Foundation Fieldbus: Dataguard™ - Iec61158-2 - Isa/Sp50 - Type A - Extended Temperature

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Foundation Fieldbus 100ohm

DataGuard™ - IEC61158-2 - ISA/SP50 - Type A - Extended Temperature

Part Number: 112101P18181

Print: YPFB REFINACION - SDCD - FOUNDATION FIELDBUS acc to. IEC61158-2 <DATAGUARD IEC60332-3-22 CAT.A UV STABLE>

Armour Above Min.


Cable formation
Item Inner Sheath wire Armour Outer Sheath Weight Bend
(IEC 61158-2 Type A)
Nom. Ø Max. Ø Radius

Max. Ø Nom. Ø Max. Ø Nom. ≠ Max. Ø

mm mm mm mm mm kg/km mm
1 1x2x18awg 8,5 0,9 10,3 1,5 13,3 290 200

Cable Construction Electrical Characteristics


stranded annealed tinned copper
Loop resistance (DC) at 20°C: ≤ 44,0 Ω/km
wires class 2 as per IEC 60228
Conductor - DC resistance (per conductor): ≤ 23,5 Ω/km
18awg

nominal formation : 7x0,40 mm - Insulation resistance at 20°C: ≥ 5.000 MΩ•km

Insulation Cross-linked polyethylene (XLPE)


- Rated voltage Uo/U: 300/500 V

Identification Orange - Blue - Mutual capacitance: 60 nF/km

- Nominal inductance: 0,7 mH/km


Shield aluminium/polyester tape in
continuous contact with a stranded
- Velocity of propagation: 66 %
annealed tinned copper drain wire

Inner sheath extruded sheath of FR-PVC, Orange - Characteristic impedance at 31,25 KHz: 100 Ω ± 20%

Armour galvanised steel wires - Attenuation at 39 KHz: Max. 3 dB/km

- Max. capacitance unbalance to shield: 4 nF/km


extruded sheath of flame retardant
Outer sheath PVC - Heat, oil and hydrocarbon
resistance and anti-vermin - Max. propagation delay change: 1,7 µs/km
impregnated, Orange
- Conductor operating temperature: 90˚C
Technical Data
- Oxygen index (LOI): 30 %

Oil Resistant: Acc. to ICEA S-73-532


- Flame retardant: IEC60332-1-2 & IEC60332-3-22 (Cat A)
Limiting Oxygen Index (LOI): Acc. to ASTM D2863 (min 30%)
Application Information
Temperature Range: -30°C to + 90°C (operation)
-30°C to +105°C (short term) <sheath only> - Rodent Protected
- UV Stable
Minimum Bending Radius: 10 x Cable Diameter
- Direct Burial
Pulling Tension: 1100N (installation) - Indoor / Outdoor Installation
- Haz. Location Compatible (Class I Div 2)

T: 01279 871150 | F: 01279 871129 | www.belcom.co.uk