Brief Operating Instructions


Cerabar PMC11, PMC21,
PMP11, PMP21, PMP23
Process pressure measurement

These Instructions are Brief Operating Instructions; they are


not a substitute for the Operating Instructions pertaining to
the device.
Detailed information about the device can be found in the
Operating Instructions and the other documentation:
Available for all device versions via:
– Internet: www.endress.com/deviceviewer
– Smart phone/tablet: Endress+Hauser Operations App
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

Order code: XXXXX-XXXXXX


1. Ser. no.: XXXXXXXXXXXX
Ext. ord. cd.: XXX.XXXX.XX

Serial number

2. www.endress.com/deviceviewer Endress+Hauser
Operations App

3.

A0023555

2 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Table of contents

Table of contents
1 Document information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5 Turn down calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2 Basic safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9


2.1 Requirements concerning the staff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 Workplace safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.5 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

3 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4 Incoming acceptance and product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11


4.1 Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2 Product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.3 Storage and transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 Influence of the installation position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3 Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4 Mounting the profiled seal for the universal process adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.5 Mounting instructions for oxygen applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.6 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

6 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.1 Connecting the measuring unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.2 Connection conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.3 Connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.4 Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

7 Operation options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.1 Plug-on display PHX20 (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Endress+Hauser 3
Document information Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

1 Document information
1.1 Document function
The Brief Operating Instructions contain all the essential information from incoming
acceptance to initial commissioning.

1.2 Symbols used


1.2.1 Safety symbols

Symbol Meaning

DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.

WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.

CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.

NOTE!
NOTICE This symbol contains information on procedures and other facts which do not result in personal
injury.

1.2.2 Electrical symbols

Symbol Meaning Symbol Meaning

Protective ground connection Ground connection


A terminal which must be connected to A grounded terminal which, as far as
ground prior to establishing any other the operator is concerned, is grounded
connections. via a grounding system.

1.2.3 Tool symbols

Symbol Meaning

Open-ended wrench

A0011222

4 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Document information

1.2.4 Symbols for certain types of information

Symbol Meaning Symbol Meaning

Permitted Tip
Procedures, processes or actions that Indicates additional information.
are permitted.

Forbidden 1. , 2. , 3. … Series of steps


Procedures, processes or actions that
are forbidden.

Reference to documentation Result of a step

Reference to graphic Visual inspection

A Reference to page

1.2.5 Symbols in graphics

Symbol Meaning

1, 2, 3 ... Item numbers

1. , 2. , 3. … Series of steps

A, B, C, ... Views

1.3 Documentation
The document types listed are available:
In the Download Area of the Endress+Hauser Internet site: www.endress.com →
Download

1.3.1 Technical Information (TI): planning aid for your device


PMC11: TI01133P
PMP11: TI01133P
PMC21: TI01133P
PMP21: TI01133P
PMP23: TI01203P
The document contains all the technical data on the device and provides an overview of the
accessories and other products that can be ordered for the device.

1.3.2 Operating Instructions (BA): your comprehensive reference


BA01271P:
These Operating Instructions contain all the information that is required in various phases of
the life cycle of the device: from product identification, incoming acceptance and storage, to
Endress+Hauser 5
Document information Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

mounting, connection, operation and commissioning through to troubleshooting,


maintenance and disposal.

1.3.3 Safety Instructions (XA)


Safety Instructions (XA) are supplied with the device depending on the approval. These
instructions are an integral part of the Operating Instructions.

Device Directive Documentation Option 1)

PMP21 ATEX II 1/2G Ex ia IIC T4 Ga/Gb XA01271P BA


PMP23

PMC21 ATEX II 2G Ex ia IIC T4 Gb XA01271P BB

PMC21 ATEX II 3G Ex ec IIC T4 Gc XA01533P BC


PMP21

PMC21 FM IS Cl. I, Div.1 Gr. A-D T4 XA01321P FA


PMP21
PMP23

PMC21 CSA C/US IS Cl. I Div. 1 Gr. A-D XA01322P CB


PMP21
PMP23

PMC21 EAC Ex ia IIC T4 Ga/Gb XA01540P GA


PMP21
PMP23

PMC21 IEC Ex ia IIC T4 Ga/Gb XA01271P IA


PMP21
PMP23

PMC21 NEPSI Ex ia IIC T4 XA01363P NA


PMP21
PMP23

PMC21 TIIS Ex ia IIC T4 In preparation TA


PMP21
PMP23

1) Product Configurator, order code for "Approval"

The nameplate provides information on the Safety Instructions (XA) that are relevant for
the device.

