Quick Setup - ms300

The document provides instructions for setting up a variable speed drive for remote control and speed variation. It lists the key parameters that need to be configured, including setting the drive to be controlled remotely and selecting the source of the speed command. Connection diagrams and a list of important setup parameters are also included.

Uploaded by

Ahmed Sabry
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views2 pages

Quick Setup - ms300

The document provides instructions for setting up a variable speed drive for remote control and speed variation. It lists the key parameters that need to be configured, including setting the drive to be controlled remotely and selecting the source of the speed command. Connection diagrams and a list of important setup parameters are also included.

Uploaded by

Ahmed Sabry
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Instructions for Remote Setup

(Remote On/Off and Speed Variation)

For remote stop and start connect between DCM


and MI1 (FWD) and MI2 (REV) (DCM is your common)
For remote Potentiometer connect the pot to +10V,
AVI and ACM (common).
QUICK SETUP INSTRUCTIONS
Set 00.20 to 2 (Remote Potentiometer) FOR VARIABLE SPEED DRIVE
1 PHASE TO 3 PHASE
Set 00.21 to 1 (Remote ON/OFF setting)
Connect Live to R and Neutral to S for single phase input AND
supply Set 02.00 to 1 or 2 (2-wire operation control) 3 PHASE TO 3 PHASE
Connections U/T1, V/T2, W/T3 go to the motor

Connect 3 phase input supply to L1/R, L2/S, L3/T


Connections U/T1, V/T2, W/T3 go to the motor

Set 02.00 to 3 (3-wire operation control)

V/F curve set up

VFD-MS300 Series
Factory setting is General purpose

HAMILTON PH: 07 847 3374


CHRISTCHURCH PH: 03 666 3374
[email protected]

AUCKLAND PH: 09 271 6063


[email protected]
Important Notice Quick Setup for Variable Speed Drive List of quick set parameters
Wiring and connection must be carried out by Turn on power to unit and follow as below: 00.02 All parameters are reset to factory settings
a registered electrician. for 50Hz, set to 9 (must be none after initial power
Connection by an unqualified person voids up)
the warranty. 00.20 Source of master Frequency Command.
Please check the suitability of the motor 0 = UP/DOWN arrow (Factory setting)
before attempting to connect it to the device. 2 = External analog input
F60.0 will be displayed on the screen.
Ensure the motor terminals are configured to 3 = External UP/DOWN terminals
Press the enter button.
suit supply from VSD, for 1ph supply VFD the 7 = Digital keypad potentiometer
00. will appear on the screen.
motor must be connected in DELTA. For 3ph 00.21 Source of master Operation Command.
Press enter again.
supply VFD please consult the motors name 0 = Digital keypad (Factory setting )
00.00 will appear on the screen.
tag for 400V connection. 1 = External terminals
Use the up and down keys to change parameters
01.00 Change to the maximum Frequency
selections to the desired one. Press "ENTER"
2 required
You will now be able to change the parameter to the
3 01.01 Change value to match Hz on motor name
desired value or setting. Press enter. End will flash
1 plate
on your screen to indicate that your setting has
01.02 Change to match voltage on motor name
been saved.
plate (Max Voltage output)
Continue the above steps till all of your parameters
4 6 01.10 Upper limit Frequency
have been set.
01.11 Lower limit Frequency
Once all the parameters have been set press the
5 01.12 Acceleration time (factory setting 10sec)
"MODE" button till the F50.0 screen comes up again.
01.13 Deceleration time (factory setting 10sec)
7 8 05.01 Set to Motor Name Plate Current
05.02 Set to Motor Name Plate kW
05.03 Set to Motor Name Plate Speed (rpm)
1. Status Display –Display the drives current status
05.04 Set as the number of poles of the
2. LED Display—Indicates frequency, voltage, current,
motor(3000rpm=2pole; 1500rpm=4pole;
user defined units
1000rpm=6pole; 750rpm=8pole)
3. Potentiometer—For local frequency control
05-00 Auto tuning, option 1 Dynamic test for
4. Run Key— to start drive locally
induction motor = 1 (note motor must be
5. UP & DOWN Key—Used to change numerical
unloaded), Static test for induction motor = 2,
numbers, frequency, parameters
after the parameter number is entered press
6. Mode—Change between different display mode
MODE button to return to main screen showing
7. STOP/RESET— Stops AC drive operation and
F30.00 or F33.33, press the RUN button to start
resets the drive after a fault has occurred
auto tune, these test should only be preformed
8. ENTER - Used to enter and save the parameters
after all the above data is entered.
FOR ADVANCED SET UP REFFER TO THE FULL
MANUAL

See back page for remote control set up
www.rotatingmachinery.co.nz/products/drives