6 Short-Circuit Currents 2p
6 Short-Circuit Currents 2p
Short-circuit Currents
Why computing short-circuit currents?
a) Choice of a suitable power system arrangement (structure) → configuration of the
transmission or distribution network
b) Determination of the required short-circuit ratings of the power system plant (thermal
ratings)
c) Determination of the breaking capacity required of the power system switchgear and
fuses
d) Design and application of equipment for the control and protection of the power system
(including earthing system)
e) Operation of the system, with particular reference to security of supply and economic
considerations
f) Investigation of unsatisfactory performance of the power system or of individual items of
power system plant CES4VO - 7 2
Short-circuit Currents
CES4VO - 7 3
3ph short-circuit 2ph short-circuit without earth fault 2ph short-circuit with earth fault 1ph short-circuit to earth
Short-circuit Currents
Factors affecting fault severity
a) Source conditions
- relate to the amount and disposition of all connected generation (including
interconnections with other systems)
- minimum and maximum connected load being of interest
b) Power system configuration: network topology, may change during/after a fault
c) Neutral earthing
- faults which involve the flow of earth current are influenced
- single-point or multiple-point earthed / direct (solid earthing) or via impedance
d) Nature and type of fault
- position
- fault impedance (arc resistance, resistance of metallic or non-metallic fault path)
- the most severe are: 3Ф and 1Ф in a solidly earthed network
CES4VO - 7 6
Short-circuit Currents / Standards
IEC 60909 : Short-circuit current in three-phase A.C. systems
Part 0 : Calculation of currents
Part 1 : Factors for the calculation of short-circuit currents according to IEC 60909-0
Part 2 : Electrical equipment data for short circuit current calculations
Part 3 : Currents during two separate simultaneous line-to-earth short circuits and
partial short-circuit currents flowing through earth
(equivalent to European Standard EN 60909, German National Standard DIN VDE 0102)
IEEE STANDARD 551-2006 - Recommended Practice for Calculating AC Short-Circuit
Currents in Industrial and Commercial Power Systems
CES4VO - 7 8
= 2 ( )
= ( )
= =
= arctan
CES4VO - 7 10
R-L circuit transients also represent time variation of a three-phase short-circuit
currents in a three-phase symmetrical system, remote from generator and
without load.
+
= 2 ( )
2
= 2 ( )
+
2
+
= 2 ( )
3
CES4VO - 7 11
CES4VO - 7 12
peak of
• Transmission
network, = 0.03
• Peak for = 0
(t = 0.0098 < 0.01s)
CES4VO - 7 15
• Distribution
network, = 1
• Peak for = 0
(t = 0.0073 < 0.01s)
CES4VO - 7 16
not examinable
used instead of
CES4VO - 7 17
CES4VO - 7 18
not examinable
used instead of
CES4VO - 7 19
• In purely inductive circuits, the first cycle peak current occurs at one
half-cycle in the phase that has the maximum initial dc component.
= ,
where =( 1) 2 .
