Electrical Protection Lecture 5 - 20211019
Electrical Protection Lecture 5 - 20211019
1
FUNDAMENTALS OF DIFFERENTIAL PROTECTION
Lenz’s law
An induced emf always gives
rise to a current whose magnetic
flux opposes the original change
in magnetic flux responsible for
inducing that emf.
2
FUNDAMENTALS OF DIFFERENTIAL PROTECTION
DOT MARKINGS
When current enters a dot marking
on the primary side of a
transformer coil, the current will
leave the similar dot marking on the
secondary side.
3
PRINCIPLE OF DIFFERENTIAL PROTECTION
𝐈𝐋 𝐈𝑳
𝑰𝒔𝒑𝒊𝒍𝒍 = − =𝟎
𝒏 𝒏
Differential scheme remains stable during normal operating conditions.
6
DIFFERENTIAL PROTECTION SCHEME BEHAVIOUR DURING
EXTERNAL FAULT
𝐈𝐟,𝐞𝐱𝐭 𝐈𝐟,𝐞𝐱𝐭
𝑰𝒔𝒑𝒊𝒍𝒍 = − =𝟎
𝒏 𝒏
Differential scheme remains stable during external faults or
through faults. 7
DIFFERENTIAL PROTECTION SCHEME BEHAVIOUR DURING
INTERNAL FAULT
𝑰𝟏 = 𝑰𝟐 + 𝑰𝒇,𝒊𝒏𝒕
𝑰𝟐 + 𝑰𝒇,𝒊𝒏𝒕 𝑰𝟐 𝑰𝒇,𝒊𝒏𝒕
𝑰𝒔𝒑𝒊𝒍𝒍 = − =
𝒏 𝒏 𝒏
I f , int
Assuming that is more than the pick-up value of the
n
over-current relay, both circuit breakers will be tripped.
8
DIFFERENTIAL PROTECTION SCHEME BEHAVIOUR DURING
INTERNAL FAULT
𝑰𝒇,𝒊𝒏𝒕 = 𝑰𝟏 + 𝑰𝟐
𝑰𝟏 𝑰𝟐 𝑰𝟏 + 𝑰𝟐 𝑰𝒇,𝒊𝒏𝒕
𝑰𝒔𝒑𝒊𝒍𝒍 = + = =
𝒏 𝒏 𝒏 𝒏
Assuming that the spill current is greater than Ips, the plug setting of the
O/C relay, the relay will operate and trip the circuit breakers on either side
of the protected equipment.
9
PROTECTION CHALLENGES AND ERRORS IN
DIFFERENTIAL PROTECTION SCHEME
Pilot wire lengths: The C.T’s and electrical equipment to be
protected are located at different locations. Normally, it is not
possible to connect relay coil to the equipotential points.
10
PROTECTION CHALLENGES AND ERRORS IN DIFFERENTIAL
PROTECTION SCHEME
CT errors during short circuit: The CT’s may have almost equal
turns ratios during normal operating conditions. But during short
circuit faults currents, the primary currents are extremely large.
The turns ratio errors of CT’s on either sides differ during these
conditions due to:
(a). Inherent difference in CT characteristic arising out of
difference in magnetic circuit, saturation conditions etc.
(b). Unequal d.c components in the short circuit currents.
11
PROTECTION CHALLENGES AND ERRORS IN DIFFERENTIAL
PROTECTION SCHEME
Saturation of CT magnetic circuits during short circuit conditions
and unequal d.c components in the short circuit currents: Due to
these conditions, the relay may operate even for external faults.
𝑰𝒑
𝒏 𝑰𝒑
𝒏
𝑰𝒑 𝑰𝒑
− 𝑰𝟎𝟏 − 𝑰𝟎𝟐
𝒏 𝑰𝒔𝒑𝒊𝒍𝒍 = 𝑰𝟎𝟐 − 𝑰𝟎𝟏 𝒏
𝑰𝒑 𝑰𝒑
𝑰𝒔𝒑𝒊𝒍𝒍 = − 𝑰 𝟎𝟏 − − 𝑰 𝟎𝟐
𝒏 𝒏
Simple differential Scheme with CT Equivalent Circuit. 14
SIMPLE DIFFERENTIAL PROTECTION RELAY BEHAVIOUR
DURING EXTERNAL FAULT
Loss of
stability
Through fault
stability limit
The higher the stability ratio, the better is the ability of the system to
discriminate between internal and external faults (reliability performance
indicator: Dependable and Secure respectively).
The stability ratio can be improved by improving the match between the
two CTs.
To overcome these difficulties and/or challenges, the “percentage differential
relay” or “Biased differential relay” is used.
