during the charging. However, the
battery round trip efficiency refers to the cyclic operation, and it considers both the charging
battery round trip efficiency refers to the cyclic operation, and it considers both the charg-
ing and discharging process. Since the annual average C-rate is considered, it is possible
to assume the following equation that relates the round trip efficiency with the charging
and discharging efficiency:
Energies 2021, 14, 4823 20 of 22
and discharging process. Since the annual average C-rate is considered, it is possible to
assume the following equation that relates the round trip efficiency with the charging and
discharging efficiency:
√
ηBch = ηBdis = ηB (A3)
The battery losses are included in the calculation of the whole losses and efficiency,
and the obtained results are shown in Table A1.
Table A1. PCS+BESS efficiency as a function of the round trip battery efficiency.
PCS+BESS Efficiency
Battery Round Trip DC/BESS DC/PV Average C-Rate
AC-Coupling
Efficiency Coupling Coupling (LiFePO)
100% 96.86% 97.02% 96.34%
≤0.25 C
98% 96.75% 96.92% 96.24%
95% 96.56% 96.71% 96.05%
90% 96.22% 96.37% 95.75% 0.25 < C-rate ≤ 4
85% 95.89% 96.03% 95.44%
80% 95.56% 95.69% 95.14% >4 C
Table A1 shows that, despite the overall system’s efficiency decrease with the decrease
in the battery round trip efficiency, the ranking of the three different layouts remains
unchanged (1st DC/BESS, 2nd AC, and 3rd DC/PV). We report that percentage difference
among efficiency values decrease with the decrease in the battery efficiency due to the
lower value of ηB compared to the PCS efficiency. The final efficiency is more weighted by
the battery losses, and the sensitivity of the efficiency parameter as a function of the PCS
layout decreases accordingly. Moreover, considering the average C-rate with which the
battery works (0.08 C) may be possible to also assume ηB around or higher than 98%, and
the error introduced is less relevant.
References
1. Liu, X.; Aichhorn, A.; Liu, L.; Li, H. Coordinated control of distributed energy storage system with tap changer transformers for
voltage rise mitigation under high photovoltaic penetration. IEEE Trans. Smart Grid 2012, 3, 897–906. [CrossRef]
2. Luo, C.; Ooi, B.T. Frequency deviation of thermal power plants due to wind farms. IEEE Trans. Energy Convers. 2006, 21, 708–716.
[CrossRef]
3. Kroposki, B.; Johnson, B.; Zhang, Y.; Gevorgian, V.; Denholm, P.; Hodge, B.M.; Hannegan, B. Achieving a 100% renewable grid:
Operating electric power systems with extremely high levels of variable renewable energy. IEEE Power Energy Mag. 2017, 15,
61–73. [CrossRef]
4. Chamana, M.; Chowdhury, B.H.; Jahanbakhsh, F. Distributed control of voltage regulating devices in the presence of high PV
penetration to mitigate ramp-rate issues. IEEE Trans. Smart Grid 2018, 9, 1086–1095. [CrossRef]
5. Datta, U.; Kalam, A.; Shi, J. Battery energy storage system control for mitigating PV penetration impact on primary frequency
control and state-of-charge recovery. IEEE Trans. Sustain. Energy 2020, 11, 746–757. [CrossRef]
6. Gevorgian, V.; O’Neill, B. Advanced Grid-Friendly Controls Demonstration Project for Utility-Scale PV Power Plants; NREL: Golden,
CO, USA, 2016.
7. Gevorgian, V.; Booth, S. Review of PREPA Technical Requirements for Interconnecting Wind and Solar Generation; NREL: Golden, CO,
USA, 2013.
8. Loutan, C.; Klauer, P.; Chowdhury, S.; Hall, S.; Morjaria, M.; Chadliev, V.; Milam, N.; Milan, C.; Gevorgian, V. Demonstration of
Essential Reliability Services by a 300-MW Solar Photovoltaic Power Plant; NREL: Golden, CO, USA, 2017.
9. Miller, N.; Manz, D.; Roedel, J.; Marken, P.; Kronbeck, E. Utility scale battery energy storage systems. In Proceedings of the IEEE
PES General Meeting, PES 2010, Minneapolis, MN, USA, 26 July 2010; pp. 1–7.
10. Muñoz-Cruzado-Alba, J.; Rojas, C.; Kouro, S.; Galván Díez, E. Power production losses study by frequency regulation in
weak-grid-connected utility-scale photovoltaic plants. Energies 2016, 9, 317. [CrossRef]
11. Díaz-González, F.; Sumper, A.; Gomis-Bellmunt, O. Energy Storage in Power Systems; Díaz-González, F., Sumper, A., Gomis-
Bellmunt, O., Eds.; John Wiley & Sons Ltd.: Chichester, UK, 2016; ISBN 9781118971291.
