MLL Emta

The document provides safety precautions and specifications for the MasterLogic-50 Series FEnet I/F Module. It details warnings and cautions for safe usage and outlines general specifications including operating temperature, storage conditions, vibration tolerance, and more.

Uploaded by

Gabriel Cores
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
200 views2 pages

MLL Emta

The document provides safety precautions and specifications for the MasterLogic-50 Series FEnet I/F Module. It details warnings and cautions for safe usage and outlines general specifications including operating temperature, storage conditions, vibration tolerance, and more.

Uploaded by

Gabriel Cores
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Safety Precautions Before handling the product

 Safety Precautions is for using the product safely and correctly in order to prevent Read this data sheet carefully prior to any operation, mounting, installation or 1. Introduction
accidents and danger, so always follow the instructions.
start-up of the product.
DATASHEET  The precautions explained here only apply to Smart I/O Series. This datasheet provides brief information about characteristics, configurations,
* MasterLogic-50 Series is available on SoftMaster Ver1.2 or later.
For safety precautions on the PLC system, refer to MasterLogic PLCs User’s manual.
and usages of MasterLogic-50 PLC FEnet I/F Module(MLL-EMTA).
 The precautions are divided into 2 sections, ‘Warning’ and ‘Caution’. Each of the
meanings is represented as follows. Name ML50 Fast Ethernet I/F Module Datasheet 2. General Specifications
If violated instructions, it may cause death, fatal injury or a Code 10310000864
MasterLogic-50 Series Warning considerable loss of property. It describes the General Specifications for of MasterLogic-50 PLC .
FEnet I/F Module Caution
If violated instructions, it may cause a slight injury or a slight Revision History No. Item Specification Standard
loss of property. Operating
1 0 ~ 55C
 The symbols which are indicated in the PLC and User’s Manual mean as follows. Publication Version Description temperature

MLL-EMTA 2007. 8 Ver. 1.0 The First Edition 2 Storage temperature -25 ~ 70C
Give warnings and cautions to prevent from risk of injury, fire, or malfunction. 2014.05 Ver1.1 Revised Address 3 Operating Humidity 5 ~ 95%RH, non-condensing
4 Storage humidity 5 ~ 95%RH, non-condensing
Give warnings and cautions to prevent from risk of electric shock.
Occasional vibration
 Store this datasheet in a safe place so that you can take out and read whenever Sweep
Frequency Acceleration Amplitude
necessary. Always forward it to the end user. count
10≤f∠57 Hz - 0.075 mm
10 times
5 Vibration 57 ≤f≤150 Hz 9.8 ㎨(1G) -
Warning Continuous vibration
in each IEC61131-2
direction
Frequency Acceleration Amplitude
 Do not contact the terminals while the power is applied. for
10≤f∠57 Hz - 0.035 mm
Risk of electric shock and malfunction. X, Y, Z
57≤f≤150 Hz 4.9 ㎨(0.5G) -
 Do not drop or insert any metallic object into the product. *Maximum shock acceleration: 147 ㎨(15G)
*Duration time :11 ms
Risk of fire, electric shock and malfunction. 6 Shocks IEC61131-2
*Pulse wave: half sine wave pulse
 Do not charge, heat, short, solder and break up the battery. ( 3 times in each of X, Y and Z directions )
Square wave
Risk of injury and fire by explosion and ignition. ±900 V
impulse noise
Electrostatic IEC61131-2
Voltage :4kV(contact discharge)
discharge IEC61000-4-2

Caution Radiated
electromagnetic 27 ~ 500 MHz, 10 V/m
IEC61131-2
7 Noise immunity IEC61000-4-3
field
 Ensure to check the rated voltage and terminal arrangement for
Digital/Analog I/O
the module before wiring work. Power
10310000864 Printed in Korea Fast transient Class communication IEC61131-2
Risk of electric shock, fire and malfunction. module
burst noise interface IEC61000-4-4

 Tighten the screw of terminal block with the specified torque range. Voltage 2kV 1kV

Risk of fire and electric shock if the terminal screw looses. 8 Atmosphere Free from corrosive gases and excessive dust
9 Altitude for use Up to 2,000m
 Use the PLC in an environment that meets the general 10 Pollution level 2 or lower
specifications contained in this datasheet. 11 Cooling method Self-cooling

