0% found this document useful (0 votes)
81 views34 pages

Instruction Manual - Alfa Laval Rotacheck Rotacheck Basic

This document provides an instruction manual for Alfa Laval Rotacheck+ and Rotacheck Basic machines. It covers declarations of

Uploaded by

Eber TM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
81 views34 pages

Instruction Manual - Alfa Laval Rotacheck Rotacheck Basic

This document provides an instruction manual for Alfa Laval Rotacheck+ and Rotacheck Basic machines. It covers declarations of

Uploaded by

Eber TM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34

Instruction Manual

Alfa Laval Rotacheck+ & Rotacheck Basic

Covering: Standard Machines


Machines delivered with ATEX Certification in accordance with Directive 2014/34/EU
TE91A664
First published: 2012-09

ESE02219-EN8 2022-10
Original manual
Table of contents

The information herein is correct at the time of issue but may be subject to change without prior notice

1. Declarations of Conformity ................................................................. 4

2. Safety .......................................................................................... 6
2.1. Important information ............................................................................. 6
2.2. Warning signs ..................................................................................... 6
2.3. Safety precautions ................................................................................ 7

3. Introduction .................................................................................. 8
3.1. Introduction ........................................................................................ 8
3.2. Patents and Trademarks ......................................................................... 9
3.3. ATEX Marking ..................................................................................... 10

4. Installation .................................................................................... 11
4.1. General Description ............................................................................... 11
4.2. Specific Conditions for Safe Use in Accordance with ATEX Certification ................... 12
4.3. Mounting position of Hygienic Tank Connection ............................................... 13
4.4. Overview of installation instructions ............................................................. 14
4.5. Product dimensions .............................................................................. 15
4.6. Mounting Rotacheck on tank – step 1 .......................................................... 16
4.7. Connect electrical cable - step 2 ................................................................ 17
4.8. Digital version - PNP .............................................................................. 19
4.9. Calibrate - step 3 - Rotacheck Basic ........................................................... 20
4.10. Calibrate - step 3 – Rotacheck+ (with TEACH) ................................................ 21
4.11. Recycling information ............................................................................. 24

5. Troubleshooting ............................................................................. 25
5.1. No light ............................................................................................. 25
5.2. Red light ........................................................................................... 25
5.3. Red/Yellow flashing light ......................................................................... 25
5.4. Other failure modes ............................................................................... 25

6. Technical Data ............................................................................... 26


6.1. Technical data ..................................................................................... 26

7. Parts Lists and Drawing ..................................................................... 28


7.1. Parts drawing and list ............................................................................ 28
7.2. Optional parts ..................................................................................... 30

8. Short functional guide ....................................................................... 32


8.1. LED signals ....................................................................................... 32
8.2. Push button (PB) operation ..................................................................... 32

9. General Information ......................................................................... 33


9.1. Service & Repair .................................................................................. 33
9.2. Warranty ........................................................................................... 33
9.3. How to contact Alfa Laval Kolding A/S ......................................................... 33

3
1 Declarations of Conformity

EU Declaration of Conformity

The Designated Company

Alfa Laval Kolding A/S, Albuen 31, DK-6000 Kolding, Denmark, +45 79 32 22 00
Company name, address and phone number

Hereby declare that

Rotacheck+ & Rotacheck Basic


Designation

Unit for rotation validation of tank cleaning machines


Type

is in conformity with the following directives with amendments:

- EMC Directive 2014/30/EU


- RoHS Directive 2011/65/EU and amendments
- ATEX Directive 2014/34/EU
EN IEC 60079-0:2018, EN IEC 60079-7:2015/A1:2018, EN 60079-11:2012, EN 60079-26:2015 and EN 60079-31:2014

EC Type Examination Certificate no. IBExU12ATEX1125 X

Marking: II 1/3G Ex ia/nA IIB T4/T3 Ga/Gc


Marking: II 1/3D Ex ia/tc IIIB T40ºC Da/Dc
IBExU Institut für Sicherheitstechnik GmbH, Certification Body number 0637. Fuchsmühlenweg 7, 09599 Freiberg, Germany

The person authorised to compile the technical file is the signer of this document.

