Ventilation Calculation Report
Ventilation Calculation Report
VENTILATION REPORT
In this scenario a steady fire is considered. For analysis of the vent system the maximum
anticipated fire power needs to be found.
Goal - Develop a vent design for the subject building that will maintain a tenable
environment for a period of time at least equal to the time required to evacuate the building
and equal to the time required to maintain the hot upper layer a minimum of 3 meters above
floor level until the local fire department enters the building.
Objective - Determine the vent area required to maintain the smoke layer at least 3
meters above floor level. And also limit the heat flux at floor level to a maximum of 4 kW/m²,
the threshold irradiance that causes severe pain to exposed skin, during the time required or
evacuation of the building occupants.
Q = 5,270 Kw
Predicted fire diameter, D can be thought as the diameter of a circle having the same area
as the floor area of the fuel concentration.
Thus: D = 2 (A/∏)^½
A = Fuel Area
D = 2(20/∏)^½
D = 5 meters
The mean height of the flame, L can be calculated using the above data as follows.
L = 1.14 meters
The mean height of the flame is greater than ceiling height. So the flame will impinge on the
ceiling and flow radially outward.
Case 1: Clear height = 3 meters
Assuming the convective heat flow, Qc is only 70% of the total heat flow, mass flow rate can
be calculated as follows where, L ˃ Zs (2.5m)
ṁp = (0.0056Qc)Zs/L
Zs = height above the base of the fire, m (Base of fire is assumed to be 0.5m)
ṁp = 29.72 kg/s
Temperature rise in the smoke layer can be estimated using the following equation.
ΔT = KQc/Cp ṁp
K = fraction of converted energy contained in the smoke layer gases (=0.5, unless an
analysis acceptable to AHJ is provided to validate the use of an alternative value.)
Thus,
ΔT = 62
T = 62 + 297
T = 359 K
At this temperature radiant flux at the floor level can be calculated from the below equation.
Flux = kεфT^4
Where;
ε = emissivity = 1
ф = configuration factor = 1
Thu Flux,
Flux = 1 KW/m²
This will produce unacceptable levels of radiant flux at the floor and there is a risk where fire
can flash over the combustibles under the smoke layer. Further at this temperature
unprotected steel begins losing strength.
Sizing of Vents
This arrangement will not meet objectives. Although the vent sizing calculation will be carried
out as this design will be common to other alternatives designs.
The aerodynamic vent area Ava can be calculated from the below equation.
At steady state mass flow though vents is equal to the smoke production rate. ṁp
ṁv = ṁp = 29.72 kg/s
po = 1.2 kg/m³
g = 9.81 m/s²
To = 297 K
ΔT = 62
T = 359 K
d = 4.5 meters
thus,
Ava = 7 m²
The vent area assumed to have a discharge coefficient of 0.61; thus the corresponding
actual vent area.
M = 1 + ½
²
M = 1 + ½
. ²
M = 2.60
The ventilation of the fire pump room will be provided by separate fans one smoke
extraction and one for makeup fresh air as shown in the plan. The extraction and make up
fresh air shall be directly to and from out of the building as per fire safety standard.
Parameters:
Calculation:
Calculation: