EA990G5 10-30kVA (3/3) Maintenance Manual: East Group Co., LTD
EA990G5 10-30kVA (3/3) Maintenance Manual: East Group Co., LTD
Maintenance Manual
User of document
This document (manual) is mainly applicable for the following engineers:
Technical support engineer
Maintenance engineer
Revision history
The revision history provides description on each document upgrade. The latest version of
document includes the upgraded content of all previous versions.
Document version: V01 (15 AUG 2014)
Formally issued for first time
i
Content
Preface.................................................................................................................................................. i
1 Safety precautions............................................................................................................................1
1.1 Hazards.................................................................................................................................... 1
1.2 Warning....................................................................................................................................1
2 Description of model........................................................................................................................2
2.1 Description of EA990G5 10-30kVA serial model...................................................................2
2.2 Appearance introduction of EA990G5 10-30kVA series model..............................................3
2.3 The operation control LCD panel introduction of EA990G5 10-30kVA................................ 6
3 Internal Introduction.................................................................................................................... 23
3.1 System Configuration............................................................................................................23
3.2 System Block Diagram..........................................................................................................26
3.3 Introduction to Internal Boards............................................................................................. 27
4 Troubleshooting............................................................................................................................. 28
4.1 Repair tool List...................................................................................................................... 28
4.2 Troubleshooting process........................................................................................................28
4.3 Alarm information collection................................................................................................ 30
4.4 Common faults and troubleshooting methods.......................................................................30
4.5 Alarm detailed explanation and handling suggestions.......................................................... 30
5 Board replacement........................................................................................................................ 35
5.1 Board replacement of 10kVA model..................................................................................... 35
5.2 Board replacement of 15kVA model..................................................................................... 37
5.3 Board replacement of 20kVA model..................................................................................... 40
5.4 Board replacement of 30kVA model..................................................................................... 42
6 Board maintenance........................................................................................................................45
6.1 Maintenance of power board................................................................................................. 45
6.2 Maintenance of IP/OP board................................................................................................. 58
6.3 Maintenance of Bypass board............................................................................................... 66
7 Test.................................................................................................................................................. 72
7.1 Boards installation................................................................................................................. 72
7.2 Preparation before power-on................................................................................................. 72
7.3 Power-on and testing............................................................................................................. 72
1 Safety precautions
1.1 Hazards
1.As dangerous voltage exists in the UPS and the battery holder, installation and maintenance are only
completed by a professional engineer holding professional electrician qualification of the company or authorized
by the company.
2.Operators and maintainers, and professional technicians should receive full training on safe use and
equipment maintenance and work on the equipment after enough precautionary measures are taken and personal
safety equipment is used.
3.As the UPS is connected with the battery, voltage may exist on its output end even if it is not connected
with AC mains supply.
4.When the UPS is moved or rewired, the inputs, such as mains supply, the battery, etc., must be
disconnected, corresponding operation may be performed after the UPS powers down fully (more than 10min),
and otherwise the voltage may exist on its output end.
5.Before use, the UPS is reliably earthed to ensure personal safety and the normal use of the UPS.
6.When the UPS is maintained, the maintainer must wear insulated shoes and use insulated tools.
7.If temperature and humidity exceeds the limit value specified in the user manual, do not operate the
equipment.
8.Before maintenance of the UPS, all inputs and outputs of the UPS (including battery input) must be
disconnected.
9.Do not place the battery in fire to avoid explosion and endangering personal safety.
10.Do not stop the protector and ignore warnings, cautions and precautionary measures provided in the
manual and equipment nameplate.
1.2 Warning
1.Do not open the battery cover or damage the battery. If you are exposed to electrolyte, immediately wash
with plenty of clear water and seek medical advice.
2.Remove watch, ring and other metal article, wear insulating gloves and use the tools with insulated handle
during work on the battery.
3.During equipment operation, make sure that all sides and internal panels are securely fixed and front door
is closed.
1
2 Description of model
2.1 Description of EA990G5 10-30kVA serial model
Our EA990G5 10-30kVA series models are divided into tower type and rack type. The power level is
10/15/20/30KVA and the output power factor is 1.0. It can realize parallel operation of up to 4 units, provide
redundant power supply, and provide stable and reliable power supply for customer loads.
SNMP card/protocol
Remote network monitoring can be realized (RJ45 interface, as a
conversion
iDA-ST200P protocol conversion card, an adapter cable is required)
card(including
The built-in card is directly inserted into the card slot;
packaging materials)
SNMP card/protocol
Remote network monitoring can be realized (RJ45 interface, as a
conversion
iDA-ST200P protocol conversion card, an adapter cable is required)
card(excluding
The built-in card is directly inserted into the card slot;
packaging materials)
This device needs to be used with an SNMP card;
When the SNMP card detects that the UPS has an alarm, the SNMP
card can control the SMS modem to send the alarm content to the
SMS cat iDM-MDM200E mobile phone of the designated user;
It does not contain a SIM card and needs to be purchased separately.
