Tripp Lite Owners Manual 773185
Tripp Lite Owners Manual 773185
Tripp Lite Owners Manual 773185
Self-Contained
Air Conditioning Unit
Model: SRCOOL33K
The contents in this service manual are subject to change without notice.
1
Table of Contents
1. Specifications 3 9. Basic Test Procedure 26
2. Unit Dimensions 4 9.1 Defective Compressor 26
3. LCD Control Panel 5 9.1.1 Compressor Wiring Test 26
9.1.2 Ground Test 26
4. Refrigerant Cycle Diagram 6
9.1.3 Checking Compressor Efficiency 26
5. PCB and Wiring Diagrams 7
9.1.4 Compressor Thermal Overload (Internal) 27
5.1 Circuit Diagram 7
9.1.5 Testing the Internal Overload for Failure 27
5.2 PCBA Diagrams 8
9.2 Sealed Refrigeration System Repairs 27
5.2.1 Power PCBA 8
9.2.1 Equipment Required for 27
5.2.1.1 Power PCBA Schematic 8
Refrigeration System Repairs
5.2.1.2 Power PCBA Critical 9
Components Layout 9.2.2 Equipment Requirements 27
5.2.1.3 Power PCBA Gerber Layout 10 9.2.3 Compressor Replacement 28
5.2.2 Display and Control PCBA 11 9.2.4 Special Procedure in the Event of 28
5.2.2.1 Display and Control 11 Compressor Motor Burnout
PCBA Schematic 9.2.5 Refrigerant Charge 29
5.2.2.2 Display and Control 12 9.3 Fan Motor 29
PCBA LCD and Buttons Layout 9.3.1 Fan Motor Test 29
5.2.2.3 Display and Control 12
9.4 Capacitor 30
PCBA Gerber Layout
9.4.1 Capacitor Test 30
5.2.3 Translator PCBA 13
5.2.3.1 Translator PCBA Schematic 13 10. Temperature Sensor Table 31
5.2.3.2 Translator PCBA Gerber Layout 14 11. Troubleshooting 32
6. Unit Disassembly 15 11.1 Troubleshooting Table 32
6.1 Removing Side Panels 15 11.2 Troubleshooting Flowcharts 34
6.2 Opening the Door 15 11.2.1 General Troubleshooting Flowchart 34
6.3 PCB Cover Removal 16 11.2.2 Electrical System Troubleshooting 35
Flowchart
7. Exploded Diagram and BOM 17
Español 36
8. Electronic Function 21
8.1. Main Features 21
8.2 General Controller Technical Specifications 21
8.3 Sensor Definitions 21
8.4 Main Control Functions 22
8.4.1 Energy Saving Mode 22
8.4.2 Normal Mode 23
8.5 Fan Speed Switching (Evaporator) 24
8.6 Other Controls (Self-Evaporating Motors 24
and Water Pumps)
8.7 Internal Timers 24
8.8 Protection Controls 24
8.8.1 Compressor Delay Protection 24
8.8.2 Defrost Protection 24
8.8.3 Other Protection Controls 24
8.9 Memory Function 25
8.10 UART/RS232 Communication 25
8.11 Factory Defaults 25
8.12 Unit Defaults During Power Up 25
After Power Loss
2
1. Specifications
Model SRCOOL33K
Nameplate Marking TRIPPLITE
Power Supply 1φ, 208~240V/60 Hz
Cooling Capacity 33000 Btu/h
Cooling Power Consumption 3000W
Cooling Rated Current 12.5A
Cooling SCE 8.24W/W
System Data
Refrigerant Type R410A / 2250 g
Operation Pressure 3.0~3.5 Mpa
Moisture Removal (30oCR H80%) 80.4 L/Day
Indoor Air Flow 29 m³/min
Noise Level <60 dBA
Dimensions and Weight
Unit Dimensions [W x H x D] 23.6 x 78.4 x 42.7 in. (599 x 1991 x 1085 mm)
Shipping Dimensions [W x H x D] 26 x 84.3 x 44.9 in (660 x 2140 x 1140 mm)
Net/Gross weight 558 lb. / 672 lb. (253 kg / 305 kg)
System Details
Compressor Model 55A842G
Type Rotary
Capacity 33330 Btu ±5% /h
Input 3315W ±5%
Rated Current (RLA) 14.8A ±5%
Locked Rotor Amp (LRA) 79.5A ±5%
Thermal Protector UP14RE5115
Capacitor 40 μF / 420V AC
Refrigerant Oil 660 CC ±10 CC
Oil Type NMOC Ze-GLES RB68EP (or equivalent)
Fan Motor EVA Motor CON Motor
Model FH355AP000 FH355AP000
Input 355W / 325W / 215W 345W
Capacitor 8uF / 17uF / 25uF 8uF
Speed (hi/mi/lo) ±50 1600 / 1200 / 1000 Rpm 1550 Rpm
Evaporator (EVA)
Number of Rows 3
Tube Pitch [a] x Row Pitch [b] 0.83 x 0.78 in. (21 x 19.7 mm)
Fin Spacing 18 FPI
Fin Type (Code) Hydrophilic aluminum
Tube Outside Dimension Type φ7 mm Inner-Groove Tube
Axial [L x H x W] 18.3 x 24.8 x 1.5 in. (465 x 630 x 38.1 mm)
Number of Circuits 5
Condenser (CON)
Number of Rows 4
Tube Pitch (a) x Row Pitch (b) 0.83 x 0.78 in. (21 x 19.7 mm)
Fin 18
Fin Type (Code) Aluminum
Tube Outside Dimension Type φ7 mm Inner-Groove Tube
Axial [L x H x W] 18.3 x 36.4 x 2.5 in. (465 x 924 x 63.5 mm)
Number of Circuits 2
3
2. Unit Dimensions
78.4 in.
(1991 mm)
42.7 in.
(1085 mm)
23.6 in.
(599 mm)
4
3. LCD Control Panel
A POWER Button: Switch on/off; default standby.
B MODE Button: Switch between energy saving mode (ENERGY SAVING) and normal mode (NORMAL COOLING).
Note: Normal cooling mode is the default setting. When the unit is powered off, hold this button for 3 seconds to switch between
Fahrenheit (F) and Celsius (C) temperature units.
Note: Fahrenheit is the default setting.
C TEMP + : Sets cooling temperature in +1°F/°C increments. Hold this button to scroll to the highest value.
The set temperature will flash in the display.
D TEMP - : Sets cooling temperature in -1°F/°C increments. Hold this button to scroll to the lowest value.
The set temperature will flash in the display.
E SPEED: When in ENERGY SAVING mode, use this button to switch between automatic, high, medium or low fan speed.
HI SPEED, MED SPEED, LOW SPEED, or AUTO will light up accordingly.
Note: AUTO is the default setting. If there is no response during NORMAL COOLING, the speed will be set to AUTO.
F Status LEDs
G LCD Screen
F G
A B C D E
5
4. Refrigerant Cycle Diagram
The below diagram briefly describes the critical components and their functions combined with the refrigeration system.
Evaporator
2) service port x 2
Condenser
High-pressure liquid coolant
High-pressure gas coolant
Dissipate heat
6
5. PCB and Wiring Diagrams
UPPER FAN
MOTOR
LOWER FAN
MOTOR
7
5. PCB and Wiring Diagrams
5.2 PCBA Diagrams
5.2.1 Power PCBA
The following diagrams are for Tripp Lite part no. 167752T.
