Seismic Handbook ENG

Download as pdf or txt
Download as pdf or txt
You are on page 1of 148

SEISMIC

HANDBOOK
SEISMIC
HANDBOOK

SCIENTIFIC SUPERVISOR:

Prof. Stefano Grimaz


Laboratorio Sicurezza e protezione intersettoriale,
Dipartimento Politecnico di Ingegneria e Architettura—Università degli Studi di Udine

PREPARED BY:

Alberto Moretti, Fausto Barazza, Andrea Dusso


Safexpertise s.r.l., Start-up dell’Università di Udine
www.safexpertise.com - [email protected]

TRANSLATED FROM THE ITALIAN BY:

Olivier Braquet
CADDY Seismic Protection
Pentair Electrical & Fastening Solutions
WARNING Pentair products shall be installed and used only as indicated in Pentair’s product instruction
sheets and training materials. Instruction sheets are available at www.erico.pentair.com and from your
Pentair customer service representative. Improper installation, misuse, misapplication or other failure to
completely follow Pentair’s instructions and warnings may cause product malfunction, property damage,
serious bodily injury and/or death, and void your warranty.

© 2017 ERICO International Corporation/ERICO Italy

All rights reserved. No part of this publication may be reproduced, distributed, or transmitted in any form
or by any means, including photocopying, recording, or other electronic or mechanical methods, without
the prior written permission of the publisher, except in the case of brief quotations embodied in critical
reviews and certain other noncommercial uses permitted by copyright law.
The installation of sprinkler systems is beco- ducing flexible joints between parts that can
ming more widespread. Sprinkler systems are a undergo relative movements, and (5) anchoring
very effective technology to defend against fires: properly the various distributed services to
to safeguard lives, to protect assets, to contain avoid falls or unwanted movements.
losses and to ensure business continuity. Very
Consequently, in seismic areas it is essential to
often such systems are installed in buildings or
operate in an integrated manner. Structural en-
structures that are located in areas that are also
gineers, services designers, fire protection tech-
seismic. One must therefore make sure that in
nicians, architects and contractors need to
case of earthquakes these services do not be-
work together to define concerted solutions,
come themselves the cause of damage to the
shared with and accepted by the field engineers
occupants due to their collapses or as a result
and inspectors of the insurance companies.
of unwanted activations. When installed in stra-
tegic structures, or where it is imperative to This handbook, designed and structured in that
maintain an efficient defense against fires, the spirit, is intended to assist all those involved in
fire sprinkler systems must be able to operate the installation and the inspection of sprinkler
efficiently in the immediate aftermath of an ear- systems in seismic areas. It also provides de-
thquake. sign guidelines using a graphical approach di-
rectly traceable to the requirements of the indi-
Over the last decade, the earthquakes that hit
vidual international standard followed. This par-
Italy in L'Aquila (2009), in Emilia (2012) and mo-
ticular document offers solutions using FM Ap-
re recently in Central Italy (2016) have shown
proved CADDY's products.
that in a seismic zone, services too should be
specifically designed or adjusted to resist a sei-
This handbook can be used as a useful opera-
smic event. This need has already emerged in
tional tool to design and implement solutions to
other seismic countries, like the United States
protect activities located in areas with significant
and Japan, where the installation of sprinkler
seismic activity (sites with expected ground ac-
systems is more widespread. Most observed
celeration greater than 0.125g). This is espe-
seismic damage arises from the impact
cially true in Italy where the National Fire De-
between (1) the sprinkler system and other ser-
partment issued specific measures for sprinkler
vices, (2) any distributed services and non-
systems in its technical guide Guidelines for the
structural elements such as suspended ceilings
reduction of firefighting equipment seismic vul-
and (3) any distributed services and structures.
nerability (these guidelines are the most essen-
Therefore, the potential negative interaction
tial reference for installations subject to the con-
between these distributed systems and compo-
trol of the Fire Department). Additionally, the
nents must be analyzed and prevented.
elements selected to provide the seismic pro-
Hence, this highlights the need to consciously tection must also conform to Italy's technical
expand the design analysis to all types of con- norms (building code) for construction.
struction, including non-structural elements and
in particular distributed services. Prof. Eng. Stefano Grimaz
Insurance companies and technical associa- Director of the Safety and Intersectorial Protection Labora-
tions, especially those based in the US, levera- tory
ged such observations to issue specific recom- Politecnic Department of Engineering and Architecture
mendations for the design of sprinkler systems University degli Studi di Udine
in seismic areas.
These standards set up the seismic design by
focusing on the following key elements: (1) loca-
ting large mass elements as low as possible in
the building’s structure to reduce the stresses
induced by the earthquake, (2) bracing the di-
stributed services to control their oscillations, (3)
ensuring clearance when crossings walls and
floors to avoid destructive interactions, (4) intro-

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
User consultation guide CG 1 — CG 5
Fire sprinkler diagram—Glossary G1—G2
Clearances C A— C C, C fi
Sway bracing installation overview SB 1 — SB 4
Fire sprinklers system components
Fire Pump installations P A1— P B4, P fi
Risers R A1 — R D4
Horizontal crossmains/feedmains H A — H G2, H fi
Vertical crossmains/feedmains VA—VD
Branch lines B A — B F, B fi
Drops D A1 — D C2
In-Rack systems I A— I C5, I fi
CADDY sway bracing parts
CADDY sway bracing system CSB — CSB 1

Lateral sway braces CSB LAT 1— CSB LAT 3

Longitudinal sway braces CSB LONG 1— CSB LONG 2

Structure attachments CSB STR 1 — CSB STR 7


Applications
Maps of common applications A 1, A 2

Crossing seismic separation joints AA

Walls penetration AB

Obstacles avoidance — feedmains/crossmains AC1—AC6


Horizontal changes of direction — 90 angles AD1—AD3
Horizontal changes of direction — other angles A E 1, A E 2

Obstacles avoidance— risers AF1—AF3


Obstacles avoidance— beams AG1—AG9
Floors penetration AH

Sloped ceilings AI1 —AI5

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
This HANDBOOK constitutes an aid to the de- encountered situations such as obstacle avoi-
sign and to the verification of the installation of dance, changes of directions etc.
seismic protection systems for fire sprinklers as
This handbook does not cover the installation
required by FM Global’s Standard, FM Global
systems for vertical loads (hangers). Also, the
Property Loss Prevention Data Sheet 2-8 Ear-
instructions provided do not replace the struc-
thquake Protection for Water-Based Fire Pro-
tural calculation, which is necessary to comply
tection Systems. As described in Data Sheet 1-
with the local seismic regulations. In fact, the
2, Earthquakes, this handbook will address lo-
calculation results may lead to a greater number
cations in FM Global 50-year through 500-year
of sway braces than the minimum specified in
earthquake zones.
the FM Global Property Loss Prevention Data
CADDY’s handbook is organized in sections, Sheets.
inside of which are graphically represented re-
The handbook provides a set of general infor-
quirements of the fire sprinkler system. The
mation, not automatically transferable to the
graphics include the identification of the sway
actual situations of specific job sites; the person
bracing locations, the maximum intervals
in charge of the entire structural design, inclu-
between sway bracing, the types of couplings
ding verification of the sway braces and verifica-
required, etc. for the various situations presen-
tion of the support structure of the building is
ted in FM Global Property Loss Prevention Data
still the engineer in charge, as provided by the
Sheet 2-8. Each illustration is accompanied by
local codes.
a commentary that summarizes the require-
ments, quoting from time to time sections of the
FM data sheets related to the situation detailed.
The sections are organized in two levels: at a
first level are the major parts of the fire sprinkler
system ("R" section for the risers, "H" section
for the horizontal crossmains/feedmains, etc...).
Each section identifies the requirements of the
fire sprinkler system components. Subsections,
identified with the subscript letter "D" in the en-
coding (e.g. RD for riser, HD for horizontal cross-
mains/feedmains, etc.), present detailed in-
structions for the proper design and installation
of the seismic protection system at a second
level.
Each section is introduced by an "overview", or
diagram, which depicts this major part of the
fire sprinkler subsections with the correspon-
ding nomenclature, the corresponding section
of the FM data sheet referenced, and the sub-
sections to which to refer to find detailed in-
structions.
Following the sections about the fire sprinklers
major parts, CADDY’s sway bracing product
range is presented with tables that contain in-
formation about the application(s) for which they
have been designed and the pipe diameters
that they can brace.
This handbook also contains suggestions of
possible solutions using combinations of in-
structions from the FM data sheet for frequently

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Letter code identifying the
section covering this system
component (e.g.
H=Horizontal, R=Riser, etc.)

Fire sprinklers system component sec-


Color code identifying the Handbook’s fire
sprinkler code

Area of interest details:

Description of area of inte-

2.2.1.1.4.C.1

Section(s) of the Handbook page(s)


fire sprinkler code covering specific area
of interest: the first
letter identifies the sy-
stem component; the
Page release
second letter identifies
date
the area of interest

Handbook’s fire sprinkler


code referenced

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Letter code identifying
Letter code identifying the the area of interest
system component cove-
red (e.g. H=Horizontal) Variation
(if necessary)

Color code identifying the Handbook’s


System component sec- fire sprinkler code

Identifier of the area of interest

Identifier of the area of


interest details

Code signaling a
detailed instruction

Letter code identifying


the area of interest

Page release Handbook’s fire sprinkler


date code referenced

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Proper area in
which to locate
the sway braces
(in green)

Pipe run
being braced (in red)

Pipe run on which Representation of


SWAY BRACES are in- attachments to
stalled (in grey) any type of struc-
ture

Pipe run being bra-


ced (in red)

Representation of the fire pump


unit

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
FOUR-WAY SWAY BRACE symbol
FOUR-WAY SWAY BRACE
and location

LATERAL SWAY BRACE symbol


LATERAL SWAY BRACE
and location

LONGITUDINAL SWAY BRACE sym-


LONGITUDINAL SWAY BRACE
bol and location

Rigid coupling Flexible coupling

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
A device with a thermo-sensitive sealing element that opens to discharge water onto a
fire.

Pipes supplying sprinklers, either directly or through riser nipples (a.k.a. sprigs), drops,
return bends, or arm-overs.

Space required so that pipes or other elements do not come into contact with walls or
floors in case of earthquakes.

Connector used to join two or more pipe sections of the sprinkler system together.

Pipe supplying the branch lines between the feedmain and the system’s branch lines.

Pipe run of variable length descending from a main pipe or a branchline to feed a lo-
wer branchline.

Pipes supplying cross mains and the distribution piping, either directly or through ri-
sers.

Adjacent sway braces intended to resist differential movement of the system piping in
all horizontal directions.

A sway brace intended to resist a system piping movements perpendicular to its axis.

A sway brace intended to resist a system piping movement parallel to its axis.

Assembly consisting of more than one riser connected to a same supply pipe.

The vertical supply pipes in a sprinkler system.

Vertical piece of pipe between the main and a branch line.

Assembly of fittings, pipe, flexible pipe, and/or couplings that permits movement in all
directions to accommodate seismic differential movement across building seismic
separation joints.

A system that consists of an integrated network of specifially sized piping and all of
the other necessary elements to provide sprinkler protection to a building, including
one or more sprinkler grids, the distribution systems up to each grid and the water
source.

Assembly of rigid or flexible elements (cables) intended to be attached to the system


piping in order to resist horizontal earthquake loads in two directions.

SWAY-BRACE that acts in both tension and compression.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

2.2.1.5.2.A

2.2.1.5.2.B

2.2.1.5.1
2.2.1.5.2.C

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
DH
CLEARANCE

Dpipe

Where piping passes through walls, platforms, mezzanines, roofs, or floors, provide:
- a hole or sleeve with a nominal diameter DH = Dpipe + 2 in./50mm for pipes 1 in./25mm diameter through 3-1⁄2
in./90mm
- a hole or sleeve with a nominal diameter DH = Dpipe + 4 in./100 mm for pipe sizes 4 in./100 mm and larger.
Openings may be sealed with mastic or a weak, frangible mortar. If the pipe passes through a fire separation, the
space can be filled with mineral wool held in place with a pipe collar.
CLEARANCE is not needed when the structural member crossed material is frangible, such as gypsum board, and the
sturctural member crossed is not required to have a fire rating.

≥ 2 in. /

≥ 2 in. /

When piping passes through walls or structural


members, provide at least 2 in. / 50 mm clearance
between any flanges, fittings, or other devices on the
piping and walls/structural members crossed.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≥ 2 in. /

Provide at least 2 in. / 50 mm CLEARANCE between


ends of piping and walls or other structural mem-
bers.

