0% found this document useful (0 votes)
23 views

Lec-Gas Witch: Program Thermostat Owners Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views

Lec-Gas Witch: Program Thermostat Owners Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Program Thermostat Owners Manual and could cause personal injury and/or property damage. 1.

and could cause personal injury and/or property damage. 1. Move system switch to heat mode. If the auxiliary heating system has a standing pilot,
ModeCP2810 Selector Switches be sure to light it.
Temperature Keys: Keys for Battery Compartment:
LCD Display:Shows raising or lowering trmperature Front access allows Electric/Gas Switch (Fan Option) 2. Press to adjust thermostat setting to 1℃ above room temperature. The heating
Time,Day,Temperature, setting. easy insertion of two
Program Number,and Reviews filter usage AA 1.5V batteries. Front Door: system should begin to operate. The display should show “STG1”. However, if the
in hours and minutes.
other feature information
as required.
Also resets filter Battery cover setpoint temperature display is flashing, the compressor lockout feature is operating
counter to zero. Open with one
finger from top. (see Configuration menu, item 5).
3. Adjust temperature setting to 3° above room temperature.If your system configuration
F is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the
display should show “STG1+2” 2”.
4. Press to adjust the thermostat below room temperature. The heating system should
stop operating.
Emergency System
Fan Switch: Fan
system fan

switch for Automatic EMER bypasses the Heat Pump to use the heat source wired to terminal E on the
cool off heat auto on auto
or Continuous fan
operation.
thermostat. EMER is typically used when compressor operation is not desired, or you
prefer back-up heat only.

GAS
System Switch:
Selector switch for
Cool,Off,Heat or auto.
1. Press SYSTEM switch to select Heat mode. then press EMER key.. “EMER” will show
lec-Gas K2 on the display.

ELEC
Soft touch programming Front Door:Covers keys Open with one finger from left or right. witch 2. Press to adjust thermostat setting above room temperature. The Aux. heating system
FEATURES buttons (see below) will begin to operate. The display will show “STG1” “EMER” to indicate that the Aux.
Structure of thermostat and explanation for the keypads Figure 1. Electric/Gas Switch (Fan Option) system is operating.
For entering This thermostat is configured from the factory to operate a heat/ cool, fossil fuel (gas, oil, 3. Adjust temperature setting to 2°C above room temperature.The auxiliary heat system
minute of day. etc.), forced air system. It is configured correctly for any system that DOES NOT require should begin to operate and the display should show “STG1+2” 2”.
For entering
hour of day. For entering day of week.
Overrides energy- Enters Program Mode
the thermostat to energize the fan on a call for heat. If you system is an electric heat or 4. Press to adjust the thermostat below room temperature. The Aux. heating system
saving program for reviewing and changing heat-pump system that requires the thermostat to turn on the fan on a call for heat, should stop operating.
temperatures while weekday, weekend,or daily
you are at home
HOME
TODAY
HOUR MIN DAY PROG programs. locate the ELEC/GAS switch on the back of the thermostat (see fig. 1) and switch it to Cooling System
for the day.
the ELEC position. This will allow the thermostat to energize the fan immediately on a 1. Move SYSTEM switch to select the Cool mode.
Measures and displays
heating and cooling system ENER
AUTO PROG
EMER
HOLD call for heat. If you are unsure if the heating/ cooling system requires the thermostat to 2. Press to adjust thermostat setting below room temperature. The blower should come
operating time for Today, PROG DAY / RUN

Yesterday,This Week,Last control the fan, contact a qualified heating and air conditioning service person. When the on immediately on high speed, followed by cold air circulation. The display should show
Week,or Total. By monitoring
your energy usage, you can
Provides permanent temperature setting thermostat is configured for Heat Pump, the thermostat will always power the circulator “STG1”.
by overriding stored programs. It also
program the thermostat to EMER Mode. returns the thermostat to current program fan on a call for heat in the HEAT mode. The ELEC/GAS switch must be set to match the 3. Adjust temperature setting to 2°C below room temperature. The second stage cooling
optimize energy savings. control from manual override or Home
Automatically programs the Today mode. Returns display to current
type of Auxiliary heat your system uses for proper operation in the EMERgency mode. should begin to operate and
thermostat to its built-in time and temperature. All wiring diagrams are for typical systems only. Refer to equipment manufacturers’ the display should show “STG1+2”
ENERGY STAR R compliant Selects the day or days to
program setting. review or change in Program instructions for specific system wiring information. 4. Press to adjust the temperature setting above room temperature. The cooling system
Mode. Attach Thermostat Base to Wall should stop operating.
