The document reports on the results of tests conducted on a relay. It provides details on the relay settings, injected currents during tests, observed currents, timing test results, pickup test results and characteristic test results. The tests were conducted to verify the technical specifications and performance of the relay.

Uploaded by

Abhishek Rajput
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views3 pages

Test Report - RET 650

The document reports on the results of tests conducted on a relay. It provides details on the relay settings, injected currents during tests, observed currents, timing test results, pickup test results and characteristic test results. The tests were conducted to verify the technical specifications and performance of the relay.

Uploaded by

Abhishek Rajput
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

RELAY TEST REPORT

4/17/2023
PAGE 1

Nameplate Data
Substation Test Status Pass
Protection Job Number
Manufacturer Current Input Current Transformer
Model Voltage Input Potential Transformer
Asset ID CT Ratio 1000 A : 1 A Earthing L->N
Serial Number PT Ratio 1000 V : 1 V
Relay Firmware Rotation Counter Clockwise Rotation 0-360 Lead

Differential Settings 4/17/2023 3:12:22 PM

Pickup 0.2 pu Current Tolerance 15 % Slope From Base Point


Trip Time 150 ms Trip Time Tolerance 10 % +50 ms Restraint Equation max |Ip|or|Is|
Prefault Level 100 % Simulate Breaker NO Unrestrained Pickup 10 pu
Prefault Time 500 ms Use Reference Voltage NO Slope Restraint pu Gradient (%)
Off Delay 50 ms 1 1.25 20
Through Fault Current 100 % Ib Harmonic Tolerance 10 % 2 3 40
2nd Harmonic Content 15 % Harmonic Ramp Mode Ramp To Operate
Fault Duration 500 ms Nth Harmonic Content 35 % 5th
*A vertical offset is created between slopes
ICT Correction NO Nominal Current Protected Object when two equivalent restraint values are entered.
The Gradient % of the first equivalent point will be
the value of the vertical offset in per unit.

132 kV 33 kV
50 MVA
400 :1 A 1,200 :1 A

0 218.69 A 874.77 A
0
I0 elimination
YnYn0 (enabled)
0.547 A 0.729 A
Single Phase Single Phase
Pickup Factor Interposing CTs 1.00 Pickup Factor
1.00

Stabilization Test 4/17/2023 3:18:52 PM

Injected Currents Currents Observed From Relay


Phase

W1 W2 W1 W2
Irestraint Ioperate
I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°) I (A) ϕ (°)
0.547 0 0.729 180
A-N 0.000 0 0.000 0 0 0
218.693 0 874.773 180
0.547 240 0.729 60
B-N 0.000 0 0.000 0 0 0
218.693 240 874.773 60
0.547 120 0.729 300
C-N 0.000 0 0.000 0 0 0
218.693 120 874.773 300

Timing Test 4/17/2023 3:20:36 PM

TEST EQUIPMENT USED: SMRT46P (SN202109070011) TESTED BY:

COPYRIGHT © 2002-2023 POWERDB, INC. www.powerdb.com Form Schema 0


RELAY TEST REPORT
4/17/2023
PAGE 2

Phase Fault Current Expected Maximum Measured P/F


Tested (% Ib) Trip Time (s) Trip Time (s) Trip Time (s)

A-N 100.0 0.150 0.215 0.031 P

B-N 100.0 0.150 0.215 0.033 P

C-N 100.0 0.150 0.215 0.029 P

ABC 100.0 0.150 0.215 0.032 P

Pickup Test 4/17/2023 4:06:24 PM

Winding 1 Winding 2
Phase
Pickup Pickup
Pickup Pickup Error P/F Pickup Pickup Error P/F
Setting Setting
(Pu) (A) (%) (Pu) (A) (%)
(pu) (pu)

A-N 0.20 0.200 0.164 0.0 P 0.20 0.206 0.225 3.0 P

B-N 0.20 0.200 0.164 0.0 P 0.20 0.200 0.219 0.0 P

C-N 0.20 0.200 0.164 0.0 P 0.20 0.198 0.217 -1.0 P

ABC 0.20 0.200 0.109 0.0 P 0.20 0.202 0.147 1.0 P

Characteristic Test 4/17/2023 4:12:59 PM

Irestraint Ioperate W1 W2 Error P/F


# (pu) (pu) (A) (A) (%)
1 0.50 0.20 0.16 0.36 0.0 P
2 2.20 0.39 0.99 1.60 -0.0 P
3 3.60 0.77 1.55 2.62 -3.0 P
4 4.80 1.22 1.96 3.50 -4.0 P

Characteristic Shot Test 4/17/2023 4:35:00 PM

COPYRIGHT © 2002-2023 POWERDB, INC. www.powerdb.com Form Schema 0


RELAY TEST REPORT
4/17/2023
PAGE 3

Irestraint Ioperate W1 W2 P/F


# (pu) (pu) (A) (A)
1 1.90 0.80 0.60 1.39 P
2 3.60 1.40 1.20 2.62 P
3 5.40 0.70 2.57 3.94 P
4 4.30 0.60 2.02 3.13 P

2nd Harmonic Block Test 4/17/2023 4:25:15 PM

Winding 1 Winding 2
Pickup = 0.150A , Tolerance = 10% Pickup = 0.150A , Tolerance = 10%
Phase

Funda- 2nd 2nd Funda- 2nd 2nd


Error P/F Error P/F
mental Harmonic Harmonic mental Harmonic Harmonic
(%) (%)
I (A) I (A) I (%) I (A) I (A) I (%)

A-N 1.00 0.148 14.850 -1.0 P 1.00 0.148 14.850 -1.0 P

B-N 1.00 0.148 14.850 -1.0 P 1.00 0.148 14.850 -1.0 P

C-N 1.00 0.148 14.850 -1.0 P 1.00 0.148 14.850 -1.0 P

ABC 1.00 0.148 14.850 -1.0 P 1.00 0.148 14.850 -1.0 P

Nth Harmonic Shot Test 4/17/2023 4:30:43 PM

Winding 1 Winding 2
Fundamental Current = 0.000A Fundamental Current = 0.000A
Phase

5th 5th 5th 5th 5th 5th 5th 5th No


Harmonic Harmonic Operate Harmonic Harmonic No Harmonic Harmonic Operate Harmonic Harmonic Operate
Operate
I (A) I (%) I (A) I (%) I (A) I (%) I (A) I (%)

A-N 0.300 30.00 P 0.400 40.00 P 0.300 30.00 P 0.400 40.00 P

B-N 0.300 30.00 P 0.400 40.00 P 0.300 30.00 P 0.400 40.00 P

C-N 0.300 30.00 P 0.400 40.00 P 0.300 30.00 P 0.400 40.00 P

ABC 0.300 30.00 P 0.400 40.00 P 0.300 30.00 P 0.400 40.00 P

Harmonic Content for No Operation: 40 % Harmonic Content for Operation: 30 %