At the same time, it only applies to standard SIM cards of China
Mobile and China Unicom.
The alarm information of the UPS can be automatically sent to the
mobile phone of the designated user;
SMS alarm iDM-ALM200P It does not contain a SIM card and needs to be purchased separately.
At the same time, it only applies to standard SIM cards of China
Mobile and China Unicom.
WIFI--glue stick antenna; you can connect the WIFIF module
WIFI module iDM-SPW202P through a mobile phone or computer to check the running status and
parameters of the UPS.
GPRS module iDM-SPG203P GPRS - glue stick antenna; you can connect the GPRS module
2
(external, DB9) through a mobile phone or computer to check the running status and
parameters of the UPS.
3
Fig.2-3 The rear pannel of 10kVA, 15kVA, 20kVA long-delay UPS (Tower)
Fig.2-4 The rear pannel of 10kVA, 15kVA, 20kVA standard UPS (Tower)
4
Fig.2-5 The rear pannel of 30kVA UPS (Tower)
5
Fig.2-7 The rear pannel of 30kVA UPS (Rack)
6
Fig.2-8 Control and display panel
LED Indicator
There are 2 LEDs on the panel to indicate the operating status and fault.The description of indicators is
shown in table 2-4。
Alarm
There are two different types of audible alarm during UPS operation, as shown in table 2-5
Alarm Description
Intermittent alarm when system has general alarm (for example: AC fault),
Continuous alarm When system has serious faults (for example: hardware fault)
7
Fig.2-9 Menu
8
No. Area Function description
2 Energy flow diagram Display the energy flow state of the cabinet. Click the
corresponding work interface to view the status information.
3 Status bar Display operation status, system time, buzzer status, alarm
status, HMI and monitoring communication status, USB status
of the cabinet.
4 Cold start Start the UPS in battery mode. The icon will be hidden after two
minutes.
Password login/logout key. After clicking, enter user password or advanced password
by the keyboard. The screen will be locked automatically.
2.3.3 System
In the "System" information interface, the "Mains ", "Bypass ", "Battery ", "Output", "Other", "Statistics" and
"About " information of the system can be inquired in the secondary menu at the left side.
Mains
The menu interface of the mains input is shown in Fig. 2-11, and displays information on three phases ABC
from left to right. The interface description is shown in Table 2-9.
9
Fig. 2-11 Input interface
Bypass
The menu interface of the bypass input is shown in Fig. 2-12, and the interface description is shown in Table
2-10.
10
Display item Description
Current (A) Bypass input phase current
Frequency (Hz) Bypass input frequency
PF Bypass input Power factor
Battery
The interface menu of battery input is shown in Fig. 2-13, and the interface description is shown in Table
2-11.
Output
The interface of output menu is shown in Fig. 2-14, and the interface description is shown in Table 2-12.
11
Fig. 2-14 Output interface
Other
The interface of other menu is shown in Fig. 2-15, and the interface description is shown in Table 2-13.
12
Table 2-13 Description of other interface
Statistics
The interface of statistics menu is shown in Fig. 2-16, and the interface description is shown in Table 2-14.
About
The interface of “About” menu is shown in Fig. 2-17, and the interface description is shown in Table 2-15.
13
Fig. 2-17 About interface
2.3.4 Alarm
In the "Alarms" information interface, you can view "Active alarm"and"Fault record "from the secondary
menu in the lower left corner. Click to select the type of alarm you want to view. The interface of alarm menu is
shown in Fig. 2-18.
14
Active alarm
The active alarm interface displays the relevant information of the current warning of UPS system, The
interface description is shown in Table 2.16.
History records
The "history record" is divided into "Location ID ", "Information " and "Tine ", as shown in Fig.2-19, The
interface description is shown in Table 2-17.
Fig.2-19
15
4.2.6 Control
In the "Control " information interface, you can select relevant operation from the left secondary menu,
which contains "On-Off "and "Maintain".
On-Off
The interface of the On-Off menu is shown in Fig. 2-20, and the interface description is shown in Table 2-18.
Maintenance
The interface of maintenance menu is shown in Fig. 2-21, and the interface description is shown in Table
2-19.
16
Fig. 2-21 Maintenance interface
2.3.6 Settings
Common settings
The interface of common settings menu is shown in Fig. 2-22, and the interface description is shown in Table
2-20.
17
Fig. 2-22 Common setting interface
Communication settings
The interface of the communication setting menu is shown in Fig. 2-23, and the interface description is
shown in Table 2-21.
