Daikin FUW Cabinet Fan Coil Unit
Daikin FUW Cabinet Fan Coil Unit
Daikin FUW Cabinet Fan Coil Unit
Vertical Unit
Model: FUW040V-FUW250V
Air Flow: 4000m3/h-25000m3/h
FUW Cabinet Fan Coil Units
Overview
DAIKIN FUW cabinet fan coil unit adopts high-strength cabinet, professionally selected and precision machined coil, efficient fan with low noises
and filter to better meet wide customers' requirements for air handling units and save the indoor space for customers. FUW products showcase the
characteristics such as high external total pressure, large cooling capacity, compact size and low noises and can be widely applied to central air
conditioning projects such as hotels, shopping malls, airports, hospitals, factories and office buildings, especially suitable for occasions where the
installation space is restricted, the noise requirement is high, and an old house is reconstructed.
小型商业写字楼
Commercial office building Shopping mall Light industrial workshop
Contents
Motor power - Quick reference for maximum external total pressure .............................................................. 27
Precautions...................................................................................................................................................... 28
Nomenclature
FUW 080 F A A E L A A - 0 0 F E
Export
Power Supply:
F -- 380V/3N~/50Hz
R -- 380V/3N~/60Hz
P -- 208-230V/3N~/60Hz
Q -- 460V/3N~/60Hz
Electric heater:
0 -- No electric heater
A -- With electric heater
Control options:
0 -- No control
1 -- Local start-up cabinet
2 -- Remote start-up cabinet
3 -- Local control cabinet
4 -- Remote control cabinet
Fan motor options:
- -- Fixed-frequency belt transmission
V -- Variable-frequency belt transmission
Filter type:
A -- Nylon filter
B -- G3 flat filter
C -- Aluminum (standard configuration for electric heater)
D -- G3 flat filter + F5 flat medium filter
E -- G3 flat filter + PM2.5 special filter
Drain pain material and aluminum foil material:
A -- Galvanized steel plate + common aluminum
B -- Galvanized steel plate + hydrophilic aluminum
C -- Stainless steel plate + common aluminum
D -- Stainless steel plate + hydrophilic aluminum
Pipe connection mode: L -- Facing air flow left hand; R -- Facing air flow right hand
External total pressure code, refer to below table
Cooling coil:
A -- 4C0H
B -- 6C0H
Heating coil attached in front of the cooling coil:
C -- 4C1H (4 rows cooling and 1 row heating)
D -- 6C1H (6 rows cooling and 1 row heating)
E -- 4C2H (4 rows cooling and 2 rows heating)
F -- 6C2H (6 rows cooling and 2 rows heating)
wet film humidifier attached behind the cooling coil:
G -- 4C0H1W (4 rows cooling, 100mm wet film)
H -- 6C0H1W (6 rows cooling, 100mm wet film)
Cooling coil attached with heating coil in the front and
wet film humidifier at the back
J -- 4C1H1W (4 rows cooling and 1 row heating,
100mm wet film)
K -- 6C1H1W (6 rows cooling and 1 row heating,
100mm wet film)
L -- 4C2H1W (4 rows cooling and 2 row heating,
100mm wet film)
M -- 6C2H1W (6 rows cooling and 2 row heating,
100mm wet film)
S -- 0C1H
T -- 0C2H
Structure type + application characteristics:
A -- Horizontal return air basic model
B -- Horizontal fresh air basic model
C -- Horizontal return air multi-function model
D -- Horizontal fresh air multi-function model
G -- Horizontal return air model with mixing box
F -- Horizontal fresh air model with mixing box
Design SN: F -- Horizontal type
Air flow code: 080 air flow is 8000m3/h (air flow = air flow code*100m3/h)
Model name and code: FUW-cabinet fan coil unit
Unit: Pa
A B C D E F G H J Where:
75 100 125 150 175 200 225 250 275 For the FUW020~070 models, the standard external total
K L M N P Q R S
pressure of unit is 150, 225, or 300 Pa.
For the FUW080~150 models, the standard external total
300 350 400 450 500 550 600 650
pressure of unit is 225, 300, or 400Pa.
Note: Basic model configuration: primary filter (digit 13: A) + cooling coil (heating coil) + fan
Multi-function model configuration: primary filter + (medium filter) + (heating coil / electric heater) + cooling coil + (wet film) + fan;
The function section in () is optional.
Mixing box is available for basic model and multi-function model.
The above nomenclature applies only to the standard units. For a unit of which the model is selected by the software, the nomenclature is
automatically generated.
3
FUW Cabinet fan coil Units
Unit features
Heat
preservation
PE
Heat preservation PE Heat preservation PE Seal ring attached to the Seal ring Header Seal ring
attached outside the overall attached between the flange panel wiring hole pipe sealing
drain pan and panel
150Pa
■ Multiple standard external total pressures are available, and multiple Pa
17
150
5P
a
Pa
optional parts can also be provided: primary/medium-efficiency filter (G3/ a1
25
20
0P
0P
a
10
5P
75
coil, fresh air preheated electric heater, wet film humidifier, stainless steel
25 450
Pa
Pa
0
Pa 27 5 P 40 0
50 a 3 0 0 P a 3 5 0 Pa Pa
0P a 65 0
5 5 0 P a 6 00 Pa
drain pan, etc., making selection more rapid, convenient and flexible.
300Pa
400Pa
4
Cabinet Fan Coil Units FUW
Diagrams
Note: When the unit select electric heater section, the filter must be aluminum filter; heating coil and electric heater section can’t be selected at the same time.
The external total pressure, dimensions, and weight of the unit vary with requirements of the optional function section. For details, see our selection software.
Heating coil and cooling coiling can’t be selected at the same time for basic model configuration.
Heat exchanger
■ The copper tubes with a thin wall and the latest type of fins are adopted, and mechanical expanding ensures close fit between the
copper tubes and fins, thus achieving the optimal heat exchange efficiency of the coil.
■ Before delivery, all the heat exchangers will do pressure leakage test by filling nitrogen according to the national standard requirements
to avoid leakage.
●
2 ●
2 ● Quality copper tubes are laid out in the cross counterflow mode to enhance the air
turbulence and improve the heat exchange.
●
1
Cross counterflow layout
Heat exchanger
●
1 ● Fins are corrugated aluminium sheets, which increase the
heat exchange area, optimize the heat exchange, make
condensate water flow down easily and prevent water
drops from being gathered on the fin surface.
● FPI, 11 to 14 fins can be selected.
Aluminum foil ● Hydrophilic aluminum foil is optional.
