Transformer
Transformer
As you know, the amount of power used by the load of an electrical circuit is equal to the current
in the load times the voltage across the load, or P = EI. If, for example, the load in an electrical
circuit requires an input of 2 amperes at 10 volts (20 watts) and the source is capable of delivering
only 1 ampere at 20 volts, the circuit could not normally be used with this particular source.
However, if a transformer is connected between the source and the load, the voltage can be
decreased (stepped down) to 10 volts and the current increased (stepped up) to 2 amperes.
Notice in the above case that the power remains the same. That is, 20 volts times 1 ampere equals
the same power as 10 volts times 2 amperes.
BASIC OPERATION OF A TRANSFORMER
In its most basic form a transformer consists of:
Refer to the transformer circuit in figure 1 as you read the following explanation: The primary
winding is connected to a 60 hertz ac voltage source. The magnetic field (flux) builds up (expands)
and collapses (contracts) about the primary winding. The expanding and contracting magnetic
field around the primary winding cuts the secondary winding and induces an alternating voltage
into the winding. This voltage causes alternating current to flow through the load. The voltage
may be stepped up or down depending on the design of the primary and secondary windings.
Figure 1.—Basic transformer action.
Shell-Core Transformers
The most popular and efficient transformer core is the SHELL CORE, as illustrated in figure 3. As
shown, each layer of the core consists of E- and I-shaped sections of metal. These sections are
butted together to form the laminations. The laminations are insulated from each other and then
pressed together to form the core.
Figure 3.—Shell-type core construction.
The transformer represented in part (B) of figure 4 has a ten-turn primary and a two-turn
secondary. Since the flux induces one volt per turn, the total voltage across the secondary is two
volts. Notice that the volts per turn are the same for both primary and secondary windings. Since
the counter emf in the primary is equal (or almost) to the applied voltage, a proportion may be set
up to express the value of the voltage induced in terms of the voltage applied to the primary and
the number of turns in each winding. This proportion also shows the relationship between the
number of turns in each winding and the voltage across each winding.
TRANSFORMER RATING:
We know that, Transformer always rated in kVA. Below are the two simple formulas to find
the rating of Single phase and three phase Transformers.
In simple words,
Transformer rating in kVA = 100 kVA
Primary Voltages = 11000 = 11kV
Primary Current = 5.25 A
Secondary Voltages = 415V
Secondary Current = 139.1 Amperes.
Once again, we noticed that the rating of Transformer (on Nameplate) is 100kVA but according to
calculation…it comes about 57kVA…
The difference comes due to ignorance of that we used single phase formula instead of three
phase formula.
EXAMPLE 1:
How to find primary and secondary side current of a 1500 kVA transformer (11kv/400v).
As we know
KVA = √3* V * I *1000
1500 = 1.7321 * 11000 * I
So
I = 1500* 1000 /1.7321/11000
I = 78.72 Amps
This is full load current of transformer
You can calculate current on 400 volts side.
11 KV voltage is phase to phase voltage.
EXAMPLE 3: