Design Report on the Embedded Part (EP) for Main Air Lock Barrel (MALB) in
Inner Containment Wall (ICW) of KAPP-3&4
Rajiv Ranjan
Sr. Executive Engineer (C)
Indrajit Ray
Dy. Chief Engineer (C)
DOCUMENT TYPE: DR
Table of Contents
Table of Contents.........................................................................................................................................................4
List of Tables ..............................................................................................................................................................5
List of Figures ..............................................................................................................................................................5
Abbreviations Used......................................................................................................................................................6
CHAPTER:-1 INTRODUCTION..................................................................................................................................7
1.1 GENERAL.....................................................................................................................................................................7
1.2 OBJECTIVE..................................................................................................................................................................7
1.3 SCOPE..........................................................................................................................................................................7
1.4 REPORT LAYOUT.........................................................................................................................................................7
1.5 DOCUMENTS AND APPLICABLE CODES.......................................................................................................................7
CHAPTER:-2 GENERAL DESCRIPTION OF THE EMBEDDED PART FOR MAIN AIR LOCK BARREL........9
2.1 GENERAL.....................................................................................................................................................................9
2.2 DETAILS OF EP AND JOINT BETWEEN I.C. AND MAIN AIRLOCK BARREL..................................................................9
2.2.1. Details of EP......................................................................................................................................................9
2.2.2. Joint between I.C. and Airlock Barrel...............................................................................................................9
2.3 MATERIAL...................................................................................................................................................................9
2.4 LIMIT OF STRESSES.....................................................................................................................................................9
CHAPTER:-3 ANALYSIS METHODOLOGY..........................................................................................................12
3.1 GENERAL...................................................................................................................................................................12
3.2 LOADS.......................................................................................................................................................................12
3.3 ANALYSIS METHOD..................................................................................................................................................12
3.3.1. FE Model.........................................................................................................................................................12
3.3.2. Load Modelling................................................................................................................................................12
3.3.3. FE Model Boundary Condition.......................................................................................................................13
3.4 ANALYSIS OF EP FOR MALB...................................................................................................................................13
3.4.1. Calculation of Strains on Outer Face of IC Structure.....................................................................................13
3.4.2. Calculation of Stress and Strain in EP for MALB...........................................................................................13
3.5 ANALYSIS RESULTS..................................................................................................................................................14
3.5.1. Stresses in the EP for MALB...........................................................................................................................14
CHAPTER:-4 DESIGN, SUMMARY AND CONCLUSION....................................................................................15
4.1 GENERAL...................................................................................................................................................................15
4.2 DESIGN OF EMBEDDED PART (EP)...........................................................................................................................15
4.3 DESIGN OF ANCHOR..................................................................................................................................................15
4.3.1. Design for pull-out...........................................................................................................................................15
4.3.2. Design check for anchor bond.........................................................................................................................16
4.3.3. Design for anchor strength..............................................................................................................................16
4.3.4. Design check for shear....................................................................................................................................16
4.3.5. Design of Bearing Plate at the end of anchor.................................................................................................17
4.4 WELD DESIGN...........................................................................................................................................................17
4.4.1. Between EP plate and stud..............................................................................................................................17
4.5 SUMMARY.................................................................................................................................................................18
4.6 CONCLUSION.............................................................................................................................................................18
REFERENCES ............................................................................................................................................................19
NUCLEAR POWER CORPORATION OF INDIA LIMITED
REV NO.:
DESIGN REPORT ON THE EMBEDDED KAPP-3&4/DC//21000/ R0
PART (EP) FOR MAIN AIR LOCK BARREL 40/R0 AUGUST
(MALB) IN INNER CONTAINMENT WALL 2010
(ICW) OF KAPP-3&4
PAGE: of
List of Tables
List of Figures
Abbreviations Used
NB Nuclear Building
RB Reactor Building
IC Inner Containment
SA Sealing Arrangement
IS Indian Standard
DL Dead Load
IP Internal Pressure
TA Temperature Accident
FEM Finite Element Method
MS Mild Steel
EP Embedded Part
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 7 of 27
CHAPTER:-1 INTRODUCTION
1.1 General
This report covers the analysis and design of the Embedded Part (EP) for Main Air Lock
Barrel (MALB) in the Inner Containment (IC) wall of KAPP-3&4 as per ASME Section-
III, Division-I, Sub-part NE.
1.2 Objective
The present analysis and design work of the EP in the IC wall of KAPP-3&4 has been
carried out for the maximum load coming from the bellow corresponding to maximum
allowable axial and lateral movement of bellow as per design under design load
combination.
1.3 Scope
The scope of the present report is the analysis and design of the embedded part (EP) for
Main Air Lock Barrel (MALB) in the Inner Containment Wall (ICW) of KAPP-3&4 for
loading condition due to bellow type expansion joint.
Chapter-1: Introduction
This chapter consists of the objective, scope, report layout and the reference documents
and applicable codes.
