cài đặt và mã lỗi
cài đặt và mã lỗi
cài đặt và mã lỗi
User Guide
Chapter 3: Wiring...................................................................................................................................22
3.1. Elevator Integrated Controller Therminal Wiring Diagram..................................................................................22
I
3.2.1 Main circuit structure ................................................................................................................................23
II
4.4. Commissioning Parameters .................................................................................................................................52
Chapter 5: Parameters...........................................................................................................................62
5.1. Parameters Function Classifications ....................................................................................................................62
5.3.2 Monitoring Parameter for I/O Status, Cabin Signal & Interference Appraisal (U1-U5) .............................64
III
5.4.8 Encoder Setup Parameters (F8) .................................................................................................................75
6.1.1 Elevator Rated Speed, Motor Rated Speed, Encoder pulses Setup...........................................................80
IV
6.8.1 Different Mode Selection...........................................................................................................................90
V
7.5. Motor Parameters Tuning..................................................................................................................................108
VI
9.1. Safety Precautions for Drive Maintenance & Storage .......................................................................................132
10.3.2 Wiring.....................................................................................................................................................136
VII
11.2.4 Interface Circuit .....................................................................................................................................142
Appendix 5: Menu operation processes with Digital tubes & operation keys ..................................... 156
VIII
FOREWORD
Thank you for using BL6-B series elevator controller. BL6 series elevator integrated controller is the next generation
elevator control system developed by Shenyang Bluelight Automatic Technology CO. LTD. It combines elevator
intellectual logic control and high-performance VVVF drive control. With user friendly interface and advanced
technology integrated together, the system not only has outstanding performance, but also shows strong reliability in
practice.
u The system combines intellectual logic control and high-performance VVVF drive control.
u Adopts advanced vector control technology, demodulates motor with high precision, takes full advantage of
motor capacity, improves elevator performance and comfort feel.
u Adopts advanced space vector PWM calculation method, compare with traditional sine/cosine PWM method, it
improves elevator operation efficiency and saves more energy.
u Adopts full function of BL2000/3000 system, maximize the performance of elevator in different application.
u When using Bluelight Synchronous machine, controller could pre-define the machine type with the most
optimized model, save machine parameter input and auto-tuning process, improves the commissioning efficiency and
maximize the machine performance.
u Fuzzy logic control with non-load-compensation start-up. Excellent comfort feels without lift weighing device.
u Rotating or stopping auto-tuning to get motor parameters and initial angle.
u Suitable for both gearless PM Synchronous traction machine and asynchronous induction machine.
u Brake units are built in for the whole BL3-B series to reduce external component cost.
u Internal encoder and frequency dividing interface to match different PG signal.
u Advanced double 32 bit CPU and FPGA for complete elevator control, with high reliability on elevator safety.
u Redundancy design and full software-hardware protection to achieve elevator safety and reliability.
u Passed professional EMC test, suitable for complicated job site.
u Monitor the cutting current from controller to main motor every time elevator stops.
u Generate optimized speed curve based on target floor to enable lift stop directly with high efficiency.
u CAN BUS serial communication technology for duplex control with high speed and reliability. Simplify system
wiring/extension.
u Adopts wireless/LAN remote control interface, convenient for long distance commissioning, maintenance and
elevator monitoring.
u Equips upper monitoring and software, convenient for parameter setting, commissioning and debugging.
u Data recorder to save integrated controller operation data, help for onsite maintenance /trouble shooting.
u Parameter upload, download and copy to help onsite maintenance.
u Support ARD function with only UPS unit.
u Match GB7588-2003 (equivalent to EN-81) safety standard.
This user guide has introduced on how to use BL6-B series elevator controller. Please read it carefully and understand
safety items before use (installation, running maintenance). This user guide is for elevator designer, installation and
maintenance technician. The installation, commissioning and maintenance must be performed by train technician.
The intellectual property of this user guide is owned by Shenyang Bluelight Group. Any information from this user
guide should not be copied without permission.
IX
Chapter 1:Safety Information
The following conventions are used to indicate precautions in this user guide. Failure to notice the precautions
provided in this user guide can result in serious or even fatal injury to damage to the products or to related equipment
and systems.
Indicates precautions that if not heeded could possibly result in loss of life or serious injury.
Indicates precautions that if not heeded could result in relatively serious or minor injury to the
operator and damage to the product. Also, it should be noted that even for
precautions, in certain situations could result in serious accident.
1
Chapter 1: Safety Information
u Wiring
² Always turn OFF the input power supply before wiring terminals.
Otherwise, an electric shock or fire can occur.
² Wiring must be performed by an authorized person qualified in electrical work.
Otherwise, an electric shock or fire can occur.
² Be sure to ground the ground terminal. (200 V Class: Ground to 100 Ω or less, 400 V Class:
Ground to 10 Ω or less)
Otherwise, an electric shock or fire can occur.
² Always check the operation of any Emergency stop circuits after they are wired.
Otherwise, there is the possibility of injury. (Wiring is the responsibility of the user.)
² Never touch the output terminals directly with your hands or allow the output lines to
come into contact with the Inverter case. Never short the output circuits.
Otherwise, an electric shock or ground short can occur.
² Check to be sure that the voltage of the main AC power supply satisfies the rated voltage
of the Inverter.
Injury or fire can occur if the voltage is not correct.
² Do not perform voltage withstand tests on the Inverter.
Otherwise, semiconductor elements and other devices can be damaged.
² Connect braking resistors, Braking Resistor Units, and Braking Units as shown in the I/O
wiring examples.
Otherwise, a fire can occur and the Inverter, braking resistors, Braking Resistor Units, and
Braking Units can be damaged.
² Tighten all terminal screws to the specified tightening torque.
Otherwise, a fire may occur.
² Do not connect AC power to output terminals U, V, and W.
The interior parts of the Inverter will be damaged if voltage is applied to the output terminals.
² Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits.
The Inverter can be damaged or interior parts burnt if these devices are connected.
² When a magnetic contactor is connected to the output circuits, do not switch it ON and
OFF while the Inverter is running.
Surge current will cause the over current protection circuit inside the Inverter to operate.
² Do not make terminal DC+/ P1 and DC- short link.
Otherwise, a fire or explosion may occur.
u Trial Operation
2
Chapter 1:Safety Information
² Check to be sure that the front cover is attached before turning ON the power supply.
Otherwise, an electric shock may occur.
² Do not get close to machine and related objects when choosing the error auto reset
function, as the drive will automatically restart after warning reset.
Otherwise, an injury may occur.
² Provide a separate fast stop switch; the Digital Operator STOP Key is valid only when its
function is set.
Otherwise, an Injury may occur.
² Reset alarms only after confirming that the RUN signal is OFF.
Otherwise, an Injury may occur.
² Do not perform fault operation and signal checking while the drive is running.
Otherwise an injury may occur and the drive may get damaged.
² Do not touch the radiation fins (heat sink), braking resistor, or Braking Resistor Unit.
These can become very hot.
Otherwise, a burn injury may occur.
² Do not touch the braking resistor.
Doing so can result in electric shock.
² Be careful when changing Inverter settings. The Inverter is factory set to suitable settings.
Otherwise, the equipment may be damaged.
² Do not touch the Inverter terminals. Some of the terminals carry high voltages and are
extremely dangerous.
Doing so can result in electric shock.
² Always have the protective cover in place when power is being supplied to the Inverter.
When attaching the cover, always turn OFF power to the Inverter through the MCCB.
Doing so can result in electric shock.
² After turning OFF the main circuit power supply, wait for the time indicated on the front
cover, and make sure the CHARGE indicator light has gone out, and then perform maintenance
and inspection.
The capacitor will remain charged and is dangerous.
² Maintenance, inspection, and replacement of parts must be performed only by authorized
personnel. Remove all metal objects, such as watches and rings, before starting work. Always
use grounded tools.
Failure to heed these warning can result in electric shock.
² Do not change the wiring, or remove connectors or terminal, during power on period.
Otherwise, an electric shock may occur.
3
Chapter 1: Safety Information
² A CMOS IC is used in the control board. Handle the control board and CMOS IC carefully.
The CMOS IC can be destroyed by static electricity if touched directly.
u Other
Read and follow all warning labels on the controller before installation.
Warnings Warnings
listed here listed here
WARNING
4
Chapter 2: Introduction and Installation
The model of the elevator integrated controller on the nameplate indicates the specification, voltage level, and
maximum motor capacity of the controller in alphanumeric codes. Refer to Figure 2.1 for example (22kw, 400V rank).
BL6 - U O 4 022 - W
Controller series Additional Type
Maximum machine power None:Serial integrated
Controller type 002:2.2KW controller (with glass
U: Elevator in-built controller 003:3.7KW Shield or no Shield)
S: High performance inverter 005:5.5KW W:with metal Shield
007:7.5KW B:parallel
Protective structure 011:11KW C : Ultra-thin without
C: Closed type 015:15KW sheel
O: Open type 018:18.5KW S:Small size
022:22KW H:For home lift
Voltage level 030:30KW
4:380V 037:37KW
2:220V 045:45KW
055:55KW
075:75KW
(Bar code)
5
Chapter 2: Introduction and Installation
2.3. Specifications
Specifications of BL6-B series elevator integrated controller in chart 2.1.
5.5 9 14 18 27 34 41 48
RATED OUTPUT CURRENT(A)
65 80 96 128 165
MAX OUTPUT VOLTAGE(V) 3-PHASE, AC380 (CORRESPONDING TO THE INPUT VOLTAGE)
RATED FREQUENCY(H Z ) 50
MAX OUTPUT FREQUENCY(H Z ) 120
RATED VOLTAGE (V) 3-PHASE, AC380
RATED FREQUENCY (H Z ) 50
INPUT POWER
10 12 17 22 32 41 49 58
RATED INPUT CURRENT (A)
78 96 115 147 190
ALLOWABLE VOLTAGE FLUCTUATION ±15%
ALLOWABLE FREQ FLUCTUATION ±5%
MODEL BL6-B□20□□-□□ 2002 2003 2005 2007 2011 2015 2018 2022
MAX MOTOR POWER(KW) 2.2 3.7 5.5 7.5 11 15 18.5 22
RATED OUTPUT CAPACITY (KVA) 4 7 10 14 20 27 33 40
RATED OUTPUT
6
Chapter 2: Introduction and Installation
L OW OPTO -ISOLATED INPUTS 26-CHANEL SWITCHES: RATED LOAD: 7MA/DC24V, UPPER FREQ100HZ
HIGH OPTO - ISOLATED INPUTS 3-CHANEL SWITCHES: RATED LOAD: 8MA/AC110V, UPPER FREQ100HZ
12-CHANEL SWITCHES:
PROGRAMMABLE RELAY OUTPUT 9 CHANNELS: 1NO, CONTACTOR CAPACITY: 5A/30VDC, 5A/250VAC
3 CHANNELS: 1NO, CONTACTOR CAPACITY: 8A/30VDC, 10A/250VAC
CAN COMMUNICATION INTERFACE 2CHANELS:DUPLEX/ GROUP CONTROL,HOP/COP,REMOTE WIRELESS MONITORING
RS-232COMMUNICATION INTERFACE 1CHANEL: DIGITAL OPERATOR/ PC MONITORING/ PROGRAMMABLE INTERFACE
DIGITAL OPERATOR LCD DISPLAY IN CHINESE/ENGLISH
DISPLAY
M ONITORING SOFTWARE
DISPLAY PARAMETERS, ELEVATOR RUNNING STATUS, DIGITAL WAVE
INTERFACE
OVER CURRENT STOP WHEN CURRENT EXCEED 200% RATED OUTPUT CURRENT
MAIN PROTECTION FUNCTION
7
Chapter 2: Introduction and Installation
DOOR INTERLOCK FAULT PROTECT AT DOOR INTERLOCK CIRCUIT OPEN WHEN RUNNING
SAFETY CIRCUIT FAULT PROTECT AT SAFETY CIRCUIT OPEN WHEN RUNNING
BRAKE CIRCUIT FAULT NO BRAKE OPEN FEEDBACK SIGNAL AFTER OUTPUT BRAKE OPEN COMMAND
L EVELING ZONE FAULT PROTECT AT LEVELING ZONE SIGNAL FAULT
OUTPUT CONTACTOR FAULT PROTECT AT OUTPUT CONTACTOR FAULT
RUNNING TIME PROTECTION PROTECT AT SIGNAL RUNNING TIME EXCEEDS LIMIT
FLOOR COUNTING FAULT PROTECT AT FLOOR COUNTER FAULT
COMMUNICATION INTERFERENCE
PROTECT AT COMMUNICATION INTERFERENCE FAULT
FAULT
HOISTWAY PARAMETER LEARNING
HOISTWAY PARAMETER LEARNING FAULT PROTECTION
FAULT
BL6-B series elevator controller has Without shield type and shield type .Different from BL3-U series elevator controller,
BL6-B can be installed only by hanging method. Refer to Figure 2.3-2.6 and chart 2.2-2.3 for appearance and exterior
dimension of BL6-B series elevator controller.
8
Chapter 2: Introduction and Installation
FIGURE 2.3 WITHOUT SHIELD TYPE EXTERIOR DIMENSION FIGURE 2.4 W ITHOUT SHIELD TYPE APPEARANCE
Exterior Dimension
Voltage Max Motor Weight
Controller Model Figure
level Power (KW) W H D W1 H1 H2 kg
2.2 BL6-BO4002
3.7 BL6-BO4003 200 290 173 170 275 8 5.6
BL6-BO4005-S
5.5
BL6-BO4005 6.5
400V 3-phase
7.5 BL6-BO4007 7
225 348 193 190 333
11 BL6-BO4011 Figure 2.3 8
8.5
15 BL6-BO4015 8.5
18.5 BL6-BO4018 13
280 418 203 230 403
22 BL6-BO4022 13
30 BL6-BO4030 320 480 228 270 460 10 19
37 BL6-BO4037
441 650 324 310 626 10.5 46
45 BL6-BO4045
2.2 BL6-BO2002 200 290 173 170 275 8 5.6
3.7 BL6-BO2003 7
5.5 BL6-BO2005 225 348 193 190 333 8.5 8
200V 3-phase
9
Chapter 2: Introduction and Installation
Note: 5.5kw BL6 has two dimensions: Dimension of model BL6-BO4005-S and BL6-BO4005-SC is same as above chart.
Dimension of model BL6-BO4005 and BL6-BO4005-C is same as 7.5-15kw BL6. Please distinguish while installation
and using.
FIGURE 2.5 SHIELD TYPE EXTERIOR DIMENSION FIGURE 2.6 SHIELD TYPE A PPEARANCE
5.5
BL6-BO4005-W
Figure 2.5 7.5
7.5 BL6-BO4007-W
225 348 200 190 333
11 BL6-BO4011-W 9
8.5
15 BL6-BO4015-W 9
18.5 BL6-BO4018-W
280 418 210 230 403 14
22 BL6-BO4022-W
2.2 BL6-BO2002 200 290 180 170 275 8 6
3.7 BL6-BO2003 8
200V 3-phase
Note: 5.5kw controller has two type of dimensions:Dimension of model BL6-BO4005-SW is as above chart. And
Dimension of model BL6-BO4005-W is same as dimension of 7.5-15kw controller. Please distinguish them when
installation.
10
Chapter 2: Introduction and Installation
NOTES METHOD
Check if product model is correct. Check the model on the nameplate.
Check if product is broken. Check exterior for any damage caused by shipment.
Check mounting structure. Tighten the loose components with a screw
Check if mounting structure is loose.
driver, if required.
Remove the front cover, and check mounting structure. Tighten the
Check if main control board is loose.
loose component switch a screw driver, if required.
With any abnormalities above, please contact the company or regional office.
