Instruction Manual - Alfa Laval Rotacheck Rotacheck Basic
Instruction Manual - Alfa Laval Rotacheck Rotacheck Basic
ESE02219-EN8 2022-10
Original manual
Table of contents
The information herein is correct at the time of issue but may be subject to change without prior notice
2. Safety .......................................................................................... 6
2.1. Important information ............................................................................. 6
2.2. Warning signs ..................................................................................... 6
2.3. Safety precautions ................................................................................ 7
3. Introduction .................................................................................. 8
3.1. Introduction ........................................................................................ 8
3.2. Patents and Trademarks ......................................................................... 9
3.3. ATEX Marking ..................................................................................... 10
4. Installation .................................................................................... 11
4.1. General Description ............................................................................... 11
4.2. Specific Conditions for Safe Use in Accordance with ATEX Certification ................... 12
4.3. Mounting position of Hygienic Tank Connection ............................................... 13
4.4. Overview of installation instructions ............................................................. 14
4.5. Product dimensions .............................................................................. 15
4.6. Mounting Rotacheck on tank – step 1 .......................................................... 16
4.7. Connect electrical cable - step 2 ................................................................ 17
4.8. Digital version - PNP .............................................................................. 19
4.9. Calibrate - step 3 - Rotacheck Basic ........................................................... 20
4.10. Calibrate - step 3 – Rotacheck+ (with TEACH) ................................................ 21
4.11. Recycling information ............................................................................. 24
5. Troubleshooting ............................................................................. 25
5.1. No light ............................................................................................. 25
5.2. Red light ........................................................................................... 25
5.3. Red/Yellow flashing light ......................................................................... 25
5.4. Other failure modes ............................................................................... 25
3
1 Declarations of Conformity
EU Declaration of Conformity
Alfa Laval Kolding A/S, Albuen 31, DK-6000 Kolding, Denmark, +45 79 32 22 00
Company name, address and phone number
The person authorised to compile the technical file is the signer of this document.
4
1 Declarations of Conformity
UK Declaration of Conformity
Alfa Laval Kolding A/S, Albuen 31, DK-6000 Kolding, Denmark, +45 79 32 22 00
Company name, address and phone number
DoC Revison_01_102022
5
2 Safety
Unsafe practices and other important information are emphasized in this manual. Warnings are emphasized by means of special
signs. Pay special attention to the instructions below in order to avoid serious personal injury or damage to the top unit.
Always read the manual before using the Rotacheck+ or the Rotacheck Basic.
WARNING
Indicates that special procedures must be followed to avoid serious personal injury.
CAUTION
Indicates that special procedures must be followed to avoid damage to the Rotacheck + or the Rotacheck Basic.
NOTE
Indicates important information to simplify or clarify procedures.
General war
warning:
ning:
Caustic agents:
6
2 Safety
Unsafe practices and other important information are emphasized in this manual. Warnings are emphasized by means of special
signs. Pay special attention to the instructions below in order to avoid serious personal injury or damage to the top unit.
Installation:
Always read the technical data thoroughly. (See chapter 6.1 Technical data page 26).
Always use a power supply that complies with IEC/EN60950-1 or IEC/EN61010-1 standard and limited-energy circuit
requirements.
Operation:
Always read the technical data thoroughly. (See chapter 6.1 Technical data page 26).
Never touch the Rotacheck or the connected equipment when processing hot liquids or when sterilizing.
Always handle lye and acid with great care.
Transportation:
Always remove the protective cap directly before starting assembly to avoid damaging the Rotacheck. The delivered
protective cap has to be stored.
Always place the protective cap on the Rotacheck again immediately after disassembly.
Always make sure that all connections are disconnected before attempting to remove the Rotacheck from the installation.
Always ensure adequate fixing of the Rotacheck during transportation – if specially designed packaging material is
available it must be used.
7
3 Introduction
3.1 Introduction
This manual has been prepared as a guide for installing, operating and maintaining your Alfa Laval Rotacheck Basic and Ro-
tacheck+. Should you require further assistance, our Technical Sales Support department and worldwide net of sales offices are
pleased to help you.
Important Before installing the Alfa Laval Rotacheck Basic and Rotacheck+ and setting it into operation, carefully read the
information: safety precautions (page 7 ) and the specific conditions for safe use in accordance with ATEX Certification
Directive Directive 2014/34/EU (page 12) and take all necessary precautions according to your application and
local regulations.
NOTE
The illustrations and specifications contained in this manual were effective at the date of printing. However, as continuous
improvements are our policy, we reserve the right to alter or modify any unit specification on any product without prior notice or
any obligation
The English version of the instruction manual is the original manual. We make reservations in regard to possible mistranslations in
language versions of the instruction manual. In case of doubt, the English version of the instruction manual applies.