≥ 2 in. / 50mm

When piping passes through walls or structural


members, then turns 90 degrees to run parallel to
the wall, provide at least 2 in. / 50 mm clearance
between the parallel pipe run and the wall/structural
member.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
For sprinklers (sprinkler heads) installed in suspended ceilings, if possible provide an oversize adapter through the
ceiling tile to allow for free movement of 1 in. / 25 mm in all horizontal directions. If not possible, provide at least a 1⁄2
in. / 13 mm gap around ceiling penetrations for sprinklers.

For other sprinklers (sprinkler heads), provide vertical and horizontal CLEARANCE of at least 2 in. / 50 mm to structural
or nonstructural elements. A smaller CLEARANCE is acceptable where the system is arranged so that less relative mo-
vement between the sprinkler (head) and the object is expected or where the sprinkler (head) is protected from im-
pact. Provide greater horizontal CLEARANCE (4–6 in. / 100–150 mm) to sprinklers (sprinkler heads) when possible.

Note: The minimum sprinkler head clearance is 2 in. / 50 mm but best practice would be 4-6 in. / 100-150 mm.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Fastener to structure or structural adap-
ter

Brace member
Structural attachment—Building attached
component (BAC)
Pipe attachment—Pipe attached
component (PAC)

Sprinkler pipe

Locations allowed:
Angles ≥ 30° from vertical
Optimal locations:
Not allowed:
Angles at or near 45° from vertical
Angles < 30° from vertical

SWAY BRACE intended to resist movement parallel to the axis of the system piping.
LONGITUDINAL BRACE elements shall be sized and configured according to the guidlines of section 2.2.1.3.5.
Braces can be steel pipe, steel angle, steel rods, or steel flats.
Section 2.2.1.3.5.A calls for positioning the diagonal brace element(s) at an angle of at least 30° from the vertical.
Note. It is recommended to target a brace angle as close to 45° from the vertical as possible.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Structural attachment—Building attached
Fastener to structure or
component (BAC)
structural adapter

Brace member

Pipe attachment —Pipe attached component (PAC)

Sprinkler pipe

Not allowed:
Angles < 30° from vertical

Locations allowed:
Angles ≥ 30° from verti-
cal
Optimal locations:
Angles at or near 45°
from vertical

SWAY BRACE intended to resist movement perpendicular to the axis of the system piping.
LATERAL BRACE elements shall be sized and configured according to the guidlines of section 2.2.1.3.5.
Braces can be steel pipe, steel angle, steel rods, or steel flats.
Section 2.2.1.3.5.A calls for positioning the diagonal element(s) at an angle of at least 30° from vertical.
Note. It is recommended to target a brace angle as close to 45° from the vertical as possible.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Hanger
with rod stiffener

≤ 6 in. / 0.15m ≤ 6 in. / 0.15m

Hanger
with rod stiffener

≤ 6 in. / 0.15m ≤ 6 in. / 0.15m

For the configurations illustrated above it is required to calculate the net vertical uplift force as described in section
2.2.1.3.5.D.1. If the net vertical lift force is greater than 0 (zero) it is necessary to add vertical reinforcement to resist
the uplift force. The vertical brace, when needed, can either be a brace of the same shape and size of the LATERAL or
LONGITUDINAL brace and connected to the pipe at the same point, without any further calculation, or it can be selec-
ted on the basis of the actual calculated net vertical uplift force.
Although less desirable, the vertical brace may be a hanger that is located no more than 6 in. / 0.15m from the point
of attachment of the LATERAL or the LONGITUDINAL brace. In this case, the hanger must meet the following criteria:
 The hanger has been determined to be able to resist the net vertical resultant load uplift force (which may
necessitate the use of a rod stiffener or other means, but in any case the slenderness ratio between length
and least radius of gyration should not exceed 200),
 The hanger is capable of transferring vertical upward loads and is fastened to the structure by a positive
means of mechanical attachment (such as through bolts, lag screws, or concrete anchors that are properly
sized for the load, and
 The hanger attachment to the fire protection system piping is snug and concentric, with no more than 1/2
in. / 13mm between the top of the piping and the hanger so that excessive movement cannot occur.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
ro = radius of the outside pipe wall of the bracing
pipe

L max
r  ri
2 2

r  o

Section 2.2.1.3.5.B mandates that for braces used to resist both tension and compression the slenderness ratio l/r
(ratio between the length of the brace and its least radius of gyration) does not exceed 200.
For braces used in tension only, (section 2.2.1.3.5.C) mandates the slenderness ratio not to exceed 300.
The table below gives the maximum length L max for braces made of steel pipe based on the schedule and the no-
minal diameter of the pipe used:

Schedule 10
25 1 10.9 [0.43] 1.1 [3.61] 2.2 [7.22] 3.3 [10.83]
32 1 1/4 14.0 [0.55] 1.4 [4.59] 2.8 [9.19] 4.2 [13.78]
40 1 1/2 16.1 [0.63] 1.6 [5.25] 3.2 [10.50] 4.8 [15.75]
50 2 20.4 [0.80] 2.0 [6.56] 4.1 [13.45] 6.1 [20.01]
Schedule 30
25 1 10.5 [0.41] 1.0 [3.28] 2.1 [6.89] 3.1 [10.17]
32 1 1/4 13.5 [0.53] 1.4 [4.59] 2.7 [8.86] 4.1 [13.45]
40 1 1/2 15.6 [0.61] 1.6 [5.25] 3.1 [10.17] 4.7 [15.42]
50 2 19.7 [0.78] 2.0 [6.56] 3.9 [12.80] 5.9 [19.36]
Schedule 40
25 1 10.7 [0.42] 1.1 [3.61] 2.1 [6.89] 3.2 [10.50]
32 1 1/4 13.7 [0.54] 1.4 [4.59] 2.7 [8.86] 4.1 [13.45]
40 1 1/2 15.8 [0.62] 1.6 [5.25] 3.2 [10.50] 4.7 [15.42]
50 2 20.0 [0.79] 2.0 [6.56] 4.0 [13.12] 6.0 [19.69]

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

2.2.6

2.2.5

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6 m

For anchored tanks, when the tank discharge pipe runs horizontally to a pump, provide two flexible couplings on the
pipe between the tank and the pump. Locate one as close to the tank wall as possible and the other within 2 ft / 0.6
m of the pump.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6 m

For anchored tanks, when the tank discharge pipe feeds into an underground main, provide two flexible couplings
between the tank and the ground entrance. Locate one as close to the tank wall as possible. Locate the other within
2 ft / 0.6 m of the ground entrance.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
FOUR WAY brace as for RISERS

Fire pump unit

Provide FOUR-WAY sway bracing the same as for sprinkler system RISERS for any vertical RISER piping that extends
from the pump to discharge through the ceiling to floors above (see section R of this handbook).

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Horizontal overhead piping: LATERAL and LONGITUDINAL
braces same as for horizontal CROSSMAINS/FEEDMAINS

FOUR WAY brace same as for RI-

Fire pump unit

Piping on pipe stands: LATERAL and LONGITU-


DINAL braces same as for CROSSMAINS/

Provide horizontal overhead piping and piping on pipe stands with LATERAL and LONGITUDINAL sway bracing.
Design sway bracing on the same basis as for sprinkler system piping. Make attachments for the sway bracing at
structural elements capable of carrying the seismic loads. (see sections H and V of this handbook).

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Fire pump unit

Discharge piping, no
CLEARANCE provided
around the piping

Suction piping, no CLEA-


RANCE provided around
the piping

Ground

When the pump house rests directly on the ground and suction or discharge piping enters or exits through the floor,
and no CLEARANCE around the piping is provided, flexible couplings are unnecessary because the pump house floor is
not expected to move differentially from the ground.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Fire pump unit

Discharge piping

Suction piping

Ground

When the fire pump and driver, including suction and discharge piping, are located above grade/ground in a building,
provide flexibility on the suction and discharge piping the same as for sprinkler system piping (See sections R and H
of this handbook).

Note: Here, flexibility means providing flexible couplings

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Flexible couplings are not needed for pipe penetrations that feed hose headers or relief valve discharge outlets on an
outside wall.

Provide flexibility on fuel line connections to both the fire pump drivers and the fuel tanks that supply fire pump dri-
vers.

Provide CLEARANCE per section 2.2.1.5.1 around piping penetrations through walls, platforms, mezzanines, roofs, and
floors. (see Section C of this handbook)

Anchor the controller to the floor and/or to the wall to prevent damage to the controller itself, and to prevent
breakage of piping or electrical connections between the controller and other equipment due to differential move-
ments.

Anchor the fuel tanks for internal combustion engines to the support frames, if any, or directly to the supporting floor
and/or wall. Brace the support frames to prevent buckling of the legs and also anchor the frames.

For internal combustion engines, restrain the starter battery sets, brace the battery racks to prevent buckling of the
legs, and anchor the battery racks to prevent sliding and/or overturning that could damage the connections between
batteries or from the battery set to the engine.

Anchor any other unrestrained equipment in the pump house if it exposes any of the fire pump equipment to damage
from impact due to uncontrolled differential movement such as sliding, overturning, or swinging.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

2.2.1.1.2.A
2.2.1.4.3.A

2.2.1.1.2.B
2.2.1.4.3.E

2.2.1.1.4.D.1
2.2.1.4.3.C

2.2.1.1.2.B
2.2.1.4.3.A
2.2.1.4.3.D

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6m
≤ 2 ft / 0.6m

Provide a FOUR-WAY within 2 ft / 0.6 m of the top of the RISER.


For risers directly connected to underground piping, provide a flexible coupling within 2 ft / 0.6 m of the top of each
individual RISERS. This applies to risers located outside and inside buildings.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft. / 0.6m

flexible elbow rigid elbow

≤ 2 ft. / 0.6m ≤ 2 ft. / 0.6m

required
flexible coupling

Provide a FOUR-WAY sway brace within 2 ft / 0.6 m of the top of the RISER. The FOUR-WAY brace may be located either
on the RISER or on the main (see green pipe location in A1).
For risers directly connected to underground piping, provide a flexible coupling within 2 ft / 0.6 m of the top of each
individual RISER. This applies to risers located outside and inside buildings.
Generally speaking a FOUR-WAY brace goes within 2 ft / 0.6 m from a flexible coupling on the RISER.

When possible, avoid the use of manifolded FOUR-WAY sway bracing at the top of multiple adjacent RISERS.
If used, limit the manifolded arrangement to two RISERS, and design an engineered FOUR-WAY bracing system to carry
the total loads for both RISERS.
Note: individual FOUR-WAY sway braces are an acceptable solution.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6m

≤ 2 ft / 0.6m

For RISERS directly connected to underground piping, provide a flexible coupling within 2 ft / 0.6 m of the bottom of
each individual riser. This applies to RISERS located outside and inside buildings.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
LATERAL brace

≤ 3 ft / 0.9 m

≤ 2 ft / 0.6 m

≤ 6 ft / 1.8 m
≥ 6 ft / 1.8 m ≤ 2 ft / 0.6 m

When multiple RISERS are supplied by a single MANIFOLD connection to an underground MAIN, provide each RISER with
a flexible coupling at the top, and a flexible coupling at the bottom where connected to the MANIFOLD within 2 ft / 0.6
m of the horizontal piping. The horizontal MANIFOLD piping must be located no more than 3 ft / 0.9 m above floor
level. The horizontal MANIFOLD must be connected to the main RISER coming from the undergroud supply at floor level
via flanged or other rigid connections. Where welded piping systems exist from the riser through the crossmains, the
flexible coupling at the top of the riser may be omitted.
If the section of horizontal pipe is longer than 6ft / 1.8m, place a LATERAL brace within 2 ft / 0.6m of the end of the
horizontal section.

flexible coupling
LATERAL brace LATERAL brace
flexible coupling beyond the reque-
beyond the reque- sted minimum
sted minimum

≤ 2 ft / 0.6 m ≤ 2 ft / 0.6 m

When there is one or more flexible coupling(s) on either the horizontal manifold piping (B 4) or along the vertical pipe
section between the floor and the connection with the horizontal portion (B 5), place a LATERAL sway brace within 2 ft /
0.6m of the end of the horizontal section of the pipe.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Interval between FOUR-WAY bra-

Interval between FOUR-WAY bra-


ces ≤ 40 ft / 12.2m

ces ≤ 40 ft / 12.2m
≤ 2 ft / 0.6m
≤ 2 ft / 0.6m
Interval between FOUR-WAY

Interval between FOUR-WAY


braces ≤ 40 ft / 12.2m

braces ≤ 40 ft / 12.2m

Position intermediate FOUR-WAY sway bracing at an interval not to exceed 40 ft / 12.2m.