We are pleased you have selected one of our broad line of wall thermostat. Our products 1. Remove the packing material from the thermostat. Gently pull the cover straight off the CONFIGURATION MENU
are manufactured to high quality standards and are designed for years of service. base. Forcing or prying on the thermostat will cause damage to the unit. INSTALLER/CONFIGURATION MENU
Read This Before Installing Thermostat 2. Connect wires beneath terminal screws on base using appropriate wiring schematic Step Press Displayed Press up or down Comments
OPERATION (see figs. 2 through 4). Button (Factory Default) key to select
YOUR THERMOSTAT REPLACES 3. Place base over hole in wall and mark mounting hole locations on wall using base as 1 F MS 2 SS1, HP2, HP1 Selects Single stage, Multi-stage,
Description 1F85-277 a template. or Heat Pump (Single stage or
Heat Pump (No Aux. or Emergency Heat) Yes 4. Move base out of the way. Drill mounting holes. 2-stage) System Configuration
Heat Pump (with Aux. or Emergency Heat) Yes 5. Fasten base loosely to wall, as shown in fig. 1, using two mounting screws. Place a 2 F (RECO)off on Auto Recovery select
Standard Heat & Cooling Systems Yes level against bottom of base, adjust until level, and then tighten screws. (Leveling is for 3 F (SPAN)2 1,3 Span(one stage)
Two Stage Heat & One Stage Cool Yes appearance only and will not affect thermostat operation.) If you are using existing 4 F (BLIT)on off BackLight
Standard Heat Only Systems Yes mounting holes, or if holes drilled are too large and do not allow you to tighten base
5 F (SP2)2 1,3 Span(Two Stage)
snugly, use plastic screw anchors to secure subbase.
Millivolt Heat Only Systems– Floor or Wall Furnaces Yes 6 F (TEMP)F C Selects temperature display
6. Push excess wire into wall and plug hole with a fireresistant material (such as
Standard Central Air Conditioning Yes F° or C°
fiberglass insulation) to prevent drafts from affecting thermostat operation.
Gas or Oil Heat Yes 7 F HOUR(12) 24 Selects time format display
Electric Furnace Yes 12hours or 24hours
Hydronic (Hot Water) Zone Heat-2 Wires Yes 8 F COMP(OFF) ON Selects Compressor
Hydronic (Hot Water) Zone Heat–3 Wires No Lockout OFF or ON
This Thermostat will NOT control 110/220Volt systems. 9 F COOL(1) 2 This model must select 1
IMPORTANT 10 F FACT(0) 1,2 This model must select 1 to
2, Read the entire installation section of this Owner’s Manual thoroughly before you back factory Default
begin to install or operate your Thermostat. The configuration menu allows you to set certain thermostat operating characteristics to
REMOVE THE MYLAR LABEL FORM THE LCD DISPLAY WINDOW. your system or personal requirements. Set SYSTEM switch to OFF, then simultaneously
INSTALLATION Mounting press up and down keys to enter configuration menu. The display will show the first item
3, All installation is normally performed at your thermostat. Mounting in the configuration menu.The configuration menu table summarizes the configuration
Hole Hole
ARMCHAIR PROGRAMMING options. An explanation of each option follows.Press F key to change to the next menu
4,You can program your thermostat before installation by inserting the batteries and item. To exit the menu and return to the program operation, press Hold/Run Key. If no
following the instructions starting configuration menu.This can be done while you relax in keys are pressed within fifteen Seconds, the thermostat will revert to normal operation.
your favorite chair and is a very good way to familiarize yourself with all the functions of 1)Single Stage, Multi-stage or Heat Pump System Configuration
your thermostat. Figure 2. Thermostat base This control can be configured for Heat Pump or two stage heat/one stage cool
The following time and temperature settings are pre-programmed into the thermostat: E/ W1
multi-stage operation.The display indicates “MS 2” (default for multi-stage mode) in the
THERMOSTAT
Temperature in F˚ (C˚) O B Y1 G W2 C

L R display. The Multi-stage configuration can be toggled to “SS1”, or “HP1” by pressing the
Program Number Time Heat Cool
SYSTEM up or down key. In Multi-stage configuration, EMER mode is useless.in this model.the
Rever si ng Rever si ng
Val ve Fan Emer gency SYSTEM “HP2” is no use.