8
5. PCB and Wiring Diagrams
5.2.1.2 Power PCBA Critical Components Layout
Display
Inner Temperature
Sensor
Outer Temperature
Sensor
Upper
Fan
Lower Fan
9
5. PCB and Wiring Diagrams
5.2.1.3 Power PCBA Gerber Layout
10
5. PCB and Wiring Diagrams
5.2.2 Display and Control PCBA
The following diagrams are for Tripp Lite part no. 167751T.
11
5. PCB and Wiring Diagrams
5.2.2.2 Display and Control PCBA LCD and Buttons Layout
12
5. PCB and Wiring Diagrams
5.2.3 Translator PCBA
The following diagrams are for Tripp Lite part no. 167788T.
13
5. PCB and Wiring Diagrams
5.2.3.2 Translator PCBA Gerber Layout
14
6. Unit Disassembly
6.1 Removing Side Panels
To remove a side panel from the unit, push down the latches to disengage the locks. Then carefully pull the panel out and up
to remove from the unit’s frame. Repeat for additional panels.
15
6. Unit Disassembly
6.3 PCB Cover Removal
To remove the PCB Cover, remove the screws as shown in the diagram below.
Screws
PCB
16
7. Exploded Diagram and BOM
Note: Parts with the RP- prefix can be ordered directly from Tripp Lite. For all other parts, contact Tripp Lite Technical Support at
773.869.1234 or https://www.tripplite.com/support.
20
8. Electronic Function
8.1. Main Features
• Function: Cooling only
• Modes: Energy Saving (no hot gas bypass) or Normal cooling (with hot gas bypass)
• Temperature setting range: Cooling: 63 ~ 86°F (17 ~ 30°C)
• Compressor delay function: 3.5 minutes during startup for self-protection
• Evaporator fan: 3 levels—high, medium or low; auto switch between high, medium or low upon request
• Condenser fan: One speed, synchronized with the compressor
• Self-diagnostic error code display
• Memory function during power shut down (or unplug)
• Displays both ambient and setting temperature
• Temperature default setting: Fahrenheit; interchangeable between Fahrenheit and Celsius
• No beep when button is pressed, but alarm sounds when unit is reported malfunctioning
21
8. Electronic Function
8.4 Main Control Functions
The following diagrams show the cooling temperatures in Energy Saving Mode and Normal Mode.
22
8. Electronic Function
8.4.2 Normal Mode
Note: When the compressor is stopped, the COOLING indicator will flash; otherwise it illuminates solid. The default setting temperature,
Ts, is 77°F (25°C). The oF or oC indicator will illuminate according to the unit setting in Fahrenheit or Celsius.
23
8. Electronic Function
24
8. Electronic Function
• After the unit runs for a total of 730 hours (per the sentry timer), the 2-digit temperature setting display shows “E8” and
WARNING indicator flashes within 5 seconds, but the unit continues running. Press and hold the SPEED buttons for
3 seconds, then turn off the alert and reset the internal timer to zero.
• When ALARM or WARNING indicators flash, the alarm will sound 10 times (every 0.5 second) to alert the end user.
• When WARNING indicators flash, the 2-digit temperature setting display shows “dF” or “E8”. The display will continue
showing the correct mode status, evaporator fan speed, ambient temperature or whether T1 is using an external thermostat.
• When ALARM indicators flash, except when the 2-digit temperature setting display shows “E1/E2/E3/E4/E7”, others will be
blank in display.
25
9. Basic Test Procedure
Remove the compressor terminal box cover and disconnect wires from terminals. Using an ohmmeter, check continuity across
the following:
- Terminal “C” and “R” - no continuity. Open winding - replace compressor.
- Terminal “R” and “S” - no continuity. Open winding - replace compressor.
- Terminal “C” and “S” - no continuity. Open winding - replace compressor.
26
9. Basic Test Procedure
If the test shows:
• Below normal high side pressure,
• Above normal low side pressure,
• Low temperature difference across coil,
Then the compressor valves are faulty; replace the compressor.
27
9. Basic Test Procedure
9.2.3 Compressor Replacement
The following procedure applies when replacing components in the sealed refrigeration circuit or repairing refrigerant leaks.
This includes the compressor, condenser, evaporator, capillary tube, refrigerant leaks, etc.
1. Recover the refrigerant from the system at the high-side service port (HP) and low-side service port (LP). Apply gauge from
the service port(s) to an EPA-approved recovery system. Recover CFCs in system to at least 5%.
2. Disconnect the high-side service port (HP) and make sure it is closed.
3. Connect the line from the nitrogen tank to the low-side service port (LP).
4. Drift dry nitrogen through the system and unsolder the more distant connection first (filter drier, high side process tube,
etc.).
5. Replace the inoperative component. Always install a new filter drier. Drift dry nitrogen through the system when making
these connections.
6. Pressurize system to 30 PSIG with proper refrigerant and boost refrigerant pressure to 150 PSIG with dry nitrogen.
7. Leak test the complete system with an electric halogen leak detector, correcting any leaks found.
8. Reduce the system to zero-gauge pressure.
9. Connect a vacuum pump to the high-side service port (HP) and low-side service port (LP). When connecting to the system,
make sure to deep vacuum hoses or copper tubing (do not use regular hoses).
10. Evacuate the system to maximum absolute holding pressure of 200 microns or less.
Note: This process can be sped up by use of heat lamps, or by breaking the vacuum with refrigerant or dry nitrogen at 5,000 microns.
Pressure system to 5 PSIG and leave in system for a minimum of 10 minutes. Recover refrigerant and proceed with
evacuation of a pressure of 200 microns or a minimum of 10%.
11. Break vacuum by charging the system from the high-side service port (HP) with the correct amount of refrigerant specified.
This will prevent boiling the oil out of the compressor.
Note: If the entire charge will not enter the high side, allow the remainder to enter the low side in small increments while operating the
unit.
12. Restart the unit several times after allowing pressures to stabilize. Disconnect all the hoses and close both the high-side
service port (HP) and low-side service port (LP).
28
9. Basic Test Procedure
9.2.5 Refrigerant Charge
1. The refrigerant charge is extremely critical. It must be measured carefully and as exact as possible to the nameplate
charge.
2. The correct method for charging the rotary is to introduce liquid refrigerant into the high-side service port (HP) of the
system with the unit off. Then start compressor and enter the balance of the charge—gas only—into the low-side service
port (LP).
The introduction of liquid into the low-side without the use of a capillary tube will cause damage to the discharge valve of the
rotary compressor.
Note: All inoperative compressors returned must have all lines properly plugged with the plugs from the replacement compressor.
29
9. Basic Test Procedure
9.4 Capacitor
A run capacitor is wired across the auxiliary and main winding of a single-phase permanent split capacitor motor, such as the
compressor and fan motor. A single capacitor can be used for each motor or a dual-rated capacitor can be used for both.
The capacitor’s primary function is to reduce the line current while greatly improving the torque characteristics of a motor. The
capacitor also reduces the line current to the motor by improving the power factor of the load. The line side of the capacitor is
marked with a red dot and is wired to the line side of the circuit
30
10. Temperature Sensor Table
R25/50=5K
Temperature Resistance Voltage Temperature Resistance Voltage Temperature Resistance Voltage
Value Value Value
°C °F Rt(K) Vh(V) °C °F Rt(K) Vh(V) °C °F Rt(K) Vh(V)
-20 -4 37.432 0.59 15 59 7.448 2.01 50 122 2.032 3.56
-19 -2 35.558 0.62 16 61 7.149 2.06 51 124 1.965 3.59
-18 0 33.788 0.64 17 63 6.864 2.11 52 126 1.901 3.62
-17 1 32.116 0.67 18 64 6.592 2.16 53 127 1.839 3.66
-16 3 30.537 0.70 19 66 6.332 2.21 54 129 1.779 3.69
-15 5 29.046 0.73 20 68 6.085 2.26 55 131 1.722 3.72
-14 7 27.636 0.77 21 70 5.848 2.30 56 133 1.667 3.75
-13 9 26.303 0.80 22 72 5.621 2.35 57 135 1.614 3.78
-12 10 25.042 0.83 23 73 5.404 2.40 58 136 1.563 3.81
-11 12 23.849 0.87 24 75 5.138 2.47 59 138 1.514 3.84
-10 14 22.715 0.90 25 77 5.000 2.50 60 140 1.467 3.87
-9 16 21.643 0.94 26 79 4.811 2.55 61 142 1.420 3.89
-8 18 20.629 0.98 27 81 4.629 2.60 62 144 1.375 3.92
-7 19 19.669 1.01 28 82 4.456 2.64 63 145 1.332 3.95
-6 21 18.760 1.05 29 84 4.291 2.69 64 147 1.290 3.97
-5 23 17.900 1.09 30 86 4.132 2.74 65 149 1.250 4.00
-4 25 17.086 1.13 31 88 3.980 2.78 66 151 1.212 4.02
-3 27 16.313 1.17 32 90 3.834 2.83 67 153 1.174 4.05
-2 28 15.582 1.21 33 91 3.695 2.88 68 154 1.139 4.07
-1 30 14.888 1.26 34 93 3.561 2.92 69 156 1.104 4.10
0 32 14.229 1.30 35 95 3.433 2.96 70 158 1.071 4.12
1 34 13.600 1.34 36 97 3.310 3.01 71 160 1.040 4.14
2 36 13.002 1.39 37 99 3.193 3.05 72 162 1.009 4.16
3 37 12.435 1.43 38 100 3.080 3.09 73 163 0.979 4.18
4 39 11.896 1.48 39 102 2.972 3.14 74 165 0.950 4.20
5 41 11.385 1.53 40 104 2.869 3.18 75 167 0.922 4.22
6 43 10.899 1.57 41 106 2.769 3.22 76 169 0.895 4.24
7 45 10.436 1.62 42 108 2.673 3.26 77 171 0.869 4.26
8 46 9.997 1.67 43 109 2.581 3.30 78 172 0.844 4.28
9 48 9.579 1.71 44 111 2.493 3.34 79 174 0.819 4.30
10 50 9.181 1.76 45 113 2.408 3.37 80 176 0.796 4.31
11 52 8.800 1.81 46 115 2.327 3.41 81 178 0.773 4.33
12 54 8.436 1.86 47 117 2.248 3.45 82 180 0.751 4.35
13 55 8.091 1.91 48 118 2.173 3.49 83 181 0.730 4.36
14 57 7.761 1.96 49 120 2.101 3.52 84 183 0.709 4.38
Vh=E×R0/(Rt+R0) Remarks: E=5V R0=5.0K
31
11. Troubleshooting
11.1 Troubleshooting Table
Problem Possible Cause Solution
No power displayed on Power failure Check if the power supplier is supplying power to the unit. Check
panel or any one of the the power cord and correct if damaged.
buttons failure Transformer (discharge Check resistance between the two input/output lines on
transformer before testing) transformer. Replace the transformer if either the input/output is
open or the transformer is damaged.
Display board or main PCB Check the voltage on the display board. Replace the display
Remote control failure failure board if it is +5V. Otherwise, replace the main PCB.
Battery failure Check the battery voltage. Replace batteries if the voltage is
lower than 2.3V.
Fan motor runs Cycles on overload Check voltage. Call an electrician if not within limits.
intermittently Test capacitor. Replace if not within +/-10% of manufacturer's
rating.
Check bearings. Replace the motor if the blower wheel cannot
rotate freely.
Pay attention to any change from high speed to low speed.
Compressor stops Refrigerant The amount of the refrigerant is too much, making the
instantly after startup compressor load too big. Recycle and recharge the refrigerant
after checking for the reason.
Compressor The compressor is blocked inside. Replace after checking for the
reason.
Fan motor will not run No power Check voltage at electrical outlet. Correct if none.
Water alarm Check and correct if water alarm happens.
Power supply cord Check voltage at the power cord terminal on Main PCB. Replace
the power cord if none.
Transformer (discharge Check resistance between the two input/output lines on
transformer before testing) transformer. Replace the transformer if either the input/output is
open or the transformer is damaged.
Wire disconnected or Connect wire. Refer to wiring diagram for terminal identification.
connection loose Repair or replace loose terminal.
Main PCB failure Select fan speed and check the voltage on main PCB. Replace
the main PCB if no voltage is present.
Capacitor (discharge capacitor Test capacitor. Replace if not within +/-10% of manufacturer's
before testing) rating. Replace if shorted, open or damaged.
Will not rotate Fan blower hitting scroll. Realign assembly. Check fan motor
bearings. Replace the motor if motor shaft does not rotate.
Fan motor noise Fan blower Replace the fan blower if cracked, out of balance or partially
missing.
Loose screws Tighten screws accordingly.
Worn bearings Replace the motor if knocking sounds continue when running or
loose, or if the motor hums or noise appears to be internal while
running.
Compressor will not run Voltage Check voltage. Call your local utility if not within limits.
while fan motor runs Wiring Check the wire connections. If loose, repair or replace the
terminal. If wires are off, refer to wiring diagram for identification
and replace. Check wire locations. If not per wiring diagram,
correct.
Main PCB failure Check voltage of main PCB. Replace the main PCB if open.
Capacitor (discharge capacitor Check the capacitor. Replace if not within +/-10% of
before testing) manufacturer’s rating. Replace if shorted, open or damaged.
32
11. Troubleshooting
Problem Possible Cause Solution
Compressor will not run Room Temp Sensor Check the temperature setting if not at the coolest (in cooling
while fan motor runs mode) or warmest (in heating mode). Set it if not.
(continued) Compressor Check the compressor for open circuit or ground. If open or
grounded, replace the compressor.
Copper tubing Remove the cabinet and carefully rearrange tubing not to contact
cabinet, compressor, shroud and barrier.
Water tank full Check and pour if the water tank is full.
Water level sensor Check operation. Drain water if full. Replace if tank is empty and
code is set.
Water depth is overloaded in Check and drain the water in the chassis by opening the drainage
chassis hose on the chassis.
Water depth sensing structure Check and replace, or realign if the structure failed.
Air filter Clean or replace if restricted.
Air discharge pipe Realign and assemble if the installation of the air discharging pipe
failed. Replace if damaged.
Unit undersized Determine if the unit is properly sized for the area to be cooled or
heated.
Condenser and Evaporator Clean or replace if restricted.
