Boq - Scrubber
Boq - Scrubber
shall have minimum efficiency of pump shall be 50%. Pump shall be with
PN-16 ratings. The scope also shall include following.
a Set of suitable size Triple duty valve & End suction guide for each pump
b 19mm thick polyvinyl nitrile rubber insulation duly cladded between
aluminium sheets of 0.5mm thickness and properly clamped to pump.
c 2 Nos. - 150 mm dia dial type pressure gauges
d Mounting frame with antivibration pads ( In case pumps are inline, anti
vibration system shall be as per Manufacturers recommendation)
e RCC/cement concrete foundation for the pump unit. ( In case pumps are
inline, foundation shall be as per Manufacturers recommendation)
2.1 Capacity unit not less than 230 LPM of water at 15 mtr head. 2 Nos.
3 Air Handling units (AHUs)
Supply, Installation, Testing and commissioning of factory built floor
mounted chilled water double skin type horizontal/vertical air handling units
made of 25mm thick panels consisting of pre plasticized G.I. casing of
thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane
foam (PUF) insulation factory injected between them by injection moulding
machine, complete with blower section with blower suitable for static
pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil
section with aluminium finned copper tubes (tubes thickness not less than
0.5mm) cooling coil of Six row deep, filter section with 50mm thick metal
viscous/ washable synthetic type air prefilters (EU4, more than 90%
efficiency for 10 Microns) & fine (Bag filter EU7 3 Microns), belt drive
package with TEFC drive motor of efficiency class IE3 suitable for 415 ±
10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe
Capacity (CFM)
3.1 FM AHU
3.1.1 6500 1 Set
3.1.2 3500 1 Set
3.1.3 3000 1 Set
3.1.4 3200 1 Set
3.1.5 6000 1 Set
3.2 C/S AHU
3.2.1 1200 2 Set
3.2.2 3000 1 Set
3.2.3 1500 1 Set
3.2.4 4000 1 Set
3.2.5 2500 1 Set
3.2.6 6000 2 Set
3.3 In addition to above HEPA filter (H 13) section shall also be provided as
part of C/S AHU with HEPA
3.3.1 1200 1 Set
3.3.2 3000 1 Set
3.4 In addition to above HEPA filter (H 13) section shall also be provided
as part of FM AHU with HEPA
3.4.1 1500 1 Set
3.5 In addition to above HEPA filter (H 13) in supply section and Exhaust
section with exhaust fan having only pre filters shall also be provided as
part of OT FM AHU. The unit shall be in two tier ( Supply section / return
section - one above the other). The scope shall include 2 row deep reheat
coil & 6KW pantype humidifier. The scope shall include 3 way controle
valve & humidistat for operating reheat coil & wiring complete as required.
6.2 Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer
for chilled / hot water circulation including insulation as specified.
8.1 50 mmdia. 5 RM
8.2 40 mmdia. 25 RM
8.3 32 mmdia. 35 RM
8.4 25mmdia 125 RM
13 Supply and fixing of acoustic lining of supply air duct and plenum with 25
mm thick resin bonded glass wool having density of 32kg/m³, with 25 mm X
25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered
with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum
40 Sq.m
sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick
pins, CPRX compound etc. complete as required and as per specifications.
14 Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with
50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction
fixed in 610mm x 610 mm frame work made of 25X50X50X50X25 mm 210 Sqm
made out of
0.6mm thick GI sheet U shaped channel and covered with reinforced fiber
glass tissue and finished with 0.80 mm perforated aluminiumsheet etc.
complete as required and as per specifications. AHU room ( 6 x 4 x 3.5
walls)
16 Supplying & fixing of powder coated extruded aluminium Supply Air Grills
with aluminium volume control dampers as per specifications. 20 Sqm
23 Scrubber
Supply, Installation, Testing and commissioning of Dry scrubber for kitchen
exhaust consisting of Electrostatic Precipitator, backward curve SISW
centrifugal fan with elongated shaft having bearing & drive package out of
exhaust air stream, TEFC induction motor, common channel base frame for
Fan and motor, vibration isolation arrangement by means of spring type
vibration isolators or turret mounts, fire retardent flexible canvass
connections made out of canvass sleeve and the scope includes unit
mounted stater panel in enclosure.