used instead of
CES4VO - 7 23
F System equivalent at F:
= ( )
= 2 ( ) = arctan
SW
( + )
Complete circuit impedance : = ( ) [ ( )] , = arctan
+
CES4VO - 7 24
Example 1 assumptions
peak current
= = 0.03 and
→ = 1/(1 )
=1
CES4VO - 7 25
Example 2 assumptions
= = 1 and
peak current
=1
CES4VO - 7 26
not examinable
used instead of
CES4VO - 7 27
( )
= 2 sin ( )
( )
CES4VO - 7 28
( )
Structure of a two-pole,
three-phase, salient-
pole synchronous
machine
CES4VO - 7 30
Schematic diagram of a synchronous machine
q-axis
d-axis
ROTOR
L L
L L L
L
SHORT-CIRCUITED
FIELD
STATOR DAMPER WINDINGS
CES4VO - 7 31
2 2 ′′ ( ), stator RL transients
2 2
CES4VO - 7 32
Expression for three-phase short-circuit current at a generator terminals:
= 2 sin ( )
= 2 cos ( )
CES4VO - 7 33
′′
= 2 cos 2 ,
′′ ′ ′
- where decaying ac component is: =
′′ = ′′ / ′′ - subtransient component
′ = ′ / ′ - transient component
= / - continuous (steady-state) component
′′ ′′
- initial dc component is: = /
“0” indicates open-circuit / not loaded operation
no stator voltage drops → EMF equal to the pre-fault terminal phase voltage
CES4VO - 7 34
′′
→ subtransient time constant / relates to very rapid decaying component of
the ac short-circuit current, depends on rotor damper winding L/R ratio, the same
value for all types of short-circuits
′′ ′′ ′′
= , where is subtransient open-circuit time constant
(characterising transients when loaded machine is suddenly open)
′′ ′′
≈ 50 → ≈ 30
′
→ transient time constant / relates to considerably slower decaying,
depends on the field L/R ratio, different values for three-phase, two-phase and
single-phase short circuits (≈ 1 for round-rotor and ≈ 2 for salient-pole)
′ ′ ′
= , where is transient open-circuit time constant
CES4VO - 7 35
→ armature dc time constant / depends upon the L/R ratio of the armature,
the same for all kinds of short-circuits
CES4VO - 7 36
Positive-sequence reactances during the short circuit period:
′′
→ subtransient reactance (also referred as the initial reactance) / embraces
leakage reactances of stator and rotor windings, including effects of rotor
damper windings or bars and solid rotor construction
′
→ transient reactance (also referred as the total leakage reactance)
consists of leakage reactances of stator and field windings ( ≈ 1.2 1.6)
CES4VO - 7 37
VC VB
phasors
120 always 120
rotate anti-
VA clockwise VA
n n
VB VC
CES4VO - 7 38
Three-phase currents in armature windings create rotating magnetic field at
synchronous speed (armature-reaction).
Positive-sequence currents → clockwise rotation of magnetic field
Negative-sequence currents → anti-clockwise rotation
phase A phase A
negative sequence ACB
positive sequence ABC
CES4VO - 7 39
phase B
→ Currents at double the stator frequency are
phase C
therefore induced in rotor field and damper
windings.
negative sequence ACB
CES4VO - 7 41
+ ′′
- Round-rotor machines: = ≈
′′
- Salient-pole machines: about 20% greater than
′′
Zero-sequence reactance ≈
- Depends only upon leakage fields, since a zero-sequence system produces
no rotating field.
- Significant only for earth faults at a generator terminal when the stator neutral
point is connected to earth.
CES4VO - 7 42
Since ′′ ≪ ′ , the ac component can be approximated using simplified
expressions in three characteristic periods:
′′ ′′
, 0≤ ≤ /5
′′
Subtransient period ( < 3 ): =ቐ
′′ ′ ′ ′′ ′′
, /5 < < 3
′ ′′ ′
, 3 ≤ ≤ /5
′′ ′
Transient period (3 ≤ ≤3 ): =ቐ
′ ′ ′
, /5 < < 3
′
Continuous (steady-state) period : = , ≥3
′′ - initial ac component
′
- initial ac component when there are no damper windings
CES4VO - 7 43
subtransient
transient
CES4VO - 7 44
− Τ
Approximation is based on the following properties of = (0) :
0 , 0 ≤ ≤ /5
( )≈൞ 0 − Τ
, /5 < < 3
0 , ≥3
CES4VO - 7 45
′′ ′′ ′′
= ( sin ) ( cos )
′ ′ ′
= ( sin ) ( cos )
= ( sin ) ( cos )
CES4VO - 7 46
• Assuming a loaded machine pre-fault condition: rated terminal voltage
= (phase voltage) and rated load current = .
′ ′ ′
- Transient voltage → = 1 2 sin ( )
• Examples:
′′ ′ ′′ ′
Generator cos / / /
Cylindrical 0.2 0.3 1 0.8 (ind.) 1.13 1.2 2.72
Salient-pole 0.2 0.26 1.1 0.95 (ind.) 1.08 1.11 1.7
• Typical ranges: ′′ / ′/
Generator /
lower limit /air-cooled
Cylindrical 1.05 - 1.23 1.08 – 1.36 1.97 - 3.2
upper limit / water-cooled
Salient-pole 1.09 – 1.28 1.13 – 1.4 1.6 – 2.44
CES4VO - 7 49
CES4VO - 7 50
CES4VO - 7 51
CES4VO - 7 52
subtransient
transient
CES4VO - 7 53
CES4VO - 7 54
CES4VO - 7 55
not examinable
CES4VO - 7 56
All shunt
circuit
elements
L are omitted.