Provide a flexible coupling within 2 ft / 0.6 m above or below any intermediate points of lateral restraint for RISERS.

Where welded piping systems exist from the RISER through the CROSSMAINS, these flexible couplings may be omitted.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6m

≤ 2 ft / 0.6m

≤ 2 ft / 0.6m

When flexible couplings are used on risers, provide FOUR-WAY sway bracing so a brace is provided within 2 ft / 0.6 m
of every other flexible coupling.
Correct solution: C2; Incorrect solution: C3.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

Position intermediate FOUR-WAY sway bracing at an interval not to exceed 40 ft / 12.2 m. FOUR-WAY sway bracing
consists of two LATERAL braces.
Provide a flexible coupling within 2 ft / 0.6 m below or above the intermediate FOUR-WAY sway bracing as the four-
way bracing constitutes an intermediate point of lateral restraint for the risers.

ANY RESTRICTION OR ANY RESTRICTION OR


OBSTACLE TO LATERAL OBSTACLE TO
MOVEMENT LATERAL MOVEMENT

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

Provide a flexible coupling within 2 ft / 0.6 m above or below any intermediate points of lateral restraint for RISERS.
Where welded piping systems exist from the RISER through the CROSSMAINS, these flexible couplings may be omitted.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6m
≤ 2 ft / 0.6m

≤ 2 ft / 0.6m
≤ 2 ft / 0.6m

Interval between FOUR-WAY braces ≤ 40 ft / 12.2m


≤ 1 ft / ≤ 1 ft /

Interval between FOUR-WAY braces ≤ 40 ft / 12.2m


0.3m 0.3m

MAIN between
floors

≤ 1 ft / ≤ 1 ft /
0.3m 0.3m
WAY braces ≤ 40 ft. / 12.2
Interval between FOUR-

≤ 2 ft / ≤ 2 ft /
0.6m 0.6m

In multistory buildings, provide a FOUR-WAY at each floor having a supply MAIN.


When a RISER passes through a structural floor, and CLEARANCES do not exceed the minimums per 2.2.1.5, a FOUR-
WAY brace is considered to exist at this point (i.e. the floor is the four-way brace).
Provide intermediate FOUR-WAY way bracing at an interval not to exceed 40 ft / 12.2 m.
For multistory building RISERS where CLEARANCES meet the recommendations of 2.2.1.5.1, an additional flexible cou-
pling is needed at each floor level within 1ft / 0.3 m of the floor (either above or below the floor).

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
flexible coupling flexible coupling
CLEARANCE that
meets the re- CLEARANCE smaller
commendations than recommen-
of 2.2.1.5.1 ≤ 1 ft / 0.3 m ded by 2.2.1.5.1 ≤ 1 ft / 0.3 m

start of MAIN supply Start of MAIN supply

alternative
location for flexible coupling
the flexible below the start of
coupling the horizontal

CLEARANCE that
meets the re- CLEARANCE smaller
commendations than recommen-
of 2.2.1.5.1 ≤ 1 ft / 0.3 m ded by 2.2.1.5.1 ≤ 1 ft / 0.3 m

≤ 1 ft / 0.3 m

; ;

In multistory buildings, place a FOUR-WAY brace along


the RISER at each floor where there is a MAIN. In multistory buildings, place a FOUR-WAY brace along
FOR RISERS servicing multistory buildings, where clea- the RISER at each floor where there is a MAIN.
rances meet the recommendations of 2.2.1.5.1, provi- For RISERS servicing multistory buildings, where clea-
de an additional flexible coupling at each floor level rances do not meet the recommendations of
within 1 ft / 0.3 m either above or below the floor. 2.2.1.5.1, provide additional flexible couplings at
When locating the flexible coupling below the floor, in each floor level within 1 ft / 0.3 m above and below
the case of a MAIN supply under a floor, locate the the floor.
flexible coupling below that MAIN (regardless of the In the case of a MAIN supply under a floor, locate the
distance from the floor above). flexible coupling below that MAIN (regardless of the
distance from the floor).

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
flexible coupling flexible coupling
CLEARANCE that CLEARANCE smaller
meets the re- than recommen-
commendations ded by 2.2.1.5.1
of 2.2.1.5.1 ≤ 1 ft / 0.3 m ≤ 1 ft / 0.3 m

≤ 1 ft / 0.3 m

CLEARANCE that flexible coupling flexible coupling


CLEARANCE smaller
meets the re-
than recommen-
commendations
ded by 2.2.1.5.1
of 2.2.1.5.1 ≤ 1 ft / 0.3 m ≤ 1 ft / 0.3 m

≤ 1 ft / 0.3 m

For RISERS servicing multistory buildings, where CLEA- For RISERS servicing multistory buildings, where CLEA-
RANCES meet the recommendations of 2.2.1.5.1, RANCES do not meet the recommendations of
provide a flexible couplings at each floor level within 2.2.1.5.1, provide additional flexible couplings at
1 ft / 0.3 m either above or below the floor. each floor level within 1 ft / 0.3 m above and below
the floor.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
CLEARANCE that
meets the re-
commendations Maximum space
of 2.2.1.5.1 allowed from the
floor ≤ 1 ft / 0.3m

The CLEARANCE at the crossing of the floor meets the


minimum required by 2.2.1.5.1, but the flexible cou-
pling has been positioned at a distance of more than
1 ft / 0.3 m from the floor.

CLEARANCE smaller CLEARANCE smaller


than than
recommended by recommended by
2.2.1.5.1 2.2.1.5.1

La CLEARANCE at the crossing of the floor does not meet the minimum requirement of 2.2.1.5.1 and the then manda-
ted flexible couplings have not been provided (illustrations D5 and D6).

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

2.2.1.1.4.D.1 2.2.1.1.4.D.2 2.2.1.1.4.A 2.2.1.1.4.B


2.2.1.1.4.D.3 2.2.1.1.4.C.2

2.2.1.1.4.D 2.2.1.4.4.D 2.2.1.1.4.C.1

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Intervals between LONGITUDINAL bra-
ces ≤ 80 ft / 24.4 m

Intervals between LATERAL


braces ≤ 40 ft / 12.2 m
Intervals between LATERAL bra-
ces ≤ 40 ft / 12.2 m
Intervals between LATERAL bra-
ces ≤ 40 ft / 12.2 m

In straight runs, the SWAY BRACES must be positioned as follows:


 maximum distance between two LATERAL BRACES ≤ 40 ft / 12.2m;
 maximum distance between two LONGITUDINAL BRACES ≤ 80 ft / 24.4m

LONGITUDINAL

LATERAL

LONGITUDINAL and LATERAL SWAY BRACE.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 40 ft / 12.2 m between LATERAL braces

≤ 80 ft / 24.4 m between LONGITUDINAL braces

A FOUR-WAY brace on a vertical pipe of the same or larger diameter than the CROSSMAIN may be counted as the initial
LATERAL and as the initial LONGITUDINAL braces for the CROSSMAIN.
The FOUR-WAY brace must be located within 2 ft / 0.6 m of the horizontal pipe and its design load should include the
tributary loads from both the vertical and the horizontal pipes.

≤ 2 ft / 0.6 m

A FOUR-WAY brace on a vertical FEEDMAIN/CROSSMAIN or on a RISER of the same or bigger diameter may be counted as
the initial LATERAL and LONGITUDINAL brace for the attached FEEDMAIN/CROSSMAIN when the brace is located within 2
ft / 0.6 m of the horizontal pipe, if the design load for this FOUR-WAY brace includes the tributary loads from both
the vertical and the horizontal pipes.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
LATERAL brace within 6 ft / 1.8 m

LONGITUDINAL brace within 40 ft / 12.2 m

LONGITUDINAL brace within 40 ft / 12.2 m


LONGITUDINAL brace within 40 ft / 12.2 m
LATERAL brace within 6 ft / 1.8 m

LATERAL brace within 6 ft / 1.8 m

At the end of a horizontal pipe run, there must be:


 One LATERAL brace within 6 ft / 1.8 m of the end of the pipe;
 One LONGITUDINAL brace within 40 ft / 12.2 m of the end of the pipe.
Seismic separation joints must be considered as ends of pipe.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 6 ft / 1.8 m

≤ 40 ft / 12.2 m

≤ 6 ft / 1.8

≤ 40 ft / 12.2 m

Seismic separation assemblies are considered the end of the piping on both sides of the assembly.
Install a LATERAL sway brace within 6 ft / 1.8 m and a LONGITUDINAL sway brace within 40 ft / 12.2 m of both sides of
the SEISMIC SEPARATION ASSEMBLY.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 6 ft / 1.8 m

≤ 40 ft / 12.2 m

≤ 6 ft / 1.8 m

≤ 40 ft / 12.2 m

Seismic separation assemblies are considered the end of the piping on both sides of the assembly.
Install a LATERAL sway brace within 6 ft / 1.8 m and a LONGITUDINAL sway brace within 40 ft / 12.2 m of both sides of
the SEISMIC SEPARATION ASSEMBLY.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Distance of LATERAL brace from coupling ≤ 2 ft / 0.6 m

Distance of LATERAL brace from coupling ≤ 2 ft / 0.6 m

When more flexible couplings than recommended are installed on feedmains or crossmains, install an additional LATE-
RAL brace at every other flexible coupling within 2 ft / 0.6 m of the flexible coupling.

Correct solution (D2) and incorrect solution (D3).

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Run Y Run X Run Y Run X

LONGITUDINAL brace for the run Y: within 2 ft / 0.6 m LATERAL brace for the run Y: within 2 ft / 0.6 m

A LATERAL [LONGITUDINAL] brace within 2 ft. / 0.6 m of the end of a FEEDMAIN or CROSSMAIN piping connection (run X) to
another main that is perpendicular and of the same or lesser diameter (run Y) may be used to also act as a LONGITUDI-
NAL [LATERAL] brace for the perpendicular main.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Run Y Run Y
Run X Run X

≤ 2 ft / 0.6 m ≤ 2 ft / 0.6 m

Run X

Run X

≤ 2 ft / 0.6 m
Run Y
≤ 2 ft / 0.6 m
Run Y

A LATERAL [LONGITUDINAL] brace within 2 ft. / 0.6 m of the end of a FEEDMAIN or CROSSMAIN piping connection (run X) to
another main that is perpendicular and of the same or lesser diameter (run Y) may be used to also act as a LONGITUDI-
NAL [LATERAL] brace for the perpendicular main.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Installing the SWAY BRACES on a FEEDMAIN/CROSSMAIN of smaller diameter than the one being braced is not allowed.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m
CROSSMAIN Run ≥ 6 ft / 1.8 m
CROSSMAIN Run ≥ 6 ft / 1.8 m

At a horizontal change of direction, when the CROSSMAIN run adjacent to the change of direction is 6 ft / 1.8 m or
longer, a LATERAL and a LONGITUDINAL sway braces are required within 2 ft / 0.6 m of the change of direction.

Crossmain run < 6 ft / 1.8

Run length
< 6 ft / 1.8 m

When the CROSSMAIN/FEEDMAIN runs adjacent to the horizontal direction change are shorter than 6 ft / 1.8 m, additio-
nal SWAY BRACE at the change of direction are not required.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Any length Any length

≤ 2 ft / 0.6

≤ 2 ft / 0.6 m

When flexible couplings are present at a horizontal change of direction, an additional LATERAL sway brace must be
installed within 2 ft / 0.6 m of the change of direction, regardless of the length of the pipe run adjacent to the change
in direction.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Run length Run length
≥ 6 ft / 1.8 m ≥ 6 ft / 1.8 m

≤ 2 ft / 0.6 m
≤ 2 ft / 0.6 m
≤ 2 ft / 0.6 m

The CROSSMAIN/FEEDMAIN runs longer than 6 ft / 1.8 m adjacent to changes of direction are required to have a LATE-
RAL and a LONGITUDINAL sway braces within 2 ft / 0.6 m of the change of direction.
If the CROSSMAIN/FEEDMAIN diameter decreases at the change of direction, locate the SWAY BRACES on the run with the
larger diameter.

≤ 2 ft / 0.6 m ≤ 2 ft / 0.6 m ≤ 2 ft / 0.6 m ≤ 2 ft / 0.6 m

Run length ≥ 6 ft / 1.8 m Run length ≥ 6 ft / 1.8 m

Alternative solutions made with two LATERAL braces, Alternative solutions made with two LONGITUDINAL
one of which works as a LONGITUDINAL brace for the braces, one of which works as a LATERAL brace for
perpendicular run. the perpendicular run.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Run length
Run length < 6 ft /1.8 m
< 6 ft /1.8 m
Crossmain run
< 6 ft / 1.8 m

When the CROSSMAIN/FEEDMAIN runs adjacent to horizontal direction changes are shorter than 6 ft / 1.8 m, additional
SWAY BRACES at the changes of direction are not required.