17
PERCENTAGE DIFFERENTIAL PROTECTION SCHEME
The simple differential relay can be made more stable if one can
develop a restraining torque proportional to the through fault
current, the operating torque still proportional to the spill current.
NR I1 + I 2
I1 − I 2 = + I0
N0 2
I f , max,ext
Stability ratio =
I f , min,int
REFERENCE
21
TRANSFORMER PROTECTION
Transformers are static devices, totally enclosed and generally oil
immersed. Therefore, chances of faults occurring on them are very
rare. However, the consequences of even a rare fault may be very
serious unless the transformer is quickly disconnected from the
system.
22
COMMON TRANSFORMER FAULTS
• Open circuits
• Overheating
• Winding short circuits
e.g. Earth faults
Phase-phase
Inter-turn
Therefore, transformer protection is absolutely
necessary for internal and external faults.
23
PROTECTION SCHEMES FOR TRANSFORMERS
24
TRANSFORMER DIFFERENTIAL PROTECTION SCHEME
Single-fed-system
Assuming that the spill current is greater than the plug setting of
the O/C relay, the relay will operate and trip the circuit breakers
on either side of the protected transformer. 28
DIFFERENTIAL PROTECTION SCHEME
Double-fed-system
Assuming that the spill current is greater than the plug setting of
the O/C relay, the relay will operate and trip the circuit breakers
on either side of the protected transformer. 29
INSTALLATION OF PROTECTION TRANSFORMERS
32
TRANSFORMER CONNECTIONS
33
TRANSFORMER CONNECTIONS
34
TRANSFORMER CONNECTIONS
35
TRANSFORMER CONNECTIONS
36
TRANSFORMER CONNECTIONS
37
TRANSFORMER CONNECTIONS
38
TRANSFORMER CONNECTIONS
39
VECTOR GROUP OF 3-PHASE TRANSFORMER
The secondary voltages of a 3-phase transformer may undergo a
phase shift of either +30° leading or -30° lagging or 0° i.e, no phase
shift or 180° reversal with respective line-to-neutral voltages or
phase-to-neutral voltages.
41
VECTOR GROUP OF 3-PHASE TRANSFORMER
The angle between two consecutive numbers on the clock is 30°.
43
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 1 : Dy11 Transformer
Step 1: Draw Phase-Neutral Voltage Vectors
A
a
C B
c 44
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 1 : Dy11 Transformer
Step 2: Draw Delta Connection
A
a
C B
c 45
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 1 : Dy11 Transformer
Step 3: Draw A Phase Windings
A
a
A
b
C B
c 46
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 1 : Dy11 Transformer
Step 4: Complete Connections
A
a
C A
b
C B B
c 47
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 1 : Dy11 Transformer
Step 4: Complete Connections
ILA= IPA-IPC A a
Ipa = ILa
IPA
IPC
C A
b
C B B
c 48
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 1 : Dy11 Transformer
Step 4: Complete Connections
A
a
C A
b
C B B
c
49
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 2: Yd1 Transformer
50
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 3: Yd11 Transformer
51
VECTOR GROUP OF 3-PHASE TRANSFORMER
52
VECTOR GROUP OF 3-PHASE TRANSFORMER
Dy1 Transformer
53
VECTOR GROUP OF 3-PHASE TRANSFORMER
54
VECTOR GROUP OF 3-PHASE TRANSFORMER
Dy5 Transformer
55
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 2 : Dy5 Transformer
A
c
C A
b
B
C B
a
56
VECTOR GROUP OF 3-PHASE TRANSFORMER
57
VECTOR GROUP OF 3-PHASE TRANSFORMER
Dy7 Transformer
58
VECTOR GROUP OF 3-PHASE TRANSFORMER
Example 2 : Dy7 Transformer
A
b
A B c
C
B
C
a
59
VECTOR GROUP OF 3-PHASE TRANSFORMER
60
VECTOR GROUP OF 3-PHASE TRANSFORMER
Dy1 Transformer
61
VECTOR GROUP OF 3-PHASE TRANSFORMER
62
VECTOR GROUP OF 3-PHASE TRANSFORMER
63
FUNDAMENTALS OF DIFFERENTIAL PROTECTION
REFERENCE
Fundamentals of Power System Protection, by
Y.G. Paithankar and S.R. Bhide
RECOMMENDED READING
Protection of Electricity Distribution Networks,
3rd Edition, Juan M. Gers and Edward J. Holmes
64
VECTOR GROUP OF 3-PHASE TRANSFORMER
Determine the vector group of each transformer connection below.
65
VECTOR GROUP OF 3-PHASE TRANSFORMER
Determine the vector group of each transformer connection below.
66
VECTOR GROUP OF 3-PHASE TRANSFORMER
Determine the vector group of each transformer connection below.
C A b
B
C B
a 72