Risk of electrical shock, fire, erroneous operation and deterioration of the PLC.
Remark
 Ensure that external load do not exceed the rating of output module.
1) IEC (International Electro-technical Commission):
Risk of fire and erroneous operation.
For more information on MasterLogic PLCs , contact your nearest Honeywell office . An international nongovernmental organization which promotes internationally cooperated
 Do not use the PLC in the environment of direct vibration standardization in electric/electronic fields, publishes international standards and manages
Australia Japan Singapore
Honeywell Ltd. Honeywell Inc. Honeywell Pte Ltd. Risk of electrical shock, fire and erroneous operation. applicable estimation system related with.
Phone : (61) 2-9353-4500 Phone: (81)3-5440-1395 Phone: (65) 6355-2828
Fax : (61) 2-9353-7677 Fax: (81)3-5440-1368 Fax: (65) 6445-3033 2) Pollution degree:
 Do not disassemble, repair or modify the PLC. An index indicating pollution level of the operating environment which decides insulation
China South Korea Thailand
Honeywell (Tianjin) Ltd. – Beijing Honeywell Co., Ltd. Honeywell Systems Ltd. Risk of electrical shock, fire and erroneous operation. performance of the devices. For instance, Pollution level 2 indicates the state generally that
Phone: (86-10) 8458-3280 Phone : (82) 2-799-6114 Phone: (662) 693-3099
Fax: (86-10) 8458-3102 Fax : (82) 2-792-9015 Fax: (662) 693-3085 only non- conductive pollution occurs. However, this state contains temporary conduction
 When disposing of PLC and battery, treat it as industrial waste.
Honeywell (Tianjin) Ltd. – Shanghai Malaysia Taiwan due to dew produced.
Phone: (86-21) 6237-0237 Honeywell Engineering Sdn Bhd. Honeywell Taiwan Ltd. Risk of poisonous pollution or explosion.
Fax : (86-21) 6237-3102 Phone: (603) 7958-4988 Phone: (886) 2-2245-1000
Fax: (603) 7958-8922 Fax: (886) 2-2245-3241
Indonesia 3. Performance Specification
PT Honeywell Indonesia New Zealand For Countries (SE Asia) Listed
Phone : (62) 21-535-8833 Honeywell Ltd. below, call Honeywell Singapore
Fax : (62) 21-5367-1008 Phone: (64-9) 623-5050 Office It describes the Performance Specification for of MasterLogic-50 PLC FEnet
Fax: (64-9) 623-5060 Pakistan, Cambodia, Laos,
India Myanmar, Vietnam and East Timor I/F module.
Honeywell Automation India Ltd. Philippines Precautions for use
Phone: (91) 20-5603-9400 Honeywell Systems Inc. For Countries Listed below, Items Performance
Fax: (91)-20-5603-9800 Phone: (63-2) 633-2830 call Honeywell India Office  Do not install in places other than PLC controlled place.
Fax: (63-2) 638-4013 Bangladesh, Nepal, and Sri Lanka  Ensure that the FG terminal is grounded with class 3 grounding which is dedicated to the PLC.
Speed 10/100Mbps
Otherwise, it may cause disorder or malfunction of the PLC.
Transfer System
Base Band
PLC Others PLC Others PLC Others Max. extended distance
-
of Station-to-Station
100m
Max. Segment Length.
< Best > < Good > < Bad > (Node-Hub)
Honeywell Process Solution Max. Node No. Able to link to 9 hub stages (Recommended)
Transfer Node Interval -
 Connect expansion connector correctly when expansion modules are needed.
HFS Asia Pacific Spec.
 Do not detach PCB from the case of the module and do not modify the module. Max. Protocol Vol. 512Byte
Honeywell Building  Turn off the power when attaching or detaching module. Excess Method of
CSMA/CD
17 Changin Business Park Central 1
 Cellular phone or walkie-talkie should be farther than 30cm from the PLC. Communication Range
 Input signal and communication line should be farther than minimum 100mm from a Frame Error Check 15 14 13
CRC16 = X + X + X + ... + X + X + 1
2
Singapore 486073 high-tension line and a power line in order not to be affected by noise and magnetic
Number of Max.
www.honeywellprocess.com/ field. Installation module 2