2.6. Installation
2.6.1 Installation Site
Install BL6-B series elevator controller in an area that meets the requirements listed in chart 2.5
11
Chapter 2: Introduction and Installation
Release the screw at the terminal cover (arrow), raise the cover according to arrow direction to remove the cover for
wiring.
Figure 2.7 Remove terminal cover on shield type Figure 2.8 Without Shield type elevator controller
12
Chapter 2: Introduction and Installation
Install the controller vertically to avoid reducing the cooling effect. When installing the controller, please make sure
that installation space is greater than that shown in Figure 2.9, in order to ensure that the BL6-B series elevator
integrated controller normal working and cooling.
Elevator is a typically potential energy load type device. When the elevator is in brake mode, the electricity feedback of
motor will make the DC bus voltage increase. Some additional brake component should be applied to release the
energy. Otherwise, over-voltage protection will be activated. BL6-B series elevator controller has internal brake unit,
customers just need to equip appropriate braking resistor. The numerical value of resistance and power depend on the
motor capacity.
13
Chapter 2: Introduction and Installation
14
Chapter 2: Introduction and Installation
15
Chapter 2: Introduction and Installation
16
Chapter 2: Introduction and Installation
17
Chapter 2: Introduction and Installation
18
Chapter 2: Introduction and Installation
19
Chapter 2: Introduction and Installation
20
Chapter 2: Introduction and Installation
21
Chapter 3:Wiring
Chapter 3: Wiring
This chapter describs the terminals and wiring specifications for main circuit, control circuit and PG card of the
integrated controller.
22
Chapter 3:Wiring
Note: In “Intensive Serial Communication Resolution” of Appendix 6, the terminal with “*” has no need to wire except
X5. For more detail, please check Appendix 6.
P1 B1 B2
R U
S V
T W
PE Control circuit
23
Chapter 3:Wiring
When wiring the main circuit, please pay attention to the following maters.
24
Chapter 3:Wiring
4. Terminals Wiring
If there is no phase sequence requirements, the input power supply can be connected with any one terminal (R, S,
T) the phase sequence of input power supply does not necessary correspond to the terminal sequence.
4. Never use capacity, surge absorber, power factor regulator and noise filter.
Never connect capacity, surge absorber, power factor regulator and noise filter to output circuit. The
high-frequency components of the controller output may result in overheating or damage to these parts or may
result in damage to the controller
1. Ensure that earth protection terminal PE connects to ground (Grounding resistance less than 10Ω).
25
Chapter 3:Wiring
2. Do not share the GND with other devices such as welding machines or power tools.
3. GND wire should be as short as possible and should be as thick as possible.
4. Connect to earth at one point.
3.2.5.4 CONNECT BRAKE RESISTOR
1. There is an internal brake unit in the controller, but must equip an external resistor to absorb the feedback
energy during brake. Refer to chart 2.6for the configurations of the brake resistance.
4. The installation of the braking resistor should consider the need of cooling. If necessary, Fans and protection
cover can be applied to ensure ventilation and away from burn, electric shock and fire.
26
Chapter 3:Wiring
4x Φ 4.0
Digital tubes & operation keys
Input interface
Output
204 213
PG card
interface
189
213
FIGURE 3.4 TERMINAL ARRANGEMENTS FOR CONTROL CIRCUIT
Control circuit includes integrated control board, PG card, digital operator and so on. PG card and digital operator will
be introduced separately in Chapter 4. As elevator floor varies, the input, output of the controller and CAN
communication interface is separate with the other parts of the controller, so the I/0 interface of the controller should
be connected with DC 24V power supply. Besides, DC 24V can also be used with HOP and COP. So the power supply
should be equipped with suitable capacity according with the floor.
27
Chapter 3:Wiring
X36+ J1-1 Door inter-lock input + (110V-220VAC) Input OC AC110V 10mS 100Hz
X36- J1-2 Door inter-lock input – (110V-220VAC)
8mA
Y0 J1-3 KBC brake output
28
Chapter 3:Wiring
Chart 3.3 Control Circuit Port definition and function list (Cont’d)
Interface Tech Spec
Port Terminal
Location Definition Usage
No. Symbol
Rated On/off
Interface Type Max Speed
Capacity Time
29
Chapter 3:Wiring
Chart 3.3 Control Circuit Port definition and function list (Cont’d)
J9 X20 J9-6 SGM door close signal input 1 Input OC DC24V 7mA 10mS 100Hz
X21 J9-5 SKMW1 door open limit input 1
X22 J9-4 SGMW1 door close limit input 1
X23 J9-3 STAB1 safe plate 1 input
X24 J9-2 SDS electronic lock signal input
X25 J9-1 SCZ over-load input
X26 J10-10 SMZ full-load input
X27 J10-9 Spare
X28 J10-8 Light-load input
X29 J10-7 SZH Attendant input
J10 X30 J10-6 SZS Bypass drive input Input OC DC 24V 7mA 10mS 100Hz
X31 J10-5 Brake position switch input
X32 J10-4 Thermal switch input
X33 J10-3 SKM2 door open input 2
X34 J10-2 SGM2 door close Input 2
X35 J10-1 Standby
30
Chapter 3:Wiring
Chart 3.3 Control Circuit Port definition and function list (Cont’d)
Note: 1. Definition of DIP switches: Normally, please set all 4 DIP switches to OFF status.
In addition to the terminals above, there are some debugging interfaces on the main control board.
600V plastic insulated wire should be used. Choose appropriate wire model based on terminal function and Refer to
Chart 3.5.
The common terminal of board for digital value input interface is +24V,so it should be contactor input or common
emitter input ( 0V common terminal ) as shown in Figure 3.5 and Figure 3.6.
31
Chapter 3:Wiring
vcc
+24V
X0~X25
COM
vcc
+24V
X0~X25
COM
0H CAN-H
0L CAN-L
The controller, COP and HOP are connected through CAN bus. The reliability of CAN BUS communication is directly
related to cable wiring. It is specifically required that shaft cable and traveling cable should be twisted-pair shield cable.
The twisted-pair can stop the differential mode interference of the long wire while shield can isolate the
32
Chapter 3:Wiring
electromagnetic interference caused during elevator running. The function and connection of the CAN communication
interface is shown in the Figure 3.7.
The voltage range of analog input interface is -10~+10V,for selecting the load information provided by weighing device.
As analog signal is easy to get interference, the wire of analog input terminal should be TWISTED-PAIR SHIELD CABLE.
Its input and connection is shown in Figure 3.8.
AG0_IN
GND_IN
AC 110V input interface is for testing of Emergency stop/Door Drive. Its interface/connection is shown in Figure 3.9.
33
Chapter 3:Wiring
PG_V6 interface card is sync/async machine universal pulse encoder speed feedback and frequency dividing output
card.
PG_V6 is in supporting use of 5V line driver output type encoder. Encoder for async machine: A/B, and encoder for sync
machine: A/B/Z/U/V/W. Refer to Figure 3.11 below for detail.
When installing PG_V6 card, first cut off the controller power supply, ensure that charge indicator LED in the controller
is out. Then remove the digital operator and the front cover and install the PG_V6 card.
34
Chapter 3:Wiring
Installation procedures: first match the connector of the PG_V6 card (welding parts) towards the JPGR connector of the
main control board. Match the other two installation hole toward the corresponded two nylon tube (pre-installed).
Then keep the PG_V6 card horizontal and fix the nylon screws to location holes by screwdriver.
Removing procedures: first cut off the controller power supply, ensure that the charge indicator LED in the controller is
out. Then remove the digital operator and front cover, remove the terminal connection of PG_V6 card. Removed wire
should be treated carefully, not contact with other charged objects. Then remove the nylon screws by screw driver,
then remove the PG card.
1. Don’t touch the chip with bare hand directly to avoid the static charge damage the chip.
2. Choose suitable tool, such as screwdriver, needle point pliers and else.
3. Never damage the components of the card.
4. Never damage the components of the main control board.
5. While recovering the connection, please connect as per wire number and the requirements; make sure that the
connections are correct.
3.4.1.3 PG_V6 Terminal Definition & Function List
Differential
U+ JG1-2 U+ Differential signal U+ ±20mA/3.1-5V 500KHz
input
Differential
Z+ JG1-3 Z+ Differential signal Z+ ±20mA/3.1-5V 500KHz
input
Differential
B+ JG1-4 B+ Differential signal B+ ±20mA/3.1-5V 500KHz
input
JG1
Differential
A+ JG1-5 A+ Differential signal A+ ±20mA/3.1-5V 500KHz
input
Power supply
GND JG1-6 GND 5V GND --
GND
Differential
U- JG1-7 U- Differential signal U- ±20mA/3.1-5V 500KHz
input
Differential
Z- JG1-8 Z- Differential signal Z- ±20mA/3.1-5V 500KHz
input
35
Chapter 3:Wiring
The parameters above are for PG_V6 interface card work in the environment temperature of 0 ̊C-70 ̊C, if the
temperature exceeds the range, PG interface card may not work normally or even damage.
3.4.1.4 PG_V6 Connection for 5V long line drive output encoder (for Asynchronous Machine)
Connection of PG_V6 card and 5Vlong line driver output encoder (for asynchronous machine) is shown in Figure 3.12.
Connect the 5V/B+/A+/B-/A-/0V on the encoder to the PG card D-type connector JG1 (standard 3-line 15-pin
D-type connector hole socket) terminal+5V/B+/A+/B-/A-/GND, that is the D-type connector pin socket
terminal corresponding 1/4/5/9/10/6 of JG1. Ensure that the wiring correct, then then plug and lock well.
FIGURE 3.12 PG_V6 CARD CONNECTION TO 5V LONG LINE DRIVE OUTPUT ENCODER (FOR ASYNCHRONOUS MACHINE)
3.4.1.5 PG_V6 card connection with 5V long cable drive output encoder (for Synchronous Machine)
The connection of PG_V6 card and 5V long line drive output encoder(for synchronous machine)is shown in Figure 3.13.
36
Chapter 3:Wiring
Figure 3.13 PG_V6 connection with 5V long line drive output encoder (for synchronous machine)
For the 15-pin differential output encoder interface of the PG_V6 card, the input pulse signal frequency is required to
be no more than 500 KHz, the parameter of the input and output signal current and voltage cannot exceed the range
given in the chart 3.6 above.
If the parameter of the input and output signal current and voltage exceed the given range, the PG interface card may
not work normally, even PG card and encoder get damaged.
Manufacturer suggests that if the external circuit working condition is not well, please do not power other circuits
except the encoder by using the PG_V6 interface card +5V power supply to avoid PG card being interfered or damaged.
37
Chapter 3:Wiring
PG_V6X interface card is async machine universal pulse encoder speed feedback and frequency dividing output card.
PG_V6X is in supporting use of 12V OC output type, and push-pull output pulse encoder. Encoder for async machine:
A/B. Diagram is shown in Figure 3.14 below.
When installing PG_V6X card, first cut off the controller power supply, ensure that charge indicator LED in the
controller is out (Remove the front cover first for shield type controller). Then remove the digital operator and the
front cover and install the PG_V6X card.
Installation procedures: first match the connector of the PG_V6X card (welding parts) towards the JPGR connector of
the main control board. Match the other two installation hole toward the corresponded two nylon tube (pre-installed).
Then keep the PG_V6X card horizontal and fix the nylon screws to location holes by screwdriver.
Removing procedures: first cut off the controller power supply, ensure that the charge indicator LED in the controller is
out. Then remove the digital operator and front cover, remove the terminal connection of PG_V6 card. Removed wire
should be treated carefully, not contact with other charged objects. Then remove the nylon screws by screw driver,
then remove the PG card.
1. Don’t touch the chip with bare hand directly to avoid the static charge damage the chip.
2. Choose suitable tool, such as screwdriver, needle point pliers and else.
3. Never damage the components of the card.
4. Never damage the components of the main control board.
5. While recovering the connection, please connect as per wire number and the requirements; make sure that the
connections are correct.
38
Chapter 3:Wiring
The parameters above are for PG_V6X interface card work in the environment temperature of 0 ̊C-70 ̊C, if
the temperature exceeds the range, PG interface card may not work normally or even damage.
3.4.2.4 PG_V6Xcard connection with 12V push-pull /OC drive output encoder (for Asynchronous
Machine)
The connection of PG_V6X card and 12V push-pull/OC output encoder (for asynchronous machine) is shown in Figure
3.15.
Connect the 12V/B/A/0V of encoder to the +12V/IB/IA/0V of the terminal JEN (the related pin of 4/3/2/1 of
JEN).
39
Chapter 3:Wiring
FIGURE 3.15 PG_V6X CONNECT WITH 12V PUSH-PULL/OC DRIVE OUTPUT ENCODER
For the push-pull/OC output encoder interface of the PG_V6X card, the input pulse signal frequency is required to be
no more than 500 KHz, the parameter of the input and output signal current and voltage cannot exceed the range
given in the chart 3.7 above.
If the parameter of the input and output signal current and voltage exceed the given range, the PG interface card may
not work normally, even PG card and encoder get damaged.
Manufacturer suggests that if the external circuit working condition is not well, please do not power other circuits
except the encoder by using the PG_V6X interface card +5V power supply to avoid PG card being interfered or
damaged.
Please note that user will take responsibility for the consequence caused by the reasons above.
SPG_V6 interface card is sync/async machine universal sine cosine encoder speed feedback andfrequency dividing
output card.SPG_V6 is in supporting use of 5V line driver output type sine cosineencoder.Encoder for async
machine:A/B, and encoder for sync machine:A/B/R/C/D.
Refer to Figure 3.16 below for detail.
40
Chapter 3:Wiring
Chart 3.8 SPG_V6 Terminal Definition & Function (D-input/output refers to Differential input/output)
Power Supply
Frequency signal Sync-frequency OC/ push-pull
A+ JEN -2 ±50mA 500KHZ
OC output A+ division output
JENDAT
+500mA/5V±2.5%
5V JG1-9 +5V 5Vpower Power output Voltage
ripple<50mV
C- JG1-10 C- Differential signal C- D-input 40KHz
C+ JG1-11 C+ Differential signal C+ D-input 40KHz
D+ JG1-12 D+ Differential signal D+ D-input 40KHz
D- JG1-13 D- Differential signal D- D-input 40KHz
* JG1-14 -- -- --
* JG1-15 -- -- --
41
Chapter 3:Wiring
The resistor for ground terminal GND_E is not essential component. There might be different requirement
between different versions.
1. Sine/cosine PG card can provide power output of 5V±2.5%/500mA for encoder. If the current required exceeds
the PG card rated value, it may damage the PG card or encoder.
2. The cut-off frequency of the analog input signal is requested to be lower than 40KHz. This is decided by filter
circuit. If the input signal bandwidth exceeds this range, PG card cannot guarantee to analyze the signal correctly
and the driver may not work properly.
3. If use the frequency output function that PG card provided, make sure that the current in frequency dividing
interface is within rated level to avoid any unwanted circuit protection mechanism. Also, the maximum
frequency dividing output rate is 250KB/S; beyond such limit of the speed rate may cause frequency dividing
signal not output properly.
4. The two ground terminal of GND_E is connected inside. At site, one terminal is required to connect to the system
GND wires, and the GND resistance should be minimized with independent ground connection point. The other
terminal is connected to the shielding layer of the signal cable for the sine/cosine encoder. For the shielding
layer of the signal cable, it is suggested that two terminals are grounded at both sides or at the end terminal of
GND_E side. As the output signal of the sine/cosine encoder is small analog signal which is easier to get
interference, it is better to use the recommended signal cable with complete shield layer, lower transfer
impedance and wire twin twisted. Inappropriate ground connection or use unsuitable signal transfer cable may
result in system not working properly.
42
Chapter 3:Wiring
SPG_V6E interface card is sync/async machine universal sine cosine encoder speed feedback andfrequency dividing
output card.SPG_V6 is in supporting use of 5V line driver output type sine cosineencoder.Encoder for async
machine:A/B, and encoder for sync machine:A/B/R/C/D. (Suitble for ECN1313)
Refer to Figure 3.18 below for detail.