Fan motor
■ The fan is a high-efficiency and low-noise forward DWDI fans, and the professional
software ensures that all the fans operate in the safe and efficient status.
■ The motor is a fully-enclosed three-phase asynchronous motor, with the protection
grade up to IP55 and insulation grade F, applicable to adverse application environments.
● The impeller will be strict static and ● Multiple motor type: single speed, double
dynamic balanced, stable and low speed, and variable frequency.
noise.
●
2
●
1 ●
1
●
1
●
2
●
2
●
1 The narrow V type belt of international 1 Flexible joint is adopted at the air outlet of
● 1 A door handle is installed at the access
●
famous brand is adopted; fan to effectively isolate vibration. hole to facilitate access;
2 Pulley and push structure to facilitate quick
● 2 The motor is configured with a slide
● 2 The motor junction box is far away from
●
assembly and overhaul. rail regulating device, which can be coil inlet and outlet to prevent leakage of
adjusted to the best installation position electricity, safe and reliable.
to make maintenance convenient.
5
FUW Cabinet Fan Coil Units
Water
进水 inlet
Humidifying
加湿空气 air Water进风
inlet
Drainage
排水
■ It uses electric energy to heat air and the capacity can be ■ Professional selection software of fan coil units
adjusted by groups. The electric heater tube is made of ■ Providing multiple model selection configurations according
stainless steel tube wrapped with stainless steel sheets. to customers' requirements
■ The electric heater section provides the triple protection device ■ Automatically exporting unit performance parameters, CAD
of over high temperature protector (fuse wire and temperature appearance drawings and quotations
switch) and no-air power-off protector to eradicate the potential ■ Chinese and English versions
safety hazard arising from superheat of the heater.
■ It applies to winter fresh air pretreatment and prevents frost
cracking of the coil.
●
1 ●
2
6
Cabinet Fan Coil Units FUW
Model FUW020F FUW030F FUW040F FUW050F FUW060F FUW070F FUW080F FUW100F FUW120F FUW150F
Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 10000 12000 15000
Ⅰ 150 150 150 150 150 150 225 225 225 225
External total pressure
Ⅱ 225 225 225 225 225 225 300 300 300 300
(Pa)
Ⅲ 300 300 300 300 300 300 400 400 400 400
4 rows (return air) 11.4 18.1 22.6 29.3 34.1 42.6 48.7 61.2 73.6 93.3
Nominal cooling capacity 4 rows (fresh air) 28.8 41.6 53.8 65.3 75.0 95.3 104.9 138.3 163.7 201.7
(kW) 6 rows (return air) 15.5 23.0 29.1 36.6 44.0 53.5 58.9 81.3 93.0 117.0
6 rows (fresh air) 35.3 53.8 66.6 89.1 101.1 130.4 142.5 177.3 210.4 260.2
4 rows (return air) 18.9 28.8 35.1 48.1 55.3 68.0 75.7 102.2 122.7 153.3
Nominal heating capacity 4 rows (fresh air) 31.1 45.8 56.8 79.6 86.5 108.9 121.6 166.1 199.3 249.2
(kW) 6 rows (return air) 21.8 32.3 40.9 54.9 61.6 78.0 86.9 122.9 144.8 180.9
6 rows (fresh air) 35.2 51.8 69.6 93.7 106.4 132.3 149.1 194.4 232.2 291.7
4 rows (return air) 0.54 0.86 1.07 1.40 1.63 2.03 2.32 2.92 3.50 4.44
Nominal chilled water flow 4 rows (fresh air) 1.37 1.98 2.56 3.11 3.57 4.54 5.00 6.59 7.79 9.60
(l/s) 6 rows (return air) 0.74 1.10 1.38 1.74 2.10 2.55 2.80 3.87 4.43 5.57
6 rows (fresh air) 1.68 2.56 3.17 4.24 4.81 6.21 6.79 8.44 10.02 12.39
4 rows (return air) 0.45 0.69 0.84 1.15 1.32 1.62 1.80 2.43 2.92 3.65
Nominal hot water flow 4 rows (fresh air) 0.74 1.09 1.35 1.89 2.06 2.59 2.89 3.96 4.75 5.93
(l/s) 6 rows (return air) 0.52 0.77 0.97 1.31 1.47 1.86 2.07 2.93 3.45 4.31
6 rows (fresh air) 0.84 1.23 1.66 2.23 2.53 3.15 3.55 4.63 5.53 6.94
4 rows (return air) 11.6 34.1 29.4 24.8 37.2 29.7 41.5 26.4 31.3 43.8
Nominal chilled water 4 rows (fresh air) 55.6 29.4 62.3 15.0 25.7 27.9 39.6 71.3 75.7 83.7
resistance (kPa) 6 rows (return air) 30.5 25.2 23.2 15.7 13.8 22.8 29.6 61.6 22.9 31.5
6 rows (fresh air) 20.0 55.6 40.8 67.5 96.0 95.0 125.0 81.0 74.8 82.6
Piece/inch 12
Type/material High-efficiency forward centrifugal fans with multiple wings/galvanized steel plates
Type Three-phase asynchronous motor, insulation grade F and protection grade IP55
Power (kW) II 0.55 0.55 (0.75) 0.75 (1.1) 1.5 1.5 1.5 2.2 3 3 (4) 5.5
III 0.55 0.75 1.1 1.5 1.5 (2.2) 2.2 2.2 (3) 4 4 5.5
Cabinet Type Quality galvanized steel plate, with efficient soundproof and heat insulating material PE attached inside
Length (mm) 870 870 870 870 870 870 900 900 990 990
Dimension of basic model Width (mm) 800 1040 1300 1550 1800 1720 1800 2180 2270 2490
Height (mm) 498 498 498 498 498 620 620 620 715 740
Weight of basic model 4 rows 77 99 123 128 142 166 174 232 280 318
(kg) 6 rows 80 103 129 135 151 176 185 247 298 340
NOTE:
■ THE ABOVE PARAMETERS ARE FOR BASIC MODEL ONLY; IN CASE OF ANY SPECIAL REQUIREMENT, DAIKIN WILL PROVIDE A SPECIAL DESIGN.
