Test Report

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 5

TEST REPORT

Ø Filter Integrity Test Ø


Customer M/s Chandrakanth Nethralaya Certificate No FLT/2023-24/ 1132
Calicut Kerala Date of Test 20.05.2023
Next Due Date 20.11.2023
Test Description:
Determine the leakage size of installed filter system in a clean area/clean zone by aerosel challenge scanning method.
Details of Instruments Used for testing
Instrument Used Aerosol Photometer Instrument Sr. No. 4269
Make TEC Services Calibrated On 02.12.2022
Model PH-5 Calibration Due On 02.12.2023
Aerosol Generator Type Poly dispersed Aerosol Aerosol Used PAO
Details of Specification and Area
Test Specification Maximum Permiceable leakage 0.01% Occupancy State "At Rest"
Area of Test Operation Theatres Test Reference ISO-14644/1
AHU Number 1 Test Location Terminal HEPA Filter
Ø Obtained Test Results Ø
Average
Up Obtained Test Results
Filter Efficiency at SLP of DL for Tests
ROOM NAME Filter NAME Streem Test Status
Particle Size * after Installation **
Concentrati (% Leakage)
on (%)
HF-01 99.997% 0.3µm 0.01% 0.0000 Pass
HF-02 99.997% 0.3µm 0.01% 0.0000 Pass
HF-03 99.997% 0.3µm 0.01% 0.0000 Pass
Lasik OT 106
HF-04 99.997% 0.3µm 0.01% 0.0000 Pass
HF-05 99.997% 0.3µm 0.01% 0.0000 Pass
HF-06 99.997% 0.3µm 0.01% 0.0000 Pass

Note: * Overall or intrgral efficiency.


** These leak criteria have historically applied to scanning HEPA filters with a photometer; using
aerosol generated by Laskin Nozzle, But may not be applicable to scanning with other combinations
of aerosol and detector.
SLP Standard Leak Penetration
DL Designated Leak
Conclusion:
1.Leakage test of the above mensioned intalled filter system leakage size detected is with in the acceptable criteria mentioned.
Test Conducted By Checked & Approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Filter Integrity Test Ø
Customer M/s Chandrakanth Nethralaya Certificate No FLT/2023-24/ 1133
Calicut Kerala Date of Test 20.05.2023
Next Due Date 20.11.2023
Test Description:
Determine the leakage size of installed filter system in a clean area/clean zone by aerosel challenge scanning method.
Details of Instruments Used for testing
Instrument Used Aerosol Photometer Instrument Sr. No. 4269
Make TEC Services Calibrated On 02.12.2022
Model PH-5 Calibration Due On 02.12.2023
Aerosol Generator Type Poly dispersed Aerosol Aerosol Used PAO
Details of Specification and Area
Test Specification Maximum Permiceable leakage 0.01% Occupancy State "At Rest"
Area of Test Operation Theatres Test Reference ISO-14644/1
AHU Number 3 Test Location Terminal HEPA Filter
Ø Obtained Test Results Ø
Average
Up Obtained Test Results
Filter Efficiency at SLP of DL for Tests
ROOM NAME Filter NAME Streem Test Status
Particle Size * after Installation **
Concentrati (% Leakage)
on (%)
HF-01 99.997% 0.3µm 0.01% 0.0000 Pass
HF-02 99.997% 0.3µm 0.01% 0.0000 Pass
HF-03 99.997% 0.3µm 0.01% 0.0000 Pass
Retina & Cornea OT 106
HF-04 99.997% 0.3µm 0.01% 0.0000 Pass
HF-05 99.997% 0.3µm 0.01% 0.0000 Pass
HF-06 99.997% 0.3µm 0.01% 0.0000 Pass

Note: * Overall or intrgral efficiency.


** These leak criteria have historically applied to scanning HEPA filters with a photometer; using
aerosol generated by Laskin Nozzle, But may not be applicable to scanning with other combinations
of aerosol and detector.
SLP Standard Leak Penetration
DL Designated Leak
Conclusion:
1.Leakage test of the above mensioned intalled filter system leakage size detected is with in the acceptable criteria mentioned.
Test Conducted By Checked & Approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Filter Integrity Test Ø
Customer M/s Chandrakanth Nethralaya Certificate No FLT/2023-24/ 1134
Calicut Kerala Date of Test 20.05.2023
Next Due Date 20.11.2023
Test Description:
Determine the leakage size of installed filter system in a clean area/clean zone by aerosel challenge scanning method.
Details of Instruments Used for testing
Instrument Used Aerosol Photometer Instrument Sr. No. 4269
Make TEC Services Calibrated On 02.12.2022
Model PH-5 Calibration Due On 02.12.2023
Aerosol Generator Type Poly dispersed Aerosol Aerosol Used PAO
Details of Specification and Area
Test Specification Maximum Permiceable leakage 0.01% Occupancy State "At Rest"
Area of Test Operation Theatres Test Reference ISO-14644/1
AHU Number 2 Test Location Terminal HEPA Filter
Ø Obtained Test Results Ø
Average
Up Obtained Test Results
Filter Efficiency at SLP of DL for Tests
ROOM NAME Filter NAME Streem Test Status
Particle Size * after Installation **
Concentrati (% Leakage)
on (%)
HF-01 99.997% 0.3µm 0.01% 0.0000 Pass
HF-02 99.997% 0.3µm 0.01% 0.0000 Pass
HF-03 99.997% 0.3µm 0.01% 0.0000 Pass
Cataract OT - I 106
HF-04 99.997% 0.3µm 0.01% 0.0000 Pass
HF-05 99.997% 0.3µm 0.01% 0.0000 Pass
HF-06 99.997% 0.3µm 0.01% 0.0000 Pass

Note: * Overall or intrgral efficiency.