50
56
111
117
Chart 3.9 SPG_V6E Terminal Definition & Function (D-input/output refers to Differential input/output)
Power Supply
Frequency signal Sync-frequency OC/ push-pull
A+ JEN -2 ±50mA 500KHZ
OC output A division output
JENDAT
* JG1-2 -- -- --
* JG1-3 * JG1-2 -- -- --
* JG1-4 * JG1-2 -- -- --
43
Chapter 3:Wiring
Chart 3.9 SPG_V6E Terminal Definition & Function (D-input/output refers to Differential input/output)(Cont’d)
ripple<50mV
C- JG1-10 Clock- Differential signal C- D-input 40KHz
C+ JG1-11 Clock+ Differential signal C+ D-input 40KHz
D+ JG1-12 Data+ Differential signal D+ D-input/output 40KHz
D- JG1-13 Data- Differential signal D- D-input/output 40KHz
* JG1-14 -- -- --
* JG1-15 -- -- --
1. Before connection, please pay attention to the precautions mentioned in chapter 1.2, especially the “warning”
and “caution” part.
2. Before connection,make sure that the power supply is off, and the charge indicator LED is out.
3. Please ask professional engineers with training and authorization for the wiring.
4. The wire size and clamping torque should follow the regulation of Chart 3.2 and chart 3.4
5. To increase wiring convenience and reliability,it is better to use round crimp type terminal ( for main circuit ) and
club-shaped terminal ( for control circuit).
7. CAN communication cable、encoder cable、encoder frequency output cable and analog input cable should use
TWISTED-PAIR SHIELD CABLE.
44
Chapter 3:Wiring
8. Please ground the cable shield wire correctly, and maximize the contact area.
9. Make sure the signal cable for PG/encoder is less than 30m in length, and as short as possible.
10. Make sure the cable between controller and machine is less than100m, and as short as possible.
11. Make sure the brake resistor is connected between B1 and B2.
12. Make sure the connection of ground terminal PE is secure, do not share the ground cable with other devices such
as welding machines or power tools. Minimize length and dimension of ground cable and ground at one point.
3) Whether the connection of the screw, the terminals and the connection parts is loose.
45
Chapter 4: Operator
The digital operator OP-V6 has the main LCD screen with resolution of 128×64 LCD, 5 LED and 11 function buttons.
Refer to Figure 4.1 below for detail.
5 leds on the top of the operator display controller current state simply and directly. The definition and display function
of each LED, as shown in chart 4.1.
Name Function
DRV When the controller is in operation, the led light.
FWD When the controller is in forward running operation, the led light.
REV When the controller is in reversal running operation, the led light.
COM When the controller communication is normal, the led light.
ERR When the controller is in fault, the led light.
46
Chapter 4: Operator
47
Chapter 4: Operator
The main interface displays the main information of the elevator in present status, including floor number, elevator
speed, running direction, door lock status, running model, fault code and else. On the main interface, the above
information is live updated.
The instructions for the information shown in the Digital operator LCD display interface are as following:
48
Chapter 4: Operator
The connection for the digital operator of the opening controller is as follows: remove the front cover of the controller,
connect one side of the special communication cable to digital operator, and connect the other side to the J232_T
connection on the main board. Make sure the connection is securely; install the front cover of the controller.
1. The installation, dismantle, insert and remove of the digital operator can be carried out when the
controller is power-on. That is to say, hot plug is accepted by the digital controller.
2. Please install, dismantle, insert and remove the digital operator carefully to avoid unwanted damage of
the digital operator.
3. Please save the removed digital operator and communication cable well, DO NOT press, damage the
operator or put it in extreme environment.
49
Chapter 4: Operator
The structure and interface switch process of the digital operator, as shown in Figure 4.3.
50
Chapter 4: Operator
……
In the interface of parameter menu: Press [ENTER] key to enter the interface. (First, it should input the correct user
password in the environment setting menu, otherwise, pressing the [ENTER] key will enter the interface of user
password setting. So please pay attention to distinguish the factory password and user password. If you want to input
the factory password, please press the [ESC] key, returning to previous menu, then press the [DOWN] key to change
the prompt to “input the factory password”, after that press the [ENTER] key, entering to the interface of the inputting
factory password). Press the [UP] or [DOWN] key to check all the parameters. Please press the [ENTER] key to enter the
interface of parameter menu. Please press [LEFT] or [RIGHT] key to move the arrow to left or right. Press the [UP] or
[DOWN] to increase or decrease the value that the arrow point at. After setting the value, please press the [ENTER] key
to save the parameter.
Some parameter values are combination values of the status. Their setting cannot follow the above flowchart directly
and should follow the ToolTip in the parameter changing interface. Press [RES] key to enter the bit parameter setting
interface to set the status value as per the bit. After enter the bit parameter setting interface, press [UP] or [DOWN]
key to check the status of the present bit. When the status of the present bit need to be changed, press [ENTER] key to
enter the status change interface. In the status change interface, press [UP] or [DOWN] key to check the status of the
present bit, press the [ENTER] key to save the status of the present bit, press [ESC] key to return the Previous Menu
51
Chapter 4: Operator
……
FIGURE 4.5 SETTING BIT PARAMETERS
In commissioning interface: Move the arrow by pressing [UP] key or [DOWN] key to carry out the operation, press
[ENTER] to enter the selected interface.
In floor selection interface: Press [UP] key or [DOWN] key to check the car call status in present floor. If need to set car
call on current floor, press [ENTER] key in the interface to save the car call information. In the interface, the
information follow “F:” is the present floor the elevator car at.
In the interface of door control: Press [LEFT] key in the interface to carry out the command “opening front door”. Press
[RIGHT] key to carry out the command “close front door”. Press [UP] key to carry out the command “open rear door”.
Press [DOWN] key to carry out the command “close rear door”, Press [RES] key to cancel all the commands.
52
Chapter 4: Operator
In Motor Control interface: Press [UP]/ [DOWN] key to select the running mode is continuous running or JOG. In
continuous running mode, press [RUN] key to start motor first, press [UP]/ [DOWN] key to increase/decrease the
motor given speed. The motor given speed can be negative (negative speed means motor reverse run), press [ENTER]
key to save the given speed. Press [STOP] key to stop the motor. In the mode of JOG, press [UP]/ [DOWN] key to
increase/decrease the JOG operation frequency, after press the [ENTER] to save the setting, and then press the [RUN]
key to start, and press the [STOP] to stop the operation.
The process of operator to control the motor running is shown below in the Figure 4.8.
In interface of call testing: Press [UP]/ [DOWN] key to check the connections for all floors. Normally, it displays running
success, otherwise it shows fails. Press [ESC] key to return to the Previous Menu.
53
Chapter 4: Operator
Modified(D) [ENTER]
Call Test(D3)
Door Ctrl(D1) 01 call test
Motor Ctrl(D2) [ESC] D3-00:Success
Call Test(D3)
[ ]
[ ]
Call Test(D3)
02 call test
D3-01:Success
[ ]
[ ]
[ ]
[ ]
Call Test(D3)
06 call test
D3-05:Success
OK Communication normal
ER Controller receiving data error (please check communication connection & car control board), when there
appears a numerical value, it refers to the times of error on car control board communication.
OK communication good
ET the controller sending data error (please check landing call communication connection), when there appears a
figure, it refers to the times of error on system communication.
54
Chapter 4: Operator
ET/ER Duplex control system communication abnormal (When choose this option)
In the interface of saving parameter, press the [ENTER] to save all the parameters in the F menu. During saving process,
LCD will display “Waiting”; after saving, it will display “Success” or “Failure”. The flowchart of saving parameter is
shown in the Figure 4.11.
In hoistway learning interface: when status display “To Down limit”, the hoistway learning cannot start directly. The
elevator should manual run to the down limit position first, and “To Down limit” status disappear, the screen will
display “[ENTER] to start”, press the [ENTER] key to start hoistway learning. During the learning process, the interface
will display the current learning floor and display the status of “Waiting”, when the hoistway learning is completed, the
status will display “Success”, when there are errors during the hoistway learning, the status will display “ERR” and
display error code. Press [ESC] key to return the Previous Menu.
55
Chapter 4: Operator
Motor Auto-tuning includes two parts: Motor angle tuning and motor parameter tuning. In the interface of Motor Tune:
Press [UP] or [DOWN] key to move the arrow to select related tuning information; Press [ENTER] key to enter the
pointed tuning interface.
In the interface of Motor Angle Tuning and Motor Parameter Tuning, press [ENTER] to start turning. During tuning, the
operator display “waiting”; after tuning, it will display “success”. During tuning, if there is error, the tuning process will
be terminated, and LCD will display “Tune End”, and the status is “error”, with error code followed.
Before auto-tuning process, make sure to set the parameters in the F5 & F8 menu first.
Make sure motor has no load, first carry out motor parameter tuning, then carry out the motor angle tuning. Press [ESC]
key to return to the previous menu. The flowchart of the motor learning is shown in Figure 4.13.
Motor Load Tuning also includes two parts: Light loaded tuning and Full-loaded tuning.
In the interface of load tuning: Press [UP] or [DOWN] move the arrow to select related tuning information; press
[ENTER] key to enter the pointed tuning interface.
In light-loaded tuning or full-loaded tuning interface: Press [ENTER] to start tuning process, the operator display the
present status. Press [ESC] key to return to the Previous Menu.
56
Chapter 4: Operator
In the interface of time setting, the last two digit of “Year”, “month”, “day”, “hour”, “Minute” and “second” are
editable, press [LEFT] or [RIGHT] to move the arrow to the right place. Press [UP] or [DOWN] key to change the pointed
value. After setting: Press the [ENTER] key to save. Press [ESC] key to return the Previous Menu.
In the interface of Fault Record: Press [UP] or [DOWN] key to check the elevator and controller fault record. Press
[ENTER] to enter the selected fault record, press [UP] or [DOWN] key to check the latest 30 fault history record.
Each elevator fault record includes error code, time, elevator status at fault (Floor number, running direction, running
speed, I/O state), and related information. This helps to find the root cause of the elevator fault and guide the elevator
maintenance.
Each controller fault record includes error code, time, elevator status at fault and other important data (Running speed,
line/BUS voltage and current).This helps to find the root cause of the controller fault and guide the elevator
maintenance.
The flowchart of the fault record check is shown in the Figure 4.16.
57
Chapter 4: Operator
In environment initialization interface, the display language, the parameter visit grade, input password and the
shortcut menu of the operator can be set.
Initialization [ENTER]
Initialization
Language Sel Language Sel ……
A0-00:CHN [ESC] A0-00:CHN
[ ]
[ ]
Initialization [ENTER]
Initialization
User Password User Password ……
A0-01:00000000 [ESC] A0-01:00000000
[ ]
[ ]
Initialization [ENTER]
Initialization
Factory Password Factory password ……
A0-02:00000000 [ESC] A0-02:00000000
[ ]
[ ]
Initialization [ENTER]
Initialization
Contrast Contrast ……
A0-04:5 [ESC] A0-04:5
58
Chapter 4: Operator
Language Selection
The flowchart for the language selection is shown in the Figure 4.18.
Press [UP] or [DOWN] to select language, and press [ENTER] key to save the selection.
In the interface of password, press the [LEFT] or [RIGHT] key to move the arrow to the pointed position, press [UP] or
[DOWN] key to increase or decrease the pointed value, press the [ENTER] key to input the password. When password
input is incorrect, “invalid password” will be displayed, and the password cannot be changed at this time. When the
password input is correct, “Password OK” will be displayed, next press [ENTER] first then press [RES] key to enter the
password setting interface and reset the password. Resetting password is similar to input password. Finally press the
[ENTER] key to save the new password.
The flowchart of the password input and change is shown in the Figure 4.19.
The process of the factory level password input and setting refers to the user level password input and setting.
Contrast setting
Set the LCD display gray scale. Press[RES] key to change de display grayscale.
59
Chapter 4: Operator
The function parameter copy is to simplify the parameter setting and commissioning process, especially for multiple
elevators with same configurations. After finishing the parameter setting and commissioning of one elevator, this
function can copy all the parameters (Saved in the digital operator memory), take the digital operator and connect to
other elevators, copy all the parameters to the controller, check parameters, and the elevator can run normally.
In the interface of parameter copy: Press [UP] or [DOWN] key to move the arrow to carry on the necessary operation,
press the [ENTER] key to start operation.
If necessary, the controller can be restored to the factory (default) setting. Press the [ENTER] key to restore the factory
setting, the interface will display the status and the result.
The flowchart of restore the factory setting is shown in the Figure 4.23.
60
Chapter 4: Operator
When using Blue-Light Integrated Controller, if the traction machine is also made by Blue-Light, you only need to input
the machine model number and encoder information on the machine name plate to finish the parameter setting of the
machine.
The interface of the Blue-Light machine input is showing in Figure 4.24(a). The input content has three parts, separated
by “.”. The first part is the model number(separated in 4 digits), the middle part is encoder resolution information, the
last part is the PG model. The detail information is showing in Figure 4.24(b).
Use [UP] or [DOWN] key to set the content of the pointed area, then press the [ENTER] key to confirm. The cursor is
then moved to next bit. If the pointed area is not set, the cursor will not move even you press the [ENTER] key (Except
the 4th number of the machine model, e.g. S1.0D- as the last number is empty, you can press the [ENTER] key directly
to set the next bit).
The flow chart of the Blue-Light machine input is shown below in Figure 4.25 (S0.75D as an example).
61
Chapter 5: Parameters
Chapter 5: Parameters
According different function, parameters are divided into groups as shown in chart 5.1.
SL Motor Type
62
Chapter 5: Parameters
After hoistway learning, please check the floor calibration, if the calibration value is higher than expected, it is possible
that elevator’s rated speed setup is higher than the actual value or elevator encoder pulse setup is smaller than the
actual pulse. If the calibration value is too low, it is possible that elevator rated speed setup is lower than the actual
value or its encoder pulse setup is larger than the actual pulse.
Hoistway location parameter’s number, description and content are shown in chart 5.2
Para Ref
Display Content Range Unit
No. Page
The location of bottom limit in hoistway. Data
U0-00 Lower Limit will be recorded after finishing hoistway -- m --
learning
63
Chapter 5: Parameters
5.3.2 Monitoring Parameter for I/O Status, Cabin Signal & Interference Appraisal (U1-U5)
Chart 5.3 U1~U5 Monitoring Parameter List
Para Ref
Display Content Range Unit
No. Page
Controller input data show in decimal type. It
U1-00 Input Data will be turned into binary type to show the -- -- 29
logical status of the input port.
Input Bin Input port data show in binary type .Each data
U1-01 -- --
correspond to logical status of one input port.
64
Chapter 5: Parameters
Para
Display Content Range Unit Ref Page
No.
For the meaning of input status U1-01 AND output status U2-00, please refer to the control terminal
definition chart 3.3. (Page29)
Cabin signal symbol definition and content isshown in chart 5.4. (Page 63).
65
Chapter 5: Parameters
66
Chapter 5: Parameters
“N” states the parameter cannot be changed in the process of running. ”Y” states the parameter can be
changed in the process of running. It has same meaning in the following Chart.
When elevator rated speed/Single floor running speed is lower than 0.5m/sec, please properly decrease the
acceleration B1, deceleration B2; otherwise it will affect the system calculation of current speed. When user
modifies the two speed value out of limit, system will reset to the data before modification.
67
Chapter 5: Parameters
Acceleration B1, deceleration B2,S curve P1,P2,P3,P4 work together to determine the final speed curve and
its trend. These parameters have internal relation with each other and are not allow to change at will. When
the modified value is out of limit, the value will recover to the previous data.