■ NOMINAL RETURN AIR COOLING CONDITION: 27℃ (DB)/19.5℃ (WB); NOMINAL FRESH AIR COOLING CONDITION: 35℃ (DB)/28℃ (WB); NOMINAL CHILLED WATER
INLET AND OUTLET TEMPERATURES: 7℃ (WATER INLET); 12℃ (WATER OUTLET);
■ NOMINAL RETURN AIR HEATING CONDITION: 21℃ (DRY BULB); NOMINAL FRESH AIR HEATING CONDITION: 0℃ (DRY BULB); NOMINAL HEATING WATER INLET AND
OUTLET TEMPERATURES: 60℃ (WATER INLET); 50℃ (WATER OUTLET);
■ THE WEIGHT LISTED IN THE ABOVE TABLE IS NET WEIGHT OF UNIT. THE OPERATING WEIGHT MAY INCREASE BY ABOUT 20%;
■ VALUE INSIDE ( ) IN THE ABOVE TABLE IS THE MOTOR POWER OF UNIT WITH 6 ROWS OF COILS;
■ FOR THE MAXIMUM EXTERNAL TOTAL PRESSURE CORRESPONDING TO MOTOR POWER, SEE P27;
■ THE COIL CIRCUIT FOR UNITS WITH FULL RETURN AIR (THE BASIC MODEL IS "A") AND UNITS WITH FULL FRESH AIR (THE BASIC MODEL IS "B") MAY BE DIFFERENT.
PLEASE SPECIFY THE INLET AIR WORKING CONDITIONS WHILE PLACING ORDERS. DAIKIN CAN PROVIDE COMPUTER-AIDED MODEL SELECTION TO MEET
SPECIAL REQUIREMENTS. FOR DETAILED PARAMETERS, PLEASE REFER TO THE MODEL SELECTION RESULTS.
7
FUW Cabinet Fan Coil Units
Model FUW020F FUW030F FUW040F FUW050F FUW060F FUW070F FUW080F FUW100F FUW120F FUW150F
Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 10000 12000 15000
1 row (return air) 5.8 9.5 13.0 18.0 22.1 25.2 29.1 35.4 42.4 53.9
Nominal 1 row (fresh air) 10.7 16.4 21.8 30.6 37.4 42.6 49.0 60.3 72.3 90.4
heating
capacity (kW) 2 rows (return air) 11.3 17.9 24.6 31.3 38.0 44.0 50.6 53.7 77.1 97.2
2 rows (fresh air) 19.7 28.7 31.6 52.4 63.5 69.7 76.3 105.5 126.6 155.7
1 row (return air) 0.14 0.23 0.31 0.43 0.53 0.60 0.69 0.84 1.01 1.28
Nominal 1 row (fresh air) 0.25 0.39 0.52 0.73 0.89 1.01 1.17 1.44 1.72 2.15
heating water
flow (l/s) 2 rows (return air) 0.27 0.43 0.59 0.75 0.91 1.05 1.21 1.28 1.83 2.31
2 rows (fresh air) 0.47 0.68 0.75 1.25 1.51 1.66 1.82 2.51 3.02 3.71
Heating coil
1 row (return air) 0.5 0.7 1.4 3.3 5.5 4.8 6.4 7.5 6.6 9.3
Nominal 1 row (fresh air) 1.2 2.2 4.4 9.6 15.3 13.4 17.9 20.0 17.3 23.8
heating water
resistance
(kPa) 2 rows (return air) 1.7 4.3 8.9 16.3 27.0 22.8 30.3 33.6 32.2 44.5
2 rows (fresh air) 4.3 10.5 14.7 43.3 70.7 66.2 68.6 75.3 63.2 70.1
Piece/inch 12
Electric heater Maximum electric heater power (kW) 6.7 10.1 13.4 16.8 20.1 23.5 26.8 33.5 40.2 50.3
Wet film humidifier Maximum humidifying capacity (kg/h) 9.1 13.4 18.1 22.5 27.0 32.0 33.8 41.8 49.3 60.9
Length (mm) 970 970 970 970 970 970 1000 1000 1090 1090
Type I Width (mm) 800 1040 1300 1550 1800 1720 1800 2180 2270 2490
Height (mm) 498 498 498 498 498 620 620 620 715 740
Multi-function cabinet
dimensions
Length (mm) 1100 1100 1100 1100 1100 1100 1081 1102 1220 1220
Type II Width (mm) 800 1040 1300 1550 1800 1720 1800 2180 2270 2490
Height (mm) 498 498 498 498 498 620 620 620 715 740
NOTES:
■ THE ABOVE TABLE PROVIDES THE PARAMETERS OF ALL OPTIONAL PARTS FOR MULTI-FUNCTION MODELS; THE UNIT APPEARANCE DIMENSIONS, UNIT WEIGHT,
AND TOTAL EXTERNAL TOTAL PRESSURE VARY WITH THE REQUIREMENTS OF OPTIONAL FUNCTION SEGMENTS. FOR DETAILS, SEE THE MODEL SELECTION SOFTWARE
OF DAIKIN;
■ NOMINAL RETURN AIR HEATING CONDITION: 21℃ (DRY BULB); NOMINAL FRESH AIR HEATING CONDITION: 0℃ (DRY BULB); NOMINAL HEATING WATER INLET AND
OUTLET TEMPERATURES: 60℃ (WATER INLET); 50℃ (WATER OUTLET);
■ THE MULTI-FUNCTION TYPE-Ⅰ CABINET DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).
Parts Nylon Aluminum G3 G4 F5 PM2.5 1 row 2 rows Wet film humidifier (100 mm)
NOTE:
■ THE RESISTANCE VALUE OF ABOVE PART IS THE AVERAGE VALUE OF EACH MODEL UNDER THE NOMINAL AIR FLOW. FOR THE DETAILED RESISTANCE UNDER
SPECIFIED AIR FLOW, SEE THE MODEL SELECTION RESULT.
■ IN THE BASIC MODEL CONFIGURATION, THE PARAMETERS OF THE HEATING COIL ARE THE SAME AS THOSE OF THE MULTI-FUNCTIONAL CONFIGURATION.
8
Cabinet Fan Coil Units FUW
77 Q
P
N
M-60
M
B
57 A W
F S Water inlet Water outlet N L
30
pipe R pipe R
J
H
K
C
E
34
85
70
L L N N P P R R W W
Model A B C M T H J K Q F E S
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
FUW020F 870 800 498 1041 749 294 50 88 88 66 110 202 202 R1-1/2 R1-1/2 423 564 155 262 232 51 66
FUW030F 870 1040 498 1041 989 294 50 88 88 66 110 202 202 R1-1/2 R1-1/2 423 804 209 262 298 51 66
NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.
