Boq - Scrubber

This document provides a list of HVAC equipment for a project including: 1. An 80KW hot water generator with electric heaters and controls for temperature and pressure. 2. Two hot water circulation pumps that can deliver 230 LPM of water at 15m head along with valves, insulation, gauges and foundations. 3. Several air handling units of varying sizes and configurations including double skin construction, coils, filters and motors. 4. Several fan coil units of varying sizes for cooling with coils, insulation, drain pans and motor controls.

Uploaded by

pawan saini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
563 views16 pages

Boq - Scrubber

This document provides a list of HVAC equipment for a project including: 1. An 80KW hot water generator with electric heaters and controls for temperature and pressure. 2. Two hot water circulation pumps that can deliver 230 LPM of water at 15m head along with valves, insulation, gauges and foundations. 3. Several air handling units of varying sizes and configurations including double skin construction, coils, filters and motors. 4. Several fan coil units of varying sizes for cooling with coils, insulation, drain pans and motor controls.

Uploaded by

pawan saini
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 16

Sl.

No Description Qty Unit

Sub Head IX: HVAC

1 Supply, installation, testing and commissioning of 80KWBMS compactable


package type electric Hot Water generator having top open-able cover for
easy access and removal of heaters. The HWG shall be constructed out
Shell Sheet : 08mm thick Mild Steel Dish end Sheet : 10mm thick Mild Steel
Panel Sheet : 16 Gauge thick CRC Skin Pass
Paneling Sheet : 18 Gauge thick CRC Skin Pass
Enclosure : I.P-54 (Indoor Unit)
Insulation : Resin Bonded Fiber Glass wool (50mm thick – 24 kg Density)
Clading : Aluminum Sheet (0.8mm Thick)

Inlet-Outlet : 03 inch Pipe Flange ends. Heaters: Electric Resistance


Immersion type
Heater Material : Copper Tube chrome plated Power Supply : 3 phase, 415
Volt, 50 Hz. AC supply.
Capacity : 8KW X 2 Nos. INTO 05 Steps = 80KW
Controls : Step Controller with PLC display
Working Pressure: 100 P.S.I.G Test Pressure : 250 P.S.I.G Pressure
Gauges with Ball Valves, Pressure Relief Valve at Inlet – 100 P.S.I.G, Level
Switch with Electronic controller for Low Level cutout
Master Thermostat for High Temperature Cutout 2 Nos
The generator shall be complete with Internally Factory wired complete with
Electrical Panel with with PLC display, Auto Air Purging Valve, float valve,
pressure gauge with ball valve, master and bank thermostats, etc. The
generator shall complete with self- contained incoming isolation, ammeter,
voltmeter, contactors for heater banks in Three steps complete with
manual/auto rotary switches.

2 Supply, erection, testing and commissioning of end suction / Vertical Inline


Split Coupled (Long coupled) centrifugal Hot water pumps (Reheat) set
capable of delivering following capacity of water, each comprising of the
following and complete with TEFC squirrel cage induction motor, efficiency
IE3 with class 'F" insulation. 1450 rpm synchronous speed, operating on
415+ 10% volts, 3 phase, 50 Hz A.C. supply, BMS compatible. pump shall
have CI body, SS/Bronze impeller, spacer coupling and coupling guard,
The mechanical seal shall be outside type, The internal components of
pumps including mechanical seal shall be suitable to sustain a temperature
of 122 degree Fahrenheit. Vendor shall be provide
antivibration arrangement for pumps . Pumps

shall have minimum efficiency of pump shall be 50%. Pump shall be with
PN-16 ratings. The scope also shall include following.
a Set of suitable size Triple duty valve & End suction guide for each pump
b 19mm thick polyvinyl nitrile rubber insulation duly cladded between
aluminium sheets of 0.5mm thickness and properly clamped to pump.
c 2 Nos. - 150 mm dia dial type pressure gauges
d Mounting frame with antivibration pads ( In case pumps are inline, anti
vibration system shall be as per Manufacturers recommendation)
e RCC/cement concrete foundation for the pump unit. ( In case pumps are
inline, foundation shall be as per Manufacturers recommendation)
2.1 Capacity unit not less than 230 LPM of water at 15 mtr head. 2 Nos.

