Engineer Programming Eclipse 8-16-32 (2
Engineer Programming Eclipse 8-16-32 (2
PROGRAMMING
MANUAL
ECLIPSE 8
ECLIPSE 16
ECLIPSE 32
(S.W. 2.0x)
Attention:
This manual contains information on limitations regarding product use and
function and information on the limitations as to liability of the manufacturer.
The entire manual should be carefully read.
Table of Contents:
APPENDIX......................................................................................................................................................................... 83
APPENDIX 1. Memory LOG Events..................................................................................................................................... 83
APPENDIX 2. FIRE DELAY Operation Algorithm (ADDRESS 2015) ................................................................................... 86
APPENDIX 3. VD/ DTMF Operation Algorithm .................................................................................................................... 87
APPENDIX 4. Text Tree-Structure Menus ECLIPSE Series ................................................................................................ 88
APPENDIX 5. Style Diagrams for Zone Connection ............................................................................................................ 97
APPENDIX 6. ECLIPSE Series Control Panels – Main board Connection Diagrams ......................................................... 98
2
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
GUARANTEE
The guarantee terms are determined by the serial number (barcode) of the electronic device!
During the guarantee period the manufacturer shall, at its sole discretion, replace or repair any defective product when it is returned to the factory. All
parts replaced and/or repaired shall be covered for the remainder of the original guarantee, or 6 months, whichever period is longer. The original
purchaser shall immediately send manufacturer a written notice of the defective parts or workmanship.
INTERNATIONAL GUARANTEE
Foreign customers shall possess the same guarantee rights as those any customer in Bulgaria, except that manufacturer shall not be liable for any
related customs duties, taxes or VAT, which may be payable.
GUARANTEE PROCEDURE
The guarantee will be granted when the appliance in question is returned. The guarantee period and the period for repair are determined in advance.
The manufacturer shall not accept any product, of which no prior notice has been received via the RAN form at: http://www.teletek-
electronics.com/en/support/Service
The setup and programming included in the technical documentation shall not be regarded as defects. Teletek Electronics bears no responsibility for
the loss of programming information in the device being serviced.
WAIVER
This Guarantee shall contain the entire guarantee and shall be prevailing over any and all other guarantees, explicit or implicit (including any implicit
guarantees on behalf of the dealer, or adaptability to specific purposes), and over any other responsibilities or liabilities on behalf of the
manufacturer. The manufacturer does neither agree, nor empower, any person, acting on his own behalf, to modify, service or alter this Guarantee,
nor to replace it with another guarantee, or another liability with regard to this product.
UNWARRANTED SERVICES
The manufacturer shall repair or replace unwarranted products, which have been returned to its factory, at its sole discretion under the conditions
below. The manufacturer shall accept no products for which no prior notice has been received via the RAN form at: http://www.teletek-
electronics.com/en/support/Service .
The products, which the manufacturer deems repairable, will be repaired and returned. The manufacturer has prepared a price list and those
products, which can be repaired, shall be paid for by the Customer. The devices with unwarranted services carry 6 month guarantee for the replaced
parts.
The closest equivalent product, available at the time, shall replace the products, the manufacturer deems un-repairable. The current market price
shall be charged for every replaced product.
The CE mark is placed for indication that the Eclipse Series control panels comply with the requirement of EU for safety, health, environmental and
customer protection.
The Eclipse Series control panels are suitable for installation and operation in security systems specially designed to comply with standard EN
50131-1, grade 2.
3
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
1. GENERAL INFORMATION
ECLIPSE Series are control panels providing security and management of small and medium residential or office sites.
The programming of options, parameters and attributes is organized in menus and the engineer can choose among
three programming styles according his preferences:
1. 4-digit addresses;
2. 3-digit operations;
3. Text menus (tree-structure).
The default programming style is the one using text tree-structure for the engineer menus. To change the programming
style at the beginning you have to enter first the engineer menu with valid code (7777 by default) and choose in
sequence:
Confirm your choice with ENTER button – the keyboard will confirm the operation with a sound signal. The next
entering in the engineer menu will be with the selected programming style.
For installer’s convenience, the menus in this manual are presented with all programming styles as they are pointed at
the head and the functionality in details is described in the table under it.
The engineer menus are available for programming only when the system is disarmed and the engineer
access is enabled from the Manager programming menus.
4-digit addresses. The programming of the system parameters is organized with 4-digit address codes. The
menus have the following structure:
o 0ххх – General Settings Menu.
o 1xxx – General User Menu; 1uuy – User Settings, where “uu” is a user number from 01 to 64, and “y” is an
option.
o 2xxx – General Zone Settings Menu; 2zzy – Zone settings, as “zz” is a zone number from 01 to 32, and “y”
is an option.
o 3xxx – General Setting for PGM 4; 3ppy – Settings for PGMs, as “pp” is a PGM number from 01 to 32, and
“y” is an option.
o 4xxx – General Areas Menu; 4aay – Area Settings, as “aa” is an Area from 01 to 08, and “y” is an option.
o 5tty – Timeslots Settings, as “tt” is a time slot number from 01 to 08, and “y” is an option.
In addition, at addresses 5411 to 5524 are set holidays and nonworking days by months.
o 60хх – General Settings for the digital communicator; 6nny – Phone Settings, as “nn” is a phone number
from 01 to 04, and “y” is an option.
o 61xx – General settings for the voice dialer; 61ny – Phones settings, as “n” is a phone number from 1 to 8,
and “y” is an option.
o 69хх – General settings for UDL remote programming.
o 8ddy – Device Menu, as “dd” is a device number from 01 to 31, and “y” is an option.
Note: The Device 01 is always the main PCB of the control panel.
4
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
3-digit operations. The programming of the system parameters is organized with 3-digit operation codes. The
menus have the following structure:
o 0хх – General Settings Menu.
o 1xx – General User Menu; 1uu - Options for Users, as “uu” is an option number; after the option
number is necessary to enter a user number from 01 to 64.
o 2xx – General Zone Menu; 2zz – Zone options settings, as “zz” is an option number; after the option
number is necessary to enter a zone number from 01 to 32.
o 3xx – General Setting for PGM 4; 3pp – PGM options settings, as “pp” is an option number; after the
option number is necessary to enter a PGM number from 01 to 32.
o 4xx – General Areas Menu; 4aa – Area options settings, as “aa” is an option number; after the option
number is necessary to enter an Area number from 01 to 08.
o 5tt – Timeslot Menu, as “tt” in an option number; after the option number is necessary to enter an
Timeslot number from 01 to 08. In addition, at addresses 541 to 544 are set holidays and nonworking
days – and the number of the month from 01 to 12.
o 6хх – General Settings for the digital communicator; 6nn – Phones options settings; after the option
number is necessary to enter a phone number from 01 to 04.
o 67x – General settings for the voice dialer, where „х“ is number of an option from 0 to 3.
o 680 – Entering of telephone numbers for the voice dialer.
o 69х – General settings for UDL remote programming.
o 810 + dd – Device Menu, as “dd” is a device number from 01 to 31.
Note: The Device 01 is always the main PCB of the control panel.
Parameter
Engineer 3-digit Settings
Code operation
2-digit Parameter
Cancel the entered settings menu Settings
and return to the main menu
Text menus (tree-structure). The system parameters are organized in text menus with tree-structure:
1 2 3 4 5 6 7 8 9
COMMUNICATION
MAINTENANCE
INPUTS
DEVICES
SETTINGS
OUTPUTS
CODES
PARTITIONS
SCHEDULES
► ► ► ► ► ► ► ►
◄ ◄ ◄ ◄ ◄ ◄ ◄ ◄
To enter in a text menu select it with the arrow buttons and confirm with ENTER. The programming of the parameters
in the menus may differ according to their usage. Use the arrow buttons to scroll of the available menus or submenus.
You can also directly enter in a menu with pressing its number – see the structure above.
The exit to the upper menu or submenu is with pressing the CANCEL button.
5
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
There are several ways for setting parameters – that depends on the menu:
- When the submenu allows choosing only one option or attribute, or parameter from a list, the installer
scrolls down to the desired one and confirms his choice with button. The set option is displayed with a “check”
mark in front of it. The exit of the submenu is automatic. See Example 1 below.
- When the submenu allows choosing of several options or attributes, or parameters at the same time then
the installer has to scroll down to each one and to enable it with pressing the button. The set option is displayed
with a “check” mark in front of it. The installer has to move to the next option using the arrow buttons and so on. To
disable an option scroll down to it and press button – the “check” mark will be deleted. When all the desired
options are selected, the choice is confirmed with button. See Example 2 below.
6
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ATTENTION: The operation with text menus is set by default for control panels ECLIPSE 8/16/32.
The text menus are accessible for operation with LCD keyboards.
In case of using a LED keyboard for programming and settings the 4-digits address menus are used
by default.
7
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
The sound signalization for a system trouble (two short sound signals at every 20 seconds) can be disabled/ enabled
in Menu 2. SETTINGS – 03. TRBL SOUNDS (ADDRESS 0013 or OPERATION 013). The signalization is common for
all troubles. By default, the sound signalization for all system troubles is enabled.
* NOTE: It is possible after the initial power-up of ECLIPSE 32 panel a trouble message for 8. SOUNDER FAULT to be
displayed on the screen of LCD keyboards (8 zone number lights on the LED display). That indicates some problems
with sounder connected to PGM5. In case the PGM5 is used as a standard output, you have to terminate it with 1K
resistor, or to program it as regular output – disable option 1 at ADDRESS 3051.
** The message is displayed immediately after the initial power-up of the system or after full hardware reset – the time
and date should be set at addresses 0051 and 0052.
8
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Quick button for Stay Arming Mode. The button has a special function in text entering
STAY ARM
mode – shifting between small and capital letters.
SLEEP
Quick button for Sleep Arming Mode.
ARM
Entry in Manager and User programming modes. The button has a special function in
engineer programming mode – saving the entered settings and moves forward as the
PRG current index number is increased with +1 (see the note and the example following this
table).
Entry in Service Keyboard Mode.
Bypassing zones. The button lights on permanently if there are bypassed zones in the
system. The button is blinking during the bypassed zones review.
BYPASS The button has a special function in engineer programming – canceling the entered
settings and moves forward as the current index number is increased with +1 (see the
note and the example following this table), option 0.
9
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Reviewing the system troubles. The button lights on permanently if there are system
TROUBLE
problems. The button is blinking during the system troubles review.
Reviewing the memory events log file. The button lights on permanently if there are
memory events. The button is blinking during the memory events review. The button has a
MEMORY
special function in text entering mode – entering of special symbols (see the item 2.8
Entering text for LCD Keyboard).
Scroll
Arrows for moving the cursor on the left and on the right in programming mode.
arrows
Digit
0-9 Digital buttons for entering parameters, codes, etc.
Buttons
10
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
In normal operation mode the DISARM button (LED 8) or Area Letters (LED 16A) light on in green. The DISARM
button has a specific functionality in engineer programming menus.
Note: The button DISARM used in the previous design of the keyboard and has the same functionality!
3. Press the right arrow button. The cursor will move one position on the right, zone 2
starts blinking and lighting on digit number shows the next number of the address (or
operation).
4. Proceed in an analogical way reviewing the address number up to the last digit.
5. Press the button again to step back in parameter setting mode.
Note: You can also leave the view mode and with single pressing the CANCEL button.
Recommendation: If you are not familiar in details with the engineer programming
menus (address and operation numbers) write down in sequence the digits (of lighting
buttons) corresponding to the respective address positions (zone numbers).
- Engineer Programming
The engineer programming menus are accessible only when the system is disarmed. Lighting on symbols or
indicate the currently set programming style type.
To access the engineer programming menus enter valid engineer code (7777 by default). A confirmation sound signal
is heard and the system starts waiting for the installer to enter ADDRESS or OPERATION number for programming.
According the set programming style, the LED displays:
- The zone numbers 1, 2, 3 and 4, and lighting on - 4-digit ADDRESS programming style
- The zone numbers 1, 2 and 3, and lighting on - 3-digit OPERATION programming style
The symbol lights on permanently together with the letter for the set programming style – 4-digit ADDRESS
programming style is set by default.
To proceed with programming, enter ADDRESS number and according the descriptions provided in item 7, set
parameters, attributes and options for the system configuration. Use the digit buttons to enter the address number.
Every pressing of a button turns one zone number off, and the pressed button lights on. After pressing the last digit of
the address number, the system enters automatically in mode for setting parameters - lights on, and or light
off.