68
Chapter 5: Parameters
69
Chapter 5: Parameters
70
Chapter 5: Parameters
Hour:
00:00
F2-20 Stop Time1 System will run bypass the set floor minut
… 00:00 Y
F2-21 start until this time. e
23:59
The elevator automatic switch: F2-14,F2-15 F2-16,F2-17 were set separately as per hours and minutes.
Please follow the operator indication for this setting.
71
Chapter 5: Parameters
72
Chapter 5: Parameters
Note: See more detail of F4-06 and F4-07, please refer to Chart 6.4.
73
Chapter 5: Parameters
74
Chapter 5: Parameters
75
Chapter 5: Parameters
F9-21 FULL Comp Pro Full load compensation proportion 0~200 100 -- Y --
76
Chapter 5: Parameters
Special parameters (FC) are mapping a part of factory parameters (FX) in customer level; users can access this part
information by user level password. In these parameters, FC-00~FC-06 can only be viewed but not editable, while other
parameters can be changed. Special parameters (FC) number, description and content are shown below in Chart 5.16.
77
Chapter 5: Parameters
78
Chapter 5: Parameters
79
Chapter 6: Parameters Setup
6.1.1 Elevator Rated Speed, Motor Rated Speed, Encoder pulses Setup
1. Elevator rated speed (F1-00) can be calculated through motor RPM, traction ratio, reduction ratio and traction
sheave diameter.
Elevator rated speed is used for calculating the ratio between motor rated speed and elevator speed,
modifying this parameter cannot change the actual running speed of elevator; if need to change elevator
running speed, please modify parameter F6-02 (Speed Zoom)
2. Motor rated speed (F1-01) is the speed of traction machine (RPM) under elevator rated speed.
3. Encoder Pulse (F1-02) is the pulse number of encoder for hoistway counting at elevator running.
4 .Motor rated speed and elevator rated speed much follow the condition below:
For example: Motor rated speed is1370 rev/min., traction sheave diameter 590mm, speed reduction ratio: 2/53,
traction ratio 1/1, then:
After setting elevator rated speed, motor rated speed, encoder pulse number, system record the relationships
between traction ratio, speed reduction ratio, traction sheave diameter and relationships between shaft counting
pulse and running distance. If the setting is incorrect, the following problems may happen:
1) The elevator running speed on digital operator or software is different with the elevator actual running speed.
For example, if encoder pulse or motor rated speed is set to a smaller value, speed indicated on the display will be
higher than actual speed, after hoistway learning, floor height learned by the system will be larger than actual
height.
2) As the floor height learned by the system is higher, the elevator deceleration curve will be steeper than the
setting. This could result elevator cannot leveling sometimes (running out of leveling zone with sudden brake).
80
Chapter 6: Parameters Setup
If bottom/top terminal (X8/X7) is valid, elevator slow down to 1/2 inspection speed to prevent exceeding the limit.
When up/down jogging is cancelled, speed given will be instantly 0 without deceleration curves.
1. Due to fault or other reasons, elevator stops outside leveling zone, after elevator restores, it runs in rescue speed to
the nearest floor and open door to release passengers;
2. When there is a hoistway counting error (ER14, Er18), elevator will run at rescue speed to the bottom floor for
recalibration; After elevator reaches the bottom terminal, elevator will run at 1/2 of rescue speed to the bottom
leveling position.
Elevator can generate several optimal running curves based on rated speed setting to suit for different speed/distance
running. But note lowest running speed curve is limited by F1-06.
...
Acceleration, deceleration for normal running curve and Acce/Decefor S curve are set by the following parameters:
81
Chapter 6: Parameters Setup
² Elevator running comfort level can be set through the above 6 parameters. (Comfort level is also
related to the drive control parameters.)The relationship between b1, b2, P1, P2, P3, P4 and running curve are
shown in Figure 6.2.
² Increase parameters value, the corresponded curve will be steeper. While decreasing value will smooth
the corresponded curve. Adjusting the above six parameters properly can reach good comfort level at elevator
running, and meet the related standard.
The timing diagram for normal running is shown below in Figure 6.3.
If smooth start running speed (F1-04) is set to “0”, smooth start running function will be disabled; smooth start time
(F2-13) will be disabled too.
82
Chapter 6: Parameters Setup
Speed
(F1-06~F1-00)
Running Contactor(Y9)
Inner Running
Running Speed
Zero Speed
Arrival at speed
deceleration point for
t0 t1 t2 t3 destination floor t6 t7 t8 t9 t10
t4 t5
Detail explanation of timing diagram for elevator normal running is explained below in Chart 6.1
83
Chapter 6: Parameters Setup
Timing diagram for elevator inspection running can be seen below in Figure 6.4.
Inspection Speed
(F1-03)
Running Contactor(Y9)
Inner Running
Running Speed
t0 t1 t2 t3 t4 t5 ta t8 t9 t10
84
Chapter 6: Parameters Setup
Definitions and instructions for timing diagram above are shown below in Chart 6.2.
Leveling Speed
(F1-05)
Threshold of Zero
Speed(F1-16)
Running Contactor(Y9)
Inner Running
Running Speed
Zero Speed
FIGURE 6.5 TIMING DIAGRAMS FOR RESCUE RUNNING (SAME DEFINITION & SETTING WITH NORMAL RUNNING)
85
Chapter 6: Parameters Setup
FIGURE 6.6 TIMING DIAGRAMS FOR RECALIBRATION RUNNING (SAME DEFINITION & SETTING WITH NORMAL RUNNING)
86
Chapter 6: Parameters Setup
T0: The actual door-drive running time for door to open or close completely;
T1: Door open or close time (F2-08).
T1 should be 1s more than T0 to ensure the door normal open/close action, otherwise:
1. After system output door close signal, but door dose not close completely after T1 door close time (F2-08),
elevator will open the door again, and door cannot be closed.
2. After system output door open signal, but door does not open completely after T1door open time (F2-08),
elevator stops the door open action, and door cannot reach the self-lock position.
Door close limit should be fixed in the position where it is only valid after door is completely closed, otherwise:
1. Door cannot close in inspection mode.
2. Door close limit valid, system stops output door close signal, door cannot close, system open the door again.
3. Door close limit is valid, system will open door after set time in F2-08. Door can still be closed under the holding
force of door drive, but system will show a door close error, and elevator can run normally.
If the door open/close limit switches cannot be valid after installation, elevator will control door open/close based on
time set in F2-08. If door open/close limit signals are normal; the control of door open and close will be based on door
open/close limit signals.
1. After landing, door open, if elevator has no landing/car call, waiting time is door open holding time (F2-05).
2. After landing, door open, if elevator has only landing call, waiting time is door open holding time (F2-05) minus 2s.
3. After landing, door open, if elevator has both landing/car calls, waiting time is twice of door open holding time
(F2-05) minus 2s.
4. If door open delay time (F1-30) is valid (Set as 1), and after door open, door open delay button is pushed, waiting
time will be door open delay time (F2-06). After the delay time or press door close button to close door in advance
and then reopen door again, door open delay function will be cancelled, unless push door open delay button again
after door is open.
87
Chapter 6: Parameters Setup
5. When elevator enables disabled function, if there are disabled landing/car calls on current floor, waiting time will
be door open delay time (F2-06).
In inspection mode, door open and close are both jog mode based on international standard.
1. In fire mode, if elevator is running, elevator will land to the nearest floor but does not open door, then
elevator return to fireman floor.
2. In fire mode, if elevator stops at other floor, door will not open after fully closed, then elevator return to
the fireman floor. If door is open, door will close at once, but before the door is completely closed, the door can
be opened again by pushing the door open button.
4. In fire mode, except on fireman floor, on all other floors door can only be controlled in jog mode.
Elevator in auto mode (no duplex/group control), if there are no landing/car calls in set time, elevator will return to
homing floor.
1. Electric lock input (X20) invalid, elevator in auto mode, it will return to parking floor (F0-03) after finishing all car
calls.
2. Electric lock input (X20) invalid, elevator in attendant/special use mode, as door cannot close automatically, after
finishing all car calls, door must be closed manually, elevator will then return to parking floor.
3. Electric lock input (X20) invalid, elevator in inspection mode, it will be locked at once.
Automatic Start/Stop:
88
Chapter 6: Parameters Setup
1. Electric lock input (X20) valid, set auto parking (F1-28) as 1, automatic start time (F2-14), automatic stop time
(F2-15) to correspond value to enable this function.
2. Electric lock input (X20) invalid, elevator will enter parking state; cannot set auto start/stop function.
3. In elevator auto stop time and elevator need to run temporarily, turn the electric lock to invalid and restore to
valid, elevator will run. After the running, operate the electric lock in same procedures, elevator will re-enter
lock mode, until reach auto-start time, then it starts running again.
Controller has three kinds of fireman operation mode; fireman mode (F1-23) can be set as “0, 1, and 2”:
0: Normal fireman mode: When fireman input is valid, elevator lands to the nearest floor but doesn’t open door, then
it returns to the fireman floor(F0-02), it opens door and stops, meanwhile it enters into the fireman mode, elevator can
run in fireman standard.
1: Fire emergency stop mode: When fireman input is valid, elevator lands to the nearest floor but doesn’t open door,
then it return to the fireman floor (F0-02), it opens door and stops. Meanwhile elevator stops running, until fireman
input is eliminated.
2: Fireman control mode: It includes two steps, step 1 is fire emergency return, and step 2 is fireman operation. Only
after elevator returns to the fireman floor could step 2 be operated.
1) Fireman input switch has two states (ON/OFF); it is connected to X12 on main control board. Fireman operation
switch has three states (ON/START/OFF), ON is connected to fireman input (by-pass input) on COP, START is
connected to the door close input in parallel (For fireman to close door, when fireman turns the key to the
START position, point ON is still valid, after releasing switch will automatically return to ON.)
Step 1: Fireman input X12 is valid, if elevator is running, it will cancel all car call and landing call and stop at the
nearest floor, but doesn’t open door and then return to the fireman floor; if elevator is under stop and door open
state, elevator will close door at once and return to the fireman floor. After elevator returns to the fireman floor,
it opens door and stop running.
Step 2: Elevator in fire mode, return to fireman floor then stop running; At this time fireman operation running
can be activated by fireman operator switch, switch to ON/STAR, elevator will run under fireman operation(Only
serve one car call, door open and close follow fireman operation function). After switch to ON/STAR and elevator
finished serving fireman operation, if elevator already leave the fireman floor, and switch is turned to OFF, at this
time elevator will keep running. Only when elevator returns to the fireman floor again then it will stop running.
2) After elevator enters fire mode, light curtain input will be invalid. Elevator will exit from fire mode only when
fireman input switch, fireman operation switch are both in OFF state.
89
Chapter 6: Parameters Setup
According to the rear door mode, HOP address setting and COP wiring are different too:
1) When rear door mode on controller is set as0, 1, 3, HOP address is same as usual;
2) When rear door mode on controller is set as2,4,5, HOP address is set as below:
a) 1~32is the absolute floor number at front door side:
1is the bottom floor, 2is second to bottom floor, maximum number is 32, total 32 floors.
b) 33~64is absolute floor number at rear door side:
33 is the bottom floor, 34 is second to bottom floor, maximum number is 64, total 32floors.
c) If there is only one door on some floors, then the HOP address for the other door is empty.
Example 1: Elevator has one basement floor with both front and rear doors, on this floor HOP address is 1 for
front door and 33 for rear door.
Example 2: Elevator has one basement floor with only front door, and one ground floor with both front and rear
doors, on the basement floor HOP address is 1 for front door and empty for rear door. On the ground floor HOP
address is 2 for front door and 34 for rear door.
2. C.O.P button wiring:
1) When rear door mode on controller is set as 0, 1: 1~N floor buttons are connected to the COP terminal as
usual.
2) When rear door mode on controller is set as 2, 4, 5: set total floor no. N, then the 1~N car call ports
correspond to 1~N floor car call buttons at front door, 1 is the bottom floor, N is the top floor. N+1~2N floor car
call ports correspond to the 1~N floor car call buttons at rear door, N+1 is the bottom floor, 2N is the top floor.
90
Chapter 6: Parameters Setup
For example: Elevator has 6 floors (1~6), no basement, 3rd floor has double entrance; other floors have only front
entrance. Then car call buttons 1~6 at front door should be connected to 1~6 car call ports, car call button 3 at
rear door should be connected to N+3=6+3=9 car call port.
When rear door mode is 1, 2, 3, 4, 5,need to install two sets of door open/close buttons, this is to open
front and rear door separately in inspection running.
If rear door mode is 1, and there is one set of door open/close buttons, please set parameter FU18 to “ON”.
In other mode, if there is only one set of door open and close buttons, in inspection running, only front door
can be opened by door open button, rear door cannot be opened by the button.
Input type on main control board (F3-00) can be changed based on actual ON/OFF state. When switch is at valid
position/state and switch is closed, then its input type is ON. When switch is at valid position/state and switch is open,
then its input type is OFF. Input type setup on main control board can be seen below in Chart 6.3
input
SKDY auxiliary contactor
X5 J1-3 F3-00-05 ON OPEN ON
input
KBC brake contactor
X6 J1-2 F3-00-06 ON OPEN ON
feedback
X7 J1-1 Door open limit 2 input F3-00-07 OFF CLOSE ON
X8 J8-8 Door close limit 2 input F3-00-08 OFF CLOSE ON
X9 J8-7 Safe plates 2 input F3-00-09 OFF CLOSE OFF
X10 J8-6 SJT Emergency stop input F3-00-10 ON OPEN OFF
X11 J8-5 SMB door inter-lock input F3-00-11 ON OPEN OFF
X12 J8-4 spare F3-00-12 ON OPEN OFF
X13 J8-3 SXF fire input F3-00-13 ON OPEN OFF
91
Chapter 6: Parameters Setup
If the top/bottom limit circuit is closed in normal state, default input level shows “ON”.
If the top/bottom limit circuit is open in normal state, default input level shows “OFF”.
Non-stop floors in the system can be set through F4-00 and F4-01. For the floors elevator can land, set “ON”, for the
floors elevator cannot land, set “OFF”. After setting F4-00, F4-01, elevator cannot land to the set floors in any case.
92
Chapter 6: Parameters Setup
Based on this function (refer to the function selection Chart), non-stop on certain floor in set time function is available
too. Between the non-stop beginning time (F2-14/15) and ending time (F2-16/17), if elevator cannot land on some
floors, please set the non-stop floors by setting F4-02 and F4-03 “OFF”.
When using SJT-300 weighing device, load detection is available through communication with main control board on
CAN BUS. See below for setup procedures:
a) Adjust the simulated load compensation gain in inverter until elevator runs down from top floor with no
sliding;
b) Move the empty elevator to bottom floor, increase load compensation adjustment parameter until elevator
runs up from bottom floor with no sliding;
Controller has internal integrated duplex module, two elevators are connected through CAN1 in parallel, corresponded
parameters need to be set to achieve duplex control.
Setup procedures:
After setup please save the parameters, reset the power and updating the communication address.
93
Chapter 6: Parameters Setup
Main control board and group control board are connected through CAN1 port. (See group control board manual),
corresponded parameters need to be set to achieve group control.
Setup procedures:
After elevator landing, if elevator speed curve has no problem (i.e. there is no sudden stop and overrun leveling zone at
elevator landing) and elevator runs outside leveling zone (it stops higher than leveling zone in up-running, lower than
leveling zone in down-running), need to decrease leveling adjustment parameter F1-17 (default 50); if elevator cannot
reach leveling position(it stops lower in up running, higher in down running), increase leveling adjustment parameter
F1-17, general range for adjustment is 40-60, if the adjustment is big, please adjust driving parameter PI, or speed
curve shape (F1-10~F1-15).
In parameter F0-05~F0-69, we can set third bit display, first two bit can be figure, characters or “-“ , third bit can only
be the following capital characters: ABCDEFGHIJKLMNO. If only need two bits, set the first two bits only and third big is
empty.(Third bit indication should be supported by the HOP board, otherwise it cannot display normally.)
