CHARGER & POWER CABLE

SIZING FORMULAS
P O W E R I N G T E C H N O L O G Y

CHARGER SIZING FORMULAS POWER CABLING FORMULAS

1. CALCULATING CHARGER REQUIREMENTS WIRE GAUGE TABLE

1.1C AREA SIZE AREA SIZE AREA


SIZE
A = ——— + L AWG
CIRC. AWG CIRC. AWG CIRC.
H MILS MCM * MILS MCM * MILS

2. CALCULATING HOURS TO RECHARGE 18 1,620 1 83,690 600 600,000


16 2,580 0 105,600 700 700,000
14 4,110 00 131,100 750 750,000
1.1C
H = ——— 12 6,530 000 167,800 800 800,000
A-L 10 10,380 0000 211,600 900 900,000
8 16,510 250 250,000 1,000 1,000,000
3. CALCULATING CHARGER LOSSES (BTUs) 6 26,240 300 300,000 1,250 1,250,000
4 41,740 350 350,000 1,500 1,500,000
3 52,620 400 400,000 1,750 1,750,000
1
BTUs PER HOUR = ——— - 1 x Wdc x 3.42
EFF ( ) 2 66,360 500
SOURCE: Handbook 100 National Bureau of Standards.
500,000 2,000 2,000,000

NOTE: All wire size #6 and larger is stranded.


4. CALCULATING CHARGER INPUT CURRENT DRAIN * All sizes larger than #0000 are expressed in MCM.
SINGLE-PHASE CHARGERS

1. CALCULATING WIRE SIZE REQUIREMENTS


EOUT x IOUT
IIN = ————————
EIN x EFF x P.F. A x LF x K
CMA = —————
THREE-PHASE CHARGERS
AVD
2. CALCULATING CURRENT CARRYING
EOUT x IOUT CAPACITY OF WIRE
IIN = ——————————
EIN x EFF x P.F. x √3
CMA x AVD
MAX. AMP = ——————
LF x K
TABLE OF CONVENTIONS
A = DC output rating of charger in amperes
TABLE OF CONVENTIONS
1.1 = Efficiency factor to return 100% ampere-hours
removed from a lead-acid battery. CMA = Cross section of wire In circular MIL area
Use 1.4 for NiCad batteries. A= Ultimate drain in amperes
C = Calculated number of ampere-hours discharged LF = Conductor loop feet
from battery. (time in hours x load) MAX. AMP = Maximum allowable amperes for given
H = Number of hours recharge time voltage drop
L = Load on system in amperes AVD = Allowable voltage drop
Wdc = Output volts x output amperes K = 11.1 constant factor for commercial (TW type)
IIN = Input current (amperes ac) copper wire (KS5482-01)
EOUT = Output voltage (volts dc) = 17.4 for aluminum (KS20189)
IOUT = Output current (amperes dc)
EIN = Input vollage (volts ac)
sizing_formulas-an-revC-0920.indd

EFF = Efficiency (e.g. 88% = 0.88)


P.F. = Power Factor (E.G. 92% = 0.92)
√3 = 1.7321

www.unipowerco.com