Catalogue CA-FUW-F(AC)-202101

FUW Cabinet Fan Coil Units


Horizontal Unit
Model: FUW020F-FUW150F
Air Flow: 2000m3/h-15000m3/h

Vertical Unit
Model: FUW040V-FUW250V
Air Flow: 4000m3/h-25000m3/h
FUW Cabinet Fan Coil Units

Overview

DAIKIN FUW cabinet fan coil unit adopts high-strength cabinet, professionally selected and precision machined coil, efficient fan with low noises
and filter to better meet wide customers' requirements for air handling units and save the indoor space for customers. FUW products showcase the
characteristics such as high external total pressure, large cooling capacity, compact size and low noises and can be widely applied to central air
conditioning projects such as hotels, shopping malls, airports, hospitals, factories and office buildings, especially suitable for occasions where the
installation space is restricted, the noise requirement is high, and an old house is reconstructed.

小型商业写字楼
Commercial office building Shopping mall Light industrial workshop

Contents

FUW horizontal cabinet fan coil unit


Nomenclature .................................................................................................................................................... 3
Features ........................................................................................................................................................ 4~6
Specifications ................................................................................................................................................ 7~8
Dimensions .................................................................................................................................................. 9~20
FUW vertical cabinet fan coil unit
Nomenclature .................................................................................................................................................. 21
Features .......................................................................................................................................................... 22
Specifications .................................................................................................................................................. 23
Dimensions ............................................................................................................................................... 24~26

Motor power - Quick reference for maximum external total pressure .............................................................. 27
Precautions...................................................................................................................................................... 28

FUW horizontal cabinet fan coil unit


Ten models of FUW horizontal cabinet fan coil units are available,
with the unit air flow in the range of 1000 to 15000m3/h, cooling
capacity in the range of 11.4 to 260.2kW, and the external
total pressure in the range of 75 to 850 Pa. The unit provides
a lot of optional functions such as primary/medium-efficiency
filter, heating coil, electric heater and wet film humidifier to meet
various fan coil systems.
2
Cabinet Fan Coil Units FUW

Nomenclature

FUW  080  F  A  A  E  L  A  A  -  0  0  F  E
Export

Power Supply:
F -- 380V/3N~/50Hz
R -- 380V/3N~/60Hz
P -- 208-230V/3N~/60Hz
Q -- 460V/3N~/60Hz
Electric heater:
0 -- No electric heater
A -- With electric heater
Control options:
0 -- No control
1 -- Local start-up cabinet
2 -- Remote start-up cabinet
3 -- Local control cabinet
4 -- Remote control cabinet
Fan motor options:
- -- Fixed-frequency belt transmission
V -- Variable-frequency belt transmission
Filter type:
A -- Nylon filter
B -- G3 flat filter
C -- Aluminum (standard configuration for electric heater)
D -- G3 flat filter + F5 flat medium filter
E -- G3 flat filter + PM2.5 special filter
Drain pain material and aluminum foil material:
A -- Galvanized steel plate + common aluminum
B -- Galvanized steel plate + hydrophilic aluminum
C -- Stainless steel plate + common aluminum
D -- Stainless steel plate + hydrophilic aluminum
Pipe connection mode: L -- Facing air flow left hand; R -- Facing air flow right hand
External total pressure code, refer to below table
Cooling coil:
A -- 4C0H
B -- 6C0H
Heating coil attached in front of the cooling coil:
C -- 4C1H (4 rows cooling and 1 row heating)
D -- 6C1H (6 rows cooling and 1 row heating)
E -- 4C2H (4 rows cooling and 2 rows heating)
F -- 6C2H (6 rows cooling and 2 rows heating)
wet film humidifier attached behind the cooling coil:
G -- 4C0H1W (4 rows cooling, 100mm wet film)
H -- 6C0H1W (6 rows cooling, 100mm wet film)
Cooling coil attached with heating coil in the front and
wet film humidifier at the back
J -- 4C1H1W (4 rows cooling and 1 row heating,
100mm wet film)
K -- 6C1H1W (6 rows cooling and 1 row heating,
100mm wet film)
L -- 4C2H1W (4 rows cooling and 2 row heating,
100mm wet film)
M -- 6C2H1W (6 rows cooling and 2 row heating,
100mm wet film)
S -- 0C1H
T -- 0C2H
Structure type + application characteristics:
A -- Horizontal return air basic model
B -- Horizontal fresh air basic model
C -- Horizontal return air multi-function model
D -- Horizontal fresh air multi-function model
G -- Horizontal return air model with mixing box
F -- Horizontal fresh air model with mixing box
Design SN: F -- Horizontal type
Air flow code: 080 air flow is 8000m3/h (air flow = air flow code*100m3/h)
Model name and code: FUW-cabinet fan coil unit

Unit: Pa
A B C D E F G H J Where:
75 100 125 150 175 200 225 250 275 For the FUW020~070 models, the standard external total
K L M N P Q R S
pressure of unit is 150, 225, or 300 Pa.
For the FUW080~150 models, the standard external total
300 350 400 450 500 550 600 650
pressure of unit is 225, 300, or 400Pa.

Note: Basic model configuration: primary filter (digit 13: A) + cooling coil (heating coil) + fan
Multi-function model configuration: primary filter + (medium filter) + (heating coil / electric heater) + cooling coil + (wet film) + fan;
The function section in () is optional.
Mixing box is available for basic model and multi-function model.
The above nomenclature applies only to the standard units. For a unit of which the model is selected by the software, the nomenclature is
automatically generated.
3
FUW Cabinet fan coil Units

Unit features

Excellent cabinet performance


■The cabinet adopts quality galvanized steel plates, antirust and corrosion resistant; the specially selected new type PE heat preservation
material is attached inside, with superexcellent thermal insulation and sound-absorbing effect. We also supply high strength galvanized steel
sheets coated with electrostatic epoxy spraying for option.
Excellent anti-cold bridge performance Excellent tightness
■ The unit baseplate is designed as an intergrated drain pan, ■ Pressure-proof and wear-proof seal ring is filled in at all the joints
heat insulating material is attached outside the whole surface between the cabinet and exposed parts and mechanically fixed
of air output plate, thoroughly avoiding cold bridge. to effectively reduce air leakage.
■ Heat insulating material is attached between the external
parts such as flange and the panel so that the unit is free of
condensation even in a high humidity environment.

Heat
preservation
PE

Heat preservation PE Heat preservation PE Seal ring attached to the Seal ring Header Seal ring
attached outside the overall attached between the flange panel wiring hole pipe sealing
drain pan and panel

Different assembly to meet requirements


of various fan coil systems
Common comfortable system
■ Two-pipe system and four-pipe system for option to serve various fan
coil system of various scenarios
■ Electric heater optional, winter fresh air pretreatment to prevent
cracking of the coil Primary filter + heating coil + cooling coil + fan
■ Able to meet the temperature control requirement of comfortable places

Common cleaning system


■ Two stage air purification to achieve higher purification
■ Wet film humidifier to improve indoor dry air
■ Serving places with general requirements for the air purification, Primary + medium filter +
temperature and humidity heating coil + cooling coil + wet film + fan

Multiple external total pressures and parts for selection

150Pa
■ Multiple standard external total pressures are available, and multiple Pa
17
150
5P
a
Pa
optional parts can also be provided: primary/medium-efficiency filter (G3/ a1
25
20
0P
0P

a
10

G4/aluminum/F5/PM2.5) for filtration and purification, four-pipe system 225Pa


22
Pa

5P
75

coil, fresh air preheated electric heater, wet film humidifier, stainless steel
25 450

Pa
Pa
0

Pa 27 5 P 40 0
50 a 3 0 0 P a 3 5 0 Pa Pa
0P a 65 0
5 5 0 P a 6 00 Pa
drain pan, etc., making selection more rapid, convenient and flexible.
300Pa
400Pa

4
Cabinet Fan Coil Units FUW

Available assembly of Function Sections

Basic model configuration Optional configuration of the multi-function model


Function
section Primary Heating coil Cooling coil Fan Heating coil Cooling coil Electric heater Wet film Fan
Mixing box section Primary filter section Medium filter section
filter section section section section section section section humidifying section section
Optional 1/2/4/6 Fan F5 flat PM2.5 Electrical 100mm wet film
Nylon 1 row 2 rows Flange Damper Aluminum G3 G4 1 row 2 rows 1/2/4/6 rows Fan motor
parts rows motor type special filter heating tube humidifier

Diagrams

Note: When the unit select electric heater section, the filter must be aluminum filter; heating coil and electric heater section can’t be selected at the same time.
The external total pressure, dimensions, and weight of the unit vary with requirements of the optional function section. For details, see our selection software.
Heating coil and cooling coiling can’t be selected at the same time for basic model configuration.