Additional LATERAL Additional LATERAL

Excessive flexible coupling Excessive flexible coupling

≤ 2 ft / 0.6 m
≤ 2 ft / 0.6 m
≤ 2 ft / 0.6 m

When the pipe connection at changes in direction is made using flexible couplings, an additional LATERAL brace must
be inserted within 2 ft / 0.6 m of the change of direction, regardless of the length of the adjacent pipe run. If there is
no change in pipe diameter at the change of direction, the LATERAL brace can be indifferently located on either of the
two runs as long as it is within 2 ft / 0.6 m limit from the change of direction. On the other hand, if there is a change
in pipe diameter, then the LATERAL brace must be located on the pipe with the larger diameter.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
CLEARANCE does not meet
CLEARANCE meets the
the recommendations of
recommendations of
2.2.1.5.1 - Solution inclu-
2.2.1.5.1
ding flexible couplings

When the CROSSMAIN/FEEDMAIN penetrates through a wall made of non-breakable / frangible material and the CLEA-
RANCE does not meet the recommendations indicated in Section 2.2.1.5.1, flexible couplings must be installed on
both sides of the wall at a distance less than or equal to 1 ft / 0.3m from the wall itself.
Where the piping systems are welded from the RISERS through the CROSSMAINS, these flexible couplings may be omit-
ted.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 1 ft / 0.3 m ≤ 1 ft / 0.3 m

CLEARANCE that
does not meet the
recommendations of
2.2.1.5.1

When the FEEDMAIN/CROSSMAIN crosses a wall made of non-breakable / frangible material and the CLEARANCE does
not meet the recommendations indicated in Section 2.2.1.5.1, flexible couplings must be installed on both sides of
the wall at a distance less than or equal to 1 ft / 0.3 m from the wall itself.
Where the piping systems are welded from the RISER through the CROSSMAINS, these flexible couplings may be omit-
ted.

≤ 1 ft / 0.3 m ≤ 1 ft / 0.3 m ≤ 1 ft / 0.3 m ≤ 1 ft / 0.3 m

CLEARANCE that CLEARANCE that


does not meet the does not meet the
recommendations recommendations
of 2.2.1.5.1 of 2.2.1.5.1

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
A properly sized and attached U-bolt that fastens the CROSSMAIN/FEEDMAIN directly to, and holds the CROSSMAIN/
FEEDMAIN tightly against, a structural supporting member may be used as a LATERAL brace.

Do not use U-hangers, including wraparound types, as LATERAL brace for FEEDMAINS and CROSSMAINS.

For FEEDMAINS and CROSSMAINS, do not omit LATERAL braces even if the pipes are individually supported by short han-
ger rods.

Do not consider any SWAY BRACE on the BRANCH LINES as providing LATERAL or LONGITUDINAL sway bracing to the
FEEDMAINSand CROSSMAINS.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

2.2.1.1.3
2.2.1.4.4.B

2.2.1.4.4.D

2.2.1.1.3.A
2.2.1.4.4.A

2.2.1.1.3
2.2.1.4.4.B

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

For vertical CROSSMAINS or FEEDMAINS with pipe runs of 6 ft / 1.8 m or more, provide a FOUR-WAY brace at the top and
at the bottom of the vertical run. The FOUR-WAY should be located on the pipe with the larger diameter within 2 ft /
0.6 m of the piping turn/connection.

A flexible coupling should also be located at the top of the vertical pipe run within 2 ft / 0.6 m of the end of the pipe.
Where welded piping systems exist from the RISER through the CROSSMAINS, these flexible couplings may be omitted.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6 m

< 6 ft / 1.8 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

< 6 ft / 1.8 m < 6 ft / 1.8 m

≤ 2 ft / 0.6 m

For vertical CROSSMAINS or FEEDMAINS less than 6 ft / 1.8 m long without FOUR-WAY brace, flexible couplings should
not be present within the vertical pipe runs, piping turns/connections included.
If flexible couplings are used or needed to satisfy flexibility recommendations at one or both turns/connections, then
provide FOUR-WAY bracing within 2 ft / 0.6 m of each turn equipped with flexible coupling(s).

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

For vertical CROSSMAINS or FEEDMAINS with runs of 6 ft / 1.8 m or more, provide a FOUR-WAY brace at the top of the
vertical run. The FOUR-WAY brace should be located on the pipe with the larger diameter within 2 ft / 0.6 m of the
piping turn/connection.

Provide also a flexible coupling at the top of the vertical pipe run within 2 ft / 0.6 m of the end of the pipe. Where wel-
ded piping systems exist from the RISER through the CROSSMAINS, these flexible couplings may be omitted.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

Note: Locating the FOUR-WAY on the smaller pipe is


acceptable if the larger pipe load is not included in
the zone of influence and the larger pipe is braced
independently.

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

For vertical crossmains or feedmains with pipe runs of 6 ft / 1.8 m or more, provide a four-way brace at the bottom
of the vertical run. Install the four-way brace on the pipe with the larger diameter within 2 ft / 0.6 m of the piping turn/
connection.
Provide also a flexible coupling at the bottom of the vertical pipe run within 2 ft / 0.6 m of the beginning of the pipe.
Where welded piping systems exist from the riser through the crossmains, these flexible couplings may be omitted.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Vertical run length ≥ 6 ft / 1.8 m

Interval between

≤ 40 ft / 12.2 m
FOUR-WAYS
Interval between

≤ 40 ft / 12.2 m
FOUR-WAYS

Locate intermediate FOUR-WAY bracing like for RISERS: maximum distance between two FOUR-WAY braces not to ex-
ceed 40 ft / 12.2 m; When there are excessive flexible couplings, locate one FOUR-WAY brace every other flexible
coupling; In multistory buildings, locate a FOUR-WAY brace at every floor in which a horizontal CROSSMAIN/FEEDMAIN
branches out; When a RISER passes through a structural floor, and clearances do not exceed the minimum per
2.2.1.5.1., a FOUR-WAY brace is considered to exist at this point. (Refer to the R section of this handbook for further
details.)
Install a flexible coupling within 2 ft / 0.6 m above or below intermediate points of lateral restraints for vertical pipe.
Where the RISER through CROSSMAINS piping system is welded, this flexible coupling can be omitted.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
CLEARANCE that does
not meet the
recommendations in
2.2.1.5.1. CLEARANCE that meets
Solution with insertion the recommendations
of flexible couplings. in 2.2.1.5.1.

Where vertical FEEDMAINS/CROSSMAINS penetrate through a floor made of non-breakable material (structural floor)
and CLEARANCES per Section 2.2.1.5.1 are not provided, install flexible couplings on both sides of the floor at no more
than 1 ft / 0.3 m from the floor itself.
Where the piping systems is welded from the RISER through the CROSSMAINS , these flexible couplings may be omit-
ted.

CLEARANCE re-
quirements not
met
< 1 ft / 0.3 m

< 1 ft / 0.3 m

Where vertical FEEDMAINS/CROSSMAINS penetrate a floor made of non-breakable material and CLEARANCES per
Section 2.2.1.5.1 are not provided, install flexible couplings ought on both sides of the floor at no more than 1 ft / 0.3
m from the floor itself.
Where the piping systems is welded from the RISER through the CROSSMAINS, these flexible couplings may be omitted.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

2.2.1.1.5.A.2 2.2.1.1.5.A.7 2.2.1.1.5.A.10 2.2.1.1.5.A.8


2.2.1.1.5.B.1 2.2.1.1.5.B.3 2.2.1.1.5.B.6 2.2.1.1.5.B.4

2.2.1.1.5.A.6.a 2.2.1.1.5.A.3 2.2.1.1.5.A.9


2.2.1.1.5.B.2 2.2.1.1.5.B.5

BRANCH LINES that are less than 2-1⁄2 in. / 65 mm in diameter do not require SWAY BRACES.

BRANCH LINES that are 2-1⁄2 in. / 65 mm or more in diameter do require SWAY BRACES.
For BRANCH LINES that are less than 4 in. / 100 mm in diameter, LATERAL sway bracing is not needed on pipes indivi-
dually supported by rods that meet the following criteria:
- All rods have a length less than 6 in. / 150 mm from the supporting member attachment to the top of the branch
line, and
- There is no more than 1⁄2 in. / 13 mm of space between the top of the BRANCH LINE piping and the bottom of the
support rod.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Intervals between LONGITUDINAL bra-
ces ≤ 80 ft / 24.4m

Intervals between LATERAL bra-


ces ≤ 40 ft / 12.2m
Intervals between LATERAL
braces ≤ 40 ft / 12.2m
Intervals between LATERAL bra-
ces ≤ 40 ft / 12.2m

Provide SWAY BRACES on straight runs of pipe spaced at the following maximum:
 Maximum interval between LATERAL braces ≤ 40 ft / 12.2 m;
 Maximum interval between LONGITUDINAL braces ≤ 80 ft / 24.4 m

LONGITUDINAL and LATERAL SWAY BRACE.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6 m

A FOUR-WAY brace on a vertical pipe (e.g. at the bottom of a DROP) may be counted as the initial LATERAL and LONGITU-
DINAL braces for the attached horizontal branch line of the same or smaller diameter when the brace is located within
2 ft / 0.6 m of the horizontal pipe and when the design load for this FOUR-WAY brace includes the tributary loads from
both the vertical and the horizontal pipes.

20 ft / 6.1 m ≤ space to first LONGITUDINAL brace ≤ 80 ft / 24.4m

10 ft / 3.1 m ≤ space to first LATERAL brace ≤ 40 ft / 12.2 m

Locate the first LATERAL sway bracing no closer than 10 ft / 3.1 m nor greater than 40 ft / 12.2 m from the branch line
connection to the CROSSMAIN. This distance must be calculated including all vertical and horizontal BRANCH LINES
section lengths.
Locate the first LONGITUDINAL sway bracing no closer than 20 ft / 6.1 m nor greater than 80 ft / 24.4 m from the
branch line connection to the CROSSMAIN. This distance must be calculated including all vertical and horizontal
BRANCH LINES section lengths starting from the connection with the CROSSMAIN.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
LONGITUDINAL brace within ≤ 40 ft / 12.2 m

LATERAL brace within ≤ 6 ft / 1.8 m

LONGITUDINAL brace within ≤ 40 ft / 12.2 m


LONGITUDINAL brace within ≤ 40 ft / 12.2 m

LATERAL brace LATERAL


within 6 ft / 1.8m brace wi-
thin 6 ft /

For dead-end BRANCH LINES, locate the last LATERAL brace not more than 6 ft / 1.8 m from the end; Consider seismic
separation assemblies as the end of the piping on both sides of the assembly.
Locate the last LONGITUDINAL brace not more than 40 ft / 12.2 m from the end; Consider seismic separation assem-
blies as the end of the piping on both sides of the assembly.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Flexible cou-
plings

Flexible cou-
plings

Flexible cou-
plings

space between LATERAL brace and coupling ≤ 2 ft / 0.6 m

space between LATERAL brace and coupling ≤ 2 ft / 0.6 m

When more flexible couplings than recommended in Section 2.2.1.4 are installed on straight pipe runs, provide addi-
tional LATERAL sway bracing within 2 ft / 0.6 m of every other flexible coupling.

Additional LATERAL sway


brace required by the flexible
coupling

≤ 2 ft / 0.6m

When more flexible couplings than recommended in


Section 2.2.1.4 are installed on straight pipe runs,
provide additional LATERAL sway bracing within 2 ft /
0.6 m of every other flexible coupling.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6m ≤ 2 ft / 0.6m

A LATERAL [LONGITUDINAL] brace located within 2 ft / 0.6 m of the end of a BRANCH LINE connection to another branch
line that is perpendicular and of the same or lesser diameter may be used to also act as a LONGITUDINAL [LATERAL]
brace for the perpendicular branch line as long as the sway brace design loads include the tributary lateral and longi-
tudinal loads for the braced branch lines.