9
FUW Cabinet Fan Coil Units
77 Q
P
N
M-60
M
B
57 A W
F S D S Water inlet Water outlet N L
30
pipe R pipe R
J
H
K
C
E
34
85
70
Condensate water
pipe R1-1/4 398
B+80 M
L L N N P P R R W W
Model A B C M T H J K Q D F E S
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
FUW040F 870 1300 498 1041 1249 294 50 88 88 66 110 202 202 R1-1/2 R1-1/2 423 1064 184 166 262 232 51 66
FUW050F 870 1550 498 1041 1499 294 50 88 88 66 110 202 202 R1-1/2 R2 423 1314 184 282 262 232 51 66
FUW060F 870 1800 498 1041 1749 294 50 88 88 66 110 202 202 R1-1/2 R2 423 1564 244 307 262 298 51 66
FUW070F 870 1720 620 1041 1669 395 60 88 88 66 110 202 202 R1-1/2 R2 545 1484 214 312 289 265 51 66
FUW080F 900 1800 620 1071 1749 395 60 88 88 66 110 202 202 R1-1/2 R2 545 1564 264 272 289 331 51 66
FUW100F 900 2180 620 1071 2129 392 64 91 83 82.5 137.5 205 197 R2 R2-1/2 545 1924 244 476 341 309 51 66
FUW120F 990 2270 715 1161 2219 456 65 91 83 82.5 137.5 205 197 R2 R2-1/2 640 2013 294 416 404 373 51 66
FUW150F 990 2490 740 1161 2439 519 64 91 83 82.5 137.5 205 197 R2 R2-1/2 665 2223 294 516 404 373 51 66
NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.
10
Cabinet Fan Coil Units FUW
77 Q
P
N
M-60
M
B 57 W
A
30 Water inlet Water outlet N
F S L
pipe R pipe R
J
H
K
C
E
34
85
70
Condensate water
B+80 pipe R1-1/4 617
M
Return air
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Filter frame (optional)
inlet
W
L L N N P P R R W W
Model A B C M T H J K Q F E S (G3/G4+F5,
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
G3/G4+PM2.5)
FUW020F 970 800 498 1230 749 294 50 88 88 66 110 187 187 R1-1/2 R1-1/2 423 564 155 262 232 51 66 165
FUW030F 970 1040 498 1230 989 294 50 88 88 66 110 187 187 R1-1/2 R1-1/2 423 804 209 262 298 51 66 165
NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ THE MULTI-FUNCTION TYPE-Ⅰ CABINET DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).
11
FUW Cabinet Fan Coil Units
77 Q
P
N
M-60
M
B 57 A W
30 Water inlet Water outlet N L
F S D S
pipe R pipe R
J
H
K
C
E
34
85
70
Condensate water
617
B+80 pipe R1-1/4
M
Return air
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Filter frame (optional)
inlet
W
L L N N P P R R W W
Model A B C M T H J K Q D F E S (G3/G4+F5,
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
G3/G4+PM2.5)
FUW040F 970 1300 498 1230 1249 294 50 88 88 66 110 187 187 R1-1/2 R1-1/2 423 1064 184 166 262 232 51 66 165
FUW050F 970 1550 498 1230 1499 294 50 88 88 66 110 187 187 R1-1/2 R2 423 1314 184 282 262 232 51 66 165
FUW060F 970 1800 498 1230 1749 294 50 88 88 66 110 187 187 R1-1/2 R2 423 1564 244 307 262 298 51 66 165
FUW070F 970 1720 620 1230 1669 395 60 88 88 66 110 187 187 R1-1/2 R2 545 1484 214 312 289 265 51 66 165
FUW080F 1000 1800 620 1260 1749 395 60 88 88 66 110 187 187 R1-1/2 R2 545 1564 264 272 289 331 51 66 165
FUW100F 1000 2180 620 1260 2129 392 64 91 83 82.5 137.5 190 182 R2 R2-1/2 545 1924 244 476 341 309 51 66 165
FUW120F 1090 2270 715 1350 2219 456 65 91 83 82.5 137.5 190 182 R2 R2-1/2 640 2013 294 416 404 373 51 66 165
FUW150F 1090 2490 740 1350 2439 519 64 91 83 82.5 137.5 190 182 R2 R2-1/2 665 2223 294 516 404 373 51 66 165
NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ THE MULTI-FUNCTION TYPE-Ⅰ CABINET DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).
12
Cabinet Fan Coil Units FUW
77 Q
P
L1
N1
L
I
L2
N2
M-60
M
57 A W
L
B Water outlet pipeR1 L2 L1
K
C
E
34
85
70
Condensate water
pipe R1-1/4 I
Water inlet
B+80 Water inlet pipe R2 pipe R1
M
W
N1 N2 N2 R2 R2 W W
Model A B C M T H I J L L1 L2 P R1 K Q F E S (G3/G4+F5,
(1/2) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
G3/G4+PM2.5)
FUW020F 1100 800 498 1360 749 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R1-1/2 423 564 155 262 232 51 66 165
FUW030F 1100 1040 498 1360 989 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R1-1/2 423 804 209 262 298 51 66 165
NOTES:
■ THE UNIT OF CONNECTON PIPE (R1/R2) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ FOR HEATING SECTION SELECTION FOR THE MULTI-FUNCTION TYPE-II CABINET, ONLY ONE CAN BE SELECTED BETWEEN HEATING COIL AND ELECTRIC HEATER.
WHEN ELECTRIC HEATER IS SELECTED, THE FILTER IS CONFIGURED WITH AN ALUMINUM ACCORDING TO THE STANDARD, AND THE INLET AND OUTLET WATER
PIPES IN THE FIGURE ARE DOTTED LINES AND DO NOT EXIST; WHEN HEATING COIL IS SELECTED, THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE
SOLID LINES AND EXIST. FOR THE DETAILED PIPE ORIENTATION DIMENSIONS, SEE THE ABOVE TABLE.