Global Product Quality Manager Lars Kruse Andersen


Title Name

Kolding, Denmark 2022–10–01


Place Date (YYYY-MM-DD) Signature

This Declaration of Conformity replaces Declaration of Conformity dated 2022-08-18

4
1 Declarations of Conformity

UK Declaration of Conformity

The Designated Company

Alfa Laval Kolding A/S, Albuen 31, DK-6000 Kolding, Denmark, +45 79 32 22 00
Company name, address and phone number

Hereby declare that

Rotacheck+ & Rotacheck Basic


Designation

Unit for rotation validation of tank cleaning machines


Type

is in conformity with the following directives with amendments:

- The Electromagnetic Compatibility Regulations 2016


- The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012
- The Equipment and Protective Systems Intended for use in Potentially Explosive Atmospheres Regulations 2016
EN IEC 60079-0:2018, EN IEC 60079-7:2015/A1:2018, EN 60079-11:2012, EN 60079-26:2015 and EN 60079-31:2014

EC Type Examination Certificate no. IBExU12ATEX1125 X

Marking: II 1/3G Ex ia/nA IIB T4/T3 Ga/Gc


Marking: II 1/3D Ex ia/tc IIIB T40ºC Da/Dc
IBExU Institut für Sicherheitstechnik GmbH, Certification Body number 0637. Fuchsmühlenweg 7, 09599 Freiberg, Germany

Signed on behalf of: Alfa Laval Kolding A/S

Global Product Quality Manager Lars Kruse Andersen


Title Name

Kolding, Denmark 2022–10–01


Place Date (YYYY-MM-DD) Signature

DoC Revison_01_102022

5
2 Safety
Unsafe practices and other important information are emphasized in this manual. Warnings are emphasized by means of special
signs. Pay special attention to the instructions below in order to avoid serious personal injury or damage to the top unit.

2.1 Important information

Always read the manual before using the Rotacheck+ or the Rotacheck Basic.

WARNING
Indicates that special procedures must be followed to avoid serious personal injury.

CAUTION
Indicates that special procedures must be followed to avoid damage to the Rotacheck + or the Rotacheck Basic.

NOTE
Indicates important information to simplify or clarify procedures.

2.2 Warning signs

General war
warning:
ning:

Danger ous electrical voltage:

Caustic agents:

6
2 Safety
Unsafe practices and other important information are emphasized in this manual. Warnings are emphasized by means of special
signs. Pay special attention to the instructions below in order to avoid serious personal injury or damage to the top unit.

2.3 Safety precautions

Installation:
Always read the technical data thoroughly. (See chapter 6.1 Technical data page 26).
Always use a power supply that complies with IEC/EN60950-1 or IEC/EN61010-1 standard and limited-energy circuit
requirements.

Operation:

Always read the technical data thoroughly. (See chapter 6.1 Technical data page 26).
Never touch the Rotacheck or the connected equipment when processing hot liquids or when sterilizing.
Always handle lye and acid with great care.

Transportation:

Always remove the protective cap directly before starting assembly to avoid damaging the Rotacheck. The delivered
protective cap has to be stored.
Always place the protective cap on the Rotacheck again immediately after disassembly.
Always make sure that all connections are disconnected before attempting to remove the Rotacheck from the installation.
Always ensure adequate fixing of the Rotacheck during transportation – if specially designed packaging material is
available it must be used.

7
3 Introduction

3.1 Introduction

This manual has been prepared as a guide for installing, operating and maintaining your Alfa Laval Rotacheck Basic and Ro-
tacheck+. Should you require further assistance, our Technical Sales Support department and worldwide net of sales offices are
pleased to help you.

Important Before installing the Alfa Laval Rotacheck Basic and Rotacheck+ and setting it into operation, carefully read the
information: safety precautions (page 7 ) and the specific conditions for safe use in accordance with ATEX Certification
Directive Directive 2014/34/EU (page 12) and take all necessary precautions according to your application and
local regulations.

NOTE
The illustrations and specifications contained in this manual were effective at the date of printing. However, as continuous
improvements are our policy, we reserve the right to alter or modify any unit specification on any product without prior notice or
any obligation

The English version of the instruction manual is the original manual. We make reservations in regard to possible mistranslations in
language versions of the instruction manual. In case of doubt, the English version of the instruction manual applies.

8
3 Introduction

3.2 Patents and Trademarks

This Instruction Manual is published by Alfa Laval Kolding A/S without any warranty. Improvements and changes to this
Instruction Manual may at any time be made by Alfa Laval Kolding A/S without prior notice. Such changes will, however,
be incorporated in new editions of this Instruction Manual.

Alfa Laval, Kolding A/S. All rights reserved.

The Rotacheck product has patents in the EPO member states and in other countries. The Alfa Laval logotype is a trademark
or a registered trademark of Alfa Laval Corporate AB. Other products or company names mentioned herein may be the
trademarks of their respective owners. Any rights not expressly granted herein are reserved.

9
3 Introduction
If ordered with ATEX certificate

3.3 ATEX Marking

The Alfa Laval Rotacheck+ and Rotacheck Basic is certified as category I components. The certification is carried out by the
certified body IBExU Institut für Sicherheitstechnik GmbH, who has issued the certificate no. IBExU12ATEX1125 X. The marking
on the ATEX certified Alfa Laval Rotacheck+ and Rotacheck Basic is as follows:

Changes to the Alfa Laval Rotacheck+ and Rotacheck Basic are not allowed without approval by the person responsible for the
ATEX certification at Alfa Laval Kolding A/S. If changes are made – or spare parts other than Alfa Laval original spare parts are
used - the EC Type Examination certification (the ATEX Directive) is no longer valid.

Important See also page 12 regarding specific conditions for safe use in accordance with the ATEX certification, Directive
ATEX 2014/34/EU.
information:

10
4 Installation

4.1 General Description

Concept

Rotacheck is a control and validation unit for tank cleaning machines, in particular Rotary Jet Heads. Communication
is digital PNP to and from a PLC.

Rotacheck consists of a sensor unit with its sensing device located on the inside of a processing tank. The sensor is connected
to a sensor board where the signal is processed and communicated to the PLC.

The Alfa Laval Rotacheck is ideal for validation of the cleaning process inside any hygienic tank cleaned with a rotary Jet head.
It is available in two versions: Rotacheck+ with a built-in validation function and Rotacheck Basic with standard functionality.

The hygienic installation is guaranteed by using the new Alfa Laval full flushable connection, certified by 3A and EHEDG.

Rotacheck is designed for use in Ex areas.

Working principle

Rotacheck+
The Alfa Laval Rotacheck+ is based on an Alfa Laval invention which features unique teach-in and monitoring functions. The
teach-in function is used during a reference CIP run. During this first CIP run the Rotacheck+ stores time and pressure data
from the cleaning process.

In terms of cleaning jet intensity on the tank wall (hits) and the time between the hits from the water jet the reference data
represents a unique pattern for the specific process. Status is shown by digital PLC output as well as a visual light indication.

Afterwards, during production, the feedback from the integrated pressure transducer is continuously compared to the stored
acceptance window, and the Rotacheck+ digitally outputs a validated feedback. This digital feedback clearly indicates the
state that the cleaning proces is in.

The system feedback has 3 different outputs.


Rotation OK output: on when rotation is within acceptance window
Alarm output: on when cleaning is out of teach-in acceptance window
IDLE output: on when cleaning is not performed

Rotacheck Basic
The Rotacheck Basic registers when the sensor head is hit by the cleaning jet. Status is shown by digital PLC output as well
as a visual light indication.

The system feedback has 3 different outputs.