LATERAL brace used as acting LONGITUDI-


NAL brace for the perpendicular branch LONGITUDINAL brace used as acting LATE-
line RAL brace for the perendicular branch line

≤ 2 ft / 0.6m ≤ 2 ft / 0.6m

Pipe run with same or lesser diameter than that Pipe run with same or lesser diameter than
of the pipe run onto which the LATERAL brace is that of the pipe run onto which the LONGITUDI-
located NAL brace is located

A LATERAL [LONGITUDINAL] brace located within 2 ft / 0.6 m of the end of a BRANCH LINE connection to another branch
line that is perpendicular and of the same or lesser diameter may be used to also act as a LONGITUDINAL [LATERAL]
brace for the perpendicular branch line as long as the sway brace design loads include the tributary lateral and longi-
tudinal loads for the braced branch lines.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
distance to first LONGITUDINAL brace ≤ 40 ft / 12.2 m

flexible cou-
plings

≤ 2 ft / 0.6m
distance to first LATERAL brace ≤ 6 ft / 1.8 m

Locate the first LATERAL brace not more than 6 ft / When more flexible couplings than recommended in
1.8 m from horizontal changes in direction. Section 2.2.1.4 are installed at changes in horizontal
Locate a LONGITUDINAL brace not more than 40 ft / pipe direction, provide an additional LATERAL sway
12.2m from horizontal changes in direction. bracing within 2 ft / 0.6 m of every flexible coupling
installed.

flexible coupling not re-


quired by 2.2.1.4

≤ 2 ft / 0.6 m
≤ 2 ft / 0.6 m

When more flexible couplings than recommended in Section 2.2.1.4 are installed at changes in horizontal pipe direc-
tion, provide an additional LATERAL sway bracing within 2 ft / 0.6 m of every flexible coupling installed.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
A properly sized and attached U-bolt that fastens the pipe directly to, and holds the pipe tightly against, a structural
supporting member may be used as a LATERAL brace.

Wraparound U-hangers may be used as LATERAL sway bracing for BRANCH LINES if they meet the criteria
per Section 2.2.1.3.4.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

2.2.1.4.6.B

2.2.1.4.6.B

2.2.1.4.6.B

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
FOUR-WAY brace
(Only if required for the overhead piping)

≤ 2 ft / 0.6m

For pipe DROPS that exceed 2 ft / 0.6 m in length, provide a flexible coupling within 2 ft / 0.6 m of the connection to
overhead piping or armovers.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
FOUR-WAY brace
(Only if required for
the overhead piping)
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

FOUR-WAY brace
(Only if required for the overhead piping)
≤ 2 ft / 0.6 m

Provide a flexible coupling within 2 ft / 0.6 m of the connection to armovers for pipe DROPS that exceed 2 ft / 0.6 m in
length.
No flexible couplings are needed on the armover itself.
Provide hangers of the type that resist upward vertical movement as per 2.2.1.8.1.B.

Provide hangers of the type that resist upward vertical movement at the following locations:
1. On all armovers to vertical pipe drops that supply more than one sprinkler, regardless of the length of the armover,
located within 2 ft / 0.6 m of the drop.
2. On all armovers greater than 2 ft / 0.6 m long that supply one sprinkler, located within 2 ft / 0.6 m of the drop
Note that for very long armovers, hangers in addition to those recommended below will be needed when normal
hanger spacing rules apply.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Provide a FOUR-WAY brace at the end
of the DROP within 2 ft / 0.6m of the
Tee connection

≤ 2 ft / 0.6m

Provide a FOUR-WAY brace at the end


of the DROP within 2 ft / 0.6m of the
elbow connection

≤ 2 ft / 0.6m

Provide flexible coupling(s) on the horizontal portion within 2 ft / 0.6 m of any tee or elbow connectiing pipe DROPS to
sprinkler piping.
Flexible couplings may be omitted on pipe DROPS that supply a single sprinkler.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
FOUR-WAY brace
(Only if required for the overhead piping)

≤ 2 ft / 0.6 m
Required flexible coupling

Required flexible coupling if


there exist a point of lateral
restraint

Provide a FOUR-WAY brace at the end


of the DROP within 2 ft / 0.6 m of the
Tee connection ≤ 2 ft / 0.6 m

Point of lateral restraint

≤ 2 ft / 0.6 m

Alternative brace locations

≤ 2 ft / 0.6 m ≤ 2 ft / 0.6 m

Provide a flexible coupling within 2 ft / 0.6 m above and/or below any intermediate points of lateral restraint to the
pipe DROPS when needed to accommodate differential movement.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
FOUR-WAY brace
(Only if required for the overhead piping)

≤ 2 ft / 0.6m

Required flexible coupling if there exist a


point of lateral restraint

Provide a FOUR-WAY brace at the end


of the DROP within 2 ft / 0.6m of the
elbow connection ≤ 2 ft / 0.6m

Point of lateral restraint

≤ 2 ft / 0.6m

≤ 2 ft / 0.6m

Provide a flexible coupling within 2 ft / 0.6 m above and/or below any intermediate points of lateral restraint to the
pipe DROPS when needed to accommodate differential movement.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

2.2.1.4.5.A 2.2.1.4.5.D
2.2.1.4.5.G

2.2.1.4.5.E

2.2.1.4.5.F

2.2.1.4.5.A

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6 m
≤ 2 ft / 0.6 m

Provide flexible couplings within 2 ft / 0.6 m of the top of each in-rack sprinkler system RISER, both in cases where
the RISER is attached directly to the ceiling sprinkler system RISER, and where the in-rack sprinkler system RISER is
attached directly to the underground piping.
Where the piping systems is welded from the RISER through the CROSSMAINS, the flexible coupling at the top of the
riser may be omitted.
Refer to the R section of this handbook to locate the FOUR-WAY braces.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
In-rack sprinkler system
RISER

≤ 2 ft / 0.6m

In cases where the in-rack sprinkler system RISER is attached directly to the underground piping, provide flexible cou-
plings within 2 ft. / 0.6 m of the bottom of each in-rack sprinkler system RISER.

In-rack sprinkler system Ceiling sprinkler sy-


RISER stem RISER

Flexible coupling
within 2 ft / 0.6m of
the connection ≤ 2 ft / 0.6m

In cases where the in-rack sprinkler system RISER is attached directly to the ceiling sprinkler system riser, provide
flexible couplings within 2 ft. / 0.6 m of the connection of each in-rack sprinkler system RISER.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
RISER for ceiling
sprinklers
RISER for In-Rack
sprinklers

≤ 2 ft /
0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

Provide flexible couplings within 2 ft / 0.6 m of the bottom of in-rack sprinkler systems RISERS, both in case where the
RISER is attached directly to the underground piping and where it is attached directly to the ceiling sprinkler system
RISER.
In cases where the in-rack sprinkler system RISER is attached to the ceiling sprinkler system RISER, provide a flexible
coupling on the in-rack sprinkler system RISER within 2 ft / 0.6 m of the connection.
Provide also a flexible coupling within 2 ft / 0.6 m of the bottom of the RISER for the ceiling sprinkler system.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Overhead MAIN

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m
≤ 2 ft / 0.6 m

Provide a FOUR-WAY brace within 2 ft / 0.6 m of the connection of pipe DROPS to the overhead feed piping.
Provide a flexible coupling within 2 ft / 0.6 m of the connection of pipe DROPS to the overhead feed piping.
Provide a flexible coupling within 2 ft / 0.6 m above the initial in-rack sprinkler pipe DROP attachment to the rack.
Provide flexible coupling(s) on the horizontal portion of in-rack sprinkler piping within 2 ft / 0.6 m of the connections to
vertical pipe DROPS .
Note: The pipe DROP attachments to the rack act as FOUR-WAY braces.
Note: The first pipe DROP attachment to the rack should be located as low as possible in order to allow for the maxi-
mum flexibility in the DROP.
Note: Bracing should be located along the in-rack horizontal sprinkler piping as for BRANCH LINES.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Overhead MAIN

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

Provide a FOUR-WAY brace within 2 ft / 0.6 m of the connection of pipe DROPS to the overhead feed piping.
Provide a flexible coupling within 2 ft / 0.6 m of the connection of pipe DROPS to the overhead feed piping.
Provide a flexible coupling within 2 ft / 0.6 m above the initial in-rack sprinkler pipe DROP attachment to the rack.
Provide flexible coupling(s) on the horizontal portion of in-rack sprinkler piping within 2 ft / 0.6 m of the connections to
vertical pipe DROPS.

Note: The pipe DROP attachments to the rack act as FOUR-WAY braces.

Note: The first pipe DROP attachment to the rack should be located as low as possible in order to allow for the ma-
ximum flexibility of the DROP.

Note: Bracing should be located along the in-rack horizontal sprinkler piping as for BRANCH LINES.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

Overhead MAIN

≤ 2 ft / 0.6 m

Provide a four-way brace within 2 ft / 0.6 m of the connection of pipe drops to the overhead feed piping.
Provide a flexible coupling within 2 ft / 0.6 m of the connection of pipe drops to the overhead feed piping.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

Provide a FOUR-WAY brace within 2 ft / 0.6 m of the connection of pipe DROPS to the overhead feed piping.
When pipe DROPS supplying in-rack sprinklers are connected to overhead horizontal piping via an armover, provide a
flexible coupling within 2 ft / 0.6 m of the connection of the pipe DROPS to the armover. No flexible couplings are nee-
ded on the armover.
However, provide a hanger of the type that will resist vertical upward movement per 2.2.1.8.1.B.

Provide hangers of the type that resist upward vertical movement at the following locations:
1. On all armovers to vertical pipe DROPS that supply more than one sprinkler, regardless of the length of the armover,
located within 2 ft / 0.6 m of the DROP.
2. On all armovers greater than 2 ft / 0.6 m long that supply one sprinkler, located within 2 ft / 0.6 m of the DROP
Note that for very long armovers, hangers in addition to those recommended below will be needed when normal
hanger spacing rules apply.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
First point of attachment
of the DROP to the rack

≤ 2 ft / 0.6 m

Pipe run to in-rack


sprinklers
≤ 2 ft / 0.6 m

≤ 2 ft / 0.6 m

First point of attachment


of the DROP to the rack

≤ 2 ft / 0.6 m

Pipe run to in-rack sprinklers


≤ 2 ft / 0.6 m

Provide a flexible coupling within 2 ft / 0.6 m above the initial in-rack sprinkler pipe DROP attachment to the rack.
Provide flexible coupling(s) on the horizontal portion of in-rack sprinkler piping within 2 ft / 0.6 m of the connections to
vertical pipe DROPS.
Note: The pipe DROP attachments to the rack act as FOUR-WAY braces.
Note: The first pipe DROP attachment to the rack should be located as low as possible in order to provide maximum
flexibility in the DROP.
Note: Bracing should be located along the in-rack horizontal sprinkler piping same as BRANCH LINES (refer to section
B of this handbook for further details)

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Provide a seismic separation assembly (SSA) where any piping crosses a building seismic expansion joint.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
OVERVIEW

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
 All galvanized product line

 Works in conjunction with the CADDY bracing calculator for projects per FM guidelines and NFPA13 standard

 FM approved, all products tested and listed for FM projects world wide

 Innovative products minimize installation time

 Easy to inspect: snap-off bolt head enables easy installation and inspection

 Fastest to install sway braces

 Fewer tool changes: requires only one size wrench for installation on most products

 Minimized loose parts

 ASTM SCH40

 AS1074 H

 EN 10255 H

 GBT 3091

 JIS 3454

 ASTM SCH40  ASTM SCH10  LIGHTWALL

 AS1074 H  AS1074 M  AS1074 L

 EN 10255 H  EN 10255 M  EN 10255 L

 GBT 3091  JIS 3452  EN 10220

 JIS 3454  GBT 8163

 CSB CADDY Sway Brace

 EZU, STU, QG, S1A, ETC. Product type: Easy Universal, STandard Universal, Quick Grip,
Structural size 1 Assembly

 #### Pipe size, e.g. 0150 = 1 1/2” pipe

 EG, HD Finish (Electro-Galvanized / Hot Dipped galvanized)

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Universal for lateral and longitudinal braces

Pipe to brace: Brace pipe:


in. 1 1¼ 1½ 2 2½ 3 4 5 6 8 10 in. 1 1¼ 1½ 2
DN 25 32 40 50 65 80 100 125 150 200 250 DN 25 32 40 50

Product information is available at erico.pentair.com

Available October 2017.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Pipe to brace: Brace pipe:
in. 1 1¼ 1½ 2 in. 1 1¼
DN 25 32 40 50 DN 25 32

Product information is available at erico.pentair.com

Replace this picture with updated


one with bolts all the way to pipe

Pipe to brace: Brace pipe:


in. 2½ 3 4 6 8 in. 1 1¼
DN 65 80 100 150 200 DN 25 32

Product information is available at erico.pentair.com

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Pipe to brace: Brace pipe:
in. 1 1¼ 1½ 2 2½ 3 4 5 6 in. 1 1¼ 1½ 2
DN 25 32 40 50 65 80 100 125 150 DN 25 32 40 50

Product information is available at erico.pentair.com

Pipe to brace: Brace pipe:


in. 1 1¼ 1½ 2 2½ 3 4 5 6 8 10 in. 1 1¼ 1½ 2
DN 25 32 40 50 65 80 100 125 150 200 250 DN 25 32 40 50

Product information is available at erico.pentair.com

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Universal for lateral and longitudinal braces

Pipe to brace: Brace pipe:


in. 1 1¼ 1½ 2 2½ 3 4 5 6 8 10 in. 1 1¼ 1½ 2
DN 25 32 40 50 65 80 100 125 150 200 250 DN 25 32 40 50

Product information is available at erico.pentair.com

Available October 2017.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Pipe to brace: Brace pipe:
in. 1 1¼ 1½ 2 2½ 3 4 5 6 in. 1 1¼ 1½ 2
DN 25 32 40 50 65 80 100 125 150 DN 25 32 40 50

Product information is available at erico.pentair.com

Pipe to brace: Brace pipe:


in. 1 1¼ 1½ 2 2½ 3 4 5 6 8 10 in. 1 1¼ 1½ 2
DN 25 32 40 50 65 80 100 125 150 200 250 DN 25 32 40 50

Product information is available at erico.pentair.com

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Can be used on any structural flange including bar joists, beams, channels and angles.
The brace can be orientated parallel or perpendicular to the direction of the structural element.
Product information is available at erico.pentair.com

Available October 2017.