Chapter-2: General Description of the Embedded Part (EP) for MALB
This chapter consists of the description of the embedded part (EP) for main air lock barrel
(MALB) in the ICW of KAPP-3&4. The material specifications for the EP have been
covered. The design allowable for the EP in terms of permissible stresses as per ASME
Section III Division 1, Sub-part NE has also been covered in this chapter.
Chapter-3: Analysis Methodology
This chapter consists of the description of the loads, finite element model and boundary
conditions for the embedded part (EP). The analysis methodology and the analytical results
have also been covered in this chapter.
Chapter-4: Design, Summary and Conclusion
This chapter consists of the design of the EP and its anchor. This chapter also consists of
the summary and conclusion for the present work. The references used are also mentioned.
2.1 General
The Inner Containment Structure is a prestressed concrete structure consisting of Main Air
Lock Barrel (MALB) and Auxiliary Air Lock Barrel (AALB). The MALB is located on
Grid-3 towards west side of reactor building. The Main Air Lock has rectangular opening
with clear inside dimension of 4.5m wide and 5.54m high. The embedded part (EP) for
Main Air Lock Barrel is made of 10 mm thick steel plate.
2.2.1. Details of EP
The EP is circular in shape and is made up of 10 mm thick Mild Steel (MS) Plate. The EP
has clear inside dimension of 4.5 m wide and 5.5 m high. The detail of the EP is given in
Figure-1 and Figure-2. The general construction of MAL EP is similar to the EP provided
to TAPP-3&4 projects and design methodology is also similar for the EP of TAPP-3&4.
2.3 Material
The material used for design of EP for MALB is weldable type structural steel as per IS:
2062 Grade C (Designation is Fe410WC).The mechanical property of the material as used
in the design is given in Table-2 below:
The design allowable for the design of EP for MALB has been specified in terms of
stresses, forces and displacement, as applicable. The rules for allowable stress intensities
and allowable stresses are given in NE-3200, where the allowable stress intensity Smc is 1.1
times the S value given in ASME Section II, Part D, Sub-Para 1, Tables 1A, except Smc
shall not exceed 90% of the material yield strength.
The value of S is taken for that grade of steel, which has yield strength and tensile strength
values closer to the values of the IS 2062 Grade C steel. The value of S is 17.1 ksi. Hence,
the value of Smc = 1.1 * 17.1 = 18.8 ksi, i.e. 13220 T/m2.
As per the basis for establishing allowable stress values, for Class I components given in
Appendix III of ASME Section III Division 1, Clause III 2110, Sm,1 for class 1 component
is lowest of the following:
a) One third of the specified minimum tensile strength: i.e. 0.333 x 410 = 136.67 MPa
b) Two thirds of the specified yield Strength: i.e. 0.667 x 250 = 166.67 MPa
As per Table NE 3221-1 or Figure- NE 3221-1 to 3, allowable limits of stress intensity for
various stress categories are summarized in Table-3.
In the design of EP for MALB, loads from the bellow has been calculated based on the
axial and lateral stiffness of bellow and corresponding allowable axial and lateral
deformation. The deformation corresponds to the maximum deformation of the IC around
the MALB opening under design load combination. As such for MALB EP design check,
the stress level cannot be categorized in to level A, B, or C. However, the minimum stress
level corresponding to primary membrane stress has been used as a limiting value of stress
for MALB EP design, which is 132.2 MPa or 13220 T/m2.
The allowable stress for anchor has been calculated as per ACI: 349, Cl.B.4.2. The
allowable stress limits has been calculated and is given in section 4.3.
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 12 of 27
3.1 General
The EP for MALB in the IC wall of KAPP-3&4 has been analyzed using analytical
approach using FEM for structural response for a loading condition due to bellow type
expansion joint. The EP for MALB is designed according to rules of ASME-NE-3100 &
NE-3200, while the studs (anchors) are checked using ACI: 349 rules.
3.2 Loads
The EP for MALB is subjected to loads due to bellow type expansion joint. The allowable
axial spring rate is 750 Kg/mm and the allowable lateral spring rate is 85000 Kg/mm. The
allowable movements of bellow are specified in Chapter-2. Hence, for their movement the
maximum axial load is 12 MTon in the axial direction and the maximum horizontal load is
935 MTon in the horizontal direction and the maximum vertical load is 340 MTon in the
vertical direction.
3.3.1. FE Model
A detailed 3-D finite element model of IC has been developed to analyze the exact
behaviour of the EP for MALB in the IC wall of KAPP-3&4.The EP for MALB is
modeled using general shell element (NKTP-20) of NISA software. The large opening due
to main air lock barrel is modeled in F.E. model. The FE model developed for the EP for
MALB is shown in Figure-4. The FE model details are given in Table-4 below.