Several zone numbers will light on as their number depends on the current parameters for programming. Zone 1 is
blinking to show that the first digit of the value is currently set. A permanently lit digit button shows the current set
value. To change it, press other digit button according the parameter. If there are several values (when setting the date
for example), you can review them using the arrow buttons. Note: In case of setting options from ENABLE/ DISABLE
type keep in mind that the opting is disabled when all digit buttons are off, and the option is enabled when all digit
button are lighting on. You can change the setting of the option with pressing random digit button or arrows buttons.
To confirm the entered settings press the ENTER button – the system automatically moves to the next address
number. To cancel the entered parameters press the CANCEL button – the system will move back to the main screen
11
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
for ADDRESS entry. To exit to main screen press CANCEL button a couple of times. In normal operation mode only
the DISARM button lights on in green.
According the entered ADDRESS number the LED indication will differ. Use the detailed descriptions in item 7 to
become familiar with the system settings.
Attention: The exit from the engineer programming menus is not automatic! Press CANCEL button several times to
exit to the main display and normal operation mode – only the DISARM button lights on in green.
Example for reviewing of ADDRESS number in engineer menu with LED 8/ 16A keyboard:
- The symbols and are lighting on. Zone 1 is blinking and Button 1 lights on.
- Press the button. It starts blinking showing that the system is in mode for address reviewing.
- The symbols and light up. Letter means that the set programming style is with 4-digit ADDRESSES.
- Zone 1 is blinking. Button 0 is lighting on – this is the first digit of the ADDRESS number.
- Press the right arrow button.
- Zone 2 is blinking. Button 0 is lighting on – this is the second digit of the ADDRESS number.
- Press the right arrow button again.
- Zone 3 is blinking. Button 9 is lighting on – this is the third digit of the ADDRESS number.
- Press the right arrow button for the last time.
- Zone 4 is blinking. Button 7 is lighting on – this is the last digit of the ADDRESS number.
- The reviewed ADDRESS number is 0097 – Changing the programming style type.
- To go back to the parameter settings mode press the button again.
- Manager Programming
To access the manager programming menus enter valid manager code (0000 by default). A confirmation sound signal
will be heard. Press the PRG ( ) button to enter in manager programming menus. Zone numbers 1 and 2, and LEDs
and are lighting on. The manager programming menus are 2-digit and are described in details in ECLIPSE
Series Operation Manual – Manager and User Programming. If 30 sec after entering the manager programming there
is no activity (pressed button), the system will exit in normal operation mode. It is possible to enter in manager
programming menus from several keyboards at a time using the same manager access code.
Example for date setting in Manager programming menus using LED 8/ 16A keyboard:
- Enter valid Manager code (0000 by default) and press button.
- LEDs and are lighting on. Zone number 1 is blinking, and 2 is lighting on – the system waits for entering
of 2-digit ADDRESS number.
- Enter 15 – ADDRESS for date setting.
- LEDs and are lighting on. Zone number 1 is blinking, zones from 2 to 6 are lighting on. The “0” digit
button is lighting on (the set date by default is 01/01/12).
- Enter the new date using the format DDMMYY. You can use the buttons with arrows to review the entered
new date before saving it – the lighting on digit button shows the set value for every currently blinking zone number on
the display.
- Confirm the new set date with ENTER.
- Engineer Programming
The engineer programming menus are accessible only when the system is disarmed.
According to the set programming style after entering an engineer code (7777 by default) the LED displays:
- The zone numbers 13, 14, 15 and 16 lighting on - 4-digit ADDRESS programming style
- The zone numbers 14, 15 and 16 lighting on - 3-digit OPERATION programming style
12
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
The both LEDs „lightning” (white) and „padlock” (red) are blinking together showing that the system is in engineer
programming mode. Now, the system waits for entering of ADDRESS or OPERATION for programming – by default
the 4-digit ADDRESS programming style is set.
Use the digit buttons to enter an ADDRESS number – the detailed description of the ADDRESSES and their
functionality is provided in item 7. Every pressing of a button enters one digit and the lighting on zone numbers are
reduced with one, the number of the pressed digit button lights up (for 0 lights on digit 10). According the entered
address number the indication for the parameters is different. Use the address descriptions provided in item 7 to
orientate for the required settings. To confirm the entered settings press the ENTER button, to reject them – the
CANCEL button. To return to the display for address entering press single the CANCEL button. To exit the engineer
programming menu press the CANCEL button once again. The keyboard is in normal operation mode when LEDs
“Lightning” (white) and “padlock” (green) are lighting on together with the numbers of the used areas.
Attention: The exit of engineer programming menu is not automatic! To exit the engineer menu press CANCEL button
several times until return to the normal operation mode.
- Manager Programming
To access the manager programming menus enter valid manager code (0000 by default). A confirmation sound signal
will be heard. Press the PRG ( ) button to enter in manager programming menus. Zone numbers 15 and 16 are
lighting on, and both LEDs “Lightning” and “padlock” are blinking only on the keyboard for programming. The manager
programming menus are 2-digit and are described in details in ECLIPSE Series Operation Manual – Manager and User
Programming. If 30 sec after entering the manager programming there is no activity (pressed button), the system will
exit in normal operation mode. It is possible to enter in manager programming menus from several keyboards at a time
using the same manager access code.
To enter codes, addresses and parameters use the digit buttons. For arming the system can be used neither the quick
buttons with the respective pictograms, or to choose the arming type from the screen scrolling with the arrows and
confirmation with ENTER button. Use the provided in item 7 detailed descriptions of the all addresses in the system. To
exit the engineer or manager programming menu press CANCEL button several times until return to main screen in
normal operation mode.
The regular letters and digits can be entered directly by the buttons or as a code combination after pressing the
MEMORY button – look at the tables below.
It is possible to enter text up to 16 symbols including space.
13
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Table of the symbols and codes correspondence for CYR keyboard version:
Example: To enter
the „asterisk”
symbol, first press
the MEMORY button
(a solid cursor
appears on the place)
and after that enter
code 042. The
asterisk symbol will
appear and the
cursor will move one
position to the right.
14
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Eclipse 8/ 16
Serial connection between the ECLIPSE 8 / 16/ 32 and PC with ProsTE software
The service keyboard is not enrolled at a certain address and that is why its removing will not cause a system trouble
for a lost device.
You can connect only one service keyboards to the system configuration at the same time.
The “Service keyboard” mode allows access only to the engineer programming menus and the Manager and User
programming menus are not available. The system arming and disarming is also unavailable.
Every Eclipse Series keyboard can be service keyboard if it is not currently connected and enrolled to the
system configuration.
The service keyboard can be connected to the control panel in two ways:
- Via specialized cable for connection of service keyboard to the interface connector Service KBD on the
control panel PCB.
- To the system bus of the control panel.
The indication of a keyboard when used as service keyboard in the system, depends on its type:
15
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
The cable is factory prepared for connection to interface connector “Service KBD” on the panel’s PCB from the one
side and for connection to the keyboard terminals at the other – Figure 24.
Attention!
The interface connector Service To enter in the service keyboard mode:
Eclipse KBD is available in the following - Connect the interface connector to “Service KBD”
Keyboard hardware versions: terminals on the panel.
- Eclipse 8 rev. 1.5 - Connect the color wires to the keyboard terminals
- Eclipse 16 rev. 1.1 as observe the polarity of the connection.
- Eclipse 32 rev. 1.8 - Wait the initial initialization to complete.
- Single press the PRG button ( ).
- When you finish with the engineer programming,
Eclipse exit to the main screen.
Keyboard - Unplug the interface connector from the “Service
KBD” terminal.
Figure 24.
To enter the “Service keyboard” mode with a present keyboard in the system configuration:
- Use one of the other keyboards in the system configuration to delete the unique ID number of the one
selected for service keyboard – enter the keyboard ID address 8xx0, where “xx” is the device number from
02 to 32 (01 is always the PCB of the control panel), and delete the ID number with pressing the “0” button
for 2-3 seconds. It is not necessary to confirm with ENTER.
- Press the PRG ( ) button.
- When you finish with the engineer programming, exit to the main screen.
ATTENTION: If the engineer access is disabled from the manager programming menu the access will
be denied and for the service keyboard!
16
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
IMPORTANT NOTE!
When enrolling devices to ECLIPSE 8 control panel, the first is automatically added to ZONE 7, and
the second to ZONE 8!
3. Press the ENTER button (for a keyboard), the tamper-switch (for modules and standalone proxy reader) or
approach a proxy card (for a reader) of the device connected to the system bus and which you want to enroll to
the system configuration.
4. After successful enrollment to the control panel, the screen displays:
* Eclipse 8: Up to 2 devices can be enrolled to the system bus: 2 keyboards, 2 proximity card readers or 1
keyboard and 1 proximity card reader.
** Eclipse 16: Up to 5 devices can be enrolled to the system bus irrespective of their type.
*** Eclipse 32: Up to 30 devices can be enrolled to the system bus irrespective of their type.
NOTE: It is not necessary to enroll the built-in proximity reader in keyboards LED 32, LCD 32 and LCD 32S.
The wireless devices can be enrolled only to wireless expander module Eclipse WL, which already has been
added to the system configuration.
5. Press ENTER button of the used for programming keyboard. The keyboard will confirm the end of the
successful enrollment procedure with sound signal.
6. The new enrolled device is in normal operation mode and ready for further programming and configuration.
17
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
* Note: Other way for enrolling of a new device is to enter its unique ID number directly at a free address as use the
digit buttons and some button combinations – see the table below. The unique ID number is provided from the
manufacturer with a sticker on the backside of the PCB of the device.
The button is used in the previous design of the keyboards and has the same functionality.
* Eclipse 8: Up to 2 devices can be enrolled to the system bus: 2 keyboards, 2 proximity card readers or 1
keyboard and 1 proximity card reader.
** Eclipse 16: Up to 5 devices can be enrolled to the system bus irrespective of their type.
*** Eclipse 32: Up to 30 devices can be enrolled to the system bus irrespective of their type.
NOTE: It is not necessary to enroll the built-in proximity reader in keyboards LED 32, LCD 32 and LCD 32S.
The wireless devices can be enrolled only to wireless expander module Eclipse WL, which already has been
added to the system configuration.
5. Press ENTER button of the used for programming keyboard. The keyboard will confirm the end of the
successful enrollment procedure with sound signal.
6. The new enrolled device is in normal operation mode and ready for further programming and configuration.
18
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
6. ENGINEER PROGRAMMING
The Engineer programming menus are available only when the system is fully disarmed. By default, the engineer
access code is 7777.
The display performance is different according to the used keyboard model for programming:
The access to the Engineer programming menus is from one keyboard only while all other connected to the system
bus keyboards are temporally disabled for any operation. The LCD keyboards display a message „Engineer Mode!!!”
The default programming style is the one using text tree-structure for the engineer menus. To change the programming
style at the beginning you have to enter first the engineer menu with valid code (7777 by default) and choose in
sequence:
7777 – 2.SETTINGS – 14. MENU STYLE: TEXT, ADDRESS or OPERATION
Before starting the programming of any system parameter read carefully the provided detailed information for
each menu and make sure that you understand the descriptions.
ADDRESS 0000
ENG1 CODE OPERATION 000
TEXT MENU 3. CODES – 2. ENGINEER – 1. ENG1 CODE
Programming Menu type Access
Parameter
19
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Important Notes!
6.2 Indication
The indication while programming different system parameter is performed in several common types according the
structure of the address or operation.
Enter the new time using the digit buttons. The time interval varies according
LCD the parameter. For values smaller than 10 enter “00” in front of it – for example
005.
The zones 14, 15 and 16 show the number of the digits of the parameter. The
zones from 1 to 10 show the current set value for every digit, as 10 means 0.
The currently set digit is blinking. Use the arrows to review the values set to all
digits. For example, the zone 14 is blinking – the first digit of the parameter
LED 32
and its value is 0 (10 lighting on). Move to the right to review the set value for
the second digit – zone 15 is blinking and 1 is lighting on. Enter the new time
using the digit buttons. Every pressing of a button sets new value and
automatically moves the cursor to the right.
The zones 1, 2 and 3 show the number of the digits of the parameter. LED
LED 8/
symbol “V” is lighting on to show that the system is in value programing mode.
LED 16A
Lighting on digit button shows the current set value for every digit.
The “ENABLE” parameter is set when the zone numbers from 1 to 8 are
LED 32 lighting on; The “DISABLE” parameter is set when all zone numbers are off.
Press random digit button or arrows to switch over.
The zone 1 is blinking and LED symbol “V” is lighting on to show that the
system is in value programing mode.