To meet certain special requirements from customers, this control system has included some customized functions
(F4-06 & F4-07).
94
Chapter 6: Parameters Setup
Number Instruction
After elevator stops, based on current floor, if there is no landing/car call ahead of the current floor
F4-06-00
in previous running direction, system will cancel all the car calls.
F4-06-01 Only for internal test.
ON: In Fire mode when elevator leaves fire floor then disable fire linkage output, when elevator
F4-06-02
return to fire floor then restore fire linkage output.
F4-06-03 ON: Disable ER29 fault.
ON: Two elevators in duplex control and not in service, when the same floor has both up/down
F4-06-04
landing call registered, both elevator serve this call. OFF: Only one elevator serve this call.
ON: Elevator disable cabin overload signal, this is used in elevator 125% load test. OFF: Overload
F4-06-05
signal enable.
ON: Y16 means inspection output, when floor display is in 7-segment code mode (First 7-segment
F4-06-06
display must be not occupied).
F4-06-07 ON: Direction arrow flashes when the car is running
ON: When set floor display to 7-segment code mode, the floor display remains.
F4-06-08
OFF: When set floor display to 7-segment code mode, the floor display doesn’t remain.
ON: Elevator can cancel registered car call at running. If all call canceled, elevator stops in nearby
F4-06-09
floor.
F4-06-10 Only for internal test. Remain the default OFF state. ON: New curve is applied compulsively.
95
Chapter 6: Parameters Setup
F4-06-13 Spare
F4-06-15 ON: Disable all display relays when elevator is in electric lock mode or emergency mode.
ON: When door lock is closed, door close limit must be valid too.
F4-06-16
OFF: Door lock state is not related to door close limit.
ON: When elevator stops in inspection mode, inverter direction given and brake are released together.
F4-06-17 OFF: When elevator stops in inspection mode, inverter direction given drop is 0.5s later than brake
close.
ON: In rear door mode, elevator only installs one set of door open& close buttons.
F4-06-18
OFF: In rear door mode, elevator installs two sets of door open & close buttons.
ON: Door close 1 and door close 2 will share the Y3 Output. Y5 is economy resistance.
F4-06-19
OFF: Y3 is door close 1, and Y5 is door close 2.
ON: 3-phase 380V 50Hz power supply (with back-up generator)
F4-06-20
OFF: Battery power supply (disable BUS under voltage fault)
ON: In inspection mode, door cannot open outside leveling zone.
F4-06-21
OFF: In inspection mode, door can open at any position.
F4-06-22 ON: Simplex collective OFF: Full collective Default:OFF
ON: Use SJT-300 weighing device through CAN BUS
F4-06-23
OFF: Use SJT-150 weighing device through RS485
F4-06-24 Spare
ON: When the elevator cannot open door in current floor (OP fault in controller), it will automatically go
F4-06-25
to the next floor and open door.
ON: passengers can input more than three car calls in light-load mode ;
F4-06-26
OFF: passengers cannot input more than three car calls in light-load mode ;
F4-06-27 ON: Redirection when zero speed has been detected. OFF: Redirection after brake close at zero speed.
ON: Use light curtains/safety plates separately, the attendant up/down input terminal is used as
F4-06-28 front/rear door safety plates input.
OFF: Light curtains and safety plates have serial connection (Blue-light default Setting)
F4-06-29 Spare
ON: Integrated controller LED has reverse display. This is used for Blue-light G-series cabinet in
F4-06-30 room-less elevator (where control board is placed reversely)
OFF: Integrated controller LED has normal display. (Blue-light default Settings)
96
Chapter 6: Parameters Setup
Number Instruction
ON: When ARD function is active, system will open brake for 1s (when sliding speed >0.1m/s, brake will
F4-07-00 close again), it will then find the heavy load direction based on the sliding direction, use battery to land
the cabin on heavy load direction and reduce leveling energy cost.
ON: Enable elevator data recorder. Together with PC debugging software, after-sales/ service team can
F4-07-01
provide fault diagnosis。
F4-07-02 ON: Re-levelling enable; OFF:Re-levelling disable.
F4-07-03 ON: Door open in advance enable; OFF: Door open in advance disable.
F4-07-04 ON: Open door standby at all floors.
F4-07-05 Spare(gnxz38)
F4-07-06 Spare(gnxz39)
ON: If car speed inside leveling zone is still faster than rescue speed, then the car will be forced to stop
F4-07-07
in leveling zone.
F4-07-08 Spare(gnxz41)
F4-07-09 Spare(gnxz42)
F4-07-10 Spare
F4-07-11 Spare
ON: Enable clearing car calls when no light curtain actions within three car-call stops in auto running
F4-07-12
mode to anti trouble make.
ON: Enable auto-restricting-door function to prevent door lock loop disconnect caused by no
F4-07-13
self-locking power.
Default: OFF. Improve car stop.
F4-07-14
ON: Give up the time-dependent decreasing speed curve after speed change in leveling zone.
F4-07-15 For internal test.(gnxz48)
F4-07-16 For internal test.(gnxz49)
ON: In UPS running mode, elevator will arrive in leveling zone, open the door, and close the Y23
F4-07-17
contactor in 30s, then cut-off the UPS circuit to avoid UPS battery pack deep discharge.(gnxz50)
F4-07-18 ON: The car waits at homing floor with door open.
ON: Enable elevator run to bottom level in UPS running mode.(gnxz52)*: When applying this function,
F4-07-19
F4-07-00 and F4-07-25 will be no effect.
ON:Enable TIM Stop Floor function.
Stop floor time set1 Start time:F2-18 & 19; End time:F2-20 & 21
TIM stop floor time set1 corresponds Set Stop Floor parameter is:F4-00 Set Stop Floor1, F4-01 Set Stop
Floor2.
F4-07-20
Stop floor time set2 Start time: F2-14&15; End time: F2-16 & 17(multiplexing start time/stop time
setting).
TIM stop floor time set2 corresponds Set Stop Floor parameter is:F4-02 Set Stop Floor1, F4-03 Set
Stop Floor2.
97
Chapter 6: Parameters Setup
Number Instruction
ON: There is only one door zone signal, the elevator will still level while it turns from inspection to auto
F4-07-21 or from error to normal, or runs in ARD mode. It will avoid that the car door vane cannot drive the hall
door when it is too short.
ON: Hall door circuit is separate from car door circuit. X36: hall door detect; X35: car door detect (non
F4-07-22
-high voltage circuit).
F4-07-23 Spare
F4-07-24 ON: Elevator return to homing floor to proofreading level number when power on for the first time.
F4-07-25 Spare
F4-07-26 Spare
F4-07-27 Spare
F4-07-28 Spare
ON: Leveling adjustment can be set separately. The default Leveling adjustment of each floor (1~64
F4-07-29
floor) in setting parameters is 50mm.
F4-07-30 Spare
F4-07-31 Spare
Note:
Please notice the function number with “*” and distinguish software version.
Software version(U5-00) is 1000_55XX;
F5-00: motor type. 0: synchronous outer rotor machine; 1: asynchronous machine, 2: synchronous inner rotor machine.
Please make sure the machine type is set correctly, as system will perform motor auto-tuning and vector control based
on motor type.
Also, please input following motor parameters based on the machine nameplate or user manual to ensure the accuracy
of system generated motor digital model and vector control coupling.
98
Chapter 6: Parameters Setup
9. F5-09: No-load current (this parameter is only valid for asynchronous machine, it can be acquired from motor
self-learning)
10. F5-10: Motor rated Slip (this parameter is only valid for asynchronous machine)
Beside above, when some parameters are not accurate, please perform motor parameter auto-tuning.
For the drive versions above 0007, parameter auto-tuning is not necessary.
Elevator rated speed (F1-00) and motor rated speed (RPM) (F1-01) are used to calculate the ratio between elevator
rated running speed and motor RPM. Also, with encoder pulse number per cycle (F1-03), we can get the relationship
between each pulse and traveling distance in hoistway, and this achieves the distance detection of elevator running.
Therefore changing F1-00, F1-01 will only change their ratio, but not elevator actual running speed.
When F1-03 for hoistway counting is from inner pulse source, pulse number in one cycle (F1-03) = pulse number of
motor encoder (F8-00) / PG frequency division ratio (F8-01). Rated speed of traction machine (F1-01) = Motor rated
speed (F5-04).
If F1-03 for hoistway counting is from outer pulse source (i.e. speed limiter encoder, must adopt special PG card), F1-03
should be set as pulse number in one cycle from outer pulse source, Rated speed of traction machine (F1-01) = Outer
pulse source speed (i.e. speed limiter speed).
If need to reduce the elevator actual speed, please change the value of speed ratio (F6-02), when F6-02=100%, elevator
runs in rated speed; reduce F6-02 elevator actual speed will decrease in corresponded ratio.
For speed control under vector control, there are two ways, F7-00: when multi-section PI enable is set 0, PI does not
change with speed given change. Instead, it is a fixed value for the whole elevator speed range, which simplifies setup
procedures.
This is the most used method, the flow diagram can be seen below in Figure 6.11.
99
Chapter 6: Parameters Setup
F7-05, F7-06: Group 1 PI; it is generally adopted in low speed period at motor start.
F7-07, F7-08: Group 2 PI; it is generally adopted in middle speed section at acceleration period or steady-speed section
at low speed period.
F7-11, F7-12: Group 3 PI; it is generally adopted in deceleration period.
Switching frequency for the above groups of PI parameter are set in F7-01~F7-04: frequency setting of PI effective
range.
When motor starts from zero speed or in acceleration period, if the current frequency given is smaller than F7-01,
system will adopt F7-05, F7-06 of group 1 PI to adjust the speed. To enable elevator quick stable at zero speed when
brake release and follow the speed curve quickly in initial acceleration, F7-05 and F7-06 can be set slight bigger.
After motor starts, when speed (acceleration) is larger than the set frequency in F7-01 and smaller than F7-02,
system will adopts F7-07, F7-08 of group 2 PI to adjust the speed. When motor running speed is larger than the set
frequency in F7-02, system will adopts F6-04 and F6-05.
100
Chapter 6: Parameters Setup
When motor speed is smaller than the set frequency in F7-03 (deceleration), system will adopts F7-11, F7-12 of
group 3 PI to adjust the speed. This group of PI parameters is used for adjustment in deceleration to stop period. If
F7-03 is 0, system will adopt the last group of PI parameters before deceleration.
For different groups of PI effective range please see Figure 6.13 below.
101
Chapter 6: Parameters Setup
6. In synchronous machine control, as there is no compensation chain for low building, Blue -light weighing device
can only measure the load in cabin and cannot detect the rope weight variation on different floor. In this case
load compensation adjustment (F1-18) need to be used.
Adjustment Procedures:
Set F8-00 based on encoder pulse number. Encoder pulse usages can be seen below in Figure 6.15.
102
Chapter 6: Parameters Setup
When using BL6 series integrated controller with Sine/Cosine PG card, it is possible to achieve comfort start without
load compensation by proper setup in FA group parameters. (It means elevator can reach the same effect of load
compensation even without weighing device.)
1) Principles: As can be seen in Figure 6.16 below, when brake open, based on the position feedback from
Sine/Cosine PG card, system can calculates the necessary torque required for motor to remain the steady
position under current load, and it gives corresponded torque at once to minimize the traction sheave
movement and to achieve comfortable start.
103
Chapter 6: Parameters Setup
3) Adjustment method: Main parameters used are FA-08, FA-09 and FA-11.
FA-09
This parameter is the working time for starting without load compensation after brake opens, it must be set according
to the actual brake opening time, if the time is too short, elevator will slip as this action will be over before brake fully
opened; Also the value of F2-00 (brake opening time before running) must be 100ms longer than the value of FA-09, so
that this action can finish before speed curve start.
Two gain parameters for the starting without load compensation action, these two parameters can be adjusted
according to the elevator slipping condition and comfort level, if the slipping is too much please increase the value of
FA-08; if the traction machine gets vibration, please reduce this value; during the period of torque keeping, if there is
slight slipping or small back-and-forth movement on traction sheave, please increase the value of FA-11, if there is
vibration, please reduce this value.
1. During commissioning, besides the mentioned 3 parameters, other FA group parameters can be kept
with factory setting.
2. For different versions of program,the name of FA group parameters might be different, but their
positions remain the same. As a result, only adjust FA-08, FA-09, FA-11 despite the operator version.
3. The setting value of above parameters is just for reference, as the PG card is not same in different job
side; please adjust above parameters based on site condition.
4. F9-00 is the pre-set torque when the starting without load compensation function is enabled. Generally
there is no need to change its value, please keep it with factory setting (0)
Controller support remote monitor function. Connect controller with assorted WCR remote monitor
module, it will use same CAN Bus with COP/HOP communication. Set relative parameters, then remote
monitor can be achieved. Parameter setting is as follow,
1. Set Remote monitor enable, F1-27=1;
2. Save parameter.
104
Chapter 7: Commissioning
Chapter 7: Commissioning
1. Thanks for purchasing our product, please read this manual and related instruction thoroughly before
processing with installation, connection (wiring), operation, maintenance and inspection. To avoid any
damage/loss of the products or accident to people, please make sure you have sound knowledge of the device
and familiar with all safety information/precautions before processing to operate the control system.
2. Before commissioning and running the product, please read the manual carefully and refer to this manual
during commissioning and running.
3. Make sure that all the mechanical devices are installed properly beforehand, especially the devices in hoistway
(the devices that should be set in the machine room depends on the situation of the machine room).
4. Make sure that the installation and commissioning for the devices, which should be finished before
commissioning of the control system, have been completed.
5. Before commissioning, it is necessary to get signature confirmation from a person responsible for mechanical
installation and commissioning.
6. Make sure that all the mechanical devices and other devices which are related to the system commissioning
are installed and tested properly.
7. Make sure that there are no unsafe factors which could cause injuries and damages to personnel and devices.
10. When doing commissioning for both electric and mechanical parts, technicians for both parts should
collaborate.
11. If this manual could not meet your requirement, please contact our company at once to acquire help and to
avoid accident and loss.
12. Before system commissioning, make sure all the conditions are sufficiently prepared.
After electric system is installed, please check the electric system carefully and pay attention to the following items:
1. Compare with the manual and electric diagram, check if the connections are all correct.
105
Chapter 7: Commissioning
2. Check if there is interference between high voltage part and low voltage part. Use a multi-meter to measure the
resistor in different circuit, resistor to earth must be infinity big.
3. Please check if wiring from power supply to the control cabinet and traction machine is correct, this is to avoid
damaging the controller after powering on.
4. Check wiring between encoder and controller, coaxial degree of encoder and traction machine shaft, wiring
between encoder and traction machine.
1) Check if the enclosure of the controller and motor, cabin, landing door are reliably earthed to ensure the
safety to personnel.
2) Make sure correct wiring of the terminal block J1 on control board to avoid any damage to the main control
board.
Controller has special digital operator, it should be connected to the socket J232 on main control
board by a special cable before commissioning. USB serial communication cable is also available;
connect it to the port USB0 on main control board to computer, then do commissioning with
special software. (please refer to commissioning software manual)
2. Confirm mode switch on the controller is at “inspection”, emergency stop button is pressed.
3. Confirm inspection switches on car top and cabin are both in “normal” positions.
5. Check voltage on the main power supply::3 phase voltage is 380±15%VAC, phase-phase voltage difference is
smaller than 15VAC, Phase-N voltage is 220±7%VAC.