Hit output: on when sensor head is hit by cleaning jet
Alarm output: on in case of unit failure or constant hit (cleaning device error)
IDLE output: on when cleaning is not performed

11
4 Installation

4.2 Specific Conditions for Safe Use in Accordance with ATEX Certification

Directive 2014/34/EU

arning:
War ning: Surface temperatur e
The surface temperature must not exceed 140°C.

arning:
War ning: Use in explosive atmospher e
The device may be used in an explosive atmosphere, the apparatus of category 1 requires only operate if there
are atmospheric conditions (temperature of -20°C to +60°C, pressure of 0.8 bar to 1.1 bar).

12
4 Installation

4.3 Mounting position of Hygienic Tank Connection

In order to ensure optimum signal quality, the Rotacheck


should be placed with an offset to the downpipe as close as
possible to the offset of the jets nozzles of the tank cleaning
machine in use.

Examples of difdiffer
ferent
fer ent of
offset:
fset:
Tank cleaning machine type Offset (E)
Toftejorg TJ20G 75 mm
Toftejorg TJ40G 91 mm
Toftejorg TZ-74 78 mm
Toftejorg TZ-79 98 mm
Toftejorg MultiJet 65 with 4 nozzles 98 mm
Toftejorg TZ-89 50-90 mm (depending on size of mounting connection)
Toftejorg TZ-750 115 mm
Toftejorg MultiJet 65 with 2 nozzles 115 mm

Deviations from the above given positions may work, but will influence the signal quality.

It is not recommended to go closer to the centerline, as there is a risk of having no signal. If the Rotacheck Sensor is placed
further away from the centerline, the number of times it is directly hit by a jet is reduced.

13
4 Installation

4.4 Overview of installation instructions

Step 1
Mount Rotacheck on tank

Step 2
Connect electrical cable

Step 3
Calibrate.

14
4 Installation

4.5 Product dimensions

Weight: 0.6 kg

15
4 Installation

4.6 Mounting Rotacheck on tank – step 1

Step 1
Remove protective cap from sensor.
Check that o-ring on sensor head is in place.

Step 2
Mount Rotacheck on flange.

Step 3
Tighten clamp ring.

16
4 Installation

4.7 Connect electrical cable - step 2

WARNING
hazardous
Special considerations for use in hazar dous ar
areas
eas
For the installation, maintenance and cleaning of the device, you must absolutely observe the relevant regulations and stipulations
on explosion protection (EN 60079-14 and EN60079-17) as well as the occupational safety provisions.
The device is designed acc. to standards:
EN60079-0:2009, EN60079-11:2007, EN60079-15:2010, EN60079-26:2007 and EN60079-31:2009.

Cable gland version

Step 1
Remove the prism/top cover by turning the prism/top cover
counter-clockwise. Counterhold on the base part. When the mark
on the prism (J) is aligned with the open padlock symbol (K), the
prism/top cover can be lifted off.

Step 2
Install the cable in the cable gland (M) and tighten nut.
NOTE!
Cable connection:
Cable gland: M16 (ø5-ø8)
Max. wire diameter: 1.0 mm2 (AWG 18)

If the cable gland comes loose from the control head during installation, it must be secured with a tightening torque of 4 Nm.

17
4 Installation

Step 3
Connect wires to board according to illustration number 4512-0018 on page 19.

M12 plug version

Step 1
Connect the electrical M12 plug to the connector on Rotacheck.
Tighten the knurled nut.
See wiring diagram on page 19.

