IEC104 Gateway Datasheet 01

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Smart Protocol Converter

IEC104 Gateway
Data Sheet

IEC104 Gateway

Rear panel

The IEC104 Gateway allows an easy connection of up to eight IEC 60870-5-101 based telecontrol substations to modern IEC 60870-5-104 based control systems. This provides excellent conditions for the change-over to the TCP/IP capable IEC 60870-5-104 protocol. At the same time the IEC104 Gateway guarantees that IEC 60870-5-101 protocol based telecontrol substations within the installation can still be used.

Application Gateway between IEC 60870-5-101 telecontrol substations and IEC 60870-5-104 control systems Main Features Protocol conversion between IEC 60870-5-101 and IEC 60870-5-104 protocol Multiplexing of IEC 60870-5-101 connections to one serial line (party line) Redundant connection to the control system Configurable Parameters (extract) In the direction of telecontrol substations/control direction Transmission method (balanced/unbalanced) Link Address length Common Address (CA) length Information Object Address (IOA) length Cause of Transmission (COT) length

Data packets are transmitted via IEC104 Gateway between the control system and the telecontrol substation in control and in monitoring direction. In the direction of the control system the IEC104 Gateway acts as IEC 60870-5-104 slave and as IEC 60870-5-101 master in the direction of the substations. The IEC104 Gateway takes over the protocol specific time stamp adaptation as well as the adaptation of the configured field length for the Common Address (CA), Information Object Address (IOA) and Cause of Transmission (COT).

In the direction of the control system/monitoring direction TCP/UDP port for the connection to the IEC104 master Control system IP address Models IEC104 Gateway with 8 serial interfaces IEC104 Gateway with 4 serial interfaces IEC104 Gateway with 2 serial interfaces Addtional Modules Modem module for DSL, UMTS/GPRS or TETRA VPN license for the data encryption via VPN tunnels according to IPSec standard

Due to a permanent product development design and technical specifications are subject to change without prior notice. For additional information or questions please contact our support team. The latest data sheets are available at www.nentec.com. Trademarks are the property of the respective owner. PSI Nentec 5/2010

Smart Protocol Converter

IEC104 Gateway
Data Sheet
Flexibility With its large number of interfaces the IEC104 Gateway offers a suitable connection solution for any topology. Ethernet and DSL connections as well as radio communication via GPRS/UMTS or TETRA are used as transport routes between the control systems and the IEC104 Gateway. Unused interfaces can be deactivated to prevent unauthorized access. The galvanic separation of the serial interfaces of the IEC104 Gateway guarantees an undisturbed operation. Security With the VPN Security package the complete data traffic from and to the control system can be encrypted via VPN tunnel according to IPSec standard. This optimally protects your security-relevant data on the transport routes. Configuration The IEC104 Gateway configuration can be alternatively done via an intuitive Web interface, a command line interface or by directly editing the configuration file. High Availability Use the IEC104 Gateway to realize redundant connections with only one device. The redundant connection to the control system is realised through the different interfaces. The device itself provides two power supply inputs to guarantee a redundant supply.

Virtual RTU To activate or deactivate single serial connections or telecontrol substations by the control system and to get their status information, within the overall system the IEC104 Gateway itself can be addressed as telecontrol substations by the control system. Status changes at the serial connections or telecontrol substations are reported to the control system with the aid of specific Information Object Addresses. The time synchronization for the IEC104 Gateway is made via NTP time server, manual input or by sending an IEC time synchronization message to the Common Address of the IEC104 Gateway. The time synchronization in the direction of the telecontrol substations is made after the connection setup to the telecontrol substation and if required in a configurable time interval. Project specific details should be discussed at first to guarantee a correct operation in the respective environment. We offer you broad consulting services on the basis of your existing installation.

Due to a permanent product development design and technical specifications are subject to change without prior notice. For additional information or questions please contact our support team. The latest data sheets are available at www.nentec.com. Trademarks are the property of the respective owner. PSI Nentec 5/2010

Smart Protocol Converter

IEC104 Gateway
Data Sheet
Software Operating system: Software version: Basic features: NENUX (Linux kernel 2.6) 1.0 protocol conversion between IEC 60870-5-101 and IEC 60870-5-104 protocol packaging of telecontrol protocols logical telecontrol line control dynamic IP routing between WAN and LAN interfaces IEC 60870-5-101, IEC 60870-5-104 configuration via web interface and command line interface (CLI) statistic commands, diagnosis via integrated trace system Power supply Type Power consumption Input voltage Connector Redundancy DC 15 VA 12 ... 24 VDC 10 % 3 pin connector conforming to IEC 60130-9 (IP 40) with screw ring second DC connector (hot standby)

TC protocols: Management: Statistics & diagnosis:

External power supply unit wall-mount power adapter Model (Made in Germany) 100 ... 240 VAC/50 ... 60 Hz Primary voltage Secondary voltage Output power Primary connector 15 VDC (controlled) 18 VA (overload protection, shortcircuit-proof) exchangeable system: Euro, UK, USA/Japan, AUS, IEC 320 approx. 2 m 200.000 hours @ 25 C additional power supply needed second power supply (TCG WPS) central power supply (TCG CPS) DIN rail power supply (TCG DPS)