ε 1,2=(ε x + ε y )/2± √[ (ε x
2
/ 2−ε y /2 ) +(γ xy /2 ) ]
2
εx
= Strain on outer face of concrete element in the local X-direction
εy
= Strain on outer face of concrete element in the local Y-direction
γ xy
= In plane shear strain on the outer face of concrete element
γ max =( ε −ε
1 2)
ε 1 ε 2
Where, and are major & minor principal strain on the outer face of concrete element,
γ max
obtained from the IC analysis. The stress contour ( and ) induced in the concrete
portion on the outer face of IC structure around the MALB opening is shown in the Figure-
6 and Figure-7. The stress induced in the EP plate can be calculated using Hook’s law if
the strain in the EP plate is in the linear range of stress-strain curve of EP plate. The
principal stresses in the EP for MALB is calculated as follows:
2
σ = E s /(1−ν )∗[ ε + ν ε ]
1 1 2
2
σ = E s /(1−ν )∗[ ε +ν ε ]
2 2 1
τ = γ ×G
1,2 max s
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 14 of 27
σ σ
1 2 τ 1,2
, are major and minor principal stresses in the EP plate and is the principal shear
stress in the EP plate.
4.1 General
The embedded part (EP) for main air lock barrel is designed according to rules of ASME
Section III: Division-1: Sub NE-3100 & NE-3200, while the studs (anchors) are checked
using ACI: 349 rules.
The total no of anchor having center to center spacing equal to 600 mm = 222
The total no of anchor having center to center spacing equal to 400 mm = 150
Assuming each stud resists pullout using its own effective concrete area, the area of
concrete available to resist pullout when spacing between anchors is 600 mm:
The area of concrete available to resist pullout when spacing between anchors is 400 mm:
The detail of the effective stress area for anchorage pullout is given in Figure-8.
4∗φ∗√ f c '
Maximum Permissible pullout force when spacing between anchors is 600 mm:
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 16 of 27
= 172.67 * 0.111
= 19.16 MTon
Maximum Permissible pullout force when spacing between anchors is 400 mm:
= 172.67 * 0.04
= 6.9 MTon
The total maximum permissible pullout force when spacing between anchors is 600 mm:
= 222 * 19.16
= 4253.52 MTon
The total maximum permissible pullout force when spacing between anchors is 400 mm:
= 150 * 6.9
= 1035 MTon
The total maximum permissible pullout force for combined case:
= 4253.52 + 1035
= 5288.52 > 12 MTon <safe>
The total no of anchor subjected to shear on the EP plate welded to bellow = 220
The total no of anchor subjected to pullout on the EP plate welded to bellow = 132
τv
Shear strength of anchor = 592 * * (π * 16 * 16/4)
= 1189.68 MTon
τ bd
Pullout strength of anchor = 132 * * π * 16 * 300
= 378 MTon
= 3.12 MTon
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 18 of 27
4.5 Summary
The present analysis and design work of the EP for MALB of the IC of the Nuclear
Building (NB) of Kakrapara Atomic Power Project-3&4 has been carried out to check the
adequacy of the MALB EP plate for load conditions due to bellow type expansion joint.
The EP for MALB has been analyzed using both analytical and numerical approach for
global response of the system. The structural response of the EP for MALB has been
studied in terms of stresses in the embedded part (EP).
4.6 Conclusion
Based on the above study it has been found that the design of EP for MALB is safe and
meets the design requirements.
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 19 of 27
REFERENCES
1 Document No.: KAPP-3&4/PSAR/01000/01/R2 July-2008 ‘Preliminary Safety Analysis Report
Section-3: Plant Layout, Buildings and Structures Part-2, Nuclear Power Corporation of India
Limited (A Government of India Enterprise), Mumbai, India.
2 Report No.: KAPP-3&4/DC/21000/15/R0 April, 2009. ‘Design report of Inner Containment
Structure (ICS) of KAPP-3&4’, Nuclear Power Corporation (A Government of India Enterprise),
Mumbai, India.
3 “ROARK’S Formula for Stress & Strain” by Warren C Young, 6 th edition, McGraw-Hill
International Editions.
4 Subramanian N. Design of Steel Structures. Oxford University Press, 2008.
5 Report No.4005/E/DN-32 (R0) Jan 1999. Design Report on Sealing Arrangement for SG
Opening in IC Dome of TAPP-3&4. STUP Consultant Limited, Navi Mumbai.
6 Drawing No.: KAPP-3&4/21032/2000/DD, Details of EP for Main Air Lock Barrel in the IC
Wall of KAPP-3&4.
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 20 of 27
E EL 106950
Bellow
Axial
Stiffness
= 750Kg/mm
ICW
Figure-4: Inner Containment Structure (ICS) and Main Air Lock Barrel (MALB)
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 24 of 27
Figure-6: Sxx Stress Contour Around MALB Opening due to Bellow Load
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 26 of 27
Figure-7: Syy Stress Contour Around MALB Opening due to Bellow Load
NUCLEAR POWER CORPORATION OF INDIA LIMITED
DESIGN REPORT ON THE EMBEDDED REV NO.:
PART (EP) FOR MAIN AIR LOCK KAPP-3&4/DC//21000/ R0
BARREL (MALB) IN INNER 40/R0 AUGUST
CONTAINMENT WALL (ICW) OF KAPP- 2010
3&4 PAGE: 27 of 27