IntelligentValve Desigo
IntelligentValve Desigo
2
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
About this document
Revision history
Referenced documents
Target audience
3
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Cyber security disclaimer
Siemens provides a portfolio of products, solutions, systems and services that includes
security functions that support the secure operation of plants, systems, machines and
networks. In the field of Building Technologies, this includes building automation and control,
fire safety, security management as well as physical security systems.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art security
concept. Siemens’ portfolio only forms one element of such a concept.
You are responsible for preventing unauthorized access to your plants, systems, machines
and networks which should only be connected to an enterprise network or the internet if and
to the extent such a connection is necessary and only when appropriate security measures
(e.g. firewalls and/or network segmentation) are in place. Additionally, Siemens’ guidance on
appropriate security measures should be taken into account. For additional information,
please contact your Siemens sales representative or visit
https://www.siemens.com/global/en/home/company/topic-areas/future-of-
manufacturing/industrial-security.html.
Siemens’ portfolio undergoes continuous development to make it more secure. Siemens
strongly recommends that updates are applied as soon as they are available and that the
latest versions are used. Use of versions that are no longer supported, and failure to apply
the latest updates may increase your exposure to cyber threats. Siemens strongly
recommends to comply with security advisories on the latest security threats, patches and
other related measures, published, among others, under
https://www.siemens.com/cert/en/cert-security-advisories.htm.
Term Explanation
ABT Go Desigo ABT (Automation Building Tool) application to commission Desigo TRA
(Total Room Automation) and devices such as the Intelligent Valve, available in
iOS and Android versions
ABT Site Desigo ABT to engineer and commission Desigo TRA and devices such as the
Intelligent Valve
CFC Classic editor Graphic tool for creating CFC (Continuous Flow Chart) plans. Enables you to
create and change programs.
Desigo Siemens building automation and control system
Desigo CC Siemens building platform
Network Configurator XWP tool to define the network topology
Point Configurator XWP tool to define functions of an automation station
Project Manager XWP tool to manage Desigo projects
XWP XWORKS plus, toolset to engineer and commission Desigo PX system
components
4
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Introduction
The Intelligent Valve EVG.. and EVF.. can be integrated into the Desigo System via BACnet
capable PX Primary Controllers. The integration into the PX primary controller is facilitated
with a prepared solution (compound), specific for EVG.. and EVF.. devices. Once integrated
into the PX Primary Controller, integration into Desigo CC is easily possible with Desigo
CC’s proven Desigo PX System Integration and pre-engineered graphics in the Desigo CC
Graphics Library.
5
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Engineering and commissioning
Overview of workflows
This section introduces the reader to the engineering and commissioning workflows of the
Intelligent Valve EVG../EVF.. within the described Desigo environment.
In general, one can distinguish between two basic workflows.
(XWP) (ABT Site) (XWP) (ABT Go) (ABT Site) (XWP) (Desigo CC)
6
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Intelligent Valve Integration Workflow 1: hydronic balancing with ABT Site
This section provides step-by-step instructions for workflow 1.
# Description Tool
1.1 Create project. Project Manager
7
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tool
1.3 Create network. Network Configurator
8
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Engineer Intelligent Valve in ABT Site
# Description Tab
2.1 Define building hierarchy. Building
This building hierarchy is only relevant for ABT Site and will not be visible in the management station later.
9
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
2.4 Import desired application templates by executing the provided installer file. The installation instructions Configuration
will guide you through the process.
The installation process will close ABT Site. Re-open the tool once the installation is completed.
10
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
2.5 Add desired application templates to your project. Configuration
For this workflow, the application templates VLV2V101 and VLV2V111 are recommended.
● Select VLV2V101 if you plan to control your Intelligent Valve via an analog signal.
● Select VLV2V111 if you plan to control your Intelligent Valve via BACnet.
2.6 Adapt I/O configuration of application templates if required. Configuration
11
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
2.8 Once the application templates are defined, select Add device…. Building
2.10 Easily instantiate multiple devices at once. Define IP addresses and BACnet instance numbers. Building
12
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
2.11 Adjust instance parameters where required. Also set the parameters for hydronic balancing (VflMaxRel, Building
EnVflMin, VflMinRel).
13
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Engineer PX Primary Controller in XWP
# Description Tool
3.1 Instantiate automation station. Project Manager
14
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tool
3.4 Check complete network, including any previously defined Intelligent Valve. Network Configurator
This is the building hierarchy that will be imported into Desigo CC later.
15
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tool
3.7 Configure automation station solution, making use of Intelligent Valve compound with prepared alarming Point Configurator
and trending.
16
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tool
3.8 Generate CFC data. Point Configurator
3.9 Perform BACnet referencing to Intelligent Valve via prepared compound. CFC
17
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Commission and balance Intelligent Valve with ABT Site
NOTICE
At this point, make sure your devices are installed properly. Check the mounting
instructions [7] for further information.
