Project Job Ref.
NESPAK
Section Sheet no./rev.
1
Calc. by Date Chk'd by Date App'd by Date
AH 12/11/2021
RC WALL DESIGN
In accordance with ACI 318-19
Tedds calculation version 1.2.04
Geometry of wall
Depth of wall; h = 60.00 in
Clear cover to reinforcement (both sides) ; cc = 1.50 in
Unsupported height of wall; lu = 144.0 in
Effective height factor; k = 0.50
Reinforcement of wall
Numbers of reinforcement layers; Nl = 2
Vertical steel bar diameter number ; Dver_num = 6
Spacing of vertical steel; sv = 9.00 in
Diameter of vertical steel bar; Dver = 0.750 in
Horizontal steel bar diameter number ; Dhor_num = 6
Spacing of horizontal steel; sh = 5.00 in
Diameter of horizontal bar; Dhor = 0.750 in
Specified yield strength of reinforcement ; fy = 60000 psi
Specified compressive strength of concrete ; f'c = 3000 psi
Modulus of elasticity of bar reinforcement ; Es = 29 106 psi
Modulus of elasticity of concrete; Ec = 57000 f’c1/2 (1psi)1/2 = 3122019 psi
Ultimate design strain; c = 0.003 in/in
Compression-controlled strain limit ty = 0.002
Check for minimum area of vertical steel of double layer reinforcement wall to cl. 11.6.1
Gross area of wall per running foot length ; Ag = h 12in = 720.000 in2
Project Job Ref.
NESPAK
Section Sheet no./rev.
2
Calc. by Date Chk'd by Date App'd by Date
AH 12/11/2021
Numbers of vertical bars per running foot length ; Nv = 12in/s v = 1.333
Area of vertical steel per running foot length ; Ast_v =2 Nv ( Dver2) / 4 = 1.178 in2
Minimum area of vertical steel required ; Ast_v_min= 1.080 in2
PASS- Minimum vertical steel check
Check for minimum area of horizontal steel of double layer reinforcement wall to cl. 11.6.1
Gross area of wall per running foot length ; Ag = h 12in = 720.000 in2
Number of horizontal bar per running foot height ; Nh = 12in / s h = 2.400
Area of horizontal steel per running foot height ; Ast_h = 2Nh ( Dhor2) / 4 = 2.121 in2
Minimum area of horizontal steel required ; Ast_h_min= 1.800 in2
PASS- Minimum horizontal steel check
Braced wall slenderness check to 6.2.5
Maximum slenderness ratio limit ; sr_max = 100
Permissible slenderness ratio ; sr_perm = min(34 + 12 (M1_act / M2_act), 40) = 34.0
Slenderness check for braced wall
Radius of gyration; rmin = 0.3 h = 18.00 in
Actual slenderness ratio; sr_act = k lu / rmin = 4.00
Wall slenderness limit OK, wall is braced short wall
Design loads for wall subjected to shear and axial load
Ultimate axial force per running foot; Pu_act = 23.00 kips/ft
Ultimate shear force per running foot ; Vu_act = 5.00 kips/ft
Check for axial load carrying capacity of wall subjected to shear and axial load cl. 22.4.2.1
Strength reduction factor; = 0.65
Ultimate axial load capacity of wall; Pu =0.8(0.85f’c(Ag - Ast_v)/1ft+fyAst_v/1ft) = 989.914 kips/ft
PASS- Wall is safe in axial loading
Check for shear capacity of wall cl. 22.5
Required shear strength Vu_act = 5.000 kips/ft
Strength reduction factor v = 0.75
Effective cover to reinforcement; d’ = cc + (Dver/2) = 1.875 in
Depth of tension steel; dt = h - d’ = 58.125 in
Size effect factor – cl. 22.5.5.1.3 s = min((2 / (1 + (dt / 1 in) / 10)),1.0) = 0.54
Ratio of longitudinal reinforcement w = As / (dt 12 in)= 0.001
Maximum shear force resisting capacity of wall Vmax = 5 × (f’c × 1 psi) dt = 191.018 kips/ft
Shear strength provided by concrete Vc1 = (8 × s × (w)1/3 (f’c × 1 psi) + Pu_act / (6 Ag) 12 in) dt =
19.367 kips/ft
Design shear capacity of section Vc = v × min(Vc1, Vmax)= 14.525 kips/ft
PASS- Wall is safe in shear force