18
4 Installation

4.8 Digital version - PNP

Supply voltage
Supply voltage 24 Vdc +÷ 10%
Max. power consumption of the sensor unit
Power consumption max 70 mA
Output signals fr
from
om the sensor unit to the connected digital interface (PLC)
Outputs (Hit/Rotation OK, Alarm, Idle) Logic PNP
Max. current per output 50 mA

Electrical connection on PCB

board
Sensor boar d
Designation No.
Supply 24 VDC 1
Supply 0 VDC 2
Feedback Idle 3
Feedback Hit/Rotation OK 4
Alarm 5
Activate teach (Rotacheck+ only) 6

M12 connector
Designation No.
Supply 24 VDC 1
Supply 0 VDC 3
Feedback Idle 5
Feedback Hit/Rotation OK 2
Alarm 6
Activate teach (Rotacheck+ only) 4

View from mounting side

Alfa Laval part number 9611995257 (not part of delivery)

19
4 Installation

4.9 Calibrate - step 3 - Rotacheck Basic

Step 1
The Rotacheck Basic must be fully installed:
- Mechanically
- Electrically

The unit will flash green on power up and perform an internal


calibration after 5 sec.

The unit is ready to use when the green LED lights steadily.

Optional re-calibration
Push the blue button (N) on the sensor unit until you see a yellow
flash.
The Rotacheck Basic will automatically re-calibrate.

Step 2
(If unit has been opened)
Put the prism/top cover back on the base part by pushing it down
when the mark on the prism (J) and the open padlock (K) are
aligned. Then turn it clockwise towards the closed padlock (L) to
secure. Counterhold on the base part.

Operating LED and PLC feedback

Rotacheck Basic status LED feedback PLC feedback


Calibration Green, flashing No feedback
Idle Green, steady On
Hit Yellow, 1 sec On, 1 sec
Alarm* Red, steady On
* Unit failure or constant hit (cleaning device error)

20
4 Installation

4.10 Calibrate - step 3 – Rotacheck+ (with TEACH)

Step 1
The Rotacheck Basic must be fully installed:
- Mechanically
- Electrically

Usage before TEACH has been performed:


Rotacheck+ where TEACH has not yet been performed, will show
similar functionality as Rotacheck Basic, except that Idle mode is
indicated by a flashing (mostly on) green LED.

Step 2

Calibration - TEACH
Method 1: Auto-TEACH
- Ensure that cleaning machine is commissioned, and its performance is approved by end-user
- Install Rotacheck+, ensure “green LED is flashing (mostly on)”
- Open top cap of Rotacheck+
- Start cleaning machine
Enable TEACH by pressing the blue button on sensor board for 1 sec and release after 1 yellow LED flash is seen.

Duration of TEACH is preset to 16 minutes.


- A red LED is flashing to indicate TEACH ongoing
- Let the cleaning process run for at least 16 minutes (the Rotacheck+ will teach-in cleaning pattern during this time)
- Every sensor hit during TEACH is indicated by a yellow LED flash
- Rotacheck+ will light up green when teach-in is finished
The TEACH sequence is terminated if no sensor hits are registered within a 4 min. interval.

NOTE
Longer TEACH intervals may be necessary in some cases, to secure proper calibration data. For example in case of
unfavourable placement of Rotacheck, see guidelines for installation, page 13. In these cases manual calibration according to
method 2 is recommended.

Method 2: Manual TEACH


- Ensure that cleaning machine is commissioned, and its performance is approved by end-user
- Install Rotacheck+, ensure “green LED is flashing (mostly on)”
- Start cleaning machine
Enable TEACH by activating input on sensor board, connector number 6, see table page 19.

TEACH will be performed as long as the input is activated, up to maximum 60 minutes.

For proper calibration TEACH must run for sufficiently long time. This is application dependant and must be determined on-site.
- A red LED is flashing to indicate TEACH ongoing
- Let the cleaning process run for at least 16 minutes (the Rotacheck+ will teach-in cleaning pattern during this time)
- Every sensor hit during TEACH is indicated by a yellow LED flash
- Let the cleaning process run for sufficient time (the Rotacheck+ will teach-in cleaning pattern during this time)
- De-activate TEACH input on sensor board, terminal 6 after the desired time is elapsed.
- Rotacheck+ will light up green when teach-in is finished

21
4 Installation

Step 3
Operation after TEACH
If TEACH is completed, Rotacheck+ will enter Idle mode.
- When cleaning is ongoing, Rotacheck+ compares cleaning parameters to the reference cycle.
- If parameters are within the calibrated values, a “Rotation OK” feedback is initiated
- If parameters are outside the calibrated values, the alarm function is entered.