18
Table 2-21 Description of communication settings interface
Rate parameters
The interface of the rate parameters menu is shown in Fig. 2-25, and the interface description is shown in
Table 2-23.
19
Fig. 2-25 Bypass parameters interface
Advanced parameters
The interface of advanced parameters menu is shown in Fig. 2-26, and the interface description is shown in
Table 2-24.
20
Table 2-24 Description of advanced parameters interface
Battery parameters
The interface of battery parameters menu is shown in Fig. 2-27, and the interface description is shown in
Table 2-25.
21
Setting item Default Options Description
et according to the total number of battery cells connected
Battery to the UPS system, each conventional lead-acid battery
40 settable
number has 6 battery cells, for example, 32 batteries × 6=192
battery cells.
Battery
capacity 18 settable Single battery capacity connected to the UPS system.
(Ah)
Charge
curr.limit(A 1 10 Set according to the needs,20% * UPS capacity limited.
)
Boost time
2 1-48 Set according to the needs.
limit
Cell float Charging voltage of single cells under floating charge
2.25 2.10 ~ 2.35
voltage condition.
Cell boost Charging voltage of single cells under boost charge
2.25 2.20~2.45
voltage condition.
Cell EOD
voltage for 1.65 1.6~1.85 Set according to the needs.
0.6C
Cell EOD
voltage for 1.75 1.65~1.9 Set according to the needs.
0.15C
Boost cycle 1440 1~3000h Set according to the needs.
This test will lead to the battery being partly discharged
Batt auto
to activate battery until battery voltage is low. Bypass
mainten 2880 720~30000h
must be in normal condition, the battery capacity should
cycle
be above 25%.
Batt volt
low 1.1 1.05~1.25 Set according to the needs.
coefficent
Batt
Set according to the actual battery replacement time for
mainten 3000 0-3000d
the users.
cycle
22
3 Internal Introduction
3.1 System Configuration
The Tower UPS is configured by the following part: Rectifier, Charger, Inverter, Static Switch and Manual
Bypass Switch. One or several battery strings should be installed to provide backup energy once the utility fails.
The UPS structure is shown in Fig. 3-1.
Normal Mode
The inverter of power modules continuously supply the critical AC load. The rectifier/charger derives power
from the AC mains input source and supplies DC power to the inverter while simultaneously FLOAT or BOOST
charging its associated backup battery.
23
Battery Mode
Upon failure of the AC mains input power, the inverter of power modules, which obtain power from the
battery, supply the critical AC load. There is no interruption in power to the critical load upon failure. After
restoration of the AC mains input power, the “Normal mode” operation will continue automatically without the
necessity of user intervention.
Bypass Mode
If the inverter overload capacity is exceeded under Normal mode, or if the inverter becomes unavailable for
any reason, the static transfer switch will perform a transfer of the load from the inverter to the bypass source,
with no interruption in power to the critical AC load. Should the inverter be asynchronous with the bypass, the
static switch will perform a transfer of the load from the inverter to the bypass with power interruption to the load.
This is to avoid large cross currents due to the paralleling of unsynchronized AC sources. This interruption is
programmable but typically set to be less than 3/4 of an electrical cycle, e.g., less than 15ms (50Hz) or less than
12.5ms (60Hz). The action of transfer/re-transfer can also be done by the command through monitor.
24
Maintenance Mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS becomes
unavailable e.g. during a maintenance procedure. (As shown in Fig.3-5).
Danger
During Maintenance mode, dangerous voltages are present on the terminal of input, output and neutral, even
with the LCD turned off.
ECO Mode
To improve system efficiency, UPS rack system works in Bypass mode at normal time, and inverter is
standby. When the utility fails, The UPS transfers to Battery Mode and the inverter powers the loads.
Note
There is a short interruption time (less than 10ms) when transfer from ECO mode to battery mode, it must be
sure that the interruption has no effect on loads.
25
Auto-restart Mode
The battery may become exhausted following an extended AC mains failure. The inverter shuts down when
the battery reaches the End of Discharge Voltage (EOD). The UPS may be programmed to “System Auto Start
Mode after EOD”. The system starts after a delay time when the AC mains input recovers. The mode and the
delay time are programmed by the commissioning engineer.
Frequency Converter Mode
By setting the UPS to Frequency Converter mode, the UPS could present a stable output of fixed frequency
(50 or 60Hz), and the bypass static switch is not available.
Self Aging Mode
If users want to burn in UPS without load, could set the UPS as Self Aging Mode, in this mode, the current
flow through rectifier, inverter, and back to input through bypass. It needs only 5% loss to burn in UPS with 100%
load.
26
3.3 Introduction to Internal Boards
Table 3-1 Internal Boards introduction of EA990G5 10-30kVA
27
4 Troubleshooting
This chapter mainly introduces all the alarm information of the system, the meaning of the alarm, the
possible cause of the alarm, and the processing method.