Heat exchanger
■ The copper tubes with a thin wall and the latest type of fins are adopted, and mechanical expanding ensures close fit between the
copper tubes and fins, thus achieving the optimal heat exchange efficiency of the coil.
■ Before delivery, all the heat exchangers will do pressure leakage test by filling nitrogen according to the national standard requirements
to avoid leakage.

2 ●
2 ● Quality copper tubes are laid out in the cross counterflow mode to enhance the air
turbulence and improve the heat exchange.


1
Cross counterflow layout
Heat exchanger


1 ● Fins are corrugated aluminium sheets, which increase the
heat exchange area, optimize the heat exchange, make
condensate water flow down easily and prevent water
drops from being gathered on the fin surface.
● FPI, 11 to 14 fins can be selected.
Aluminum foil ● Hydrophilic aluminum foil is optional.

Fan motor
■ The fan is a high-efficiency and low-noise forward DWDI fans, and the professional
software ensures that all the fans operate in the safe and efficient status.
■ The motor is a fully-enclosed three-phase asynchronous motor, with the protection
grade up to IP55 and insulation grade F, applicable to adverse application environments.

● The impeller will be strict static and ● Multiple motor type: single speed, double
dynamic balanced, stable and low speed, and variable frequency.
noise.


2

1 ●
1

1

2

2


1 The narrow V type belt of international 1 Flexible joint is adopted at the air outlet of
● 1 A door handle is installed at the access

famous brand is adopted; fan to effectively isolate vibration. hole to facilitate access;
2 Pulley and push structure to facilitate quick
● 2 The motor is configured with a slide
● 2 The motor junction box is far away from

assembly and overhaul. rail regulating device, which can be coil inlet and outlet to prevent leakage of
adjusted to the best installation position electricity, safe and reliable.
to make maintenance convenient.
5
FUW Cabinet Fan Coil Units

Filter Wet film humidifier


■ The anti-mildew primary nylon filter of stand configuration Direct drainage working principle of wet film
with low initial resistance greatly reduces the unit power
consumption. It can be repeatedly cleaned and used easily ■ The clean tap water passing through the solenoid valve flows
and conveniently. directly into the water distributor at the top of the wet film
■ A lot of filter forms are available, aluminum, G3, G4, plate F5 through the water pipeline and then flows down along the wet
with medium efficiency, and PM2.5 special filter. film materal to wet the wet film materal. After drop to the drain
pain, it will be flowed down by the drain plug (water will not be
PM2.5 special filter recycled). "Hot air passing through the wet film is dampened
and cooled (which is called equal enthalpy humidification).
● The charged filter material is used. Static electricity makes During this process, some water in the wet film is evaporated
dust change the motion trail and crash into the obstacle, thus without consuming additional energy.
absorbing the dust. The filtering ratio of ultrafine particles with ■ The humidifier applies to humidification of civil buildings
the diameter of 2.5um is over 99%*. and industrial cooling and can satisfy places with common
Note: *It is based on the test result provided by the heating ventilation humidity requirements.
and air conditioning laborator y of Tongji University. Test
conditions: The dry bulb temperature is 25℃ to 26℃, the relative
Humidifying Water
水分配器 distributor
humidity is 58% to 60%, and the air speed is lower than 2.5 m/s.
material
加湿材料

Water
进水 inlet

Humidifying
加湿空气 air Water进风
inlet

Drainage
排水

PM2.5 special filter Wet film direct-drainage humidifier

Electric heater FUW professional software

■ It uses electric energy to heat air and the capacity can be ■ Professional selection software of fan coil units
adjusted by groups. The electric heater tube is made of ■ Providing multiple model selection configurations according
stainless steel tube wrapped with stainless steel sheets. to customers' requirements
■ The electric heater section provides the triple protection device ■ Automatically exporting unit performance parameters, CAD
of over high temperature protector (fuse wire and temperature appearance drawings and quotations
switch) and no-air power-off protector to eradicate the potential ■ Chinese and English versions
safety hazard arising from superheat of the heater.
■ It applies to winter fresh air pretreatment and prevents frost
cracking of the coil.


1 ●
2

Electric heater section



1 ●
2

Over high temperature No-air power-off


protection device protection device
Note: The standard power supply form is 380V/3N/50Hz. If the unit adopts
other power supply, please contact the factory in advance.

6
Cabinet Fan Coil Units FUW

Specifications of FUW-F (basic model)

Model FUW020F FUW030F FUW040F FUW050F FUW060F FUW070F FUW080F FUW100F FUW120F FUW150F

Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 10000 12000 15000

Ⅰ 150 150 150 150 150 150 225 225 225 225
External total pressure
Ⅱ 225 225 225 225 225 225 300 300 300 300
(Pa)
Ⅲ 300 300 300 300 300 300 400 400 400 400

4 rows (return air) 11.4 18.1 22.6 29.3 34.1 42.6 48.7 61.2 73.6 93.3

Nominal cooling capacity 4 rows (fresh air) 28.8 41.6 53.8 65.3 75.0 95.3 104.9 138.3 163.7 201.7
(kW) 6 rows (return air) 15.5 23.0 29.1 36.6 44.0 53.5 58.9 81.3 93.0 117.0

6 rows (fresh air) 35.3 53.8 66.6 89.1 101.1 130.4 142.5 177.3 210.4 260.2

4 rows (return air) 18.9 28.8 35.1 48.1 55.3 68.0 75.7 102.2 122.7 153.3

Nominal heating capacity 4 rows (fresh air) 31.1 45.8 56.8 79.6 86.5 108.9 121.6 166.1 199.3 249.2
(kW) 6 rows (return air) 21.8 32.3 40.9 54.9 61.6 78.0 86.9 122.9 144.8 180.9

6 rows (fresh air) 35.2 51.8 69.6 93.7 106.4 132.3 149.1 194.4 232.2 291.7

4 rows (return air) 0.54 0.86 1.07 1.40 1.63 2.03 2.32 2.92 3.50 4.44

Nominal chilled water flow 4 rows (fresh air) 1.37 1.98 2.56 3.11 3.57 4.54 5.00 6.59 7.79 9.60
(l/s) 6 rows (return air) 0.74 1.10 1.38 1.74 2.10 2.55 2.80 3.87 4.43 5.57

6 rows (fresh air) 1.68 2.56 3.17 4.24 4.81 6.21 6.79 8.44 10.02 12.39

4 rows (return air) 0.45 0.69 0.84 1.15 1.32 1.62 1.80 2.43 2.92 3.65

Nominal hot water flow 4 rows (fresh air) 0.74 1.09 1.35 1.89 2.06 2.59 2.89 3.96 4.75 5.93
(l/s) 6 rows (return air) 0.52 0.77 0.97 1.31 1.47 1.86 2.07 2.93 3.45 4.31