NOTE
If it – due to special circumstances - proves too difficult to make a proper calibration, Rotacheck+ can be reset to “1st power up
mode”.
This is done by pressing the Push Button for 10 seconds, and release when 3 yellow LED flashes are seen.
After Rotacheck+ is reset it will function similar to a Rotacheck Basic, but with a flashing green LED (mostly on), when idle.

22
4 Installation

Operating LED and PLC feedback

Unit status LED feedback PLC feedback


OPERATION
OPERA TION
Self calibration on 1st power up (0-5 sec.) Green flashing(50/50 on /off) No feedback
Idle (before TEACH) Green flashing (mostly on) Idle
Idle (after TEACH) Green
Sensor hit (before TEACH) Yellow - 1 sec. Hit/Rotation OK - 1 sec
Alarm* Red Alarm
Alarm, sensor not connected Red/Yellow flashing Alarm
Rotation OK (after TEACH) Yellow flashing (slowly) Hit/Rotation OK
Sensor hit (after TEACH) Yellow – 3 flashes Hit/Rotation OK
End of cleaning sequence** Red - 3 sec. Alarm - 1 sec.

TEACH
TEACH ongoing Red flashing No feedback
Sensor hit during TEACH Yellow - 1 sec. No feedback
Termination of TEACH*** Yellow - 1 flash No feedback

*Constant sensor hit or max. tank pressure is exceeded


**If no sensor hits are recorded during the maximum interval set by TEACH function
***Finalization of TEACH after preset time or if TEACH input is de-activated. Max. duration of TEACH is 20 min. where after
Rotacheck+ automatically sets up reference data

Back to 1st power up mode (factory settings)


Rotacheck can be brought back to 1st power up mode by pressing the blue pushbutton for 10 seconds and release when 3
yellow LED flashes are seen.

Feedback test mode – Rotacheck+ (with TEACH) only


Feedback test mode is a function that can be enabled after installation to validate proper function of the external wiring. When
the mode is entered, Rotacheck+ automatically switches PLC and LED outputs in 5 seconds intervals.

Enter Feedback test mode:


Press the blue button on the sensor board and release after 5 seconds when 2 Yellow LED flashes are seen.
This mode can only be entered from 1st power-up or Idle modes.

Exit Feedback test mode:


Feedback test mode automatically terminates after 3 minutes.
The function can also be terminated by shortly pressing the blue button on the sensor board.
Exit is indicated by 2 yellow flashes.
Unit status is returned to previous state before feedback test mode was enabled.

Feedback test mode LED and PLC feedback

Unit status LED feedback PLC feedback


FEEDBACK TEST MODE
Step 1 (0-5 sec.) Red Alarm
Step 2 (5-10 sec) Yellow Hit/Rotation OK
Step 3 (10-15 sec.) Green Idle
Loop until aborted or timeout after 3 mins. Yellow – 2 flashes on termination

23
4 Installation

4.11 Recycling information

Unpacking
- Packing material consists of plastics and cardboard boxes
- Cardboard boxes can be re-used, recycled or used for energy recovery
- Plastics should be recycled or burnt at a licensed waste incineration plant

Maintenance
In principle, this device is maintenance-free. If desired, the housing of the device can be cleaned using a damp cloth and
non-aggressive cleaning solutions, in switched-off state.

Depending on the measuring medium, however, the diaphragm may be polluted or coated with deposit. Is there a pollution
tendency of the medium, the user has to determine the appropriate cleaning interval. After placing the device out of service
correctly, the diaphragm can usually be cleaned carefully with a non-aggressive cleaning solution and a soft brush or sponge.
If the diaphragm is calcified, it is recommended to send the device to Alfa Laval Tank Equipment for decalcification. Please
note the chapter “Service/Repair” page 33.
! A false cleaning of the device can cause an irreparable damage on the diaphragm. Therefore never use pointed objects
or pressured air for cleaning the diaphragm.