3 Air Handling units (AHUs)
Supply, Installation, Testing and commissioning of factory built floor
mounted chilled water double skin type horizontal/vertical air handling units
made of 25mm thick panels consisting of pre plasticized G.I. casing of
thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane
foam (PUF) insulation factory injected between them by injection moulding
machine, complete with blower section with blower suitable for static
pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil
section with aluminium finned copper tubes (tubes thickness not less than
0.5mm) cooling coil of Six row deep, filter section with 50mm thick metal
viscous/ washable synthetic type air prefilters (EU4, more than 90%
efficiency for 10 Microns) & fine (Bag filter EU7 3 Microns), belt drive
package with TEFC drive motor of efficiency class IE3 suitable for 415 ±
10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe

frequency drive applications, drain connections, stainless steel (18G) drain


pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)
and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto
purge valve wherever required, necessary vibration isolation arrangement
etc. complete as per specification and of following capacities. The scope
shall include AHU mounted VFD drive complete with incoming electrical
isolator in enclosure & UVGI lamps.

Capacity (CFM)
3.1 FM AHU
3.1.1 6500 1 Set
3.1.2 3500 1 Set
3.1.3 3000 1 Set
3.1.4 3200 1 Set
3.1.5 6000 1 Set
3.2 C/S AHU
3.2.1 1200 2 Set
3.2.2 3000 1 Set
3.2.3 1500 1 Set
3.2.4 4000 1 Set
3.2.5 2500 1 Set
3.2.6 6000 2 Set
3.3 In addition to above HEPA filter (H 13) section shall also be provided as
part of C/S AHU with HEPA
3.3.1 1200 1 Set
3.3.2 3000 1 Set
3.4 In addition to above HEPA filter (H 13) section shall also be provided
as part of FM AHU with HEPA
3.4.1 1500 1 Set

3.5 In addition to above HEPA filter (H 13) in supply section and Exhaust
section with exhaust fan having only pre filters shall also be provided as
part of OT FM AHU. The unit shall be in two tier ( Supply section / return
section - one above the other). The scope shall include 2 row deep reheat
coil & 6KW pantype humidifier. The scope shall include 3 way controle
valve & humidistat for operating reheat coil & wiring complete as required.

3.5.1 1500 4 Set


3.5.2 2000 7 Set
4 Supplying, installation, testing and commissioning of fan coil units having
following capacities, ceiling/ wall mounted complete with copper tubes, 3
row deep chilled water cooling coils having aluminium fins and auxiliaries
including ball valve set ( one with strainer), insulation of drain pan, drain
connections, blower, TEFC slow speed (3 speeds) squirrel cage induction
motor suitable for operation on 230 volts, single phase, 50 Hz, A.C. supply,
controls for fan coil units comprising solenoid valve or 2 way valve with
actuator, three speed selector switch, BMS compactable room thermostat
with ON/ OFF switch, electrical wiring etc complete as required.
4.1 400 2 Set
4.2 600 1 Set
4.3 800 2 Set

5 Supply, Installation, Testing and Commissioning of following sizes


electronic, self-balancing, pressure independent type dynamic balancing
valve with integrated 2 way modualating control valve in a single body. The
actuator shall be capable of accepting upto 10V DC andupto 20mA electric
signal and shall provide similar transduced feedback output to control
system. Maximum close off pressure shall not be less than 6 Bar for upto
50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure
rating of 25 Bar minimum.
5.1 65 Dia 4 Nos
5.2 50 Dia 6 Nos
5.3 40 Dia 7 Nos
5.4 32 Dia 10 Nos

6.0 Supplying, fixing, testing and commissioning of following valves, strainers,


gauges in the chilled water plumbing duly insulated to the same
specifications as the connected piping and adequately supported as per
specifications.
6.1 BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal
& O- Ring PN 16 pressure rating for chilled water/hot water circulation as
specified
6.1.5 65 Dia 8 Nos
6.1.6 50 Dia 12 Nos
6.1.7 40 Dia 14 Nos
6.1.8 32 Dia 20 Nos

6.2 Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer
for chilled / hot water circulation including insulation as specified.

