Power System by Davinder
Power System by Davinder
3 To study the IDMT over current relay and determine the time 10
current characteristics.
4 To study percentage differential relay. 12
EQUIPMENTS REQUIRED -
1. Ammeter: – 0 - 15A; 0 - 2.5A.
2. Voltmeter: – 0 – 40V; 0 – 250V.
3. Wattmeter: – 0 -1400 W.
CONNECTION DAIGRAM –
Apply low voltage to the field circuit so that exciting current is small.
Alternately connect a high resistance in the field circuit with full applied
voltage.
3. DETERMINATION OF NEGATIVE
SEQUENCE REACTANCE (X2)
The negative sequence reactance X2 can be obtained by running the machine at
rated speed with a low excitation and with a sustained two-phase short circuit
between the open phase and any short-circuited phase. Let open circuit voltage
be Vos and the short circuit current Isc. The negative sequence impedance Z2
and reactance X2 can be calculated using the following expressions:
Z2=Vos/3. Isc
X2=Z2 sin Ø
Short circuit two phases of the alternator through an ammeter and the
current coil of the wattmeter.
Connect the voltage coil of the wattmeter and the voltmeter between the
open phase and any short-circuited phase.
Gradually increase the excitation such that the short circuit current does not
exceed its rated value.
Apply low voltage from a variac and measure both voltage V0 and current I0
taken by the armature windings and zero sequence reactance can be
calculated using the following expression:
X0=3.Z0/I0
EXPERIMENT NO. - 2
Since the zero-, positive-, and negative-sequence currents are equals as it can
be observed in Figure 3.11. Therefore,
Line-to-Line Fault A line-to-line fault may take place either on an overhead
and/or underground transmission system and occurs when two conductors are
short-circuited. One of the characteristics of this type of fault is that its fault
impedance magnitude could vary over a wide range making very hard to
predict its upper and lower limits. It is when the fault impedance is zero that
the highest asymmetry at the line-to-line fault occurs the general
representation of a line- to-line fault is shown in Figure 3.12 where F is the fault
point with impedances Zf. Figure 3.13 shows the sequences network diagram.
Phase b and c are usually assumed to be the faulted phases; this is for
simplicity in the fault analysis calculations [1],
Graph:
PRECAUCTIONS:
1. It must be done under the guidance of the teacher.
2. Student should know the equipment’s and use of MATLAB.
3. Check the connection before run the programme.
EXPERIMENT NO.- 3
AIM: To study the IDMT over current relay and determine the time current
characteristics.
APPARATUS REQUIRED:
PROCEDURE –
STUDY THE OPERATING CURRENT & DE-OPERATING CURRENT OF DISC.
APPARATUS USED:
1. Relay Single Pole Version 1 A (Numerical Type) ‘AREVA’ make MBCH-12
2. Timer
8. Isolation Transformer
THEORY:
It is a very important protection of the transformer. It is based on the ratio
of H.T. current and L.T. current should be constant. Consider the Fig No ‘1’,
here we considering the single pole of 132/33 KV Transformer. It’s H.T.
current and L.T. current ratio will be 1:4. If the CT of H.T. side is considered
100/1 Amp, so the CT of L.T. side will be 400/1 Amp. The secondary current
of L.T. side CT and H.T. side CT will always equal in normal condition. Both
the secondary of CTs will enter in Numerical type % Differential Relay. The
secondary of CT connection is make in such a way that the CT current will
flow only through coil circuit and no extra current is to flow from Differential
coil. As soon as the fault occurs in transformer, the H.T. current will high. The
ratio of H.T. current and L.T. current will change. The secondary of H.T. side
CT current will become high with respect to secondary of L.T. side CT
current. So the difference of current will flow through differential winding.
The
secondary of differential winding transformer will go to an electronic circuit
that will operate a tripping relay to trip the breaker of main transformer. The
through windings are used to restraining the differential relay. It will more
clearly by drawing the curve between through current and differential
current.
CIRCUIT DIAGRAM:
THEORY:
If the spring controlling effect is indicated by –K3, the torque equation becomes,
Where Θ and τ are defined as positive when I lag behind V. At balance point,
the net torque is zero, and hence the equation becomes
Mho relay is suitable for EHV/UHV heavily loaded transmission lines as its
threshold characteristic in Z-plane is a circle passing through the origin, and its
diameter is ZR. Because of this, the threshold characteristic is quite compact
enclosing faulty area compactly and hence, there is lesser chance to operate
during power swing and also it is directional.