Scrapping
- At end of life, the equipment must be recycled according to the relevant, local regulations. Besides the equipment itself, any
hazardous residues from the process liquid must be taken into consideration and dealt with in a proper manner. When in
doubt, or in the absence of local regulations, please contact your local Alfa Laval sales company.

Disposal
- The device has to be disposed of according to the European Directives 2002/96/EG and 2003/108/EG (on waste
electrical and electronic equipment). It is prohibited to place electrical and electronic equipment in domestic refuse!

Depending on the used medium, deposit on the device may cause danger for the user and the environment. Comply with
adequate precautions for purification and dispose of it properly.

24
5 Troubleshooting

5.1 No light
- Check that the unit is connected to electrical power.
- Press the blue button on the sensor board shortly to restart unit.
- Power down the unit and reconnect power again after 5 seconds.
- If problem persists, please contact Alfa Laval.

5.2 Red light


Constant red LED light is an indication of an alarm condition. Such condition can be “Rotation not OK” (Rotacheck+), or if there
is a constant jet impact on the sensor (Rotacheck Basic, Rotacheck+).
- Check if there is a problem with the cleaning process.
- Check if the tank pressure is exceeding the max. rating.
- Alternatively restart unit by shortly pressing the blue button on the sensor board.
- Recalibrate TEACH (Rotacheck+) if necessary by following the instructions.
- If problem persists, please contact Alfa Laval.

5.3 Red/Yellow flashing light

Red/Yellow flashing light indicates sensor malfunction or lost internal connection between sensor board and sensor.
- Press the blue button on the sensor board shortly to restart unit, or power down the unit and reconnect power again
after 5 seconds.
- If problem persists, please contact Alfa Laval.

5.4 Other failure modes


- Check the unit for visible damage.
- Press the blue button on the sensor board shortly to restart unit.
- Power down the unit and reconnect power again after 5 seconds.
- Recalibrate TEACH (Rotacheck+) if necessary by following the instructions.
- If problem persists, please contact Alfa Laval.

25
6 Technical Data

6.1 Technical data

Electrical data

Power supply 24 Vdc ± 10%


Power consumption max. 70 mA
Outputs (OK/hit, Alarm, Idle) Logic PNP
Electrical connection Cable gland or M12 connector,
Cable-ø and wire-ø
- for Cable gland (M16) ø5-ø8mm, max. 1,0mm2 (AWG 18)
- for M12 connector ø6-ø8mm, max. 0,5mm2 (AWG 20)
Short circuit and brownout protection EN 61131-2
Surges immunity EN 61000-4-5

hazardous
Special conditions for use in hazar dous ar
areas
eas

Rotacheck is approved in accordance with ATEX directive 94/9/EC, for use in Zone 0/20 in the product wetted area and
Zone 2/22 in the non-product wetted area.
Ex identification:
II 1/3G Ex ia/nA IIB T4/T3 Ga/Gc
II 1/3D Ex ia/tc IIIB T130 °C Da/Dc
Special conditions for safe use:
T4 for media temperatures <85°C
T3 for media temperatures <140°C
Fall height 40 cm is utilized in impact test of Rotacheck with M12 cable connector plug.
Permissible temperatures for environment for use in Zone 0 (Patm 0,8 to 1,1 bar): -10°C to 60°C
WARNING!: Rotacheck must not be separated when energized

Physical data

Protection class IP66 and IP67


Pressure rating of sensor
Pressure overload on diaphragm 15 bar
Max. working pressure in tank while performing monitoring 0.3 bar
Materials
Product wetted steel parts AISI 316L
Field house Polymer PA12, reinforced
Product wetted seals EPDM
Other seals NBR
Surface roughness, product wetted parts Ra 0,5µm
Operating temperature
Wetted parts -40°C to 125°C (140°C < 1 hour)
Field house -10°C to 60°C
Weight
Weight Approx. 600 gr.

