DPS 02
DPS 02
This document represents the new SEC Distribution Planning Standards (DPS) for
Underground Low Voltage Networks. This guideline should be applied and followed
in place of Section No.3 named (Low Voltage Planning Criteria) in the existing SEC
Distribution Planning Standards (DPS , Rev. 01 , Dated: March 2004).
2.0 SCOPE
This guideline describes the standards and criteria for electrical design and planning
of underground low voltage network and its layout to deliver the sufficient supply
of electricity to new customers' loads within the defined standards limits of voltage
and loading , and to maintain the reliability of power supply under all normal
operating load and voltage conditions within the defined standards limits. It is
intended to assist the planning engineers and field personnel to achieve
standardization in design and planning and to ensure a satisfactory and economical
level of service. It covers all types of supplying new customers with low voltage
underground network including (used LV materials , configurations types , design
principles and procedures , calculations , etc ).
1. LV Underground Materials
2. Step by Step Design Procedures
3. Supply Method for LV Large Meters ( 300 , 400 , 500 , 600 , 800 Amp )
4. Supply Method for LV Customers with Load more than 800 Amp by
Private/Dedicated Distribution Substations
5. Special Case : LV Network With Ring System
6. Special Case : LV Network for Hajj Area
7. Special Case : LV Network for Random Area
8. Special Case : LV Network for Commercial Center
9. Advantageous Modules and Tables
10. Typical Layout for Underground Low Voltage Network
11. Typical Distributed Loads per Outgoing of the Substation
4.0 DEFINITIONS
Customer :
It is any entity that purchases electrical power from a power utility. It is the owner
of the building/facility supplied by SEC's power system. It is the owner of the supply
request submitted to SEC to get electrical power.
Unit :
It is intended for the building's unit. Each unit should be used by one consumer. Each
building can contain a single unit or multiple units. Each unit should be supplied by
one KWH Meter according to SEC regulations.
Supply Request :
It is the request applied by the customer to get electric power supply from SEC's
power system. It can contain a single building or multiple buildings and subsequently
it can contain a single unit or multiple units and subsequently it can contain a single
KWH Meter or multiple KWH Meters.
Diversity Factor :
It is the inverse of the Coincidence Factor.
Contracted Load:
It is the capacity of power supply (in Volt-Amperes) equivalent to the circuit breaker
rating (in Amperes) provided to the customer's KWH Meter. Supply connection fees
and insurance charges are based on contracted load.
Low Voltage (LV) :
It is a class of nominal system voltages of 1000 Volts or less.
Nominal Voltage :
It is the voltage value, by which a system is designated and to which certain
operating characteristics of the system are related.
Service Voltage :
It is the voltage value at the Customer's interface, declared by the Power Utility. This
is generally expressed as a voltage range, in terms of a nominal voltage with plus
and minus percentage variations.
Firm Capacity :
Firm Capacity of any elements in LV Distribution Network is 80% of that element's
rating.
The voltages listed in Table (1) shall be used as standard service voltages at the
interface with power customers. The service voltage shall be maintained within the
range defined by the indicated lowest and highest values, under steady state and
normal system conditions and over the full loading range of the system. Where two
voltages are listed e.g., 400/230 V the lower value refers to the phase to neutral
voltage. All other values are phase-to-phase voltages
Table (1)
Nominal Voltage Lowest Voltage Highest Voltage
400/230 V 380/219 V 420/241 V
380/220 V 361/209 V 399/231 V
220/127 V 209/121 V 231/133 V
Percentage Limits - 5% + 5%
6.0 LV UNDERGROUND MATERIALS
This paragraph sets out standards for determining the Size, Loading, Dimension and
Location of Distribution Substation in SEC. The purpose is to provide sufficient
distribution and low voltage network capacity to enable permanent connection to
all customers demand loads at foreseen future.
a) Unit Substation
b) Package Substation
c) Room Substations
Separate Transformers and Low Voltage Distribution Boards also are available as
well as 13.8 KV Ring Main Unit. These are to be used in indoor substations. As indoor
substations usually serves large spot loads, the combinations of transformers and
Low Voltage. Distribution Board may differ from those of package unit substations,
but the ratings are similar.
6.2 LV DISTRIBUTION PANELS
Low voltage distribution panels to be used in the distribution substations. The panel
contains 400A molded case circuit breakers (MCCB) for out-going circuits.
400A MCCB according to SEC specification No. 37-SDMS-02 latest revision shall be
already installed for each outgoing feeder. MCCB outgoing terminals shall be
suitable for direct connection of 300mm² Al. cable.
Table (2)
Secondary
400/230 231/133
Voltage (V)
Transformer
300 500 1000 1500 300 500 1000 1500
Rating (KVA)
L.V. Panel
500 800 1600 2500 800 1600 3000 4000
Rating (A)
Number of
Outgoing 2 4 8 10 4 8 12 14
MCCB’s
Rating of
Outgoing 400 400 400 400 400 400 400 400
MCCB (A)
6.4 LV CABLES
The 4 x 300 mm2 AL/XLPE cable is the standard for LV main Feeder. Two sizes of
cable 4 x 185 mm2 & 4 x 70 mm2 AL/XLPE shall be used for service connections.
Three-phase four wires cable are provided as standard.
Detailed materials specifications for LV Cables are referred to SEC Distribution
Materials Specification No. (11-SDMS-01, Rev. 02) with its latest updates.
The LV cables current ratings in (A) and equivalent capacities in (KVA) at different
low voltages are given in Table (3) below :
Table (3)
Rating (KVA) for Different
LV Rating Voltages (V)
Cable Size (Amps) Standard Nominal Voltages
400 380 220
4 X 300 mm² AL 310 215 204 118
4 X 185 mm² AL 230 159 151 88
4 X 70 mm² AL 135 94 89 51
Note: These ratings are based on calculations derived from IEC 287 (1982) : “ Calculation of
the Continuous Current Rating of Cables”. They are based on the cable characteristics indicated in
Table (4) and on the standard rating conditions indicated in Table (5) below. These results are based
on data for typical cable types. For more precise data, refer to the specific cable supplier.
Correction factors for deviation from these conditions are indicated in Table (23) & Table (24) &
Table (25). Where two or more circuits are installed in proximity, the load rating of all affected
cables is reduced.
The LV Cables Characteristics (AC resistance and reactance) values are given in Table
(4) below :
Table (4)
RAC 20 °C X1 (60HZ)
LV Cable Size
Ohms / km Ohms / km
4 X 300 mm² AL 0.130 0.090
4 X 185 mm² AL 0.211 0.091
4 X 70 mm² AL 0.568 0.095
Note: Impedance values are ohms per km per phase for each cable type. Multiply by square
root of 3 to derive equivalent line values. Indicated values are positive / negative sequence
impedance values. The DC resistance values are based on IEC 228: conductors of Insulated
Cables. The AC resistance values take account of skin effect and are based on data for typical
cable types. For more precise data refer to the specific cable supplier. The reactance values are
based on a trefoil conductor configuration for single core cables. They are based on data for typical
cable types. For more precise data refer to the specific cable supplier.
Table (6)
MCCB Rating Max size of conductors suitable for the
(Amps) incoming terminals
20 ,30 , 40 ,50 , 70 ,100 ,125, 150 Copper conductor up to 35mm²
200 ,250 Copper conductor up to 120mm²
300 , 400 , 500 , 600 , 800 copper/aluminum conductor up to 300mm²
Detailed materials specifications for LV Service Connections Circuit Breakers are
referred to SEC Distribution Materials Specification No. (37-SDMS-01, Rev.03) with
its latest updates.
The KWH meters used by SEC are classified as given below in Table (7) :
Table (7)
Meter Type Meter CB Rating (A)
Whole Current Meter 20 , 30 , 40 , 50 , 70 , 100 , 125, 150
CT Operated Meter 200 A ,250 , 300 A , 400 A , 500 A , 600 A , 800
Fiberglass reinforced polyester boxes to be used for Kilo Watt Hour (KWH) meters
in the distribution system.
The meter boxes used by SEC are classified as given below in Table (8) :
Table (8)
Meter Box Type No. & Type of Meters Meter CB Rating
Single meter box one whole current meter rated up to 150 A
two whole current
Double meter box each rated up to 150 A
meters
four whole current
Quadruple meter box each rated up to 150 A
meters
200/250 A CT meter box one CT meter rated 200/250 A
300/400 A CT meter box one CT meter rated 300/400 A
500/600 A CT meter box one CT meter rated 500/600 A
800 A Remote meter box one CT meter rated 800 A
The incoming terminals shall be suitable for sizes of LV Cables given for the following
different Meter Box types as shown in Table (9) below.
Table (9)
Max size of LV Cables suitable for the
Meter Box Type Box Rating
incoming terminals
Single meter box two cables of sizes up to 4x70 mm² AL 200 Amps
two cables of sizes up to 4x185 mm²
Double meter box 300 Amps
AL
two cables of sizes up to 4x300 mm²
Quadruple meter box 400 Amps
AL
200/250 A CT meter two cables of sizes up to one 4 x 300
400 Amps
box mm² + one 4 x 185 mm²
300/400 A CT meter two back to back cables of sizes up to
400 Amps
box one 4 x 300 mm² + one 4 x 185 mm²
500/600 A CT meter two back to back cables of sizes up to
600 Amps
box 4 x 300 mm²
800 A Remote meter
two cables of sizes up to 4 x 300 mm² 800 Amps
box
Detailed materials specifications for Meter Boxes are referred to SEC Distribution
Materials Specification No. (42-SDMS-01, Rev.04) , No. (42-SDMS-02, Rev.00) and
No. (42-SDMS-03, Rev.00) with its latest updates.
In order to accommodate all the different ratings of Distribution Substations i.e. 300,
500, 1000 and 1500 KVA of package substation or unit substation, a total space of
4.5 x 2 meters is required. This is to guarantee that it can handle the size of 1500
KVA substation if required in future.
Detailed Dimensions and Construction Specifications for Location and Size of
Substation Sites should be according to SEC Distribution Construction Standard No.
(SDCS-02, PART 1 , Rev.00) with its latest updates.
9.0 UNDERGROUND LOW VOLTAGE NETWORK CONFIGURATION
There are three standard connection configuration types for customer connections
in Low Voltage Underground Network depends on customers demand loads as
following :
This type of connection is shown in Figure (1) and Figure (2) , For this condition, cable
300 mm2 AL/XLPE is used from substation to distribution Pillar, and cables 185mm2
AL/XLPE, 70 mm2 AL/XLPE are used from distribution Pillar to the customer
meter/meters box. (Common Configuration).
