GENERAL INFORMATION
The insulation resistance monitor is intended to monitor the insulation resistance to ground of AC lines.
And th issue an alarm signal if the insulation resistance goes below a predetermined value. The insulation
resistance monitor is an electronic insulation detecting device with elecromechanical relay contact output.
The AC monitor permits a connection of an external meter is not to affect the detecting operation of the
monitor. Please select-up the Models as follows :
SPECIFICATIONS
GENERAL TABLE
I 1-1
MODEL
Auxiliary control voltage
Norminal Variations
Insulation resistance setting
12 step value is selectable I detecting
line voltage I
DETECTION ACCURACY
NOTE
The dead band refers to the difference in % of the set value between the pickup value and the drop out
value. The pickup value is a value at which the monitor turns to an operate state and drop value is a value
at which the monitor is reset to a non-operate state. In other words, the dead band is reset hysteresis.
The detection accuracy is the maximum deviation if the actual pickup value from the nomical set value.
DIELECTRIC STRENGTH : 2.5KV between electric circuit (T.B #8) and enclosure for 1min.
MONITOR OPERATION CHECK : A test circuit that applies a short or a dummy resistance
less than the set value across each test terminals and
ground terminals is to be provided by the user for
monitor operation check.
OPERATION TIME DELAY : 3.0 sec (f0.5 sec) definite time delay, reset time delay is 0.5 sec or less.
0 OPERATION TEMPERATURE RANGE : -20°C - +60°C
0 STORAGE TEMPERATURE RANGE : -40°C - +65"C
0 VIBRATION : The monitor is so constructed that it will withstand applications of the following
vibration for 2 hours in each X, Y and Z diractions : - for vibration frequency from 2
to 13.2Hz, 2mm double amplitude, for vibration frequencies 13.2 to 1OOHz.
KS - 6e option 72 x 72
SCALE RANGE
SCALE RANGE REMARKS
( % of indicated value )
0.05MP - 1MP f 5%
Operating temprature range
outside of above :
less than 0.05MP and
- 20 "C - + 60 "C
more than 1MP :
INSTRUCTION MANUAL ( FOR SBAG-1021202 )
GENERAL
This insulation resistance monitor consists of a meter and a power box monitor the insulation level of a
non-frounded AC electrical system.
MONITOR
The monitor convers 110V or 220V AC power into regulated DC power. The DC output voltage is
constant over an AC input voltage of 80% to 120% of the rating (110v/220V).
I t s DC output circuit is electrically isolated from the AC input circuit by means of a transformer.
FEATURES
This insulation resistance monitor features :
a. continuous monitoring of insulation level.
b. provision for low insulation level alarm, output contact can be used as either alarm m a k e or
alarm b r e a k signal.
c. error - free stable operation, use of voltage regulator circuits in both meter and relay sections.
CONNECTION
Non-grounded 1 0 , 3 0 line
-
-
ALARM SIGNAL
CONTACT
,............. -.
ltest
-
.......:
* The terminal (#a) of the monitor may be connected to any of the lines 'R', 'S' or 'T'.
* The power transformer (P.T) os not necessary when the monitored system operates on A.C 1101220V
and the input power may be obtained from across any two lines of the monitored system.
note :
Rev~s~on Date Checked Approved
Rev. No,
LFD-1 OP
C11
INPUT
MAST ALARM
ACES-264V
I I
I I
EMCY STOP
TRIP CIRCUIT
1 EMCY STOP
TRIP CIRCUIT
EMCY STOP
TRIP CIRCUIT
EMCY STOP
TRIP CIRCUIT
EMCY STOP
TRIP CIRCUIT
EMCY STOP
TRIP CIRCUIT
I I
EMCY STOP
SWITCH BOX SWBD SIDE