# Description Tab
4.1 Set up network connection and start network discovery. Startup
18
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
4.2.2 ● Possibility 2 Startup
– Send a wink from the tool and make the corresponding device blink red (2 s on, followed by
on/off flickering)
Action in tool:
Reaction on device:
Reaction in tool:
19
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
4.3 Assign correct devices individually. Startup
20
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Commission PX Primary Controller with XWP
The commissioning workflow of the primary automation station is the same as with any PX
Primary Controller. For further information, please consult the XWP Online Help [2].
21
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Mode
6.1.2 Online Engineering
Start network discovery in Desigo CC and import PX Primary Controller. (Desigo CC)
22
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Mode
6.2 Engineer graphics with pre-engineered device graphics from Desigo CC Library. [5] Engineering
(Desigo CC)
23
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Intelligent Valve Integration Workflow 2: hydronic balancing with ABT Go
This section provides step-by-step instructions for workflow 2.
# Description Tool
1.1 Create project. Project Manager
24
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tool
1.3 Create network. Network Configurator
25
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Engineer Intelligent Valve in ABT Site
# Description Tab
2.1 Define building hierarchy. Building
This building hierarchy is only relevant for ABT Site and will not be visible in the management station later.
26
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
2.4 Import desired application templates by executing the provided installer file. The installation instructions Configuration
will guide you through the process.
The installation process will close ABT Site. Re-open the tool once the installation is completed.
27
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
2.5 Add desired application templates to your project. Configuration
In this workflow, the balancing is done by an external company. For this reason, it is recommended to use
a different set of application templates than in workflow 1, step 2.5.
For this workflow, the application templates VLV2V102 and VLV2V112 are recommended.
● Select VLV2V102 if you plan to control your Intelligent Valve via an analog signal.
● Select VLV2V112 if you plan to control your Intelligent Valve via BACnet.
2.6 Adapt I/O configuration of application templates if required. Configuration
28
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
2.7 Adapt default values of application templates if required. Configuration
2.8 Once the application templates are defined, select Add device…. Building
29
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
2.10 Easily instantiate multiple devices at once. Define IP addresses and BACnet instance numbers. Building
Since hydronic balancing is done by an external company in this workflow, its parameters (VflMaxRel,
EnVflMin, VflMinRel) are not set in this step.
Switch to XWP by closing ABT Site.
30
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Engineer PX Primary Controller in XWP
# Description Tool
3.1 Instantiate automation station. Project Manager
31
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tool
3.4 Check complete network, including any previously defined Intelligent Valve. Network Configurator
This is the building hierarchy that will be imported into Desigo CC later.
32
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tool
3.7 Configure automation station solution, making use of Intelligent Valve compound with prepared alarming Point Configurator
and trending.
33
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tool
3.8 Generate CFC data. Point Configurator
3.9 Perform BACnet referencing to Intelligent Valve via prepared compound. CFC
34
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Commission Intelligent Valve with ABT Site
NOTICE
At this point, make sure your devices are installed properly. Check the mounting
instructions [7] for further information.
# Description Tab
5.1 Set up network connection and start network discovery. Startup
35
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
5.2.2 ● Possibility 2 Startup
– Send a wink from the tool and make the corresponding device blink red (2 s on, followed by
on/off flickering)
Action in tool:
Reaction on device:
Reaction in tool:
36
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
5.3 Assign correct devices individually. Startup
37
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Commission PX Primary Controller with XWP
The commissioning workflow of the primary automation station is the same as with any PX
Primary Controller. For further information, please consult the XWP Online Help [2].
38
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Mode
7.1.2 Online Engineering
Start network discovery in Desigo CC and import PX Primary Controller. (Desigo CC)
39
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Mode
7.2 Engineer graphics with pre-engineered device graphics from Desigo CC Library. [5] Engineering
(Desigo CC)
40
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Maintenance
Overview of workflow
This section gives an overview of the steps required to update firmware and application of
the Intelligent Valve devices within the described Desigo environment.
This workflow is particularly suited to new projects, in which the Intelligent Valve devices
have not yet been engineered and commissioned.
Offline Online
(ABT Site)
41
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Software Update Workflow: New Project
This section provides step-by-step instructions on how to update firmware and application in
a new project in ABT Site.
# Description Tab
1 Import desired new application templates by executing the provided installer file. The installation Configuration
instructions will guide you through the process.
The installation process will close ABT Site. Re-open the tool once the installation is completed.
Engineer valves
Engineer the valves in ABT Site as usual, following the steps described in Engineer
Intelligent Valve in ABT Site [➙ 9] and Commission and balance Intelligent Valve with ABT
Site [➙ 18].
42
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Update firmware
# Description Tab
3.1 Set up network connection and start network discovery. Startup
3.2 Select correct devices from list and assign individually. Startup
43
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
# Description Tab
3.3 Perform firmware updates one by one. Startup
Firmware on the device and new application templates in ABT Site must be of the same version set.
44
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Commission valves
# Description Tab
4.1 Download application configuration. Startup
45
Siemens A6V11572317_en--_b
Smart Information 2020-04-06
Software and firmware versions