Figure (1)
Main LV Feeder Service LV Cable
300 mm2 185 or 70 mm2
AL/XLPE
Figure (2)
( b ) Direct Connection
This type of connection is shown in Figure (3) and Figure (4) , For this condition, cable
300 mm2 AL/XLPE is used directly from substation to the customer meter/meters
box. (Heavy Load Lots only).
Figure (3)
300 or 185 mm2
Main LV Feeder
Figure (4)
In the areas where load of customers is low , the outgoing of the distribution pillar
can be used to feed the second distribution pillar to provide connection to more
consumers. This type of connection is shown in Figure (5) and Figure (6) , For this
condition, cable 300 mm2 AL/XLPE is used from substation to the first distribution
Pillar, and cables 300 mm2 AL/XLPE or 185 mm2 AL/XLPE are used from the first
distribution Pillar to the second distribution Pillar and cables 185mm2 AL/XLPE or 70
mm2 AL/XLPE are used from distribution Pillar to the customer meter/meters box.
(Light Load Lots only).
Figure (6)
The Low voltage networks (also called secondary network) are connected at one end
and have no facility of back-feeding.
The following objectives should be achieved in the design of low voltage networks
taking into account all prevailing safety and reliability standards :
The design is the most economical (Low Cost) for the projected load and layout.
The following Formula should be used to calculate the Coincident Demand Load
(CDL) on any LV Network Element for the group of all KWH Meters supplied by that
LV Network Element as below.
Where :
0.33
(0.67 + )
𝐶𝐹(𝑁) = √𝑁
1.25
𝐹𝑜𝑟 𝑁 = 1 ⇒ 𝐶𝐹(𝑁) = 1
The loading percentage on all LV Equipments shall not exceed its Firm Capacity (80%
of its ratings).
a) The LV Cables shall not be loaded more than its Firm Capacity (80% of its rated
capacity) given in Table (12) below.
Table (11)
Rating (KVA) for Different
LV Rating Voltages (V)
Cable Size (Amps) Standard Nominal Voltages
400 380 220
4 X 300 mm² AL 310 215 204 118
4 X 185 mm² AL 230 159 151 88
4 X 70 mm² AL 135 94 89 51
Table (12)
Firm Firm Capacity (KVA) for
LV Different Voltages (V)
Capacity
Cable Size
(Amps)
Standard Nominal Voltages
400 380 220
4 X 300 mm² AL 248 172 163 95
4 X 185 mm² AL 184 127 121 70
4 X 70 mm² AL 108 75 71 41
Firm Capacity = 80% × Rating
b) The Distribution Pillars shall not be loaded more than its Firm Capacity (80%
of its rated capacity) given below in Table (14).
Table (13)
Rating (KVA) for Different
Rating Voltages (V)
Distribution (Amps)
Pillar Standard Nominal Voltages
400 380 220
400 277 263 152
Table (14)
Firm Capacity (KVA) for
Firm Different Voltages (V)
Distribution Capacity
Pillar (Amps) Standard Nominal Voltages
400 380 220
320 222 211 122
Firm Capacity = 80% × Rating
c) The Distribution Substations shall not be loaded more than its Firm Capacity
(80% of its rated capacity) given in Table (15) below.
Table (15)
Rating Firm Capacity
Distribution Substation
(KVA) (KVA)
300 KVA 300 240
500 KVA 500 400
1000 KVA 1000 800
1500 KVA 1500 1200
Firm Capacity = 80% × Rating
Where:
𝑉𝐷% = Voltage drop percentage on the cable in (%)
𝐾𝑉𝐴 = Three phase power in (KVA)
= Coincident Demand Load (CDL) on the cable.
𝑅 = Resistance of conductor in ohm per kilometer in (/km)
𝑋 = Inductive reactance of conductor in ohm per kilometer in (/km)
𝜑 = Power factor angle of the supply
𝑉 = Three phase supply nominal voltage in (volts)
𝐿 = Length of the cable in (meters)
The formula has reduced to a simple constant K equivalent to the product of KVA
and length of cable in meter at power factor of 0.85 lagging. For various values of
KVA-meter the voltage drop can be calculated by dividing it with this constant K.
𝑉2
𝐾=
100 × (𝑅 × 𝑐𝑜𝑠𝜑 + 𝑋 × 𝑠𝑖𝑛𝜑)
The value of the K constant changes with the supply voltage, power factor and size
and type of cable, due to the change of resistance and inductance. The calculations
of K values are shown in Table (16) below.
Table (16)
Cable
Size 𝑽 𝑹 𝑿 𝒄𝒐𝒔𝝋 𝒔𝒊𝒏𝝋 𝑲
mm2 Volts /km /km V2.km/
300 400 0.13 0.09 0.85 0.527 10132
300 380 0.13 0.09 0.85 0.527 9144
300 220 0.13 0.09 0.85 0.527 3065
185 400 0.211 0.091 0.85 0.527 7040
185 380 0.211 0.091 0.85 0.527 6353
185 220 0.211 0.091 0.85 0.527 2129
70 400 0.568 0.095 0.85 0.527 3003
70 380 0.568 0.095 0.85 0.527 2710
70 220 0.568 0.095 0.85 0.527 908
The values of K constant to be used for various standard LV cables are provided
hereunder in table (17):
Table (17)
Constant K
LV
Cable Size Standard Nominal Voltages
400 V 380 V 220 V
4 x 300 mm2 (AL) 10132 9144 3065
4 x 185 mm2 (AL) 7040 6353 2129
4 x 70 mm2 (AL) 3003 2710 908
𝐾𝑉𝐴 × 𝐿
𝑉𝐷% =
𝐾
Where:
𝑉𝐷% = Voltage drop percentage on the cable in (%)
𝐾𝑉𝐴 = Three phase power in (KVA)
= Coincident Demand Load (CDL) on the cable
𝐿 = Length of the cable in (meters)
𝐾 = The constant in (V2.km/) according to Table (17) above
Note: Above Voltage Drop calculations formula are based on balanced 3-Phase
system.
Example :
Max Lengths (m) can be achieved within (5%) Voltage Drop with Loading up to Firm
Capacity (KVA) for Different Nominal Voltages (V) for Different Sizes of LV Cables are
calculated using the above formula, as shown in Table (18) below.
Table (18)
Max Length (m) within (5%)
Voltage Drop with Loading up to
LV Firm Capacity (KVA) for Different
Cable Size Voltages (V)
The Utility voltage drop allocations listed in Table (19) shall be used as guideline
voltage drops over the power system components supplying a low voltage customer
to minimize lengths of Service Cables as possible.
Table (19)
LV Network Component Voltage Drop %
LV Main Feeder 3.5
Service Cable 1.5
Total Voltage Drop 5.0
Example :
Max Lengths (m) can be achieved within (5%) Voltage Drop with Loading up to Firm
Capacity (KVA) on Main LV Feeder (300 mm2) & with (30 A) LV Meter (0.6 DF) on
Service Cable (70 mm2) for Different Nominal Voltages (V) are calculated by using
the Voltage Drop calculations formula and by applying the voltage drop allocations
values listed in Table (19), as shown in Table (20) below
Table (20)
Voltage Drop (%) = 3.5 1.5 5
LV Cable Size 300 mm² 70 mm² Total Length (m)
Max Length (m) within (5%) 400 V 206 361 568
Voltage Drop with Loading up to
Firm Capacity (KVA) on LV Main
Feeder (300 mm2) & with (30 A)
380 V 196 343 539
Meter (0.6 DF) on Service Cable
(70 mm2) for Different Voltages (V) 220 V 114 199 312
29. For supplying new customers, it is preferred to use the substation with (500 KVA
or 1000 KVA) rating. This is to maintain a possibility for reinforcement of these
substations (1000 KVA & 500 KVA) by replacing them with 1500 KVA substation
without the need to install a new substation.
30. The substation with 300 KVA rating can be used in light load density area and also
for remote dedicated customers with light loads.
31. No. of Meter Boxes and their sizes required to handle the KWH Meters required
to supply a customer should be as minimum as sufficient with minimum no. of
Meter Boxes. i.e. always use larger size of Meter Box to handle more possible
KWH Meters in one box instead to use multi smaller size of Meter Boxes for same
no. of KWH Meters.
32. To supply a new customer's CDL from an existing DP , evaluation for the criteria
(Loading % , Voltage Drop %) should be based on the Coincident Demand Load
(CDL) of all customers KWH Meters (concerned new customer + existing
customers) supplied from this DP. Only in case that the measured Maximum
Demand (MD) on that DP is greater than CDL of existing customers , so the CDL
of the concerned new customer should be corrected by the scaling of MD on DP
as shown in the following equation :
𝑀𝐷 𝑜𝑛 𝐷𝑃 𝑓𝑜𝑟 𝐸𝑥𝑖𝑠𝑡𝑖𝑛𝑔 𝐶𝑢𝑠𝑡𝑜𝑚𝑒𝑟𝑠
𝐶𝐷𝐿 𝑁𝑒𝑤 𝐶𝑢𝑠𝑡𝑜𝑚𝑒𝑟 = 𝐶𝐷𝐿 𝑁𝑒𝑤 𝐶𝑢𝑠𝑡𝑜𝑚𝑒𝑟 ×
𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝐶𝐷𝐿 𝑜𝑛 𝐷𝑃 𝑓𝑜𝑟 𝐸𝑥𝑖𝑠𝑡𝑖𝑛𝑔 𝐶𝑢𝑠𝑡𝑜𝑚𝑒𝑟𝑠
Then evaluating for the criteria (Loading % , Voltage Drop %) should be based on
summation of MD on DP and the corrected CDL of concerned new customer.
33. To supply a new customer's CDL from an existing SS , evaluation for the criteria
(Loading % , Voltage Drop %) should be based on the Coincident Demand Load
(CDL) of all customers KWH Meters (concerned new customer + existing
customers) supplied from this SS. Only in case that the measured Maximum
Demand (MD) on that SS is greater than CDL of existing customers , so the CDL of
the concerned new customer should be corrected by the scaling of MD on SS as
shown in the following equation :
𝑀𝐷 𝑜𝑛 𝑆𝑆 𝑓𝑜𝑟 𝐸𝑥𝑖𝑠𝑡𝑖𝑛𝑔 𝐶𝑢𝑠𝑡𝑜𝑚𝑒𝑟𝑠
𝐶𝐷𝐿 𝑁𝑒𝑤 𝐶𝑢𝑠𝑡𝑜𝑚𝑒𝑟 = 𝐶𝐷𝐿 𝑁𝑒𝑤 𝐶𝑢𝑠𝑡𝑜𝑚𝑒𝑟 ×
𝐶𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 𝐶𝐷𝐿 𝑜𝑛 𝑆𝑆 𝑓𝑜𝑟 𝐸𝑥𝑖𝑠𝑡𝑖𝑛𝑔 𝐶𝑢𝑠𝑡𝑜𝑚𝑒𝑟𝑠
Then evaluation for the criteria (Loading % , Voltage Drop %) should be based on
summation of MD on SS and the corrected CDL of concerned new customer.