Circulation in condensing Check whether water damaged the motor or if the water hose is
water blocked.
Fan motor Check the fan capacitor and replace if not within +/-10% of
manufacturer’s rating.
Air flow Clean or remove if any barrier is found to block the inlet/outlet
airflow of the unit.
Less refrigerant Check the tubes for leakage points. Recycle the refrigerant,
correct the leakage points and recharge.
Capillary tube Regulate the capillary tube flow and make the evaporating
temperature appropriate if the evaporator is frosted over. Replace
if blocked. Repair joint if leaking.
Compressor The inlet and outlet valve of the compressor is damaged,
making the low pressure connected with the high pressure.
The refrigerating system cannot produce high pressure and low
pressure. Replace the compressor after checking for this.
No power Check the voltage. Call an electrician if not within the limit.
Wiring Check the terminals. Repair and correct if loose.
Temperature setting Check and adjust the temperature setting.
Compressor Check and replace if the compressor, the overload protector or
wiring is broken.
Overheat fuse failure Check and replace if the fuse is damaged.
Main PCB Check the voltage of the main PCB. Replace the main PCB when
the unit fails in heating mode.
Power supply The input power supply voltage is too low. Call an electrician if not
within limits.
Main PCB Check and replace the main PCB if the compressor relay on the
PCB is shorted or damaged.
Room temperature When the room temperature is too high, the compressor will
protect.
33
11. Troubleshooting
11.2 Troubleshooting Flowcharts
11.2.1 General Troubleshooting Flowchart
Troubleshooting finish
34
11. Troubleshooting
11.2.2 Electrical System Troubleshooting Flowchart
No
Unit not running
YES YES
NOT NOT
No Power source Ambient T1 OK Connect and EVA coil T2 OK
Power source Repair
220V sensor wire off test sensor wire off
OK OK
No Transformer Ambient T1 Replace EVA coil T2 Replace
Fuse damaged
220V sensor damaged ambient T1 sensor damaged EVA
sensor coil T2
sensor
Transformer No Transformer Replace PCB
Check fuse
T1 / 12V damaged 167752T
No YES
35
Manual de Servicio
Unidad Autónoma de
Aire Acondicionado
Modelo: SRCOOL33K
Para preguntas, póngase en contacto con servicio técnico de Tripp Lite al 773.869.1234 o https://www.tripplite.com/support
El contenido de este manual de servicio está sujeto a cambios sin previo aviso.
36
Índice
1. Especificaciones 38 8.12 Valores Predeterminados de la Unidad 60
2. Dimensiones de la Unidad 39 Durante el Encendido Después de
Pérdida de Energía
3. Panel de Control LCD 40
9. Procedimiento Básico de Prueba 61
4. Diagrama del Ciclo del Refrigerante 41 9.1 Compresor Defectuoso 61
5. Diagramas del Cableado y PCB 42 9.1.1 Prueba de Cableado del Compresor 61
5.1 Diagrama de Circuito 42 9.1.2 Prueba de Conexión a Tierra 61
5.2 Diagramas PCBA 43 9.1.3 Verificación de la Eficiencia del Compresor 61
5.2.1 PCBA de Energía 43 9.1.4 Sobrecarga Térmica del Compresor (Interna) 62
5.2.1.1 Esquema del PCBA de Energía 43 9.1.5 Prueba de la Sobrecarga Interna 62
5.2.1.2 PCBA de Energía Crítica 44 para Detectar Falla
Distribución de Componentes
9.2 Reparaciones del Sistema 62
5.2.1.3 Diagrama PCBA Gerber de Energía 45 Sellado de Refrigeración
5.2.2 PCBA de Pantalla y Control 46 9.2.1 Equipo Requerido para Reparaciones 62
5.2.2.1 Pantalla y Control 46 del Sistema de Refrigeración
Esquema del PCBA
9.2.2 Requerimientos de Equipo 62
5.2.2.2 Pantalla y Control Diagrama del 47
PCBA del LCD y de los Botones 9.2.3 Reemplazo del Compresor 63
5.2.2.3 Pantalla y Control 47 9.2.4 Procedimiento Especial en Caso de 63
Diagrama PCBA Gerber que se Queme el Motor del Compresor
5.2.3 Traductor PCBA 48 9.2.5 Carga de Refrigerante 64
5.2.3.1 Esquema del Traductor PCBA 48 9.3 Motor del Ventilador 64
5.2.3.2 Diagrama del Traductor PCBA Gerber 49 9.3.1 Prueba del Motor del Ventilador 64
6. Desensamble de la Unidad 50 9.4 Condensador 65
6.1 Remoción de los Paneles Laterales 50 9.4.1 Prueba del Condensador 65
6.2 Apertura de la Puerta 50 10. Tabla del Sensor de Temperatura 66
6.3 Remoción de la Cubierta del PCB 51 11. Solución de Problemas 67
7. Diagrama Explotado y Lista de Materiales 52 11.1 Tabla de Solución de Problemas 67
8. Función Electrónica 56 11.2 Diagramas de Flujo de Solución de Problemas 69
8.1. Características Principales 56 11.2.1 Diagrama de Flujo General de 69
8.2 Especificaciones Técnicas 56 Solución de Problemas
del Controlador General 11.2.2 Solución de Problemas del Sistema 70
8.3 Definiciones del Sensor 56 Eléctrico Diagrama de Flujo
8.4 Funciones del Control Principal 57
8.4.1 Modo de Ahorro de Energía 57 English 1
8.4.2 Modo Normal 58
8.5 Cambios a la Velocidad del Ventilador 59
(Evaporador)
8.6 Otros Controles (Motores y Bombas de Agua 59
de Auto Evaporación)
8.7 Temporizadores Internos 59
8.8 Controles de Protección 59
8.8.1 Protección de Retraso del Compresor 59
8.8.2 Protección de Descongelado 59
8.8.3 Otros Controles de Protección 59
8.9 Función de Memoria 60
8.10 Comunicación RS232 / UART 60
8.11 Predeterminados de Fábrica 60
37
1. Especificaciones
Modelo SRCOOL33K
Marcas de Placa de Identificación TRIPPLITE
Fuente de Alimentación 1φ, 208V ~ 240V / 60Hz
Capacidad de Enfriamiento 33,000 BTU / h
Consumo de Potencia de Enfriamiento 3,000W
Corriente Nominal de Enfriamiento 12.5A
Enfriamiento SCE 8.24W/W
Datos del Sistema
Tipo de Refrigerante R410A / 2250 g
Presión de Operación 3.0 ~ 3.5 MPa
Eliminación de Humedad (30 ºC HR80%) 80.4 L / Día
Flujo de Aire Interior 29 m³ / min
Nivel de Ruido <60 dBA
Dimensiones y Peso
Dimensiones de la Unidad [An x Al x Pr] 599 x 1991 x 1085 mm [23.6" x 78.4" x 42.7"]
Dimensiones de Embarque [An x Al x Pr] 660 x 2140 x 1140 mm [26" x 84.3" x 44.9"]
Peso Neto / Bruto 253 kg / 305 kg [558 lb / 672 lb]
Detalles del Sistema
Modelo del Compresor 55A842G
Tipo Rotativo
Capacidad 33,330 BTU ±5% / h
Entrada 3315W ±5%
Corriente Especificada (RLA) 14.8A ±5%
Amperes a Rotor Bloqueado (LRA) 79.5A ±5%
Protector Térmico UP14RE5115
Condensador 40 μF / 420V CA
Aceite Refrigerante 660 CC ±10 CC
Tipo de Aceite NMOC Ze-GLES RB68EP (o equivalente)
Motor del Ventilador Motor EVA Motor CON
Modelo FH355AP000 FH355AP000
Entrada 355W / 325W / 215W 345W
Condensador 8µF / 17µF / 25µF 8µF
Velocidad (alta / media / baja) ±50 1600 / 1200 / 1000 RPM 1550 RPM
Evaporador (EVA)
Número de Hileras 3
Paso de Tubería [a] x Paso de Hileras [b] 21 x 19.7 mm [0.83" x 0.78"]
Espaciado de Aletas 18 FPI [Aletas por pulgada]
Tipo de Aleta (Código) Aluminio hidrofílico
Dimensión Tipo de Exterior de la Tubería Tubería de Ranura Interna φ7 mm
Axial [Lg x Al x An] 465 x 630 x 38.1 mm [18.3" x 24.8" x 1.5"]
Número de Circuitos 5
Condensador (CON)
Número de Hileras 4
Paso de Tubería (a) x Paso de Hileras (b) 21 x 19.7 mm [0.83" x 0.78"]
Aleta 18
Tipo de Aleta (Código) Aluminio
Dimensión Tipo de Exterior de la Tubería Tubería de Ranura Interna φ7 mm
Axial [Lg x Al x An] 465 x 924 x 63.5 mm [18.3" x 36.4" x 2.5"]
Número de Circuitos 2
38
2. Dimensiones de la Unidad
1991 mm
[78.4"]
1085 mm
[42.7"]
599 mm
[23.6"]
39
3. Panel de Control LCD
A Botón POWER [Alimentación]: Encendido y apagado; predeterminado en espera.