6 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Document information

1.4 Terms and abbreviations

p
0
LRL LRV URV URL MWP OPL
A0029505

Item Term/ Explanation


abbreviation

1 OPL The OPL (over pressure limit = sensor overload limit) for the measuring device depends on
the lowest-rated element, with regard to pressure, of the selected components, i.e. the
process connection has to be taken into consideration in addition to the measuring cell.
Also observe pressure-temperature dependency. For the relevant standards and additional
notes, see the "Pressure specifications" section of the Operating Instructions .
The OPL may only be applied for a limited period of time.

2 MWP The MWP (maximum working pressure) for the sensors depends on the lowest-rated
element, with regard to pressure, of the selected components, i.e. the process connection
has to be taken into consideration in addition to the measuring cell. Also observe
pressure-temperature dependency. For the relevant standards and additional notes, see
the "Pressure specifications" section of the Operating Instructions .
The MWP may be applied at the device for an unlimited period.
The MWP can also be found on the nameplate.

3 Maximum sensor Span between LRL and URL


measuring range This sensor measuring range is equivalent to the maximum calibratable/adjustable span.

Endress+Hauser 7
Document information Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

Item Term/ Explanation


abbreviation

4 Calibrated/adjusted Span between LRV and URV


span Factory setting: 0 to URL
Other calibrated spans can be ordered as customized spans.

p - Pressure

- LRL Lower range limit

- URL Upper range limit

- LRV Lower range value

- URV Upper range value

- TD (turn down) Turn down


The turn down is preset at the factory and cannot be changed.
Example - see the following section.

1.5 Turn down calculation

1=2 3
LRL LRV URV URL

A0029545

1 Calibrated/adjusted span
2 Zero point-based span
3 URL sensor

Example

• Sensor:10 bar (150 psi) • Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)


• Upper range value (URL) = 10 bar (150 psi) • Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
Turn down (TD):

URL
TD =
|URV - LRV|

10 bar (150 psi)


TD = = 2
|5 bar (75 psi) - 0 bar (0 psi)|

In this example, the TD is 2:1.


This span is based on the zero point.

8 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Basic safety instructions

2 Basic safety instructions


2.1 Requirements concerning the staff
The staff must fulfill the following requirements for their tasks:
‣ Trained staff: Must have a qualification which corresponds to their function and tasks.
‣ Authorized by the plant operator.
‣ Familiar with the national regulations.
‣ Before starting their work: Must have read and understood all instructions in the operating
manual and supplementary documentation as well as the certificate (depending on the
application).
‣ Must comply with all instructions and the regulatory framework.

2.2 Designated use


2.2.1 Application and media
The Cerabar is used to measure absolute and gauge pressure in gases, vapors and liquids. The
process-wetted materials of the measuring device must have an adequate level of resistance to
the media.
The measuring device may be used for the following measurements (process variables)
• in compliance with the limit values specified under "Technical data"
• in compliance with the conditions that are listed in additional documentation such as the
XA and this manual.

Measured process variable


• PMC11: gauge pressure
• PMP11: gauge pressure
• PMC21: gauge pressure or absolute pressure
• PMP21: gauge pressure or absolute pressure
• PMP23: gauge pressure or absolute pressure

Calculated process variable


Pressure

2.2.2 Incorrect use


The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in
verifying the corrosion resistance of process-wetted materials, but does not accept any
warranty or liability.

2.2.3 Residual risks


When in operation, the housing may reach a temperature close to the process temperature.
Danger of burns from contact with surfaces!
‣ For elevated process temperatures, ensure protection against contact to prevent burns.
Endress+Hauser 9
Product description Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

2.3 Workplace safety


For work on and with the device:
‣ Wear the required personal protective equipment according to federal/national
regulations.
‣ Switch off the supply voltage before connecting the device.