1. Connected Load (CL) in (KVA) for each Individual unit in customer's building
should be estimated, unit by unit, referring to SEC Distribution Planning
Standards No.(DPS-01, Rev. 02) titled (Estimation Of Customer Load Guideline)
with its latest updates.
2. Individual Circuit Breaker Rating (CBR) in (Amp) for the Individual KWH Meter for
each Individual unit in customer's building should be determined according to
the estimated connected load (CL) of that Individual unit and referring to SEC
Distribution Planning Standards No.(DPS-01, Rev. 02) titled (Estimation of
Customer Load Guideline) with its latest updates.
3. Number of Individual KWH Meters (N) required for the customer's building
should be determined according to number of Individual units in customer's
building and referring to SEC Customer Services Manual with its latest updates.
4. Calculate the Coincident Demand Load (CDL) in (Amp) for the group of all KWH
Meters of the customer's building as follows :
𝑁
𝐹𝑜𝑟 𝑁 = 1 ⇒ 𝐶𝐹(𝑁) = 1
Note :
For a group of (𝑁) KWH Meters in the customer's building where all of them have
same Circuit Breaker Rating (CBR) in (Amp) and same Demand Factor (DF), the
equation to calculate the Coincident Demand Load (CDL) in (Amp) for this group
of KWH Meters could be simplified as follows :
𝑁−1
5. Calculate the Coincident Demand Load (CDL) in (KVA) of the customer's building
from the calculated Coincident Demand Load (CDL) in (Amp) as follows :
217 248 150 172 143 163 83 95 DP 2 2 185 mm2 1 300 mm2
1 184 1 127 1 121 1 70 SS 1 1 185 mm2 Direct Feeder
185 248 128 172 122 163 70 95 SS 1 1 300 mm2 Direct Feeder
2
249 368 173 255 164 242 95 140 SS 2 2 185 mm Direct Feeder
2
369 496 256 344 243 326 141 189 SS 2 2 300 mm Direct Feeder
Table (23)
Burial Depth Correction Factors
Burial Depth – m Correction Factor
0.6 1.05
0.8 1.02
1.0 1.00
1.5 0.96
2.0 0.92
2.5 0.90
3.0 0.87
4.0 0.84
5.0 0.82
Note: Burial depth refers to the distance from the center of the cable installation to the final grade
(surface) level.
Table (24)
Soil Thermal Resistivity Correction Factors
Soil Thermal Resistivity - °C.m/w Correction Factor
1.2 1.14
1.5 1.08
2.0 1.00
2.5 0.92
3.0 0.86
Note: The value of soil thermal Resistivity chosen shall make full allowance for dry-out of the soil
adjacent to the cables, due to heat emission from the cables. All soil within the 50°C. isotherm
surrounding the cables should be assumed to be dry. The soil at the ground surface should also be
assumed to be dry. Thus the value of soil thermal Resistivity chosen shall be higher than the
background value derived from site measurements.
Table (25)
Ground Temperature Correction Factors
Ground Temperature - °C Correction Factor
30 1.04
35 1.00
40 0.95
Corrected Cable Rating (300 mm2 Cable) = 310 × 1.05 × 1.0 × 0.95 = 310 Amp
Corrected Cable Rating (185 mm2 Cable) = 230 × 1.05 × 1.0 × 0.95 = 230 Amp
Corrected Cable Rating (70 mm2 Cable) = 135 × 1.05 × 1.0 × 0.95 = 135 Amp
This concludes that the Corrected De-rated Capacity of LV Cables based on SEC
Standard Service Conditions are as shown in Table (27).
Table (27)
LV Corrected De-rated Capacity
Cable Size (Amps)
4 X 300 mm² AL 310
4 X 185 mm² AL 230
4 X 70 mm² AL 135
13.0 SUPPLY METHOD FOR LV LARGE METERS ( 300 , 400 , 500 , 600 , 800 AMP )
The following Tables (Table 31 & Table 32 & Table 33 & Table 34 & Table 35) show
the supply method for LV Large Meters (300 , 400 , 500 , 600 , 800 Amp) in
Underground LV Networks for different Demand Load Type by applying the design
principles described in Section No. (10.0) and taking in consideration the following
points :
1) The LV Cables Rating : Table (28)
1 Cable 2 Cables
Cable Size Rating
Max Max
mm2 Amp Amp Amp
300 mm² Cable 310 310 620
185 mm² Cable 230 230 460
70 mm² Cable 135 135 270
2) The Distribution Pillar's Firm Capacity and the rating of Outgoing Fuse of the
distribution pillar and the rating of Outgoing MCCB of the substation :
Table (29)
Substation Distribution Pillar Distribution Pillar
Outgoing MCCB Rating Outgoing Fuse Rating Firm Capacity
(Amp) (Amp) (Amp)
400 200 320
3) The capability of Cable connections to the outgoings of the distribution pillar and
the outgoings of the substation and the capability of Cable connections to the
incomings of the Meter Boxes (300 , 400 , 500 , 600 Amp) and Service Cabinet for
(800 Amp) Meter:
Table (30)
Connection Point Capability of Cable Connections
The supply method for these types of LV Large Meters need special configurations
design as follows :
Main LV Cable
Distribution Pillar Service LV Cable
Distribution Substation LV Meter
Figure (7)
Main LV Cable
Figure (9)
Figure (10)
(c) Two Outgoings from Substation to Service Cabinet (800 Amp) Meter
Main LV Cable
Distribution Substation LV Service Cabinet
Figure (11)
Metering Cable
Figure (12)
Table (31)
Option 1 Option 2
Limitation Scenario
Using of 1 Outgoing and 1 Cable Using of 2 Outgoings and 2 Cables
CB Demand Cable Cable
Supply No. of No. of Supply No. of No. of
Rating DF Load Size Size
Source Outgoings Cables Source Outgoings Cables
(Amp) (Amp) (mm2) (mm2)
300 0.5 150 SS 1 1 185 DP 2 2 70
300 0.6 180 SS 1 1 185 DP 2 2 70
300 0.7 210 SS 1 1 185 DP 2 2 70
300 0.8 240 SS 1 1 300 DP 2 2 70
300 0.9 270 SS 1 1 300 DP 2 2 70
SS = Substation DP = Distribution Pillar
13.2 Supply Method for 400 Amp LV Meter
Table (32)
Option 1 Option 2
Limitation Scenario
Using of 1 Outgoing and 1 Cable Using of 2 Outgoings and 2 Cables
CB Demand Cable Cable
Supply No. of No. of Supply No. of No. of
Rating DF Load Size Size
Source Outgoings Cables Source Outgoings Cables
(Amp) (Amp) (mm2) (mm2)
400 0.5 200 SS 1 1 185 DP 2 2 70
400 0.6 240 SS 1 1 300 DP 2 2 70
400 0.7 280 SS 1 1 300 DP 2 2 185
400 0.8 320 SS N/A N/A N/A SS 2 2 185
400 0.9 360 SS N/A N/A N/A SS 2 2 185
Table (33)
Option 1 Option 2
Limitation Scenario
Using of 1 Outgoing and 1 Cable Using of 2 Outgoings and 2 Cables
CB Demand Cable Cable
Supply No. of No. of Supply No. of No. of
Rating DF Load Size Size
Source Outgoings Cables Source Outgoings Cables
(Amp) (Amp) (mm2) (mm2)
500 0.5 250 SS N/A N/A N/A SS 2 2 70
500 0.6 300 SS N/A N/A N/A SS 2 2 185
500 0.7 350 SS N/A N/A N/A SS 2 2 185
500 0.8 400 SS N/A N/A N/A SS 2 2 185
500 0.9 450 SS N/A N/A N/A SS 2 2 185
Table (34)
Option 1 Option 2
Limitation Scenario
Using of 1 Outgoing and 1 Cable Using of 2 Outgoings and 2 Cables
CB Demand Cable Cable
Supply No. of No. of Supply No. of No. of
Rating DF Load Size Size
Source Outgoings Cables Source Outgoings Cables
(Amp) (Amp) (mm2) (mm2)
600 0.5 300 SS N/A N/A N/A SS 2 2 185
600 0.6 360 SS N/A N/A N/A SS 2 2 185
600 0.7 420 SS N/A N/A N/A SS 2 2 185
600 0.8 480 SS N/A N/A N/A SS 2 2 300
600 0.9 540 SS N/A N/A N/A SS 2 2 300
Table (35)
Option 1 Option 2
Limitation Scenario
Using of 1 Outgoing and 1 Cable Using of 2 Outgoings and 2 Cables
CB Demand Cable Cable
Supply No. of No. of Supply No. of No. of
Rating DF Load Size Size
Source Outgoings Cables Source Outgoings Cables
(Amp) (Amp) (mm2) (mm2)
800 0.5 400 SS N/A N/A N/A SS 2 2 185
800 0.6 480 SS N/A N/A N/A SS 2 2 300
800 0.7 560 SS N/A N/A N/A SS 2 2 300
800 0.8 640 SS N/A N/A N/A SS 2 2 300
800 0.9 720 SS N/A N/A N/A SS 2 2 300
Low Voltage Service Cabinet is intended to be used for outdoor installation to feed
bulk consumers of loads 800A in the Distribution Network as shown in Figure (12)
above. The service cabinet shall have one 800A rated MCCB.
The in-coming circuit terminals of the MCCB shall be suitable for fixing two
aluminum cables of size up to 4x300 mm2 with the use of SEC standard cable lugs.
Detailed materials specifications for LV Service Cabinet For 800A Bulk Customers are
referred to SEC Distribution Materials Specification No. (42-SDMS-02, Rev.00) with
its latest updates.
14.0 SUPPLY METHOD FOR LV CUSTOMERS WITH LOAD MORE THAN 800 AMP BY
PRIVATE / DEDICATED DISTRIBUTION SUBSTATIONS
The customer should provide the location of the proposed Private/ Dedicated
Substations according to SEC specification.