Can be used on any structural flange including bar joists, beams, channels and angles.
Preassembled to the Universal Structural Bracket.

Flange thickness: 1/4” - 3/4” / 6-19 mm

Product information is available at erico.pentair.com

Available October 2017.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Can be installed on bar joists or I-beams.
The brace can be oriented parallel or perpendicular to the direction of the structural element.

Flange thickness: 1/4” - 1/2 “ / 6.- 12 mm


Product information is available at erico.pentair.com

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
The brace can be oriented parallel or perpendicular to the direction of the structural element.

Range:
Flange thickness: 1/4” - 1 1/4” / 6 - 32 mm (3 PRODUCT SIZES)
Beam width: 4 “ - 18” / 100 - 457 mm (3 PRODUCT SIZES)

Product information is available at erico.pentair.com

Available October 2017.

The brace can be oriented parallel or perpendicular to the direction of the structural element.

Range:
Flange thickness: 1/4 INCH TO 1-1/4 INCH / 6- 32 mm (3 PRODUCT SIZES)
Beam width: 4 INCH—18 INCH / — 100 - 457 mm (3 PRODUCT SIZES)
Product information is available at erico.pentair.com

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Range:
Flange thickness: 1/4” - 3/4” / 6 - 12 mm
Product information is available at erico.pentair.com

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Enables to disperse the load over two anchors. Can be used for both LATERAL and LONGITUDINAL sway brace applica-
tions.
Attach to brace arm with Universal Structural Attachment Part Number CSBUNIV050EG or Stamped Universal Struc-
tural Attachment Part Number CSBU1, CSBU2, CSBU1HD and CSBU2HD

Range:
1/2” (M12) OR 3/4” (M20) STRUCTURAL CONNECTIONS
Product information is available at erico.pentair.com

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Attaches directly to concrete, wood, bar joist or I-beam adapters.
Can be used for both LATERAL and LONGITUDINAL sway brace applications.
Equipped with snap-off bolt head which enable an easy installation and inspection of the SWAY BRACES.

Brace pipe:
in. 1 1¼ 1½ 2
DN 25 32 40 50
Product information is available at erico.pentair.com

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
Attaches directly to concrete, wood, bar joist, steel flange adapter, steel flange adapter assembly or I-beam adap-
ters.
Can be used for both LATERAL and LONGITUDINAL sway brace applications.
Equipped with snap-off bolt head which enable an easy installation and inspection of the SWAY BRACES.

Brace pipe:
in. 1 1¼ 1½ 2
DN 25 32 40 50

Product information is available at erico.pentair.com

Available October 2017.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
VERS.
05/2017
OVERVIEW

AA AB

AC

AD

AE

Plan view

A A) Crossings of seismic expansion joints


A B) Wall penetrations
A C) Obstacles avoidance
A D) Horizontal changes of directions
A E) Horizontal changes of directions: curves not at 90°

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
OVERVIEW

AI

AF

AG
AH

Section view

A F) RISERS with offsets, vertical changes of directions


A G) Obstacles avoidance—Beams
A H) Floor penetrations
A I) Sloped ceilings

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Seismic expansion joint

Seismic Separation Assembly

Point considered the end of the

Point considered the end of the

According to section 2.2.1.4.8, SEISMIC SEPARATION ASSEMBLIES (SSA) are to be installed on all fire protection system
piping that crosses a building seismic expansion joint (including separations between two buildings) above ground
level.
Each SEISMIC SEPARATION ASSEMBLY must be studied on a case by case basis taking under account the width of the
joint so as to insure an appropriate degree of flexibility. Other engineered methods that provide an appropriate de-
gree of flexibility in both the horizontal and the vertical planes are acceptable.

From a SWAY BRACE installation standpoint, as far as the CROSSMAINS/FEEDMAINS are concerned, section 2.2.1.1.4.B
asks to consider seismic expansion joints and therefore SEISMIC SEPARATION ASSEMBLIES in CROSSMAINS/FEEDMAINS as
the end of the piping on both sides of the assembly. Consequently, it is necessary to install a LATERAL sway brace
within 6 ft / 1.8m of the end of the SSA and a LONGITUDINAL one within 40 ft / 12.2m of the end of the SSA. (Please,
refer to details C in the H section of this handbook)
Sections 2.2.1.1.5.A.8 and 2.2.1.1.5.B.4 provide the same instructions for BRANCH LINES crossing seismic expansion
joints.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Please, refer to this Handbook:
 Section C for clearance specifications
 Sections H - details G for the horizontal feedmains/crossmains

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≥ 6 ft / 1.8m

≤ 2 ft / 0.6m

< 6 ft / 1.8m

< 6 ft / 1.8m

< 6 ft / 1.8m

When horizontal CROSSMAINS or FEEDMAINS need to avoid an obstacle (e.g. a pillar, a stairwell, elevator, or distribution
systems), the instructions for horizontal CROSSMAINS or FEEDMAINS per 2.2.1.1.4.A may be applied.
When pipe runs adjacent to a horizontal change of direction are less than 6 ft / 1.8m, LATERAL and LONGITUDINAL sway
bracing is not required as long as flexible couplings are not present in the change of direction. Conversely, when pipe
runs adjacent to a horizontal change of direction are 6 ft / 1.8m long or more, both LATERAL and LONGITUDINAL sway
bracing is required within 2 ft / 0.6m of the change of direction.

< 6ft / 1.8m

End of pipe

< 6 ft / 1.8m

< 6 ft / 1.8m

< 6 ft / 1.8m

When horizontal CROSSMAINS or FEEDMAINS need to avoid an obstacle (e.g. a pillar, a stairwell, elevator, or distribution
systems), the instructions for horizontal CROSSMAINS or FEEDMAINS per 2.2.1.1.4.A may be applied.
When pipe runs adjacent to a horizontal change of direction are less than 6 ft / 1.8m, LATERAL and LONGITUDINAL sway
bracing is not required as long as flexible couplings are not present in the change of direction. When the piping ends
after avoiding the obstacle and the straight pipe run after the last curve is less than 6 ft / 1.8m, provide a LATERAL
sway brace and a LONGITUDINAL sway brace respectively within within 6 ft / 1.8m and 40 ft / 12.2m of the end of the
pipe.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≥ 6 ft / 1.8m

Horizontal change of direction with ≤ 2 ft / 0.6m


excessive flexible coupling

≤ 2 ft / 0.6m

< 6 ft / 1.8m

< 6 ft / 1.8m ≤ 2 ft / 0.6m

< 6 ft / 1.8m

≥ 6 ft / 1.8m

Horizontal change of direction with ≤ 2 ft / 0.6m


excessive flexible coupling

≤ 2 ft / 0.6m

< 6 ft / 1.8m

≤ 2 ft / 0.6m
< 6 ft / 1.8m ≤ 2 ft / 0.6m

≤ 2 ft / 0.6m ≤ 2 ft / 0.6m

< 6 ft / 1.8m
≤ 2 ft / 0.6m

When horizontal CROSSMAINS or FEEDMAINS need to avoid an obstacle (e.g. a pillar, a stairwell, elevator, or distribution
systems), the instructions for horizontal CROSSMAINS or FEEDMAINS per 2.2.1.1.4.A and 2.2.1.1.4.C may be applied.
When pipe runs adjacent to a horizontal change of direction are less than 6 ft / 1.8m, LATERAL and LONGITUDINAL sway
bracing is not required as long as flexible couplings are not present in the change of direction. Conversely, when pipe
runs adjacent to a horizontal change of direction are 6 ft / 1.8m long or more, both LATERAL and LONGITUDINAL sway
bracing is required within 2 ft / 0.6m of the change of direction.

When flexible couplings are present within the changes of directions, for each flexible coupling present an additional
LATERAL sway brace is to be located within 2 ft / 0.6m of the change of direction, no matter what is the length of the
pipe run adjacent to the change of direction. When the piping diameter remains the same on both ends of the chan-
ge of direction, the LATERAL sway brace may be indiferently located on one of the two runs as long as it is within 2 ft /
0.6m of the change of direction. On the other hand, when there is a change in piping diameter, place the LATERAL
sway brace on the pipe run with the largest diameter.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≥ 6 ft / 1.8m

≤ 2 ft / 0.6m

≤ 2 ft / 0.6m
≥ 6 ft / 1.8m

≤ 2 ft / 0.6m
≤ 2 ft / 0.6m

≤ 2 ft / 0.6m

≥ 6 ft / 1.8m
≤ 2 ft / 0.6m
≥ 6 ft / 1.8m

When horizontal CROSSMAINS or FEEDMAINS need to avoid an obstacle (e.g. a pillar, a stairwell, elevator, or distribution
systems), the instructions for horizontal CROSSMAINS or FEEDMAINS per 2.2.1.1.4.A may be applied.

Provide CROSSMAINS or FEEDMAINS piping with pipe runs of 6 ft / 1.8m or more adjacent to a horizontal change of di-
rection with both LATERAL and LONGITUDINAL sway bracing within 2 ft / 0.6m of the change of direction.

Note: Bracing is required irrespective of type of coupling used in the system.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≥ 6 ft / 1.8m

≥ 6 ft / 1.8m

≥ 6 ft / 1.8m
< 6 ft / 1.8m

When horizontal CROSSMAINS or FEEDMAINS need to avoid an obstacle (e.g. a pillar, a stairwell, elevator, or distribution
systems), the instructions for horizontal CROSSMAINS or FEEDMAINS per 2.2.1.1.4.A may be applied.

Provide CROSSMAINS or FEEDMAINS piping with pipe runs of 6 ft / 1.8m or more adjacent to a horizontal change of di-
rection with both LATERAL and LONGITUDINAL sway bracing within 2 ft / 0.6m of the change of direction.

The required SWAY BRACES may also be located on the pipe run less than 6 ft / 1.8m long within 2 ft / 0.6m of the
change of direction.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Horizontal change of
direction V-W

Horizontal change of Horizontal change


direction X-Y of direction Y-V

< 2 ft / 0.6m < 2 ft / 0.6m < 2 ft / 0.6m

< 2 ft / 0.6m < 2 ft / 0.6m


Pipe run X Pipe run Y Pipe run V Pipe run W
Length ≥ 6 ft / Length ≥ 6 ft / Length ≥ 6 ft / 1.8m Length ≥ 6 ft /
1.8m 1.8m 1.8m

The case presented uses the instructions from sections 2.2.1.1.4.A for the horizontal CROSSMAINS or FEEDMAINS and
from sections 2.2.1.1.5.A.9 and 2.2.1.1.5.B.5 for the BRANCH LINES.

Pipe runs X and Y, adjacent to a horizontal change of direction, are 6 ft / 1.8m or more: providing LATERAL and LONGI-
TUDINAL sway bracing within 2 ft / 0.6m of the change of direction X-Y itself is required. The SWAY BRACES may alter-
natively be located on the pipe run X or on the pipe run Y as long as they are within 2 ft / 0.6m of the change of di-
rection.

Pipe runs Y and V, adjacent to a horizontal change of direction, are 6 ft / 1.8m or more: providing LATERAL and LONGI-
TUDINAL sway bracing within 2 ft / 0.6m of the change of direction Y-V itself is required. The SWAY BRACES may alter-
natively be located on the pipe run Y or on the pipe run V as long as they are within 2 ft / 0.6m of the change of di-
rection.