6 rows (fresh air) 0.84 1.23 1.66 2.23 2.53 3.15 3.55 4.63 5.53 6.94

4 rows (return air) 11.6 34.1 29.4 24.8 37.2 29.7 41.5 26.4 31.3 43.8

Nominal chilled water 4 rows (fresh air) 55.6 29.4 62.3 15.0 25.7 27.9 39.6 71.3 75.7 83.7
resistance (kPa) 6 rows (return air) 30.5 25.2 23.2 15.7 13.8 22.8 29.6 61.6 22.9 31.5

6 rows (fresh air) 20.0 55.6 40.8 67.5 96.0 95.0 125.0 81.0 74.8 82.6

Type Copper tube with a new type of corrugated aluminum fins

Piece/inch 12

Coil Working pressure (MPa) 1.6

Inlte/outlet pipe R1-1/2 R1-1/2 R1-1/2 R2 R2 R2 R2 R2-1/2 R2-1/2 R2-1/2

Condensing water pipe R1-1/4

Type/material High-efficiency forward centrifugal fans with multiple wings/galvanized steel plates

Fan Drive type V-belt transmission

Air discharge Front Invert discharge

Power supply 380V/3N ~ /50Hz

Type Three-phase asynchronous motor, insulation grade F and protection grade IP55

Motor I 0.55 0.55 0.75 1.1 1.1 (1.5) 1.5 2.2 3 3 4

Power (kW) II 0.55 0.55 (0.75) 0.75 (1.1) 1.5 1.5 1.5 2.2 3 3 (4) 5.5

III 0.55 0.75 1.1 1.5 1.5 (2.2) 2.2 2.2 (3) 4 4 5.5

Type Nylon filter with primary efficiency


Filter
Thickness (mm) 8

Cabinet Type Quality galvanized steel plate, with efficient soundproof and heat insulating material PE attached inside

Length (mm) 870 870 870 870 870 870 900 900 990 990

Dimension of basic model Width (mm) 800 1040 1300 1550 1800 1720 1800 2180 2270 2490

Height (mm) 498 498 498 498 498 620 620 620 715 740

Weight of basic model 4 rows 77 99 123 128 142 166 174 232 280 318
(kg) 6 rows 80 103 129 135 151 176 185 247 298 340

NOTE:
■ THE ABOVE PARAMETERS ARE FOR BASIC MODEL ONLY; IN CASE OF ANY SPECIAL REQUIREMENT, DAIKIN WILL PROVIDE A SPECIAL DESIGN.
■ NOMINAL RETURN AIR COOLING CONDITION: 27℃ (DB)/19.5℃ (WB); NOMINAL FRESH AIR COOLING CONDITION: 35℃ (DB)/28℃ (WB); NOMINAL CHILLED WATER
INLET AND OUTLET TEMPERATURES: 7℃ (WATER INLET); 12℃ (WATER OUTLET);
■ NOMINAL RETURN AIR HEATING CONDITION: 21℃ (DRY BULB); NOMINAL FRESH AIR HEATING CONDITION: 0℃ (DRY BULB); NOMINAL HEATING WATER INLET AND
OUTLET TEMPERATURES: 60℃ (WATER INLET); 50℃ (WATER OUTLET);
■ THE WEIGHT LISTED IN THE ABOVE TABLE IS NET WEIGHT OF UNIT. THE OPERATING WEIGHT MAY INCREASE BY ABOUT 20%;
■ VALUE INSIDE ( ) IN THE ABOVE TABLE IS THE MOTOR POWER OF UNIT WITH 6 ROWS OF COILS;
■ FOR THE MAXIMUM EXTERNAL TOTAL PRESSURE CORRESPONDING TO MOTOR POWER, SEE P27;
■ THE COIL CIRCUIT FOR UNITS WITH FULL RETURN AIR (THE BASIC MODEL IS "A") AND UNITS WITH FULL FRESH AIR (THE BASIC MODEL IS "B") MAY BE DIFFERENT.
PLEASE SPECIFY THE INLET AIR WORKING CONDITIONS WHILE PLACING ORDERS. DAIKIN CAN PROVIDE COMPUTER-AIDED MODEL SELECTION TO MEET
SPECIAL REQUIREMENTS. FOR DETAILED PARAMETERS, PLEASE REFER TO THE MODEL SELECTION RESULTS.

7
FUW Cabinet Fan Coil Units

Specifications of FUW-F (Optional parts parameters of the multi-function model)

Model FUW020F FUW030F FUW040F FUW050F FUW060F FUW070F FUW080F FUW100F FUW120F FUW150F

Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 10000 12000 15000

1 row (return air) 5.8 9.5 13.0 18.0 22.1 25.2 29.1 35.4 42.4 53.9

Nominal 1 row (fresh air) 10.7 16.4 21.8 30.6 37.4 42.6 49.0 60.3 72.3 90.4
heating
capacity (kW) 2 rows (return air) 11.3 17.9 24.6 31.3 38.0 44.0 50.6 53.7 77.1 97.2

2 rows (fresh air) 19.7 28.7 31.6 52.4 63.5 69.7 76.3 105.5 126.6 155.7

1 row (return air) 0.14 0.23 0.31 0.43 0.53 0.60 0.69 0.84 1.01 1.28

Nominal 1 row (fresh air) 0.25 0.39 0.52 0.73 0.89 1.01 1.17 1.44 1.72 2.15
heating water
flow (l/s) 2 rows (return air) 0.27 0.43 0.59 0.75 0.91 1.05 1.21 1.28 1.83 2.31

2 rows (fresh air) 0.47 0.68 0.75 1.25 1.51 1.66 1.82 2.51 3.02 3.71
Heating coil
1 row (return air) 0.5 0.7 1.4 3.3 5.5 4.8 6.4 7.5 6.6 9.3

Nominal 1 row (fresh air) 1.2 2.2 4.4 9.6 15.3 13.4 17.9 20.0 17.3 23.8
heating water
resistance
(kPa) 2 rows (return air) 1.7 4.3 8.9 16.3 27.0 22.8 30.3 33.6 32.2 44.5

2 rows (fresh air) 4.3 10.5 14.7 43.3 70.7 66.2 68.6 75.3 63.2 70.1

Type Copper tube with a new type of corrugated aluminum fins

Piece/inch 12

Coil Working pressure (MPa) 1.6

Inlte/outlet pipe R1-1/2 R1-1/2 R1-1/2 R1-1/2 R1-1/2 R1-1/2 R1-1/2 R2 R2 R2

Condensing water pipe R1-1/4

Electric heater Maximum electric heater power (kW) 6.7 10.1 13.4 16.8 20.1 23.5 26.8 33.5 40.2 50.3

Wet film humidifier Maximum humidifying capacity (kg/h) 9.1 13.4 18.1 22.5 27.0 32.0 33.8 41.8 49.3 60.9

Type G3/G4 / aluminum / flat F5 with medium efficiency / PM2.5 filter


Filter
Thickness (mm) 21/21/21/96/65

Length (mm) 970 970 970 970 970 970 1000 1000 1090 1090

Type I Width (mm) 800 1040 1300 1550 1800 1720 1800 2180 2270 2490

Height (mm) 498 498 498 498 498 620 620 620 715 740
Multi-function cabinet
dimensions
Length (mm) 1100 1100 1100 1100 1100 1100 1081 1102 1220 1220

Type II Width (mm) 800 1040 1300 1550 1800 1720 1800 2180 2270 2490

Height (mm) 498 498 498 498 498 620 620 620 715 740

NOTES:
■ THE ABOVE TABLE PROVIDES THE PARAMETERS OF ALL OPTIONAL PARTS FOR MULTI-FUNCTION MODELS; THE UNIT APPEARANCE DIMENSIONS, UNIT WEIGHT,
AND TOTAL EXTERNAL TOTAL PRESSURE VARY WITH THE REQUIREMENTS OF OPTIONAL FUNCTION SEGMENTS. FOR DETAILS, SEE THE MODEL SELECTION SOFTWARE
OF DAIKIN;
■ NOMINAL RETURN AIR HEATING CONDITION: 21℃ (DRY BULB); NOMINAL FRESH AIR HEATING CONDITION: 0℃ (DRY BULB); NOMINAL HEATING WATER INLET AND
OUTLET TEMPERATURES: 60℃ (WATER INLET); 50℃ (WATER OUTLET);
■ THE MULTI-FUNCTION TYPE-Ⅰ CABINET DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).