DISTANCE RELAY - Distance protection is the name given to the
protection; whose action depends upon the distance of the feeding point
to the fault. The time of operation of such a protection is a function of
the ratio of voltage and current i.e., impedance. This impedance between
the relay and the fault depends upon the electrical distance between
them. Distance relays differ in principle from other forms of protection in
their performance and is not governed by the magnitude of the current
or the voltage in the protected circuit but rather on the ratio of these two
quantities. Distance relays are actually double actuating quantity relays
with one coil energized by voltage and the other coil by current. The
current element produces a positive or pick-up torque while the voltage
element produces a negative or reset torque. The relay operates only
when the V/I ratio falls below a predetermined value (or set value).
During a fault on a transmission line the fault current increases and the
voltage at the fault point decreases. The V/I ratio is measured at the
location of CTs and Pts. The voltage at PT location depends on the
distance between PT and the fault. If the fault is nearer, measured voltage
is lesser and if the fault is farther, measured voltage is more. Hence
assuming constant fault impedance each value of V/I measured from
relay location corresponds to distance between relaying point and the
fault along the line. Hence such protection is called the distance
protection or impedance protection. Distance protection is non-unit type
protection, the protection zone is not exact. The distance protection is
high speed protection and is simple to apply. It can be employed as a
primary as well as backup protection. It can be employed in carrier aided
distance schemes and in auto-reclosing schemes. Distance protection is
very commonly used in protection of transmission lines. Distance relays
are used where overcurrent relaying is too slow and is not so selective.
Distance relays are used for both phase fault and ground fault protection
and they provide higher speeds for clearing faults than overcurrent
relays. Distance relays are also independent of changes in magnitude of
the short-circuit currents and hence they are not much affected by
changes in the generation capacity and the system configuration. Thus,
they eliminate long clearing times for faults near the power sources
required by overcurrent relays if used for the purpose.
EXPERIMENT - 7
REQUIRED EQUIPMENT:
1. Connections:
1. First, isolate the grounding electrode under measurement by
disconnecting it from the rest of the system.
2. For Small System:
3. For 4 Terminal Earth Tester Short Current Terminal (C1) and Potential
Terminal (P1) together with a short jumper on the earth tester and
connect it to earthing electrode under test.
4. For 3 Terminal Earth Tester Connect current terminal (C1) to the earth
electrode under measurement.
5. Drive another Current Electrode (C2) into the earth 100 to 200 feet at
depth of 6 to 12 inches from the center of the electrode and connect
to C2 Terminal of earth tester.
6. Drive another potential terminal (P2) at depth of 6 to 12 inches into
the earth midway between the Current Electrode (C1) and Current
Electrode (C2) and connect to Earth Tester on P2
7. For Large System
8. Place the current electrode (C2) 400 to 600 feet from the measuring
Earth Current Electrode (C1)
9. Place the potential electrode (P1)8% of the distance from the Earth
Current Electrode (C1)
10.Measure the resistance
11.Move the current electrode (C2) farther 50 to 100 Feet away from its
present position.
12.Place the potential electrode (P2) 61.8% of the distance from the
Earth Current Electrode (C1).
13.Spike length in the earth should not be more than 1/20th distance
between two spikes.
● TESTING PROCEDURE:
1. Press START and read out the resistance value. This is the actual value
of the ground electrode under test.
2. Move the potential electrode 10 feet farther away from the electrode
and make a second Measurement.
3. Move the potential probe 10 feet closer to the electrode and make a
third measurement.
4. If the three measurements agree with each other within a few
percent of their average, then the average of the three measurements
may be used as the electrode resistance.
5. If the three measurements disagree by more than a few percent from
their average, then additional measurement procedures are required.
6. The electrode centre location seldom is known. In this case, at least
three sets of measurements are made, each with the current probe a
different distance from the electrode, preferably in different
directions.
7. When space is not available and it prevent measurements in different
directions, suitable measurements can be made by moving the
current probe in a line away from or closer to the electrode.
8. For example, the measurement may be made with the current probe
located 200, 300 and 400 feet along a line from the electrode.
9. Each set of measurements involves placing the current probe and
then moving the potential probe in 10 feet increments toward or
away from the electrode.
10.The starting point is not critical but should be 20 to 30 feet from the
electrode connection point, in which case the potential probe is
moved in 10 feet increments toward the current probe, or 20 to 30
feet from the current probe, in which case the potential probe is
moved in 10 feet increments back toward the electrode.
11.The spacing between successive potential probe locations is not
particularly critical, and does not have to be 10 feet, as long as the
measurements are taken at equal intervals along a line between the
electrode connection and the current probe.
12.Larger spacing means quicker measurements with fewer data points.
smaller spacing means more data points with slower measurements.
13.Once all measurements have been made, the data is plotted with the
distance from the electrode on the horizontal scale and the measured
resistance on the vertical scale.
● PRECAUCTIONS-
1. Experiment must be done under the guidance of the teacher
2. Connect the electrodes properly.
3. Check the connection properly