LED 8/
The “ENABLE” parameter is set when digit buttons from 0 to 9 are lighting on;
LED 16A
The “DISABLE” parameter is set when all digit buttons are off. Press random
digit button or arrows to switch over.
20
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
The digits of the enabled options/ attributes are displayed on the screen. The
LCD disabled options are performed with asterisk symbol “*”. To enable/ disable an
option press the respective digit number.
The digits of the enabled options/ attributes are lighting on the screen. The
LED 32 disabled options are off. To enable/ disable an option press the respective
digit number.
The zone 1 is blinking and LED symbol “V” is lighting on to show that the
system is in value programing mode.
LED 8/
The digit buttons corresponding to the enabled options/ attributes are lighting
LED 16A
on. The digit buttons corresponding to the disabled options are off. To enable/
disable an option press the respective digit button.
The pictograms used in the descriptions below have the following meaning:
- The option, parameter or setting is available or specific for ECLIPSE 8 control panel.
- The option, parameter or setting is available or specific for ECLIPSE 16 control panel.
- The option, parameter or setting is available or specific for ECLIPSE 32 control panel.
- Useful tip.
- Example.
21
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 0000
ENG1 CODE OPERATION 000
TEXT MENU 3. CODES – 2. ENGINEER – 1. ENG1 CODE
Changing the Engineer code
This access code has full rights for programming of all engineer menus.
After entering the menu, first you have to delete the current code combination with continuous
pressing the button “0”. The keyboard will confirm the operation with a sound signal and will wait for
entering of a new 4/6*-digit button (see also the description of address 1000). The new code is
confirmed with ENTER button.
* ECLIPSE 8/ ECLIPSE 16 allows operation only with 4-digit access codes.
Engineer Code by Default: 7777
ADDRESS 0001
ENG2 CODE OPERATION 001
TEXT MENU 3. CODES – 2. ENGINEER – 2. ENG2 CODE
Changing the Maintenance code
The Maintenance code can access all engineer programming menus except the menus for users
and communication devices - ADDRESSES 1xxx and 6xxx.
After entering the menu, first you have to delete the current code combination with continuous
pressing the button “0”. The keyboard will confirm the operation with a sound signal and will wait for
entering of a new 4/6-digit button (see also the description of address 1000). The new code is
confirmed with ENTER button.
Maintenance Code by Default: 9999
22
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 0010
AMBUSH OPERATION 010
CODE TEXT MENU 2. SETTINGS – 01. AMBUSH CODE
This setting allows users to use an authority code during unauthorized forcing to disarm the system
(ambush code).
The ambush code is a personal code that disarms the system but still sends an alarm signal to the
central monitoring station to indicate that the user has been forcefully made to disarm the system.
After entering the ambush code the system will be disarmed with no sound signalization from the
sirens, but is generated “silent panic” alarm – the event is recorded in the memory LOG file and an
alarm message is sent to the central monitoring station.
The ambush code is produced from a personal code by increasing the last digit by one. If the last
digit is 9, it is replaced by 0.
The ambush code for 1234 is 1235, and for 9009 is 9000.
The parameter status is changed with pressing of random digit button of the keyboard. The change
is confirmed with ENTER button.
ADDRESS 0011
KBD BLOCK OPERATION 011
TEXT MENU 2. SETTINGS – 02. KBD BLOCK
At this address, the engineer allows blocking the keyboard buttons for 90 seconds when three wrong
user codes are entered in sequence or an invalid user card is placed in front of the proxy reader.
The access to the system is blocked only for that keyboard through which the three wrong user
codes are entered. A continuous sound signal is heard when the access through the keyboard is
enabled again.
The keyboard blocking mode will be activated when the time between entered wrong codes is less
than 15 seconds.
The access to a blocked keyboard can be restored also after entering of valid engineer code using
any other keyboard connected to the system bus.
In keyboard blocking mode, the LCD keyboard displays a message “Keyboard is locked” and a
backward timer shows the remaining time to normal mode.
In keyboard blocking mode, the LED keyboard displays the numbers from 1 to 16 (1 to 8 for LED8)
lighting off one by one during the backward timer.
The parameter status is changed with pressing of random digit button of the keyboard. The change
is confirmed with ENTER button.
23
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 0012
CHIME OPERATION 012
TEXT MENU 2. SETTINGS – 02. CHIME
At this address, the engineer can enable or disable the “Chime” sound signalization activated for
opening of Entry-Exit, Follow or Instant type zones.
The parameter status can be changed with pressing of random button of the keyboard. The change
is confirmed with ENTER button.
ADDRESS 0013
TRBL OPERATION 013
SOUNDS TEXT MENU 2. SETTINGS – 03. TRBL SOUNDS
It is possible after the initial startup of the system a trouble message for 8. SOUNDER FAULT to be
displayed on the screen of LCD keyboards (8 zone number lights on the LED display). That
indicates some problems with sounder connected to PGM5. If case the PGM5 is used as a standard
output, you have to terminate it with 1kOm resistor, or to program it as regular output – disable
option 1 at ADDRESS 3051.
The parameter status can be changed with pressing of random button of the keyboard.
ADDRESS 0014
CONF. OPERATION 014
TIMER TEXT MENU 2. SETTINGS – 04. CONF. TIMER
24
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 0015
AC DELAY OPERATION 015
TEXT MENU 2. SETTINGS – 05.AC DELAY
Programming of time for delay indication in case of 230 VAC power supply failure.
Enter a time from 0 to 255 minutes. The set time is confirmed with ENTER button.
In case of using a LED keyboard, you can review the set time with arrow buttons. The blinking zone
number indicates a programming mode for that value. A permanently lit zone number shows the
current set value (10 means 0). To change it, press other digit button – the cursor automatically
moves on the next value to the right.
If by mistake the installer enters bigger time than maximal of 255 minutes, the keyboard will reject the
entered value and will display the maximal possible one.
ADDRESS 0016
SOUND OPERATION 016
TMPR TEXT MENU 2. SETTINGS – 06.SOUND TMPR
Programming this address will not affect the TAMPER signal when the system is in armed mode.
Programming this address will affect the performance of the programmable outputs type SIREN,
ALARM and TAMPER, the LED and sound indication of the keyboards and the digital communicator
when the system is disarmed.
Every pressing of a digital button alternatively changes the enabled / disabled status. The display
indication is shown in the table.
25
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 0017
ALARM OPERATION 017
DELAY TEXT MENU 2. SETTINGS – 07.ALARM DELAY
Programming of alarm message delay to monitoring station and siren activation with 30
seconds or until the programmed entry time is over (the smaller value of both times is taken) in case
a zone, out of the entry route, is activated.
ADDRESS 0020
WALK TEST OPERATION 020
TEXT MENU 1. MAINTENANCE – 2. WALK TEST
Enables functional test of zones. The respective light-emitting diode (LED keyboard) or a number of
a zone (LCD keyboard), blinks while the zone is activated (open) in this mode. During the test, the
zone activation is accompanied with "Chime" sound signal and with continuous sound for "reject" –
open TAMPER zone.
ADDRESS 0021
PGM TEST OPERATION 021
TEXT MENU 1. MAINTENANCE – 3. PGM TEST
Important notes
In operation with LED 8/ 16A, after entering at the address the system automatically displays the
value setting mode.
ECLIPSE 8/ 16 (PGM 1-5) ECLIPSE 32 (PGM 01-32)
The blinking digit performs the value for editing, and lighting on button displays the current set value.
To change the value press a digit button – the cursor moves on the next zone number and so on.
ECLIPSE 32: The zone number 3 performs the PGM state – ON (all buttons light on) and OFF (all
buttons light off). The state is alternatively changed with pressing a random digit button.
26
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 0023
COMM TEST OPERATION 023
TEXT MENU 1. MAINTENANCE – 4. COMM TEST
Before starting the monitoring of the communicator performance, you have to enter a telephone
number at ADDRESS 6010.
The FULL Arm ( / ) button causes test transmission from the communicator to the central
station and from the voice dialer to assigned telephone numbers. The 0 button aborts any running
communication and deletes the queue of events to be sent.
The meaning of the symbols is given below, as the "active state" means permanent lighting of the
LEDs (LED keyboard) or step number (LCD keyboard).
After communication has been successfully completed, the keyboard emits a sound signal.
The CANCEL button exits Address 0023.
Step Action
1 Dialing the telephone number.
2 Waiting for „handshake” signal from the monitoring station.
3 Transmitting data to the monitoring station.
4 Waiting for confirmation signal from the monitoring station, ‘kissoff’ signal.
Communication process has been completed and all data has been successfully
5
transmitted to the central station.
ADDRESS 0030
HWR RESET OPERATION 030
TEXT MENU 2. SETTINGS – 08.HWR RESET
Specialized service is required where the hardware RESET is disabled and the engineer code is
obscure.
The parameter status can be changed with pressing of random button of the keyboard.
ADDRESS 0031
SELECT OPERATION 031
MENU TEXT MENU 2. SETTINGS – 09.PART DEFAULT
To restore the default parameters for a menu press the respective digit button (in operation with 4-
and 3-digit addresses):
27
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 0032
RESET MNG OPERATION 032
TEXT MENU 2. SETTINGS – 10. RESET MNG
Restoration of the default main manager code (User 01). Buttons 1, 2, 3, 4, 5, 6 are pressed in
succession and confirmed with the ENTER button.
The system restores the default 0000 manager user code.
ADDRESS 0040
LOG EVENT OPERATION 040
TEXT MENU 1. MAINTENANCE – 1. VIEW LOG
Use the digit button 2 to review some additional information for the event such as user, zone or area
number. Use the digit button 1 to go back to the main screen for memory events review. For correct
reading the information use the table for the events in the APPENDIX 1.
In case of using a LED keyboard to review the memory LOG file, keep in mind that the visualization
of the memory events, as the user numbers, zones numbers, area numbers and etc, is presented in
a binary form as the order is count from right to left side – see the column “Code” of APPENDIX 1,
there is given the reference of the LED indication in decimal form.
Examples:
Reviewing the events differs according the type of used LED keyboard. In the first row of the
keyboards (zones from 1 to 8) is displayed a user number, or zone number, or output number, etc,
according the type of the event, and in the second row (zones from 9 to 16) is displayed area
number if supported. For LED 8 keyboard the area number is visualized with lighting up buttons.
In the example is displayed reviewing of event 41 “Disarming with code” in Eclipse 32 control panel.
USER 01 Number
LED 32: AREA 03 Number
Number of event 41
USER 01 Number
LED 16A: AREA 03 Number Area Buttons light up
Number of event 41 1 6
2 3
3 3+6
4 8
LED 8: 5 6+8
6 3+8
Number of event 41 USER 01 Number AREA 03 Number
7 3+6+8
8 5
28
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 0050
SYSTEM OPERATION 050
NAME TEXT MENU 2. SETTINGS – 11. SYSTEM NAME
The engineer can enter a new system name at this address. The name has to be up 16 symbols –
letters (small and capital), digits and special symbols, including spaces.
The letters can be entered directly by the digit buttons. The cursor moves automatically to the right
after choosing of letter or digit, or may be moved manually by the arrows. To enter a digit press the
respective button and hold it for 2-3 seconds. See also item 2.8. Entering text for LCD Keyboard.
Confirm the new system name with ENTER button.
ADDRESS 0051
TIME OPERATION 051
TEXT MENU 2. SETTINGS – 12. TIME
ADDRESS 0052
DATE OPERATION 052
TEXT MENU 2. SETTINGS – 13. DATE
ADDRESS 0097
MENU STYLE OPERATION 097
TEXT MENU 2. SETTINGS – 14. MENU STYLE
If you choose to operate with text menus, they will be available only with LCD keyboards in the
system, while the engineer programming via the LED keyboards in the system will the available with
4-digit address menus.
ADDRESS 0098
SW OPERATION 098
REVISION TEXT MENU 1. MAINTENANCE – 5. SW REVISION
The engineer can review the current software revision of the control panel at this address.
29
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
1. Users
In “USERS” menu, the engineer programs some parameters and settings for the managers and users in the system.
Some of the addresses are available for programming only with LCD keyboard!
Attention: The USER 01 is the Chief Manager of the system. The Chief Manager has full rights to operate with
manager’s programming menus. The Chief Manager rights cannot be changes. All other users in the system are with
freely programmable rights.
The manager has extended rights in the system and can assign user codes and rights, and also to set the date and
time, and adjust some options of the keyboards – setting of the buzzer level, brightness, etc.