The no. of the substations and their ratings should be the nearest rating available
according to SEC specification to match the calculated coincident demand load of
the customer building unless the customer ask for more than demand load. The
contracted load is the rating of the transformer. For more details follow the
procedures as below :
1) Calculate connected load according to SEC standards (DPS-01)
2) Apply demand factor and coincident factor according to SEC standards (DPS-
01) to calculate the Coincident Demand Load (CDL).
3) Select the no. of the required substations and their KVA ratings from the
available SEC standard (300, 500, 1000, 1500 KVA) where the summation of
substations ratings should provide minimum sufficient total capacity (100 %
of substation’s rated capacity) to meet the calculated Coincident Demand
Load (CDL) with minimum no. of substations.
4) If the customer asks to supply his building by a load more than calculated
demand load justified by calculation study for declared loads, in this case the
demand load as requested by the customer should be considered instead of
the calculated demand load.
The supply method for these types of customers needs special configurations design
as follows :
( a ) Unit/Package Substation with LV Panel with Main Circuit Breaker and KWH
Meter and without Outgoing MCCBs
LV Panel
w/o Outgoings MCCB
Main
Circuit Breaker
Figure (13)
Figure (14)
Interface Low Voltage Main Circuit Breaker is to be used in the LV distribution system
for this configuration type. These Circuit Breakers are supplied by the Consumer. At
the boundary between SEC and Consumer inside the Consumer panel which shall be
fed directly from the SEC transformer or the LV Distribution Board through single
core copper, XLPE insulated 630mm² cables.
The Circuit Breakers are required in seven different capacities to have the following
current ratings :
(1000 A , 1250 A , 1600 A , 2000 A , 2500 A , 3200 A , 4000 A).
The terminals shall be suitable for installation of 630mm² Cable by using SEC
standard cable lugs. The number of single core cable per phase corresponding to
each breaker capacity shall be as per Table (37) below :
Table (37)
Breaker Rated Current 1000 1250 1600 2000 2500 3200 4000
A A A A A A A
No. Of Cable/Phase 2 2 2 4 4 4 6
Detailed materials specifications for Interface Low Voltage Main Circuit Breakers are
referred to SEC Distribution Materials Specification No. (37-SDMS-04, Rev.00) with
its latest updates.
15.0 SPECIAL CASE : LV NETWORK WITH RING SYSTEM
If there is a special area / customer need higher level of reliability by providing two
point of supply (one as main supply and the second as back-up supply) from different
Substation to the customers at Low Voltage Network level (for example: Al Mashaer
Al Moqadasah), in this special case , the LV Network with Ring System Design can be
used with approval from the authorized level of management.
The design configuration of the Ring System for LV Network is executed by supplying
each distribution pillar by two different main LV feeders from two different
substations. The design configuration should satisfy the following considerations :
1) Each main LV feeder should be design to carry the full demand load of the
distribution pillar.
2) Each Substation should be design to carry the full demand load of the
distribution pillar.
3) In normal operation only one from the two main LV feeders will be energized
by closing its MCCB from substation side and the other one should be not
energized by opening its MCCB from substation side. Parallel operation is not
allowed between the two main LV feeders.
4) It is preferred that the two different substations to be fed from different MV
feeders if it is possible.
The supply method of the Ring System for LV Network needs special configurations
design as shown in figure (15) below :
Substation 1 Substation 2
Distribution Pillar
Main Feeder 1 Main Feeder 2
(Main Supply) (Back-up Supply)
Service Cables
LV Meters
Figure (15)
16.0 SPECIAL CASE : LV NETWORK FOR HAJJ AREA
Hajj Load is intended any building used for pilgrims lodging. The Hajj Area is the area
which has permits from municipality to build buildings using for pilgrims lodging. For
these areas with this type, the design of its Underground LV Networks should be
based on the following special considerations :
1. The Demand Factor (DF) is 0.9.
2. The Coincident Factor (CF) is 1.0.
The Random Area is the area which is considered as un-planned area according to
the municipality and which has many buildings without construction permits from
the municipality. Usually in this area type, the un-permitted buildings get the supply
illegally from the permitted buildings. For these areas with this type, the design of
its Underground LV Networks should be based on the following special
considerations :
1. The Demand Factor (DF) is 1.0.
2. The Coincident Factor (CF) is 0.8.
The Commercial Center or any group of commercial shops which apply common
working time so that all its shops are to be opened and closed at the same time , for
this type of commercial shops , the design of its Underground LV Networks should
be based on the following special considerations :
1. The Demand Factor (DF) is 0.7.
2. The Coincident Factor (CF) is 1.0.
The Commercial Offices Building which apply common working time so that all its
Offices are to be opened and closed at the same time , for this type of commercial
Offices, the Calculation of Coincident Demand Load should be based on the
following special considerations :
1. The Coincident Factor (CF) is 1.0.
2. The Demand Factor (DF) is 0.7
The Complex Of Workshops which apply common working time so that all its
Workshops are to be opened and closed at the same time , for this type of
Workshops, the Calculation of Coincident Demand Load should be based on the
following special considerations :
1. The Coincident Factor (CF) is 1.0.
2. The Demand Factor (DF) is 0.9.
Design of LV Underground Network for New Plot Plan should be referred to SEC
Distribution Planning Standards No. (DPS-09, DPS-10) named (General Guide Lines
for Design of Distribution Network of Private Plot Plans) with its latest updates.
Software Modules are already built in EXCEL format and attached in the Appendixes
for the following subjects :
a) Design of Underground Low Voltage Network (Appendix A1).
b) Design of Substations required to supply an Area (Appendix A2).
c) Voltage Drop Calculations (Appendix A3 , A4).
Also Advantageous Tables are already built in EXCEL format and attached in the
Appendix for the following subjects :
a) No. of Meters can be supplied by (SS , DP , LV Cables) for different Demand
Factors (0.6 , 0.7 , 0.8 , 0.9) and for different CB Ratings (20 ,30, 40 , 50 , 70 , 100
, 125 , 150 , 200 , 250 , 300 , 400 , 500 , 600 , 800 A) in different Nominal Voltages
(400 , 380 , 220 V). (Appendix A5 , A6 , A7 , A8 , A9 , A10 , A11)
b) Max Lengths (m) can be achieved within allowed Voltage Drop (5% , 3.5% , 1.5%)
in different Nominal Voltages (400 , 380 , 220 V) with different LV Cables' Sizes
(300 , 185 , 70 mm2) for different Coincident Demand Load.
(Appendix A12 , A13 , A14)
c) Voltage Drop (%) in different Nominal Voltages (400 , 380 , 220 V) with different
LV Cables' Sizes (300 , 185 , 70 mm2) for different Coincident Demand Load (KVA)
with different Cables' Length (m).
(Appendix A15 , A16 , A17 , A18 , A19 , A20 , A21 , A22 , A23)
d) Demand Factor Values (Appendix A24)
e) Coincident Factor Values (Appendix A25)
Typical layout for design of Underground Low Voltage Network with typical location
of Substations at center of load and typical location of Distribution Pillars at middle
between lots (center of load) is illustrated in the following drawing in figure (16)
below.
Figure (16)
26.0 TYPICAL DISTRIBUTED LOADS PER OUTGOING OF THE SUBSTATION
Table (38) shows the typical distributed loads per outgoing of the substation to reach
full utilization of substation's firm capacity for different ratings of substations (300 ,
500 , 1000 , 1500 KVA) and for different nominal voltages (400 , 380 , 220 V).
Table (38)
Number of
Secondary Transformer LV Panel Transformer Load per
Outgoing
Voltage Rating Rating Rating Outgoing
MCCB’s
A2.
FEEDER DL CDL CDL Cable1 L1 CDL VD1 PL. CBR CL DL CDL CDL Cable2 L2 CDL VD2 L1+L2 TVD
N CF N DF CF
mm2 Rating mm2 Rating L2
NO. (KVA) (A) % K (m) (KVA) (%) NO (A) (A) (A) (A) % K (KVA) (%) (m) (%)
AL (A) AL (A) (m)
1 185
2 185
F1 300 3 185
4 185
5 185
6 185
7 185
F2 300 8 185
9 185
10 185
11 185
12 185
F3 300 13 185
14 185
15 185
16 185
17 185
F4 300 18 185
19 185
20 185
21 185
22 185
F5 300 23 185
24 185
25 185
26 185
27 185
F6 300 28 185
29 185
30 185
31 185
32 185
F7 300 33 185
34 185
35 185
Substation, required for design of Underground Low Voltage Network.
36 185
37 185
F8 300 38 185
39 185
40 185
TOTAL NO.OF PLOT =
MODULE FOR DESIGN OF SUBSTATIONS REQUIRED TO SUPPLY AN AREA
Total Area of
Total No. No of
Scheme Enter 1 for Plot Area
of Plots in Substations
(Plots only) Commercial, 0 for (Average)
the Required for
(m2) NOT Residential (m2)
Scheme the Scheme
AVAILABLE
0.0 0
estimate No. of Substations with a certain rating required to supply an area .
This Software Module is already built in EXCEL format. It makes the calculations to
A3. MODULE FOR VOLTAGE DROP CALCULATIONS (THROUGH DP)
This Software Module is already built in EXCEL format. It makes the calculations of
Voltage Drop from Substation to a Customer supplied through Distribution Pillar and
Loading Percentage on LV Cables.
0 WR:
0 A ---------> 0A
S/S
0 0 Meters 0 Meters
A4. MODULE FOR VOLTAGE DROP CALCULATIONS (DIRECT FEEDER)
This Software Module is already built in EXCEL format. It makes the calculations of
Voltage Drop from Substation to a Customer supplied by Direct Feeder and Loading
Percentage on LV Cable.
