Izolacioni Trafo
Izolacioni Trafo
Izolacioni Trafo
1 425 36/37/38/39/48/49
1 428 28/29/30/31/32/33/34/35/36/37/38/39
CONTENT PAGE
1. Operating principle 1
. . . . . . . . . . . . . . . . . . . . . .
2. Main characteristics 1
. . . . . . . . . . . . . . . . . . . . . .
3. Range / electrical characteristics 1
. . . . . . . . .
4. Mechanicals characteristics 2
. . . . . . . . . . . . . .
5. Handling / lifting operation 3
. . . . . . . . . . . . . .
6. Protections 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7. Additional characteristics 3
. . . . . . . . . . . . . . . .
1. OPERATING PRINCIPLE 3. RANGE / ELECTRICAL CHARACTERISTICS
Sample are intended to supply general electric devices and realize • Primary 400 V, delta connection,
functional insulation with main network (change of neutral network • Secondary 230 V, star connection,neutral out.
system). • Electrostatic shield between primary and secondary windings, earthed
Principle scheme connected by construction.
Input* Output Cats. Nos. Rating Losses Voltage Efficiency at Ucc Primary Secondary
(kVA) drop reference T° (%) terminals terminals
N
No load Due to cos fi = 1 (%) (mm²) eyelet (mm²) eyelet
A1 D1 losses load Ø Ø
(W) losses at
reference
A2 D2 T°(W)
0 425 45 6.3 108 265 4.3 94.4 4.1 10 10
0 425 46 10 188 408 3.9 94.4 4.0 10 10
A3 D3
0 425 47 16 236 686 4.5 94.5 4.4 35 35
* With adjustment taps ± 5% from 50kVA included 1 425 48 25 210 808 3.1 96.1 3.6 35 35
1 425 49 40 330 1191 2.8 96.4 3.6 35 70 10
2. MAIN CHARACTERISTICS 1 425 36 50 427 2341 4.7 94.7 5.5 35 8 70 10
1 425 37 63 486 2312 3.7 95.7 5.4 35 8 120 10
• Dry type air cooled transformer.
• Single phase 50 - 60 Hz Class 1. 1 425 38 80 578 2189 3.2 96.2 5.0 70 10 120 10
• Insulation and heating: Class H. 1 425 39 100 733 2527 2.7 96.4 3.9 120 10 120 10
• Insulation voltage:
• Primary 400 V, delta connection,
- 3000 V between windings,
- 3000 V between windings and earth, • Secondary 400 V, star connection, neutral out.
• Ambiant temperature: 40 °C. • Electrostatic shield between primary and secondary windings, earthed
connected by construction.
2.1 Conformities
Cats. Nos. Rating Losses Voltage Efficiency at Ucc Primary Secondary
• Conformity to IEC 60076-11 standard. (kVA) drop reference T° (%) terminals terminals
• CE marking. No load Due to cos fi = 1 (%) (mm²) eyelet (mm²) eyelet
• CEM compatibility. losses load Ø Ø
(W) losses at
2.2 Transformer’s protection reference
T°(W)
La pTransformers can be protected by aM type fuse or D type mcb on 0 428 25 6.3 108 281 4.3 94.1 4.3 10 10
primary side. 0 428 26 10 188 383 3.8 94.6 3.7 10 10
Transformers can be protected by gG type fuse or C type mcb on 0 428 27 16 256 506 3.0 95.4 3.2 35 35
secondary side. 1 428 28 25 210 859 3.3 95.9 3.7 35 35
1 428 29 40 330 1220 2.9 96.4 3.6 35 35
2.3 Casing
1 428 30 50 427 2341 4.7 94.7 5.5 35 8 35 8
2.3.1 Enclosed IP 21 - IK 08 1 428 31 63 486 2312 3.7 95.7 5.4 35 8 35 8
• RAL 7035. 1 428 32 80 578 2189 3.2 96.2 4.9 70 10 70 10
• Information: name-plaque on cover with: 1 428 33 100 733 2527 2.9 96.4 3.9 120 10 70 10
- reference number, 1 428 34 125 748 3350 2.7 96.8 3.3 120 10 120 10
- voltages and currents,
1 428 35(1) 160 748 4075 2.6 97.0 3.7 150 11 150 11
- standard,
- currents, 1 428 36(2) 200 841 4953 2.5 97.1 4.3 200 13 200 13
- rating, 1 428 37(2) 250 841 6660 2.7 97.0 5.8 200 15 200 15
- standard, 1 428 38(3) 315 982 6326 2.0 97.7 4.6 250 4x11 250 4x11
- frequency, 1 428 39(4) 400 1372 7466 1.9 97.8 3.9 315 4x11 315 4x11
- Ucc.
(1) Dimensions primary and secondary terminals: 30 x 5 mm Aluminium
2.3.2 Connection (2) Dimensions primary and secondary terminals: 40 x 5 mm Aluminium
Terminal blocs (cage system) or busbar and eyelet. (3) Dimensions primary and secondary terminals: 50 x 5 mm Aluminium
(4) Dimensions primary and secondary terminals: 63 x 5 mm Aluminium
1 425 36/37/38/39/48/49
1 428 28/29/30/31/32/33/34/35/36/37/38/39
T° amb = 50 °C - Max 85 % of the rated power C
T° amb = 60 °C - Max 75 % of the rated power
T° amb = 70 °C - Max 65 % of the rated power
Ex : with T° amb 70 °C, transformer reference 1 428 33 will have to be B Ø
loaded only with 65 kVA maximum
N D1 D2 D3 A1 A2 A3
4.1.1 400 V / 230 V range
Output Input
D1-D2-D3: 3 x 230 V + N A1-A2-A3: 3 x 400 V Cats. Nos Rating Dimensions (mm) Fixing (mm) Weight
(kVA) (kg)
A B C F G Ø
0 428 25/26/27 - 1 428 28/29
0 425 45 6.3 420 390 310 400 126 9 58
0 425 46 10 470 410 310 450 146 9 81.2
1 425 36/37/38/39/48/49
1 428 28/29/30/31/32/33/34/35/36/37/38/39
to 25 In.
(1) Dimensions include external lifting eyes.
7. ADDITIONAL CHARACTERISTICS
7.1 Calorific potential (Mega Joules)
400 V / 230 V range 400 V / 400 V range
Cats. Nos. P. Cal. (MJ) Cats. Nos. P. Cal. (MJ)
0 425 45 420 0 428 25 420
0 425 46 590 0 428 26 600
0 425 47 790 0 428 27 830
1 425 48 1360 0 428 28 1330
1 425 49 1830 0 428 29 1820
1 425 36 2660 0 428 30 2660
1 425 37 3090 0 428 31 3090
1 425 38 3600 0 428 32 3600
1 425 39 4320 0 428 33 4320
0 428 34 4480
0 428 35 5020
0 428 36 6890
0 428 37 8260
0 428 38 9160
0 428 39 11310
1 425 36/37/38/39/48/49
1 428 28/29/30/31/32/33/34/35/36/37/38/39