1 6:00 am 68˚F(20˚C) 78˚F(26˚C) Val ve MONITOR
Ener gi zed i n Ener gi zed i n Rel ay Heat SWITCH 2) Select Energy Management Recovery OFF or ON
2 8:00 am 60˚F(16˚C) 85˚F(29˚C) Cool Mode Heat , Of f , Aux Rel ay TRANSFORMER
Compr essor Your thermostat is set from the factory to gradually recover the room temperature from
3 4:00 pm 68˚F(20˚C) 78˚F(26˚C) Heat ( Cl ass Cur r ent
Emer gency Cont act or
Mode Rel ay Li mi t ed) an energy saving program to your comfort program. Therefore, the thermostat may turn
4 10:00 pm 60˚F(16˚C) 82˚F(28˚C) Hot
24 VAC 120 VAC your system on several minutes prior to your programmed.
COMPRESSOR PROTECTION Neut r al 3)Fast or Slow Crycle Selection(one stage)
5,The thermostat provides a 4 minutes delay after shutting of the heating or cooling 4)Select Backlight function OFF or on
Figure 3 Typical wiring diagram for single transformer heat pump systems
system before it can be restarted. This feature will prevent damage to your compressor E/ W1 5) Fast or Slow Crycle Selection(two stage)
THERMOSTAT
caused by rapid cycling. Note that this delay also applies to the heating system control. It CUT AND
O B Y1 G W2 C

L R
6)Select F° or C° Readout. when you change this parameter.the programming come
SYSTEM
does not provide a delay when there are power outages.you can select the function on TAPE OFF! Reversing Reversing back to fault. you have to set the programming again.
Valve Fan Emergency SYSTEM Limit or Safety
or off at the configuration. HOT Energized in
Valve
Energized in Relay Heat
MONITOR
SWITCH
Switches
Changes the display readout to Centigrade or Fahrenheit as required
Cool Mode Aux Relay TRANSFORMER
TEMPERATURE RANGE 120 VAC 24 VAC Heat, Off, Compressor
Heat (Class Current Limited) 7) Selects time format display 12hours or 24hours
Emergency Contactor
This thermostat can be programmed between 45˚F and 95˚F (7˚C and 35˚C). However, it NEUTRAL Mode Relay Hot 8)Select Compressor Lockout COMP OFF or ON
will display room temperatures from 30˚F to 99˚F (0˚C and 37˚C). “HI” will be displayed if 24 VAC 120 VAC
Selecting COMP ON will cause the thermostat to wait 4 minutes before turning on the
Neutral
the temperature is higher than 99˚F (37˚C), and “LO” will be displayed if the temperature TWO COMMONS MUST
BE JUMPERED TOGETHER! compressor if the heating and cooling system loses power. It will also wait 5 minutes
is lower than 30˚F (0˚C).This thermostat will automatically cutoff in Heat mode if the minimum between cooling and heating cycles. This is intended to help protect the
Figure 4. Typical wiring diagram for two transformer heat pump systems with NO safety circuits
temperature rises above 95˚F (35˚C), and automatically cutoff in Cool mode if the compressor from short cycling. Some newer compressors already have a time delay
E/ W 1
temperature drops below 45˚F (7˚C). O B Y1 G W2 C

L R
THERM OSTA T

built in and do not require this feature. Your compressor manufacturer can tell you if
SYSTEM Limit or
NOTE: The thermostat will automatically change to the Cool mode if the thermostat Reversing
Valve
Reversing
Fan Emergency SYSTEM
Limit or
Safety
Safety
Switches
HOT
the lockout feature is already present in their system. When the thermostat compressor
Valve M ON ITOR 24VAC 120VAC
measure a temperature over 99˚F(37℃), ”HI” will be displayed on the LCD, and the Energized in
Cool Mode
Energized in
Heat, Off, Compressor
Relay
Aux
Heat
Relay
SW ITCH Switches
24V AC N OTE
NEUTRAL
time delay occurs it will flash the setpoint for about four minutes.
Cooling system will turn On. Similarly, the thermostat will automatically change to the Emergency
Mode
Contactor Heat
Relay
A CCESSORY
RELA Y N .O.
CON TACY
Auxiliary
Heating
The accessory relay scheme
is required when safety 9) This model must select 1
Transformer
Heat mode if the temperature is below 32˚F(0℃). and ”LO” will be displayed on the LCD, Limit or
COMMON (Class
Current Limited)
circuits ezist in both systems
10) his model must select 1 to back factory Default
TW O COM M ON S M U ST Limit or Safety
and the Heating system will turn On. BE J U M PERED TOGETHER! Safety
Switches
Switches HOT
Setting Time And Day
COMMON 24 VAC 120 VAC NEUTRAL
POWER FAILURE Remove the mylar label covering the LCD display window before operating thermostat.
Heat Pump Transformer
7, Whenever the main power is interrupted or fails, the battery power retains and (Class Current Limited)
■ Initial display after power-up. The temperature will
Figure 5. Typical wiring diagram for two transformer heat pump systems with safety circuits in
current time. This thermostat has permanent memory, although you will have to reset update after a few seconds.