Quick reference table of parts resistance

Parts Nylon Aluminum G3 G4 F5 PM2.5 1 row 2 rows Wet film humidifier (100 mm)

Resistance (Pa) 25 50 92 110 128 119 21 49 50

NOTE:
■ THE RESISTANCE VALUE OF ABOVE PART IS THE AVERAGE VALUE OF EACH MODEL UNDER THE NOMINAL AIR FLOW. FOR THE DETAILED RESISTANCE UNDER
SPECIFIED AIR FLOW, SEE THE MODEL SELECTION RESULT.
■ IN THE BASIC MODEL CONFIGURATION, THE PARAMETERS OF THE HEATING COIL ARE THE SAME AS THOSE OF THE MULTI-FUNCTIONAL CONFIGURATION.

8
Cabinet Fan Coil Units FUW

Dimensions of FUW-F (basic model)

77 Q

P
N
M-60
M

Lifting hole 4-Ø12


30
T

B
57 A W
F S Water inlet Water outlet N L
30
pipe R pipe R
J
H

K
C
E

34
85

70

Condensate water 398


pipe R1-1/4
B+80 M

Return air Filter frame


Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet
inlet (optional)

L L N N P P R R W W
Model A B C M T H J K Q F E S
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)

FUW020F 870 800 498 1041 749 294 50 88 88 66 110 202 202 R1-1/2 R1-1/2 423 564 155 262 232 51 66

FUW030F 870 1040 498 1041 989 294 50 88 88 66 110 202 202 R1-1/2 R1-1/2 423 804 209 262 298 51 66

NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.

9
FUW Cabinet Fan Coil Units

Dimensions of FUW-F (basic model)

77 Q

P
N
M-60
M

Lifting hole 4-Ø12


30
T

B
57 A W
F S D S Water inlet Water outlet N L
30
pipe R pipe R
J
H

K
C
E

34
85

70

Condensate water
pipe R1-1/4 398
B+80 M

Cabinet Return air Filter frame


Dimensions Lifting holes Connection pipe Supply air outlet
dimensions inlet (optional)

L L N N P P R R W W
Model A B C M T H J K Q D F E S
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)

FUW040F 870 1300 498 1041 1249 294 50 88 88 66 110 202 202 R1-1/2 R1-1/2 423 1064 184 166 262 232 51 66

FUW050F 870 1550 498 1041 1499 294 50 88 88 66 110 202 202 R1-1/2 R2 423 1314 184 282 262 232 51 66

FUW060F 870 1800 498 1041 1749 294 50 88 88 66 110 202 202 R1-1/2 R2 423 1564 244 307 262 298 51 66

FUW070F 870 1720 620 1041 1669 395 60 88 88 66 110 202 202 R1-1/2 R2 545 1484 214 312 289 265 51 66

FUW080F 900 1800 620 1071 1749 395 60 88 88 66 110 202 202 R1-1/2 R2 545 1564 264 272 289 331 51 66

FUW100F 900 2180 620 1071 2129 392 64 91 83 82.5 137.5 205 197 R2 R2-1/2 545 1924 244 476 341 309 51 66

FUW120F 990 2270 715 1161 2219 456 65 91 83 82.5 137.5 205 197 R2 R2-1/2 640 2013 294 416 404 373 51 66

FUW150F 990 2490 740 1161 2439 519 64 91 83 82.5 137.5 205 197 R2 R2-1/2 665 2223 294 516 404 373 51 66

NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.

10
Cabinet Fan Coil Units FUW

Dimensions of FUW-F (type-I cabinet of multi-function model)

77 Q

P
N
M-60
M

Lifting hole 4-Ø12


30
T

B 57 W
A
30 Water inlet Water outlet N
F S L
pipe R pipe R
J
H

K
C
E

34
85

70

Condensate water
B+80 pipe R1-1/4 617
M

Return air
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Filter frame (optional)
inlet

W
L L N N P P R R W W
Model A B C M T H J K Q F E S (G3/G4+F5,
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
G3/G4+PM2.5)

FUW020F 970 800 498 1230 749 294 50 88 88 66 110 187 187 R1-1/2 R1-1/2 423 564 155 262 232 51 66 165

FUW030F 970 1040 498 1230 989 294 50 88 88 66 110 187 187 R1-1/2 R1-1/2 423 804 209 262 298 51 66 165

NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ THE MULTI-FUNCTION TYPE-Ⅰ CABINET DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).

11
FUW Cabinet Fan Coil Units

Dimensions of FUW-F (type-I cabinet of multi-function model)

77 Q

P
N
M-60
M

Lifting hole 4-Ø12


30
T

B 57 A W
30 Water inlet Water outlet N L
F S D S
pipe R pipe R
J
H

K
C
E

34
85

70

Condensate water
617
B+80 pipe R1-1/4
M

Return air
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Filter frame (optional)
inlet

W
L L N N P P R R W W
Model A B C M T H J K Q D F E S (G3/G4+F5,
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
G3/G4+PM2.5)

FUW040F 970 1300 498 1230 1249 294 50 88 88 66 110 187 187 R1-1/2 R1-1/2 423 1064 184 166 262 232 51 66 165

FUW050F 970 1550 498 1230 1499 294 50 88 88 66 110 187 187 R1-1/2 R2 423 1314 184 282 262 232 51 66 165

FUW060F 970 1800 498 1230 1749 294 50 88 88 66 110 187 187 R1-1/2 R2 423 1564 244 307 262 298 51 66 165

FUW070F 970 1720 620 1230 1669 395 60 88 88 66 110 187 187 R1-1/2 R2 545 1484 214 312 289 265 51 66 165

FUW080F 1000 1800 620 1260 1749 395 60 88 88 66 110 187 187 R1-1/2 R2 545 1564 264 272 289 331 51 66 165

FUW100F 1000 2180 620 1260 2129 392 64 91 83 82.5 137.5 190 182 R2 R2-1/2 545 1924 244 476 341 309 51 66 165

FUW120F 1090 2270 715 1350 2219 456 65 91 83 82.5 137.5 190 182 R2 R2-1/2 640 2013 294 416 404 373 51 66 165

FUW150F 1090 2490 740 1350 2439 519 64 91 83 82.5 137.5 190 182 R2 R2-1/2 665 2223 294 516 404 373 51 66 165

NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ THE MULTI-FUNCTION TYPE-Ⅰ CABINET DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).