Every regular user in the system can change its own code only, while the Manager can change all other regular users’
codes. A Manager in the system cannot change other Manager’s code (available for ECLIPSE 32).
30
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 1000
CODE OPERATION 100
LENGTH TEXT MENU 3. CODES – 3. CODE LENGTH
Every pressing of a digital button or the arrows alternatively changes the digits number. The set
parameter is confirmed with ENTER button.
When switching from 4- to 6-digits code, the digits 00 will automatically be added at the end. For
example, the 4-digits code 1234 will become 123400.
When changing over from 6- to 4-digits code, only the first four figures in the 4-digits code
will remain valid. For example, the 6-digits code 123456 will become 1234. Due to risk of
coincidence of codes, changing over from 6- to 4-digits code IS NOT RECOMMENDED!
ADDRESS 1001
CODE OPERATION 101
CLONE TEXT MENU 3. CODES – 4. CODE CLONE
It is possible to clone only serial number of codes. If it is necessary to clone parameters to one user
code only, then enter 00 or the same user code in the “Last Code to clone” field. Press the ENTER
button to start the cloning procedure.
Example:
1001>CODE CLONE
[03]> [04] [10]
The source code is the User Code 03 and its parameters will be programmed in the settings of User
Codes from 04 to 10 inclusive.
31
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 1010
U1 OPTIONS OPERATION 110+01
TEXT MENU 3. CODES – 1. USERS – 01. USER – 1. OPTIONS
User code 01 is the Chief Manager in the system and always has full rights for operation and
programming of the system, which cannot be changed or erased!
ADDRESS 1011
U1 AREAS OPERATION 111+01
TEXT MENU 3. CODES – 1. USERS – 01. USER – 2. AREAS
The engineer associates areas to User code 01 at this address. The User can operate (arm, disarm,
bypass zones) only with area numbers associated to its code. One or several areas can be
associated to the user code. To select area, press the corresponding to its number digit button. Next
pressing of the same button will deselect the same area. The final configuration is confirmed with
ENTER button.
The User code 01 is always associated to at least one area number. All other user codes will
be inactive if there are no associated areas to them, irrespective of the assigned rights at the
previous!
It is possible the associated area numbers to the control device (keyboard or card reader) to be
different according to the area numbers associated to User code 01. In this case, the user code or
proximity card can operate only in the common areas for the device and the code. For example, if to
the user code all areas are associated in the system, and the associated to the control device areas
are 1, 2, 3 and 4, then and the user code can operate only with them.
To associate all areas to the user press button “0” – the button alternatively switches over all
enabled / all disabled state.
32
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 1012
U1 NAME OPERATION 112+01
TEXT MENU 3. CODES – 1. USERS – 01. USER – 3. NAME
The engineer can enter a new name for User 01 at this address. The name has to be up 16 symbols
– letters (small and capital), digits and special symbols, including spaces.
The letters can be entered directly by the digit buttons. The cursor moves automatically to the right
after choosing of letter or digit, or may be moved manually by the arrows. To enter a digit, press the
respective button and hold it for 2-3 seconds. See also item 2.8. Entering text for LCD Keyboard.
Confirm the new user name with ENTER button.
ADDRESS 1013
U1 PROXY OPERATION 113+01
TEXT MENU 3. CODES – 1. USERS – 01. USER – 4. PROXY
Assigning rights for operation with proximity card for User code 01
The engineer assigns rights to the proximity card for operation (arm, disarm) with User code 01. The
settings at this address include operation with a built-in in a keyboard proxy reader only.
According the settings at the address the user code can perform disarming and/ or arming the
system.
The arming options are set as a combination of options 2 and 3.
To enable an option press the digit button corresponding to its number. The next pressing of the
same button will deselect it.
The enabled option is indicated as digit on the LCD display or lighting on zone number on the LED
display. For LED 8/ 16A keyboards the set option is indicated with lighting on digit button.
The set options are confirmed with ENTER button.
Example:
1013>CD1_PROXY
[1*3_____]
User code 01 can disarm the associated to it areas and to realize Full Arming when using a
proximity card for system management.
33
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 1014
U1 T.SLOT OPERATION 114+01
TEXT MENU 3. CODES – 1. USERS – 01. USER – 5.TIMESLOT
Default settings: 0
ADDRESS 1015
U1 OPERATION 115+01
RC FUNC TEXT MENU 3. Codes – 1. Users – 01. User – 6. RC FUNCTION
At this address the installer sets functionality of button “” BRAVO remote key fob enrolled to
Eclipse WL wireless expander in the system. All enrolled key fobs are automatically attached to the
corresponding User numbers in the system - BRAVO RC 1 to USER 1, BRAVO RC 2 to USER 2
etc.
For function of button “” can be set one of the following options:
0. Unused The button is not used.
1. Sleep ARM The button will perform Sleep Arming.
2. Stay ARM The button will perform Stay Arming.
3. FIRE Alarm The button will perform Fire panic alarm.
4. MEDICAL Alarm The button will perform Medical panic alarm.
5. POLICE Alarm The button will perform Police panic alarm.
Enter the number of option using the digit buttons and confirm the chosen setting with ENTER
button.
Only one option can be selected for button “” function of a remote key fob.
Operation with Eclipse WL wireless expander is supported from Eclipse 16 and Eclipse 32 alarm
control panels, as the number of supported remote key fobs is as follows:
- Eclipse 16 – up to 32 remote key fobs
- Eclipse 32 – up to 64 remote key fobs
Default settings: 0
34
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 1xx0
Uxx OPERATION 110+xx
OPTIONS TEXT MENU 3. CODES – 1. USERS – xx. USER – 1. OPTIONS
When the option 8. MANAGER is enabled, it is obligatory to enable and option 4. PROGRAM!
To disable/ enable all user operation rights press button “0” – the button alternatively switches over
all enabled / all disabled state.
Default settings:
User codes ECLIPSE 8 ECLIPSE 16 ECLIPSE 32
01 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4, 8
02-08 1, 2
1, 2
09-32 1, 2
33-64
35
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
2. Zones
In “ZONES” menu, the engineer programs some parameters and settings for the zones in the system.
Some of the addresses are available for programming only with LCD keyboard!
36
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 2000
Z WIRING OPERATION 200
TEXT MENU 4. INPUTS – 1. WIRING
37
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 2001
Z ABYPASS OPERATION 201
TEXT MENU 4. INPUTS – 2. AUTO BYPASS
ADDRESS 2002
Z INSTANT OPERATION 202
TEXT MENU 4. INPUTS – 3. INSTANT
ADDRESS 2003
Z PCOUNT OPERATION 203
TEXT MENU 4. INPUTS – 4. PULSE COUNT – 1. PULSES
ADDRESS 2004
Z TPCOUNT OPERATION 204
TEXT MENU 4. INPUTS – 4. PULSE COUNT – 2. TIMEOUT
38
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 2005
Z CLONE OPERATION 205
TEXT MENU 4. INPUTS – 6. ZONE CLONE
Zone Cloning
This is an address for coping (cloning) of attributes, rights, areas and time slots from one to several
zones.
The information for cloning is set in three digit sections with the following meaning:
It is possible to clone only serial number of zones. If it is necessary to clone parameters to one zone
only, then in the “Last zone to clone” field enter 00 or the same zone. Press the ENTER button to
start the cloning procedure.
Example:
2005>Z CLONE
[02]> [03] [05]
The source zone is Zone 02 and its parameters will be programmed in the settings of zone numbers
from 03, 04 and 05.
ADDRESS 2010
Z1 ATTACH OPERATION 210 + 01
TEXT MENU 4. INPUTS – 5. ZONES – 01. ZONE – 1. ATTACH
39
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Example 1. At address 8020 (Device 02) to the control panel is enrolled a keyboard with one on
board zone input. Choose a free zone in the system configuration, number 15 for example, where to
attach the keyboard zone. Enter in the engineer programming menu, type address 2150, enter in
sequence number of device 02, and input number 01. The screen displays:
Example 2. At address 8100 (Device 10) to the control panel is enrolled a zone expander with 8 on
board zone inputs. Choose a free zone in the system configuration, number 20 for example, where
to attach the first zone of the expander. Enter in the engineer programming menu, type address
2200, enter in sequence number of device 10, and input number 01. The screen displays:
To use the second zone input of the same expander you have to attach it to the next free zone in the
system configuration – for example 21. Then at address 2210, you should enter in sequence
number of device 10 and input number 02. In analogical way proceed with the other zone inputs of
the expander to attach them to free zones in the system configuration.
ADDRESS 2011
Z1 TYPE OPERATION 211 + 01
TEXT MENU 4. INPUTS – 5.ZONES – 01. ZONE – 2. TYPE
Press the digital button, which corresponds to the number of the desired type.
No Type Description
0 UNUSED The zone is not used.
Entry- Exit zone.
Provides time to arm and disarm the site. After arming, the detector,
which was triggered off in this zone, will not sound an alarm until the
programmed EXIT TIME expires for the Area (or Areas) to which the
zone is attached.
No violation of the zone when in armed mode will sound an alarm before
the programmed ENTRY TIME expires for the Area (or Areas) to which
1 ENTRY/ EXIT
the zone is attached.
A sound signal is activated from the keyboard buzzer during entry and
exit time.
In SLEEP ARMING mode, the entry-exit type zones become instant and
no entry or exit time starts running when violation in the zone occurs –
the programmable ALARM and SIREN type outputs, and the
communicator are activated at once.
Follow zone.
An alarm zone which is active only when the site is armed in Full and
Stay arming. The zone operates instantaneously and activates the
programmable ALARM and SIREN type outputs, and the communicator.
Activating the zone during entry or exit time does not cause an alarm
event.
2 FOLLOW The entry time will start running if the follow type zone is activated while
the system is in SLEEP ARMING mode.
When the system is disarmed, the activation of a zone is indicated by
blinking of the respective light-emitting diode for the zone (LED
keyboards) or displayed zone name and number (LCD keyboards) for
the time that the zone remains open (The displayed mode can
40
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
41
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Default setting:
Type
Zone number ECLIPSE 8 ECLIPSE 16 ECLIPSE 32
01 2 1 1
02 3 2 2
03 3 0 0
04 3 0 0
05 5 0 0
06 6 0 0
07 1 0 0
08 1 0 0
09-16 0 0
17-32 0
ADDRESS 2012
Z1 AREAS OPERATION 212 + 01
TEXT MENU 4. INPUTS – 5. ZONES – 01. ZONE – 3. AREAS
To select all areas press button “0” – the button alternatively switches over all enabled / all disabled
state.
42
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 2014
Z1 ATTR 1 OPERATION 214 + 01
TEXT MENU 4. INPUTS – 5. ZONES – 01. ZONE – 4. OPTIONS 1
To select all attributes press button “0” – the button alternatively switches over all enabled / all
disabled state.
The Attributes from 1 to 7 can be assigned only for certain zone types – see the table below
for zone type compatibility!
Some of the Attributes are not available in ECLIPSE 8/ 16 control panel.
No Attribute Description
Authorization for automatic Bypassing the zone after reaching the number
1 Auto BYPASS of activations per armed mode as set at address 2001 (OPERATION 201)
for an arming mode.
Authorization to Bypass a zone. Assigning this attribute to the respective
2 BYPASS zone will authorize bypass of the zone on behalf of the system user or
manager.
The zone is not going to be armed in the STAY mode. Assigning this
3 Stay ARM
attribute will authorize bypassing of the zone during Stay arming mode.
The zone is not going to be armed in the SLEEP mode. Assigning this
4 Sleep ARM
attribute will authorize bypassing of the zone during SLEEP arming mode.
If when arming the system the zone is open (activated), then the
respective
5 Force ARM
AREA will be armed, and the respective zone will be armed after its
restoration.
DOUBLE KNOCK type zone. Assigning this attribute to the respective
zone authorizes Double Knock mode performance in the zone.
A 1 to 5-minute time interval (set at ADDRESS 4001) starts when a
detector in the zone is activated for the first time when the system is
armed. An alarm event is registered if second detector activation is
DOUBLE
6 recorded within this interval in the same or another zone.
KNOCK
An alarm event will also be registered if no zone is restored within 15 sec.
of the first activation of the zone.
Note: The attribute does not apply for BRAVO PIR wireless motion
detector. BRAVO PIR can operate in “Double knock” mode ONLY if there
is set jumper on the terminals of its PCB.
When armed the zone will perform as Entry/Exit type.
The system will be armed:
7 E/E FINAL
А) When the exit time is over;
B) 3 seconds after closing the entry-exit zone.
