0% found this document useful (0 votes)
115 views9 pages

Manual Instruction For Induce Jet Fans IJA IJB & IJC II

This document provides instructions for the storage, installation, operation, and maintenance of Kruger Axial (IJA, IJB) and Cased Centrifugal (IJC II) Induced Jet Fan models. It outlines proper receiving and handling to avoid damage. Installation instructions include proper location and electrical wiring. Start-up procedures include a checklist and information on monitoring during initial operation. Troubleshooting tips are provided for issues like abnormal noise, vibration, lack of thrust, and failure to start.

Uploaded by

SAI HVAC SYSTEM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views9 pages

Manual Instruction For Induce Jet Fans IJA IJB & IJC II

This document provides instructions for the storage, installation, operation, and maintenance of Kruger Axial (IJA, IJB) and Cased Centrifugal (IJC II) Induced Jet Fan models. It outlines proper receiving and handling to avoid damage. Installation instructions include proper location and electrical wiring. Start-up procedures include a checklist and information on monitoring during initial operation. Troubleshooting tips are provided for issues like abnormal noise, vibration, lack of thrust, and failure to start.

Uploaded by

SAI HVAC SYSTEM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

IGB048.

E2/2007

General Instructions

(Induced Jet Fan)

IJA, IJB, IJC II


1 INTRODUCTION

Kruger Axial (IJA, IJB) and Cased Centrifugal (IJC II) Induced Jet Fan is special
design fan to achieve high impulse throw of discharging air. IJA & IJB fan consists of an
attenuator at the suction and discharge side, pre-designed inlet & outlet guide vane.
Kruger Induced Jet Fans are also tested and certified by TUV SUB PSB Pte Ltd in
compliance with the requirement of Standard EN 12101-3: 2015 for the following
temperature ratings;

Class Ff250 (250ºC for 120 mins)


Class F300 (300ºC for 60 mins)
Class Ff300 (300ºC for 120 mins)
Class F400 (400ºC for 120 mins)

Kruger Induced Jet Fans has been manufactured to the rigorous standards of production
and quality control in accordance with the International Quality Standards ISO 9001. All
components have been checked and tested at the end of the manufacturing process.

The purpose of this manual is to aid the user in the proper storage, installation,
operation and maintenance procedure to ensure maximum equipment life and trouble
free operation. These instructions are intended to supplement good general practices
and are not intended to cover detailed instruction procedures.

Handling and maintenance should always be performed by experienced and trained


personnel or technician.

2 RECEIVING, HANDLING AND STORAGE

Rough handling during shipment and improper storage can cause damage that is not
noticeable until the fan is in operation. This can be avoided with proper storage and
handling techniques.

Fan should be hoisted with slings placed around the fan housing. Touch up the scratch
coated surfaces during lifting, to prevent corrosion to occur at this area. Store the fan in
a clean and dry place, preferably indoor to ensure fan shaft, bearing and fan casing are
protected against dust and corrosion. Do not store the fan in a location where it will be
subjected to vibration. This can cause the internal surface to rub against each other and
damage the bearings.

1
3 INSTALLATION

1) Induced Jet fans are shipped mostly assembled, however final checking and
adjustments are required prior to hanging the fans to the ceiling.
2) Induced Jet fans should be installed close to the ceiling but below the beam and
free any obstruction at the inlet and discharge.
3) Induced Jet fans shall be installed to its proper location and position in accordance
to the final drawing used in the CFD simulation.
4) All electrical work must be done in accordance with all applicable electrical codes,
by a qualified electrician.
5) Connect the power termination in accordance to the motor nameplate and supply
voltage. Wiring diagram is shown in Section 3.2.
6) Ensure that the fan impeller rotates freely.

3.1 Installation Method

2
3.2 Wiring Diagram

Jet fans are installed with a single speed or 2 speeds motor.

3.3 Vibration Isolator Installation

1) Select proper isolator.


(Spring Isolator can be selected from Kruger selection program or isolator
catalogue)
2) Adjust deflection based on the selected isolator.
3) Maintain the operating / free height at the same level through step 2.
(The entire assembly must be levelled)
4) Check all the deflection and operating / free height is properly maintained.

3
4 START-UP

4.1 Start-up Checklist

Before putting any fan into the initial operation the manufacturer’s instruction must be
followed. Complete the following checklist to make sure the fan is ready to run.

 Lock out the primary and all secondary power sources.


 Make sure that all fasteners and screws are properly tighten.
 Spin impeller to see whether it rotates freely and is not grossly out of balance.
 Inspect impeller for correct rotation for the fan design.
 Make sure the inlet (and outlet for IJA & IJB only) protection nets are properly
installed & fastened.
 Switch on the electrical supply and allow the fan to reach full speed.
 Check carefully for:
1. Direction of rotation
2. Excessive vibration
3. Unusual noise
4. Proper amperage and voltage values

If any problem is arises, SWITCH OFF IMMEDIATELY. Lock out electrical supply, check
carefully for the cause of trouble and correct as necessary.