Pipe runs V and W, adjacent to a horizontal change of direction, are 6 ft / 1.8m or more: providing LATERAL and LON-
GITUDINAL sway bracing within 2 ft / 0.6m of the change of direction V-W itself is required. The SWAY BRACES may al-
ternatively be located on the pipe run V or on the pipe run W as long as they are within 2 ft / 0.6m of the change of
direction.

Please, note that a LATERAL [LONGITUDINAL] sway brace act as LONGITUDINAL [LATERAL] sway brace for the perpendicu-
lar pipe run.

VERS.
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Horizontal change of
direction V-W
Horizontal change
Horizontal change of of direction Y-V
direction X-Y
End of pipe

Pipe run W
Pipe run V Length < 6 ft / 1.8m
Pipe run X Pipe run Y Length ≥ 6 ft /
Length ≥ 6 ft / 1.8m Length < 6 ft / 1.8m 1.8m

The case presented uses the instructions from sections 2.2.1.1.4.A and 2.2.1.1.4.B for the horizontal CROSSMAINS or
FEEDMAINS and from sections 2.2.1.1.5.A.8, 2.2.1.1.5.A.9, 2.2.1.1.5.B.4 and 2.2.1.1.5.B.5 for the BRANCH LINES.

Pipe run X is adjacent to an horizontal change of direction and is 6 ft / 1.8m or more, pipe run Y is less than 6 ft /
1.8m: providing LATERAL and LONGITUDINAL sway bracing is required within 2 ft / 0.6m of the X-Y change of direction
itself. The SWAY BRACES may also be located on the pipe run Y within 2 ft / 0.6m of the change of direction. In that
case, the LATERAL [LONGITUDINAL] sway brace must be sized as LONGITUDINAL [LATERAL] sway brace for the pipe run X.

Pipe run Y is adjacent to a horizontal change of direction and is less than 6 ft / 1.8m, pipe run V is 6 ft / 1.8m or mo-
re: providing LATERAL and LONGITUDINAL sway bracing is required within 2 ft / 0.6m of the Y-V change of direction
itself. The SWAY BRACES may also be located on the pipe run Y within 2 ft / 0.6m of the change of direction. In that
case, the LATERAL [LONGITUDINAL] sway brace must be sized as LONGITUDINAL [LATERAL] sway brace for the pipe run V.

Pipe run V is adjacent to an horizontal change of direction and is 6 ft / 1.8m or more, pipe run W is less than 6 ft /
1.8m: providing LATERAL and LONGITUDINAL sway bracing is required within 2 ft / 0.6m of the V-W change of direction
itself. The SWAY BRACES may also be located on the pipe run W within 2 ft / 0.6m of the change of direction. In that
case, the LATERAL [LONGITUDINAL] sway brace must be sized as LONGITUDINAL [LATERAL] sway brace for the pipe run V.

In any case, the last LATERAL sway brace is to be located within 6 ft / 1.8m of the end of the pipe and the last LONGI-
TUDINAL within 40 ft / 12.2m of the end of the pipe.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
VERS.
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
LATERAL brace, does not LONGITUDINAL brace,
work as LONGITUDINAL does not work as
brace for the pipe run LATERAL brace for the
following the curve pipe run following the

< 2 ft / 0.6m < 2 ft / 0.6m

Horizontal change of Horizontal change of


direction ≠ 90° direction ≠ 90°

FOUR-WAY brace, prevents horizontal


movements even for the pipe run after
the curve, when sized accounting for
the corresponding loads

Horizontal change of direction ≠ 90°

< 2 ft / < 2 ft / 0.6m

The case presented uses the provisions in section 2.2.1.1.4.A for the horizontal CROSSMAINS or FEEDMAINS and in
sections 2.2.1.1.5.A.9 and 2.2.1.1.5.B.5 for the BRANCH LINES. Please, refer respectively to sections H, and B, of the
handbook for further information.

As explained in Appendix C of FM Global Property Loss Prevention Data Sheet 2-8, for horizontal changes of direc-
tions at angles other than 90°, the use of a LATERAL [LONGITUDINAL] sway brace on the pipe run preceeding the curve
cannot act as LONGITUDINAL [LATERAL] sway brace for the pipe run that follows that curve.
The use of a FOUR-WAY bracing, i.e. the combined use of a LATERAL and a LONGITUDINAL sway brace at the same point
relative to a curve, ensures a bracing to movements in all horizontal directions, even for the run of pipe after the
bend , provided it is sized taking under account the corresponding loads.

Note. FM Global Property Loss Prevention Data Sheet 2-0 allows bending sprinkler system piping to change horizon-
tal direction. In such a case, the minimum radius of a bend is 12 pipe diameters. There are some exceptions relative
to the minimum wall thickness in which case it is possible to reduce the radius of the bend to 6 pipe diameters (see
FM Global Property Loss Prevention Data Sheet 2-0 — section 2.5.2.2).
The SWAY BRACES are to be located as previously indicated.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
≤ 2 ft / 0.6m
FOUR-WAY brace and flexible coupling
located within 2 ft / 0.6m of the top of
the vertical MAIN
≤ 2 ft /
0.6m

FOUR-WAY brace and


flexible coupling located Vertical MAIN
within 2 ft / 0.6m of the Length ≥ 6 ft / 1.8m
FOUR-WAY brace located bottom of the vertical
within 2 ft / 0.6m of the
top of the RISER
≤ 2 ft /
0.6m
≤ 2 ft / 0.6m

≤ 2 ft / 0.6m ≤ 2 ft / 0.6m

Horizontal MAIN. SWAY BRACING may be necessary


depending on the length of the pipe run.
≤ 140 ft / 2.2 m
RISER

Flexible coupling at the


bottom of the RISER.

≤ 2 ft / 0.6m

(Section view)

For the purpose of seismic bracing, the case in which RISERS need to overcome an obstacle may be divided into the
succession of three elements: RISER—horizontal MAIN—vertical MAIN.

On RISERS, a flexible coupling is required within 2 ft / 0.6m of the bottom and another flexible coupling and a FOUR-
WAY brace are required within 2 ft / 0.6m of the top. In the case presented the highest point of the vertical piping is
considered the top of the RISER. (Refer to section R of the handbook for other instructions regarding RISERS.)

The FOUR-WAY brace located at the top of the RISER may be considered as the first LATERAL and the first LONGITUDINAL
braces of the horizontal MAIN, as long as it is located within 2 ft / 0.6m of the horizontal pipe run and is sized taking
the loads from the horizontal piping also under account.

Depending on the length of the horizontal run, additional SWAY BRACES may be necessary. (Refer to section H of the
handbook for further details.)

The next run of vertical piping is considered to be a vertical MAIN. If the length of this run is 6 ft / 1.8m or more, a
FOUR-WAY brace and a flexible coupling are required within 2 ft / 0.6m of the top and the bottom of the pipe.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
FOUR-WAY brace located
within 2 ft / 0.6m of the
Vertical MAIN < 6 ft / 1.8m
top of the RISER

≤ 2 ft / 0.6m
≤ 2 ft / 0.6m

Horizontal MAIN. SWAY BRACING may be necessary


depending on the length of the pipe run.
≤ 40 ft / 12.2 m
RISER

Flexible coupling at the


bottom of the RISER.

≤ 2 ft / 0.6m

(Section view)

For the purpose of seismic bracing, the case in which RISERS need to overcome an obstacle may be divided into the
succession of three elements: RISER—horizontal MAIN—vertical MAIN.

On RISERS, a flexible coupling is required within 2 ft / 0.6m of the bottom and another flexible coupling and a FOUR-
WAY brace are required within 2 ft / 0.6m of the top. In the case presented the highest point of the first run of vertical
piping is considered the top of the RISER. (Refer to section R of the handbook for other instructions regarding RI-
SERS.)

The FOUR-WAY brace located at the top of the RISER may be considered as the first LATERAL and the first LONGITUDINAL
braces of the horizontal MAIN, as long as it is located within 2 ft / 0.6m of the horizontal pipe run and is sized taking
the loads from the horizontal piping also under account.

Depending on the length of the horizontal run, additional SWAY BRACES may be necessary. (Refer to section H of the
handbook for further details.)

The next run of vertical piping is considered to be a vertical MAIN. If the length of this run is less than 6 ft / 1.8m and
there are no flexible couplings at the bottom and at the top of the vertical run, FOUR-WAY bracing is not required at the
bottom or at the top of the piping.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
< 6 ft / 1.8m

(Section view)

The case of CROSSMAINS or FEEDMAINS needing to avoid an obstacle (e.g. a wide beam or other piping systems) can
be addressed using the provisions in section 2.2.1.1.3 for vertical CROSSMAINS or FEEDMAINS.

When the length of vertical pipe run necessary to go around the obstacle is less than 6 ft / 1.8m, FOUR-WAY bracing is
not necessary at the bottom or at the top of the vertical run, as long as no flexible couplings are being used in con-
nection with the horizontal piping.

The horizontal pipe run may require SWAY BRACING depending on its length, according to the provisions in section
2.2.1.1.4 for horizontal CROSSMAINS or FEEDMAINS.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Flexible couplings not required
on entrance and exit

≤ 2 ft / 0.6m ≤ 2 ft / 0.6m

< 6 ft / 1.8m

(Section view)

Flexible couplings not required Flexible couplings not required

≤ 2 ft / 0.6m ≤ 2 ft / 0.6m

< 6 ft / 1.8m

≤ 2 ft / 0.6m ≤ 2 ft / 0.6m
(Section view)

The case of CROSSMAINS or FEEDMAINS needing to avoid an obstacle (e.g. a wide beam or other piping systems) can
be addressed using the provisions in section 2.2.1.1.3 for vertical CROSSMAINS or FEEDMAINS.

When the length of vertical pipe run necessary to go around the obstacle is less than 6 ft / 1.8m but flexible cou-
plings are part of the connection to the horizontal piping, a FOUR-WAY brace is required at each of the connection in
which there is a flexible coupling. Locate the FOUR-WAY brace within 2 ft / 0.6m of the connection.

The horizontal pipe run may require SWAY BRACING depending on its length, according to the provisions in section
2.2.1.1.4 for horizontal CROSSMAINS or FEEDMAINS.

Note. When it is not possible to attach the SWAY BRACES directly to the element avoided (in the case of non structural
elements for instance), it is necessary to arrange for an auxiliary structure to which to anchor.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Obstacle larger than 4 ft / 1.2 m

≤ 2 ft / 0.6m ≤ 2 ft / 0.6m

≥ 6 ft / 1.8m

≤ 2 ft / 0.6m ≤ 2 ft / 0.6m

(Section view)

The case of CROSSMAINS or FEEDMAINS needing to avoid an obstacle (e.g. a wide beam or other piping systems) can
be addressed using the provisions in section 2.2.1.1.3 e 2.2.1.4.4.B for vertical CROSSMAINS or FEEDMAINS.

When the length of vertical pipe run necessary to go around the obstacle is 6 ft / 1.8m or more, FOUR-WAY bracing is
necessary at the bottom and at the top of the vertical pipe run. The FOUR-WAY brace is to be located within 2 ft /
0.6m of the bottom and of the top of the vertical pipe run. It is also necessary to locate a flexible coupling at the bot-
tom and at the top of the vertical pipe run. These flexible couplings are to be located within 2 ft / 0.6m of the bottom
and of the top of the vertical pipe run.

The run of horizontal piping that connects the two vertical pipe runs may require SWAY BRACING depending on its
length, as per the provisions in section 2.2.1.1.4 for horizontal CROSSMAINS or FEEDMAINS.

Note. When it is not possible to attach the SWAY BRACES directly to the element avoided (in the case of non structural
elements for instance), it is necessary to arrange for an auxiliary structure to which to anchor.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6m ≤ 2 ft / 0.6m
Obstacle large less
than 4 ft / 1.2 m

≥ 6 ft / 1.8m

≤ 2 ft / 0.6m

≤ 2 ft / 0.6m

(Section view)

The case of CROSSMAINS or FEEDMAINS needing to avoid an obstacle (e.g. a wide beam or other piping systems) can
be addressed using the provisions in section 2.2.1.1.3 e 2.2.1.4.4.B for vertical CROSSMAINS or FEEDMAINS.

When the length of vertical pipe run necessary to go around the obstacle is 6 ft / 1.8m or more, FOUR-WAY bracing is
necessary at the bottom and at the top of the vertical pipe run. The FOUR-WAY brace is to be located within 2 ft /
0.6m of the bottom and of the top of the vertical pipe run. It is also necessary to locate a flexible coupling at the bot-
tom and at the top of the vertical pipe run. These flexible couplings are to be located within 2 ft / 0.6m of the bottom
and of the top of the vertical pipe run.