Programmable sensitivity of the zone – choose between 64ms (fast) and
256ms (regular).
FAST/
8 Indication:
REGULAR
LCD: REGULAR – / FAST – 8
LED: REGULAR – / FAST –
43
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 2015
Z1 ATTR 2 OPERATION 215 + 01
TEXT MENU 4. INPUTS – 5. ZONES – 01. ZONE – 5. OPTIONS
To select all attributes press button “0” – the button alternatively switches over all enabled / all
disabled state.
44
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Power up The zone will be bypassed for a 120 second period after power-up of the system
8
Delay (that eliminated the false alarms in the initial power-up of the control panel).
ADDRESS 2016
Z1 OPERATION 216 + 01
KSWITCH TEXT MENU 4. INPUTS – 5. ZONES – 01. ZONE – 6. KEY SWITCH
At this address are assigned only attributes for Key-Switch type zone.
More than one attribute can be assigned for the zone. Pressing a digital button with the respective
number will activate a given attribute. Every activated attribute number is indicated as a lighting on
LED or display the zone name and number. Pressing the same digital button again will deactivate
the attribute.
To select all attributes press button “0” – the button alternatively switches over all enabled / all
disabled state.
2 3 Arming type
Key SWITCH Not used
3
ARM type 3 Full Arming mode
2 Stay Arming mode
2 3 Sleep Arming mode
This attribute determinates whether with activation of the zone the system
4 DISARM will be disarmed:
DISARM ENABLED (4) or not - DISARM DISABLED ().
NORMAL/ Normal or inverted operation of the zone. In case of setting the INVERT (5)
5
INVERT attribute, the system will be disarmed in zone activation.
45
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 2017
Z1 AUX OPERATION 217 + 01
TEXT MENU 4. INPUTS – 5. ZONES – 01. ZONE – 7. AUXILIARY
Only one attribute AUX can be assigned at this address - a number from 0 to 9. To assign an AUX
attribute press the respective digital number. The entered attribute is confirmed with ENTER.
ADDRESS 2018
Z1 NAME OPERATION 218 + 01
TEXT MENU 4. INPUTS – 5. ZONES – 01. ZONE – 8. NAME
4. SLEEP ARM
5. Force ARM
6. DOUBLE *
7. E/E Final
8. Fast/ Regular
Add
3. Report only
* Note: When the attribute “6. DOUBLE” is set for “Follow” zone type, its functionality will be diabled during “Sleep” arming mode!
46
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 2019
Z1 LINE OPERATION 219 + 01
TEXT MENU 4. INPUTS – 5. ZONES – 01. ZONE – 9. LINE RESIST
The engineer can check the line resistance of the zone at this address. It is suitable to perform
diagnostics of the zone troubles. The displayed value can vary according the used hardware
connection style in the system and has the following meaning:
Connection style Displayed value Description
< 1.5 kΩ The zone is closed.
1
> 1.5 kΩ The zone is open.
< 0.75 kΩ The zone is open.
2 0.75 – 1.5 kΩ The zone is closed.
Single zone connection
The ZONES with numbers from 02 to 08 for ECLIPSE 8, from 02 to 16 for ECLIPSE 16 and from 02 to 32 for ECLIPSE
32 are programmed in an analogical way.
47
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
3. PGM Outputs
In “PGM Outputs” menu, the engineer programs some parameters and settings for the programmable outputs in the
system.
Some of the addresses are available for programming only with LCD keyboard!
Attention: In Eclipse 32 control panel, the PGM5 output is powerful (up to 1А) and is set by default as a monitored
output for siren connection. If after the initial power-up no siren is connected to the PGM5 output, the system will
display a system trouble “8. SIREN FAULT”. In case the PGM5 is not used for siren connection it has to be terminated
with 1kOm resistance or programmed as general output at address 3051. See also the example below the description
of address 3011.
48
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 3000
PGM OPERATION 300
OPTION TEXT MENU 5. OUTPUTS – 1. PGM OPTION
PGM 04 in the ECLIPSE 8 control panel can be used as a general programmable output or for serial
connection to TP2000 radio transmitter. The serial link is realized with connection between the AC
terminal of the transmitter and PGM 04 at the control panel.
PGM 04 in the ECLIPSE 32 control panel can be used as a general programmable output or for two-
wire connecting of fire detectors using B24 fire base.
ADDRESS 3010
PGM 01 OPERATION 310 + 01
ATTACH TEXT MENU 5. OUTPUTS – 2. PGMs – 01. PGM – 1. ATTACH
49
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Example 1. At address 8020 (Device 02) to the control panel is enrolled a keyboard with one on
board PGM output. Choose a free PGM address in the system configuration, number 15 for
example, where to attach the keyboard PGM. Enter in the engineer programming menu, type
address 3150, enter in sequence number of device 02, and output number 01. The screen displays:
Example 2. At address 8100 (Device 10) to the control panel is enrolled a PGM expander with 8 on
board PGM outputs. Choose a free PGM output in the system configuration, number 20 for example,
where to attach the first output of the expander. Enter in the engineer programming menu, type
address 3200, enter in sequence number of device 10, and output number 01. The screen displays:
To use the second PGM output of the same expander you have to attach it to other free PGM
address in the system configuration – for example 21. Then at address 2210 you should enter in
sequence number of device 10 and output number 02. In analogical way, proceed with the other
PGM outputs of the expander to attach them to free PGM addresses in the system configuration.
The attached PGM outputs cannot be programmed for operation as a fire zone like PGM4.
ADDRESS 3011
PGM 01 OPERATION 311 + 01
OPTION TEXT MENU 5. OUTPUTS – 2. PGMs – 01. PGM – 2. OPTIONS
Pay attention that both of the option statuses are used – see the description of the options in the
table below. The option numbers 3, 4 and 5 are available only for ECLIPSE 32 control panel.
50
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
3 DELAY This option concerns the set value at ADDRESS 3019 – time delay for
sec / min* activation of PGM 01:
DELAY seconds () – the set time delay at address 3019 is measured in
seconds.
DELAY minutes (3) – the set time delay at address 3019 is measured in
minutes.
4 PULSED This option is available when the PGM 01 is set as a siren output.
FIRE
ENABLE When the option is enabled, the output operates in a specific working mode:
1 1 1 1 1 1
On
Off 3 3 Sec
For LED keyboards: The option status “” is performed with non-lighting zone number.
* NOTE: The option is not applicable when the PGM is programmed as Siren output.
By default PGM 05 is programmed as a siren output – at address 3051 is set “1”. If after the initial power-up of
the control panel, no siren is connected to PGM 05 output, the system will display a trouble message “8.
SIREN FAULT”. In case the PGM 05 will be used as a general output, the setting at address 3051 must be
programmed as “”. You can leave the set by default option, but to void the displayed trouble message in that case
terminate the PGM 05 output with 1kOm resistance – you can find one in the supplied spare parts kit.
51
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 3012
PGM 01 OPERATION 312 + 01
AREAS TEXT MENU 5. OUTPUTS – 2. PGMs – 01. PGM – 3. AREAS
According the system configuration the engineer associates one or several AREA numbers for
operation with PGM 01. To select an AREA press the digit button corresponding to its number. The
next pressing of the same button will deselect the AREA.
To select all areas press button “0” – the button alternatively switches over all enabled / all disabled
state.
At ADDRESSES 3013, 3014 and 3015 is set a number of an activation event for PGM 01 output and supplementary
parameters depending on the set event – for zones, areas, users, troubles or other special ones.
The programmed activation events make sense when the PGM 01 output is programmed as general output – at
ADDRESS 3011 is set “” – see the description of the option above.
ADDRESS 3013
PGM 01 OPERATION 313 + 01
ACT TEXT MENU 5. OUTPUTS – 2. PGMs – 01. PGM – 4. ACTIVATION
Choose a number of an activation event according the Table 1. Use the digit buttons to enter the
event number. Press the ENTER to confirm.
The default content of the next two addresses (3014 and 3015) depends on the set number at this
address.
ADDRESS 3014
PGM 01 OPERATION 314 + 01
PARAM 1 TEXT MENU 5. OUTPUTS – 2. PGMs – 01. PGM – 5. PARAM 1
The type of Parameters 1 depends on the set activation event at ADDRESS 3013 – see Table 1 for
details.
ADDRESS 3015
PGM 01 OPERATION 315 + 01
PARAM 2 TEXT MENU 5. OUTPUTS – 2. PGMs – 01. PGM – 6. PARAM 2
The type of Parameters 2 depends on the set activation event at ADDRESS 3013 – see Table 1 for
details.
Default setting: 0
52
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 3017
PGM 01 OPERATION 317 + 01
DEACT. TM TEXT MENU 5. OUTPUTS – 2. PGMs – 01. PGM – 7. DEACT TIMER
Deactivation timer for PGM 01 – setting a time for deactivation the event programmed at
address 3013
A deactivation timer for the programmed at ADDRESS 3013 event is set at this address. The state
of PGM 01 will restore after the set time is over. The engineer enters time in range 000 – 255 as the
time unit (seconds or minutes) depends on the settings at ADDRESS 3011, option 5. By default, the
programmed time unit is in seconds.
ADDRESS 3019
PGM 01 OPERATION 319 + 01
DELAY TEXT MENU 5. OUTPUTS – 2. PGMs – 01. PGM – 8. DELAY
53
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Enter the number of user code Enter the number of user code to
Valid User Code Enter
to start “FROM”. end “TO”.
Activated on “OR” function (when a valid
36 To set a single user code, enter 00 at the address for
user code is entered the PGM is activated)
PARAMETERS 2.
Deactivation on time - 5 sec. To set all possible user codes, enter 00 for both addresses
PARAMETERS 1 and PARAMETERS 2.
Ambush Code Enter Enter the number of user code Enter the number of user code to
to start “FROM”. end “TO”.
37 Activated on “OR” function (when an To set a single user code, enter 00 at the address for
ambush code is entered the PGM is PARAMETERS 2.
activated) To set all possible user codes, enter 00 for both addresses
54
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
55
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
area.
Deactivation on time - 5 sec.
Time slot activation
Enter a time slot number from
62 Follows the activation of the respective time -
1 to 8.
slot number.
63 Not used
Remote control
Activation and deactivation (restore) of the
64 - -
PGM output over communication module
(AJAX, VD/DTMF, ARGUS, etc).
65 Not used
66 Alarm or entry time - -
67-72 Not used - -
56
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
4. Areas
In “AREAS” menu, the engineer programs some parameters and settings for the areas in the system.
Some of the addresses are available for programming only with LCD keyboard!
Attention: In ECLIPSE 8 control panel is available only one area in the system - AREA 01.
57
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 4000
A ACCOUNT OPERATION 400
LENGTH TEXT MENU 6. PARTITIONS – 1. ACCOUNT LENGTH
An account number digit length is assigned at this address. The digit length can be 4 or 6-digit.
Every pressing of a random button or arrows changed alternatively the parameter.
When switching from 4- to 6-digits account numbers, the digits 00 will automatically be added at the
end. For example, the 4-digits number 1234 will become 123400.
When changing over from 6- to 4-digits numbers, only the first four figures in the 4-digits
number will remain valid. For example, the 6-digits number 123456 will become 1234. Due to
risk of coincidence of account numbers, changing over from 6- to 4-digits numbers IS NOT
RECOMMENDED!
ADDRESS 4001
A DOUBLE OPERATION 401
KNOCK TEXT MENU 6. PARTITIONS – 2. DOUBLE KNOCK
The engineer assigns a time interval from 1 to 5-minute at this address. The time interval starts
running when a detector in the zone is activated for the first time when the system is armed. An
alarm event is registered if second detector activation is recorded within this interval in the same or
another zone.
An alarm event will also be registered if no zone is restored within 15 seconds of the first activation
of the zone.
ADDRESS 4002
ARM ON NO OPERATION 402
MOVE TEXT MENU 6. PARTITIONS – 3. NO MOV ALARM
Setting a time for automatic arming of the area on no moving activity in the zones
The Engineer sets a time for automatic arming of the area when there is no moving activity in all
associated to that area zones. The time is common for all areas in the system. The automated
arming is enabled on the respective area address 4xx5 (option 5), where “xx” is the area number
from 1 to 8.
Enter a time from 001 to 255 minutes. The set 000 value disables the automatic arming of the area.
Pay attention that the automatic arming will start if there is a set time at the address and after all
zones in the respective area are closed. Check also the set options at address 4xx5 (option 5 is
enabled) for the respective area.