2.4 Operational safety


Risk of injury!
‣ Operate the device in proper technical condition and fail-safe condition only.
‣ The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
‣ If, despite this, modifications are required, consult with Endress+Hauser.
Hazardous area
To eliminate the risk of danger to persons or the facility when the device is used in the
approval-related area (e.g. explosion protection, pressure equipment safety):
‣ Check the nameplate to verify if the device ordered can be put to its intended use in the
approval-related area.
‣ Observe the specifications in the separate supplementary documentation, such as the XA or
SD, which is an integral part of these Instructions.

2.5 Product safety


This measuring device is designed in accordance with good engineering practice to meet state-
of-the-art safety requirements, has been tested, and left the factory in a condition in which it
is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EU
directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms
this by affixing the CE mark to the device.

3 Product description
See Operating Instructions.

10 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Incoming acceptance and product identification

4 Incoming acceptance and product identification


4.1 Incoming acceptance
• Is the order code on the delivery note (1) identical to the order code on the product sticker
(2)?
• Are the goods undamaged?
• Do the data on the nameplate correspond to the order specifications and the delivery note?
• If required (see nameplate): Are the safety instructions (XA) present?
• Is the documentation available?
If one of these conditions does not apply, please contact your
Endress+Hauser sales office.

4.2 Product identification


The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is displayed.
For an overview of the technical documentation provided, enter the serial number from the
nameplates in the W@M Device Viewer (www.endress.com/deviceviewer)

4.2.1 Nameplate

1
2 Cerabar
Made in Germany,
D-79689 Maulburg
3 Ord. cd.:
4 Ser. no.:
5 Ext. ord. cd.:

Date:
TAG:

A0024456

1 Manufacturer's address
2 Device name
3 Order number
4 Serial number
5 Extended order number

Endress+Hauser 11
Installation Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

4.3 Storage and transport


4.3.1 Storage conditions
Use original packaging.
Store the measuring device in clean and dry conditions and protect from damage caused by
shocks (EN 837-2).

Storage temperature range


–40 to +85 °C (–40 to +185 °F)

4.3.2 Transporting the product to the measuring point


LWARNING
Incorrect transport!
Housing and diaphragm may become damaged, and there is a risk of injury!
‣ Transport the measuring device to the measuring point in its original packaging or by the
process connection.

5 Installation
5.1 Installation conditions
• No moisture may enter the housing when installing or operating the device, or when
establishing the electrical connection.
• For metal M12 plugs: Do not remove the protection cap (only for IP69 and Ex ec version) of
the M12 plug terminal until shortly before the electrical connection.
• Do not clean or touch process isolating diaphragms with hard and/or pointed objects.
• Do not remove the protector on the process isolating diaphragm until just before
installation.
• Always firmly tighten the cable entry.
• Point the cable and connector downwards where possible to prevent moisture from entering
(e.g. rain or condensation water).
• Protect the housing from impact
• The following instruction applies for devices with a gauge pressure sensor and M12 plug or
valve plug:

NOTICE
If a heated device is cooled during the cleaning process (e.g. by cold water), a vacuum
develops for a short time, whereby moisture can penetrate the sensor through the
pressure compensation element (1).
Device could be destroyed!
‣ In this case, mount the device with the pressure compensation element (1) pointing
diagonally downwards where possible or to the side.

12 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Installation

1 1 1
A0022252

5.2 Influence of the installation position


Any orientation is possible. However, the orientation may cause a zero point shift i.e. the
measured value does not show zero when the vessel is empty or partially full.

A B C

A0024708

Type Process isolating diaphragm Process isolating diaphragm Process isolating diaphragm
axis is horizontal (A) pointing upwards (B) pointing downwards (C)

PMP11 Calibration position, no effect Up to +4 mbar (+0.058 psi) Up to –4 mbar (–0.058 psi)
PMP21
PMP23

PMC11, PMC21 Calibration position, no effect Up to +0.3 mbar (+0.0044 psi) Up to –0.3 mbar (–0.0044 psi)
< 1 bar (15 psi)

PMC11, PMC21 Calibration position, no effect Up to +3 mbar (+0.0435 psi) Up to –3 mbar (–0.0435 psi)
≥1 bar (15 psi)

5.3 Mounting location


5.3.1 Pressure measurement

Pressure measurement in gases


Mount the device with shutoff device above the tapping point so that any condensate can flow
into the process.