6.2.1 65 Dia 4 Nos


6.2.2 50 Dia 6 Nos
6.2.3 40 Dia 7 Nos
6.2.4 32 Dia 10 Nos

7 Supplying, laying/ fixing, testing and commissioning of following nominal


sizes of chilled water piping plumbing inside the building (with necessary
clamps, vibration isolators and fittings but excluding valves, strainers,
gauges etc.) duly insulated with fire retardant quality expanded
polystrenemoulded pipe section of density 20 kg/cu.m after a thick coat of
cold setting adhesive (CPRX compound) wrapping with 500g polythene
faced hessain and finally applying 0.63mm aluminium sheet cladding
complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended
up to date) at joints repairing of damage to building etc. as per
specifications and as required complete in all respect.
Note:-The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS:
1239 and pipes size above 150mm shall be welded black steel pipe heavy
class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes
upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400
mm dia and above.
7.1 150mmdia. (75mm thick insulation) 40 RM
7.2 125mmdia. (50mm thick insulation) 40 RM
7.3 100mmdia (50mm thick insulation) 20 RM
7.4 80mmdia (50mm thick insulation) 20 RM
7.5 65mmdia. (50mm thick insulation) 80 RM
7.6 50mmdia. (50mm thick insulation) 120 RM
7.7 40mmdia. (50mm thick insulation) 140 RM
7.8 32mmdia. (50mm thick insulation) 200 RM
7.9 25mmdia (50mm thick insulation) 100 RM

8 Supplying, fixing, testing and commissioning of medium class G.I.


condensate drain pipes on wall/floor/roof of following size/diameters duly
insulated with 9 mm thick closed cell nitrile rubber insulation in the form of
pre- formed pipe sections and along with necessary clamps, fittings such as
bends, tees etc. adequately supported as per specifications and as
required.

8.1 50 mmdia. 5 RM
8.2 40 mmdia. 25 RM
8.3 32 mmdia. 35 RM
8.4 25mmdia 125 RM

9 Supply, installation, balancing and commissioning of factory fabricated GSS


sheet metal rectangular/round ducting complete with neoprene rubber
gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per
approved drawings and specifications of following sheet thickness complete
as required.

9.1 Thickness 1.25mm Sheet 35 Sqm


9.2 Thickness 1.00mm Sheet 105 Sqm
9.3 Thickness 0.80mm Sheet 110 Sqm
9.4 Thickness 0.63mm Sheet 250 Sqm

10 Supply, installation, balancing and commissioning of factory fabricated Al.


sheet metal rectangular/round ducting complete with neoprene rubber
gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per
approved drawings and specifications of following sheet thickness complete
as required.

10.1 Thickness 1.00mm Sheet 100 Sqm


10.2 Thickness 0.80mm Sheet 150 Sqm

11 Supplying and fixing of following thickness duly laminated aluminium foil of


mat finish closed cell Nitrile rubber (class "O") insulation on existing duct
after applying two coats of cold setting adhesive (CPR X compound). The
joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile
rubber tape insulation complete as per specifications and as required.

11.1 25 mm 700 Sqm


12 Supplying and fixing 50mm thick aluminium foil faced resin bonded fibre
glass insulation (on duct) of density 24 kg/cu.m or mineral wool
insulation(non combustible) of density 44 kg/cum after applying two coats of
cold setting adhesive (CPRX compound) sealing all joints with self
50 Sq.m
adhesivealuminium tape & covering with 0.63mmx19mm GI wire mesh
netting & butting all joints and laced with GI wire complete and finally
covered with one layer of tar felt stuck with hot bitumen as per
specifications and as required. (for outdoor applications)

13 Supply and fixing of acoustic lining of supply air duct and plenum with 25
mm thick resin bonded glass wool having density of 32kg/m³, with 25 mm X
25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered
with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum
40 Sq.m
sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick
pins, CPRX compound etc. complete as required and as per specifications.