6. Confirm the wire specification and main switch capacity match the design requirement.
106
Chapter 7: Commissioning
2. Inspect the terminal voltage on transformer TC1, the values should be in the range of ±7% of the indicated value,
if voltage exceeds this range, find out the problem and correct it.
c. (Note: Connect digital operator before power on) After power on, first see if the main menu display is
correct on LCD indicator. For example: elevator state, fault state, door lock state, current floor, running
speed and else. In this way we can tell if the controller is working properly and whether 24V power supply is
normal. Interface on digital operator LCD screen can be seen below in Figure 7.1.
Terminal L~ N 24V~ G
Voltage 220±7%VAC 24.0±0.3VDC
3) Check electric lock, set the elevator auto-start/off time to “0’, set electric lock switch to “ON”, LCD screen will
then display elevator state as “INSP”, if set electric lock switch to “OFF”, LCD screen will show “STOP”.
107
Chapter 7: Commissioning
It is very important to set Parameters based on actual site condition, as this is the foundation for controller or control
system to maximize its performance. For parameter setups please refer to chapter 4-6. When setting parameters,
please pay attention to the following points:
1. Set the motor basic parameters from motor nameplate namely motor parameter 1 content (F5 group). For
example, motor type, pole numbers, rated frequency, rated power, rated RPM, rated current, Back-EMF (only for
synchronous machine), no-load current (only for asynchronous machine), phase inductance, phase resistance and
else. Amount which phase inductance, phase resistance and other parameters that are unknown can be acquired
from motor -tuning; if system moment of inertia is unknown, leave it as default.
2. Set encoder parameter correctly (F8 group), for example encoder pulse, PG frequency division coefficient.
3. Set elevator running parameters correctly, such as motor rated RPM, encoder pulse (after frequency division.)
4. Set input type correctly, they should match the actual contactors, relays and hoistway contacts and switches.
Controller has motor parameter tuning function. Base on the input basic motor parameters, system automatically
performs control, detecting, calculation, and recognize the unknown motor parameters required. For example, phase
inductance, phase resistance, no-load current (only for asynchronous machine) and else.
Unless all the necessary motor parameters are known (F5 group), for example phase inductance (F5-06), phase
resistance (F5-07) and all other parameters, please set the parameters directly and there is no need to run the motor
parameter tuning. Otherwise motor parameter tuning is necessary.
Note: For BL6-B series elevator integrated controller, parameter tuning is not nesseray.
PG Type (F8-02) should be set correctly, and AutoTuneModeSel (FC-13/FX-20) should be set to 0.
1. Make motor (traction machine) with no load (do not attach the steel rope);
2. Short circuit running contactor output Y9 (J5-10) and COM3 (J5-6), make running contactor closed;
3. Short circuit brake output Y7(J5-8) and COM3 (J5-6), close braking contactor and release the brake;
With the digital operator, perform the motor tuning command according to Figure 7.2.
108
Chapter 7: Commissioning
After press the “Enter” button, motor parameters tuning start. Motor will remain static after a short vibration, system
continues to supply current and motor generates current noise. The whole process takes about 5 seconds.
If tuning success, return to parameter setting menu, check motor phase inductance (F5-06), and motor phase
resistance (F5-07). They should all be adjusted to the correct value. Generally, one successful tuning is enough.
However, if want to acquire more accurate results, one can record the results of this tuning, then repeat the process,
and take the average value from tuning results.
If self-learning fails, operator will indicate the error code, please refer to the troubleshooting chart in chapter 8, find
out the reason and solve the problems, then start motor parameter tuning again.
1. Close brake.
2. Select tuning method parameter FC-13 (or FX-20) to “1” on digital operator.
3. Short circuit running contactor output Y9 (J5-10) and COM3 (J5-6) to make it close; (If the system has a separate
star short circuited contactor, close it as well).
If tuning success, return to parameter setting menu, check motor phase inductance (F5-06), and motor phase
resistance (F5-07). They should all be adjusted to the correct value. Generally, one successful tuning is enough.
However, if want to acquire more accurate results, one can record the results of this tuning, then repeat the process,
and take the average value from tuning results.
If tuning fails, operator will indicate the error code, please refer to the troubleshooting chart in chapter 8, find out the
reason and solve the problems, then start motor parameter tuning again.
For synchronous motor, it is necessary to perform motor initial angle tuning. Otherwise the machine cannot run
normally, or even sever slip. Therefore, tuning initial angle is very important for synchronous machine. Before proceed
to load run, synchronous machine must first perform initial angle tuning successful and no load running successful. For
the tuning procedures, please refer to Figure 7.3.
109
Chapter 7: Commissioning
1. Synchronous motor(traction machine) must not have any load (don’t hang on steel ropes);
2. Short circuit running contactor output Y 9 (J5-10) and COM3 (J5-6) to make it close;
3. Short circuit brake contactor output Y7 (J5-8) and COM3 (J5-6) to make it close and open brake;
With digital operator, AutoTuneModeSel (FC-13/FX-20) should be set to 0(0: Rotation tuning; 1: Static tuning).With the
motor parameters (F5) and encoder parameters (F8) are set correctly, perform the initial angle rotation tuning as
follow figure.
After pressing “Enter”, tuning starts. At first, Motor will immediately rotate to a certain position, then rotate forward at
a certain speed (facing to traction sheave, anticlockwise rotation is forward direction), the speed is depended on motor
pole number and initial position. Motor will stop after at most 2 turns, and will be rotated again to a certain position to
stop for 2 seconds, then tuning stops and the operator display “success”. The whole tuning procedure lasts around 30s.
After tuning successful, perform a trial run according to chapter 4 “4.4 Parameter commissioning in Digital Operator”.
Make traction machine accelerate forward from zero speed to rated speed, run it in constant speed for a while and
observe the running condition; make motor run in opposite direction in same way.
After trial run with digital operator, please remove the short circuit on “running contactor output” and “brake control
output”. Press jog up button on control cabinet to perform inspection running, observe motor running condition; Then
press jog down button on control cabinet to perform inspection running, observe motor running condition.
When jog up (down), if the real running direction of cabin is down (up), please set F6-03 to correct it. 0: anticlockwise
rotation is down, 1: anticlockwise rotation is up, set based on actual site condition.
After the above trial running is finished, attach the steel rope and run motor with load.
110
Chapter 7: Commissioning
1. Wiring in control cabinet is completely correct, and system under inspection state;
2. Running parameter (F1), motor parameter (F5) and encoder parameter (F8) are set correctly ;
3. All mechanical faults in hoistway have been eliminated; cabin and counterweight locate at center of the
hoistway.
SetAutoTuneModeSel FC-13 (FX-20) to “1” on digital operator (0: rotation tuning, 1: static tuning), perform motor initial
angle tuning according to the following procedures shown in Figure 7.4.
After pressing “Enter”, tuning starts. When digital operator indicates “Waiting” , press jog up or down button ,Running
contactor closes, motor will vibrate a little and give a noise, the duration depends on motor rated power and rated
current, but no longer than 5s, this is static tuning period.(Make sure jog up or down button is pressed constantly, DO
NOT release the button during this period.)Motor will then start and run in inspection speed, jog up or down, until
digital operator indicates success, this is test running period. Finally, release the jog up or down button and finish the
tuning procedure.
3. To ensure safety, during tuning process, people is strictly forbidden to stay in car or hoistway;
4. Press up or down jogging button can base on the current cabin position;
3. The whole tuning procedures can be divided into two steps: static tuning and motor trial running, make sure
there is no interruption between two steps. If no fault happens, before digital operator indicates success, press
the jog up or down button constantly;
4. To achieve optimal control effect, it is recommended to repeat above tuning procedures 5 times, if the
deflection of the results is small, take the average value.
If fault occurs in tuning, please refer to chapter 8 troubleshooting chart, locate the fault and solve it accordingly, then
repeat tuning procedures.
111
Chapter 7: Commissioning
1) Inspection switch in control cabinet is at “Inspection” position, inspection switch on car top and cabin should
be in “Normal” position.
2) Safety circuit and door interlock circuit work normal, DO NOT short door interlock circuit.
3) After power on, emergency stop contactor, door interlock contactor, and power contactor in control cabinet
are closed, check if the controller works normal and parameter setting is correct, in LCD indicator, elevator
state is “INSP”.
4) Connect the brake wiring to control cabinet properly.
2. Inspection running in machine room
When the inspection running requirements in machine room are satisfied, press the Jog Up/Down
button on the control cabinet, elevator will run up/down in set inspection speed.
Note: For integrated controller with ARD function, the inspection switch is called "Emergency Run Mode Switch"
Hoistway parameter self-learning means elevator runs at a self-learning speed and measures every floor height and
record the position of every switch in the hoistway. As the floor position is the foundation for elevator normal running,
braking and floor display. Therefore, before normal running, hoistway parameter self-learning must be performed.
Before hoistway parameter self-learning, inspection running in full trip must be performed too; elevator must be able
to run normally from bottom limit to top limit.
2. Make sure all the switches in hoistway are installed and connected correctly, traveling cable and hoistway cable
are connected correctly, and finish setting the HOP/display address;
3. Elevator in inspection mode, jog elevator down to the bottom limit (bottom limit is valid);
4. Enter elevator hoistway self-learning menu through digital operator, follow the learning procedures shown below
in Figure 7.5.
112
Chapter 7: Commissioning
5. The results of learning can be seen from hoistway position parameter U00-U69 under monitor menu with unit of
meter, please check the switches position after hoistway learning.
6. In self-learning process, if control system detects any abnormal phenomenon, self-learning will be terminated and
give fault code, please refer to troubleshooting chart in chapter 8, find out the reason and solve it accordingly,
then start hoistway parameter self-learning again.
When self-learning process stops, only when LCD indicator shows “success” on digital operator,
self-learning is completed successfully.
After hoistway parameter self-learning is completed successfully, normal speed running can be carried out. Procedure
as follows:
If comfort level and leveling accuracy of elevator running are not perfect, please follow procedures blow.First, check
the mechanical system condition (Such as clearance of guide shoes, lubricating, steel rope, position of the rope hitch
plate and else.)which might influence the comfort of elevator running. After checking all the mechanical parts, then do
adjustment in controller.
As the controller control the motor running according to the given starting/braking speed curve, therefore shape of the
given speed curve, motor feedback speed to controller and the timing logic of controller signals directly influence the
comfort level of elevator running.
113
Chapter 7: Commissioning
Speed
P2 P3
b1 b2
P1 P4
Time
Direction
Brake Release
Speed Given t t
1 k tq ts td
t2
tf
1) P1: Acceleration increase in starting section, it means the rate of elevator acceleration change. Smaller value
means the slower starting section, the smoother running period and the lower the efficiency. On the other hand,
faster at acceleration starting section means higher efficiency for elevator running.
2) b1: Acceleration in starting section, it means the rate of elevator speed change. Smaller value means the slower
starting section, the smoother running period and the lower efficiency. On the other hand, faster at acceleration
section means higher efficiency for elevator running.
3) P2: Acceleration decrease at end of starting section, it means the rate of elevator acceleration change. Smaller
value means slower at end of starting section, the smoother running period and the lower efficiency. On the other
hand, faster at acceleration ending section means higher efficiency for elevator running.
1) P3: Deceleration increase at start of braking section, it means the rate of deceleration change, smaller value
means slower at start of braking section is, smoother running period and lower efficiency. On the other hand,
faster at brake starting section means higher efficiency for elevator running.
2) b2: Deceleration in braking section, it means the rate of elevator speed change. Smaller value means the slower
braking section, the smoother running period and the lower efficiency. On the other hand, faster at braking
section means higher efficiency for elevator running.
114
Chapter 7: Commissioning
3) P4: Deceleration decrease at end of braking section, it means the rate of deceleration change. Smaller value
means slower at end of braking section, smoother running period and the lower efficiency. On the other hand,
faster at brake ending section means higher efficiency for elevator running.
Commissioning at jobsite need to first guarantee the elevator running efficiency, then adjust the above 6
parameters to achieve optimal elevator running curve.
To achieve the maximum level of comfort, integrated controller must control the motor and make feedback speed
strictly following the change of running curve.
As the controller establishes the mathematic motor module based on the motor parameters input by customers, and
controller perform decoupling control by this module on motor starting/braking. Therefore, customer should input the
motor parameters correctly. (When motor parameter is not precise or not confirmed, we suggest customer perform
motor parameter tuning.)
Proportional gain on the speed circle F6-04 and integral gain F6-05 or F7-05~F7-12 for PI section parameters also
influence the motor tracking ability to speed curve. Generally, increasing the proportion gain will improve the reaction
of the system and promote the tracking speed. However, if proportion gain is set too big, it will cause system vibration
with high frequency and large motor noise. Increasing integral gain can improve the system anti-interference/tracking
ability and improve the leveling precision, but set integral gain too big will make system vibration, speed over
adjustment and wave vibration.
Generally, it is recommended to first adjust the proportion gain, increase it right before system vibration threshold.
Then adjust the integral gain, enable system with quick reaction and no over adjustment.
If system performance is not perfect at start or stop period (low speed period), try to control in multi-section PI, detail
can be seen in 6.19.2 in Chapter 6.
The control timing of this system can be seen Section 6.3 in Chapter 6, customer can adjust timing parameters and zero
speed setting.
1. Timing adjustment: Refer to section 6.3 Timing diagram under different state in Chapter 6.
2. Zero speed setting: This parameter is the threshold of zero speed. Main control board determines braking time by
this value. If this value is too big, elevator will stop with speed, if too small it will delay door open after elevator
stop.
Leveling precision adjustment should be performed after comfort level adjustment is satisfied.
115
Chapter 7: Commissioning
1. Make sure the leveling switches and leveling inductor plates are installed in the right position.
4. The position of leveling inductor plates should be precise. When elevator Is at the leveling position, the center
of the plate and center of two inductors should match together (refer to appendix), otherwise elevator leveling
will have deflection, which means in up or down running, elevator stops higher or lower than leveling position.
5. If magnetic inductors are adopted, please make sure the inductor plates inserting to the inductor sufficiently,
otherwise it will influence the reaction time of inductor, in that way elevator will overruns the leveling position.
6. To ensure precise leveling, system require elevator to crawl for a certain distance before stop.
7. In practice, first make adjustment for a middle floor, until leveling is precise. Then, adjust the other floors on
the base of these parameters.
After adjusting curve selection, ratio and integral gain in the above context, please make sure every time elevator runs
up or down, when stop at middle floor, its leveling positions are the same (each deflection of stop position ≤±2~3mm).
If elevator still cannot achieve desired leveling condition with adjustment based on instructions in section 7.9.1 in
Chapter 7, further adjustments can be done by parameters. After elevator stops in normal running, if running speed
curve has no problem (for example, no sudden stop or overrun beyond leveling zone), if elevator overruns the leveling
position (it stops higher in up-running, lower in down-running), please decrease leveling adjustment parameter F1-17
(default: 50). If elevator cannot reach the leveling position(It stops lower in up running, higher in down running),
increase leveling adjustment parameter F1-17, generally the range of this parameter is 40~60, if the adjustment is too
big, please adjust driving parameter PI, or the shape of speed curve (F1-10~F1-15).
Top and bottom terminal switch signal is used for elevator force deceleration and floor position calibration, it should be
installed in the position where it is triggered when elevator is 2.5m ahead of top (bottom) leveling position(for 1.6m/s
lift). The position should be determined as follows:
4. Distance between car sill and landing door sill should be 2.5±0.1m.
For the positions of terminal switches under other speed elevator, please refer to the appendix I.
116
Chapter 8: Troubleshooting
Chapter 8: Troubleshooting
This chapter explains in detail the fault display of integrated controller, the reasons behind and possible solution. The
fault display on integrated controller may come from elevator system errors, Hoistway learning errors, driver errors,
motor parameters setting and Encoder phasing errors.
Error
Definition Possible Solution
Code
Check the work condition of door vane and
Door inter-lock faults: Door inter-lock circuit open at
Er2 door interlock circuit. Roller should have
elevator running
enough space at both side of the vane.
Check driver fault code, find the cause of fault,
Er3 Driver faults
and resolve it.