Pressure measurement in vapors


For pressure measurement in vapors, use a siphon. The siphon reduces the temperature to
almost ambient temperature. Mount the device with a shutoff device at the same height as
the tapping point.
Advantage:
only minor/negligible heat effects on the device.

Endress+Hauser 13
Installation Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

Note the max. permitted ambient temperature of the transmitter!

Pressure measurement in liquids


Mount the device with a shutoff device at the same height as the tapping point.

5.3.2 Level measurement


• Always install the device below the lowest measuring point.
• Do not install the device at the following positions:
– In the filling curtain
– In the tank outlet
– In the suction area of a pump
– Or at a point in the tank which could be affected by pressure pulses from the agitator.

5.4 Mounting the profiled seal for the universal process adapter
For details on mounting, see KA00096F/00/A3.

5.5 Mounting instructions for oxygen applications


See Operating Instructions.

5.6 Post-installation check

 Is the device undamaged (visual inspection)?

Does the device conform to the measuring point specifications?


For example:
 • Process temperature
• Process pressure
• Ambient temperature range
• Measuring range

 Are the measuring point identification and labeling correct (visual inspection)?

 Is the device adequately protected from precipitation and direct sunlight?

 Are the securing screws tightened securely?

 Does the pressure compensation element point downwards at an angle or to the side?

 To prevent the penetration of moisture: are the connecting cables/plugs pointing downwards?

14 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Electrical connection

6 Electrical connection
6.1 Connecting the measuring unit
6.1.1 Terminal assignment
LWARNING
Risk of injury from the uncontrolled activation of processes!
‣ Switch off the supply voltage before connecting the device.
‣ Make sure that downstream processes are not started unintentionally.
LWARNING
Supply voltage might be connected!
Risk of explosion!
‣ Make sure that no supply voltage is applied when connecting.
‣ Switch off the supply voltage before connecting the device.
LWARNING
Limitation of electrical safety due to incorrect connection!
‣ In accordance with IEC/EN61010 a separate circuit breaker must be provided for the
device .
‣ The device must be operated with a 500 mA fine-wire fuse (slow-blow).
‣ When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or
Installation or Control Drawings.
‣ All explosion protection data are given in separate documentation which is available upon
request. The Ex documentation is supplied as standard with all devices approved for use in
explosion hazardous areas.
‣ Protective circuits against reverse polarity are integrated.
Connect the device in the following order:
1. Check whether the supply voltage matches the supply voltage indicated on the
nameplate.
2. Connect device in accordance with the following diagram.
Switch on supply voltage.
For devices with a cable connection: do not close reference air hose (see (a) in the following
drawings)! Protect reference air hose against penetration by water/condensate.

Endress+Hauser 15
Electrical connection Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

4 to 20 mA output
Device M12 plug Valve plug Cable

PMC11 0.5A 0.5A 1 0.5A


PMP11 L+ 1 L+ L+
PMC21 2 1
PMP21 3 2
3 4 L–
PMP23
L– 3
2
A0023487 L–
(a)
A0022823 A0023783

1 brown = L+
2 blue = L-
3 green/yellow = ground connection
(a) reference air hose

0 to 10 V output
Device M12 plug Valve plug Cable

PMC11 0.5A 1 -
PMP11 L+
2 1 3
4
3
2 L–
L–
A0017576
L+
0.5A
A0022822

6.1.2 Supply voltage


LWARNING
Supply voltage might be connected!
Risk of explosion!
‣ When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations as well as the Safety Instructions.
‣ All explosion protection data are given in separate documentation which is available upon
request. The Ex documentation is supplied as standard with all devices approved for use in
explosion hazardous areas.