14 Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with
50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction
fixed in 610mm x 610 mm frame work made of 25X50X50X50X25 mm 210 Sqm
made out of
0.6mm thick GI sheet U shaped channel and covered with reinforced fiber
glass tissue and finished with 0.80 mm perforated aluminiumsheet etc.
complete as required and as per specifications. AHU room ( 6 x 4 x 3.5
walls)

15 Supply, installation, testing and commissioning of GI volume control duct


damper complete with neoprene rubber gaskets, nuts, bolts, screws 7 sqm
linkages, flanges etc, as per specifications.

16 Supplying & fixing of powder coated extruded aluminium Supply Air Grills
with aluminium volume control dampers as per specifications. 20 Sqm

17 Supplying & fixing of powder coated extruded aluminiumReturn Air Grills


with louvers but without volume control dampers complete as required. 25 Sqm

18 Supplying, fixing testing commissioning of supply air diffusers of powder


coated aluminium with aluminium volume control dampers with anti smudge 5 Sqm
ring & removable core.

19 Supplying, fixing testing commissioning of Return air diffusers of powder


coatedaluminium without volume control dampers with anti smudge ring & 8 Sqm
removable core.

20 Supplying, Fixing,testing and commissioning of fire dampers in supply air


duct/main branch and return air path as and where required of required
sizes i/c control wiring,the damper shall be motorized and spring return so
as to close the damper in the event of power failure automatically and open
the same in case of power being restored. The spring return action shall be
inbuilt mechanism and not externally mounted. The damper shall also be
closed in the event of fire signal complete as required and as per
specifications.

i Fire Damper 40 sqm


ii Motorised Actuator 50 No.
21 SITC of 150mm deep Double layered Flexible canvass connection made of
fibreglass weave having silver grey silicon rubber coating, Flexible
connection shall be air tight & water proof and withstand high temperature
application, non flammable and does not support combustion. Flexible
12 RM
connection shall be complete with flanges made out of 22G G.S.S sheet on
both sides for connection to unit and duct complete with nuts, bolts etc.

22 Supplying, fixing, testing & commissioning of powder coated extruded


aluminium section fresh air louvers in weather maker room with aluminium
volume control dampers, bird screen etc completed as required. 40 Sqm

23 Scrubber
Supply, Installation, Testing and commissioning of Dry scrubber for kitchen
exhaust consisting of Electrostatic Precipitator, backward curve SISW
centrifugal fan with elongated shaft having bearing & drive package out of
exhaust air stream, TEFC induction motor, common channel base frame for
Fan and motor, vibration isolation arrangement by means of spring type
vibration isolators or turret mounts, fire retardent flexible canvass
connections made out of canvass sleeve and the scope includes unit
mounted stater panel in enclosure.

The Electrostatic section shall be 90-95% in single pass as per DOP test
method. Electrostatic Precipitator should be able to charge particles from
0.01 micron to 10 micron through solid state power supply. Collector cell
shall be of permanent type and slide out facility for easy removal for
cleaning. Operating voltage shall be 220+6 % volts, 50 Hz/1Ph, power
consumption shall not exceeding 50 watts per unit upto 7500 Cfm. System
should be fitted with interlock switch for safety. Velocity across the air
cleaner shall not be more than 500 FPM. Scrubber shall be provided with
pre-filters as required, pressure drop across ESP with pre filter should not
be more than 12mm of Water gauge, .ESPs shall be provided with UV &
Ozone Odours removers. ESP Modules shall have necessary provision in
terms of flanges to facilitate Ducts/Plenum connections. The scope shall
include required electrical panel. The Scrubber shall be of following
capacity.

