The document describes alarm codes and faults that may occur on a Pulsar MX UPS. There are two types of faults: internal faults related to components like the power module, battery, or frame; and environmental faults related to issues like missing modules, overload conditions, or incompatible components. Each fault has a unique code and message displayed on the UPS, and most are stored in an alarm history for service technicians to address.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
226 views4 pages
9135 Alarm Codes
The document describes alarm codes and faults that may occur on a Pulsar MX UPS. There are two types of faults: internal faults related to components like the power module, battery, or frame; and environmental faults related to issues like missing modules, overload conditions, or incompatible components. Each fault has a unique code and message displayed on the UPS, and most are stored in an alarm history for service technicians to address.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4
About alarm codes here is how it works on current Pulsar MX:
There are two kinds of fault:
Æ Internal faults - power module fault (replacement of the power module needed) - battery fault (replacement of the battery module needed) - frame fault (replacement of all the UPS needed) Æ Environment faults
Æ Internal fault :
Stored into Alarm
Title Code Fault display history CHARGER FAULT Internal SERVICE REQUIRED CHARGER FAULT 500 YES fault ALARM 500 ( ) 3s TO RESET FAN FAULT SERVICE REQUIRED FAN FAULT 007 YES ALARM 007 ( ) 3s TO RESET UPS TEMPERAT FAULT UPS TEMPERAT 004 SERVICE REQUIRED YES FAULT ALARM 004 ( ) 3s TO RESET INVERT FUSE BLOWN INVERT FUSE BLOWN 701 SERVICE REQUIRED YES ALARM 701 ( ) 3s TO RESET NORM AC FUSE BLOWN NORM AC FUSE 100 SERVICE REQUIRED YES BLOWN ALARM 100 ( ) 3s TO RESET RECTIFIER FAULT SERVICE REQUIRED RECTIFIER FAULT 305 YES ALARM 305 ( ) 3s TO RESET DCBUS x TOO xxxx DC BUS +/- TOO SERVICE REQUIRED 300 YES HIGH/LOW ALARM 300 ( ) 3s TO RESET INVERTER FAULT SERVICE REQUIRED INVERTER FAULT 704 YES ALARM 704 ( ) 3s TO RESET BATTERY FAULT SERVICE REQUIRED BATTERY FAULT 607 YES ALARM 607 ( ) 3s TO RESET AUTO BYPASS FAULT AUTO BYPASS FAULT 207 SERVICE REQUIRED YES ALARM 207 ( ) 3s TO RESET DC POWER SUP FAULT DC POWER SUP 00A SERVICE REQUIRED YES FAULT ALARM 00A ( ) 3s TO RESET INTERNAL COM INTERNAL COM FAULT FAULT 005 SERVICE REQUIRED YES (FRAME FAULT) ALARM 005 ( ) 3s TO RESET INTERNAL COM INTERNAL COM FAULT FAULT 00E SERVICE REQUIRED YES (POWER MODULE ALARM 00E FAULT) ( ) 3s TO RESET COM FAULT BETW UPS COM FAULT BETW 006 SERVICE REQUIRED YES UPS ALARM 006 ( ) 3s TO RESET Æ Environment fault :
Stored into Alarm
Title Code Fault display history NO POWER MODULE Environment INSERT MODULE NO POWER MODULE 703 YES fault ALARM 703 ------------------------------- NO BATTERY MODULE NO BATTERY INSERT MODULE 60C YES MODULE ALARM 60C ------------------------------- OUTPUT OVERLOAD REDUCE THE LOAD OUTPUT OVERLOAD 808 NO ALARM 808 ------------------------------- INV THERM OVERLOAD INV THERM 70A ALARM 70A YES OVERLOAD ------------------------------- ( ) 3s TO RESET INVERT LIMITATION ------------------------------- INVERT LIMITATION 700 YES ALARM 700 ( ) 3s TO RESET BYPASS AC FREQ NOK BYPASS AC FREQ 206 CHECK BYPASS AC NO NOK ALARM 206 ------------------------------- FREE RUNNING MODE CHECK BYPASS AC FREE RUNNING MODE 709 NO ALARM 709 ------------------------------- BYPASS AC VOLT NOK BYPASS AC VOLT CHECK BYPASS AC 209 NO NOK ALARM 209 ------------------------------- REDUNDANCY LOSS REDUCE THE LOAD REDUNDANCY LOSS 00B NO ALARM 00B ------------------------------- I/O BAD CONNECTION CHECK AC WIRING I/O BAD CONNECTION 00C YES ALARM 00C ------------------------------- NO BATTERY CHECK CONNECTION NO BATTERY 60D YES ALARM 60D ------------------------------- OPERATION LIMITS B02 : battery transfer B03 : bypass ac ALARM OPERATION nok LIMITS xxx NO B04 : UPS SERVICE REQUIRED overload www.mgeups.com/lcm B05 : Load level B06 : Ambient temp POWER MODULE POWER MODULE NOT COMPATIBLE 70C NO NOT COMPATIBLE ALARM 70C ------------------------------- UPS1/UPS2 UPS1/UPS2 NOT COMPATIBLE 00F NO NOT COMPATIBLE ALARM 00F ------------------------------- SOFT FRAME/POWER SOFT FRAME/POWER NOT COMPATIBLE 010 NO NOT COMPATIBLE ALARM 010 -------------------------------