PROJECT NUMBER SHEET NUMBER

PROJECT: SINOGULF
60493231 1
CALCULATION PREPARED BY DATE CHECKED BY DATE VERIFIED BY DATE REVISION
WATER SUPPLY
TITLE: MM 22/05/2016 KP 22/05/2016 KP 22/05/2016 0
TRANSFER PUMP SIZING CALCULATION (RESIDENTIAL) (Tag No: SG-GF-TP-01)

A Discharge pipe sizing Formula Values Units Source


Roof water tank capacity 230 m3 Water demand calculation
Duration of filling roof tank 6 hours Assumed
38.3333333333 m3/hr
Flowrate in pipework Q1 10.65 lps
0.01 m3/sec
Velocity of flow V1 1.5 m/sec RSB
Diameter of pipe 0.095 m SQRT((Q1*4)/(3.14*V1))
Diameter of pipe D 125 mm

B Pump sizing
Number of pumps in operation 3 Quantity Selection
4.86 lps
Pump flow rate Q2
0.0049 m3/sec
Velocity of flow V1 1.5 m/sec RSB
0.064 m SQRT((Q2*4)/(3.14*V1))
Diameter of pump discharge pipe (each pump)
D 80 mm

C Pumped main pipe pressure loss calculation


Total running length of pipe 250 m 350 to 600
Equivalent length 25 % Assumed
Total length of pipe L1 313 m

Flowrate of pump Q3=Q1x60 639 lpm


Friction loss Coefficient for pipe 150 See Appendix for plastic pipe
Pressure loss due to friction (Bar per m of pipe) P1 0.0005 bar See Appendix for formula
Pressure loss due to friction P2=P1xL1 1.694 m
Pressure loss through filter P2 10 m As per catalog
Static head P3 30 m Building height
Required residual pressure P4 10 m
Head of pump P5=P2+P3+P4 51.69 m
say P6 62 m

D Electrical power load calculation


Power P (g*Q*H)/n kW
Gravity g 9.81 m/s2
Flow rate Q (Q2) 0.0049 m3/s
Head of the pump H (P6) 62 m
Efficiency of pump n 60% %
Power required for each pump P 4.93 kW

E Summary
Pump flow rate 4.86 l/s
Head of pump 62 m
Power 4.93 kW
Pump discharge pipe size 80 mm
Pump header discharge pipe size 125 mm
Number of duty pumps 3 Quantity
Total number of pumps 4 Quantity