Process
Pr ocess connection

Alfa Laval Hygienic Tank Connection (HTC)

26
.

27
7 Parts Lists and Drawing

7.1 Parts drawing and list

Parts Drawing

28
7 Parts Lists and Drawing

Parts list
Pos. Qty Denomination
1 1 Top cover/prism and o-ring
assembly
1.1 - Top cover/prism assembly
1.2 - O-ring for top cover
2 1 Sensor unit with o-ring
2.1 - Sensor unit
2.2 �
- O-ring
� - O-ring (Q-doc version)
� - O-ring set (10 pcs.) EPDM

□ Configuration according to delivery note/order.

29
7 Parts Lists and Drawing

7.2 Optional parts

Optional Parts Drawing

30
7 Parts Lists and Drawing

Parts list
Pos. Qty Denomination
3 1 Clamp ring
4 1 M12 connector
5 � 1 Tank flange, Hygienic tank
connection HTC
� 1 Tank flange, Hygienic tank
connection HTC (Q-doc version)
6 � 1 Blind cap with o-ring
� 1 Blind cap with o-ring (Q-doc
version)

□ Configuration according to delivery note/order.

31
8 Short functional guide

8.1 LED signals

Colour Signal Explanation


Green Flashing (50/50%) Initial calibration
Green On Idle
Green On/off (95/5%) First power-up (Rotacheck+ before Teach)
Yellow Yellow LED flash (1s) Sensor hit (Rotacheck basic or Rotacheck+ before Teach)
Yellow On/off (50/50%) Operation In window (Rotacheck+)
Yellow 3 short flashes Sensor hit during operation In window (Rotacheck+)
Yellow 1 short flash Termination of Teach (Rotacheck+)
Red Steady on Alarm
Red/Yellow Flashing Sensor alarm
Red/Yellow/Green Switching every 5 seconds Feedback Test mode (Rotacheck+)

8.2 Push button (PB) operation

PB Operation Signal Explanation


Press shortly Flashing green LED (5s) System restart
Press 1 second 1 Yellow LED flash Enable Teach (Rotacheck+)
Press 5 seconds 2 Yellow LED flashes Enable feedback test mode (Rotacheck+)
Press 10 seconds 3 Yellow flashes Back to first power up mode (Rotacheck+)

32
9 General Information

9.1 Service & Repair

Upon every return of a product, no matter if for modifications or repair, it is necessary to contact your local Alfa Laval office to
guarantee a quick execution of your request.

You will receive instructions regarding the return procedure from your local Alfa Laval office. Be sure to follow the instructions
closely.

9.2 Warranty

The warranty conditions are subject to the legal warranty period of 12 months from the date of delivery. In case of improper use,
modifications of or damages to the device, we do not accept warranty claims. Damaged devices will also not be accepted.
Furthermore, defects due to normal wear are not subject to warranty services.

9.3 How to contact Alfa Laval Kolding A/S

For further information please feel free to contact:

Alfa Laval Kolding A/S


31, Albuen - DK 6000 Kolding - Denmark
Registration number: 30938011
Tel switchboard: +45 79 32 22 00 - Fax switchboard: +45 79 32 25 80
www.toftejorg.com, www.alfalaval.dk - [email protected]

Contact details for all countries are continually updated on our websites

33
How to contact Alfa Laval
Contact details for all countries are
continually updated on our website.
Please visit www.alfalaval.com to access the information directly.

© Alfa Laval Corporate AB


This document and its contents is owned by Alfa Laval Corporate AB and protected by laws governing intellectual property and thereto related rights. It is the responsibility of the user of this
document to comply with all applicable intellectual property laws. Without limiting any rights related to this document, no part of this document may be copied, reproduced or transmitted in any
form or by any means (electronic, mechanical, photocopying, recording, or otherwise), or for any purpose, without the expressed permission of Alfa Laval Corporate AB. Alfa Laval Corporate AB
will enforce its rights related to this document to the fullest extent of the law, including the seeking of criminal prosecution.

You might also like