1. Exchange phase “V” and “W” on motor
Elevator running in opposite direction with
Er4 2. Exchange phase “A” and “B”, on encoder
command
terminal block or change in parameter setup.
System does not receive brake open feedback signal
1. Check the traction machine brake detection
after output brake open command:
switch and wiring;
Er5 1. No X17/X12/X31 feedback after Y0 output
2. If no feedback switch, should set feedback
0.5/2s/2s.
enable to OFF
2. X17/X15/X31 enable when Y0 has no output.
During elevator running, leveling zone input signal Check leveling zone signal circuit and induction
Er6
X3, X4 is always on. switch
Er7 Encoder pulse not enough at elevator running. Check the wiring from encoder to controller.
Running contactor output not matching feedback
signal: Check the Running contactor coil and
Er9
1. After Y1 output,X5 has no feedback in 0.4s. output/feedback circuit wiring.
2. X5 is enabled when Y1 has no output.
Er10 Safety circuit open, X10 input are invalid. Check safety circuits.
Leveling switch signal missing:
Er11 Elevator is running pass the floor, but there is not Check the leveling switches and its wiring.
input at X3 /X4.
Check the encoder, top limit switch including
Er12 Elevator pass top limit switch (X1 is invalid)
its position and wiring.
Check the encoder, bottom limit switch
Er13 Elevator pass bottom limit switch (X2 is invalid)
including its position and wiring.
1. Check encoder wiring and related circuits;
Floor counter error from encoder deviation 2. Check the leveling switch and related
Er14 accumulation: after this error, elevator will return to circuits;
bottom floor in inspection speed for recalibration. 3. Possible reason: traction rope slip /door
drive shake at start.
117
Chapter 8: Troubleshooting
Error
Definition Possible Solution
Code
Er17 No drive output after running command. Check parameters in controller or contact supplier.
Floor number error: after this error, elevator
Er18 will return to bottom floor in inspection Check the encoder and its wiring.
speed for recalibration.
The deceleration distance for target floor is
not enough. Elevator did not perform 1. Decrease “Least Speed” in user menu;
Er19
hoistway parameter learning after changing 2. Do hoistway parameter learning again.
terminal switch location.
When elevator reaches top/bottom floor and
1. Increase controller PI gain parameters; Check the
get deceleration instruction, but elevator
braking resistor specification
Er20 doesn’t slow down; elevator did not perform
2. Make elevator running curve more smooth.
hoistway parameter learning after changing
3. Do hoistway parameter learning again.
terminal switch location.
1. Check the traction rope for slip or car jam.
Er21 Single running time is over set time 2. Check related parameters in drive;
3. Check value of parameter “Over Time”.
Elevator has inspection signal input (X0
Er22 Check inspection switch and related circuits.
invalid) at elevator normal running.
One of two leveling switch (X3, X4) is invalid
Er23 Check leveling switches and wirings.
at elevator normal running.
Check heat sensor circuit. If this error cannot reset in
Heat sensor protection: Braking resistor or
Er25 90s, Y23 relay on controller will output KMC contactor
motor is over heat (X32 invalid ).
open signal.
Door inter-Lock contactor working state does
Check door interlock contactor terminal & coil and
Er26 not match to its coil ( X11, X36 input
their related terminal on controller.
different)
Emergency stop contactor working state does Check emergency stop contactor terminal & coil and
Er27
not match its coil state.(X10 input error) their related terminal on controller.
Top/bottom terminal (1st or 2nd) switch
Er28 fault. (X16 or X17 valid when elevator outside Check for terminal switches location and their wirings.
their floor)
1. Run elevator in inspection mode, give door open
command and check Y2 for output signal.
2. If Y2 has no output, need to check door open, close
Er30 Door open fault (car cannot open door)
limit switch and related signal.
3. When used as a rear door, please check whether
the front door and back door were set opposite.
118
Chapter 8: Troubleshooting
Error
Definition Possible Solution
Code
Normally due to door not installed properly and short circuit door
Door close fault (car cannot close
Er31 interlock circuit. Check if door close and door interlock circuit are
door)
output at same time.
A sudden power break may affect terminal/limit switches and
Er32 Floor number counting error. cause floor number error. Elevator will then return to bottom
floor for recalibration.
External power +24V drop down Check the connection of external power +24V.
Er34
error When system find the voltage is lower than 16V, this error occurs.
The circuit hardware on main board works abnormally, please
Er35 System clock error
contact with our factory.
When system find the power of 5V is lower than 4.7V, this error
Er36 Internal power +5V error
occurs.
Running contactor vibrate while
Er37 Check the action of running contactor and its feedback X5.
brake opening
Brake force detection fail, lack of Check the brake, power off then on or disable brake force
Er39
brake force. self-detection. Recoverable.
Safety protection function act. When system find the brake
invalid, it control the car creep around door zone to release
Er40 Brake invalid and car slide error passengers and then return to top floor and brake off again, but
brake still fail to close. System announces brake invalid error and
lock, will not recover until reset.
Safety protection function act. When system find the brake
invalid, it control the car creep around door zone to release
Unintended slide error, pay attention
Er41 passengers and try to brake off. During the creeping, the brake
to brake force.
successful turn off. System record this slide error as a warning of
brake force but not display error. You can see it in Fault Record.
The car slides, system announces error and record it to prevent
While ARD mode, system find brake
Er42 power of UPS drop too low during creeping. Unless it may cause
force invalid.
unpredictable danger.
119
Chapter 8: Troubleshooting
Error
Definition Possible Solution
Code
Safety protection function act, the car
Remind maintenance man to solve the problem of door zone
runs out of door zone while re-leveling
missing. To prevent door zone missing happens as well as
Er43 and caused door circuit been cut off.
brake force invalid, or creeping will cause the car run out of
System announce door zone missing and
safety range.
lock the error until reset.
Safety protection act, then car creep around door zone.
While safety protection function works,
Er44 While up creeping, the signal from up limit(X1) vibrated.
signal of up limit has vibrated.
System will record this error and lock the error until reset.
Safety protection act, then car creep around door zone.
While safety protection function works, While down creeping, the signal from down limit(X2)
Er45
signal of down limit has vibrated. vibrated. System will record this error and lock the error until
reset.
Safety protection act, then car creep around door zone.
While safety protection function works,
Er46 While up creeping, the signal from up terminal(X16) vibrated.
signal of up terminal has vibrated.
System will record this error and lock the error until reset.
Safety protection act, then car creep around door zone.
While safety protection function works, While down creeping, the signal from down terminal(X17)
Er47
signal of down terminal has vibrated. vibrated. System will record this error and lock the error until
reset.
Parameters of safety protection function Enable safety protection, but disable open in advance &
Er48
has been wrongly set. re-level function.
Enable safety protection, but can not find door zone signals
Er49 Miss safety door zone signals.
at leveling position.
Check the follows parameters: If Park floor, Homing floor or
Fire Floor has been set to non-stop floor; If both front door
Er50 Parameters setting is not proper.
and rear door is disabled in two door mode; Group control is
enabled with duplex control or two door mode.
When running, drive module met overheat protection.
Er51 Drive module overheat protection.
Elevator stopped at nearest floor.
The up and down door zone signals are
Er52 Exchange up and down door zone signal wires.
opposite.
Haven’t used X31 as hall door detection,
1. Check if X31 is effective when F4-06-12 is OFF;
Er62 but X31 is effective. Or have no door
2. Check if X11 is effective when F4-06-13 is ON.
contactor but X11 become effective.
The minimum speed change distance is
Er97 less than the door zone segment magnetic Increase the minimum running speed of single floor.
plate.
Er98 Drive program locked Please contact with supplier.
Er99 Logic program locked. Please contact with supplier.
120
Chapter 8: Troubleshooting
121
Chapter 8: Troubleshooting
LER=24 The up and down door zone signals are Check installation position of up and down door zone
opposite in hoistway learning. sensor, exchange their wires.
Note: System has 2 top and 2 bottom terminal switches for elevator speed >2.0m/s.
122
Chapter 8: Troubleshooting
123
Chapter 8: Troubleshooting
124
Chapter 8: Troubleshooting
125
Chapter 8: Troubleshooting
126
Chapter 8: Troubleshooting
127
Chapter 8: Troubleshooting
Note: FD-21 is special function control parameter for controller. Each bit of binary stand for a function. So it have to
be set by bit.
BIT0: Ignore input phase lost
BIT1: Adjust if subdivision speed is same with normal hardware speed
BIT2: Adjust output phase lost
BIT3: Break circuit and short circuit test
BIT4: Temperature adapt
BIT5: Low voltage adapt
BIT6: 1 round tuning
BIT7: calculate poles automatically
BIT8: extend running mode for geared
BIT9-BIT15: Spared.
The final value of FD-21 depends on calculation of all above bit. The formula is as follow,
FD-21 = BIT0*2^0+BIT1*2^1+BIT2*2^2+…+BIT15*2^15;
128
Chapter 8: Troubleshooting
Chart 8.4 Motor Initial Angle Rotation Tuning Fault List (CONT’D)
Error
Definition Possible Causes Possible Solution
Code
Imbalance between inverter and motor Check motor parameters
Output current over
RF227 Wrong motor or encoder parameter Increase F5-08 to complete tuning,
limit
setting then recover F5-08.
Release Up or Down button while tuning
RF228 ESC input Do angle tuning again
ESC input effective during angle tuning
Over time at zero
speed
Brake open or brake force is not enough. Ensure brake is off.
RF229 Before start,
There’s interference in encoder. Remove interference of encoder
feedback speed is not
zero for a long time
Broken circuit at load side or lack of phase
Ensure 3-phase connection to
Imbalance phase of motor side or rated
motor.
Current detection current wrongly set
RF230 Ensure motor parameters setting.
error Inverter cannot adapt to motor
Ensure motor should adapt to
(Motor capacity is highly lower than
inveter.
inverter)
CD signals analysis fault Check CD signals wiring.
Parameters of motor or encoder have Remove interference.
CD signals of encoder
RF231 been wrongly input. Verify parameters of motor and
is abnormal
Interference in encoder. encoder.
Wrong PG type set. Check PG type set.
1. Check encoder signal connection;
1. Encoder connection fault; 2. Motor parameter input correct;
Motor does not 2. Motor has load or brake close; 3. Check motor/controller
RF232
rotate at auto tuning 3. Motor parameter input error; connection;
4. Motor & controller connection error. 4. Make sure motor has no load &
brake open.
Motor rotate in Motor phase sequences does not match 1. Adjust motor phase sequence
RF233
wrong direction encoder 2. Adjust encoder A-, A+ or B-, B+
1. Check wiring for Z pulse signal;
Encoder Z pulse 1. No detection of Z pulse signal; 2. Make sure motor has no load.
RF234
signal error. 2. Motor/Controller connection error. 3. Check motor/controller
connection.
Motor moved while Brake open or brake force is not enough. Ensure brake is closed.
RF237 static angle Bad encoder wire or interference in Check encoder A, B signals, remove
calculation encoder. interference
129
Chapter 8: Troubleshooting
Chart 8.5 Motor Initial Angle Static Tuning Fault List (Cont'd)
Error
Definition Possible Causes Possible Solution
Code
Check motor/controller
Motor/Controller connection is
Detection current connection.
PF238 incorrect.(Break circuit or phase
is too small Check rated current and rated
lost)
power of motor.
No encoder Z/R pulse signal
If motor can run, check the
Encoder Z/R pulse detected after motor tuning for
encoder wiring; otherwise find
PF239 signal lost.(For BL6 10s.
out why motor cannot run.
only) Interference in Z/R pulse signal.
Remove the interference.
A & B signals connection error.
During static angle tuning, after
initial location, motor need to
Check if there is feedback from
While static angle rotate for 3 rounds. During
SIN/COS encoder.
RF252 tuning, motor rotating, system give out speed but
Check the phase of power
speed is overproof. receive no feedback and the lasting
input.
time of this status has been over
limit. Then system announce error.
Note: 1. Above description is for SIN/COS encoder;
2. For increment encoder, RF231 correspond to UVW signals, RF234 and RF239 correspond to Z
pulse. The solution is same, and other faults are same too.
Motor parameters tuning error code and their possible causes and solution are shown below in Chart 8.6 and Chart 8.7.
(Including rotation and static parameters tuning)
130
Chapter 8: Troubleshooting
131
Chapter 9: Maintenance
Chapter 9: Maintenance
This chapter describes precautions and notes for drive storage and maintenance.
² There are high voltage terminals in integrated controller, please DO NOT TOUCH.
Otherwise there has potential risk of electric shock.
² Make sure to install front protection cover before power on integrated controller and cut
power before removing the front protection cover.
Otherwise there has potential risk of electric shock.
² Before open case service/maintenance, make sure the power is cut for 10 minutes, power
on LED (CL) is off and DC+/- bus voltage is lower than 24V.
Otherwise there has potential risk of electric shock due to capacitor remain voltage.
² Only authorized and qualified personnel are allowed to inspect/service integrated
controller.
Otherwise there has potential risk of electric shock and damage the product.
² Before maintenance, technicians must remove any metal objects (watch, ring, ect), and
must wear cloth with qualified isolation level.
Otherwise there has potential risk of electric shock.
² DO NOT remove or change terminal ports at controller power on.
Otherwise there has potential risk of electric shock.
² DO NOT change internal structure of the integrated controller.
Otherwise there has potential risk of electric shock and damage the product.
² After maintenance, please make sure all terminals and contactors are tightly secured.
Otherwise there has potential risk of controller not functioning or even get damaged.
132
Chapter 9: Maintenance
In order to increase the life time of controller and make sure the safety operation of elevator, it is necessary to check
and inspect controller in a daily basis. As it is not allowed to remove the controller front cover with controller power on,
the controller can checked by observing the device external condition, including:
2. Check if the LED indictor and digital operator of controller is working properly.
5. Check the ambient environment (Temperature -10~45℃, humidity 5~95%RH, no frozen, no oil mist or
powder in air)
7. Check if the input power and frequency are within rated range.
In order to increase the life time of controller and make sure the safety operation of elevator, it is necessary to check
and inspect controller in a routine basis. At routine check, first switch elevator to inspection mode, stop elevator
operation and cut system power. Then please perform inspections procedures based on Chart 9.1, following safety
precautions and notes mentioned above.
133
Chapter 9: Maintenance
Controller is made from many components inside, all these parts have their lifetimes, and they depends on
environment and working condition. As a result, in order to increase the life time of controller and make sure the
safety operation of elevator, it is necessary to check and inspect some of these parts in a regular basis, replace them if
needed. Chart 9.2 below is the components change standard.
Note: Conditions below are required in order for components to reach life time mentioned above.
9.5. Warranty
Integrated controller warranty period is 18 months after manufacturer (based on product name plate).However, even
within the 18-month warranty period, repair cost will be charged in the following cases:
134
Chapter 10: Controller Installation with EMC Standard
EMC (short for Electromagnetic Compatibility) refers to the device/system capability to function normally in an
environment with electromagnetic interference. It has two parts: first, the device/system must be able to work
normally in environment with electromagnetic interference. Then, the electromagnetic interference it generated must
be within a certain level so it will not affect other devices/systems in the environment.
Same as other electronic devices, the integrated controller is affected by electromagnetic interference and at the same
time it is also a source of electromagnetic interference. In order to enable the controller work normally in an
electromagnetic environment, at the same time not to affect other devices, it is specially designed to deal with EMC
characteristics shown below.
1. Input current is non-sine wave, with high frequency, this will cause strong electromagnetic interference.
2. Output voltage is high frequency PWM wave, this will cause strong electromagnetic interference.
3. As electromagnetic receiver, if controller receives too strong interference, it may not work properly.
4. Reduce controller generated electromagnetic interference will increase its own EMC level.
As determined by operating principle, the elevator integrated controller produces certain noises during operation. The
effect of noise on peripheral equipment is relevant to the noise type, transmission path as well as the design,
installation, wiring and grounding of drive system.