The Electrostatic section shall be 90-95% in single pass as per DOP test
method. Electrostatic Precipitator should be able to charge particles from
0.01 micron to 10 micron through solid state power supply. Collector cell
shall be of permanent type and slide out facility for easy removal for
cleaning. Operating voltage shall be 220+6 % volts, 50 Hz/1Ph, power
consumption shall not exceeding 50 watts per unit upto 7500 Cfm. System
should be fitted with interlock switch for safety. Velocity across the air
cleaner shall not be more than 500 FPM. Scrubber shall be provided with
pre-filters as required, pressure drop across ESP with pre filter should not
be more than 12mm of Water gauge, .ESPs shall be provided with UV &
Ozone Odours removers. ESP Modules shall have necessary provision in
terms of flanges to facilitate Ducts/Plenum connections. The scope shall
include required electrical panel. The Scrubber shall be of following
capacity.
24 Supply, installation, testing and commissioning of synthetic fill pad type air
washer at 500 FPM velocity across pads, DIDW Class-I Backward curved
centrifugal fan with TEFC weather proof motor (IE3 efficiency) of IP:55
protection suitable for 415 +10% Volts, 3 phase, 50 cycles power supply,
mounted on a common base with metallistik vibration isolators, multi sheave
pullies for fan and fan motor. The fan capacity shall be based on outlet
velocity not exceeding 2000 FPM. The cooler shall be complete with 8"
thick celdek fill, 3mm thick FRP steel reinforced tank, water pump 2 Nos.
(1+1), cover pipe, distribution pipe, distribution pan, filters at air inlet, water
piping, make up water with ball valve, drain and overflow
connection,Eleminator etc. all housed in 16 G GSS casing mounted on
vibration isolators complete in all respects as per specifications and
drawings. Capacity of coolers as under. The scope shall include required
electrical panel. The saturation efficiency of the air washer shall be 90%.
26.0 MAIN LT PANEL(HVAC)
Supplying, installation, testing & commissioning of cubical type wall / floor
mounted Distribution Panel suitable for 433 V, 3 Phase, 4Wire 50 Hz AC
supply system fabricated in compartmentalized design from CRCA sheet
steel of 2mm thick for frame work and covers, 3 mm thick for gland plates
i/c cleaning & finishing complete with 7 tank process for powder coating in
approved shade, having Suitable Amp capacity extensible type FP
Aluminium Alloy bus bars of high conductivity, SMC bus bar supports, with
short circuit withstand capacity of 35kA for I Sec. with entire panel shall
have a common Alu earth bus of size 32x6mm at the rear with 2 Nos earth
stud, solid connections from main bus bar to switch gears with required size
of Al. bus bars and control wiring with 2.5 sq.mm. PVC insulated FRLS
copper conductor Single Core cable, cable alleys, cable gland plates in two
half, i/c additional NO/NC contacts in all outgoing starters for automatic
operation through BMS and providing & fixing following switch gears:-
1 Nos
A Incomer - 1
1 No. - 400 Amps Four Pole, 50k KA (ICU=ICS) for 1 sec, MCCB with
Microprocessor release with O/C, S/C & E/F protection release, each
MCCB each shall be with following:-
B Bus Bar
TPN aluminium extensible type main bus bars of minimum of 500 A
capacity (As per capacity of corresponding incoming / Bus couplers) , and
auxiliary bus bars of suitable capacity with heat shrunk coloured sleeves
and i/c SMC bus bars supports at required intervals complete for cross
section, size supports & their spacing etc. for withstanding fault level of
35kA for 1 Sec.
C Outgoings basbar
i 2 Nos. - 160A 36 KA 4P MCCB for 80KW HWG
ii 2 Nos. - 32A 36KA TPN MCB (Motor duty) with DOL starter and single
phase preventor ( 2# HWG pump 5kw)
27 L.T. CABLES
A Supply of following size XLPE insulated and PVC sheathed aluminium
conductor armoured cable of 1.1 KV grade as per IS 7098 (Part-1) 1988
complete as required including Laying and fixing of one number PVC
insulated and PVC sheathed / XLPE power cable of 1.1 kV grade, the
scope shall also include suitable size of perforated painted with powder
coating M.S. cable trays and including supplying and making end
termination with brass compression gland and aluminium lugs.