BOTH systems
your clock when there are power outages. EXAMPLE: Set the Thermostat to the current time of 9:43 a.m. on
Heat Pump Terminal Outputs
POWER SUPPLY Saturday Refer to Figure at right
Refer to equipment manufacturers' instructions for specific system wiring information.
9,The thermostat shall be powered by 24 VAC and with batteries as backup. ■ During time and day setting mode , the temperature
You can configure the thermostat for use with the following heat pump system types:
BATTERY WARNING and program display will go blank.
HEAT PUMP TYPE 1 1. Single stage compressor system; gas or electric backup. This HOUR
9,Fresh alkaline batteries should provide about one year of service. However, when the ■ Press and hold to rapid advance to the current hour.
thermostat is designed to operate a single-transformer system. If you have a
batteries become drained, “BATT” will alternate on the display with the current time. Tap to advance one hour at a time. Note the AM /PM
two-transformer system, cut and tape off one transformer. If transformer safety circuits
When this message occurs, install 2 new AA batteries, You have approximately 1 minute indicator, as the display will cycle through 24 hours.
are in only one of the systems, remove the transformer of the system with NO safety
to change the batteries and keep thermostat’s clock and program settings. Once the MIN
■ Press and hold to rapid advance to the current
circuits. If required, replace remaining transformer with a 75VA Class II transformer. After
batteries have become too low to ensure proper operation, your system will be turned off, minute.
disconnecting one transformer, the two commons must be jumpered together.
and the display will be cleared except for “BATT” flashing on the LCD display. Tap to advance one minute at a time.
Use the terminal output information below to help you wire the thermostat properly for
CAUTION: Once only the “BATT” only display occurs, the thermostat is shut down, and DAY
■ Tap to advance one day at a time.
your heat pump system. After wiring, see CONFIGURATION section for proper
your system will no longer operate. In this condition, there is no temperature ■ When finished press to return to normal mode.
thermostat configuration.
control of your dwelling. NOTE: The backlight will not function when the HOLD After 15 seconds, the thermostat will return to normal
THERMOSTAT TERMINALS (HEAT PUMP) / RUN
thermostat is in low battery condition. automatically.
SYSTEM Heat Pump 1
NOTE: If you plan to be away from the premises over 30 days, we Auto Programming
recommend that you replace the old batteries with new alkaline batteries prior to L Malfunction
Studies conducted by the Department of Energy estimate that
leaving. C* 24 Volt(Common)
setting your thermostat back 10˚F (6 ) for two 8-hour periods
INSTALLATION R 24 Volt Emergency (hot)
during winter can reduce your fuel bill by as much as much as 33%.
What You Need E/W1 Emergency Mode 1st stage
By setting your thermostat up 5˚F (3℃) for tow 8-hour periods
This thermostat includes two #8 slotted screws and two wall anchors for mounting. To W2 HP 1 and Emergency 2nd stage
during summer you can reduce your fuel bill up to 25%.
install your thermostat, you should have the following tools and materials. Y1 Heat and Cool mode 1st stage (compressor)
Your thermostat is capable of holding up to 4 separate programs
■ Slotted Screwdriver(s) ■ Small Philips screwdriver ■ Hammer G Blower/Fan Energized on call for Heat and Cool for each day ofthe week. You can program all weekdays, Monday to
■ Electric drill and 3/16” bit ■ Two1.5V (AA) size alkaline batteries (included) Set GAS/ELEC switch for Emergency mode Friday, to the same 4 programs as show in the table, or each weekday can have
CAUTION: O Energized in Cool Mode a different set of 4 programs. Similarly weekend programs,
To prevent electrical shock and/or equipment dam- damage, age, disconnect B Energized in Heat Emergency mode Saturday and Sunday, can be the same 4 programs or each
electric power to system at main fuse or circuit breaker box until installation is weekend day can have a different set of 4 programs.
complete. Your thermostat is pre-programmed to meet the ENERGY STAR
Before removing wires from old thermostat's switching subbase, label each wire with the guidelines for energy efficiency. Note that it is easier to modify
terminal designation it was removed from. Reversing Reversing Heat
these programs than to programs than to program the thermostat
Valve Relay
1. Shut off electricity at the main fuse box until installation is complete. Ensure that Valve
manually.
Energized in Energized in Stage 1
electrical power is disconnected. Cool Mode ■ Press once. During Auto Programming, the display
Heat, Off, Compressor Fan Heat
2. Remove Old Thermostat: A standard heat/cool thermostat consists of three basic Emergency will change as shown.
Contactor Relay Relay AUTO
parts: Mode Stage 1 Stage 2 PROG
■ The thermostat will be programmed for all 7 days
a. The cover, which may be either a snap-on or hinge type. of the week as shown below.
b. The base, which is removed by loosening all captive screws. Figure 5. Typical wiring diagram for single transformer multi-stage systems Temperature in ˚F/℃
c. The switching subbase, which is removed by unscrewing the mounting screws that
hold it on the wall or adaptor plate. Program Number Time Heat Standard
CHECK THERMOSTAT OPERATION
3. Remove the front cover of the old thermostat. With wires still attached, remove wall Note: 1 6:00am 68 ˚F (20℃) 78 ˚F (26℃)
plate from the wall. If the old thermostat has a wall mounting plate, remove the To prevent static discharge problems, touch side of thermostat to release static 2 8:00am 60 ˚F (16℃) 85 ˚F (29℃)
thermostat and the wall mounting plate as an assembly. build-up before touching any keys. 3 4:00pm 68 ˚F (20℃) 78 ˚F (26℃)
4. Identify each wire attached to the old thermostat. If at any time during testing your system does not operate properly, contact a
5. Disconnect the wires from the old thermostat one at a time. DO NOT LET WIRES 4 10:00pm 60 ˚F (16℃) 85 ˚F (29℃)
qualified serviceperson.
FALL BACK INTO THE WALL. ■ Refer to Manual Programming entering or changing the programs.
Fan Operation
6. Install new thermostat using the following procedures. PROGRAMMING
If your system does not have a G terminal connection, skip to Heating System System.
WARNING Before programming or changing programs, use this Personal
1. Turn on power to system.
Do not use on circuits exceeding specified voltage. Higher voltage will damage Program Schedule to determine which times and temperature
2. Move FAN switch to ON position. The blower should begin to operate.
control and could cause shock or fire hazard. Do not short out terminals on gas Settings will best satisfy both your comfort and energy saving requirements. Use a
3. Move FAN switch to AUTO position. The blower should stop immediately
valve or primary control to test. Short or incorrect wiring will damage thermostat pencil so you can revise yours records each time you change your temperature settings.
Heating System
Heating
DAY Program1 Program2 Program3 Program4 . Filter usage and Total Energy usage are the same. Also, clearing the filter Monitor
Mon. Time Time Time Time ■ 1st weekday program is displayed. counter will clear ALL Energy Monitor counters as well.
Temp Temp Temp Temp ■ Program indicator(1) appears. Filter Monitor
Tue. Time Time Time Time ■ Mon to Fri indication appears. Your thermostat also keeps a record of the number of hours your filter has been in use.
Temp Temp Temp Temp PROG To maximize your system’s performance and energy efficiency,
Wed. Time Time Time Time ■Continue pressing DAY to view each day. change or clear your filter regularly.
Temp Temp Temp Temp ■ When the total system run time for heat and cool reaches 500
Thu. Time Time Time Time ■Continue pressing PROG to view each period. hours, you need clean or change your system’s filter, “FILT” will
Temp Temp Temp Temp continue to flash until the counter is set back to zero.
Fri. Time Time Time Time If you are armchair programming the thermostat, before you mount the face of the ■ Press to review total filter usage. The display will blink “FILT”
Temp Temp Temp Temp thermostat, turn the system selector to the OFF position. Then show the filter Monitor counter. After 15seconds, the display
Reviewing the Current Temperature Setting will return to normal mode, or you can hit RUN to exit immediately.
Sat. Time Time Time Time
Current time and temperature. The Filter Monitor will display up to 999 hours and 59 minutes of
Temp Temp Temp Temp
usage. In this example, the counter is at 410 Hours, 26 minutes.
Sun. Time Time Time Time
■ Press less than 1 second . ■ To reset the Filter Monitor counter, depress FILTER for 3 seconds.
Temp Temp Temp Temp
■ Set Temperature is shown above current room temperature. The display will blink, and the counter will be reset to zero.
Cooling
NOTE: Clearing the Filter Monitor counter will also clear ALL Energy Monitor counters,
DAY Program1 Program2 Program3 Program4 OPERATION as Filter usage and Total Energy usage are the same. Also, clearing the Energy Monitor
Mon. Time Time Time Time System Selector Switch counters will clear the Filter Monitor counter as well.
Temp Temp Temp Temp system
The System Selector Switch on the front of the thermostat determines Auto Recovery
Tue. Time Time Time Time the Operating mode of the thermostat. You may select COOL ,OFF , Auto Recovery calculates how early to turn your system back on, so that the room
Temp Temp Temp Temp HEAT,AUTO. In order to take full advantage of this thermostat’s temperature is already comfortable by the start of the comfort
Wed. Time Time Time Time feature, we recommend using the AUTO mode. Refer to the Auto Season cool Changeover
off heat auto temperature program period. Auto Recovery work’s in both Heat
Temp Temp Temp Temp information on Auto Season Changeover. and Cool modes.
Thu. Time Time Time Time NOTE: Anytime you install or remove the thermostat form the wallplate, slide the System ■When the thermostat is in Auto Recovery mode, the display will
Temp Temp Temp Temp Selector to the OFF position to prevent the possibility of a rapid system On-Off. alternate “RECO” with time, and the program indicator will flash.
Fri. Time Time Time Time Fan Switch fan ■Auto Recovery can be disabled by sliding the Recovery switch on
Temp Temp Temp Temp The Fan switch should normally be located in the AUTO position. The Fan the circuit board to disable.
Sat. Time Time Time Time will be turned on along with normal operation of your system. In a normal ■Auto Recovery will not operate if Permanent hold or Temporary hold is in operation.
Temp Temp Temp Temp gas or oil furnace, the Fan will be turned on by your furnace after its warm-up on auto ■Auto Recovery can be canceled manually if HOLD is pressed during the recovery
Sun. Time Time Time Time delay. For electric heat, air conditioning, and heat pump operation, the Fan will turn on process.
Temp Temp Temp Temp with the system. To run the Fan on continuously, slide the Fan switch to the ON position. ■Auto Recovery will be canceled and change to next period.
Manual Programming Temporary Manual Override Details of Auto Recovery Operation:
■ Your thermostat can be programmed for weekdays and weekends, or have unique To temporarily change the current set temperature without ■ Auto Recovery can be disabled by sliding the Recovery switch on the circuit board to
programs for all 7 days. Use Weekday /Weekend Programs or 7-day Programming to affecting your program: the DISABLE position.
enter or revise programs to match your Personal Program Schedule. The same steps ■ Today is in operation.
are used when entering programs for the first time, or revising programs entered during ■ Press and hold or for less than 1 second to enter ■ Auto Recovery can be canceled manually if HOLD is pressed during the recovery
Auto Programming. Manual Override mode.. process. If a recovery process is canceled manually then the recovery process will not
■ Familiarize yourself with Manual Programming, so that you can easily modify your start again until the next program period starts (an exception is that if time or program is
programs as your comfort needs change. The example below demonstrates the Manual ■ Press and to change to your desired new temperature. changed then the thermostat will check Auto Recovery conditions immediately).
Programming method. ■ Auto Recovery will be canceled and change to Home Today mode if HOME TODAY is
NOTE: ■ Press to RUN to normal mode or wait 15 seconds for it to return automatically. pressed during the recovery process.
HOLD
1,The program time can be set in 10-minute increments, and remains the same for both / RUN■ The current program number will flash to signify the Temporary Override. Keyboard lock
Heat and Cool programs. At the next program change, the Temporary Override is canceled, and the next The keyboard can be locked to prevent unauthorized changes to the thermostat.
2,The program temperature can be set in increments of 1˚F (1˚C). program temperature becomes the setpoint temperature. To lock or unlock the keyboard, press and hold hold/run Key for 3
3,The Heat setpoint can not be set higher than the Cool set point, and the Cool HOLD To end the Temporary Manual Override: seconds.The keyboard is locked.when LOCK appears on the display.
/ RUN
set point can not be set lower than the Heat set point. ■ Press and wait for HOLD to display on the lcd. ■ All keys are locked, Any time a key is pressed, LOCK will appear
4, If the system selector is in AUTO mode, the current operating mode will be used for ■ Press HOLD key twice. This will return the set temperature to the current on the display for 1 second.
programming. program set temperature. Backlighting
5,After 15 seconds without a key press, the thermostat will return to normal display NOTE: The Auto Season Changeover feature will not operate while the thermostats is Your thermostat has an electroluminescent lamp that backlights the display for easy
mode. in Temporary Manual Override. Refer to the Auto Season Changeover feature for more viewing in the dark.
6, When setting the program time, note the AM/PM indicator. information. When any key is pressed the display is illuminated.
7, With the Auto Recovery feature enabled, you do not need to set your comfort Permanent Override or a Designated Day Override The display will remain illuminated for 8 seconds after the last key is pressed. This
program times early. Auto Recovery will determine how early Recovery will determine To hold your Manual Override for vacation or Until a Designated allows the light to stay on if you need to operate several keys.
how early to turn your system on, so that the room is comfortable at the program time. Day. NOTE: If the thermostat is in Low Battery warning condition, the backlight will not
Weekday/Weekend Programming ■ Press to make the current program temperature the operate. Replace with 2 new AA alkaline batteries to restore the Backlight function.
Weekday Programs HOLD HOLD temperature. HOLD will be displayed on the LCD, Low Battery Warning
/ RUN
Press Display Reads and the Program number will disappear. Your thermostat has a two-stage lower battery warning system. When the batteries are
■ Normal display of time, temperature, ■ Follow the Temporary Manual Override instructions first detected to be weak, the first stage low battery warning is indicated
and day of the week. above to change the by “BATT” flashing on the LCD display. At your earliest convenience,
Permanent Manual Override temperature. you need to replace the batteries with 2 new AA alkaline batteries.
■ You can confirm the held set temperature by pressing for less than 1 second. When the batteries become too weak for normal operation, the
■ Press again. Hold day will be displayed on the lcd and the clock will thermostat enters the second stage low battery warning which shuts
Step 1 ■ Selects days Mon to Fir for same set of 4 HOLD
/ RUN
disappear down the thermostat. In this condition, “BATT” flashes alone on the
PROG ■Press Day key to add override days. Press Hour key display, and the thermostat will turn your system Off. Your system will
DAY programs each day.
HOLD
/ RUN
to reduce override days remain shut-off until the batteries are replaced.
■ Follow the Temporary a Designated Day Override NOTE: The thermostat will still keep the current Set Temperature and
HOUR
instructions above to change the Permanent Manual Filter run time in memory until new batteries are installed. After
DAY
Step 2 ■ Program indicator(1) is displayed. Override confirming that new batteries have been inserted, the thermostat will return to normal
■ 68℉ is displayed. temperature. operation.
PROG
Error Mode
■ Mon to Fir is displayed. If the thermostat is unable to control your system due to an unexpected battery problem,
the thermostat will enter Error Mode. In this condition, the thermostat
Step 3 ■ Press and hold until 6:00 is displayed. flashes “E1”,“E2”,”E3”or”E4”on the LCD display, and shuts off your
■ Note AM/PM system. To correct this problem, replace the batteries with 2 new AA
HOUR
alkaline batteries, even if you have recently replaced them. Move the
To end Override: battery out, and then hold any key to release the rest energy. Then
Under Permanent Override Press hold/return key twice. Under a Designated Day place the battery again. You will need to reprogram your thermostat
Step 4 ■ Press once to change temperature to 69℉. Override press the hold once. The thermostat will return to the current program, and the and confirm normal operation.
HOLD display will be canceled. If Error Mode returns, please call us for further information.
■ Weekday program 1 is complete. NOTE: The Auto Season Changeover feature will not operate while the thermostat is in Warning Mode
■ Press PROG to move to program 2,3, and 4 permanent Manual Override. Refer to the Auto Season Changeover feature for more If the SYSTEM MONITOR SWITCH is close show the system have wrong.the
and follow the same steps. information. thermostat flashs “E5”on the LCD display.
Auto Season Changeover Auto Cut Off
Use to insert or change time and temperature When the System Selector is in AUTO position , the thermostat will automatically Your thermostat will automatically cutoff in Heat mode if the room temperature rises
HOUR MIN change between Heating and Cooling systems, depending on your program. We
of other programs. above 95˚F (35˚C). It will cutoff in Cool mode if the room temperature drops below
recommend keeping your programmed heating and cooling temperature at least 4˚F 40˚F (4˚C).
■ Selects weekend days Sat, Sun for same (2˚C) apart to allow the Auto Season Changeover to occur when the appropriate Note that if your system has malfunctioned and no longer responds to thermostat
PROG
DAY set of 4 programs each weekend day. temperature span has been reached. However, if your heating and cooling programs set controls, the Auto Cut-Off will have no effect.
■ Follow steps 2-4 to enter programs. temperatures are close, there is a built-in program to prevent the thermostat is in TROUBLESHOOTING
Temporary, a Designated Day Override or Permanent Override, as these overrides are Problem Solution
energy saving settings. Auto Season Changeover will still function in Home Today mode, SCRAMBLED OR 1. Remove clear mylar sticker.
Similar to weekday programming. as this is a comfort setting. DOUBLE DISPLAY
For example, you may have the following temperatures programmed at a given time: (numbers over
to insert weekend programs. Heat Set Temp=68˚F, Cool Set Temp=78˚F numbers)
PROG HOUR MIN
If the room temperature rises above 78˚F, then the thermostat will automatically change NO DISPLAY 1. Check battery connections and batteries
Individual Day Programming to cool mode and turn on the air conditioner. 2. Move the battery out, and then hold any key to release
To program for each individual day separately by a different set of programs, first select Likewise, the thermostat will automatically change to heart mode and turn on heat when the rest energy. Then place the battery again.
day by displaying the day of program, then insert the desired times and temperatures. the room temperature falls below 68˚F.