28
1. Fault record of UPS: The first on-site information of the fault is very important. According to these
information, the fault point and the cause of the fault can be roughly judged, and the correct solution can be
formulated. Therefore, the first thing for engineers to arrive at the site is to record all the conditions of the power
system, mainly recording the following:
1) The status of the UPS system (panel and monitoring information): the information of each display
interface of the LCD screen when a fault occurs, and the display status of the UPS on the monitoring side;
2) History download: use IServiceTool II software to download and save the running history of the UPS;Or
take pictures page by page of the LCD screen history page.
3) Actual input, output and battery parameters of the UPS system: When a fault occurs, the parameters
displayed on the panel may not the real parameters of the power supply. You can use a multimeter to measure the
actual parameters on the terminals and record them, including: input voltage, output voltage, battery voltage;
4) The position of each switch of the power system;
5) Environmental records: The surrounding environment is also very important to the work of the power
system. After completing the above records, the surrounding working environment should be recorded:
1> How is the ventilation; 2> Ambient temperature; 3> Whether the surrounding installation distance meets
the requirements; 4> Is the surrounding environment bad (such as dust or humidity); 5> How is the input and
output battery wiring? Does the wire diameter meet the requirements? Is the electrical insulation damaged? Are
the terminals loose? 6> The name, type, rated power, etc. of the load (you can consult the customer).
2. Fault type identification: After recording all indications, refer to the following fault information
description table to check the abnormal indicator lights. In most cases, the fault is caused by external reasons of
the UPS, so follow the principle of "outside first and then inside", locate and eliminate external faults according to
the fault information table.
Common external failure reasons:
1> Overload
2>Input, output over, under voltage
3>The mains air switch is disconnected or the mains is abnormal
4> Output short circuit
5>The battery voltage is lower than the low voltage point.
3. If the fault may be reported due to the internal reasons of the power supply, an implementation plan shall
be made according to the fault location. Each key step in the implementation of the plan should be recorded so
that the unresolved problems can be referenced when the plan is re-developed.
4. If the above methods still cannot solve the fault of UPS system, the recorded information will be fed back
to the technical support engineer for coordination and resolution.
29
4.3 Alarm information collection
4.3.1 LCD screen alarm information collection
When the maintenance personnel arrive at the scene for the first time, the alarm information needs to be
collected as soon as possible in order to obtain an effective basis for fault analysis. Record the display conditions
of the LCD panel (mainly fault codes) in detail, and record the working conditions of the LED indicators.
According to the fault code of the machine and the indication of the LED light, we can preliminarily determine the
fault category, which is convenient for locating the fault point.
4.3.2 Monitoring and alarm information collection
If the customer's power system is connected with monitoring software, maintenance personnel can download
and export the current alarm information and all data through the monitoring software for analysis. For details,
please refer to the user manual of the corresponding network management software.
30
1. Check whether the mains input air
The effective value of the three-phase switch is disconnected;
243 Grid input breaker open
input voltage is lower than 35% 2. Check whether the mains input
insurance is damaged;
UPS maintenance breaker Maintenance bypass closed signal Check whether the maintenance
245
close trigger bypass cover is loose;
The effective value of the three-phase Check whether the bypass air circuit
246 UPS bypass breaker open
bypass voltage is lower than 35% breaker is disconnected;
31
Check whether the phase sequence of
468 Input phase sequence error input reversed
the mains input voltage is reversed
The difference between the maximum Check whether the mains input
470 Input voltage imbalance
and the lowest input voltage is 17V voltage is abnormal
Abnormal three-phase input voltage Please check whether the input neutral
474 Input null wire loss
DC line is connected normally;
Frequent switching between Mains and battery switching over 5 Check whether the mains input
477
grid and battery times within 1 hour voltage is abnormal
Please check if the battery is
480 Battery disconnect battery is not connected
connected;
There is an abnormal PFC alarm
482 Battery self check fail Please replace the power board
during the battery test
The battery voltage is 10V higher than Please check whether the battery
483 Battrey overvoltage
the equalizing voltage voltage is abnormal;
When the battery voltage is lower than
Please check whether the battery
484 Battery undervoltage DOD 1.1 times the EOD voltage, it can be
voltage is abnormal;
set
The battery current is 1.1 times greater
489 Battery charging overcurrent Please replace the I/O board
than the limit current
Open circuit of battery fuse/
491 Charger switch open Please replace the I/O board