B Botón MODE [Modo]: Cambia entre el modo de ahorro de energía (ENERGY SAVING) y el modo normal (NORMAL
COOLING).
Nota: El modo de enfriamiento normal es la configuración predeterminada. Cuando la unidad esté apagada, sostenga este botón por
3 segundos para cambiar entre unidades de temperatura Fahrenheit (F) y Celsius (C).
Nota: El parámetro predeterminado es Fahrenheit.
C TEMP+ : Establece la temperatura de enfriamiento en incrementos de +1 °F / °C. Mantenga presionado este botón para
desplazarse hasta el valor más alto.
La temperatura establecida destellará en la pantalla.
D TEMP- : Establece la temperatura de enfriamiento en decrementos de -1 °F / °C. Mantenga presionado este botón para
desplazarse hasta el valor más bajo.
La temperatura establecida destellará en la pantalla.
E SPEED [Velocidad]: Cuando esté en modo de ENERGY SAVING, use este botón para cambiar la velocidad del ventilador
entre automática, alta, media o baja.
HI SPEED, MED SPEED, LOW SPEED o AUTO [Velocidad Alta, Velocidad Media, Velocidad Baja o Automática] se
encenderán en consecuencia.
Nota: AUTO es la configuración predeterminada. Si no hay respuesta durante NORMAL COOLING [Enfriamiento Normal], la velocidad
se establecerá como AUTO.
F LEDs de Estado
G Pantalla LCD
F G
A B C D E
40
4. Diagrama del Ciclo del Refrigerante
El siguiente diagrama describe brevemente los componentes críticos y sus funciones combinadas con el sistema de refrigeración.
Evaporador
2) puerto de servicio x 2
5) Tapón fusible
cámara de Filtro
derivación
Condensador
Líquido refrigerante a alta presión
Gas refrigerante a alta presión Disipación de calor
41
5. Diagramas del Cableado y PCB
PANTALLA PCB
BLANCO BLANCO
NEGRO
VERDE / AMARILLO
SWITCH DE LLENO DE AGUA
VERDE / AMARILLO
CONTRATISTA DE CA
MOTOR DE MOTOR DE
BOMBA DRENAJE DRENAJE
BLANCO
NEGRO
BLANCO
AMARILLO
BLANCO
SOLENOID VALVE
NARANJA
NEGRO
VERDE / AMARILLO
42
5. Diagramas del Cableado y PCB
5.2 Diagramas PCBA
5.2.1 PCBA de Energía
Los siguientes diagramas son para el Nº de parte 167752T de Tripp Lite.
43
5. Diagramas del Cableado y PCB
5.2.1.2 Distribución de Componentes Críticos de PCBA de Energía
Pantalla
Sensor de
Temperatura Interna
Sensor de
Temperatura
Externa
Switch de Lleno de
Agua
Venti-
lador
Superior
Ventilador Inferior
44
5. Diagramas del Cableado y PCB
5.2.1.3 Diagrama PCBA Gerber de Energía
45
5. Diagramas del Cableado y PCB
5.2.2 PCBA de Pantalla y Control
Los siguientes diagramas son para el Nº de parte 167751T de Tripp Lite.
ENFRIAMIENTO
LED1 DE
ALARMA
LED2 DE
DE VELOCIDAD
MODO
DE
ENCENDIDO
DE
ADVERTENCIA
LED3 DE
ADVERTENCIA
46
5. Diagramas del Cableado y PCB
5.2.2.2 Diagrama del LCD y Botones de PCBA de Pantalla y Control
47
5. Diagramas del Cableado y PCB
Traductor PCBA
Los siguientes diagramas son para el Nº de parte 167788T de Tripp Lite.
48
5. Diagramas del Cableado y PCB
5.2.3.2 Diagrama del Traductor PCBA Gerber
49
6. Desensamble de la Unidad
6.1 Remoción de Paneles Laterales
Para quitar un panel lateral de la unidad, presione hacia abajo los pestillos para soltar los seguros. Después jale con cuidado
del panel hacia fuera y arriba hasta retirarlo del chasís de la unidad. Repita para los paneles adicionales.
50
6. Desensamble de la Unidad
6.3 Remoción de la Cubierta del PCB
Para quitar la cubierta del PCB, quite los tornillos como se muestra en el diagrama siguiente.