1. Power cable and signal cable should be lay out separately and stay as far as possible, make sure to avoid two kind
of cables stay in parallel or tied together. When meet situations in which signal cable must pass power cable, make
sure two cables stay in perpendicular crossing and stay as far as possible.
2. All controller signal cable must have net shield, and the shield should be grounded at the controller side, with
grounding area as large as possible.
3. For signal cables easy to get interference, such as encoder cable, it should have double twist shield cover, with
grounding area as large as possible. One suggestion is to put the cable in metal tube or in a individual metal cable
tunnel with reliable grounding condition.
135
Chapter 10: Controller Installation with EMC Standard
4. Power cable and motor cable should use power cable with armor cover or shield. Power cable should use
individual metal cable tunnel with reliable grounding point at controller side. Motor cable should follow the same
grounding principle and its shield should also connect to motor cover at motor side.
5. Power cable should be connected to inverter use RFI filter or output reactor. Motor cable should be connected
with output filter (sine/cosine filter) or install output reactor. Another solution is to surround motor cable twice with
ferrite magnetic circle.
6. Other devices that are easy to get interference should be put far away from the controller and power cable.
7. Inductive devices around controller such as contactor, relay, brake unit, their coil need to install surge controller
(such as RC filter, resistor or freewheeling diode).
10.3.2 Wiring
1) Inside control cabinet, signal cable and power cable should be placed in different area, with minimum
distance of 20cm. DO NOT put two kinds of cables in parallel or tied together. If must cross two cable, they
must remain strictly perpendicular with each other.
2) The input (power) and output (motor) of power cable cannot cross or tied together, especial when the cable
is connected with input/output filter.
3) Inductive devices inside control cabinet (such as contactor, relay, brake unit), their coil need to install surge
controller (such as RC filter, resistor or freewheeling diode).
4) Both signal and power cable should have net shield/armor with high frequency low impedance.
2. Wiring at site
1) Power cable must have 5 wires, including U/V/W, one for ground and one for neutral, DO NOT mix use.
2) At site, signal cable and power cable should be placed in different area, with minimum distance of 20cm. DO
NOT put two kinds of cables in parallel or tied together. If must cross two cable, they must remain strictly
perpendicular with each other.
3) Signal cables must have net shield, the shield should be grounded at controller side with large ground area.
4) Power cable and motor cable should use power cable with armor cover or shield. Power cable should use
individual metal cable tunnel with reliable grounding point at controller side. Motor cable should follow the
same grounding principle and its shield should also connect to motor cover at motor side.
Controller must be connected to the ground at work, grounding helps to solve the EMC issue, at the same time it brings
safety to the device and people. Ground correctly is the most important (and most reliable/economic) solution to EMC
issue, and it should be considered first. Notes for ground connections are shown below:
136
Chapter 10: Controller Installation with EMC Standard
2. The case of control cabinet must be connected to the ground public terminal. This connection can be made
between cabin door and ground public terminal copper plate (width >15mm).
3. All ground connection must remain complete on both sides, cannot connect two grounding wire in the middle.
4. The ground of integrated controller must be connected to the ground public terminal.
5. Power cable, motor cable and brake resistor cable (if necessary) shield/armor must be connected to the ground
public terminal.
6. The distance from cable shield to ground public terminal should be <50mm.
7. Ground connection wire should have low impedance (large cross sectional area and short in length).
8. Power cable should have 5 cores (U,V,W, neutral & ground) with shield, motor cable should have 4 core (U, V, W,
ground) with shield. For motor cable ground wire, one terminal should be grounded at controller side,
another terminal should be grounded at motor side.
Leakage current happens between wire and to ground, it depends on wire capacitance and controller carrier frequency.
Leakage between wire is related to wire capacitance between controller input (power cable) and output (motor cable),
controller carrier frequency, motor/power cable cross sectional area and length, while leakage current to ground is
located at ground public terminal, it will get into the system and (in some case) affect other electrical devices through
ground connection.
3. Power and motor cable cross sectional area should not be too big;
4. For long motor cable (>50m), controller output should have filter or reactor;
137
Chapter 10: Controller Installation with EMC Standard
1. In the cabinet, the filter should be located close to the power line inlet as practicably as possible. Additionally, the
filter supply line section left in the control cabinet must be as short as possible.
2. The power line filter should be grounded with reliable connection, and the grounding area should be as large as
possible.
3. The power line filter metal case should be securely attached to the control cabinet plate, with contacting area as
large as possible and ensure good electrical connection.
4. Please use power line filter that matches the system, such as inverter use power line RFI filter.
When install integrated controller and EMI filter, if the installation procedures are following EMC installation guide,
then the system could meet the standards below:
138
Chapter 11: Accessories
4-Φ3.5
J1 J3
1 2 3 4 5 6 7 8 9 10
J5
1
2
3
J4 4
5
BL-2000-QKB-V1
86
96
1
J2 2
3
149
159
1. Group control system is combined with one group control board "BL2000-QKB-V1" and several integrated
controllers in every elevator in the group. Group controller collect hall call, car call and status information of
every elevator through CAN BUS, process them, and deliver distribution orders to every elevator. In this way the
group control for up 8 elevators & 64 floors is achieved.
2. Four Running Modes
n Up peak mode: At set time, all elevators answer landing call with up call from base floor has highest priority.
n Down peak mode: At set time, one elevator answer up call with priority; other elevators answer down call
(one elevator on each area) with priority to minimize the down call reaction time.
n Balance mode: Landing call distribution is optimized according to shortest time response principle.
n Spare mode: 3 minutes at the balance mode without landing/car call, elevator will wait for the order from the
first floor on each area so that response to hall car as soon as possible.
When elevator is at status of fault, attendant, inspection, parking, fire and special use mode, it will be excluded from
group control mode. Please follow the relevant chapter in this user guide for individual elevator operation in group
control mode.
11.1.2 Application
1. Group Control from 3 to 8 elevators;
2. Elevator speed 0.5-4m/s;
3. Can be used up to 64 floors;
4. Applies to passenger and residential elevator.
139
Chapter 11: Accessories
2. J2 Connector 2.54/3P
3. J3 Twin housing 2.54/10P
4. J4 Connector 2.54/5P
5. J5 Single shield plug-in 3.96/4P
GND3 J1-3 0V
5V IN J1-4 5V Input 200mA
J1-5
J1
TXA+ J1-6 Group Control
TXA- J1-7 Communication
GND3 J1-8 0V
J1-9 Spare CANComm.TXA+
J1-10 Spare CANComm.TXA-
DA+ J2-1 RS485
J2 DA- J2-2
GND J2-3
J3 Programming Interface
TX J4-1 Communication Send RS232
J4 RX J4-2 Communication Receive
IN J4-3 Control Input
OUT J4-4 Control Output
J5 TXA+ J5-1 Group Communication
140
Chapter 11: Accessories
TXA- J5-2
GND3 J5-3 0V
J5-4
Parrallel Extension Board FR2000-EBA-V01 shape and dimension are shown below in Figure 11.3.
11.2.1 Function
Parallel extension board is used with parallel integrated controller for floor extension. Without extension board,
parallel controller can achieve maximum 7 floors (full collective), each extension board can extend 4 floors. At most,
you can connect two extension boards and extend maximum floors to 15 floors.
11.2.2 Application
1. Extend maximum car call/landing call for floors 8 to 15;
2. Each extension board can extend 4 car calls and 4 landing calls;
141
Chapter 11: Accessories
I1~I12
LED
L1~L12
LED
J J
5 6
Technical Specification
Name Terminal Location Definition Usage
Interface Type Rated Load Max Speed
24V J1-1 24V
24V J1-2 24V
None J1-3
None J1-4
Power & Communication
GND J1-5 0V
GND J1-6 0V
SOTNEB J1-7 Output data
J1
RCK J1-8 Output clock
SRCK J1-9 Output Latch
SER J1-10 Input Latch
CLK J1-11 Input clock
SH J1-12 Input data
5V J1-13 5V
5V J1-14 5V
J2 Same as J1
142
Chapter 11: Accessories
Technical Specification
Name Terminal Location Definition Usage Interface Rated Max
Type Load Speed
Full Collective/Simplex Collective
I1 J3-1
Car call input 8/ Car call input 10
Full Collective/Simplex Collective
I2 J3-2
Car call input 9/ Car call input 11
Full Collective/Simplex Collective
I3 J3-3
Car call input 10/ Car call input 12
Full Collective/Simplex Collective
I4 J3-4
143
Chapter 11: Accessories
Technical Specification
Name Terminal Location Definition Usage Interface Rated Max
Type Load Speed
Full Collective/Simplex Collective
L5 J5-5
Up call output 7/ Car call output 14
Full Collective/Simplex Collective
L6 J5-6
Up call output 8/ Car call output 15
Full Collective/Simplex Collective
J5 L7 J5-7
Up call output 9/ Call output 11
(Extension Full Collective/Simplex Collective
1) L8 J5-8
Up call output 10/ Call output 12
Full Collective/Simplex Collective
L9 J5-9
Down call output 8/ Call output 13
Full Collective/Simplex Collective
L10 J5-10
Down call output 9/ Call output 14
Full Collective/Simplex Collective
L11 J6-1
Down call output 10/ Call output 15
J6 Full Collective
L12 J6-2
(Extension Down call output 11
1) J6-3
J6-4
J6-5
Technical Specification
Name Terminal Location Definition Usage Interface Rated Max
Type Load Speed
I1 J3-1 Full Collective Car call input 12
I2 J3-2 Full Collective Car call input 13
Power & Communication
144
Chapter 11: Accessories
Technical Specification
Name Terminal Location Definition Usage Interface Rated Max
Type Load Speed
J4(Extension J4-4
2) J4-5
L1 J5-1 Full Collective Car call output 12
L2 J5-2 Full Collective Car call output 13
L3 J5-3 Full Collective Car call output 14
L4 J5-4 Full Collective Car call output 15
J5
L5 J5-5 Full Collective Up call output 11
(Extension
L6 J5-6 Full Collective Up call output 12
2)
L7 J5-7 Full Collective Up call output 13
L8 J5-8 Full Collective Up call output 14
L9 J5-9 Full Collective Down call output 12
L10 J5-10 Full Collective Down call output 13
L11 J6-1 Full Collective Down call output 14
J6 L12 J6-2 Full Collective Down call output 15
(Extension J6-3
2) J6-4
J6-5
145
Appendix 1: Hoistway Switches Information
1. Elevator stop at each floor, measure car and hall sills difference △S
on each level at elevator park (car sills higher is position, lower is
negative)
2. Adjust door zone flag on each floor, if △S>0, flag on this floor
should move down △S; move flag up △S if △S<0.
3. Elevator need to redo the hoistway parameter learning after door
zone flag adjustment.
4. Check elevator leveling on each floor, read part 1-3 if necessary.
FIGURE F1.1 DOOR ZONE FLAG & LEVELING SWITCH POSITION
1. Terminal switches are recommended to use non-contact type, such as magnetic switch.
2. Up/Down terminal switches are installed in hoistway guide rail; terminal flag is installed on top of car. Their
positions are shown blow in Figure F1.2 & F1.3.
3. For elevator speed ≤1.75m/s, only one up and one down terminal switch and one terminal flag is required. For
elevator speed ≥2.0m/s, more terminal switches should be installed for safety purpose. Please see below Chart F1.1
for up/down terminal switches position with different elevator speed.
146
Appendix 1: Hoistway Switches
Up/down terminal switches signal is used for elevator force change speed and floor position calibration, they should be
installed 2.5m from car top/bottom to top/bottom floor leveling position. (For elevator speed at 1.6m/s or 1.75m/s).
To confirm such position:
4. At this time the car sills and hall sills should have a distance of 2.5±0.1m.
147
Appendix 2: Re-leveling & Door Open in Advance
148
Appendix 2: Re-leveling & Door Open in Advance
When using the function of advance door open and re-leveling, besides the up and down leveling switches, two extra
re-leveling switches should also be installed. Their installation is shown in Figure F2.3.
mq1:Up leveling switch; mq2: down leveling switch; sl1: up re-leveling switch; sl2: down re-leveling switch; all
leveling switches should be installed in sequence. Otherwise the direction of the re-leveling running will be reversed.
mq1 10m
sl1 90m
sl2 90m
mq2
10m
149
Appendix 2: Re-leveling & Door Open in Advance
If SI1 and SI2 are magnetic sensor, their distance must remain at least 5cm, otherwise two sensors will be
affected by each other and not able to function.
1. Advance door open elevator speed (F1-07): After elevator enter door zone in normal running, the elevator speed
at advance door opening.
2. Re-leveling speed limit (F1-08): In the process of advance door opening and re-leveling, if elevator speed is
higher than this value, elevator will stop.
3. Re-leveling running speed (F1-09): Set the elevator running speed at re-leveling.
150
Appendix 3: Parameters List
151
Appendix 3: Parameters List
152
Appendix 3: Parameters List
153
Appendix 3: Parameters List
154
Appendix 4: Emergency Leveling Function
F4.3 Caution
The effect of F4-06-22 parameter is that when the emergency power supply is 220V, the voltage of DC-bus will drop
and cause low voltage fault; when emergency leveling input X18 is enable on integrated controller, the elevator will
run in emergency leveling mode. At this time if the parameter is set "OFF", the integrated controller will by-pass such
fault and continue the rescue operation.
If emergency power supply is 380V, or UPS output is 380V, please set the parameter to ON. Otherwise when X18
input signal is active, the controller cannot detect the voltage drop on main DC-bus and it cannot start the rescue
operation.
155
错误!未找到引用源。
156
错误!未找到引用源。
Digital display
F - 0 1
Keys
F ESC ∨
0 1 Enter
F - 0 1
2. F tube flashing0display error
Digital 1 code when fault occurs.
E - 1 0
3. EENTER key and 1Flip key 0
Press to select H-00~H-07 parameters:
H - 0 0 H - 0 1
H 0 0 H 0 1
H - 0 2 H - 0 3
H 0 2 H 0 3
H - 0 4 H - 0 5
H 0 4 H 0 5
157
错误!未找到引用源。
ENTER
H - 0 1 1 6 0
6. H-02:H 0 self-learning:
Hoistway parameter 1 1 6 0
H - 0 2
H ENTER 0 2
L 1
L 1 Display L2 when run elevator to lower limit position.
L 2
L 2 Press ENTER and elevator perform hoistway auto tuning
automatically. Display current floor.
L X X L E X X
L XDisplayXcorresponding error
L codeEif autoXtuningXfailed.
Press ENTER to quit auto tuning.
L 2
L 2 Restore display L2 if auto tuning successful.
Please check Appendix III hoistway auto tuning error code
Press ENTER to quit.
158
错误!未找到引用源。
7. H-03: Parameters setting with hand operator. Set once the parameter when connecting digital
operator.(Set this parameter again to support hand operator after main board reset).
ENTER
H - 0 3 0/1
H - 0 4
H 0 4
ENTER
ENTER
E - 0 1 1 0
E
Fault No.
0 1 1 0
Error code(Please check Appendix III elevator system faults)
ENTER
E - 0 2 0 9
E 0 2 9
……
ENTER
E - 3 0 0 9
E 3 0 0 9
159
错误!未找到引用源。
H - 0 5
H 0 5
H 5 - 1
H 5 Choose 1, press ENTER to enter motor auto tuning mode.
T - 0 2
T 0 2
After drive microcontroller answer normal, display is shown below:
T - 0 3
T 0 Keep3pressing jog up or jog down to rotate motor 3 circles.
Auto tuning fault
E X X X
Handling according to error information prompted.
E X X X
T - 0 4
AutoTtuning proceeds0 4
gradually.
Press ENTER to quit.
160