Base Basic and Expansion base


10310000864 Printed in Korea
Basic Power Consumption 300
Spec
Weight (g) 71
4. Cable Specification Classification Description Remark Remark
9. Warranty
(Yellow) packet 1) Since 10/100 BASE-TX cable structure is week in external noise, the
cable of No.1 & 2 which are TD+ & TD- and No.3 & 6 which are RD+ & (1) Warranty period
 TP(UTP) cable (10/100Mbps) No receiving the
Off - Honeywell provides a 12-month-warranty for new MasterLogic PLC systems
Item Unit Value packet RD shall be twisted respectively to be strong against noise.
and 90-day-warranty for spare parts, from the date of delivery.
Conductor RJ45 Connection part of RJ45 2) Hub power shall be with countermeasures against noise as separat- (2) Warranty conditions
Ω/km 93.5 ④ -
resistance(Max) -ed from PLC power. For troubles within the warranty period, Honeywell will replace the entire PLC or
connector connector
Insulation repair the troubled parts free of charge except in the following cases.
MΩ·km 2500 SPEED LED On 100Mbps operation - 3) The cable shall be installed min. 50 mm away from high current line
resistance(Min) 1) The troubles caused by improper condition, environment or treatment except
⑤ such as power line, etc.
(Green) Off 10Mbps operation - the instructions of Honeywell.
Voltage resistance V/min AC500
4) Contact an expert for terminal work, manufacture and installation of 2) The troubles caused by external devices.
Characteristic For fixing the expansion 3) The troubles caused by remodeling or repairing based on the user’s own
Ω(1~100MHz) 100±15 ⑥ Fixed Lever - cable.
impedance module (lower part) discretion.
10MHz 6.5 4) The troubles caused by improper usage of the product.
dB/100m ⑦ Fixed Lever For fixing the DIN rail -
Decrement 16MHz 8.2 5) The troubles caused by a reason which exceeded the expectation from
or less scientific and technical level when Honeywell manufactured the product.
20MHz 9.3 7. Precautions for system configuration
6) The troubles caused by natural disaster.
Near-end 10MHz 47
dB/100m 6. Installation and Wiring (3) This warranty is limited to the PLC itself only. It is not valid for the whole
crosstalk 16MHz 44 system which the PLC is attached to.
or less (1) IP addresses of FEnet I/F module shall be surely different from each other
decrement 20MHz 42
including this module. If connected via the repeated addresses,
1) Installation of MLL-EMTA (UTP) communication error may occur, leading to communication trouble.
Remark (2) Use the communication cable as specified only. If not, serious error may
1) Connecting cable for communication module is different from system occur to communication.
configuration and environment. So, consult with expert before the Network (3) Check communication cable if disconnected or shorted prior to installation
installation. (4) Tighten up communication cable connector until connected firmly. If cable
connection is unstable, serious error may occur to communication.
Hub
(5) If the cable is bent at a right angle or transformed compulsorily, cable
5. Parts Name and Descriptions
disconnection or connector damage in communication module will be
caused.
 MLL-EMTA (6) In order to equip FEnet I/F module, please insert uplift of the module on the
bottom into base board' groove first. And then, the top should be firmly fixed
① to enable lock equipment to lock. Without communication cable access and
right connection, errors to CPU may occur.
Twisted pair
② cable

8. Dimension

Unit : mm

8 pin RJ-45
connector

③  Max. segment length of 10/100BASE-TX is 100m (between this module and


④ the hub).
⑤ Straight cable
Signal
Pin No. between Hub & 1:1 cross cable
name
Module
⑥ 1 TD+ 1—1 1—3
⑦ 2 TD- 2—2 2—6
3 RD+ 3—3 3—1
 LED Description
6 RD- 6—6 6—2
4,5,7,8 N/A
Classification Description Remark
For fixing the expansion  Pin diagram for RJ-45 UTP Jack
① Fixed Lever -
module (upper part) Refer to the following pin number for Ethernet cable connection using UTP
RJ-45 connector.
On Normal -
RUN To make the cable, use RJ-45 (cutter and stripper hand tool for RJ-45) and
Off Stop Run - when it completed, check the wiring and contact with wiring check inspector if
Blink Interface with CPU - the connection is right.
I/F Off Stop interface with
-
CPU
Blink Transmitting the
-
data
TX ▶ RJ-45 (Front view)
② LED Off Stop transmitting
-
the data
Blink Receiving the data -
RX Off No Receiving the
- 1 2 3 4 5 6 7 8
data
On H/W error Check at center
ERR Off S/W error Ref. to User
manual
③ LINK LED Blink Receiving the -