Tornillos
PCB
51
7. Diagrama Explotado y Lista de Materiales
Note: Las partes con el prefijo RP pueden pedirse directamente en Tripp Lite. Para otras partes, póngase en contacto con el servicio técnico
de Tripp Lite al 773.869.1234 o https://www.tripplite.com/support
53
7. Diagrama Explotado y Lista de Materiales
Índice No. de Parte Descripción Cant. /
Tripp Lite Unidad
76 250008 Puerto de Servicio / Válvula Cerrada 2
77 Instalación del Puerto de Servicio 2
78 250007 Válvula de Derivación (Distribuidor 5 en 1) 1
79 Tubería de Conexión de la Válvula de Derivación 2
80 RP-40036A Sensor de Presión de Refrigerante LPS 1
81 RP-40036B Sensor de Presión de Refrigerante HPS 1
82 250006 Válvulas de Dos Vías - Tubería de Conexión de Salida 1
83 250009 Tubería de Filtro 1
84 Tubería de Conexión de Salida del Condensador 1
85 Línea de Alta Presión de Derivación de Gas Caliente 1
86 250005 Válvulas de 2 Vías 1
87 Tubería de Alta Presión A 1
88 Lámina Metálica - Soporte del Motor de Auto-Evaporación 2
89 RP-500018 Motor de Auto-Evaporación 2
90 Lámina de Retención de Auto-Evaporación 2
91 Volante del Ventilador de Auto-Evaporación 2
92 Lámina Metálica - Partición A 1
93 720375 Filtro PU 2
94 Cerradura de la Puerta Posterior 1
95 Lámina Metálica - Cubierta del Aire Fresco Posterior 1
96 RP-635293 Condensador de Arranque 17µF / Motor del Ventilador del CON - Baja Velocidad 1
97 8205BA Tope de Puerta 4
98 Bisagra de Puerta 2
99 Lámina Metálica - Panel Posterior 1
100 Lámina Metálica - Soporte para Tarima de Madera 2
101 301101 Pie 4
102 905748 Tarima de Madera - Anti-Impacto 1
103 55050B Rampas 2
104 905749 Caja de Cartón para Exportación 1
105 90574A Tapa de Caja de Cartón para Exportación 1
106 Motor del Batidor - Extensión 2
107 Motor de Batidor - Eje 2
108 Cubierta Metálica - Capacitores de Arranque y PCBA de Energía 1
109 250004 Mirilla 1
110 Portafusible 1
111 Tapón Fusible 1
112 73171B Cable de Alimentación con Clavija 1
113 Puerta Lateral Izquierda, Bloqueador de Aire 1
114 Puerta Lateral Derecha, Bloqueador de Aire 1
PAQUETE Etiqueta "Consumo de Energía" 1
PAQUETE 969561 Etiqueta de Advertencia "ShockWatch" [Indicador de Impacto] 1
PAQUETE 969560 Etiqueta de Advertencia "Tip N Tell" [Inclinación o Vuelco] 1
PAQUETE 965631 y 911080 Código de Barras de Caja de Cartón 1
PAQUETE 965631 y 911080 Nº de Serie de la Caja de Cartón 1
PAQUETE 932837 México Anexo de Garantía - Póliza de Garantía en México 1
ETIQUETA 96A2E0 Etiqueta de Identificación / Especificación (Unidad) 1
ETIQUETA 96A23E Esquema / Etiqueta de Circuito (Unidad) 1
ETIQUETA 965631 & 911080 Nº de Serie de la Unidad 1
54
7. Diagrama Explotado y Lista de Materiales
Índice No. de Parte Descripción Cant. /
Tripp Lite Unidad
PAQUETE 933757 Manual del Usuario 1
PAQUETE 93378C Instrucciones de Desempacado 1
PAQUETE 93378B Manual de Instalación 1
ETIQUETA 969547 Etiqueta de Advertencia para la Clavija de Alimentación (Unidad) 1
ETIQUETA 96A2EC ETIQUETA, Advertencia de Apertura de Puesta Posterior 1
ETIQUETA 969448 ETIQUETA, Advertencia de Superficie Caliente 2
ETIQUETA 969446 ETIQUETA, Advertencia de Borde Afilado 4
ETIQUETA 96A2ED ETIQUETA, ID del Puerto de Servicio, HP [Alta Presión] 1
ETIQUETA 96A2ED ETIQUETA, ID del Puerto de Servicio, LP [Baja Presión] 1
ETIQUETA 96A2EF ETIQUETA, Sensor de Presión Alta 1
ETIQUETA 96A2F0 ETIQUETA, Sensor de Presión Baja 1
ETIQUETA 969447 ETIQUETA, Advertencia de Parte Giratoria 4
ETIQUETA 96A2AB ETIQUETA DE INSTRUCCIÓN DE VÁLVULA PARA AGUA 1
PAQUETE 969542 Logotipo de Marca de Embarque TRIPPLITE 2
PAQUETE 96A2E1 ETIQUETA, Íconos de Embarque 2
PAQUETE 102711 Llave para Puerta Posterior 2
ETIQUETA 96A31D P/S, ETIQUETA, Arranque de Prod 1
55
8. Función Electrónica
8.1. Características Principales
• Función: Solo Enfriamiento
• Modos: Ahorro de energía (sin derivación de gas caliente) o Enfriamiento normal (con derivación de gas caliente)
• Rango de configuración de temperatura: Enfriamiento: 17 °C ~ 30 °C [63 °F ~ 86 °F]
• Función de retardo del compresor: 3.5 minutos durante el arranque para autoprotección
• Ventilador del evaporador: 3 niveles—alto, medio o bajo; alterna automáticamente entre alto, medio o bajo de acuerdo
con la demanda
• Ventilador del condensador: Una velocidad, sincronizado con el compresor
• Pantalla de código de error de auto-diagnóstico
• Función de memoria durante apagado (o desconexión)
• Muestra temperatura ambiente y configurada
• Configuración predeterminada de temperatura: Fahrenheit; intercambiable entre Fahrenheit y Celsius
• No suena al oprimir el botón, pero suena la alarma cuando la unidad reporta mal funcionamiento
56
8. Función Electrónica
8.4 Funciones del Control Principal
Los siguientes diagramas muestran las temperaturas de refrigeración en modo normal y modo de ahorro de energía.
ALTA ALTA
ENCENDIDO
ENCENDIDO
CERRADO CERRADO
BAJO APAGADO
BAJO
APAGADO
57
8. Función Electrónica
8.4.2 Modo Normal
Modo de Precisión de Enfriamiento
Caída de la Temperatura Ambiente
Temperatura Velocidad del Válvula
Ambiente Ventilador de 2 vías
ALTA
CERRADO
ENCENDIDO
ABIERTO
BAJO
APAGADO CERRADO
ALTA ALTA
CERRADO ENCENDIDO
ENCENDIDO
CERRADO
ABIERTO
BAJO
APAGADO
BAJO
Nota: Cuando el compresor se detiene, destellará el indicador de ENFRIAMIENTO; de lo contrario está encendido permanentemente. La
temperatura de configuración predeterminada Ts, es 25 °C [77 °F]. El indicador de ºF o ºC se iluminará según la unidad se configure en
grados Fahrenheit o Celsius.
58
8. Función Electrónica
59
8. Función Electrónica
• Cuando el HPS reporta una falla y el compresor continúa funcionando por 10 minutos, la pantalla digital muestra “E7” y
destella el indicador de ALARMA. Después de la solución de problemas, desconecte la unidad y luego reconéctela a la fuente
de alimentación.
• Después de que la unidad funcione por un total de 730 horas (por el temporizador centinela), la pantalla de configuración de
temperatura de 2 dígitos muestra "E8" y el indicador de ADVERTENCIA destella dentro de 5 segundos, pero la unidad sigue
funcionando. Presione y sostenga el botón SPEED por
3 segundos para apagar la alerta y restaurar el temporizador interno a cero.
• Cuando destellen los indicadores de ALARMA o ADVERTENCIA, la alarma sonará 10 veces (cada 0.5 segundos) para alertar al
usuario final.
• Cuando destellan los indicadores de ALERTA, la pantalla de configuración de temperatura de 2 dígitos muestra "dF" o "E8". La
pantalla continuará mostrando el estado del modo correcto, velocidad del ventilador del evaporador, temperatura ambiente o si
T1 está utilizando un termostato externo.
• Cuando destellen los indicadores de ALARMA, excepto cuando la pantalla de configuración de temperatura de 2 dígitos
muestre “E1 / E2 / E3 / E4 / E7”, los otros permanecerán en blanco en la pantalla.