** These leak criteria have historically applied to scanning HEPA filters with a photometer; using
aerosol generated by Laskin Nozzle, But may not be applicable to scanning with other combinations
of aerosol and detector.
SLP Standard Leak Penetration
DL Designated Leak
Conclusion:
1.Leakage test of the above mensioned intalled filter system leakage size detected is with in the acceptable criteria mentioned.
Test Conducted By Checked & Approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Filter Integrity Test Ø
Customer M/s Chandrakanth Nethralaya Certificate No FLT/2023-24/ 1135
Calicut Kerala Date of Test 20.05.2023
Next Due Date 20.11.2023
Test Description:
Determine the leakage size of installed filter system in a clean area/clean zone by aerosel challenge scanning method.
Details of Instruments Used for testing
Instrument Used Aerosol Photometer Instrument Sr. No. 4269
Make TEC Services Calibrated On 02.12.2022
Model PH-5 Calibration Due On 02.12.2023
Aerosol Generator Type Poly dispersed Aerosol Aerosol Used PAO
Details of Specification and Area
Test Specification Maximum Permiceable leakage 0.01% Occupancy State "At Rest"
Area of Test Operation Theatres Test Reference ISO-14644/1
AHU Number 4 Test Location Terminal HEPA Filter
Ø Obtained Test Results Ø
Average
Up Obtained Test Results
Filter Efficiency at SLP of DL for Tests
ROOM NAME Filter NAME Streem Test Status
Particle Size * after Installation **
Concentrati (% Leakage)
on (%)
HF-01 99.997% 0.3µm 0.01% 0.0000 Pass
HF-02 99.997% 0.3µm 0.01% 0.0000 Pass
HF-03 99.997% 0.3µm 0.01% 0.0000 Pass
Cataract OT - II 106
HF-04 99.997% 0.3µm 0.01% 0.0000 Pass
HF-05 99.997% 0.3µm 0.01% 0.0000 Pass
HF-06 99.997% 0.3µm 0.01% 0.0000 Pass

Note: * Overall or intrgral efficiency.


** These leak criteria have historically applied to scanning HEPA filters with a photometer; using
aerosol generated by Laskin Nozzle, But may not be applicable to scanning with other combinations
of aerosol and detector.
SLP Standard Leak Penetration
DL Designated Leak
Conclusion:
1.Leakage test of the above mensioned intalled filter system leakage size detected is with in the acceptable criteria mentioned.
Test Conducted By Checked & Approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya
TEST REPORT
Ø Filter Integrity Test Ø
Customer M/s Chandrakanth Nethralaya Certificate No FLT/2023-24/ 1136
Calicut Kerala Date of Test 20.05.2023
Next Due Date 20.11.2023
Test Description:
Determine the leakage size of installed filter system in a clean area/clean zone by aerosel challenge scanning method.
Details of Instruments Used for testing
Instrument Used Aerosol Photometer Instrument Sr. No. 4269
Make TEC Services Calibrated On 02.12.2022
Model PH-5 Calibration Due On 02.12.2023
Aerosol Generator Type Poly dispersed Aerosol Aerosol Used PAO
Details of Specification and Area
Test Specification Maximum Permiceable leakage 0.01% Occupancy State "At Rest"
Area of Test Operation Theatres Test Reference ISO-14644/1
AHU Number 5 Test Location Terminal HEPA Filter
Ø Obtained Test Results Ø
Average
Up Obtained Test Results
Filter Efficiency at SLP of DL for Tests
ROOM NAME Filter NAME Streem Test Status
Particle Size * after Installation **
Concentrati (% Leakage)
on (%)
HF-01 99.997% 0.3µm 0.01% 0.0000 Pass
HF-02 99.997% 0.3µm 0.01% 0.0000 Pass
HF-03 99.997% 0.3µm 0.01% 0.0000 Pass
Septic OT 106
HF-04 99.997% 0.3µm 0.01% 0.0000 Pass
HF-05 99.997% 0.3µm 0.01% 0.0000 Pass
HF-06 99.997% 0.3µm 0.01% 0.0000 Pass

Note: * Overall or intrgral efficiency.


** These leak criteria have historically applied to scanning HEPA filters with a photometer; using
aerosol generated by Laskin Nozzle, But may not be applicable to scanning with other combinations
of aerosol and detector.
SLP Standard Leak Penetration
DL Designated Leak
Conclusion:
1.Leakage test of the above mensioned intalled filter system leakage size detected is with in the acceptable criteria mentioned.
Test Conducted By Checked & Approved By Test Witnessed By

for SRM Clean Room Associates for SRM Clean Room Associates for Chandrakanth Nethralaya

You might also like