58
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 4003
POSTPONE OPERATION 403
AA TEXT MENU 6. PARTITIONS – 4. POSTPONE TIME
If at the time of arming, the area is not ready to be armed, the automatic arming procedure will be
delayed until the area is ready to be armed, and will be armed in the next 1 minute.
ADDRESS 4010
AREA 1 OPERATION 410 + 01
EXIT TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 01. EXIT TIME
Exit time is assigned to Entry/Exit type zones associated to Area 1. A 3-digit number between 000
and 255 seconds is entered. For an interval of time, less than 10 seconds, the first two digits must
be 0.
In case of command for arming of two or more areas, with a common Entry/Exit type zone then
every area will be armed only when its own set exit time is over. The common zone will be bypassed
in the already armed areas until and the last one area is armed. For example, the Zone 01 is
associated to all areas in the system, and when the seven of them are armed the Zone 01 will be
bypassed until and the last area 8 is armed too.
ADDRESS 4011
AREA 1 OPERATION 411 + 01
ENTRY TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 02. ENTRY TIME
Entry time is assigned to Entry/Exit type zones associated to Area 1. A 3-digit number between 000
and 255 seconds is entered. For an interval of time, less than 10 seconds, the first two digits must
be 0.
When during running of entry time after opening of Entry/ Exit type zone associated to more than
one area in the system, a valid user code associated to at least one of those areas is entered
following the area number for disarming, then this area will be disarmed and the other areas (which
numbers are not entered for disarming) will stay armed. The common Entry/ Exit type zone will be
bypassed in the left armed areas.
When one of the armed areas is in alarm mode and a valid code associated to other area is entered
(but both areas have a common zone) the siren stops (if it is associated to the same area) and the
alarm cycle continues as set. Then an alarm message is sent to the monitoring station, and the
event is recorded in the LOG file. An alarm event is generated when the entry time is over
regardless that the violated zone is restored or not.
59
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 4012
AREA 1 OPERATION 412 + 01
CYCLE TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 03. ALARM CYCLE
Duration of the alarm cycle is set for the programmable siren type outputs associated to Area 1.
A 3-digit number between 000 and 255 minutes is assigned at the address. For an interval of time,
less than 10 minutes, the first two digits must be 0.
Entering of valid user code ends the alarm cycle and restores the siren type outputs.
ADDRESS 4013
AREA 1 OPERATION 413 + 01
ACCOUNT TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 04. ACCOUNT
Programming of account number for communication with monitoring station for Area 1
The engineer enters 4 or 6-digit symbols according to the settings of ADDRESS 4000. The valid
symbols include digits from 0 to 9 and letters from A to E. Entering of letter “F” in the code
combination means cancelation of the communication.
For letters entry the engineer uses the following button combinations:
ADDRESS 4014
AREA 1 OPERATION 414 + 01
ATTR 1 TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 05. BELL OPTIONS
The Bell attributes for Area 1 are programmed at this address. Every attribute is activated with
pressing of a digit button with a respective number (from 1 to 5).
Next pressing of the same button number will deactivate the attribute. At end of the procedure, at
the keyboard’s display must be active only the numbers of the assigned attributes.
Pay attention that for attribute “5. Fire alarm duration” both of the attribute statuses are used – see
the description of the attribute in the table below. The attribute numbers 3 and 4 are available only
for ECLIPSE 32 control panel.
60
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 4015
AREA 1 OPERATION 415 + 01
ATTR 2 TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 06. ON/OFF OPTIONS
Pay attention that both of the attribute statuses are used – see their description in the table below.
The attribute numbers 1, 2 and 5 are available only for ECLIPSE 32 control panel.
61
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 4016
AREA 1 OPERATION 416 + 01
PANICS TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 07. PANICS
Silent panic (panics “2. Silent Police” and “4. Silent Medical” are set at this address) – only the
programmable Panic types outputs and the digital communicator are activated. There is no
indication for memory event. After entering of valid user code, the MEMORY LED lights on together
with the number of the activated zone.
Audible panic (panics “1. Enabled Police panic”, “3. Enabled Medical panic” and “5. Enabled Fire
panic” are set at this address) – the programmable Siren and Panic outputs and the digital
communicator are activated. The sirens are activated immediately with no time delay.
62
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
The following special cases are possible when a keyboard is used for sending of panic alarms:
1. In case of several panics are sent at the same time just the last one will be displayed.
st
2. When there are 3 keyboards in the system and the configuration is: the 1 keyboard is associated to Area
nd rd
1, the 2 keyboard is associated to Area 2, and the 3 keyboard is associated to both Areas 1 and 2, then in
rd
case of panics sent the keyboards 1 and 2 will display the panics only in their own areas, and the 3
rd
keyboard will display the both panics. In case the panic is sent from the 3 keyboard then the other two
keyboards will display the panic alarm.
ADDRESS 4017
AREA 1 OPERATION 417 + 01
NAME TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 08. NAME
ADDRESS 4018
AREA 1 OPERATION 418 + 01
BDELAY TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 09. BELL DELAY
ADDRESS 4019
AREA 1 OPERATION 419 + 01
TSLOT TEXT MENU 6. PARTITIONS – 5. AREAS – 1. AREA – 10. TIMESLOT
Pay attention that when you set time slot number at this address, the Area arming is automatic for
the time slot duration. If at the time slot start time there are open zones in the area the control panel
will wait for zones’ restoration (to be ready for arming) and after that will perform automated arming
on the set time slot.
Default setting: 0
The Area numbers from 02 to 03 (Eclipse 16)/ 08 (Eclipse 32) are programmed analogically at the respective
addresses.
63
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
5. Timeslots
The “TIMESLOTS” menu is available only for ECLIPSE 32 control panel.
The term Time Slot is used to represent a set of functions related to time intervals. A time slot is used to automate
operations fixed in time, which are periodically repeated by the security system. Such operations can be: managing
programmable input (e.g. managing door access); turning on lights; automatic arming or disarming security; restricting
user code access; automatic setting up of temporary passage routes in secured site.
ECLIPSE 32 can organize time slots to help solve tasks related to automation of periodically recurring operations. 8
time slots can be organized according the system configuration. The engineer sets start and end time of the time slot,
days and holidays included, etc. The programming of holidays and nonworking days is organized at additional
addresses, as for every month four separate addresses are provided.
5 0 8 0 Timeslot 8 Start
5 0 8 1 Timeslot 8 End
5 0 8 2 Timeslot 8 Days
5 0 8 3 Timeslot 8 Options
5 4 1 1 January: 1 – 8 dates
5 4 1 2 January: 9 – 16 dates
5 4 1 3 January: 17 – 24 dates
5 4 1 4 January: 25 – 31 dates
5 4 2 x February: dates
…
5 4 3 x March: dates
…
5 4 4 x April: dates
…
5 4 5 x May: dates
…
5 4 6 x June: dates
…
5 4 7 x July: dates
…
5 4 8 x August: dates
…
5 4 9 x September: dates
…
5 5 0 x October: dates
…
5 5 1 x November: dates
…
5 5 2 x December: dates
64
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 5010
T1 OPERATION 510 + 01
START TEXT MENU 7. SCHEDULES – 1. TIMESLOTS – 1. TIMESLOT – 1. START
The start time of Timeslot 1 is set at this address. The start time must be less than the stop time set
at address 5011. The engineer sets the start time in format [HH:MM].
The real arming on timeslot is realized 10 minutes after entered start time at this address. For
example, if the entered start time is 08:30h, at this time a sound signal will announce the running of
10 minutes time interval for leaving of protected premises from users, and the real arming of the
area or areas will be at 08.40h.
ADDRESS 5011
T1 OPERATION 511 + 01
END TEXT MENU 7. SCHEDULES – 1. TIMESLOTS – 1. TIMESLOT – 2.END
The stop time of Timeslot 1 is set at this address. The stop time must be greater than the start time
set at address 5010. The engineer sets the stop time in format [HH:MM].
If a user code has been set a timeslot from 8:30h to 17:00h, the respective user can use his code
within that specified time. From 17:00h to 0:00h and from 0:00h to 8:30h the respective code will
remain inactive.
ADDRESS 5012
T1 OPERATION 512 + 01
DAYS TEXT MENU 7. SCHEDULES – 1. TIMESLOTS – 1. TIMESLOT – 3.WEEK DAYS
The days of the week during which the timeslot 1 is to be used are set at this address.
The days of the week are selected with the digits buttons from 1 to 7. The selected days are
presented with a digit on the display or lighting on LED number – see the table below for
correspondence:
For example, if only Wednesday is set for the timeslot, the user code will only be valid on
Wednesday from 8:30 to 17:00h.
65
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 5013
T1 OPERATION 513 + 01
OPTIONS TEXT MENU 7. SCHEDULES – 1. TIMESLOTS – 1. TIMESLOT – 4.OPTIONS
Example:
At address 5010 is set start time 08.00h, and at the address 5011 – end time 17.00h.
When a Normal operation of the timeslot is set, the arming diagram is as follows:
Start End
When an Inverted operation of the timeslot is set, the arming diagram is as follows:
End Start
With the hatched area is shown the 10 minute time interval for leaving the protected area or areas
before arming the system on timeslot.
The settings of holidays and officially nonworking days are programmed at individual addresses, as for every month
four separate addresses are provided. The holidays and nonworking days are common for all Timeslot numbers. All
months are programmed analogically on different addresses – see the quick reference table at the beginning of this
section.
66
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
The address 5411 presents 8 different fields for the first eight days of January. Every field is editable
when the cursor is under it. The cursor can be moved with the arrows. In the square parentheses on
the right side of the screen, the engineer can see the editable date. To set a date as holiday move
the cursor under it and press button “0”. The selected holidays for the month are presented with “H”
capital letter. Pressing the button “0” once again will return the previous status.
Indication:
LCD: The workdays are displayed with “-” symbol. The holidays are displayed with “Н” symbol.
LED: The zone numbers corresponding to the days set for holidays are lighting on.
In the text menu structure the holidays and nonworking days are set after entry in 01. JANUARY
submenu. The holidays are selected with pressing button “0” – see also the description for operation
with text structure in item 1. GENERAL INFORMATION and APPENDIX 4.
The other days of January are set on the following address in an analogical way.
0 Define Holidays
[H-------]
_ [01]
67
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
6. Communication
The menus for communication devices programming are accessible only from the Engineer of the system (engineer
code 7777 by default).
ATTENTION: Due to differences in PSTNs provided in different countries and territories, Teletek
Electronics JSC cannot provide unconditional assurance of successful operations on every PSTN network
termination point. This may be subject to changes made to the communication facilities or procedures of
each individual telephone service provider. Additionally, Teletek Electronics JSC alarm equipment is
designed to work with traditional telephone line. Please, bear in mind that the use of alarm panels over
alternative telephone systems like VoIP (Voice over Internet Protocol) may not be as effective as with
traditional telephone line.
If you are experiencing problems with the use of a Teletek Electronics device over PSTN, please contact
us for further assistance.
68
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 6000
DIGITAL OPERATION 600
COMM TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 1. OPTIONS
69
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 6001
ATTEMPTS OPERATION 601
TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 2. ATTEMPTS
The Engineer sets the number of attempts to connect to the central station for telephone monitoring
and the number of repetitions of voice messages at the address. Use the digit numbers to enter a
value from 1 to 9. The value “0” disables the operation and the communicator will not dial a number.
The value assigned at this address is the number of attempts to be made for each of the telephones,
configured at addresses 60xx – “xx” is a number of a phone (01-04 for ECLIPSE 32 and 01-02 for
ECLIPSE 8/ 16).
If the assigned value is 4 and there are two telephone numbers set at addresses 6010 and 6020, the
number of attempts that will be made are 8 – by 4 attempts for each telephone number.
After the assigned number of attempts for communication is reached, the attempts to transmit voice
messages will be terminated. The attempts to transmit will be renewed to the central station first,
when the next transmission event occurs.
ADDRESS 6002
TEST OPERATION 602
PERIOD TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM– 3. TEST MESSAGES – 2. PERIOD
Duration of transmission of test message in hours (HHH) from 000 to 255 is entered.
Three digits must be entered. When entering a period shorter than 10 hours the first two digits must
be 0.
ADDRESS 6003
TEST OPERATION 603
HOUR TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 3. TEST MESSAGES – 1. TIME
At this address is set the first hour, at which the test message will start to be transmitted to central
monitoring station. Hours and minutes are entered (HH:MM), as the entered time is the time of
starting the first test.
The next test time will start after the assigned at ADDRESS 6002 test period.