8
3 Introduction
This Instruction Manual is published by Alfa Laval Kolding A/S without any warranty. Improvements and changes to this
Instruction Manual may at any time be made by Alfa Laval Kolding A/S without prior notice. Such changes will, however,
be incorporated in new editions of this Instruction Manual.
The Rotacheck product has patents in the EPO member states and in other countries. The Alfa Laval logotype is a trademark
or a registered trademark of Alfa Laval Corporate AB. Other products or company names mentioned herein may be the
trademarks of their respective owners. Any rights not expressly granted herein are reserved.
9
3 Introduction
If ordered with ATEX certificate
The Alfa Laval Rotacheck+ and Rotacheck Basic is certified as category I components. The certification is carried out by the
certified body IBExU Institut für Sicherheitstechnik GmbH, who has issued the certificate no. IBExU12ATEX1125 X. The marking
on the ATEX certified Alfa Laval Rotacheck+ and Rotacheck Basic is as follows:
Changes to the Alfa Laval Rotacheck+ and Rotacheck Basic are not allowed without approval by the person responsible for the
ATEX certification at Alfa Laval Kolding A/S. If changes are made – or spare parts other than Alfa Laval original spare parts are
used - the EC Type Examination certification (the ATEX Directive) is no longer valid.
Important See also page 12 regarding specific conditions for safe use in accordance with the ATEX certification, Directive
ATEX 2014/34/EU.
information:
10
4 Installation
Concept
Rotacheck is a control and validation unit for tank cleaning machines, in particular Rotary Jet Heads. Communication
is digital PNP to and from a PLC.
Rotacheck consists of a sensor unit with its sensing device located on the inside of a processing tank. The sensor is connected
to a sensor board where the signal is processed and communicated to the PLC.
The Alfa Laval Rotacheck is ideal for validation of the cleaning process inside any hygienic tank cleaned with a rotary Jet head.
It is available in two versions: Rotacheck+ with a built-in validation function and Rotacheck Basic with standard functionality.
The hygienic installation is guaranteed by using the new Alfa Laval full flushable connection, certified by 3A and EHEDG.
Working principle
Rotacheck+
The Alfa Laval Rotacheck+ is based on an Alfa Laval invention which features unique teach-in and monitoring functions. The
teach-in function is used during a reference CIP run. During this first CIP run the Rotacheck+ stores time and pressure data
from the cleaning process.
In terms of cleaning jet intensity on the tank wall (hits) and the time between the hits from the water jet the reference data
represents a unique pattern for the specific process. Status is shown by digital PLC output as well as a visual light indication.
Afterwards, during production, the feedback from the integrated pressure transducer is continuously compared to the stored
acceptance window, and the Rotacheck+ digitally outputs a validated feedback. This digital feedback clearly indicates the
state that the cleaning proces is in.
Rotacheck Basic
The Rotacheck Basic registers when the sensor head is hit by the cleaning jet. Status is shown by digital PLC output as well
as a visual light indication.
11
4 Installation
4.2 Specific Conditions for Safe Use in Accordance with ATEX Certification
Directive 2014/34/EU
arning:
War ning: Surface temperatur e
The surface temperature must not exceed 140°C.
arning:
War ning: Use in explosive atmospher e
The device may be used in an explosive atmosphere, the apparatus of category 1 requires only operate if there
are atmospheric conditions (temperature of -20°C to +60°C, pressure of 0.8 bar to 1.1 bar).
12
4 Installation
Examples of difdiffer
ferent
fer ent of
offset:
fset:
Tank cleaning machine type Offset (E)
Toftejorg TJ20G 75 mm
Toftejorg TJ40G 91 mm
Toftejorg TZ-74 78 mm
Toftejorg TZ-79 98 mm
Toftejorg MultiJet 65 with 4 nozzles 98 mm
Toftejorg TZ-89 50-90 mm (depending on size of mounting connection)
Toftejorg TZ-750 115 mm
Toftejorg MultiJet 65 with 2 nozzles 115 mm
Deviations from the above given positions may work, but will influence the signal quality.
It is not recommended to go closer to the centerline, as there is a risk of having no signal. If the Rotacheck Sensor is placed
further away from the centerline, the number of times it is directly hit by a jet is reduced.
13
4 Installation
Step 1
Mount Rotacheck on tank
Step 2
Connect electrical cable
Step 3
Calibrate.
14
4 Installation
Weight: 0.6 kg
15
4 Installation
Step 1
Remove protective cap from sensor.
Check that o-ring on sensor head is in place.
Step 2
Mount Rotacheck on flange.
Step 3
Tighten clamp ring.
