Unit 3
Unit 3
• Va2= – Ia2Z2
• Network and Zero-Sequence Impedance: The synchronous machine
does not induce any zero-sequence voltage. Three mmfs are
generated by zero-sequence currents flowing through the stator
windings; these mmfs are in time phase but are 120° apart in space.
Hence, zero-sequence currents yield no consequent air gap field.
Because of this, only zero-sequence currents cause leaking reactance
in the rotor windings.
• As the reactor's impedance Zn represents the total of the zero sequence
currents flowing through its three phases, the voltage drop it causes will
be 3 Ia0 Zn.
• Now, the voltage drop of the zero sequence from the synchronous
machine's terminal a to ground is equal to 3 Ia0 Zn + Ia0 Zg0,
• where ‘Zg0‘ is the generator's zero-sequence impedance. As ‘Ia0‘ is a zero-
sequence current, the total zero-sequence impedance is -Z0 = 3 Zn + Zg0
• With the same applied positive- and negative- sequence voltages, as well as the same speed and rotational direction, the stator
currents rise as a result, and as a result, the motor gives a lower impedance to the negative- than to the positive-sequence currents
(i.e., Z2 > Z1).
• The corresponding circuit may be thought of as just having magnetising and leakage impedances since zero-sequence stator currents
do not result in a rotating field. But, in actuality, the zero-sequence analysis of induction machines takes the presence of third-
harmonic currents and fluxes into significant account.
• Sequence Impedances of Transmission Lines:
• The positive and negative sequence impedances of a transmission line are independent of
phase sequence and equal because a fully transposed three-phase line is perfectly
symmetrical. Both positive and negative sequences can use the "Elements of Power
Systems" equation for inductive reactance. The currents in each phase of a transmission
line that exclusively carry zero-sequence currents are identical in size and phase.
• These currents partially return through the earth and partially through the above ground
wires. In contrast to the magnetic field produced by the passage of positive or negative
sequence currents, the magnetic field produced by the flow of zero-sequence currents via
transmission lines, ground wires, and the ground is extremely different. The reactance of
the zero-sequence impedance, in particular, is around.
• Sequence Impedances and Networks of Transformers:
• A transformer's leakage reactance is equal to its positive-sequence
series impedance (the resistance of the winding is usually small in
comparison to the leakage reactance). Transformers are static
devices, thus their positive and negative-sequence impedances are
the same because, as long as the applied voltages are balanced,
impedance is independent of phase order.
• Thus, for a transformer –
• Z1 = Z2 = Zleakage
• In terms of zero-sequence impedance, the situation with 3-phase transformers is
more complicated due to the potential for various connections. A transformer
offers a zero-sequence impedance that is slightly different from positive-sequence
impedance but the difference is so small that zero-sequence impedance can be
assumed to be equal to positive- or negative-sequence impedance under the
assumption that such transformer connections allow zero-sequence currents to
flow on both sides.
• However, the zero- sequence currents can flow through the winding connected
in star only if the star point is grounded. Moreover, the zero- sequence currents
cannot flow in the windings if the star point is isolated. No zero-sequence
currents can flow in the lines connected to a delta-connected winding as no
return path is available for these zero-sequence currents. Zero-sequence currents
can, however, flow through the delta-connected windings themselves if any zero
sequence voltages are induced in delta.
• This fact is illustrated in Fig. 3.13. These various conditions can be taken into
account by the use of general circuit shown in Fig. 3.14. Z0 is the zero-sequence
impedance of windings of the transformer. There are two series and two shunt
switches-one series and one shunt switch for each side. The series switch of a
particular side is closed if it is star grounded and the shunt switch is closed if
that side is delta connected, otherwise they remain left open.
•
Sequence impedances and sequence networks:
Positive sequence network:
Figure is the positive sequence network for three phase system and its equivalent for single phase system.
Here, Va1, Ia1, Z1 are voltage, current and impedance of positive sequence network
respectively, Ea is voltage magnitude in phase.
Negative sequence network:
Figure is the negative sequence network for three phase system and its equivalent
for single phase system.
• Va2, Ia2, Z2
Va2 =- Z2 Ia2
Here, Va2, Ia2, Z2 are voltage, current and impedance of positive sequence network
respectively.
• Zero sequence network:
• Figure is the zero sequence networks for three phase system and its equivalent for single
phase system.
By analyzing this sequence network, the
zero sequence voltage can be expressed as,
Here, Va0, Ia0, Z0 are voltage, current and impedance of zero sequence network respectively
and Zn is neutral impedance.
The relation between three sequence impedances is Z0 < Z2 <Z1 . These symmetrical components play
a significant role in the fault calculations and analysis of the power system networks.
EXAMPL 1:Solve the (+), (-) and (0) sequence networks of the above power
system.
Example 1: For the power system shown in the SLD, draw the sequence
networks