13
FUW Cabinet Fan Coil Units
77 Q
P
L1
N1
L
I
L2
N2
M-60
M
57 A W
L
K
C
E
34
70
85
Condensate water
pipe R1-1/4 I
Water inlet
B+80 Water inlet pipe R2 pipe R1
M
Return air
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Filter frame (optional)
inlet
W
N1 N2 N2 R2 R2 W W
Model A B C M T H I J L L1 L2 P R1 K Q D F E S (G3/G4+F5,
(1/2) (1/2/4) (6) (1/2) (4/6) (nylon) (G3/G4/AL)
G3/G4+PM2.5)
FUW040F 1100 1300 498 1360 1249 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R1-1/2 423 1064 184 166 262 232 51 66 165
FUW050F 1100 1550 498 1360 1499 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R2 423 1314 184 282 262 232 51 66 165
FUW060F 1100 1800 498 1360 1749 294 717 50 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R2 423 1564 244 307 262 298 51 66 165
FUW070F 1100 1720 620 1360 1669 395 717 60 271 88 117 66 66 110 203 R1-1/2 R1-1/2 R2 545 1484 214 312 289 265 51 66 165
FUW080F 1081 1800 620 1352 1749 395 679 60 272 91 115 66 66 110 214 R1-1/2 R1-1/2 R2 545 1564 264 272 289 331 51 66 165
FUW100F 1102 2180 620 1372 2129 392 699 64 277 84 111 82.5 82.5 137.5 213 R2 R2 R2-1/2 545 1924 244 476 341 309 51 66 165
FUW120F 1220 2270 715 1480 2219 456 737 65 321 91 147 82.5 82.5 137.5 201 R2 R2 R2-1/2 640 2013 294 416 404 373 51 66 165
FUW150F 1220 2490 740 1480 2439 519 737 64 321 83 155 82.5 82.5 137.5 203 R2 R2 R2-1/2 665 2223 294 516 404 373 51 66 165
NOTES:
■ THE UNIT OF CONNECTION PIPE (R1/R2) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE THE ABOVE FIGURE.
■ FOR HEATING SECTION SELECTION FOR THE MULTI-FUNCTION TYPE-II CABINET, ONLY ONE CAN BE SELECTED BETWEEN HEATING COIL AND ELECTRIC HEATER. WHEN ELECTRIC HEATER IS
SELECTED, THE FILTER IS CONFIGURED WITH AN ALUMINUM ACCORDING TO THE STANDARD, AND THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE DOTTED LINES AND DO NOT EXIST; WHEN
HEATING COIL IS SELECTED, THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE SOLID LINES AND EXIST. FOR THE DETAILED PIPE ORIENTATION DIMENSIONS, SEE THE ABOVE TABLE.
14
Cabinet Fan Coil Units FUW
Condensate water
pipe R1-1/4
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet
L L N N P P R R
Model A B C M T H J F E S Inlet 1 Inlet 2
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6)
FUW020F 1392 800 498 1506 749 294 50 610 610 66 110 667 667 R1-1/2 R1-1/2 155 262 232 200*300 200*430
FUW030F 1392 1040 498 1506 989 294 50 610 610 66 110 667 667 R1-1/2 R1-1/2 209 262 298 200*350 200*630
NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.
15
FUW Cabinet Fan Coil Units
Condensate water
pipe R1-1/4
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet
L L N N P P R R
Model A B C M T H J D F E S Inlet 1 Inlet 2
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6)
FUW040F 1392 1300 498 1506 1249 294 50 610 610 66 110 667 667 R1-1/2 R1-1/2 184 166 262 232 250*400 250*750
FUW050F 1392 1550 498 1506 1499 294 50 610 610 66 110 667 667 R1-1/2 R2 184 282 262 232 250*500 250*910
FUW060F 1392 1800 498 1506 1749 294 50 610 610 66 110 667 667 R1-1/2 R2 244 307 262 298 250*500 250*1000
FUW070F 1392 1720 620 1506 1669 395 60 610 610 66 110 667 667 R1-1/2 R2 214 312 289 265 250*630 250*1250
FUW080F 1422 1800 620 1536 1749 395 60 610 610 66 110 667 667 R1-1/2 R2 264 272 289 331 250*700 250*1350
FUW100F 1422 2180 620 1536 2129 392 64 613 605 82.5 137.5 670 662 R2 R2-1/2 244 476 341 309 250*910 250*1710
FUW120F 1512 2270 715 1626 2219 456 65 613 605 82.5 137.5 670 662 R2 R2-1/2 294 416 404 373 270*950 270*1870
FUW150F 1512 2490 740 1626 2439 519 64 613 605 82.5 137.5 670 662 R2 R2-1/2 294 516 404 373 300*1070 300*2100
NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.
16
Cabinet Fan Coil Units FUW
Condensate water
pipe R1-1/4
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet
L L N N P P R R
Model A B C M T H J F E S Inlet 1 Inlet 2
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6)
FUW020F 1492 800 498 1695 749 294 50 610 610 66 110 652 652 R1-1/2 R1-1/2 155 262 232 200*300 200*430
FUW030F 1492 1040 498 1695 989 294 50 610 610 66 110 652 652 R1-1/2 R1-1/2 209 262 298 200*350 200*630
NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ THE MULTI-FUNCTION TYPE-I CABINET WITH MIXING BOX DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.
17
FUW Cabinet Fan Coil Units
Condensate water
pipe R1-1/4
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet
L L N N P P R R
Model A B C M T H J D F E S Inlet 1 Inlet 2
(1/2/4) (6) (1/2/4) (6) (1/2/4) (6) (1/2) (4/6)
FUW040F 1492 1300 498 1695 1249 294 50 610 610 66 110 652 652 R1-1/2 R1-1/2 184 166 262 232 250*400 250*750
FUW050F 1492 1550 498 1695 1499 294 50 610 610 66 110 652 652 R1-1/2 R2 184 282 262 232 250*500 250*910
FUW060F 1492 1800 498 1695 1749 294 50 610 610 66 110 652 652 R1-1/2 R2 244 307 262 298 250*500 250*1000
FUW070F 1492 1720 620 1695 1669 395 60 610 610 66 110 652 652 R1-1/2 R2 214 312 289 265 250*630 250*1250
FUW080F 1522 1800 620 1725 1749 395 60 610 610 66 110 652 652 R1-1/2 R2 264 272 289 331 250*700 250*1350
FUW100F 1522 2180 620 1726 2129 392 64 613 605 82.5 137.5 655 647 R2 R2-1/2 244 476 341 309 250*910 250*1710
FUW120F 1612 2270 715 1815 2219 456 65 613 605 82.5 137.5 655 647 R2 R2-1/2 294 416 404 373 270*950 270*1870
FUW150F 1612 2490 740 1815 2439 519 64 613 605 82.5 137.5 655 647 R2 R2-1/2 294 516 404 373 300*1070 300*2100
NOTES:
■ THE UNIT OF CONNECTION PIPE (R) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ THE MULTI-FUNCTION TYPE-I CABINET WITH MIXING BOX DOES NOT CONTAIN THE HEATING SECTION (ELECTRIC HEATER OR HEATING COIL).
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.