60
9. Procedimiento Básico de Prueba
Retire la tapa de caja de terminales del compresor y desconecte los cables de las terminales. Usando un ohmíometro, revise
la continuidad entre:
- Terminal “C” y “R” - sin continuidad. Bobinas abiertas - reemplace el compresor.
- Terminal “R” y “S” - sin continuidad. Bobinas abiertas - reemplace el compresor.
- Terminal “C” y “S” - sin continuidad. Bobinas abiertas - reemplace el compresor.
61
9. Procedimiento Básico de Prueba
Si la prueba muestra:
• Por debajo de la presión del lado de alta normal,
• Por arriba de la presión del lado de baja normal,
• Bajo diferencial de temperatura a través del serpentín,
Entonces las válvulas del compresor están con falla, reemplace el compresor.
63
9. Procedimiento Básico de Prueba
9.2.5 Carga de Refrigerante
1. La carga de refrigerante es extremadamente crítica. Debe medirse cuidadosamente y tan exacto como sea posible según
la carga en la placa de identificación.
2. El método correcto para cargar el compresor rotativo es introducir líquido refrigerante en el puerto de servicio del lado
de alta presión (HP) del sistema con la unidad apagada. Entonces arranque el compresor e introduzca el balanceo de la
carga, sólo gas, en el puerto de servicio del lado de baja presión (LP).
La introducción de líquido en el lado de baja presión sin el uso de un tubo capilar puede causar daños a la válvula de
descarga del compresor rotativo.
Nota: Todos los compresores inoperantes devueltos deben tener todas las líneas correctamente tapadas con los tapones del compresor de
repuesto.
64
9. Procedimiento Básico de Prueba
9.4 Condensador
Un condensador de funcionamiento se conecta entre las bobinas auxiliares y principales de un motor monofásico de
condensador dividido permanente, como el motor del compresor y del ventilador. Puede usarse un solo condensador para
cada motor o puede usarse para ambos un condensador de especificación doble.
La función principal del condensador es reducir la corriente de línea mientras mejora enormemente las características de
torque de un motor. El condensador también reduce la corriente de línea al motor al mejorar el factor de potencia de la carga.
El lado de línea del condensador está marcado con un punto rojo y está conectado en el lado de línea del circuito
65
10. Tabla del Sensor de Temperatura
R25/50=5K
Temperatura Valor de Voltaje Temperatura Valor de Voltaje Temperatura Valor de Voltaje
Resistencia Resistencia Resistencia
°C °F Rt(K) Vh(V) °C °F Rt(K) Vh(V) °C °F Rt(K) Vh(V)
-20 -4 37.432 0.59 15 59 7.448 2.01 50 122 2.032 3.56
-19 -2 35.558 0.62 16 61 7.149 2.06 51 124 1.965 3.59
-18 0 33.788 0.64 17 63 6.864 2.11 52 126 1.901 3.62
-17 1 32.116 0.67 18 64 6.592 2.16 53 127 1.839 3.66
-16 3 30.537 0.70 19 66 6.332 2.21 54 129 1.779 3.69
-15 5 29.046 0.73 20 68 6.085 2.26 55 131 1.722 3.72
-14 7 27.636 0.77 21 70 5.848 2.30 56 133 1.667 3.75
-13 9 26.303 0.80 22 72 5.621 2.35 57 135 1.614 3.78
-12 10 25.042 0.83 23 73 5.404 2.40 58 136 1.563 3.81
-11 12 23.849 0.87 24 75 5.138 2.47 59 138 1.514 3.84
-10 14 22.715 0.90 25 77 5.000 2.50 60 140 1.467 3.87
-9 16 21.643 0.94 26 79 4.811 2.55 61 142 1.420 3.89
-8 18 20.629 0.98 27 81 4.629 2.60 62 144 1.375 3.92
-7 19 19.669 1.01 28 82 4.456 2.64 63 145 1.332 3.95
-6 21 18.760 1.05 29 84 4.291 2.69 64 147 1.290 3.97
-5 23 17.900 1.09 30 86 4.132 2.74 65 149 1.250 4.00
-4 25 17.086 1.13 31 88 3.980 2.78 66 151 1.212 4.02
-3 27 16.313 1.17 32 90 3.834 2.83 67 153 1.174 4.05
-2 28 15.582 1.21 33 91 3.695 2.88 68 154 1.139 4.07
-1 30 14.888 1.26 34 93 3.561 2.92 69 156 1.104 4.10
0 32 14.229 1.30 35 95 3.433 2.96 70 158 1.071 4.12
1 34 13.600 1.34 36 97 3.310 3.01 71 160 1.040 4.14
2 36 13.002 1.39 37 99 3.193 3.05 72 162 1.009 4.16
3 37 12.435 1.43 38 100 3.080 3.09 73 163 0.979 4.18
4 39 11.896 1.48 39 102 2.972 3.14 74 165 0.950 4.20
5 41 11.385 1.53 40 104 2.869 3.18 75 167 0.922 4.22
6 43 10.899 1.57 41 106 2.769 3.22 76 169 0.895 4.24
7 45 10.436 1.62 42 108 2.673 3.26 77 171 0.869 4.26
8 46 9.997 1.67 43 109 2.581 3.30 78 172 0.844 4.28
9 48 9.579 1.71 44 111 2.493 3.34 79 174 0.819 4.30
10 50 9.181 1.76 45 113 2.408 3.37 80 176 0.796 4.31
11 52 8.800 1.81 46 115 2.327 3.41 81 178 0.773 4.33
12 54 8.436 1.86 47 117 2.248 3.45 82 180 0.751 4.35
13 55 8.091 1.91 48 118 2.173 3.49 83 181 0.730 4.36
14 57 7.761 1.96 49 120 2.101 3.52 84 183 0.709 4.38
Vh=E×R0/(Rt+R0) Notas: E=5V R0=5.0K
66
11. Solución de Problemas
11.1 Tabla de Solución de Problemas
Problema Causa Posible Solución:
No se muestra energía en el Falla de energía Compruebe si la fuente de alimentación está alimentando la unidad.
panel ni falla de cualquiera Compruebe el cable de alimentación y corríjalo si está dañado.
de los botones Transformador (descargue el Verifique la resistencia entre las dos líneas de entrada y salida en el
transformador antes de probarlo) transformador. Reemplace el transformador si el transformador está
dañado o si está abierta la entrada o salida.
Falla en el tablero de la pantalla o Compruebe el voltaje en el tablero de pantalla. Reemplace el tablero de
Falla del control remoto PCB principal pantalla si es +5V. De lo contrario, reemplace la PCB principal.
Falla de la batería Compruebe el voltaje de la batería. Si el voltaje es inferior a 2.3V,
reemplace las baterías.
El motor del ventilador Ciclos en sobrecarga Compruebe el voltaje. Si está fuera de los límites, llame a un electricista.
funciona intermitente Pruebe el condensador Reemplácelo si no está dentro de +/-10% de la
especificación del fabricante.
Compruebe los rodamientos. Si el volante del soplador no gira
libremente, reemplace el motor.
Preste atención a cualquier cambio de velocidad alta a velocidad baja.
El compresor se detiene Refrigerante La cantidad de refrigerante es demasiada, haciendo la carga del
inmediatamente después del compresor demasiado grande. Recicle y recargue el refrigerante después
arranque de comprobar la razón.