ADDRESS 6004
TLM OPERATION 604
DELAY TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 4. FAULT DELAY
70
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 6010
PH1 OPERATION 610 +01
NUMBER TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 5. PHONES – 1. PHONE – 1. PHONE NUMBER
A Telephone 1 number is assigned for communicating with central station. The telephone number
must not exceed 32 characters. Some special functions can be entered by using the next button
combinations:
1. Buttons / + 0 - Switches on "pulse dialer". “P” letter is displayed on the screen.
2. Buttons / + 1 - Switches on "tone dialer". “T” letter is displayed on the screen.
3. Buttons / + 2 - 2 seconds pause. “D” letter is displayed on the screen.
4. Buttons / + 3 - Switches on "Wait dial tone". “” symbol is displayed on the screen.
5. Buttons / + 4 - "Blind dialing"; Switches off "Wait dial tone". “#” symbol is displayed on the
screen.
6. Buttons / + 5 - Deletes the entered telephone number.
Note: The button is used in the previous design of the keyboards and has the same
functionality.
ADDRESS 6011
PH1 OPERATION 611 + 01
PROTOCOL TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM– 5. PHONES – 1. PHONE – 2. PROTOCOL
The engineer sets the communication protocol type for Telephone 1 at the address. The supported
communication protocols are CID and SIA.
Every pressing of random key switches alternatively between the two protocols. Confirm you choice
with ENTER button.
ADDRESS 6012
PH1 OPERATION 612 + 01
MESSAGES TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM– 5. PHONES – 1. PHONE – 3. MESSAGES TYPE
At this address are assigned the one or more type of the messages which will be transmitted to a
central monitoring station in case of alarm condition through Telephone 1.
To the Telephone 1 can be programmed to be transmitted only chosen messages. In case the user
wants some messages to be transmitted and through telephone number 2 (3, 4 or all), then the
same chosen messages have to be assigned and at ADDRESS 6022 (6032, 6042). If it does not
matter through which of the telephone numbers the messages are sent, you have to leave the
ADDRESS 6022 (6032,6042) with its default programming (No messages are assigned).
The digit buttons 1 to 8 are used for programming. Pressing them each time will alternatively change
the status of the respective message type - report (active status of the parameter) or no report
(inactive status of the parameter). At the end of the procedure only those parameters, which
correspond to the designated for report messages, should remain activated on the display.
71
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 6013
PH1 OPERATION 613 + 01
AREAS TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 5. PHONES – 1. PHONE – 4. ATTACH
72
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 6100
VD OPERATION 670
OPTIONS TEXT MENU 8. Communication – 2. Voice Dialer – 1. VD Options
Indication:
LCD: In the text menus the option is enabled with pressing button “1” – a check mark appears in
front of the text.
LED: Press a digit button corresponding to the number of the option. The zone numbers
corresponding to the enabled options are lighting on.
ADDRESS 6101
VD OPERATION 671
MSG REP. TEXT MENU 8. Communication – 2. Voice Dialer – 2. VD Message Rep.
The Engineer sets the number for message repetition for the voice dialer in this address. Set a value
from 0 to 9. When setting value 0, the dialer will send the message for events occurrence without
repeating it; when the value 1 is set, the dialer will send the message for events occurrence and will
repeated it ones, and so on. The entered value is confirmed with ENTER button.
ADDRESS 6102
VD OPERATION 672
DIAL REP TEXT MENU 8. Communication – 2. Voice Dialer – 3. VD Dial Rep.
The Engineer sets the number of dialing attempts to the telephone numbers set at addresses 61x0,
where “x” is phone number, for the voice dialer. Use the digit numbers to enter a value from 1 to 9.
When setting the value 0, the dialer will make only one attempt to dial the set phone numbers; when
the set value is 1 – two attempts, and so on. The entered value is confirmed with ENTER button.
73
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 6103
VD OPERATION 673
LANGUAGE TEXT MENU 8. Communication – 2. Voice Dialer – 4. VD Language
ADDRESS 6110
VD PH1 OPERATION 680 +01
NUMBER TEXT MENU 8. Communication – 2. Voice Dialer – 5. VD Phones – 1. Phone – 1. Phone Number
The telephone number must not exceed 32 characters. Some special functions can be entered by
using the next button combinations:
1. Buttons / + 0 - Switches on "pulse dialer". “P” letter is displayed on the screen.
2. Buttons / + 1 - Switches on "tone dialer". “T” letter is displayed on the screen.
3. Buttons / + 2 - 2 seconds pause. “D” letter is displayed on the screen.
4. Buttons / + 3 - Switches on "Wait dial tone". “” symbol is displayed on the screen.
5. Buttons / + 4 - "Blind dialing"; Switches off "Wait dial tone". “#” symbol is displayed on the
screen.
6. Buttons / + 5 - Deletes the entered telephone number.
Note: The button is used in the previous design of the keyboards and has the same
functionality.
ADDRESS 6111
VD PH1 OPERATION 681 + 01
AREAS TEXT MENU 8. Communication – 2. Voice Dialer – 5. VD Phones – 1. Phone – 2. Attach
According the system configuration the engineer associates one or several AREA numbers for
operation with Telephone 1. To select an AREA press the digit button corresponding to its number.
The next pressing of the same button will deselect the AREA.
To select all areas press button “0” – the button alternatively switches over all enabled / all disabled
state.
Telephone numbers from 2 to 8 for the voice dialer are programmed in an analogical way.
74
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 6901
PC ID OPERATION 691
TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 6. UDL – 2. PC ID
The PC ID number for up / down loading is configured at this address. Four digits can be introduced.
Valid are symbols 0 to 9. The entered number is saved with pressing the ENTER button.
ADDRESS 6904
UDL OPERATION 694
OPTIONS TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 6. UDL – 5. OPTIONS
ADDRESS 6905
RINGS OPERATION 695
TEXT MENU 8. COMMUNICATION – 1. DIGITAL COMM – 6. UDL – 6. RINGS
Default setting: 04
75
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
8. Peripheral Devices
At ADDRESSES 8ххх are programmed the parameters and options for all enrolled devices to the control panel.
The first enrolled device at ADDRESS 8010 is always the main PCB and this cannot be changed. It is recommended
the second enrolled device at address 8020 to be a LCD keyboard for programming and settings.
The steps for enrolling of new devices to the control panel are listed in item “5. Enrolling of new devices”.
* The menus are accessible only for wireless expander module Eclipse WL. Address 8хх6 is accessible only from the
screen for entering an address number.
** The menus are accessible only for proximity card readers.
76
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 8010
DEV 01 OPERATION 810 + 01
ID TEXT MENU 9. DEVICES – 01. DEVICE [MAIN] – 1. ID
8010>DEV1_ID
[MAIN][XXXXXXXX]
ADDRESS 8011
DEV 01 OPERATION 811 + 01
AREAS TEXT MENU 9. DEVICES – 01. DEVICE [MAIN] – 2.AREAS
According the system configuration the engineer associates one or several AREA numbers for
operation with Device 01. To select an AREA press the digit button corresponding to its number.
The next pressing of the same button will deselect the AREA.
To select all areas press button “0” – the button alternatively switches over all enabled / all disabled
state.
ADDRESS 8013
DEV 01 OPERATION 813 + 01
RESOURCES TEXT MENU 9. DEVICES – 01. DEVICE [MAIN] – 4. RESOURCES
77
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
The following addresses are about the programming of DEVICE 02 – the first added to the system configuration. The
manufacturer recommends that to be a control keyboard.
ADDRESS 8020
DEV 02 OPERATION 810 + 02
ID TEXT MENU 9. DEVICES – 02. DEVICE [Name] – 1. ID
* Eclipse 8: Up to 2 devices can be enrolled to the system bus: 2 keyboards, 2 proxy readers or 1
keyboard and 1 proxy reader.
** Eclipse 16: Up to 5 devices can be enrolled to the system bus irrespective of their type.
*** Eclipse 32: Up to 30 devices can be enrolled to the system bus irrespective of their type.
NOTE: It is not necessary to enroll the built-in proximity reader in keyboards LED 32, LCD 32 and
LCD 32S.
All wireless devices must be enrolled to a wireless expander module, which is attached to the
system configuration.
The steps for enrolling devices to the control panel are described in item 5. Enrolling new devices.
You can also enter the unique ID number of the device directly with the digit buttons and letters:
Note: The button is used in the previous design of the keyboards and has the same
functionality.
To delete the device from the address press and hold the button “0” for 2-3 seconds.
78
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 8021
DEV 02 OPERATION 811 + 02
AREAS TEXT MENU 9. DEVICES – 02. DEVICE [Name] – 2.AREAS
Keyboards and modules: If all areas for a device are disabled the device becomes inactive,
irrespective there are any options programmed for it. If the device is a keyboard then it can perform
only engineer and maintenance programming, and the manager and user programming are disabled
as and the arming and disarming operations with it.
LED 8: The keyboard supports operation with one area only. If more than one area are set at this
address for LED8 keyboard, then only the area with the smallest number will be active.
LED 16A: The keyboard supports operation with three areas named А, В and С. If more than three
areas are set at this address for LED 16A keyboard, then only the three areas with the smallest
numbers will be active.
Proximity card readers: If all areas for the reader are disabled at this address, then the device will
operate only in MODE A and MODE B set at addresses 8xx7 and 8xx8.
You must consider the following important notes for Eclipse Series Keyboards, when design and organize the
security system including ECLIPSE panels!
Display Indication
Keyboard
type Area 1
LED 8 LED Icon No specific indication
LED 16A LED Icon A
LED 32 LED Icon A1
LCD 32 (S) LCD Text 1
Display Indication
Keyboard
type Area 1 Area 3 Area 3
LED 8* LED Icon One Area: No specific indication
LED 16A LED Icon A B C
LED 32 LED Icon A1 A2 A3
LCD 32 (S) LCD Text 1 2 3
Display Indication
Keyboard
type Area 1 Area 2 Area 3 Area 4 Area 5 Area 6 Area 7 Area 8
LED 8* LED Icon One Area: No specific indication
LED 16A** LED Icon Three Areas: A, B and C indication
LED 32 LED Icon A1 A2 A3 A4 A5 A6 A7 A8
LCD 32 (S) LCD Text 1 2 3 4 5 6 7 8
* Note: The area number is set at address 8xx3, where “xx” is the keyboard number in the system.
** Note: LED 16 A keyboard supports operation with three independent areas in the system. The area numbers are set at
address 8xx3, where “xx” is the keyboard number in the system. The areas are displayed as A, B and C where A is the area
with the smaller number, and C - the area with higher one. Note that there may not be direct correspondence between the
area number and the keyboard indication letter.
79
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 8022
DEV 02 OPERATION 812 + 02
OPTIONS TEXT MENU 9. DEVICES – 02. DEVICE [Name] – 3. OPTIONS
The options from 1 to 4 can be programmed only for the connected to the system bus keyboards
irrespective of their type.
The option 1 can be programmed for the connected to the system bus proximity card readers.
The options must be programmed for every device separately at the respective address.
The options are not supported for devices type MAIN, ZEXP, PEXP and WEXP.
* When the option is enabled, the keyboard will enter in confidential mode irrespective of the current
system status (Armed or Disarmed). The confidential mode is inactive when the system is in
programming mode (user, manager or engineer).
80
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 8023
DEV 02 OPERATION 813 + 02
RESOURCES TEXT MENU 9. DEVICES – 02. DEVICE [NAME] – 4. RECOURSES
Default setting: according the type of the device and the used connection style
ADDRESS 8024
DEV 02 OPERATION 814 + 02
COMM TEXT MENU 9. DEVICES – 02. DEVICE [NAME] – 5. COMM QUALITY
The following address are available for programming of Eclipse WL wireless expander only (XX is a number of device
from 02 to 31). Up to one wireless expander can be connected to Eclipse 16/ 32 control panel.
You can find detailed information for installation and operation with Eclipse WL wireless expander in “Installation and
programming manual for Eclipse WL”.
ADDRESS 8хх5
WL Device OPERATION 815 + хх
[XX] TEXT MENU 9. Devices – хх. DEVICE [WEXP] – 8. WL Device
After entering at the address the installer has to enter number of a device using the digit buttons of
the keyboard and to confirm with pressing ENTER button. If the device number is free: the screen of
LCD keyboard displays “FREE [________]”; when using LED 32 keyboard – zone numbers from 1
to 16 are lighting on; when using LED 8/ 16A keyboard – the button “0” is lighting on.
To enroll a wireless device, dismount its cover and remove the protection folio from the battery. At
the free position for a wireless device, press the ENTER button of the keyboard and while the
message “Searching…” is displayed press the ENROLL button of the wireless device. If the
enrollment is successful, the type of the device is displayed on the screen with the unique ID code.