18
Cabinet Fan Coil Units FUW
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet
N1 N2 N2 R2 R2
Model A B C M T H I J L1 L2 P R1 F E S Inlet 1 Inlet 2
(1/2) (1/2/4) (6) (1/2) (4/6)
FUW020F 1622 800 498 1825 749 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R1-1/2 155 262 232 200*300 200*430
FUW030F 1622 1040 498 1825 989 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R1-1/2 209 262 298 200*350 200*630
NOTES:
■ THE UNIT OF CONNECTON PIPE (R1/R2) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
■ FOR HEATING SECTION SELECTION FOR THE MULTI-FUNCTION TYPE-II CABINET WITH MIXING BOX, ONLY ONE CAN BE SELECTED BETWEEN HEATING COIL AND
ELECTRIC HEATER. WHEN ELECTRIC HEATER IS SELECTED, THE FILTER IS CONFIGURED WITH AN ALUMINUM ACCORDING TO THE STANDARD, AND THE INLET
AND OUTLET WATER PIPES IN THE FIGURE ARE DOTTED LINES AND DO NOT EXIST; WHEN HEATING COIL IS SELECTED, THE INLET AND OUTLET WATER PIPES IN
THE FIGURE ARE SOLID LINES AND EXIST. FOR THE DETAILED PIPE ORIENTATION DIMENSIONS, SEE THE ABOVE TABLE.
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.
19
FUW Cabinet Fan Coil Units
Dimensions Cabinet dimensions Lifting holes Connection pipe Supply air outlet Air inlet
N1 N2 N2 R2 R2
Model A B C M T H I J L1 L2 P R1 D F E S Inlet 1 Inlet 2
(1/2) (1/2/4) (6) (1/2) (4/6)
FUW040F 1622 1300 498 1825 1249 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R1-1/2 184 166 262 232 250*400 250*750
FUW050F 1622 1550 498 1825 1499 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R2 184 282 262 232 250*500 250*910
FUW060F 1622 1800 498 1825 1749 294 1182 50 610 117 66 66 110 146 R1-1/2 R1-1/2 R2 244 307 262 298 250*500 250*1000
FUW070F 1622 1720 620 1825 1669 395 1182 60 610 117 66 66 110 146 R1-1/2 R1-1/2 R2 214 312 289 265 250*630 250*1250
FUW080F 1603 1800 620 1817 1749 395 1144 60 613 115 66 66 110 157 R1-1/2 R1-1/2 R2 264 272 289 331 250*700 250*1350
FUW100F 1624 2180 620 1837 2129 392 1164 64 606 111 82.5 82.5 137.5 156 R2 R2 R2-1/2 244 476 341 309 250*910 250*1710
FUW120F 1742 2270 715 1945 2219 456 1202 65 613 147 82.5 82.5 137.5 144 R2 R2 R2-1/2 294 416 404 373 270*950 270*1870
FUW150F 1742 2490 740 1945 2439 519 1202 64 605 155 82.5 82.5 137.5 146 R2 R2 R2-1/2 294 516 404 373 300*1070 300*2100
NOTES:
■ THE UNIT OF CONNECTON PIPE (R1/R2) IS INCH, AND OTHER UNITS ARE MM.
■ THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE THE ABOVE FIGURE.
■ FOR HEATING SECTION SELECTION FOR THE MULTI-FUNCTION TYPE-II CABINET WITH MIXING BOX, ONLY ONE CAN BE SELECTED BETWEEN HEATING COIL AND ELECTRIC HEATER. WHEN
ELECTRIC HEATER IS SELECTED, THE FILTER IS CONFIGURED WITH AN ALUMINUM ACCORDING TO THE STANDARD, AND THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE DOTTED
LINES AND DO NOT EXIST; WHEN HEATING COIL IS SELECTED, THE INLET AND OUTLET WATER PIPES IN THE FIGURE ARE SOLID LINES AND EXIST. FOR THE DETAILED PIPE ORIENTATION
DIMENSIONS, SEE THE ABOVE TABLE.
■ ONE OR TWO AIR INLET CAN BE SELECTED, POSITION CAN BE TOP, REAR UP OR BOTTOM.
20
Cabinet Fan Coil Units FUW
The FUW vertical cabinet fan coil unit adopts an electrostatic sprayed cabinet of high strength, and provides professional model selection and
a lot of optional functions such as heating coil and wet film humidifier. It can meet requirements of wide customers. Ten models of FUW vertical
cabinet fan coil units are available, with the air flow in the range of 4000 to 25000 m3/h, cooling capacity in the range of 23 to 420 kW, and the
external total pressure in the range of 90 to 550 Pa.
Nomenclature
FUW 080 V R 08 -4 L -F T D E
Export
Internal identification code
Air supply mode:
T -- Top air outlet
Power Supply:
F -- 380V/3N~/50Hz
R -- 380V/3N~/60Hz
P -- 208-230V/3N~/60Hz
Q -- 460V/3N~/60Hz
Pipe orientation:
L -- Left connected pipe
R -- Right connected pipe
Rows of coils:
4 -- 4 rows of coils
6 -- 6 rows of coils
External total pressure:
08 -- 80Pa
15 -- 150Pa
22 -- 220Pa
30 -- 300Pa
Application features:
R -- Return air
F -- Fresh air
Structure type: V indicates the vertical type
Air flow code: 080-air flow is 8000m3/h (air flow = air flow code*100m3/h)
Model name and code: FUW-cabinet fan coil unit
Judgment of the left type and right type: if the pipe is connected on the
Air flow
left when you face the airflow direction, it is the left type; otherwise it is
direction
the right type. This unit
adopts the left
Left
connected
pipe.
connected
pipe
Features
Quality materials and elaborate design
The electro galvanized plate treated with Mechanically expanded copper tubes
electrostatic spraying of pure polyester with a thin wall and a new type of fins
is used to realize efficient anticorrosion. produced using leading-edge impor ted
The heat insulating material is new XPE OAK manufacturing facilities achieve close
material with excellent heat insulating and fitting between copper tubes and fins,
sound absorption effect, which does not thus ensuring the optimal heat exchange
absorb water and can effectively prevent efficiency of coils and paving the way for
cold bridge. efficient operation of the unit.
Fan Filter
A high-efficiency forward fan with multiple It adopts the anti-mildew primary efficiency
wings provides a large air flow and stable filter with low initial resistance, which
and reliable performance with low noises. greatly reduces the unit power consumption
The fan bearing does not require adding and can be easily cleaned and conveniently
lubricant, thus saving maintenance cost used.
for customers.