Compresor El compresor está bloqueado internamente. Reemplácelo después de
comprobar la razón.
El motor del ventilador no No hay energía Compruebe el voltaje en el tomacorrientes. Si no hay, corríjalo.
funciona Alarma de agua Si hay una alarma de agua, revise y corrija.
Cable de alimentación Verifique el voltaje en la terminal del cable de alimentación en la PCB
principal. Si no hay voltaje, reemplace el cable de alimentación.
Transformador (descargue el Verifique la resistencia entre las dos líneas de entrada y salida en el
transformador antes de probarlo) transformador. Reemplace el transformador si el transformador está
dañado o si está abierta la entrada o salida.
Cable desconectado o conexión Conecte el cable. Para identificación de la terminal, consulte el diagrama
floja de cableado. Repare o reemplace la terminal floja.
Falla de PCB principal Seleccione la velocidad del ventilador y revise el voltaje en la PCB
principal. Si no hay voltaje, reemplace la PCB principal
Condensador (descargue el Pruebe el condensador Reemplácelo si no está dentro de +/-10% de
condensador antes de probarlo) la especificación del fabricante. Reemplácelo si está en corto, abierto o
dañado.
No gira El soplador del ventilador golpea al desplazamiento Realinee el conjunto.
Compruebe los rodamientos del motor del ventilador. Si la flecha del
motor no gira, reemplace el motor.
Ruido en motor del Soplador del ventilador Reemplace el soplador de ventilador si falta parcialmente o está
ventilador agrietado o fuera de balance.
Tornillos flojos Apriete los tornillos en consecuencia.
Rodamientos gastados Reemplace el motor si continúan sonando golpeteos cuando funciona o
está flojo o si el motor zumba o el ruido parece ser interno mientras está
funcionando.
El compresor no funciona Voltaje Compruebe el voltaje. Si no está dentro de los límites, llame a su
mientras el motor del compañía de electricidad local.
ventilador funciona Cableado Compruebe las conexiones del cableado. Si están flojas, repare o
reemplace la terminal. Si los cables están desconectados, consulte el
diagrama de cableado para la identificación y reemplazo. Compruebe las
ubicaciones de cableado. Si no corresponden al diagrama, corríjalo.
Falla de PCB principal Compruebe el voltaje de la PCB principal. Si está abierta, reemplace la
PCB principal.
Condensador (descargue el Compruebe el condensador. Reemplácelo si no está dentro de +/-10%
condensador antes de probarlo) de la especificación del fabricante. Reemplácelo si está en corto, abierto
o dañado.
67
11. Solución de Problemas
Problema Causa Posible Solución:
El compresor no funciona Sensor de Temperatura Compruebe que el ajuste de temperatura no esté en el más frío (en
mientras el motor del Ambiente modo de enfriamiento) o más caliente (en modo de calefacción). Si
ventilador funciona no es así, calíbrelo.
(continuación) Compresor Compruebe el compresor para detectar un circuito abierto o a
tierra. Si está abierto o a tierra, reemplace el compresor.
Tubería de Cobre Retire el gabinete y cuidadosamente reacomode la tubería no para
que no haga contacto con el gabinete, compresor, guarda y barrera.
Tanque de agua lleno Compruebe y vacíe si el tanque de agua está lleno.
Sensor de nivel de agua Compruebe la operación. Si está lleno, drene el agua. Si el tanque
está vacío y el código activo, reemplácelo.
La profundidad del agua está Revise y drene el agua en el bastidor abriendo la manguera de
sobrecargada en el gabinete. drenaje en el bastidor.
Estructura de detección de Si falló la estructura, compruebe y reemplace o realinee.
profundidad del agua
Filtro de Aire Si está restringido, límpielo o reemplácelo.
Tubería de descarga de aire Si falló la instalación del tubo de descarga de aire, vuelva a
alinearlo y ensamblarlo. Si está dañado, reemplácelo.
Unidad de tamaño insuficiente Determine si la unidad está dimensionada correctamente para el
área a ser enfriada o calentada.
Condensador y Evaporador Si está restringido, límpielo o reemplácelo.
Circulación en agua de Compruebe si el agua dañó el motor o si está bloqueada la
condensación manguera de agua.
Motor del ventilador Revise el condensador del ventilador y reemplácelo si no está
dentro de +/-10% de la especificación del fabricante.
Flujo de aire Si encuentra cualquier barrera que bloquee el flujo de aire de
entrada/salida de la unidad, límpiela o elimínela.
Menos refrigerante Revise las tuberías para detectar puntos de fuga. Recicle el
refrigerante, corrija los puntos de fuga y recargue.
Tubo capilar Si el evaporador está congelado, regule el flujo del tubo capilar
y haga que la temperatura de evaporación sea apropiada.
Reemplácelo si está bloqueado. Si hay fuga, reemplace la junta.
Compresor Está dañada la válvula de entrada y salida del compresor, haciendo
que la presión baja esté conectada con la presión alta. El sistema
de refrigeración no puede producir alta presión y baja presión.
Reemplace el compresor después de comprobar si se da esto.
No hay energía Compruebe el voltaje. Si está fuera del límite, llame a un
electricista.
Cableado Revise las terminales. Si están flojas, repárelas y corríjalas.
Configuración de la Revise y ajuste el ajuste de la temperatura.
temperatura
Compresor Revise y reemplace si el compresor, el protector de sobrecarga o el
cableado están rotos.
Falla del fusible de Revise y reemplace si el fusible está dañado.
sobrecalentamiento
PCB Principal Verifique el voltaje de la PCB principal. Cuando la unidad falle en
modo de calefacción, reemplace la PCB principal.
Fuente de alimentación El voltaje de la fuente de alimentación es demasiado bajo. Si está
fuera de los límites, llame a un electricista.
PCB Principal Verifique y reemplace la PCB principal si el relevador del compresor
en la PCB está en corto circuito o dañado.
Temperatura ambiente Cuando la temperatura del cuarto sea demasiado alta, el
compresor protegerá.
68
11. Solución de Problemas
11.2 Diagramas de Flujo de Solución de Problemas
11.2.1 Diagrama de Flujo General de Solución de Problemas
No
Problema de Problema del Lleno de agua después SI Bomba de agua
con bip
69
11. Solución de Problemas
11.2.2 Diagrama de Flujo para Solución de Problemas del Sistema Eléctrico
No
La unidad no funciona
SI SI
NO NO
Fuente de ali- No Fuente de ali- Cable del sensor OK Conecte y Cable de sensor T2 del OK Repa-
mentación mentación 220V de ambiente T1 apagado pruebe serpentín del EVA apagado ración
OK OK
No Transformador de Sensor de Reemplace Sensor T2 de serpentín Reemplace
Fusible dañado el sensor
220V ambiente T1 dañado el sensor T1 de EVA dañado
T2 del
de ambiente serpentín
del EVA
Transformador No Transformador Reemplace
Revise el fusible
T1 / 12V dañado PCB 167752T
No SI
SI Reemplace PCB
PCB dañado OK
167752T
No
Solución de problemas de
cableado defectuoso
70
71
1111 W. 35th Street, Chicago, IL 60609 EE UU • www.tripplite.com/support
72 18-06-003 93-3868_RevA