23.1 Air Qty. - 8000Cfm, Pressure Drop - 50mmWG 1 Nos

24 Supply, installation, testing and commissioning of synthetic fill pad type air
washer at 500 FPM velocity across pads, DIDW Class-I Backward curved
centrifugal fan with TEFC weather proof motor (IE3 efficiency) of IP:55
protection suitable for 415 +10% Volts, 3 phase, 50 cycles power supply,
mounted on a common base with metallistik vibration isolators, multi sheave
pullies for fan and fan motor. The fan capacity shall be based on outlet
velocity not exceeding 2000 FPM. The cooler shall be complete with 8"
thick celdek fill, 3mm thick FRP steel reinforced tank, water pump 2 Nos.
(1+1), cover pipe, distribution pipe, distribution pan, filters at air inlet, water
piping, make up water with ball valve, drain and overflow
connection,Eleminator etc. all housed in 16 G GSS casing mounted on
vibration isolators complete in all respects as per specifications and
drawings. Capacity of coolers as under. The scope shall include required
electrical panel. The saturation efficiency of the air washer shall be 90%.

24.1 6400 CFM External Static pressure: 15mm WG 1 Nos


25 Supply, installation, testing and commissioning of Duct mounted in-line
exhaust air fans comprising of Housing made out of heavy gauge
galvanized sheets, DIDW forward curved centrifugal fan complete with
internal rotor motor suitable for single phase, 230 volts, 50 Hz required for
the exhaust. The fan shall be complete with speed regulator, external
gravity louvers, thermal overload release for the motor as well as terminal
box for termination of external power supply for the following Capacities.

25.1 200CFM 3 Nos


25.2 100CFM 3 Nos
25.3 50CFM 7 Nos

26.0 MAIN LT PANEL(HVAC)
Supplying, installation, testing & commissioning of cubical type wall / floor
mounted Distribution Panel suitable for 433 V, 3 Phase, 4Wire 50 Hz AC
supply system fabricated in compartmentalized design from CRCA sheet
steel of 2mm thick for frame work and covers, 3 mm thick for gland plates
i/c cleaning & finishing complete with 7 tank process for powder coating in
approved shade, having Suitable Amp capacity extensible type FP
Aluminium Alloy bus bars of high conductivity, SMC bus bar supports, with
short circuit withstand capacity of 35kA for I Sec. with entire panel shall
have a common Alu earth bus of size 32x6mm at the rear with 2 Nos earth
stud, solid connections from main bus bar to switch gears with required size
of Al. bus bars and control wiring with 2.5 sq.mm. PVC insulated FRLS
copper conductor Single Core cable, cable alleys, cable gland plates in two
half, i/c additional NO/NC contacts in all outgoing starters for automatic
operation through BMS and providing & fixing following switch gears:-

1 Nos
A Incomer - 1
1 No. - 400 Amps Four Pole, 50k KA (ICU=ICS) for 1 sec, MCCB with
Microprocessor release with O/C, S/C & E/F protection release, each
MCCB each shall be with following:-
B Bus Bar
TPN aluminium extensible type main bus bars of minimum of 500 A
capacity (As per capacity of corresponding incoming / Bus couplers) , and
auxiliary bus bars of suitable capacity with heat shrunk coloured sleeves
and i/c SMC bus bars supports at required intervals complete for cross
section, size supports & their spacing etc. for withstanding fault level of
35kA for 1 Sec.

C Outgoings basbar
i 2 Nos. - 160A 36 KA 4P MCCB for 80KW HWG
ii 2 Nos. - 32A 36KA TPN MCB (Motor duty) with DOL starter and single
phase preventor ( 2# HWG pump 5kw)
27 L.T. CABLES
A Supply of following size XLPE insulated and PVC sheathed aluminium
conductor armoured cable of 1.1 KV grade as per IS 7098 (Part-1) 1988
complete as required including Laying and fixing of one number PVC
insulated and PVC sheathed / XLPE power cable of 1.1 kV grade, the
scope shall also include suitable size of perforated painted with powder
coating M.S. cable trays and including supplying and making end
termination with brass compression gland and aluminium lugs.

i 4C x 120 sq.mm. (HWG) 40 RM


ii 3C x 6 40 RM
28 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for
connections etc. as required. 80 meter
29 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop
earthing as required. 80 meter
30 Credit for old dismantling items including AHUs, valves,MS water
1 Job
pipe,GIpipes,Metal ducting, air diffusers,air washers, Main LT HVAC panel
and Cables etc . TOTAL AMOUNT
Unit Rate Amount