16
4 Installation
WARNING
hazardous
Special considerations for use in hazar dous ar
areas
eas
For the installation, maintenance and cleaning of the device, you must absolutely observe the relevant regulations and stipulations
on explosion protection (EN 60079-14 and EN60079-17) as well as the occupational safety provisions.
The device is designed acc. to standards:
EN60079-0:2009, EN60079-11:2007, EN60079-15:2010, EN60079-26:2007 and EN60079-31:2009.
Step 1
Remove the prism/top cover by turning the prism/top cover
counter-clockwise. Counterhold on the base part. When the mark
on the prism (J) is aligned with the open padlock symbol (K), the
prism/top cover can be lifted off.
Step 2
Install the cable in the cable gland (M) and tighten nut.
NOTE!
Cable connection:
Cable gland: M16 (ø5-ø8)
Max. wire diameter: 1.0 mm2 (AWG 18)
If the cable gland comes loose from the control head during installation, it must be secured with a tightening torque of 4 Nm.
17
4 Installation
Step 3
Connect wires to board according to illustration number 4512-0018 on page 19.
Step 1
Connect the electrical M12 plug to the connector on Rotacheck.
Tighten the knurled nut.
See wiring diagram on page 19.
18
4 Installation
Supply voltage
Supply voltage 24 Vdc +÷ 10%
Max. power consumption of the sensor unit
Power consumption max 70 mA
Output signals fr
from
om the sensor unit to the connected digital interface (PLC)
Outputs (Hit/Rotation OK, Alarm, Idle) Logic PNP
Max. current per output 50 mA
board
Sensor boar d
Designation No.
Supply 24 VDC 1
Supply 0 VDC 2
Feedback Idle 3
Feedback Hit/Rotation OK 4
Alarm 5
Activate teach (Rotacheck+ only) 6
M12 connector
Designation No.
Supply 24 VDC 1
Supply 0 VDC 3
Feedback Idle 5
Feedback Hit/Rotation OK 2
Alarm 6
Activate teach (Rotacheck+ only) 4
19
4 Installation
Step 1
The Rotacheck Basic must be fully installed:
- Mechanically
- Electrically
The unit is ready to use when the green LED lights steadily.
Optional re-calibration
Push the blue button (N) on the sensor unit until you see a yellow
flash.
The Rotacheck Basic will automatically re-calibrate.
Step 2
(If unit has been opened)
Put the prism/top cover back on the base part by pushing it down
when the mark on the prism (J) and the open padlock (K) are
aligned. Then turn it clockwise towards the closed padlock (L) to
secure. Counterhold on the base part.
20
4 Installation
Step 1
The Rotacheck Basic must be fully installed:
- Mechanically
- Electrically
Step 2
Calibration - TEACH
Method 1: Auto-TEACH
- Ensure that cleaning machine is commissioned, and its performance is approved by end-user
- Install Rotacheck+, ensure “green LED is flashing (mostly on)”
- Open top cap of Rotacheck+
- Start cleaning machine
Enable TEACH by pressing the blue button on sensor board for 1 sec and release after 1 yellow LED flash is seen.
NOTE
Longer TEACH intervals may be necessary in some cases, to secure proper calibration data. For example in case of
unfavourable placement of Rotacheck, see guidelines for installation, page 13. In these cases manual calibration according to
method 2 is recommended.
For proper calibration TEACH must run for sufficiently long time. This is application dependant and must be determined on-site.
- A red LED is flashing to indicate TEACH ongoing
- Let the cleaning process run for at least 16 minutes (the Rotacheck+ will teach-in cleaning pattern during this time)
- Every sensor hit during TEACH is indicated by a yellow LED flash
- Let the cleaning process run for sufficient time (the Rotacheck+ will teach-in cleaning pattern during this time)
- De-activate TEACH input on sensor board, terminal 6 after the desired time is elapsed.
- Rotacheck+ will light up green when teach-in is finished
21
4 Installation
Step 3
Operation after TEACH
If TEACH is completed, Rotacheck+ will enter Idle mode.
- When cleaning is ongoing, Rotacheck+ compares cleaning parameters to the reference cycle.
- If parameters are within the calibrated values, a “Rotation OK” feedback is initiated
- If parameters are outside the calibrated values, the alarm function is entered.
NOTE
If it – due to special circumstances - proves too difficult to make a proper calibration, Rotacheck+ can be reset to “1st power up
mode”.
This is done by pressing the Push Button for 10 seconds, and release when 3 yellow LED flashes are seen.
After Rotacheck+ is reset it will function similar to a Rotacheck Basic, but with a flashing green LED (mostly on), when idle.