12. Han, Z.; Luo, G.; Song, X.; Yang, C.; Zhang, L.; Jia, Y.; Zhao, Z.; Jin, Y. Research on the dispatch proportion of battery capacity
in photovoltaic primary frequency control. In Proceedings of the 2019 3rd IEEE Conference on Energy Internet and Energy System
Integration: Ubiquitous Energy Network Connecting Everything, Changsha, China, 8–10 November 2019; Institute of Electrical and
Electronics Engineers: Piscataway, NJ, USA, 2019; pp. 1098–1103.
Energies 2021, 14, 4823 21 of 22
13. Barchi, G.; Pierro, M.; Moser, D. Predictive energy control strategy for peak shaving and shifting using BESS and PV generation
applied to the retail sector. Electronics 2019, 8, 526. [CrossRef]
14. Solar Power Europe. Grid Intelligent Solar Unleashing the Full Potential of Utility-Scale Solar Generation in Europe; Solar Power
Europe: Brussels, Belgium, 2019.
15. International Renewable Energy Agency. Utility-Scale Batteries Innovation Landscape Brief ; International Renewable Energy Agency:
Abu Dhabi, United Arab Emirates, 2019; ISBN 978-92-9260-139-3.
16. Abdelrazek, S.A.; Kamalasadan, S. Integrated PV capacity firming and energy time shift battery energy storage management
using energy-oriented optimization. IEEE Trans. Ind. Appl. 2016, 52, 2607–2617. [CrossRef]
17. Ahmed, M.; Kamalasadan, S. Energy storage PV capacity firming with forecasted power reference and optimal error minimization.
In Proceedings of the 2015 North American Power Symposium, Charlotte, NC, USA, 4–6 October 2015; Institute of Electrical and
Electronics Engineers: Piscataway, NJ, USA, 2015; pp. 1–6.
18. Yang, Y.; Kim, K.A.; Blaabjerg, F.; Sangwongwanich, A. Flexible active power control of PV systems. In Advances in Grid-Connected
Photovoltaic Power Conversion Systems; Elsevier: Amsterdam, The Netherlands, 2019; pp. 153–185.
19. Denholm, P.; Eichman, J.; Margolis, R. Evaluating the Technical and Economic Performance of PV Plus Storage Power Plants; NREL:
Golden, CO, USA, 2017.
20. Dynapower AC vs. DC Coupling for Solar Plus Energy Storage Projects|Dynapower. Available online: https://www.dynapower.
com/ac-vs-dc-coupled-solar-plus-storage/ (accessed on 27 January 2021).
21. Go Big, Go DC: An In-Depth Look at DC-Coupled Solar-Plus-Storage|Energy Storage News. Available online: https://www.
energy-storage.news/blogs/go-big-go-dc-an-in-depth-look-at-dc-coupled-solar-plus-storage (accessed on 27 January 2021).
22. Fluence a Battery for Hire: AC vs. DC Coupling for Solar + Energy Storage Projects. Available online: https://blog.fluenceenergy.
com/energy-storage-ac-dc-coupled-solar (accessed on 27 January 2021).
23. Sterling & Wilson why Large-Scale Solar Alone no Longer Makes Sense. Available online: https://www.pv-magazine.com/
webinars/why-large-scale-solar-alone-no-longer-makes-sense/ (accessed on 27 January 2021).
24. DiOrio, N.; Denholm, P.; Hobbs, W.B. A model for evaluating the configuration and dispatch of PV plus battery power plants.
Appl. Energy 2020, 262, 114465. [CrossRef]
25. He, J.; Yang, Y.; Vinnikov, D. Energy storage for 1500 V photovoltaic systems: A comparative reliability analysis of DC- and
AC-coupling. Energies 2020, 13, 3355. [CrossRef]
26. Sandelic, M.; Sangwongwanich, A.; Blaabjerg, F. Reliability evaluation of PV systems with integrated battery energy storage
systems: DC-coupled and AC-coupled configurations. Electronics 2019, 8, 1059. [CrossRef]
27. Despeghel, J.; Tant, J.; Driesen, J. Loss model for improved efficiency characterization of DC coupled PV-battery system converters.
In Proceedings of the IECON Proceedings (Industrial Electronics Conference), Lisbon, Portugal, 14–17 October 2019; IEEE Computer
Society: Washington, DC, USA, 2019; pp. 4740–4745.