12
Cabinet Fan Coil Units FUW

Dimensions of FUW-F (type-II cabinet of multi-function model)

77 Q

P
L1
N1

L
I
L2
N2
M-60
M

Lifting hole 4-Ø12


30
T

57 A W
L
B Water outlet pipeR1 L2 L1

F S 30 Water outlet pipeR2 N2 N1


J
H

K
C
E

34
85

70

Condensate water
pipe R1-1/4 I
Water inlet
B+80 Water inlet pipe R2 pipe R1
M

Cabinet Lifting Return air Supply air


Dimensions Connection pipe Filter frame (optional)
dimensions holes inlet outlet

W
N1 N2 N2 R2 R2 W W
Model A B C M T H I J L L1 L2 P R1 K Q F E S (G3/G4+F5,
(1/2) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
G3/G4+PM2.5)

FUW020F 1100 800 498 1360 749 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R1-1/2 423 564 155 262 232 51 66 165

FUW030F 1100 1040 498 1360 989 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R1-1/2 423 804 209 262 298 51 66 165

NOTES:
■ THE UNIT OF CONNECTON PIPE (R1/R2) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ FOR HEATING SECTION SELECTION FOR THE MULTI-FUNCTION TYPE-II CABINET, ONLY ONE CAN BE SELECTED BETWEEN HEATING COIL AND ELECTRIC HEATER.
WHEN ELECTRIC HEATER IS SELECTED, THE FILTER IS CONFIGURED WITH AN ALUMINUM ACCORDING TO THE STANDARD, AND THE INLET AND OUTLET WATER
PIPES IN THE FIGURE ARE DOTTED LINES AND DO NOT EXIST; WHEN HEATING COIL IS SELECTED, THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE
SOLID LINES AND EXIST. FOR THE DETAILED PIPE ORIENTATION DIMENSIONS, SEE THE ABOVE TABLE.

13
FUW Cabinet Fan Coil Units

Dimensions of FUW-F (type-II cabinet of multi-function model)

77 Q

P
L1
N1
L
I
L2
N2
M-60
M

Lifting hole 4-Ø12


30
T

57 A W
L

B Water outlet pipeR1 L2 L1

F S D S 30 Water outlet pipeR2 N2 N1


JH

K
C
E

34
70
85

Condensate water
pipe R1-1/4 I
Water inlet
B+80 Water inlet pipe R2 pipe R1
M

Return air
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Filter frame (optional)
inlet

W
N1 N2 N2 R2 R2 W W
Model A B C M T H I J L L1 L2 P R1 K Q D F E S (G3/G4+F5,
(1/2) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
G3/G4+PM2.5)

FUW040F 1100 1300 498 1360 1249 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R1-1/2 423 1064 184 166 262 232 51 66 165

FUW050F 1100 1550 498 1360 1499 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R2 423 1314 184 282 262 232 51 66 165

FUW060F 1100 1800 498 1360 1749 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R2 423 1564 244 307 262 298 51 66 165

FUW070F 1100 1720 620 1360 1669 395 717 60 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R2 545 1484 214 312 289 265 51 66 165

FUW080F 1081 1800 620 1352 1749 395 679 60 272 91 115 66 66 110 214 R1-1/2 R1-1/2 R2 545 1564 264 272 289 331 51 66 165

FUW100F 1102 2180 620 1372 2129 392 699 64 277 84 111 82.5 82.5 137.5 213 R2 R2 R2-1/2 545 1924 244 476 341 309 51 66 165

FUW120F 1220 2270 715 1480 2219 456 737 65 321 91 147 82.5 82.5 137.5 201 R2 R2 R2-1/2 640 2013 294 416 404 373 51 66 165

FUW150F 1220 2490 740 1480 2439 519 737 64 321 83 155 82.5 82.5 137.5 203 R2 R2 R2-1/2 665 2223 294 516 404 373 51 66 165

NOTES:
■ THE UNIT OF CONNECTION PIPE (R1/R2) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE THE ABOVE FIGURE.
■ FOR HEATING SECTION SELECTION FOR THE MULTI-FUNCTION TYPE-II CABINET, ONLY ONE CAN BE SELECTED BETWEEN HEATING COIL AND ELECTRIC HEATER. WHEN ELECTRIC HEATER IS
SELECTED, THE FILTER IS CONFIGURED WITH AN ALUMINUM ACCORDING TO THE STANDARD, AND THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE DOTTED LINES AND DO NOT EXIST; WHEN
HEATING COIL IS SELECTED, THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE SOLID LINES AND EXIST. FOR THE DETAILED PIPE ORIENTATION DIMENSIONS, SEE THE ABOVE TABLE.

14
Cabinet Fan Coil Units FUW

Dimensions of FUW-F (basic model with mixing box)

Qty and type of air inlet shall be


subject to the actual selection
Lifting hole 4-Ø12

Water inlet Water outlet


pipe R pipe R

Condensate water
pipe R1-1/4

Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet

L L N N P P R R
Model A B C M T H J F E S Inlet 1 Inlet 2
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6)

FUW020F 1392 800 498 1506 749 294 50 610 610 66 110 667 667 R1-1/2 R1-1/2 155 262 232 200*300 200*430

FUW030F 1392 1040 498 1506 989 294 50 610 610 66 110 667 667 R1-1/2 R1-1/2 209 262 298 200*350 200*630

NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.

15
FUW Cabinet Fan Coil Units

Dimensions of FUW-F (basic model with mixing box)

Qty and type of air inlet shall be


subject to the actual selection
Lifting hole 4-Ø12

Water inlet Water outlet


pipe R pipe R

Condensate water
pipe R1-1/4

Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet

L L N N P P R R
Model A B C M T H J D F E S Inlet 1 Inlet 2
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6)

FUW040F 1392 1300 498 1506 1249 294 50 610 610 66 110 667 667 R1-1/2 R1-1/2 184 166 262 232 250*400 250*750

FUW050F 1392 1550 498 1506 1499 294 50 610 610 66 110 667 667 R1-1/2 R2 184 282 262 232 250*500 250*910

FUW060F 1392 1800 498 1506 1749 294 50 610 610 66 110 667 667 R1-1/2 R2 244 307 262 298 250*500 250*1000

FUW070F 1392 1720 620 1506 1669 395 60 610 610 66 110 667 667 R1-1/2 R2 214 312 289 265 250*630 250*1250

FUW080F 1422 1800 620 1536 1749 395 60 610 610 66 110 667 667 R1-1/2 R2 264 272 289 331 250*700 250*1350

FUW100F 1422 2180 620 1536 2129 392 64 613 605 82.5 137.5 670 662 R2 R2-1/2 244 476 341 309 250*910 250*1710

FUW120F 1512 2270 715 1626 2219 456 65 613 605 82.5 137.5 670 662 R2 R2-1/2 294 416 404 373 270*950 270*1870

FUW150F 1512 2490 740 1626 2439 519 64 613 605 82.5 137.5 670 662 R2 R2-1/2 294 516 404 373 300*1070 300*2100

NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.

16
Cabinet Fan Coil Units FUW

Dimensions of FUW-F (type-I cabinet of multi-function model with mixing box)

Qty and type of air inlet shall be


subject to the actual selection
Lifting hole 4-Ø12

Water inlet Water outlet


pipe R pipe R

Condensate water
pipe R1-1/4

Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet

L L N N P P R R
Model A B C M T H J F E S Inlet 1 Inlet 2
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6)

FUW020F 1492 800 498 1695 749 294 50 610 610 66 110 652 652 R1-1/2 R1-1/2 155 262 232 200*300 200*430

FUW030F 1492 1040 498 1695 989 294 50 610 610 66 110 652 652 R1-1/2 R1-1/2 209 262 298 200*350 200*630

NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ THE MULTI-FUNCTION TYPE-I CABINET WITH MIXING BOX DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.