When the width of the obstacle to avoid allows it, it is possible to use only one FOUR-WAY brace to brace both the
vertical pipe runs, as long as it is sized to take under account the loads associated with both pipe runs.

Note. When it is not possible to attach the SWAY BRACES directly to the element avoided (in the case of non structural
elements for instance), it is necessary to arrange for an auxiliary structure to which to anchor.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
Connection with rigid couplings Connection with rigid couplings

≥ 6 ft / 1.8m

Connection with rigid couplings Connection with rigid couplings

(Section view)

Solution not compliant with sections 2.2.1.1.3 and 2.2.1.4.4.B for vertical CROSSMAINS or FEEDMAINS.

The length of vertical piping necessary to avoid the obstacle is 6 ft / 1.8m or more, therefore it is necessary to locate
a FOUR-WAY bracing at the bottom and at the top of the vertical pipe run within 2 ft / 0.6m of the bottom and of the
top of the vertical pipe run. It is also necessary to locate a flexible coupling at the bottom of the vertical piping and
another one at the top. These flexible couplings are to be located within 2 ft / 0.6m of the bottom and of the top of
the vertical pipe run.

In the solution in illustration, the required flexible couplings have been omitted, thereby making the solution non-
compliant with FM’s requirements.

Note. When it is not possible to attach the SWAY BRACES directly to the element avoided (in the case of non structural
elements for instance), it is necessary to arrange for an auxiliary structure to which to anchor.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Connection with flexible coupling

≤ 2 ft / 0.6m
Connection with rigid couplings

≥ 6 ft / 1.8m

<6 ft / 1.8m

≤ 2 ft / 0.6m Connection with rigid couplings


Connection with flexible coupling

(Section view)

The case illustrated can be narrowed down to the provisions in sections 2.2.1.1.3 and 2.2.1.4.4.B for vertical CROSS-
MAINS or FEEDMAINS.

It is necessary to locate FOUR-WAY braces at the beginning and at the end of the vertical pipe run 6 ft / 1.8m long or
more required to avoid the obstacle. The FOUR-WAY braces are to be located within 2 ft / 0.6m of the beginning and
of the end of the vertical pipe run. It is also necessary to locate a flexible coupling at the beginning and at the end of
the vertical pipe run. These flexible couplings are to be located within 2 ft / 0.6m of the beginning and of the end of
the vertical piping. FOUR-WAY is not required at the beginning and at the end of vertical pipe runs less than 6 ft / 1.8m,
as long as there are no flexible couplings in the connections with the horizontal piping.

The run of horizontal piping that connects the two vertical pipe runs may require SWAY BRACING depending on its
length, as per the provisions in section 2.2.1.1.4 for horizontal CROSSMAINS or FEEDMAINS.

Note. When it is not possible to attach the SWAY BRACES directly to the element avoided (in the case of non structural
elements for instance), it is necessary to arrange for an auxiliary structure to which to anchor.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
FOUR-WAY bracing located
within 2 ft / 0.6m of the DROP
on the pipe run with the lar-
gest diameter

≤ 2 ft / 0.6m

≥ 6 ft / 1.8m

≤ 2 ft / 0.6m

Pipe run to more


sprinklers

≤ 2 ft / 0.6m

(Section view)

The case of pipe DROPS that feed more than one sprinkler needing to avoid an obstacle (e.g. a wide beam, other pi-
ping systems or other distribution systems) can be addressed using sections 2.2.1.1.3 and 2.2.1.4.6.

If the length of vertical piping necessary to avoid the obstacle is 6 ft / 1.8m or more, it is necessary to locate a FOUR-
WAY brace at the beginning and at the end of the vertical pipe run. The FOUR-WAY braces are to be located on the
piping with the largest diameter within 2 ft / 0.6m of the beginning and of the end of the vertical piping. It is also ne-
cessary to locate a flexible coupling at the beginning and at the end of the vertical pipe run within 2 ft / 0.6m of the
connection with the horizontal piping and a flexible coupling on the horizontal piping that feeds the sprinklers within 2
ft / 0.6m of the connection with the pipe DROP.

The horizontal pipe run that feeds the sprinklers may require SWAY BRACING depending on its length, as per the provi-
sions in section 2.2.1.1.4 for the horizontal CROSSMAINS o FEEDMAINS or in section 2.2.1.1.5 for the BRANCH LINES.
(REFER TO SEFCTIONS H AND B.)

Note. When it is not possible to attach the SWAY BRACES directly to the element avoided (in the case of non structural
elements for instance), it is necessary to arrange for an auxiliary structure to which to anchor.

HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
≤ 2 ft / 0.6m

Pipe run to more sprinklers

≤ 2 ft / 0.6m

(Section view)

The case of pipe DROPS that feed more than one sprinkler needing to avoid an obstacle (e.g. a wide beam, other pi-
ping systems or other distribution systems) can be addressed using sections 2.2.1.1.3 and 2.2.1.4.6.

If the length of vertical piping necessary to avoid the obstacle is less than 0.6m, neither flexible couplings nor FOUR-
WAY bracing are necessary at the beginning of the vertical piping. It is however necessary to locate a flexible coupling
on the horizontal piping that feeds the sprinklers within 2 ft / 0.6m of the connection with the pipe DROP.

The horizontal pipe run that feeds the sprinklers may require SWAY BRACING depending on its length, as per the provi-
sions in section 2.2.1.1.4 for the horizontal CROSSMAINS o FEEDMAINS or in section 2.2.1.1.5 for the BRANCH LINES.
(REFER TO SEFCTIONS H AND B.)

Note. When it is not possible to attach the SWAY BRACES directly to the element avoided (in the case of non structural
elements for instance), it is necessary to arrange for an auxiliary structure to which to anchor.

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
Please, refer to the following sections of the handbook:
 Section C for the clearance specifications
 section V - details D for the vertical CROSSMAINS
 section R - details D for the RISERS

VERS. HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER
05/2017
HANDBOOK FOR THE DESIGN AND INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLER VERS.
05/2017
VERS. HANDBOOK FOR THE DESIGN AND THE INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLERS
05/2017
BRANCH LINES: SWAY BRACING as
per handbook section B.
Ceiling slope angle compatible with
FM 2-0 specifications or the
relevant occupancy-specific data
sheet.

HORIZONTAL CROSSMAINS:
SWAY BRACING as per handbook
section H. In order to respect
the bracing members slender-
ness limits, it may be necessary
to install structural appendices
for brace attachment to struc-
ture.

RISERS: SWAY BRACING


as per
handbook section R.

In section 2.1.1.6 for nonstorage sprinklers and in section 2.2.1.6 for storage sprinklers, FM 2-0 specifies the cases
in which installing a fire sprinkler system under a sloped ceiling is permitted unless recommended otherwise by the
relevant occupancy-specific data sheet, and defines the specifications that the sprinkler system and the ceiling geo-
metry must meet.

As far as the bracing of sprinkler systems installed under a sloped ceiling is concerned, FM 2-8 does not provide
specific instructions. One must therefore turn to the provisions for individual pipe runs.

In the case in illustration, the BRANCH LINES are connected to the CROSSMAIN via RISER NIPPLES. Please note that, de-
pending on the characteristics of the ceiling, it may be necessary to install structural appendices or structures espe-
cially designed to brace the CROSSMAIN and/or the BRANCH LINES in order to satisfy the brace members slenderness
requirements.

HANDBOOK FOR THE DESIGN AND THE INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLERS VERS.
05/2017
BRANCH LINES: SWAY BRACING as
per handbook section B. HORIZONTAL CROSSMAINS:
SWAY BRACING as per handbook
section H.

RISERS: SWAY BRACING as per hand-


Ceiling slope angle compatible with
book section R.
FM 2-0 specifications or the
relevant occupancy-specific data
sheet.

In section 2.1.1.6 for nonstorage sprinklers and in section 2.2.1.6 for storage sprinklers, FM 2-0 specifies the cases
in which installing a fire sprinkler system under a sloped ceiling is permitted unless recommended otherwise by the
relevant occupancy-specific data sheet, and defines the specifications that the sprinkler system and the ceiling geo-
metry must meet.

As far as the bracing of sprinkler systems installed under a sloped ceiling is concerned, FM 2-8 does not provide
specific instructions. One must therefore turn to the provisions for individual pipe runs.

In the case in illustration, the CROSSMAIN runs parallel to the sloped ceiling and the BRANCH LINES are connected di-
rectly to the CROSSMAIN. Depending on the load capacity of structure making up the ceiling, the sway bracing may
be attached directly to the ceiling; if the structural elements load capacity is not sufficient, it may be necessary to
install an ad hoc structure in which to anchor the braces.

VERS. HANDBOOK FOR THE DESIGN AND THE INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLERS
05/2017
Ceiling slope angle not
compatible with FM 2-0 It may be necessary to add a structure
specifications or with the specifically designed to hold the suspended
relevant occupancy-specific ceiling and to brace the fire sprinkler system.
data sheet.

BRANCH LINES: SWAY BRACING as


per handbook section B.

Suspended ceiling
HORIZONTAL CROSSMAINS: made according to FM
SWAY BRACING as per handbook 2-0 requirements
section H.

RISERS: SWAY BRACING


as per
handbook section R.

In section 2.1.1.6 for nonstorage sprinklers and in section 2.2.1.6 for storage sprinklers, FM 2-0 specifies the cases
in which installing a fire sprinkler system under a sloped ceiling is permitted unless recommended otherwise by the
relevant occupancy-specific data sheet, and defines the specifications that the sprinkler system and the ceiling geo-
metry must meet. For ceiling slopes that exceed the maximum allowed, it is required to install a flat, continuous
suspended ceiling over the protected area. The suspended ceiling must extend for 20 ft / 6.0m in all direction be-
yond the protected area. The suspended ceiling is to be designed according to the specifications of data sheet 1-12
Ceilings and conceiled spaces and is to withstand a minimum uplift pressure of 3 lb/ft2—14.4kg/m2.
As far as the bracing of sprinkler systems installed under a sloped ceiling is concerned, FM 2-8 does not provide
specific instructions. One must therefore turn to the provisions for individual pipe runs.

Depending on the characteristics of the ceiling, it may be necessary to install structural appendices or structures
specifically designed to brace the CROSSMAIN and the BRANCH LINES in order to satisfy the brace members slender-
ness requirements.

HANDBOOK FOR THE DESIGN AND THE INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLERS VERS.
05/2017
It may be necessary to resort to add a
structure specifically designed to hold the
Ceiling slope angle not suspended ceiling and to brace the fire
HORIZONTAL CROSSMAINS:
compatible with FM 2-0 sprinkler system.
SWAY BRACING as per handbook
specifications or with the relevant section H.
occupancy-specific data sheet.

Suspended ceiling
made according to FM
2-0 requirements

BRANCH LINES: SWAY BRACING as


per handbook section B.

DROPS: SWAY BRACING as per


handbook section D.

RISERS: SWAY BRACINGas per


handbook section R.

In section 2.1.1.6 for nonstorage sprinklers and in section 2.2.1.6 for storage sprinklers, FM 2-0 specifies the cases
in which installing a fire sprinkler system under a sloped ceiling is permitted unless recommended otherwise by the
relevant occupancy-specific data sheet, and defines the specifications that the sprinkler system and the ceiling geo-
metry must meet. For ceiling slopes that exceed the maximum allowed, it is required to install a flat, continuous
suspended ceiling over the protected area. The suspended ceiling must extend for 20 ft / 6.0m in all direction be-
yond the protected. The suspended ceiling is to be designed according to the specifications of data sheet 1-12 Cei-
lings and conceiled spaces and is to withstand a minimum uplift pressure of 3 lb/ft2—14.4kg/m2.
As far as the bracing of sprinkler systems installed under a sloped ceiling is concerned, FM 2-8 does not provide
specific instructions. One must therefore turn to the provisions for individual pipe runs.

Depending on the characteristics of the ceiling, it may be necessary to install structural appendices or structures
specifically designed to brace the CROSSMAIN and the BRANCH LINES in order to satisfy the brace members slender-
ness requirements.

VERS. HANDBOOK FOR THE DESIGN AND THE INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLERS
05/2017
B1310W-WWEN B327LT17WWEN WB1017

HANDBOOK FOR THE DESIGN AND THE INSTALLATION OF SEISMIC PROTECTION SYSTEMS FOR FIRE SPRINKLERS VERS.
05/2017

You might also like