28. Akeyo, O.; Rallabandi, V.; Jewell, N.; Ionel, D.M. The design and analysis of large solar PV farm configurations with DC-connected
battery systems. IEEE Trans. Ind. Appl. 2020, 56, 2903–2912. [CrossRef]
29. Müller, N.; Kouro, S.; Zanchetta, P.; Wheeler, P.; Bittner, G.; Girardi, F. Energy storage sizing strategy for grid-tied PV plants under
power clipping limitations. Energies 2019, 12, 1812. [CrossRef]
30. Central Inverter PVS980-58. Available online: https://www.fimer.com/sites/default/files/FIMER_PVS980-58-from4348to5000_
EN_RevB__0.pdf (accessed on 24 May 2021).
31. Asian Development Bank. Handbook on Battery Energy Storage System; Asian Development Bank: Mandaluyong, Philippines, 2018;
ISBN 9789292614706.
32. HITACHI ABB Battery Energy Storage System PQpluSTM . Available online: https://www.hitachiabb-powergrids.com/it/it/
offering/product-and-system/energystorage/pqplus (accessed on 3 July 2021).
33. World Bank Group Economic Analysis of Battery Energy Storage Systems. Available online: https://openknowledge.worldbank.
org/bitstream/handle/10986/33971/Economic-Analysis-of-Battery-Energy-Storage-Systems.pdf?sequence=1&isAllowed=y
(accessed on 3 July 2021).
34. ITP Renewables Reports—Lithium Ion Battery Test Centre. Available online: https://batterytestcentre.com.au/reports/ (accessed
on 3 July 2021).
35. Kosmadakis, I.E.; Elmasides, C.; Koulinas, G.; Tsagarakis, K.P. Energy unit cost assessment of six photovoltaic-battery configura-
tions. Renew. Energy 2021, 173, 24–41. [CrossRef]
36. Susanto, J.; Shahnia, F.; Ludwig, D. A framework to technically evaluate integration of utility-scale photovoltaic plants to weak
power distribution systems. Appl. Energy 2018, 231, 207–221. [CrossRef]
37. European Network of Transmission System Operators for Electricity (ENTSO-E). Inertia and Rate of Change of Frequency (RoCoF);
European Network of Transmission System Operators for Electricity (ENTSO-E): Brussels, Belgium, 2020.
38. Puerto Rico Electric Power Authority’s Minimum Technical Renewables Interconnection Requirements—ESIG. Available
online: https://www.esig.energy/wiki-main-page/puerto-rico-electric-power-authority-s-minimum-technical-renewables-
interconnection-requirements/#Frequency_Response.2FRegulationRegulation (accessed on 27 January 2021).
39. Denholm, P.; O’Connell, M.; Brinkman, G.; Jorgenson, J. Overgeneration from Solar Energy in California: A Field Guide to the Duck
Chart; NREL: Golden, CO, USA, 2015.
Energies 2021, 14, 4823 22 of 22
40. Mathews, I.; Xu, B.; He, W.; Barreto, V.; Buonassisi, T.; Peters, I.M. Technoeconomic model of second-life batteries for utility-scale
solar considering calendar and cycle aging. Appl. Energy 2020, 269, 115127. [CrossRef]
41. Stieneker, M.; Mortimer, B.J.; Averous, N.R.; Stagge, H.; de Doncker, R.W. Optimum design of medium-voltage DC collector grids
depending on the offshore-wind-park power. In Proceedings of the PEMWA 2014—2014 IEEE Symposium on Power Electronics and
Machines for Wind and Water Applications, Milwaukee, WI, USA, 24–26 July 2014; Institute of Electrical and Electronics Engineers:
Piscataway, NJ, USA, 2014; pp. 1–8.
42. Morandi, A.; Gholizad, B.; Stieneker, M.; Stagge, H.; de Doncker, R.W. Technical and economical evaluation of DC high-
temperature superconductor solutions for the grid connection of offshore wind parks. IEEE Trans. Appl. Supercond. 2016, 26, 1–10.
[CrossRef]
43. Italweber Electra General Catalougue. Available online: www.italweberelettra.it (accessed on 27 January 2021).
44. Stan, A.I.; Swierczynski, M.; Stroe, D.I.; Teodorescu, R.; Andreasen, S.J.; Moth, K. A comparative study of lithium ion to lead acid
batteries for use in UPS applications. In Proceedings of the INTELEC, International Telecommunications Energy Conference, Vancuver,
BC, USA, 28 September–2 October 2014; Institute of Electrical and Electronics Engineers: Piscataway, NJ, USA, 2014; pp. 1–8.