17
FUW Cabinet Fan Coil Units

Dimensions of FUW-F (type-I cabinet of multi-function model with mixing box)

Qty and type of air inlet shall be


subject to the actual selection
Lifting hole 4-Ø12

Water inlet Water outlet


pipe R pipe R

Condensate water
pipe R1-1/4

Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet

L L N N P P R R
Model A B C M T H J D F E S Inlet 1 Inlet 2
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6)

FUW040F 1492 1300 498 1695 1249 294 50 610 610 66 110 652 652 R1-1/2 R1-1/2 184 166 262 232 250*400 250*750

FUW050F 1492 1550 498 1695 1499 294 50 610 610 66 110 652 652 R1-1/2 R2 184 282 262 232 250*500 250*910

FUW060F 1492 1800 498 1695 1749 294 50 610 610 66 110 652 652 R1-1/2 R2 244 307 262 298 250*500 250*1000

FUW070F 1492 1720 620 1695 1669 395 60 610 610 66 110 652 652 R1-1/2 R2 214 312 289 265 250*630 250*1250

FUW080F 1522 1800 620 1725 1749 395 60 610 610 66 110 652 652 R1-1/2 R2 264 272 289 331 250*700 250*1350

FUW100F 1522 2180 620 1726 2129 392 64 613 605 82.5 137.5 655 647 R2 R2-1/2 244 476 341 309 250*910 250*1710

FUW120F 1612 2270 715 1815 2219 456 65 613 605 82.5 137.5 655 647 R2 R2-1/2 294 416 404 373 270*950 270*1870

FUW150F 1612 2490 740 1815 2439 519 64 613 605 82.5 137.5 655 647 R2 R2-1/2 294 516 404 373 300*1070 300*2100

NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ THE MULTI-FUNCTION TYPE-I CABINET WITH MIXING BOX DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.

18
Cabinet Fan Coil Units FUW

Dimensions of FUW-F (type-II cabinet of multi-function model with mixing box)

Qty and type of air inlet shall be


Lifting hole 4-Ø12 subject to the actual selection

Water outlet Water outlet


pipe R2 pipe R1

Condensate water Water inlet Water inlet


pipe R1-1/4 pipe R2 pipe R1

Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet

N1 N2 N2 R2 R2
Model A B C M T H I J L1 L2 P R1 F E S Inlet 1 Inlet 2
(1/2) (1/2/4) (6) (1/2) (4/6)

FUW020F 1622 800 498 1825 749 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R1-1/2 155 262 232 200*300 200*430

FUW030F 1622 1040 498 1825 989 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R1-1/2 209 262 298 200*350 200*630

NOTES:
■ THE UNIT OF CONNECTON PIPE (R1/R2) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ FOR HEATING SECTION SELECTION FOR THE MULTI-FUNCTION TYPE-II CABINET WITH MIXING BOX, ONLY ONE CAN BE SELECTED BETWEEN HEATING COIL AND
ELECTRIC HEATER. WHEN ELECTRIC HEATER IS SELECTED, THE FILTER IS CONFIGURED WITH AN ALUMINUM ACCORDING TO THE STANDARD, AND THE INLET
AND OUTLET WATER PIPES IN THE FIGURE ARE DOTTED LINES AND DO NOT EXIST; WHEN HEATING COIL IS SELECTED, THE INLET AND OUTLET WATER PIPES IN
THE FIGURE ARE SOLID LINES AND EXIST. FOR THE DETAILED PIPE ORIENTATION DIMENSIONS, SEE THE ABOVE TABLE.
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.

19
FUW Cabinet Fan Coil Units

Dimensions of FUW-F (type-II cabinet of multi-function model with mixing box)

Qty and type of air inlet shall be


subject to the actual selection
Lifting hole 4-Ø12

Water outlet Water outlet


pipe R2 pipe R1

Condensate water Water inlet Water inlet


pipe R1-1/4 pipe R2 pipe R1

Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet

N1 N2 N2 R2 R2
Model A B C M T H I J L1 L2 P R1 D F E S Inlet 1 Inlet 2
(1/2) (1/2/4) (6) (1/2) (4/6)

FUW040F 1622 1300 498 1825 1249 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R1-1/2 184 166 262 232 250*400 250*750

FUW050F 1622 1550 498 1825 1499 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R2 184 282 262 232 250*500 250*910

FUW060F 1622 1800 498 1825 1749 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R2 244 307 262 298 250*500 250*1000

FUW070F 1622 1720 620 1825 1669 395 1182 60 610 117 66 66 110 146 R1-1/2 R1-1/2 R2 214 312 289 265 250*630 250*1250

FUW080F 1603 1800 620 1817 1749 395 1144 60 613 115 66 66 110 157 R1-1/2 R1-1/2 R2 264 272 289 331 250*700 250*1350

FUW100F 1624 2180 620 1837 2129 392 1164 64 606 111 82.5 82.5 137.5 156 R2 R2 R2-1/2 244 476 341 309 250*910 250*1710

FUW120F 1742 2270 715 1945 2219 456 1202 65 613 147 82.5 82.5 137.5 144 R2 R2 R2-1/2 294 416 404 373 270*950 270*1870

FUW150F 1742 2490 740 1945 2439 519 1202 64 605 155 82.5 82.5 137.5 146 R2 R2 R2-1/2 294 516 404 373 300*1070 300*2100

NOTES:
■ THE UNIT OF CONNECTON PIPE (R1/R2) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE THE ABOVE FIGURE.
■ FOR HEATING SECTION SELECTION FOR THE MULTI-FUNCTION TYPE-II CABINET WITH MIXING BOX, ONLY ONE CAN BE SELECTED BETWEEN HEATING COIL AND ELECTRIC HEATER. WHEN
ELECTRIC HEATER IS SELECTED, THE FILTER IS CONFIGURED WITH AN ALUMINUM ACCORDING TO THE STANDARD, AND THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE DOTTED
LINES AND DO NOT EXIST; WHEN HEATING COIL IS SELECTED, THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE SOLID LINES AND EXIST. FOR THE DETAILED PIPE ORIENTATION
DIMENSIONS, SEE THE ABOVE TABLE.
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.

20
Cabinet Fan Coil Units FUW

FUW vertical cabinet fan coil unit

The FUW vertical cabinet fan coil unit adopts an electrostatic sprayed cabinet of high strength, and provides professional model selection and
a lot of optional functions such as heating coil and wet film humidifier. It can meet requirements of wide customers. Ten models of FUW vertical
cabinet fan coil units are available, with the air flow in the range of 4000 to 25000 m3/h, cooling capacity in the range of 23 to 420 kW, and the
external total pressure in the range of 90 to 550 Pa.

Nomenclature
FUW  080  V  R  08  -4  L  -F  T  D  E
Export
Internal identification code
Air supply mode:
T -- Top air outlet
Power Supply:
F -- 380V/3N~/50Hz
R -- 380V/3N~/60Hz
P -- 208-230V/3N~/60Hz
Q -- 460V/3N~/60Hz
Pipe orientation:
L -- Left connected pipe
R -- Right connected pipe
Rows of coils:
4 -- 4 rows of coils
6 -- 6 rows of coils
External total pressure:
08 -- 80Pa
15 -- 150Pa
22 -- 220Pa
30 -- 300Pa
Application features:
R -- Return air
F -- Fresh air
Structure type: V indicates the vertical type
Air flow code: 080-air flow is 8000m3/h (air flow = air flow code*100m3/h)
Model name and code: FUW-cabinet fan coil unit

Judgment of the left type and right type: if the pipe is connected on the
Air flow
left when you face the airflow direction, it is the left type; otherwise it is
direction
the right type. This unit
adopts the left

Left
connected
pipe.

connected
pipe

Diagram for judging the


left/right type
21
FUW Cabinet Fan Coil Units

Features
Quality materials and elaborate design

Cabinet Heat exchanger

The electro galvanized plate treated with Mechanically expanded copper tubes
electrostatic spraying of pure polyester with a thin wall and a new type of fins
is used to realize efficient anticorrosion. produced using leading-edge impor ted
The heat insulating material is new XPE OAK manufacturing facilities achieve close
material with excellent heat insulating and fitting between copper tubes and fins,
sound absorption effect, which does not thus ensuring the optimal heat exchange
absorb water and can effectively prevent efficiency of coils and paving the way for
cold bridge. efficient operation of the unit.