charger switch
492 Charger switch short circuit Charger switch short circuit Please replace the I/O board
Please check whether the battery is
494 Reverse battery connection battery reversed
connected properly;
The busbar soft-start stage does not
521 PFC sofe start fail Please replace the power board
reach the set voltage
Rectifier IGBT module Rectification temperature is higher Please check whether the fan is
528
overtemperature than 80 degrees abnormal;
Rectifier E2PROM Rectifier E2PROM read and write
529 Please replace the I/O board
read-write failure failed
The charger voltage soft start does not
546 Charger sofe start fail Please replace the I/O board
reach the battery voltage
32
The charger voltage is 10V higher
547 Charger overvoltage Please replace the I/O board
than the equalizing voltage
Charger voltage is lower than 80% of
549 Charger undervoltage Please replace the I/O board
battery voltage
The bus voltage continuously drops
592 Bus-bar short circuit Please replace the power board
more than 150V in 3ms
594 Bus-bar overvoltage Bus voltage higher than 450V Please replace the power board
595 Bus-bar undervoltage Bus voltage below 286V Please replace the power board
The difference between the positive
596 Bus-bar voltage imbalance Please replace the power board
and negative bus voltage is 40V
Inverter voltage is 1.05 times higher
608 Inverter overvoltage Please replace the power board
than rated
Inverter voltage is 0.95 times lower
609 Inverter undervoltage Please replace the power board
than rated
Inverter module 105% Inverter overload 105 and more than 1
612 Please remove non-critical loads
overload hour
Inverter module 110% Inverter overload 110% and more than
613 Please remove non-critical loads
overload 1 hour
Inverter module 125% Inverter overload 125% and more than
614 Please remove non-critical loads
overload 10 minutes
Inverter module 150% Inverter overload 150% and more than
615 Please remove non-critical loads
overload 1 minute
Short circuit of inverter Remove the load and check for a short
616 Inverter short circuit exceeds 200ms
output circuit
Inverter module overload
617 Inverter overload 100% Please remove non-critical loads
alarm
Bypass overload 125% for more than
626 BYP 125% overload Please remove non-critical loads
10 minutes
Bypass overload 135% for more than
627 BYP 135% overload Please remove non-critical loads
1 minute
Bypass overload 150% for more than
628 BYP 150% overload Please remove non-critical loads
1 second
Bypass overload 200% for more than
629 BYP 200% overload Please remove non-critical loads
20ms
630 Bypass overload alarm Bypass overload 100% Please remove non-critical loads
33
1. Check whether the parallel cable
Parallel operation wire
648 Parallel operation wire abnormal connection is normal;
abnormal
2. Replace the parallel line;
Inverter radiator Inverter temperature is higher than 80 Please check whether the fan is
656
overtemperature degrees abnormal;
Inverter E2PROM operation Inverter E2PROM read and write
657 Please replace the I/O board
failure failed
Inverter DSP and monitor The communication of the clock chip
658 Please replace the I/O board
communication failure is abnormal
Please check whether the EPO
663 Emergency shutdown Emergency shutdown
terminal is loose;
672 Inverter relay open circuit Inverter relay open circuit Please replace the I/O board
673 Inverter relay short circuit Inverter relay short circuit Please replace the I/O board
SPI communication failure SPI communication failure between
676 Please replace the I/O board
between rectifier and inverter rectifier and inverter
34
5 Board replacement
5.1 Board replacement of 10kVA model
The 10kVA model includes the following boards: power board, IP/OP board, bypass board, monitoring board,
cold start board, parallel interface board, communication interface board, dry contact board; the specific locations
are shown in Fig.5-1 to 5-5.
35
Fig.5-3 The right side board of 10kVA standard model (Tower)
36
Fig.5-5 The board of 10kVA model (Rack)
37
Fig.5-7 The left side board of 15kVA long-delay model (Tower)
38
Fig.5-9 The left side board of 15kVA standard model (Tower)
39
5.3 Board replacement of 20kVA model
The 20kVA model includes the following boards: power board, IP/OP board, bypass board, monitoring board,
cold start board, parallel interface board, communication interface board, dry contact board; the specific locations
are shown in Fig.5-11 to 5-15.
40
Fig.5-13 The right side board of 20kVA standard model (Tower)
41
Fig.5-15 The board of 20kVA model (Rack)
42
Fig.5-17 The left side board of 30kVA long-delay model (Tower)
43
Fig.5-19 The left side board of 30kVA standard model (Tower)
44
6 Board maintenance
Maintenance of EA990 G5 10-30kVA series UPS requires maintenance engineer having basic circuit theory,
power electronics related knowledge, and knowledge of related circuit topology. In addition, the improvement of
maintenance skills requires the accumulation of long-term maintenance experience. Please keep a good record of
maintenance notes during the maintenance process. The maintenance notes are convenient for future maintenance,
which can help maintenance engineer quickly locate problem points, quickly solve problems, and improve his
maintenance efficiency.
According to the actual use, the EA990 G5 10-30kVA vulnerable parts are the main power board, input and
output board, bypass board, monitoring board and cold start board. The following will explain the maintenance of
these boards of the whole series of UPS.