WR:
VD % = 5 PF = 0.85 Lag
Nominal Voltage 400 V 400 V 400 V 380 V 380 V 380 V 220 V 220 V 220 V
Cable Size 300 mm2 185 mm2 70 mm2 300 mm2 185 mm2 70 mm2 300 mm2 185 mm2 70 mm2
K Constant 10132 7040 3003 9144 6353 2710 3065 2129 908
CDL Length Length Length Length Length Length Length Length Length
(KVA) (m) (m) (m) (m) (m) (m) (m) (m) (m)
5 560 560 560 530 530 530 310 310 310
10 560 560 560 530 530 530 310 310 310
15 560 560 560 530 530 530 310 310 303
20 560 560 560 530 530 530 310 310 227
25 560 560 560 530 530 530 310 310 182
30 560 560 500 530 530 452 310 310 151
35 560 560 429 530 530 387 310 304 130
40 560 560 375 530 530 339 310 266 114
45 560 560 334 530 530 301 310 237
50 560 560 300 530 530 271 307 213
55 560 560 273 530 530 246 279 194
60 560 560 250 530 529 226 255 177
65 560 542 231 530 489 208 236 164
70 560 503 214 530 454 194 219 152
75 560 469 200 530 424 204
80 560 440 530 397 192
85 560 414 530 374 180
90 560 391 508 353 170
95 533 371 481 334 161
100 507 352 457 318
105 482 335 435 303
110 461 320 416 289
115 441 306 398 276
120 422 293 381 265
125 405 282 366
130 390 352
135 375 339
140 362 327
145 349 315
150 338 305
155 327 295
160 317 286
165 307
170 298
Firm Capacity
172 127 75 163 121 71 95 70 41
(KVA)
A13. TABLE FOR MAX LENGTHS WITHIN (3.5%) VOLTAGE DROP
This Table shows the Max Lengths (m) can be achieved within (3.5%) Voltage Drop
for different Coincident Demand Load (KVA) and for different Nominal Voltages (400
, 380 , 220 V) and for different LV Cables' Sizes (300 , 185 , 70 mm2).
A16. TABLE FOR VOLTAGE DROP (%) IN (400 V) WITH (185 MM2 CABLE)
A15. TABLE FOR VOLTAGE DROP (%) IN (400 V) WITH (300 MM2 CABLE)
170 0.34 0.67 1.01 1.34 1.68 2.01 2.35 2.68 3.02 3.36 3.69 4.03 4.36 4.70 5.03 5.37 5.70 6.04 6.38 6.71 7.05 7.38 7.72 8.05 8.39
This Table shows the Voltage Drop (%) in (400 V) LV Network with LV Cable size (300
mm2) for different Coincident Demand Load (KVA) with different Cables' Length (m).
Nominal Voltage 400 V Cable Size 185 mm2 K Constant 7040 PF = 0.85 Lag
Voltage Drop (%)
Length (m) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500
CDL (KVA)
5 0.01 0.03 0.04 0.06 0.07 0.09 0.10 0.11 0.13 0.14 0.16 0.17 0.18 0.20 0.21 0.23 0.24 0.26 0.27 0.28 0.30 0.31 0.33 0.34 0.36
10 0.03 0.06 0.09 0.11 0.14 0.17 0.20 0.23 0.26 0.28 0.31 0.34 0.37 0.40 0.43 0.45 0.48 0.51 0.54 0.57 0.60 0.63 0.65 0.68 0.71
15 0.04 0.09 0.13 0.17 0.21 0.26 0.30 0.34 0.38 0.43 0.47 0.51 0.55 0.60 0.64 0.68 0.72 0.77 0.81 0.85 0.89 0.94 0.98 1.02 1.07
20 0.06 0.11 0.17 0.23 0.28 0.34 0.40 0.45 0.51 0.57 0.63 0.68 0.74 0.80 0.85 0.91 0.97 1.02 1.08 1.14 1.19 1.25 1.31 1.36 1.42
25 0.07 0.14 0.21 0.28 0.36 0.43 0.50 0.57 0.64 0.71 0.78 0.85 0.92 0.99 1.07 1.14 1.21 1.28 1.35 1.42 1.49 1.56 1.63 1.70 1.78
30 0.09 0.17 0.26 0.34 0.43 0.51 0.60 0.68 0.77 0.85 0.94 1.02 1.11 1.19 1.28 1.36 1.45 1.53 1.62 1.70 1.79 1.88 1.96 2.05 2.13
35 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.89 0.99 1.09 1.19 1.29 1.39 1.49 1.59 1.69 1.79 1.89 1.99 2.09 2.19 2.29 2.39 2.49
40 0.11 0.23 0.34 0.45 0.57 0.68 0.80 0.91 1.02 1.14 1.25 1.36 1.48 1.59 1.70 1.82 1.93 2.05 2.16 2.27 2.39 2.50 2.61 2.73 2.84
45 0.13 0.26 0.38 0.51 0.64 0.77 0.89 1.02 1.15 1.28 1.41 1.53 1.66 1.79 1.92 2.05 2.17 2.30 2.43 2.56 2.68 2.81 2.94 3.07 3.20
50 0.14 0.28 0.43 0.57 0.71 0.85 0.99 1.14 1.28 1.42 1.56 1.70 1.85 1.99 2.13 2.27 2.41 2.56 2.70 2.84 2.98 3.13 3.27 3.41 3.55
55 0.16 0.31 0.47 0.63 0.78 0.94 1.09 1.25 1.41 1.56 1.72 1.88 2.03 2.19 2.34 2.50 2.66 2.81 2.97 3.13 3.28 3.44 3.59 3.75 3.91
60 0.17 0.34 0.51 0.68 0.85 1.02 1.19 1.36 1.53 1.70 1.88 2.05 2.22 2.39 2.56 2.73 2.90 3.07 3.24 3.41 3.58 3.75 3.92 4.09 4.26
65 0.18 0.37 0.55 0.74 0.92 1.11 1.29 1.48 1.66 1.85 2.03 2.22 2.40 2.59 2.77 2.95 3.14 3.32 3.51 3.69 3.88 4.06 4.25 4.43 4.62
70 0.20 0.40 0.60 0.80 0.99 1.19 1.39 1.59 1.79 1.99 2.19 2.39 2.59 2.78 2.98 3.18 3.38 3.58 3.78 3.98 4.18 4.38 4.57 4.77 4.97
75 0.21 0.43 0.64 0.85 1.07 1.28 1.49 1.70 1.92 2.13 2.34 2.56 2.77 2.98 3.20 3.41 3.62 3.84 4.05 4.26 4.47 4.69 4.90 5.11 5.33
80 0.23 0.45 0.68 0.91 1.14 1.36 1.59 1.82 2.05 2.27 2.50 2.73 2.95 3.18 3.41 3.64 3.86 4.09 4.32 4.55 4.77 5.00 5.23 5.45 5.68
85 0.24 0.48 0.72 0.97 1.21 1.45 1.69 1.93 2.17 2.41 2.66 2.90 3.14 3.38 3.62 3.86 4.11 4.35 4.59 4.83 5.07 5.31 5.55 5.80 6.04
90 0.26 0.51 0.77 1.02 1.28 1.53 1.79 2.05 2.30 2.56 2.81 3.07 3.32 3.58 3.84 4.09 4.35 4.60 4.86 5.11 5.37 5.63 5.88 6.14 6.39
95 0.27 0.54 0.81 1.08 1.35 1.62 1.89 2.16 2.43 2.70 2.97 3.24 3.51 3.78 4.05 4.32 4.59 4.86 5.13 5.40 5.67 5.94 6.21 6.48 6.75
100 0.28 0.57 0.85 1.14 1.42 1.70 1.99 2.27 2.56 2.84 3.13 3.41 3.69 3.98 4.26 4.55 4.83 5.11 5.40 5.68 5.97 6.25 6.53 6.82 7.10
105 0.30 0.60 0.89 1.19 1.49 1.79 2.09 2.39 2.68 2.98 3.28 3.58 3.88 4.18 4.47 4.77 5.07 5.37 5.67 5.97 6.26 6.56 6.86 7.16 7.46
110 0.31 0.63 0.94 1.25 1.56 1.88 2.19 2.50 2.81 3.13 3.44 3.75 4.06 4.38 4.69 5.00 5.31 5.63 5.94 6.25 6.56 6.88 7.19 7.50 7.81
115 0.33 0.65 0.98 1.31 1.63 1.96 2.29 2.61 2.94 3.27 3.59 3.92 4.25 4.57 4.90 5.23 5.55 5.88 6.21 6.53 6.86 7.19 7.51 7.84 8.17
120 0.34 0.68 1.02 1.36 1.70 2.05 2.39 2.73 3.07 3.41 3.75 4.09 4.43 4.77 5.11 5.45 5.80 6.14 6.48 6.82 7.16 7.50 7.84 8.18 8.52
125 0.36 0.71 1.07 1.42 1.78 2.13 2.49 2.84 3.20 3.55 3.91 4.26 4.62 4.97 5.33 5.68 6.04 6.39 6.75 7.10 7.46 7.81 8.17 8.52 8.88
A17. TABLE FOR VOLTAGE DROP (%) IN (400 V) WITH (70 MM2 CABLE)
This Table shows the Voltage Drop (%) in (400 V) LV Network with LV Cable size (185
mm2) for different Coincident Demand Load (KVA) with different Cables' Length (m).