22
4 Installation
TEACH
TEACH ongoing Red flashing No feedback
Sensor hit during TEACH Yellow - 1 sec. No feedback
Termination of TEACH*** Yellow - 1 flash No feedback
23
4 Installation
Unpacking
- Packing material consists of plastics and cardboard boxes
- Cardboard boxes can be re-used, recycled or used for energy recovery
- Plastics should be recycled or burnt at a licensed waste incineration plant
Maintenance
In principle, this device is maintenance-free. If desired, the housing of the device can be cleaned using a damp cloth and
non-aggressive cleaning solutions, in switched-off state.
Depending on the measuring medium, however, the diaphragm may be polluted or coated with deposit. Is there a pollution
tendency of the medium, the user has to determine the appropriate cleaning interval. After placing the device out of service
correctly, the diaphragm can usually be cleaned carefully with a non-aggressive cleaning solution and a soft brush or sponge.
If the diaphragm is calcified, it is recommended to send the device to Alfa Laval Tank Equipment for decalcification. Please
note the chapter “Service/Repair” page 33.
! A false cleaning of the device can cause an irreparable damage on the diaphragm. Therefore never use pointed objects
or pressured air for cleaning the diaphragm.
Scrapping
- At end of life, the equipment must be recycled according to the relevant, local regulations. Besides the equipment itself, any
hazardous residues from the process liquid must be taken into consideration and dealt with in a proper manner. When in
doubt, or in the absence of local regulations, please contact your local Alfa Laval sales company.
Disposal
- The device has to be disposed of according to the European Directives 2002/96/EG and 2003/108/EG (on waste
electrical and electronic equipment). It is prohibited to place electrical and electronic equipment in domestic refuse!
Depending on the used medium, deposit on the device may cause danger for the user and the environment. Comply with
adequate precautions for purification and dispose of it properly.
24
5 Troubleshooting
5.1 No light
- Check that the unit is connected to electrical power.
- Press the blue button on the sensor board shortly to restart unit.
- Power down the unit and reconnect power again after 5 seconds.
- If problem persists, please contact Alfa Laval.
Red/Yellow flashing light indicates sensor malfunction or lost internal connection between sensor board and sensor.
- Press the blue button on the sensor board shortly to restart unit, or power down the unit and reconnect power again
after 5 seconds.
- If problem persists, please contact Alfa Laval.
25
6 Technical Data
Electrical data
hazardous
Special conditions for use in hazar dous ar
areas
eas
Rotacheck is approved in accordance with ATEX directive 94/9/EC, for use in Zone 0/20 in the product wetted area and
Zone 2/22 in the non-product wetted area.
Ex identification:
II 1/3G Ex ia/nA IIB T4/T3 Ga/Gc
II 1/3D Ex ia/tc IIIB T130 °C Da/Dc
Special conditions for safe use:
T4 for media temperatures <85°C
T3 for media temperatures <140°C
Fall height 40 cm is utilized in impact test of Rotacheck with M12 cable connector plug.
Permissible temperatures for environment for use in Zone 0 (Patm 0,8 to 1,1 bar): -10°C to 60°C
WARNING!: Rotacheck must not be separated when energized
Physical data
Process
Pr ocess connection
26
.
27
7 Parts Lists and Drawing
Parts Drawing
28
7 Parts Lists and Drawing
Parts list
Pos. Qty Denomination
1 1 Top cover/prism and o-ring
assembly
1.1 - Top cover/prism assembly
1.2 - O-ring for top cover
2 1 Sensor unit with o-ring
2.1 - Sensor unit
2.2 �
- O-ring
� - O-ring (Q-doc version)
� - O-ring set (10 pcs.) EPDM
29
7 Parts Lists and Drawing
30
7 Parts Lists and Drawing
Parts list
Pos. Qty Denomination
3 1 Clamp ring
4 1 M12 connector
5 � 1 Tank flange, Hygienic tank
connection HTC
� 1 Tank flange, Hygienic tank
connection HTC (Q-doc version)
6 � 1 Blind cap with o-ring
� 1 Blind cap with o-ring (Q-doc
version)
31
8 Short functional guide
32
9 General Information
Upon every return of a product, no matter if for modifications or repair, it is necessary to contact your local Alfa Laval office to
guarantee a quick execution of your request.
You will receive instructions regarding the return procedure from your local Alfa Laval office. Be sure to follow the instructions
closely.
9.2 Warranty
The warranty conditions are subject to the legal warranty period of 12 months from the date of delivery. In case of improper use,
modifications of or damages to the device, we do not accept warranty claims. Damaged devices will also not be accepted.
Furthermore, defects due to normal wear are not subject to warranty services.
Contact details for all countries are continually updated on our websites
33
How to contact Alfa Laval
Contact details for all countries are
continually updated on our website.
Please visit www.alfalaval.com to access the information directly.