The next pressing of ENTER button of the keyboard will move back to the screen for entering
number of a new device.
After the enrollment to the wireless expander, the devices PIR, MC, FD, FL and SR type must to be
attached to a free zone numbers of the panel – see the examples after description of address 2010,
as the sirens SR must be attached and also to a free PGM number with “Siren” option set – see
description of address 3010.
81
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
This address is accessible for entering only from the main screen in ENGINEER
PROGRAMMING MENU.
After entering at the address the installer has to enter number of a remote key fob using the digit
buttons of the keyboard and to confirm with pressing ENTER button. If the number is free: the
screen of LCD keyboard displays “FREE [________]”; when using LED 32 keyboard – zone
numbers from 1 to 16 are lighting on; when using LED 8/ 16A keyboard – the button “0” is lighting
on.
To enroll a remote key fob, dismount its cover and remove the protection folio from the battery. At
the free position for a remote key fob, press the ENTER button of the keyboard and while the
message “Searching…” is displayed press a random button of the remote key fob. If the enrollment
is successful, the type of the device is displayed on the screen with the unique ID code. The next
pressing of ENTER button of the keyboard will move back to the screen for entering number of a
new remote key fob.
The enrolled remote key fobs are automatically attached to the corresponding User numbers in the
system - RC1 to User 1, RC2 to User 2 and so on.
The following menus are available for proximity cards readers only (XX is a number of device from 02 to 31).
ADDRESS 8xx7
DEV XX OPERATION 817 + xx
ARM MODE A TEXT MENU 9. DEVICES – 02. DEVICE [PRX] – 6. ARM MODE A
Indication:
LCD: The respective letter for the chosen operation for the area is displayed on the screen.
LED: After entering the address, the system shows the set type for the Area 1. Use the arrow buttons
to review the set types for the other Areas. To change the arming type, press the button
corresponding to the respective operation. Every pressing of a button sets the new arming type and
moves on to the next area number.
82
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
ADDRESS 8xx8
DEV XX OPERATION 818 + xx
ARM MODE B TEXT MENU 9. DEVICES – 02. DEVICE [PRX] – 7. ARM MODE B
APPENDIX
APPENDIX 1. Memory LOG Events
LED Event System Zone/ CID SIA
Code Description
Indication number Event (LOG) User Code Code
1 1 Burglary Alarm event Z## Alarm Zone No/ name 1 13A BA
2 2 Burglary Alarm event restore Z## Alarm R Zone No/ name 3 13A BH
3 3 Fire Alarm event Z## Fire Zone No/ name 1 11A FA
4 4 Fire Alarm event restore Z## Fire R Zone No/ name 3 11A FH
5 5 Panic Alarm event Z## Panic Zone No/ name 1 12A PA
6 6 Panic Alarm event restore Z## Panic R Zone No/ name 3 12A PR
7 7 Tamper Alarm event Z## Tamper Zone No/ name 1 137 TA
8 8 Tamper Alarm event restore Z## Tamper R Zone No/ name 3 137 TR
9 9 Medical Alarm event Z## Medical Zone No/ name 1 1AA MA
10 10 Medical Alarm event restore Z## Medical R Zone No/ name 3 1AA MR
Activated zone with „24h
11 11
Burglary" AUX attribute
Z## 24h Alarm Zone No/ name 1 13A BA
Restored zone with „24h
12 12
Burglary" AUX attribute
Z## 24h Alarm R Zone No/ name 3 13A BH
Activated zone with AUX „AC
13 13
Loss" attribute
Z## AC Loss Zone No 1 3A1 AT
Restored zone with AUX „AC
14 14
Loss" attribute
Z## AC Restore Zone No 3 3A1 AR
Activated zone with AUX
15 15
„Battery Low" attribute
Z## Batt Low Zone No 1 3A2 YT
Restored zone with AUX
16 16
„Battery Low" attribute
Z## Batt Restore Zone No 3 3A2 YR
Activated zone with AUX „Water
17 17
leakage" attribute
Z## Water leak Zone No 1 154 WA
Restored zone with AUX „Water
18 18
leakage" attribute
Z## Water leak R Zone No 3 154 WR
Activated zone with AUX „GAS
19 19
Detector" attribute
Z## Gas Zone No 1 151 GA
Restored zone with AUX „GAS
20 20
Detector" attribute
Z## Gas R Zone No 3 151 GR
Activated zone with AUX „GSM
21 21
Link Trouble" attribute
Z## GSM Link Zone No 1 354 YS
Restored zone with AUX „GSM
22 22
Link Trouble" attribute
Z## GSM Link R Zone No 3 354 YK
Activated zone with AUX „GAS
23 23
Trouble" attribute
Z## Gas Trbl Zone No 1 157 GT
Restored zone with AUX „GAS
24 24
Trouble" attribute
Z## Gas Trbl R Zone No 3 157 GR
Activated zone with AUX „High
25 25
temperature" attribute
Z## High Temp Zone No 1 158 KA
Restored zone with AUX „High
26 26
temperature" attribute
Z## High Temp R Zone No 3 158 KR
Activated zone with AUX „Low
27 27
temp" attribute
Z## Low Temp Zone No 1 159 ZA
Restored zone with AUX „Low
28 28
temp" attribute
Z## Low Temp R Zone No 3 159 ZR
Activated zone with AUX „Loss
29 29
of heat" attribute
Z## Heat Loss Zone No 1 153 ZA
83
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
84
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
80 2-wire fire line fault (PGM1) Fire line Flt - 1 373 FT
2-wire fire line fault restored Fire line Rstr - 3 373 FJ
81
(PGM1)
82 Fuse blown out Fuse Blow - 1 3AA YP
83 Fuse restore Fuse Restore - 3 3AA YQ
84 Telephone line loss TLM trouble - 1 351 LT
85 Telephone line restore TLM restore - 3 351 LR
86 System power up Power UP - 1 3A8 RR
87 System reset Reset - 1 3A5 YW
88 Time change Time Changed - 3 625 JT
89 Communication error for report Report Error - 1 354 YC
to monitoring station
90 Report to monitoring station Report Restore - 3 354 YK
restore
91 Periphery device loss D## Absent Device No/ name 1 333 ET
92 Periphery device restore D## Restore Device No/ name 3 333 ER
93 Tamper form periphery device D## Tamper Device No/ name 1 145 TA
94 Tamper form periphery device D## Tamper R Device No/ name 3 145 TR
restore
95 Arming on “no movement” failure A## Failed AutoArm Area No - -
96 User Code Changed U## Code Changed User No/ name - JV
97 Invalid date and time Invalid clock - 1 626 JT
98 Clearing the log from user U# #Memory Clear User No/ name - -
Arming without reviewing the
99
current system troubles
U# #OverrideARM User No/ name - -
Low battery charge of wireless
100
device
WLDev##Batt Low WL Dev. No/ name 1 384 XT
Low battery charge of wireless
101
device Restore
WLDev##Batt OK WL Dev. No/ name 3 384 XR
102 Lost battery of wireless device WLDev##Batt Lost WL Dev. No/ name 1 381 US
103 Wireless device Restored WLDev##Restore WL Dev. No/ name 3 381 UR
Dirty smoke chamber of wireless
104
fire alarm detector
WLDev##Clear Fire WL Dev. No/ name 1 616 AS
Dirty smoke chamber of wireless
105
fire alarm detector Restored
WLDev##Fire Rest WL Dev. No/ name 3 616 AN
Radio frequency jamming of
106
wireless expander
WLExp RF Jamming Device No/ name 1 344 XQ
Radio frequency jamming of
107
wireless expander Restored
WLExp RF Jam Rest Device No/ name 3 344 XH
Loss of main power supply of
108
device
D## AcLost Device No/ name 1 342 ET
Loss of main power supply of
109
device Restore
D## Ac Restore Device No/ name 3 342 ER
Problem with battery of wireless
110
device
WLDev##Batt Trbl WL Dev. No/ name 1 338 ET
Problem with battery of wireless
111
device Restore
WLDev##Batt Rest WL Dev. No/ name 3 338 ER
112 Blown up fuse of device D## Fuse Blown Device No/ name 1 337 ET
113 Blown up fuse of device Restore D## Fuse Rest Device No/ name 3 337 ER
114 Forced Arming PreventARM - - -
85
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
86
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
If during 40 seconds time interval there is no action – pressed button, the system will break up the line.
87
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
2. WALK TEST
3. PGM TEST
4. COMMTEST
5. SW REVISION
88
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
89
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
64. USER
2. AREAS AREA 1
AREA 2
….
2. ENGINEER 1. ENG1 CODE AREA 8
3. NAME
2. ENG2 CODE
NOTE!
Use buttons:
To the 4. INPUTS Menus
to DISABLE
to ENABLE
5. TIMESLOT [1-8; 0]
90
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
3. AREAS AREA 1
AREA 2
….
4. OPTIONS 1 5. OPTIONS 2 AREA 8
Auto Bypass Bell Delay
Bypass Fire Delay
Stay ARM Report Only
Sleep ARM Video on Armed 4. OPTIONS 1 Choose options NOTE!
Force ARM Write to LOG Use buttons:
Double Knock Chime
E / E Final Pulse Count to DISABLE
Sens. Fast 64ms Power Up Delay 5. OPTIONS 2 Choose options
to ENABLE
91
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
3. AREAS AREA 1
AREA 2
….
AREA 8
NOTE! 4. ACTIVATION
Use button: AREA ARM 4. ACTIVATION Choose an option
ALARM IN AREA
to ENABLE PANIC IN AREA
VALID CODE ENTER 5. PARAMETER 1 Choose Parameter 1,
AMBUSH CODE according the
BLOCKED KBD activation event.
VALID PROXY
INVALID PROXY
VALID RC
SYSTEM FAULT 6. PARAMETER 2 Choose Parameter 2,
ENG. MENU ENTRY
according the
CHIME EVENT
activation event.
VIDEO ON ARMED
FIRE RESET
TIMESLOT
REMOTE CONTROL
7. DEACT. TIMER 000-255sec; 000
REMOTE ACCESS
UNUSED
ZONE OPEN
To the 6. PARTITIONS Menu ZONE BYPASS
ZONE TAMPER 8. DELAY 000-255sec; 000
ZONE IN ALARM
ZONE IN FIRE
ZONE IN MEDICAL
92
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
8. AREA
03. ALARM CYCLE [0-255 min; 001]
E
04. ACCOUNT [FFFF]
05. BELL OPTIONS 06. ON/OFF OPTIONS
ARM SQUAWK TIMESLOT DISARM E
DISARM SQUAWK AUTO STAY ARM
RING BACK SQUAWK DISARM CLR BRS 05. BELL OPTIONS [Choose options
10 MIN WARNING QUICK ARM
FIRE ALARM DUR. ARM on NO MOVE E
06. ON/OFF OPTIONS [Choose options
07. PANICS NOTE! E
POLICE Use buttons:
SILENT POLICE 07. PANICS [Choose options
MEDICAL to DISABLE
SILENT MEDICAL to ENABLE E
FIRE 08. NAME
E
09. BELL DELAY [0-255 sec; 000]
E
10. TIMESLOT [1-8; 0]
93
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
Note: The menus are available only for ECLIPSE 32 control panel.
2. END [23:59]
8. TIMESLOT
3. WEEK DAYS MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
4. OPTIONS HOLIDAYS
INVERT OPERATION
NOTE!
Use buttons:
12. DECEMBER DAY 01
.... to DISABLE
DAY 31
to ENABLE
94
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
2. ATTEMPTS [0-9; 4]
NOTE!
Use buttons: 3. TEST MESSAGES 1. TIME [00:05]
to DISABLE
to ENABLE 2. PERIOD [000-255hours; 024]
6. UDL 2. PC ID [1234]
PHONE
3. OPTIONS ANS.MACHINE
2. VD Voice Dialer 1. VD Options VD Report
VD Manage
PHONE
95
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
2. AREAS AREA 1
AREA 2
….
AREA 8
31. DEVICE [NAME]
3. OPTIONS CHIME
HIDE ZONE INFO In the menus are set combinations of operation in the
CONFIDENTIAL areas – arming type and/ or disarming for every area.
CONF EXIT Use the buttons to set the respective operation:
4. RESOURCES
96
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
97
Eclipse 8/ 32 Series - Engineer Programming Manual
230V/0.63A
17V/
23VA
230V/0.63A
98
Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
99
www.teletek-electronics.com