Nominal Voltage 400 V Cable Size 70 mm2 K Constant 3003 PF = 0.85 Lag
Voltage Drop (%)
Length (m) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500
CDL (KVA)
5 0.03 0.07 0.10 0.13 0.17 0.20 0.23 0.27 0.30 0.33 0.37 0.40 0.43 0.47 0.50 0.53 0.57 0.60 0.63 0.67 0.70 0.73 0.77 0.80 0.83
10 0.07 0.13 0.20 0.27 0.33 0.40 0.47 0.53 0.60 0.67 0.73 0.80 0.87 0.93 1.00 1.07 1.13 1.20 1.27 1.33 1.40 1.47 1.53 1.60 1.67
15 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40 2.50
20 0.13 0.27 0.40 0.53 0.67 0.80 0.93 1.07 1.20 1.33 1.47 1.60 1.73 1.86 2.00 2.13 2.26 2.40 2.53 2.66 2.80 2.93 3.06 3.20 3.33
25 0.17 0.33 0.50 0.67 0.83 1.00 1.17 1.33 1.50 1.67 1.83 2.00 2.16 2.33 2.50 2.66 2.83 3.00 3.16 3.33 3.50 3.66 3.83 4.00 4.16
30 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 2.00 2.20 2.40 2.60 2.80 3.00 3.20 3.40 3.60 3.80 4.00 4.20 4.40 4.60 4.80 5.00
35 0.23 0.47 0.70 0.93 1.17 1.40 1.63 1.86 2.10 2.33 2.56 2.80 3.03 3.26 3.50 3.73 3.96 4.20 4.43 4.66 4.90 5.13 5.36 5.59 5.83
40 0.27 0.53 0.80 1.07 1.33 1.60 1.86 2.13 2.40 2.66 2.93 3.20 3.46 3.73 4.00 4.26 4.53 4.80 5.06 5.33 5.59 5.86 6.13 6.39 6.66
45 0.30 0.60 0.90 1.20 1.50 1.80 2.10 2.40 2.70 3.00 3.30 3.60 3.90 4.20 4.50 4.80 5.10 5.40 5.69 5.99 6.29 6.59 6.89 7.19 7.49
50 0.33 0.67 1.00 1.33 1.67 2.00 2.33 2.66 3.00 3.33 3.66 4.00 4.33 4.66 5.00 5.33 5.66 5.99 6.33 6.66 6.99 7.33 7.66 7.99 8.33
55 0.37 0.73 1.10 1.47 1.83 2.20 2.56 2.93 3.30 3.66 4.03 4.40 4.76 5.13 5.49 5.86 6.23 6.59 6.96 7.33 7.69 8.06 8.43 8.79 9.16
60 0.40 0.80 1.20 1.60 2.00 2.40 2.80 3.20 3.60 4.00 4.40 4.80 5.20 5.59 5.99 6.39 6.79 7.19 7.59 7.99 8.39 8.79 9.19 9.59 9.99
65 0.43 0.87 1.30 1.73 2.16 2.60 3.03 3.46 3.90 4.33 4.76 5.20 5.63 6.06 6.49 6.93 7.36 7.79 8.23 8.66 9.09 9.52 9.96 10.39 10.82
70 0.47 0.93 1.40 1.86 2.33 2.80 3.26 3.73 4.20 4.66 5.13 5.59 6.06 6.53 6.99 7.46 7.93 8.39 8.86 9.32 9.79 10.26 10.72 11.19 11.66
75 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.49 5.99 6.49 6.99 7.49 7.99 8.49 8.99 9.49 9.99 10.49 10.99 11.49 11.99 12.49
A18. TABLE FOR VOLTAGE DROP (%) IN (380 V) WITH (300 MM2 CABLE)
This Table shows the Voltage Drop (%) in (400 V) LV Network with LV Cable size (70
mm2) for different Coincident Demand Load (KVA) with different Cables' Length (m).
Nominal Voltage 380 V Cable Size 300 mm2 K Constant 9144 PF = 0.85 Lag
Voltage Drop (%)
Length (m) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500
CDL (KVA)
5 0.01 0.02 0.03 0.04 0.05 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.19 0.20 0.21 0.22 0.23 0.24 0.25 0.26 0.27
10 0.02 0.04 0.07 0.09 0.11 0.13 0.15 0.17 0.20 0.22 0.24 0.26 0.28 0.31 0.33 0.35 0.37 0.39 0.42 0.44 0.46 0.48 0.50 0.52 0.55
15 0.03 0.07 0.10 0.13 0.16 0.20 0.23 0.26 0.30 0.33 0.36 0.39 0.43 0.46 0.49 0.52 0.56 0.59 0.62 0.66 0.69 0.72 0.75 0.79 0.82
20 0.04 0.09 0.13 0.17 0.22 0.26 0.31 0.35 0.39 0.44 0.48 0.52 0.57 0.61 0.66 0.70 0.74 0.79 0.83 0.87 0.92 0.96 1.01 1.05 1.09
25 0.05 0.11 0.16 0.22 0.27 0.33 0.38 0.44 0.49 0.55 0.60 0.66 0.71 0.77 0.82 0.87 0.93 0.98 1.04 1.09 1.15 1.20 1.26 1.31 1.37
30 0.07 0.13 0.20 0.26 0.33 0.39 0.46 0.52 0.59 0.66 0.72 0.79 0.85 0.92 0.98 1.05 1.12 1.18 1.25 1.31 1.38 1.44 1.51 1.57 1.64
35 0.08 0.15 0.23 0.31 0.38 0.46 0.54 0.61 0.69 0.77 0.84 0.92 1.00 1.07 1.15 1.22 1.30 1.38 1.45 1.53 1.61 1.68 1.76 1.84 1.91
40 0.09 0.17 0.26 0.35 0.44 0.52 0.61 0.70 0.79 0.87 0.96 1.05 1.14 1.22 1.31 1.40 1.49 1.57 1.66 1.75 1.84 1.92 2.01 2.10 2.19
45 0.10 0.20 0.30 0.39 0.49 0.59 0.69 0.79 0.89 0.98 1.08 1.18 1.28 1.38 1.48 1.57 1.67 1.77 1.87 1.97 2.07 2.17 2.26 2.36 2.46
50 0.11 0.22 0.33 0.44 0.55 0.66 0.77 0.87 0.98 1.09 1.20 1.31 1.42 1.53 1.64 1.75 1.86 1.97 2.08 2.19 2.30 2.41 2.52 2.62 2.73
55 0.12 0.24 0.36 0.48 0.60 0.72 0.84 0.96 1.08 1.20 1.32 1.44 1.56 1.68 1.80 1.92 2.04 2.17 2.29 2.41 2.53 2.65 2.77 2.89 3.01
60 0.13 0.26 0.39 0.52 0.66 0.79 0.92 1.05 1.18 1.31 1.44 1.57 1.71 1.84 1.97 2.10 2.23 2.36 2.49 2.62 2.76 2.89 3.02 3.15 3.28
65 0.14 0.28 0.43 0.57 0.71 0.85 1.00 1.14 1.28 1.42 1.56 1.71 1.85 1.99 2.13 2.27 2.42 2.56 2.70 2.84 2.99 3.13 3.27 3.41 3.55
70 0.15 0.31 0.46 0.61 0.77 0.92 1.07 1.22 1.38 1.53 1.68 1.84 1.99 2.14 2.30 2.45 2.60 2.76 2.91 3.06 3.22 3.37 3.52 3.67 3.83
75 0.16 0.33 0.49 0.66 0.82 0.98 1.15 1.31 1.48 1.64 1.80 1.97 2.13 2.30 2.46 2.62 2.79 2.95 3.12 3.28 3.44 3.61 3.77 3.94 4.10
80 0.17 0.35 0.52 0.70 0.87 1.05 1.22 1.40 1.57 1.75 1.92 2.10 2.27 2.45 2.62 2.80 2.97 3.15 3.32 3.50 3.67 3.85 4.02 4.20 4.37
85 0.19 0.37 0.56 0.74 0.93 1.12 1.30 1.49 1.67 1.86 2.04 2.23 2.42 2.60 2.79 2.97 3.16 3.35 3.53 3.72 3.90 4.09 4.28 4.46 4.65
90 0.20 0.39 0.59 0.79 0.98 1.18 1.38 1.57 1.77 1.97 2.17 2.36 2.56 2.76 2.95 3.15 3.35 3.54 3.74 3.94 4.13 4.33 4.53 4.72 4.92
95 0.21 0.42 0.62 0.83 1.04 1.25 1.45 1.66 1.87 2.08 2.29 2.49 2.70 2.91 3.12 3.32 3.53 3.74 3.95 4.16 4.36 4.57 4.78 4.99 5.19
100 0.22 0.44 0.66 0.87 1.09 1.31 1.53 1.75 1.97 2.19 2.41 2.62 2.84 3.06 3.28 3.50 3.72 3.94 4.16 4.37 4.59 4.81 5.03 5.25 5.47
105 0.23 0.46 0.69 0.92 1.15 1.38 1.61 1.84 2.07 2.30 2.53 2.76 2.99 3.22 3.44 3.67 3.90 4.13 4.36 4.59 4.82 5.05 5.28 5.51 5.74
110 0.24 0.48 0.72 0.96 1.20 1.44 1.68 1.92 2.17 2.41 2.65 2.89 3.13 3.37 3.61 3.85 4.09 4.33 4.57 4.81 5.05 5.29 5.53 5.77 6.01
115 0.25 0.50 0.75 1.01 1.26 1.51 1.76 2.01 2.26 2.52 2.77 3.02 3.27 3.52 3.77 4.02 4.28 4.53 4.78 5.03 5.28 5.53 5.78 6.04 6.29
120 0.26 0.52 0.79 1.05 1.31 1.57 1.84 2.10 2.36 2.62 2.89 3.15 3.41 3.67 3.94 4.20 4.46 4.72 4.99 5.25 5.51 5.77 6.04 6.30 6.56
125 0.27 0.55 0.82 1.09 1.37 1.64 1.91 2.19 2.46 2.73 3.01 3.28 3.55 3.83 4.10 4.37 4.65 4.92 5.19 5.47 5.74 6.01 6.29 6.56 6.83
130 0.28 0.57 0.85 1.14 1.42 1.71 1.99 2.27 2.56 2.84 3.13 3.41 3.70 3.98 4.26 4.55 4.83 5.12 5.40 5.69 5.97 6.26 6.54 6.82 7.11
135 0.30 0.59 0.89 1.18 1.48 1.77 2.07 2.36 2.66 2.95 3.25 3.54 3.84 4.13 4.43 4.72 5.02 5.31 5.61 5.91 6.20 6.50 6.79 7.09 7.38
140 0.31 0.61 0.92 1.22 1.53 1.84 2.14 2.45 2.76 3.06 3.37 3.67 3.98 4.29 4.59 4.90 5.21 5.51 5.82 6.12 6.43 6.74 7.04 7.35 7.65
145 0.32 0.63 0.95 1.27 1.59 1.90 2.22 2.54 2.85 3.17 3.49 3.81 4.12 4.44 4.76 5.07 5.39 5.71 6.03 6.34 6.66 6.98 7.29 7.61 7.93
150 0.33 0.66 0.98 1.31 1.64 1.97 2.30 2.62 2.95 3.28 3.61 3.94 4.26 4.59 4.92 5.25 5.58 5.91 6.23 6.56 6.89 7.22 7.55 7.87 8.20
155 0.34 0.68 1.02 1.36 1.70 2.03 2.37 2.71 3.05 3.39 3.73 4.07 4.41 4.75 5.09 5.42 5.76 6.10 6.44 6.78 7.12 7.46 7.80 8.14 8.48
160 0.35 0.70 1.05 1.40 1.75 2.10 2.45 2.80 3.15 3.50 3.85 4.20 4.55 4.90 5.25 5.60 5.95 6.30 6.65 7.00 7.35 7.70 8.05 8.40 8.75
A19. TABLE FOR VOLTAGE DROP (%) IN (380 V) WITH (185 MM2 CABLE)
This Table shows the Voltage Drop (%) in (380 V) LV Network with LV Cable size (300
mm2) for different Coincident Demand Load (KVA) with different Cables' Length (m).