Fan Filter
A high-efficiency forward fan with multiple It adopts the anti-mildew primary efficiency
wings provides a large air flow and stable filter with low initial resistance, which
and reliable performance with low noises. greatly reduces the unit power consumption
The fan bearing does not require adding and can be easily cleaned and conveniently
lubricant, thus saving maintenance cost used.
for customers.

Eradicating condensation dripping Performance


■ Heat preservation sponge attached to FUW units feature a high external total
the inlet/outlet water pipe of coil pressure, large cooling capacity, low noises,
■ Heat preservation sponge attached compact and simple structure, and easy
between the air outlet and air port plate installation and maintenance.

FUW professional software for model selection

■ Professional model selection software of fan coil units


■ Providing multiple model selection configurations according to
customers' requirements
■ Automatically expor ting unit performance parameters, CAD
appearance drawings and quotations
■ Chinese and English versions

Optional parts for unit

Standard configuration Optional configuration


Function section
Primary filter section Cooling coil section Fan section Heating coil section Wet film humidifying section

Combination type √ √ √ √ √

Notes:
1. Non-woven fabric filters are available for the selected unit as needed (nylon filter is adopted for the standard configuration);
2. Cooling coil and heating coil can’t be selected at the same time.
3. The unit power and external total pressure may be changed accordingly;
4. The length of the unit may be increased as actually needed. The detailed parameters are subject to the software model selection results.

22
Cabinet Fan Coil Units FUW

Specifications of FUW vertical cabinet fan coil unit

Model FUW040V FUW050V FUW060V FUW080V FUW100V FUW120V FUW150V FUW180V FUW200V FUW250V

Nominal air flow (m3/h) 4000 5000 6000 8000 10000 12000 15000 18000 20000 25000
Ⅰ - 80 - - - - - - - -

External total Ⅱ 150 150 150 150 150 150 - 150 150 150
pressure (Pa) Ⅲ 220 220 220 220 220 220 220 220 220 220
Ⅳ 300 300 300 300 300 300 300 300 300 300
4 rows of coils (return air) 23 31 35 51 59 79 90 116 125 150

Nominal cooling 4 rows of coils (fresh air) 50 68 76 111 128 177 205 256 273 325
capacity (kW) 6 rows of coils (return air) 28 39 44 63 75 100 117 144 156 185
6 rows of coils (fresh air) 64 86 96 142 167 219 252 319 343 420
4 rows of coils (return air) 36 48 55 82 97 126 149 185 201 245

Nominal heating 4 rows of coils (fresh air) 58 76 87 129 153 199 237 294 319 398
capacity (kW) 6 rows of coils (return air) 44 57 66 95 115 145 176 214 234 289
6 rows of coils (fresh air) 69 90 105 150 182 229 279 338 369 461
4 rows of coils (return air) 1.10 1.48 1.67 2.43 2.82 3.77 4.30 5.54 5.97 7.16
Nominal chilled
4 rows of coils (fresh air) 2.39 3.25 3.63 5.30 6.11 8.45 9.79 12.22 13.03 15.51
water flow
6 rows of coils (return air) 1.34 1.86 2.10 3.01 3.58 4.77 5.58 6.87 7.45 8.83
(l/s)
6 rows of coils (fresh air) 3.05 4.11 4.58 6.78 7.97 10.45 12.03 15.23 16.37 20.05
4 rows of coils (return air) 0.86 1.15 1.31 1.96 2.32 3.01 3.56 4.42 4.80 5.85
Nominal heating
4 rows of coils (fresh air) 1.38 1.81 2.08 3.08 3.65 4.75 5.66 7.02 7.61 9.50
water flow
6 rows of coils (return air) 1.05 1.36 1.58 2.27 2.74 3.46 4.20 5.11 5.58 6.90
(l/s)
6 rows of coils (fresh air) 1.65 2.15 2.51 3.58 4.34 5.47 6.66 8.07 8.81 11.00
4 rows of coils (return air) 40.9 62.8 78.5 35.0 44.7 30.7 38.8 56.0 63.9 36.3
Cooling conditions
4 rows of coils (fresh air) 68.1 41.1 50.5 22.7 29.1 45.0 58.1 67.7 67.6 76.9
Water resistance
6 rows of coils (return air) 29.1 45.0 56.9 26.4 35.1 48.4 63.9 41.8 48.2 30.9
(kPa)
6 rows of coils (fresh air) 62.2 79.0 78.8 49.3 65.3 81.5 81.3 74.1 84.6 95.0
Type Copper tube with a new type of corrugated aluminum fins
Piece/inch 12
Coil Working pressure (MPa) 1.6
Size of inlet/outlet water pipe connector R1-1/2 R1-1/2 R1-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2
Size of condensate water pipe connector R1-1/4
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/galvanized steel plates
Fan Transmission type V-belt transmission
Air discharge Top discharge
Power supply 380V/3N ~ /50Hz
Type Three-phase asynchronous motor, insulation grade F and protection grade IP55
Ⅰ - 0.75(1.1) - - - - - - - -
Motor
Ⅱ 1.1(1.1) 1.1(1.1) 1.5(2.2) 1.5(1.5) 2.2(3.0) 2.2(2.2) - 4.0(4.0) 4.0(5.5) 5.5(5.5)
Power (kW)
Ⅲ 1.1(1.5) 1.1(1.5) 1.5(2.2) 1.5(2.2) 3.0(3.0) 2.2(3.0) 4.0(4.0) 4.0(4.0) 5.5(5.5) 5.5(7.5)
Ⅳ 1.5(1.5) 1.5(1.5) 2.2(2.2) 2.2(2.2) 3.0(3.0) 3.0(3.0) 4.0(5.5) 5.5(5.5) 5.5(7.5) 7.5(7.5)
Type Nylon filter with primary efficiency
Filter
Thickness (mm) 8
Cabinet Type Galvanized steel plate of electrostatic coating, with efficient soundproof and heat insulating material PE attached inside
Length (mm) 935 1135 1135 1350 1350 1774 1774 2124 2124 2476
Unit cabinet
Width (mm) 585 655 655 736 736 956 956 955 955 955
dimensions
Height (mm) 1082 1320 1320 1676 1676 2036 2036 2070 2070 2191
4 rows of coils 135 185 188 265 269 440 450 556 571 665
Unit weight (kg)
6 rows of coils 146 199 202 285 289 473 483 598 613 716

NOTES:
■ THE ABOVE PARAMETERS ARE STANDARD MODEL PARAMETERS; IN CASE OF ANY SPECIAL REQUIREMENT, DAIKIN WILL PROVIDE A SPECIAL DESIGN;
■ NOMINAL RETURN AIR COOLING CONDITION: 27℃ (DRY BULB)/19.5℃ (WET BULB); NOMINAL FRESH AIR COOLING CONDITION: 34℃ (DRY BULB)/28℃ (WET BULB);
NOMINAL CHILLED WATER INLET AND OUTLET TEMPERATURES: 7℃ (WATER INLET); 12℃ (WATER OUTLET);
■ NOMINAL RETURN AIR HEATING CONDITION: 21℃ (DRY BULB); NOMINAL FRESH AIR HEATING CONDITION: 0℃ (DRY BULB); NOMINAL HEATING WATER INLET AND
OUTLET TEMPERATURES: 60℃ (WATER INLET); 50℃ (WATER OUTLET);
■ THE WEIGHT LISTED IN THE ABOVE TABLE IS THE NET WEIGHT OF UNIT. THE OPERATING WEIGHT WILL INCREASE BY ABOUT 20%;
■ VALUE INSIDE ( ) IN THE ABOVE TABLE IS THE MOTOR POWER OF UNIT WITH 6 ROWS OF COILS.
■ FOR THE MAXIMUM EXTERNAL TOTAL PRESSURE CORRESPONDING TO MOTOR POWER, SEE P22;
■ THE COIL CIRCUIT FOR UNITS WITH FULL RETURN AIR ("R") AND UNITS WITH FULL FRESH AIR ("F") MAY BE DIFFERENT. PLEASE SPECIFY THE INLET AIR WORKING
CONDITIONS WHILE PLACING ORDERS. DAIKIN CAN PROVIDE COMPUTER-AIDED MODEL SELECTION TO MEET SPECIAL REQUIREMENTS. FOR DETAILED PARAMETERS,
PLEASE SEE THE MODEL SELECTION RESULTS.