Mechanics Chassis Dimension Packaging dimension Weight / gross weight Wrmeabfuhr Environment Operation EN 60721-3-3: 1995 / A2:1997 class 3K3, 0 to +40 30 % to 80 % C C, rel. humidity (not condensing) EN 60721-3-2: 1997 class 2K3, -20 to +85 5 % to 95 % C C, rel. humidity (not condensing) EN 60721-3-1: 1997 class 1K3, -20 to +85 5 % to 95 % C C, rel. humidity (not condensing) 19 rack mount chassis (1 RU) 436 44.45 276 mm3 (W/H/H) according to DIN 41494, part 5 54 15 37 cm (W/H/D) 3.6 kg / 4.6 kg convection cooling Electronics Main processor Program memory Main memory
3

Cable length Reliability Redundancy operation Supplies (optional)

32 Bit RISC Processor @533 MHz 256 MB 128 MB, max. 256 MB (SDRAM)

Transport

Storage (in packaging) EMC Emission

EN 55022:2006+A1:2007 class A EN 61000-3-2:2006 EN 61000-3-3:1995+A1:01+A2:05 EN 55024:1998+A1:2001+A2:2003 EN 61850-3:2002 for telecontrol lines with enhanced values for substations: IEC 10004-2:2008: 8 kV Kontaktentladung, 15 kV Luftentladung IEC 1000-4-4:1995: 4 kV Datenleitungen IEC 1000-4-5:1995: 2 kV Datenleitungen

Interfaces Telecontrol interfaces Ethernet interfaces RS232 interface USB host interfaces X.21 interface ISDN-S0 interfaces

IEC104GW-8

IEC104GW-4

IEC104GW-2

8 4 1 2 2 1

4 2 1 2 2 1

2 2 1 2 2 1

Telecontrol interface V.24/V.28 Type Purpose Signal transmission Interface rate Electrical parameters Isolation Bus capability Connector V.24 (RS232) level adjustment and galvanical isolation TXD, RXD, RTS, CTS, DTR, DCD 50 to 19200 baud conforming to V.28 1kV eff possibility to passivate sender (party line) 8 pin RJ45 socket (ISO 8877)

Noise immunity

Product safety Electrical safety Conformity EN 60950, low voltage directive (2006/95/EG) CE

Due to a permanent product development design and technical specifications are subject to change without prior notice. For additional information or questions please contact our support team. The latest data sheets are available at www.nentec.com. Trademarks are the property of the respective owner. PSI Nentec 5/2010

Smart Protocol Converter

IEC104 Gateway
Data Sheet
LAN interfaces Type Purpose Electrical parameters Connector RS-232 interface Purpose Electrical parameters Connector USB host interfaces Purpose Funktion Connector extensions USB 2.0 host, Hi-Speed USB host interface Connector configuration and servicing access 38400 baud conforming to V.24 8 ping RJ45 socket (ISO 8877) Connector DSL interface (optional) Purpose Function Access type Transmission rate data communication via ADSL modem integrated ADSL modem ADSL/ADSL2/ADSL2+ depending on the access type up to 24 Mbps downstream and up to 3.5 Mbps upstream 2-wire-interface 10/100 Mbps Twisted-Pair (TP) uplinks to the control systems conforming to IEEE 802.3I (100BaseT), impedance: 100 (symmetrical) 8 pin RJ45 socket (ISO 8877) TETRA interface (optional) Type Purpose Radio network Transmission rate Betriebsart integrated TETRA data modem data communication via TETRA digital trunk radio communication system TETRA (400 MHz band) 1 W (compl. to EN303035-1, class 4) Packet Data Application (PDA); encrypted FME antenna connector

X.21 interfaces (optional) Connection control Transmission rate Electrical parameters Betriebsart Connector point-to-point connection 2.4 Kbps to 2048 Kbps conforming to ITU X.27 or V.11/ITU X.24 leased line 8 pin RJ45 socket (ISO 8877) LAN interfaces Telecontrol interfaces ISDN-S0 interface X.21 interfaces Signalling contact Function indicators System

LEDs for system messages (SYS) and power supply (PWR A, PWR B) LEDs for activity and TP connection status (LI/ACT) LEDs for line activity (RX, TX), error (ERR) S0 B cannel LEDs (B1, B2) clock pulse active LED (CLK) potential free alert contact with max. capacity 230 VAC/60 VDC/1 A

ISDN-S0 interface (optional) Channel structure Transmission rate Electrical parameters Overvoltage security D channel protocol Connector Configuration 2 B64 + 1 D16 64 Kbps each B channel ETS 300 012 ETS 300 047-3 DSS1 (Euro-ISDN) 8 pin RJ45 socket (ISO 8877) ISDN operating mode DSS1 (EuroISDN), dial-up and point-to-point connections software controlled

Connection control

UMTS/GPRS interface (optional) Purpose Type Radio frequencies Operating modes data communication via UMTS/GPRSmobile network integrated UMTS/GPRS transceiver with modem functionality UMTS 1900/2000 MHz data transfer: GPRS: max. 48 Kbps downlink UMTS: max. 384 Kbps downlink EDGE: max. 384 Kbps downlink HSDPA: max. 3.2 Mbps downlink, max. 7.2 Mbps downlink (projected) FME antenna connector PSI Nentec GmbH Greschbachstrae 12 76229 Karlsruhe Germany Tel. +49 721 94249-0 Fax: +49 721 94249-10 [email protected] www.nentec.de
Due to a permanent product development design and technical specifications are subject to change without prior notice. For additional information or questions please contact our support team. The latest data sheets are available at www.nentec.com. Trademarks are the property of the respective owner. PSI Nentec 5/2010

Connector

You might also like