45
Fig.6-1 Key components identification of 10kVA power board
46
After completing the inspection work in steps 1-6, replace the damaged device; after replacing the device,
use the shorting cap to short-circuit J2 of the rectifier control board CT1 and J2 of the inverter control board CT2,
and then follow the steps shown in Figure 6-2. Connection method Connect the main power board to the input and
output board (only connect the signal cable, not the copper bus), and carry out the drive test. The test waveforms
of each key device are shown in Table 6-2.
High level
+15V±1V;
Frequency
40KHz;
High level
+15V±1V;
Frequency
20KHz;
47
High level
+15V±1V;
Frequency
20KHz;
High level
1V-1.5V;
Battery SCR
S7,S8,S9,S10,S11,S12
Low level
0V;
If it is found that the individual IGBT or SCR drive is abnormal during the drive test, please re-check
whether the device is replaced, and check whether the corresponding drive module is damaged.
6.1.2 Maintenance of 15kVA power board
The 15kVA power board is mainly divided into a rectifier booster part and an inverter part. Among them, the
fragile components are shown in Table 6-3, and the position of the board is shown in Fig. 6-3.
48
ZD17,ZD18,ZD19,ZD20,ZD21,
ZD22,ZD23,ZD24,ZD25,ZD26,
ZD27,ZD28,ZD29,ZD30,ZD31,
ZD32,ZD33,ZD34,ZD35,ZD36,
ZD37,ZD38,ZD39,ZD40,ZD41
Boost diode D1,D2,D3,D4,D5,D6 RHRP3060 MM30FU60K
49
Step 5: Use the diode gear of the multimeter to test the input rectifier diode and Boost diode. If the forward
voltage drop is too low (less than 0.1V) or there is also a reverse voltage drop, the diode may be damaged and
needs to be replaced.
Step 6: Measure the resistance of the battery thyristor (SCR) with a multimeter in the ohm range. The normal
resistance should be around 20Ω. If not, it needs to be replaced.
After completing the inspection work in steps 1-6, replace the damaged device; after replacing the device,
use the shorting cap to short-circuit J2 of the rectifier control board CT1 and J2 of the inverter control board CT2,
and then follow the steps shown in Figure 6-4. Connection method Connect the main power board to the input and
output board (only connect the signal cable, not the copper bus), and carry out the drive test. The test waveforms
of each key device are shown in Table 6-4.
High level
+15V±1V;
Frequency
40KHz;
50
High level
+15V±1V;
Frequency
20KHz;
High level
+15V±1V;
Frequency
20KHz;
High level
1V-1.5V;
Battery SCR
S7,S8,S9,S10,S11,S12
Low level
0V;
If it is found that the individual IGBT or SCR drive is abnormal during the drive test, please re-check
whether the device is replaced, and check whether the corresponding drive module is damaged.
51
Table 6-5 The fragile componments of 20kVA power board
52
Step 3: Use the diode gear of the multimeter to detect the PIN1(+)-PIN3(-) and PIN2(+)-PIN3(-) of the boost
IGBT and the inverter outer/inner bridge IGBT. If the multimeter shows that the voltage drop is too low (less than
0.1V), you need to replace the corresponding IGBT.
Note: When replacing the IGBT, it is necessary to apply heat dissipation paste on the back of the IGBT. If the
corresponding insulating gasket is blackened, burned, burned through, burned, etc., it should also be replaced
together.
Step 4: Use the multimeter diode gear to detect the Zenner diode of IGBT driver. If the multimeter shows that
the voltage drop is too low (less than 0.1V), the corresponding Zener diode needs to be replaced.
Note: If the IGBT is found to be damaged in step 3, the corresponding driving Zener diode will also be
damaged.
Step 5: Use the diode gear of the multimeter to test the input rectifier diode and Boost diode. If the forward
voltage drop is too low (less than 0.1V) or there is also a reverse voltage drop, the diode may be damaged and
needs to be replaced.
Step 6: Measure the resistance of the battery thyristor (SCR) with a multimeter in the ohm range. The normal
resistance should be around 20Ω. If not, it needs to be replaced.
After completing the inspection work in steps 1-6, replace the damaged device; after replacing the device,
use the shorting cap to short-circuit J2 of the rectifier control board CT1 and J2 of the inverter control board CT2,
and then follow the steps shown in Figure 6-6. Connection method Connect the main power board to the input and
output board (only connect the signal cable, not the copper bus), and carry out the drive test. The test waveforms
of each key device are shown in Table 6-6.