CES4VO - 7 57
′′
Three-phase short-circuit current: = 2 cos 2
′′ ′′ / ′′ ′ ′/ ′ ′′ ′′
= , = , = / , = /
′′ ′′ ′ ′
= , = , = , =
′′ ′′ ′ ′
= , = , =
CES4VO - 7 58
Modelling effect of network resistance is important for cable networks.
Fault current will have lower value when resistance is not omitted ( ≠ ).
−
′′
= 2 sin 2 sin( )
CES4VO - 7 59
− − −
′′ ′ ′ ′′
= 2 sin 2 sin( )
′′ ′
= = , = = ,
+ +
′′ ′′
= / , = /
′′ ′
Effect of network resistance on and is negligible, = .
CES4VO - 7 60
′′
Component /
Turbogenerator < 100 MW 15 – 85
Turbogenerator 100 – 500 MW 100 – 140
Hydro generator / no damper windings 40 – 60
Hydro generator / with damper windings 60 – 90
/
Transformer 5 – 30 MVA 7 – 17
Transformer 60 – 500 MVA 20 – 50
Overhead lines ACSR > 110kV ( 3 - line voltage) 3 /40
Cables 6 – 35 kV 0.2 – 1,5
CES4VO - 7 61
VT
AVR
CES4VO - 7 62
Impact of Automatic Voltage Regulator (AVR)
− −
′′ ′ ′
= 1 1 ( )
−
≈1 exp( )
CES4VO - 7 63
Impact of AVR
CES4VO - 7 64
L
′′ ′
Parameters: G → = 0.495Ω, = 0.745Ω, = 2.98Ω
′′ ′
= 0.04 , =1 , = 0.15
′′ = 9.27 , ′ = 9.49 , = 14.2
AVR: = 1.6
CES4VO - 7 68
“
CES4VO - 7 69
CES4VO - 7 70
- -
CES4VO - 7 71
a) no AVR
b) with AVR
CES4VO - 7 72
Maximal electromagnetic forces are proportional to the square of peak short-circuit
current.
Permitted mechanical stress of a electrical system component is specified using
maximum permitted peak fault current.
Peak current will occur in the subtransient period, hence we use the following
expression:
′′ ′ ′ ′′
= 2 sin 2 sin( )
Assume that the maximum fault current corresponds to the peak of ac component
(approximation) and it sums up with dc component:
′′ ′ ′ ′′
= 2 2 sin( ) ,
where is found from: = /2
CES4VO - 7 73
Peak current: = 2 ′′ ,
Including = ൘ = ≈ (approximation),
.
( )
the peak factor is: = 1
.
. .
the peak factor is = 1
CES4VO - 7 74
Joule integral and thermal equivalent short-time current
For a proper rating of power conductors and equipment the thermal effects of short-
circuit currents have to be considered.
In the majority of cases the three-phase short-circuit currents have the highest
magnitudes and produce the most pronounced thermal stresses → relevant for thermal
sizing.
Under assumption that the heating of current conducting elements during short-circuit is
practically adiabatic owing to short fault duration (no time to transfer energy), the
thermal stresses of these elements are closely related to the Joule integral (energy
released in 1Ω resistance),
= , /Ω = /Ω = , where is short-circuit duration.