Combination type √ √ √ √ √
Notes:
1. Non-woven fabric filters are available for the selected unit as needed (nylon filter is adopted for the standard configuration);
2. Cooling coil and heating coil can’t be selected at the same time.
3. The unit power and external total pressure may be changed accordingly;
4. The length of the unit may be increased as actually needed. The detailed parameters are subject to the software model selection results.
22
Cabinet Fan Coil Units FUW
Model FUW040V FUW050V FUW060V FUW080V FUW100V FUW120V FUW150V FUW180V FUW200V FUW250V
Nominal air flow (m3/h) 4000 5000 6000 8000 10000 12000 15000 18000 20000 25000
Ⅰ - 80 - - - - - - - -
External total Ⅱ 150 150 150 150 150 150 - 150 150 150
pressure (Pa) Ⅲ 220 220 220 220 220 220 220 220 220 220
Ⅳ 300 300 300 300 300 300 300 300 300 300
4 rows of coils (return air) 23 31 35 51 59 79 90 116 125 150
Nominal cooling 4 rows of coils (fresh air) 50 68 76 111 128 177 205 256 273 325
capacity (kW) 6 rows of coils (return air) 28 39 44 63 75 100 117 144 156 185
6 rows of coils (fresh air) 64 86 96 142 167 219 252 319 343 420
4 rows of coils (return air) 36 48 55 82 97 126 149 185 201 245
Nominal heating 4 rows of coils (fresh air) 58 76 87 129 153 199 237 294 319 398
capacity (kW) 6 rows of coils (return air) 44 57 66 95 115 145 176 214 234 289
6 rows of coils (fresh air) 69 90 105 150 182 229 279 338 369 461
4 rows of coils (return air) 1.10 1.48 1.67 2.43 2.82 3.77 4.30 5.54 5.97 7.16
Nominal chilled
4 rows of coils (fresh air) 2.39 3.25 3.63 5.30 6.11 8.45 9.79 12.22 13.03 15.51
water flow
6 rows of coils (return air) 1.34 1.86 2.10 3.01 3.58 4.77 5.58 6.87 7.45 8.83
(l/s)
6 rows of coils (fresh air) 3.05 4.11 4.58 6.78 7.97 10.45 12.03 15.23 16.37 20.05
4 rows of coils (return air) 0.86 1.15 1.31 1.96 2.32 3.01 3.56 4.42 4.80 5.85
Nominal heating
4 rows of coils (fresh air) 1.38 1.81 2.08 3.08 3.65 4.75 5.66 7.02 7.61 9.50
water flow
6 rows of coils (return air) 1.05 1.36 1.58 2.27 2.74 3.46 4.20 5.11 5.58 6.90
(l/s)
6 rows of coils (fresh air) 1.65 2.15 2.51 3.58 4.34 5.47 6.66 8.07 8.81 11.00
4 rows of coils (return air) 40.9 62.8 78.5 35.0 44.7 30.7 38.8 56.0 63.9 36.3
Cooling conditions
4 rows of coils (fresh air) 68.1 41.1 50.5 22.7 29.1 45.0 58.1 67.7 67.6 76.9
Water resistance
6 rows of coils (return air) 29.1 45.0 56.9 26.4 35.1 48.4 63.9 41.8 48.2 30.9
(kPa)
6 rows of coils (fresh air) 62.2 79.0 78.8 49.3 65.3 81.5 81.3 74.1 84.6 95.0
Type Copper tube with a new type of corrugated aluminum fins
Piece/inch 12
Coil Working pressure (MPa) 1.6
Size of inlet/outlet water pipe connector R1-1/2 R1-1/2 R1-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2 R2-1/2
Size of condensate water pipe connector R1-1/4
Type/material High-efficiency forward-pitched centrifugal fans with multiple wings/galvanized steel plates
Fan Transmission type V-belt transmission
Air discharge Top discharge
Power supply 380V/3N ~ /50Hz
Type Three-phase asynchronous motor, insulation grade F and protection grade IP55
Ⅰ - 0.75(1.1) - - - - - - - -
Motor
Ⅱ 1.1(1.1) 1.1(1.1) 1.5(2.2) 1.5(1.5) 2.2(3.0) 2.2(2.2) - 4.0(4.0) 4.0(5.5) 5.5(5.5)
Power (kW)
Ⅲ 1.1(1.5) 1.1(1.5) 1.5(2.2) 1.5(2.2) 3.0(3.0) 2.2(3.0) 4.0(4.0) 4.0(4.0) 5.5(5.5) 5.5(7.5)
Ⅳ 1.5(1.5) 1.5(1.5) 2.2(2.2) 2.2(2.2) 3.0(3.0) 3.0(3.0) 4.0(5.5) 5.5(5.5) 5.5(7.5) 7.5(7.5)
Type Nylon filter with primary efficiency
Filter
Thickness (mm) 8
Cabinet Type Galvanized steel plate of electrostatic coating, with efficient soundproof and heat insulating material PE attached inside
Length (mm) 935 1135 1135 1350 1350 1774 1774 2124 2124 2476
Unit cabinet
Width (mm) 585 655 655 736 736 956 956 955 955 955
dimensions
Height (mm) 1082 1320 1320 1676 1676 2036 2036 2070 2070 2191
4 rows of coils 135 185 188 265 269 440 450 556 571 665
Unit weight (kg)
6 rows of coils 146 199 202 285 289 473 483 598 613 716
NOTES:
■ THE ABOVE PARAMETERS ARE STANDARD MODEL PARAMETERS; IN CASE OF ANY SPECIAL REQUIREMENT, DAIKIN WILL PROVIDE A SPECIAL DESIGN;
■ NOMINAL RETURN AIR COOLING CONDITION: 27℃ (DRY BULB)/19.5℃ (WET BULB); NOMINAL FRESH AIR COOLING CONDITION: 34℃ (DRY BULB)/28℃ (WET BULB);
NOMINAL CHILLED WATER INLET AND OUTLET TEMPERATURES: 7℃ (WATER INLET); 12℃ (WATER OUTLET);
■ NOMINAL RETURN AIR HEATING CONDITION: 21℃ (DRY BULB); NOMINAL FRESH AIR HEATING CONDITION: 0℃ (DRY BULB); NOMINAL HEATING WATER INLET AND
OUTLET TEMPERATURES: 60℃ (WATER INLET); 50℃ (WATER OUTLET);
■ THE WEIGHT LISTED IN THE ABOVE TABLE IS THE NET WEIGHT OF UNIT. THE OPERATING WEIGHT WILL INCREASE BY ABOUT 20%;
■ VALUE INSIDE ( ) IN THE ABOVE TABLE IS THE MOTOR POWER OF UNIT WITH 6 ROWS OF COILS.