53
High level
+15V±1V;
Frequency
40KHz;
High level
+15V±1V;
Frequency
20KHz;
High level
+15V±1V;
Frequency
20KHz;
54
High level
Main and battery SCR 1V-1.5V;
S1,S2,S3,S4,S5,S6,S7,S8,S9,S1
0,S11,S12 Low level
0V;
If it is found that the individual IGBT or SCR drive is abnormal during the drive test, please re-check
whether the device is replaced, and check whether the corresponding drive module is damaged.
55
Fig.6-7 Key components identification of 30kVA power board
56
After completing the inspection work in steps 1-6, replace the damaged device; after replacing the device,
use the shorting cap to short-circuit J2 of the rectifier control board CT1 and J2 of the inverter control board CT2,
and then follow the steps shown in Figure 6-8. Connection method Connect the main power board to the input and
output board (only connect the signal cable, not the copper bus), and carry out the drive test. The test waveforms
of each key device are shown in Table 6-8.
High level
+15V±1V;
Frequency
40KHz;
High level
+15V±1V;
Frequency
20KHz;
57
High level
+15V±1V;
Frequency
20KHz;
High level
Main and battery SCR 1V-1.5V;
S1,S2,S3,S4,S5,S6,S7,S8,S9,S1
0,S11,S12 Low level
0V;
If it is found that the individual IGBT or SCR drive is abnormal during the drive test, please re-check
whether the device is replaced, and check whether the corresponding drive module is damaged.
Alternative
Components Tag Number Specifications
specification
Input/Output Fuse F1,F3,F5,F8,F10,F12 324-0324030
Battery Fuse F15,F16 100A/690V
Charger Fuse F13,F14 10A/250V
Charger IGBT Q23,Q24 IKW30N65H5 JT050N065WED
Charger Diode D9,D10,D33,D34 RHRP3060 MM30FU60K
58
Fig.6-9 The key components identification of 10kVA IP/OP board
59
and then follow the steps shown in Figure 6-10. Connection method for drive test. The test waveforms of each key
device are shown in Table 6-10.
High level
+15V±1V;
Frequency
40KHz;
If it is found that the individual IGBT drive wareform is abnormal during the drive test, please re-check
whether the device is replaced, and check whether the corresponding drive module is damaged.
6.2.2 Maintenance of 15kVA IP/OP board
15kVA IP/OP board mainly includes auxiliary power supply, charger, input filter, output filter and mains soft
start circuit. Among them, the fragile components are shown in Table 6-11, and the position of the board is shown
in Fig 6-11.
Alternative
Components Tag Number Specifications
specification
Input/Output Fuse F1,F3,F5,F8,F10,F12 324-0324030
Battery Fuse F15,F16 100A/690V
Charger Fuse F13,F14 10A/250V
Charger IGBT Q23,Q24 IKW30N65H5 JT050N065WED
Charger Diode D9,D10,D43,D44 RHRP3060 MM30FU60K
60
Fig.6-11 The key components identification of 15kVA IP/OP board
61
and then follow the steps shown in Figure 6-12. Connection method for drive test. The test waveforms of each key
device are shown in Table 6-12.
High level
+15V±1V;
Frequency
40KHz;
If it is found that the individual IGBT drive wareform is abnormal during the drive test, please re-check
whether the device is replaced, and check whether the corresponding drive module is damaged.
6.2.3 Maintenance of 20kVA IP/OP board
20kVA IP/OP board mainly includes auxiliary power supply, charger, input filter and output filter. Among
them, the fragile components are shown in Table 6-13, and the position of the board is shown in Fig 6-13.
Alternative
Components Tag Number Specifications
specification
F1,F2,F3,F4,F5,F6,F8,F9,F10,F11,F1
Input/Output Fuse 324-0324030
2,F13
Battery Fuse F15,F16 100A/690V
Charger Fuse F13,F14 10A/250V
Charger IGBT Q23,Q24 IKW30N65H5 JT050N065WED
Charger Diode D9,D10,D43,D44 RHRP3060 MM30FU60K
62
Fig.6-13 The key components identification of 20kVA IP/OP board
63
and then follow the steps shown in Figure 6-14. Connection method for drive test. The test waveforms of each key
device are shown in Table 6-14.
High level
+15V±1V;
Frequency
40KHz;
If it is found that the individual IGBT drive wareform is abnormal during the drive test, please re-check
whether the device is replaced, and check whether the corresponding drive module is damaged.
6.2.4 Maintenance of 30kVA IP/OP board
30kVA IP/OP board mainly includes auxiliary power supply, charger, input filter and output filter. Among
them, the fragile components are shown in Table 6-15, and the position of the board is shown in Fig 6-15.
Alternative
Components Tag Number Specifications
specification
Input/Output Fuse F4,F5,F6,F25,F26,F27 100A/690V
Battery Fuse F13,F14 10A/250V
Charger Fuse Q19,Q20 IKW40N65H5 JT050N065WED
Charger IGBT D9,D10,D6,D7 RHRP3060 MM30FU60K
64
Fig.6-15 The key components identification of 30kVA IP/OP board
65
and then follow the steps shown in Figure 6-16. Connection method for drive test. The test waveforms of each key
device are shown in Table 6-16.