ENTIRE DISPLAY 1. Replace Batteries
Press Display Reads HOME TODAY
DIMS
■ Mon to Fir are selected. Mon to Fir will have This patent pending feature allows you to quickly and Temporarily Override your energy
PROGRAM DOES 1. Check that the time is set properly to “AM” or “PM”
PROG Same programs. saving program setting on days when you are normally away from home with one key
DAY NOT CHANGE AT 2. Check that the thermostat is not in “HOLD” o r “ Home
press.
YOUR DESIRE Today” mode.
■ Press to enter the Home Today override .The highest program temperature for
HOLD SETTING 3. Check for the correct day settings.
/ RUN today will be selected from your programs in Heat mode
AUTO/FAN DOES 1. Move HG/HE selector to opposite position is in the
■ Sat to Sun will have and become the set temperature.(In Cool mode ,Home
NOT TURN ON correct position (“HEAT,”COOL” or “AUTO”)
Same programs. Today will select the lowest program temperature for today
PROG 2. The thermostat may be in the AUTO Mode. Look
DAY to be the set temperature.)
for ”AUTO” on the LCD display. If the Heat and Cool
■ The display will alternate between “HOME” and the
program temperature are close, then the thermostat
current time.
HOME
TODAY ■ When pressed during the day, the thermostat will remain in Home Today mode
requires a larger room temperature change before
■ Mon is selected, program for Mon only.
changing from Heat or Cool.
until the first program of the next day.
PROG 3. There may be as much as 4 minute delay before the
DAY ■If the system is changed between Heat and Cool modes (either manually or by
Heat or Cool system turns On-wait and check.
Auto Season Changeover) during the “Home Today” override period, the setpoint
(Compressor protection delay).
temperature will be automatically update. It will automatically change from the lowest
4,Check your circuit breaks and switches to ensure there
Use to enter programs for Monday. cool program setpoint to the highest heat program setpoint.
is power to the system.
PROG
HOUR MIN ■ Press to exit Home Today mode before the schedule ending time. ”HOME” is
DAY HOLD 5. Replace batteries.
/ RUN no longer displayed on the LCD screen, and the thermostat returns to the current
6. Make sure your furnace blower door is closed properly.
program.
7. If your system only uses 4-wires, be sure the jumper
Similarly ■Tue to Sunday can be selected. ■ You can manually change the setpoint temperature while in Home Today mode.
wire is installed between the RC and RH terminals.
Refer to the Temporary Manual Override instructions .Manually changing the set
PROG 8. Check the position of the Furnace or Heat Pump selector
DAY temperature while in Home Today mode will not affect the Home Today ending
switches: Normal/O/B.
time, However, the set temperature will not change automatically with a manual
or Automatic change between heating and cooling. ERRATIC DISPLAY 1. Move the battery out, and then hold any key to release
the rest energy. Then place the battery again.
Display the day to be programmed and use Energy Monitor
■ The Energy monitor feature measures and stores the IF UNIT CONTINUES 1. Replace unit
PROG
MIN amount of time the heating and air conditioning system TO OPERATE IN THE
DAY HOUR to enter programs.
ENER
operates. Usage can be display for Today (since 12 am), OFF POSITION
NOTE: Another approach to programming is to first program all weekdays Mon Yesterday, This Week (since Monday), Last Week (last THERMOSTAT 1. Replace unit.
through Fir and Sat and Sun as same programs. Then, display and change the Monday through Sunday), and Total (up to 999 Hrs). By PERMANENTLY
programs of only those days which will have different programs. monitoring your energy usage, you see how much the set-back periods are READS “HI”, “LO”,
Reviewing Programs saving, and you can test program adjustment to save even more. To review OR “E1”,“E2”.
energy usage, press to cycle through Today, Yesterday, this Week, Last Week, If you experience any other problems, call us for technical assistance.
You may want to review the programs to see that the settings are compatible with your and Total. Press again to return to normal mode, or wait 15 seconds for the The service number is 1-866-591-9898
lifestyle. display to return to normal mode .You can also return to normal mode at any time
by pressing RUN.
■ Normal display of current time, day of week ■ For example: This LCD display shows Today’s usage to be 10 Hours, 26
temperature, and day of week. minutes.
HOLD ■ Press and hold for 3 seconds to reset the Energy Monitor’s counters.
/ RUN
The display will blink, and counters will be cleared to zero.
NOTE: Clearing the Energy Monitor counter will also clear the Filter Monitor counter , as

You might also like