Thus, = ,
′′ ′′
where = 2 sin( ) exp = 1 exp( 2 / ) sin( )
′′
In practice we can round to higher value = 1 exp( 2 / )
′′
For faults far from generator ≥ → =
CES4VO - 7 76
Joule integral and thermal equivalent short-time current
′ ′′ ′ ′
Since in practice exp( / )≈1 → = ( ) =
′
Solving the integral: = ( ∆ ),
where time correction
′′ ′′ ′′
∆ = 1 1 exp( 2 / ) 2 1 1 exp( / )
Complicated! CES4VO - 7 77
′
Thermal equivalent short-time current: =
where = ቐ1 , = 1 exp( 2 / )
1 ℎ
+ + +
= ( ) ( ) ≈
− − −
Practical simplifications:
+ +
≈ sin = Assume ( ) and
− −
will not
+ ′′ change much in T
≈ 2 sin =
−
CES4VO - 7 79
Thus, = ( ) → = ( )
Knowing the fault current at the generator terminals for a three-phase short-circuit
at ( ′′ = 8.31 , ′ = 6.95 , = 3.94 , ′′ = 8.16 , ′′ = 0.049 ,
′
= 1.52 , = 0.037 ), calculate:
a) Peak current (assume inductive network)
b) Joule integral and thermal equivalent short-time current (use fault duration 0.3s)
c) Breaking current (use breaker delay time = 0.09 )
CES4VO - 7 81
CES4VO - 7 82
CES4VO - 7 83
CES4VO - 7 84
Problem: For the three-phase short circuit at location F, calculate: peak
current, Joule integral and thermal equivalent short-time current (fault
duration is 0.2s), and breaking current (minimal breaker delay time is
0.09s). Solve using Thevenin’s equivalent on 231kV voltage level.
CES4VO - 7 85
CES4VO - 7 86
CES4VO - 7 87
CES4VO - 7 88
CES4VO - 7 89
CES4VO - 7 90
CES4VO - 7 91
CES4VO - 7 92
Assumptions in Transmission Network Fault Analysis
To simplify analysis of short-circuit currents in transmission networks (efficiently
earthed) we'll make several assumptions:
4. Induction motors are ignored or treated as synchronous machines (if large rating).
CES4VO - 7 93
Solution Techniques
Models used during a fault allow network to be represented as a linear circuit.
There are two main methods for solving for fault currents:
a) Direct method (reduction / back-substitution)
Use pre-fault conditions to solve for the internal machine voltages; then
apply fault and solve directly. → only for the systems with single voltage
source
b) Superposition / Thevenin’s equivalent
Fault is represented by two opposing voltage sources; solve system by
superposition → split the system in two circuits:
– Pre-fault circuit: voltage source represents the pre-fault operating point
– Delta circuit: it has only a single (remaining) voltage source
CES4VO - 7 94
Superposition / Thevenin’s equivalent
Faulted system
Generator Motor
CES4VO - 7 95
Pre-fault circuit solutions (1) equal to the pre-fault power flow solution.
The pre-fault
( )
“fault current” =0
is zero!
CES4VO - 7 96
Superposition / Thevenin’s equivalent
Fault current component (2) in the Delta circuit (a single voltage source at the
fault location with a magnitude equal to the negative of the pre-fault voltage
at the fault location):
Superposition:
I f = I (1)
f + If = 0+ If
(2) (2)
CES4VO - 7 97
Assumption:
The system with unsymmetrical fault is only unsymmetrical at a point of fault!
Symmetrical
and passive
network
Faulted network:
Symmetrical
and passive
network
CES4VO - 7 100
Analysis of Unsymmetrical Fault Types
Faulted network: Fault location
Symmetrical
and passive
network
Sequence networks:
CES4VO - 7 101
CES4VO - 7 102
Analysis of Unsymmetrical Fault Types
In practice we do not know driving voltages of all generators, therefore
→ knowing pre-fault voltage at a fault location (or assuming 1pu) we can use
Thevenin’s equivalent (Thevenin voltage = pre-fault voltage)
→ distribution of a fault current in network braches can be calculated using the
superposition theorem.
Boxes = Thevenin’s
Analysis of Unsymmetrical Fault Types equivalents
CES4VO - 7 104
Analysis of Unsymmetrical Fault Types
symmetrical
CES4VO - 7 105
CES4VO - 7 109
Algorithm
/ Example
CES4VO - 7 110
Effect of fault impedance / Algorithm extension
CES4VO - 7 111
CES4VO - 7 112
Effect of
fault
impedance
/ Algorithm
extension
CES4VO - 7 113
CES4VO - 7 114