High level
+15V±1V;
Frequency
40KHz;
If it is found that the individual IGBT drive wareform is abnormal during the drive test, please re-check
whether the device is replaced, and check whether the corresponding drive module is damaged.
Alternative
Components Tag Number Specifications
specification
Bypass SCR Q1,Q2,Q3,Q4,Q5,Q6 VS-40TPS12A-M3 BT155W-1200T
66
Fig.6-17 The key components identification of 10kVA bypass board
67
Table 6-18 The driver test description of 10kVA bypass board
High level
1V-1.5V;
Bypass SCR
Q1,Q2,Q3,Q4,Q5,Q6
Low level
0V;
If it is found that the individual SCR is abnormally driven during the drive test, please re-check whether the
device is replaced, and check whether the corresponding drive module is damaged.
6.3.2 Maintenance of 15kVA/20kVA bypass board.
The 15kVA and 20kVA model share the bypass board, and the board mainly includes the bypass output
circuit and the output current sampling circuit. Among them, the frogile components have bypass SCR, which are
shown in Table 6-19, and its position in the board is shown in Figure 6-19.
Alternative
Components Tag Number Specifications
specification
Bypass SCR Q1,Q2,Q3,Q4,Q5,Q6 VS-50TPS12A BT155W-1200T
68
Step 1: Check whether the copper foil is corroded and rusted on the entire I/O board. You can use a
multimeter to assist in the inspection. If there is corrosion, the copper foil needs to be re-soldered.
Step 2: Visually inspect the entire I/O board for obvious burns or explosions, and replace if necessary.
Step 3: Measure the resistance of the bypass thyristor (SCR) with the ohm gear of the multimeter. The normal
resistance should be around 20Ω. If not, it needs to be replaced.
Note: When replacing the SCR, it is necessary to apply thermal paste on the back of the device. If the
corresponding insulating gasket is blackened, burned, burned through, burned, etc., it needs to be replaced
together.
After completing the inspection work in steps 1-3, replace the damaged device; after replacing the device,
use the shorting cap to short-circuit J2 of the rectifier control board CT1 and J2 of the inverter control board CT2,
and then follow the steps shown in Figure 6-20. Connection method for drive test. The test waveforms of each key
device are shown in Table 6-20.
High level
1V-1.5V;
Bypass SCR
Q1,Q2,Q3,Q4,Q5,Q6
Low level
0V;
If it is found that the individual SCR is abnormally driven during the drive test, please re-check whether the
device is replaced, and check whether the corresponding drive module is damaged.
6.3.3 Maintenance of 30kVA bypass board
The 30kVA bypass board mainly includes bypass output circuit and output current sampling circuit. Among
them, the forgile component is bypass SCR, which is shown in Table 6-21, and its position in the board is shown
in Fig.6-21.
69
Table 6-21 The frogile component of 30kVA bypass board
Alternative
Components Tag Number Specifications
specification
Bypass SCR Q1,Q2,Q3,Q4,Q5,Q6 VS-70TPSPBF
70
Table 6-20 The driver test description of 30kVA bypass board
High level
1V-1.5V;
Bypass SCR
Q1,Q2,Q3,Q4,Q5,Q6
Low level
0V;
If it is found that the individual SCR is abnormally driven during the drive test, please re-check whether the
device is replaced, and check whether the corresponding drive module is damaged.
71
7 Test
This chapter mainly introduces how to test the UPS after maintenance.
72
Step 6: 5 minutes after the UPS is completely powered off, re-close the battery pack air switch; press the cold
start switch until the LCD screen of the UPS lights up (about 3seconds), and then click the "cold start" button on
the screen to start the battery cold start. The UPS operates in battery inverter mode.
Note: If the machine can work normally in battery mode, mains mode, and battery self-check mode, it means
that the UPS has been repaired, and you can proceed to the next step. If the above operations are performed and
the machine works abnormally, it is necessary to further find the problem and repair it.
Step 7: Close the main circuit input circuit breaker and bypass circuit breaker, and wait for the UPS to switch
to the mains inverter mode. In the "mains inverter mode" and "battery self-test mode", the output load is 50%, and
check whether the input and output voltage and current of the UPS are normal. If the UPS can work normally, the
UPS has been repaired. If it is not working properly, then the problem needs to be further investigated and
repaired.
Reminder: If possible, try to use an oscilloscope and a isolated probe to measure the waveforms of ﹢BUS,
-BUS, INV voltage, output current, etc. during the above operation. This is more helpful to judge whether the UPS
is repaired or not.
73