■ FOR THE MAXIMUM EXTERNAL TOTAL PRESSURE CORRESPONDING TO MOTOR POWER, SEE P22;
■ THE COIL CIRCUIT FOR UNITS WITH FULL RETURN AIR ("R") AND UNITS WITH FULL FRESH AIR ("F") MAY BE DIFFERENT. PLEASE SPECIFY THE INLET AIR WORKING
CONDITIONS WHILE PLACING ORDERS. DAIKIN CAN PROVIDE COMPUTER-AIDED MODEL SELECTION TO MEET SPECIAL REQUIREMENTS. FOR DETAILED PARAMETERS,
PLEASE SEE THE MODEL SELECTION RESULTS.
23
FUW Cabinet Fan Coil Units
Chilled water
Junction outlet pipe
box
H
Chilled water
inlet pipe
T L 50 R
Condensate water
outlet pipe R1-1/4
Unit: mm
Unit Supply air outlet Return air inlet Clearance Base hole positioning
dimensions Cabinet dimensions Pipe orientation dimensions
dimensions dimensions length of unit dimensions
Model A B C L L T T
D E F J K H G R M N
(length) (width) (height) (4 rows) (6 rows) (4 rows) (6 rows)
FUW040V 935 585 1082 335 293 200 840 592 446 182 66 110 236 192 1055 968 520
FUW050V 1135 655 1320 395 341 254 1040 692 546 152 66 110 326 282 1255 1168 590
FUW060V 1135 655 1320 395 341 254 1040 692 546 152 66 110 326 282 1255 1168 590
NOTE: THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, DAMPER/FLANGE, FILTER AND HANGING ROD). FOR
DETAILS, SEE THE ABOVE FIGURE.
24
Cabinet Fan Coil Units FUW
Chilled water
Junction outlet pipe
box
K
H
Chilled water
inlet pipe
T L 50
Condensate water
outlet pipe R1-1/4
R
Unit: mm
Unit Supply air outlet Return air inlet Forklift hole Clearance Base hole positioning
dimensions Cabinet dimensions Pipe orientation dimensions
dimensions dimensions position length of unit dimensions
Model A B C L L T T
D E F J K H G Q R M N P
(length) (width) (height) (4 rows) (6 rows) (4 rows) (6 rows)
FUW080V 1350 736 1676 471 404 281 1256 873 720 182 83 137 343 288 500 1493 1400 675 197
FUW100V 1350 736 1676 471 404 281 1256 873 720 182 83 137 343 288 500 1493 1400 675 197
FUW120V 1774 956 2036 561 482 483 1680 1112 950 480 83 137 228 184 655 1902 1826 907 334
FUW150V 1774 956 2036 561 482 483 1680 1112 950 480 83 137 228 184 655 1902 1826 907 334
NOTE: THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS,
SEE THE ABOVE FIGURE.
25
FUW Cabinet Fan Coil Units
S D S
Chilled water
Junction outlet pipe
box
K
H
Chilled water
inlet pipe
269
Condensate water
outlet pipe R1-1/4
T L 50
Unit: mm
Unit Supply air outlet Return air inlet Forklift hole Clearance Base hole positioning
dimensions Cabinet dimensions Pipe orientation dimensions
dimensions dimensions position length of unit dimensions
Model A B C L L T T
S D E J K H Q R M N P
(length) (width) (height) (4 rows) (6 rows) (4 rows) (6 rows)
FUW180V 2124 955 2070 476 382 406 2032 1253 1077 83 137 224 180 1003 2247 2175 907 334
FUW200V 2124 955 2070 476 382 406 2032 1253 1077 83 137 224 180 1003 2247 2175 907 334
FUW250V 2476 955 2191 561 454 478 2379 1253 1077 83 137 224 180 701 2597 2525 907 660
NOTE: THE CABINET DIMENSIONS EXCLUDE THE PROTRUDING PARTS (SUCH AS THE WATER PIPE HEADER, AIR VENT, FILTER AND HANGING ROD). FOR DETAILS, SEE
THE ABOVE FIGURE.
26
Cabinet Fan Coil Units FUW
Model FUW020F FUW030F FUW040F FUW050F FUW060F FUW070F FUW080F FUW100F FUW120F FUW150F
Nominal air flow (m3/h) 2000 3000 4000 5000 6000 7000 8000 10000 12000 15000
Motor power
Rows External total pressure (Pa)
(kW)
0.55 400 250 100
4 rows of cooling coil 2.2 700 500 450 400 150 125
NOTES:
■ THE ABOVE TABLE PROVIDES THE MAXIMUM EXTERNAL TOTAL PRESSURE OF UNIT (INCLUDING THE STANDARD CONFIGURATION FILTER AND COOLING COIL)
CORRESPONDING TO THE MOTOR POWER. TO ADD A FUNCTION SECTION, REDUCE THE RESISTANCE OF THE CORRESPONDING PART. FOR THE DETAILED
RESISTANCE VALUES, SEE THE PARAMETER TABLE ON P8. FOR EXAMPLE, THE MOTOR POWER SELECTED FOR FUW040 IS 1.1KW, THERE ARE 4 ROWS OF
COOLING COILS, AND THE CORRESPONDING MAXIMUM EXTERNAL TOTAL PRESSURE IS 350PA. IF FILTER F5 IS ADDED FOR THE UNIT, THE RESISTANCE OF F5 IS
128PA ACCORDING TO THE TABLE ON P8, AND THE CORRESPONDING MAXIMUM EXTERNAL TOTAL PRESSURE IS 350-128=222PA.
Model FUW040V FUW050V FUW060V FUW080V FUW100V FUW120V FUW150V FUW180V FUW200V FUW250V
Nominal air flow (m3/h) 4000 5000 6000 8000 10000 12000 15000 18000 20000 25000
Motor power
Rows of coils External total pressure (Pa)
(kW)
0.75 90
7.5 430
0.75
4 270 230
27
FUW Cabinet Fan Coil Units
Precautions
■ Appropriate water seal should be fitted to ensure the smooth drainage of condensate water during the installation. The installation diagram
for water seal is shown in Fig 1.
Not greater
than 1/2H
28
Warning ● Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in
a particular country. Prior to purchase, please therefore confirm with your local authorized importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable
for use, in the region where the product will be used. This statement does not purport to exclude,
restrict or modify the application of any local legislation.
● Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
● Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
● Read the User’s Manual carefully before using this product. The User’s Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/