Nominal Voltage 380 V Cable Size 185 mm2 K Constant 6353 PF = 0.85 Lag
Voltage Drop (%)
Length (m) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500
CDL (KVA)
5 0.02 0.03 0.05 0.06 0.08 0.09 0.11 0.13 0.14 0.16 0.17 0.19 0.20 0.22 0.24 0.25 0.27 0.28 0.30 0.31 0.33 0.35 0.36 0.38 0.39
10 0.03 0.06 0.09 0.13 0.16 0.19 0.22 0.25 0.28 0.31 0.35 0.38 0.41 0.44 0.47 0.50 0.54 0.57 0.60 0.63 0.66 0.69 0.72 0.76 0.79
15 0.05 0.09 0.14 0.19 0.24 0.28 0.33 0.38 0.42 0.47 0.52 0.57 0.61 0.66 0.71 0.76 0.80 0.85 0.90 0.94 0.99 1.04 1.09 1.13 1.18
20 0.06 0.13 0.19 0.25 0.31 0.38 0.44 0.50 0.57 0.63 0.69 0.76 0.82 0.88 0.94 1.01 1.07 1.13 1.20 1.26 1.32 1.39 1.45 1.51 1.57
25 0.08 0.16 0.24 0.31 0.39 0.47 0.55 0.63 0.71 0.79 0.87 0.94 1.02 1.10 1.18 1.26 1.34 1.42 1.50 1.57 1.65 1.73 1.81 1.89 1.97
30 0.09 0.19 0.28 0.38 0.47 0.57 0.66 0.76 0.85 0.94 1.04 1.13 1.23 1.32 1.42 1.51 1.61 1.70 1.79 1.89 1.98 2.08 2.17 2.27 2.36
35 0.11 0.22 0.33 0.44 0.55 0.66 0.77 0.88 0.99 1.10 1.21 1.32 1.43 1.54 1.65 1.76 1.87 1.98 2.09 2.20 2.31 2.42 2.53 2.64 2.75
40 0.13 0.25 0.38 0.50 0.63 0.76 0.88 1.01 1.13 1.26 1.39 1.51 1.64 1.76 1.89 2.01 2.14 2.27 2.39 2.52 2.64 2.77 2.90 3.02 3.15
45 0.14 0.28 0.42 0.57 0.71 0.85 0.99 1.13 1.27 1.42 1.56 1.70 1.84 1.98 2.12 2.27 2.41 2.55 2.69 2.83 2.97 3.12 3.26 3.40 3.54
50 0.16 0.31 0.47 0.63 0.79 0.94 1.10 1.26 1.42 1.57 1.73 1.89 2.05 2.20 2.36 2.52 2.68 2.83 2.99 3.15 3.31 3.46 3.62 3.78 3.94
55 0.17 0.35 0.52 0.69 0.87 1.04 1.21 1.39 1.56 1.73 1.90 2.08 2.25 2.42 2.60 2.77 2.94 3.12 3.29 3.46 3.64 3.81 3.98 4.16 4.33
60 0.19 0.38 0.57 0.76 0.94 1.13 1.32 1.51 1.70 1.89 2.08 2.27 2.46 2.64 2.83 3.02 3.21 3.40 3.59 3.78 3.97 4.16 4.34 4.53 4.72
65 0.20 0.41 0.61 0.82 1.02 1.23 1.43 1.64 1.84 2.05 2.25 2.46 2.66 2.86 3.07 3.27 3.48 3.68 3.89 4.09 4.30 4.50 4.71 4.91 5.12
70 0.22 0.44 0.66 0.88 1.10 1.32 1.54 1.76 1.98 2.20 2.42 2.64 2.86 3.09 3.31 3.53 3.75 3.97 4.19 4.41 4.63 4.85 5.07 5.29 5.51
75 0.24 0.47 0.71 0.94 1.18 1.42 1.65 1.89 2.12 2.36 2.60 2.83 3.07 3.31 3.54 3.78 4.01 4.25 4.49 4.72 4.96 5.19 5.43 5.67 5.90
80 0.25 0.50 0.76 1.01 1.26 1.51 1.76 2.01 2.27 2.52 2.77 3.02 3.27 3.53 3.78 4.03 4.28 4.53 4.78 5.04 5.29 5.54 5.79 6.04 6.30
85 0.27 0.54 0.80 1.07 1.34 1.61 1.87 2.14 2.41 2.68 2.94 3.21 3.48 3.75 4.01 4.28 4.55 4.82 5.08 5.35 5.62 5.89 6.15 6.42 6.69
90 0.28 0.57 0.85 1.13 1.42 1.70 1.98 2.27 2.55 2.83 3.12 3.40 3.68 3.97 4.25 4.53 4.82 5.10 5.38 5.67 5.95 6.23 6.52 6.80 7.08
95 0.30 0.60 0.90 1.20 1.50 1.79 2.09 2.39 2.69 2.99 3.29 3.59 3.89 4.19 4.49 4.78 5.08 5.38 5.68 5.98 6.28 6.58 6.88 7.18 7.48
100 0.31 0.63 0.94 1.26 1.57 1.89 2.20 2.52 2.83 3.15 3.46 3.78 4.09 4.41 4.72 5.04 5.35 5.67 5.98 6.30 6.61 6.93 7.24 7.56 7.87
105 0.33 0.66 0.99 1.32 1.65 1.98 2.31 2.64 2.97 3.31 3.64 3.97 4.30 4.63 4.96 5.29 5.62 5.95 6.28 6.61 6.94 7.27 7.60 7.93 8.26
110 0.35 0.69 1.04 1.39 1.73 2.08 2.42 2.77 3.12 3.46 3.81 4.16 4.50 4.85 5.19 5.54 5.89 6.23 6.58 6.93 7.27 7.62 7.96 8.31 8.66
115 0.36 0.72 1.09 1.45 1.81 2.17 2.53 2.90 3.26 3.62 3.98 4.34 4.71 5.07 5.43 5.79 6.15 6.52 6.88 7.24 7.60 7.96 8.33 8.69 9.05
120 0.38 0.76 1.13 1.51 1.89 2.27 2.64 3.02 3.40 3.78 4.16 4.53 4.91 5.29 5.67 6.04 6.42 6.80 7.18 7.56 7.93 8.31 8.69 9.07 9.44
A20. TABLE FOR VOLTAGE DROP (%) IN (380 V) WITH (70 MM2 CABLE)
This Table shows the Voltage Drop (%) in (380 V) LV Network with LV Cable size (185
mm2) for different Coincident Demand Load (KVA) with different Cables' Length (m).
Nominal Voltage 380 V Cable Size 70 mm2 K Constant 2710 PF = 0.85 Lag
Voltage Drop (%)
Length (m) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500
CDL (KVA)
5 0.04 0.07 0.11 0.15 0.18 0.22 0.26 0.30 0.33 0.37 0.41 0.44 0.48 0.52 0.55 0.59 0.63 0.66 0.70 0.74 0.77 0.81 0.85 0.89 0.92
10 0.07 0.15 0.22 0.30 0.37 0.44 0.52 0.59 0.66 0.74 0.81 0.89 0.96 1.03 1.11 1.18 1.25 1.33 1.40 1.48 1.55 1.62 1.70 1.77 1.85
15 0.11 0.22 0.33 0.44 0.55 0.66 0.77 0.89 1.00 1.11 1.22 1.33 1.44 1.55 1.66 1.77 1.88 1.99 2.10 2.21 2.32 2.44 2.55 2.66 2.77
20 0.15 0.30 0.44 0.59 0.74 0.89 1.03 1.18 1.33 1.48 1.62 1.77 1.92 2.07 2.21 2.36 2.51 2.66 2.80 2.95 3.10 3.25 3.39 3.54 3.69
25 0.18 0.37 0.55 0.74 0.92 1.11 1.29 1.48 1.66 1.85 2.03 2.21 2.40 2.58 2.77 2.95 3.14 3.32 3.51 3.69 3.87 4.06 4.24 4.43 4.61
30 0.22 0.44 0.66 0.89 1.11 1.33 1.55 1.77 1.99 2.21 2.44 2.66 2.88 3.10 3.32 3.54 3.76 3.99 4.21 4.43 4.65 4.87 5.09 5.31 5.54
35 0.26 0.52 0.77 1.03 1.29 1.55 1.81 2.07 2.32 2.58 2.84 3.10 3.36 3.62 3.87 4.13 4.39 4.65 4.91 5.17 5.42 5.68 5.94 6.20 6.46
40 0.30 0.59 0.89 1.18 1.48 1.77 2.07 2.36 2.66 2.95 3.25 3.54 3.84 4.13 4.43 4.72 5.02 5.31 5.61 5.90 6.20 6.49 6.79 7.08 7.38
45 0.33 0.66 1.00 1.33 1.66 1.99 2.32 2.66 2.99 3.32 3.65 3.99 4.32 4.65 4.98 5.31 5.65 5.98 6.31 6.64 6.97 7.31 7.64 7.97 8.30
50 0.37 0.74 1.11 1.48 1.85 2.21 2.58 2.95 3.32 3.69 4.06 4.43 4.80 5.17 5.54 5.90 6.27 6.64 7.01 7.38 7.75 8.12 8.49 8.86 9.23
55 0.41 0.81 1.22 1.62 2.03 2.44 2.84 3.25 3.65 4.06 4.46 4.87 5.28 5.68 6.09 6.49 6.90 7.31 7.71 8.12 8.52 8.93 9.34 9.74 10.15
60 0.44 0.89 1.33 1.77 2.21 2.66 3.10 3.54 3.99 4.43 4.87 5.31 5.76 6.20 6.64 7.08 7.53 7.97 8.41 8.86 9.30 9.74 10.18 10.63 11.07
65 0.48 0.96 1.44 1.92 2.40 2.88 3.36 3.84 4.32 4.80 5.28 5.76 6.24 6.72 7.20 7.68 8.16 8.63 9.11 9.59 10.07 10.55 11.03 11.51 11.99
70 0.52 1.03 1.55 2.07 2.58 3.10 3.62 4.13 4.65 5.17 5.68 6.20 6.72 7.23 7.75 8.27 8.78 9.30 9.82 10.33 10.85 11.37 11.88 12.40 12.92
A21. TABLE FOR VOLTAGE DROP (%) IN (220 V) WITH (300 MM2 CABLE)
This Table shows the Voltage Drop (%) in (380 V) LV Network with LV Cable size (70
mm2) for different Coincident Demand Load (KVA) with different Cables' Length (m).
