Pump and Line Sizing Calc

This document contains calculations for sizing a pump and pipe for transferring water. It calculates flow rates, velocities, pressures, losses and friction for both the suction and discharge sides. Key parameters calculated include the pipe diameter needed, NPSH required, suction and discharge pressures, developed head and pressure difference across the pump. Friction losses and static head are accounted for in the pressure calculations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
153 views5 pages

Pump and Line Sizing Calc

This document contains calculations for sizing a pump and pipe for transferring water. It calculates flow rates, velocities, pressures, losses and friction for both the suction and discharge sides. Key parameters calculated include the pipe diameter needed, NPSH required, suction and discharge pressures, developed head and pressure difference across the pump. Friction losses and static head are accounted for in the pressure calculations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

design

PUMP AND LINE SIZE CALCULATION


typical velocit 2 m/s
Fluid Water area of pipe 0.001394523 m2
temperature 35 C diameter 0.042148106 m
density 986 kg/m3 42.14810596 mm
viscosity 0.8 Cp economic pipe diameter
normal flow rate 2.75 Kg/s d,optimum 37.23639688 mm
design max. Flow rate 3.96 Kg/s
volumetric flow rate 0.002789047 m3/s
equipment pressure 1 bar
cross sectional area of pipe 1962.5
0.0019625
fluid velocity 1.421170269
SUCTION CALCULATION f 0.005454534
LINE SIZE 50 MM
from friction chart
normal maximum f 566.985986
VELOCITY 1.421170269 1.2528 m/s f 0.566985986
FRICTION LOSS 0.566985986 0.81645982 kpa/m
LINE LENGTH 6.00488408 8.647033075 m
LINE LOSS 3.404685121 4.902746574 kpa
ENTRANCE LOSS 1.433843125 2.0647341 kpa
STRAINER 40 40 Kpa
SUBTOTAL1 4.838528246 6.967480674 kpa
static head 1.2 1.2 m
density*g*z1 11.607192 11.832 kpa
equipment pressure 100 100 kpa
sub total 2 111.607192 111.832 kpa
SUCTION PRESSURE 106.7686638 104.8645193 Kpa
vapour pressure 40 40
NPSH 6.902823396 6.705964991 m

cross sectional area of pipe


DISCHARGE CALCULATION
LINE SIZE 40 MM velocity
VELOCITY 0.056803394 0.081796888 m/s
FRICTION LOSS 0.000540847 0.00077882 kpa
LINE LENGTH 14.24 20.5056 m
LINE LOSS 0.007701661 0.015970164 kpa
control valve 50 72 kpa
Dynamic loss 50.00770166 72.01597016 kpa
static head 3.2 3.2 m
Equip. pr. 100 100 kpa
density*g*z2 30.952512 30.952512 kpa
subtotal 130.952512 130.952512 kpa
discharge pressure 180.9602137 202.9684822 kpa
suction pressure 137.344 137.857889 Kpa
Diff pressure 43.61621366 65.11059316 kpa

Diff pressure 4.509226383 6.731405132 m

head 11.41204978 13.43737012 m

Page 1
design

pump flow rate 10.04056795 m3/hr


head 18.31487318 m
NPSH 6.902823396 m

Page 2
design

Nre 103895.0812 If Re<2100,f=16/NRe


Re 3000to 50000,f=0.0014+[0.125/Re^(.32)]
Re 50000 to 1*10^6, f= 0.046*Re^(-0.2)

Nre 613057.3248

mm2 actual line length 1.2 m


m2 bend 2 2.528886358 m
m/s valve 1 2.275997722 m
total length 6.00488408 m

R/density x u2 0.003
N/m2
Kpa

1256 mm2 NRE 17502.54582


0.0491 m2 f 0.006518349
0.056803394 m/s
through friction chart R/density x u2 0.0017
f 0.540846981 N/m2
0.000540847 kpa

line actual length 8 m


bends 4 4.8 m
valves 2 1.44 m
14.24 m

Page 3
design

1.791685284 1.057115483
7.449997982

Page 4
actual practical

Pump discharge pressure 1.5 kg/cm2


Pr. At out let of dryer 1 kg/cm2
line length given in prev. sheet

from previous sheet data

developed head 4.563894523 m

Page 5