23
FUW Cabinet Fan Coil Units

Dimensions of FUW vertical cabinet fan coil unit

Chilled water
Junction outlet pipe
box
H

Chilled water
inlet pipe

T L 50 R
Condensate water
outlet pipe R1-1/4

Unit: mm

Unit Supply air outlet Return air inlet Clearance Base hole positioning
dimensions Cabinet dimensions Pipe orientation dimensions
dimensions dimensions length of unit dimensions
Model A B C L L T T
D E F J K H G R M N
(length) (width) (height) (4 rows) (6 rows) (4 rows) (6 rows)

FUW040V 935 585 1082 335 293 200 840 592 446 182 66 110 236 192 1055 968 520

FUW050V 1135 655 1320 395 341 254 1040 692 546 152 66 110 326 282 1255 1168 590

FUW060V 1135 655 1320 395 341 254 1040 692 546 152 66 110 326 282 1255 1168 590

NOTE: THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, DAMPER/FLANGE, FILTER AND HANGING ROD). FOR
DETAILS, SEE THE ABOVE FIGURE.

24
Cabinet Fan Coil Units FUW

Dimensions of FUW vertical cabinet fan coil unit

Chilled water
Junction outlet pipe
box
K
H

Chilled water
inlet pipe

T L 50

Condensate water
outlet pipe R1-1/4
R

Unit: mm

Unit Supply air outlet Return air inlet Forklift hole Clearance Base hole positioning
dimensions Cabinet dimensions Pipe orientation dimensions
dimensions dimensions position length of unit dimensions
Model A B C L L T T
D E F J K H G Q R M N P
(length) (width) (height) (4 rows) (6 rows) (4 rows) (6 rows)
FUW080V 1350 736 1676 471 404 281 1256 873 720 182 83 137 343 288 500 1493 1400 675 197

FUW100V 1350 736 1676 471 404 281 1256 873 720 182 83 137 343 288 500 1493 1400 675 197

FUW120V 1774 956 2036 561 482 483 1680 1112 950 480 83 137 228 184 655 1902 1826 907 334

FUW150V 1774 956 2036 561 482 483 1680 1112 950 480 83 137 228 184 655 1902 1826 907 334

NOTE: THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.

25
FUW Cabinet Fan Coil Units

Dimensions of FUW vertical cabinet fan coil unit

S D S

Chilled water
Junction outlet pipe
box
K
H

Chilled water
inlet pipe
269

Condensate water
outlet pipe R1-1/4
T L 50

Unit: mm

Unit Supply air outlet Return air inlet Forklift hole Clearance Base hole positioning
dimensions Cabinet dimensions Pipe orientation dimensions
dimensions dimensions position length of unit dimensions
Model A B C L L T T
S D E J K H Q R M N P
(length) (width) (height) (4 rows) (6 rows) (4 rows) (6 rows)
FUW180V 2124 955 2070 476 382 406 2032 1253 1077 83 137 224 180 1003 2247 2175 907 334

FUW200V 2124 955 2070 476 382 406 2032 1253 1077 83 137 224 180 1003 2247 2175 907 334

FUW250V 2476 955 2191 561 454 478 2379 1253 1077 83 137 224 180 701 2597 2525 907 660

NOTE: THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.

26
Cabinet Fan Coil Units FUW

Motor power - Quick reference for maximum external total pressure

FUW horizontal cabinet fan coil unit

Model FUW020F FUW030F FUW040F FUW050F FUW060F FUW070F FUW080F FUW100F FUW120F FUW150F

Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 10000 12000 15000
Motor power
Rows External total pressure (Pa)
(kW)
0.55 400 250 100

0.75 600 350 225

1.1 550 350 200 150 100

1.5 550 400 300 250 200

4 rows of cooling coil 2.2 700 500 450 400 150 125

3 550 700 550 350 300

4 850 600 500 275

5.5 800 765 550

7.5 780 800

0.55 400 200

0.75 550 300 175

1.1 500 300 150 100

1.5 500 350 275 225 150

6 rows of cooling coil 2.2 650 450 450 300 75

3 500 650 500 300 250

4 800 550 450 225

5.5 750 715 500

7.5 730 750

NOTES:
■ THE ABOVE TABLE PROVIDES THE MAXIMUM EXTERNAL TOTAL PRESSURE OF UNIT (INCLUDING THE STANDARD CONFIGURATION FILTER AND COOLING COIL)
CORRESPONDING TO THE MOTOR POWER. TO ADD A FUNCTION SECTION, REDUCE THE RESISTANCE OF THE CORRESPONDING PART. FOR THE DETAILED
RESISTANCE VALUES, SEE THE PARAMETER TABLE ON P8. FOR EXAMPLE, THE MOTOR POWER SELECTED FOR FUW040 IS 1.1KW, THERE ARE 4 ROWS OF
COOLING COILS, AND THE CORRESPONDING MAXIMUM EXTERNAL TOTAL PRESSURE IS 350PA. IF FILTER F5 IS ADDED FOR THE UNIT, THE RESISTANCE OF F5 IS
128PA ACCORDING TO THE TABLE ON P8, AND THE CORRESPONDING MAXIMUM EXTERNAL TOTAL PRESSURE IS 350-128=222PA.

FUW vertical cabinet fan coil unit

Model FUW040V FUW050V FUW060V FUW080V FUW100V FUW120V FUW150V FUW180V FUW200V FUW250V

Nominal air flow (m3/h) 4000 5000 6000 8000 10000 12000 15000 18000 20000 25000
Motor power
Rows of coils External total pressure (Pa)
(kW)
0.75 90

1.1 270 240 90

1.5 470 390 230 230

2.2 460 420 200 230


4 rows of cooling coils
3 430 420 160

4 360 270 160

5.5 450 350 240

7.5 430

0.75

1.1 190 170

1.5 370 330 150 180

2.5 370 370 130 180


6 rows of cooling coils
3 350 370

4 270 230

5.5 550 400 270 170

7.5 500 360

27
FUW Cabinet Fan Coil Units

Precautions

■ Appropriate water seal should be fitted to ensure the smooth drainage of condensate water during the installation. The installation diagram
for water seal is shown in Fig 1.

Connected to the drain pipe

Not greater
than 1/2H

Note: H>Maximum negative pressure of unit (1mmH2O=9.8Pa) + 20 mm

Figure 1 Water seal installation

28
Warning ● Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in
a particular country. Prior to purchase, please therefore confirm with your local authorized importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable
for use, in the region where the product will be used. This statement does not purport to exclude,
restrict or modify the application of any local legislation.
● Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
● Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
● Read the User’s Manual carefully before using this product. The User’s Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the
unit close to the sea shore, contact your local distributor.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/

© All rights reserved

Printed with soy ink.

Literature No.: CA-FUW-F(AC)-202101


Supersedes: CA-FUW-201901A