Nominal Voltage 220 V Cable Size 300 mm2 K Constant 3065 PF = 0.85 Lag
Voltage Drop (%)
Length (m) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500
CDL (KVA)
5 0.03 0.07 0.10 0.13 0.16 0.20 0.23 0.26 0.29 0.33 0.36 0.39 0.42 0.46 0.49 0.52 0.55 0.59 0.62 0.65 0.69 0.72 0.75 0.78 0.82
10 0.07 0.13 0.20 0.26 0.33 0.39 0.46 0.52 0.59 0.65 0.72 0.78 0.85 0.91 0.98 1.04 1.11 1.17 1.24 1.31 1.37 1.44 1.50 1.57 1.63
15 0.10 0.20 0.29 0.39 0.49 0.59 0.69 0.78 0.88 0.98 1.08 1.17 1.27 1.37 1.47 1.57 1.66 1.76 1.86 1.96 2.06 2.15 2.25 2.35 2.45
20 0.13 0.26 0.39 0.52 0.65 0.78 0.91 1.04 1.17 1.31 1.44 1.57 1.70 1.83 1.96 2.09 2.22 2.35 2.48 2.61 2.74 2.87 3.00 3.13 3.26
25 0.16 0.33 0.49 0.65 0.82 0.98 1.14 1.31 1.47 1.63 1.79 1.96 2.12 2.28 2.45 2.61 2.77 2.94 3.10 3.26 3.43 3.59 3.75 3.92 4.08
30 0.20 0.39 0.59 0.78 0.98 1.17 1.37 1.57 1.76 1.96 2.15 2.35 2.54 2.74 2.94 3.13 3.33 3.52 3.72 3.92 4.11 4.31 4.50 4.70 4.89
35 0.23 0.46 0.69 0.91 1.14 1.37 1.60 1.83 2.06 2.28 2.51 2.74 2.97 3.20 3.43 3.65 3.88 4.11 4.34 4.57 4.80 5.02 5.25 5.48 5.71
40 0.26 0.52 0.78 1.04 1.31 1.57 1.83 2.09 2.35 2.61 2.87 3.13 3.39 3.65 3.92 4.18 4.44 4.70 4.96 5.22 5.48 5.74 6.00 6.26 6.53
45 0.29 0.59 0.88 1.17 1.47 1.76 2.06 2.35 2.64 2.94 3.23 3.52 3.82 4.11 4.40 4.70 4.99 5.29 5.58 5.87 6.17 6.46 6.75 7.05 7.34
50 0.33 0.65 0.98 1.31 1.63 1.96 2.28 2.61 2.94 3.26 3.59 3.92 4.24 4.57 4.89 5.22 5.55 5.87 6.20 6.53 6.85 7.18 7.50 7.83 8.16
55 0.36 0.72 1.08 1.44 1.79 2.15 2.51 2.87 3.23 3.59 3.95 4.31 4.67 5.02 5.38 5.74 6.10 6.46 6.82 7.18 7.54 7.90 8.25 8.61 8.97
60 0.39 0.78 1.17 1.57 1.96 2.35 2.74 3.13 3.52 3.92 4.31 4.70 5.09 5.48 5.87 6.26 6.66 7.05 7.44 7.83 8.22 8.61 9.00 9.40 9.79
65 0.42 0.85 1.27 1.70 2.12 2.54 2.97 3.39 3.82 4.24 4.67 5.09 5.51 5.94 6.36 6.79 7.21 7.63 8.06 8.48 8.91 9.33 9.76 10.18 10.60
70 0.46 0.91 1.37 1.83 2.28 2.74 3.20 3.65 4.11 4.57 5.02 5.48 5.94 6.39 6.85 7.31 7.77 8.22 8.68 9.14 9.59 10.05 10.51 10.96 11.42
75 0.49 0.98 1.47 1.96 2.45 2.94 3.43 3.92 4.40 4.89 5.38 5.87 6.36 6.85 7.34 7.83 8.32 8.81 9.30 9.79 10.28 10.77 11.26 11.75 12.23
80 0.52 1.04 1.57 2.09 2.61 3.13 3.65 4.18 4.70 5.22 5.74 6.26 6.79 7.31 7.83 8.35 8.87 9.40 9.92 10.44 10.96 11.48 12.01 12.53 13.05
85 0.55 1.11 1.66 2.22 2.77 3.33 3.88 4.44 4.99 5.55 6.10 6.66 7.21 7.77 8.32 8.87 9.43 9.98 10.54 11.09 11.65 12.20 12.76 13.31 13.87
90 0.59 1.17 1.76 2.35 2.94 3.52 4.11 4.70 5.29 5.87 6.46 7.05 7.63 8.22 8.81 9.40 9.98 10.57 11.16 11.75 12.33 12.92 13.51 14.09 14.68
95 0.62 1.24 1.86 2.48 3.10 3.72 4.34 4.96 5.58 6.20 6.82 7.44 8.06 8.68 9.30 9.92 10.54 11.16 11.78 12.40 13.02 13.64 14.26 14.88 15.50
A22. TABLE FOR VOLTAGE DROP (%) IN (220 V) WITH (185 MM2 CABLE)
This Table shows the Voltage Drop (%) in (220 V) LV Network with LV Cable size (300
mm2) for different Coincident Demand Load (KVA) with different Cables' Length (m).
Nominal Voltage 220 V Cable Size 185 mm2 K Constant 2129 PF = 0.85 Lag
Voltage Drop (%)
Length (m) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500
CDL (KVA)
5 0.05 0.09 0.14 0.19 0.23 0.28 0.33 0.38 0.42 0.47 0.52 0.56 0.61 0.66 0.70 0.75 0.80 0.85 0.89 0.94 0.99 1.03 1.08 1.13 1.17
10 0.09 0.19 0.28 0.38 0.47 0.56 0.66 0.75 0.85 0.94 1.03 1.13 1.22 1.31 1.41 1.50 1.60 1.69 1.78 1.88 1.97 2.07 2.16 2.25 2.35
15 0.14 0.28 0.42 0.56 0.70 0.85 0.99 1.13 1.27 1.41 1.55 1.69 1.83 1.97 2.11 2.25 2.39 2.54 2.68 2.82 2.96 3.10 3.24 3.38 3.52
20 0.19 0.38 0.56 0.75 0.94 1.13 1.31 1.50 1.69 1.88 2.07 2.25 2.44 2.63 2.82 3.01 3.19 3.38 3.57 3.76 3.94 4.13 4.32 4.51 4.70
25 0.23 0.47 0.70 0.94 1.17 1.41 1.64 1.88 2.11 2.35 2.58 2.82 3.05 3.29 3.52 3.76 3.99 4.23 4.46 4.70 4.93 5.17 5.40 5.64 5.87
30 0.28 0.56 0.85 1.13 1.41 1.69 1.97 2.25 2.54 2.82 3.10 3.38 3.66 3.94 4.23 4.51 4.79 5.07 5.35 5.64 5.92 6.20 6.48 6.76 7.04
35 0.33 0.66 0.99 1.31 1.64 1.97 2.30 2.63 2.96 3.29 3.62 3.94 4.27 4.60 4.93 5.26 5.59 5.92 6.25 6.57 6.90 7.23 7.56 7.89 8.22
40 0.38 0.75 1.13 1.50 1.88 2.25 2.63 3.01 3.38 3.76 4.13 4.51 4.88 5.26 5.64 6.01 6.39 6.76 7.14 7.51 7.89 8.26 8.64 9.02 9.39
45 0.42 0.85 1.27 1.69 2.11 2.54 2.96 3.38 3.80 4.23 4.65 5.07 5.49 5.92 6.34 6.76 7.18 7.61 8.03 8.45 8.88 9.30 9.72 10.14 10.57
50 0.47 0.94 1.41 1.88 2.35 2.82 3.29 3.76 4.23 4.70 5.17 5.64 6.10 6.57 7.04 7.51 7.98 8.45 8.92 9.39 9.86 10.33 10.80 11.27 11.74
55 0.52 1.03 1.55 2.07 2.58 3.10 3.62 4.13 4.65 5.17 5.68 6.20 6.72 7.23 7.75 8.26 8.78 9.30 9.81 10.33 10.85 11.36 11.88 12.40 12.91
60 0.56 1.13 1.69 2.25 2.82 3.38 3.94 4.51 5.07 5.64 6.20 6.76 7.33 7.89 8.45 9.02 9.58 10.14 10.71 11.27 11.83 12.40 12.96 13.52 14.09
65 0.61 1.22 1.83 2.44 3.05 3.66 4.27 4.88 5.49 6.10 6.72 7.33 7.94 8.55 9.16 9.77 10.38 10.99 11.60 12.21 12.82 13.43 14.04 14.65 15.26
70 0.66 1.31 1.97 2.63 3.29 3.94 4.60 5.26 5.92 6.57 7.23 7.89 8.55 9.20 9.86 10.52 11.18 11.83 12.49 13.15 13.81 14.46 15.12 15.78 16.44
A23. TABLE FOR VOLTAGE DROP (%) IN (220 V) WITH (70 MM2 CABLE)
This Table shows the Voltage Drop (%) in (220 V) LV Network with LV Cable size (185
mm2) for different Coincident Demand Load (KVA) with different Cables' Length (m).
Nominal Voltage 220 V Cable Size 70 mm2 K Constant 908 PF = 0.85 Lag
Voltage Drop (%)
Length (m) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500
CDL (KVA)
5 0.11 0.22 0.33 0.44 0.55 0.66 0.77 0.88 0.99 1.10 1.21 1.32 1.43 1.54 1.65 1.76 1.87 1.98 2.09 2.20 2.31 2.42 2.53 2.64 2.75
10 0.22 0.44 0.66 0.88 1.10 1.32 1.54 1.76 1.98 2.20 2.42 2.64 2.86 3.08 3.30 3.52 3.74 3.96 4.18 4.40 4.62 4.84 5.06 5.28 5.50
15 0.33 0.66 0.99 1.32 1.65 1.98 2.31 2.64 2.97 3.30 3.63 3.96 4.29 4.62 4.95 5.28 5.61 5.94 6.28 6.61 6.94 7.27 7.60 7.93 8.26
20 0.44 0.88 1.32 1.76 2.20 2.64 3.08 3.52 3.96 4.40 4.84 5.28 5.72 6.17 6.61 7.05 7.49 7.93 8.37 8.81 9.25 9.69 10.13 10.57 11.01