Electronic version Device Supply voltage

4 to 20 mA output PMC11 10 to 30 V DC
PMP11
PMC21
PMP21
PMP23

0 to 10 V output PMC11 12 to 30 V DC
PMP11

16 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Electrical connection

6.1.3 Current consumption and alarm signal

Number of wires Device Normal operation Alarm signal 1)

2 PMC11 ≤ 26 mA > 21 mA
PMP11
PMC21
PMP21
PMP23

3 PMC11 < 12 mA 11 V
PMP11

1) For MAX alarm (factory setting)

6.2 Connection conditions


6.2.1 Cable specification
For valve plug: < 1.5 mm2 (16 AWG) and Ø3.5 to 6.5 mm (0.14 to 0.26 in)

6.3 Connection data

6.3.1 Load (for 4 to 20 mA devices )


In order to guarantee sufficient terminal voltage in two-wire devices, a maximum load
resistance RL (including line resistance) must not be exceeded, depending on the supply
voltage UB of the supply unit.

R L max
[W ]
1068

614 2 R L max £ U B - 6.5V


22mA

10 20 30 UB
[V]
1

A0029452

1 Power supply 10 to 30 V DC
2 RLmax maximum load resistance
UB Supply voltage

6.3.2 Load resistance (for 0 to 10 V devices)


The load resistance must be ≥ 5 [kΩ].

Endress+Hauser 17
Operation options Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

6.4 Post-connection check

 Is the device or cable undamaged (visual check)?

 Do the cables comply with the requirements ?

 Do the cables have adequate strain relief?

 Are all the cable glands installed, firmly tightened and leak-tight?

 Does the supply voltage match the specifications on the nameplate?

 Is the terminal assignment correct ?

 If required: Has protective ground connection been established ?

7 Operation options
7.1 Plug-on display PHX20 (optional)
No display or other operation facility is required to operate the device. However, devices with
a valve plug can be fitted with the optional local display PHX20.
A 1-line liquid crystal display (LCD) is used. The local display shows measured values, fault
messages and information messages. The device display can be turned in 90° steps. Depending
on the orientation of the device, it is therefore easy to read the measured values.

7.1.1 Storage conditions


• Use original packaging.
• Storage temperature range: –30 to +80 °C (–22 to +176 °F)

7.1.2 Installation

1 2 3 4

A0022208

1. Place seals between the sensor/plug-on display and the plug-on display/connector.
2. Fit the plug-on display (2) between the connector (3) and connector socket (1) of the
sensor.
3. Replace the securing screw (4) with the longer screw included in the delivery.

18 Endress+Hauser
Cerabar PMC11, PMC21, PMP11, PMP21, PMP23 Operation options

4. An adhesive label (included in the delivery) with information on the technical unit can
be fixed beneath the LED display.

7.1.3 Technical data


See Operating Instructions.

7.1.4 Electrical connection

Pin assignment
LWARNING
Is the supply voltage switched off?
Risk of electric shock!
‣ Switch off the supply voltage before connecting the device.
• PIN 1: L+ (supply voltage UB)
• PIN 2: L- (0 V)
• PIN 3: Not assigned

Supply voltage
The supply voltage (mostly 24 V DC) must be greater than the sum of the voltage drop Us at
the sensor, the voltage drop of 5 V at the display and other voltage loss Ua (such as additional
evaluation and power loss).
The following therefore applies: Ub = Us + 5 V + Ua

Post-connection check

 Is the device or cable undamaged (visual check)?

 Are all cable glands installed, securely tightened and leak-tight?

 If supply voltage is present, is the device ready for operation and do values appear on the display module?

7.1.5 Commissioning
NOTICE
Risk of injury from the uncontrolled activation of processes!
‣ Ensure that no uncontrolled processes are activated in the system.
Configuring the menu items
To configure the menu items, loosen the 4 Phillips screws (1) on the display and remove the
cover.

Endress+Hauser 19
Operation options Cerabar PMC11, PMC21, PMP11, PMP21, PMP23

1 1

A B
1 1

A0022209

A Move down and select the items


B Move up and select the items
A+B Select the item to configure or acknowledge the setting

Setting the decimal point


See Operating Instructions.

Out of range setting


See Operating Instructions.

20 Endress+Hauser