4.2 Start-Up

The fan may now be put into operation but during the first 8 hrs of running, it should be
periodically observed and checked for excessive vibration and noise. Checks should be
made of motor input current and motor & bearing temperature to ensure that they do
not exceed manufacturer’s recommendation. After 8 hrs of operation, the fan should be
shut down to check the following items: -

1. Hanger, screws and bolts


2. Impeller condition
3. Motor alignment
4. Motor temperature

4
5 TROUBLE-SHOOTING

5.1 Fan is developing or emitting abnormal or excessive noise

Problem Possible Cause Remedy


1) Lean-in cable not secure 1) Fasten the cable properly
2) Noisy motor bearings 2) Replace bearings
3) Single phasing a 3 phase motor 3) Check power supply
Motor 4) Low voltage 4) Check power supply
5) Cooling fan striking shroud 5) Check motor assembly
6) Electromagnetic fault in motor 6-8) Replace motor
7) AC hum in motor or relay
8) Starting relay chatter

1) Impeller loose on shaft 1) Tighten impeller


Fan 2) Impeller unbalance 2) Balance impeller
Components 3) Impeller not in center 3) Adjust impeller to center
4) Blade broken/damaged 4) Replace blades
IJC II Only: IJC II Only:
5) Impeller in contact with inlet 5) Correct inlet cone position
cone
6) Impurities or foreign material 6) Clean inside fan and impeller
inside fan housing

5.2 Fan is vibrating excessively

Problem Possible Cause Remedy


1) Impeller unbalanced due to 1) Clean impeller, rebalance the
Impeller deposits (dirt or grease) fan
2) Impeller unbalanced due to 2) Replace impeller
wear

5
5.3 Required thrust not achieved

Problem Possible Cause Remedy


1) Impeller/inlet dirty or clogged 1) Clean the impeller or inlet
2) Improper running clearance / 2) Change to correct clearance
inlet cone to impeller fit
3) Impeller installed or running at 3) Change to correct rotation by
Impeller wrong direction changing poles of electrical
feed line to motor
4) Incorrect speed of impeller 4) Change to correct speed:
because of:
i) Wrong motor speed i) Change motor
ii) Wrong calibration of inverter ii) Adjust inverter calibration
IJA & IJB Only: IJA & IJB Only:
5) Improper blade setting 5) Adjust to correct angle

1) Obstructions near fan outlet or 1) Clear obstruction / review CFD


System inlet simulation fan positioning

5.4 Fan does not start or operate

Problem Possible Cause Remedy


1) Blown fuses 1) Check fuses/circuit breakers
2) Electricity turned off 2) Check for switched off or
Electrical disconnected
Supply 3) Wrong voltage 3) Check for correct power supply
4) Failure of one or two phases 4) Check for correct power supply
5) Low voltage, excessive line 5) Check for correct wire size
drop or inadequate wire size

1) Motor not correctly connected 1) Connect the motor according to


the motor label
2) Load inertia too large for motor 2) Change motor
Motor 3) Motor protection unit or switch 3) Reduce temperatures, check
are stopping as temperature and change insulation class,
are too high increase motor rating
4) Motor too small and overload 4) Change motor
protector has broken circuit

6
5.5 High power absorption

Problem Possible Cause Remedy


Impeller 1) Blade angle/wheel rotation not 1) Adjust blade angle/wheel
set properly rotation

1) Faults in the motor windings 1) Replace motor


Motor 2) Motor power supply voltage 2) Check with motor supplier
lower than the value indicated
on the identification plate

1) Calculated horsepower 1) Check selection


requirements based on lower
air density (e.g. High
Gas Density temperature) but actual air
density is higher
(e.g. Cold start up)

6 ROUTINE MAINTENANCE

Maintenance should always be performed by experienced and trained personnel. Do not


attempt any maintenance on a fan unless the electrical supply has been locked out or
tagged out and the impeller has been secured.

Under normal circumstances, handling clean air, the system should require cleaning only
about a Year. However, the fan and system should be checked at regular intervals to
detect any unusual accumulation.

The fan impeller should be specially checked for build-up of material or dirt which may
cause an Imbalance with resulting undue wear on bearings and belt drives. A regular
maintenance program should be established as needed to prevent material build-up.

Periodic inspection of the rotating assembly must be made to detect any indication of
weakening of the rotor because of corrosion, erosion, or metal fatigue.

7
KRUGER GROUP (VENTILATION)

• THAILAND (Regional HQ) • AUSTRALIA


KRUGER VENTILATION INDUSTRIES ASIA CO. LTD. S&P-KRUGER AUSTRALIA PTY LTD
30/159 Moo 1, Sinsakorn Industrial Estate, 2 Cunningham St, Moorebank N.S.W. 2170
Chetsadawithi Road, Khok Kham Mueng, Samuthsakorn 74000, Thailand Tel. +61 2-98227747
Tel. +662 1054298 - Fax +662 0248256-9 Fax. +61 2-98227757
Website: www.krugerfan.com Email: [email protected]

· CHINA ( BEIJING) • CHINA (GUANGZHOU)


BEIJING KRUGER VENTILATION CO. LTD GUANGZHOU KRUGER VENTILATION CO. LTD
Level 7, A Block, Rising International Building, 29 JingHai San Road, BDA, No. 9 Huahui Road, Huashan, Huadu,
Beijing, P.R.China 100176 Guangzhou, P.R. China 510880
Tel. +86 10-67881366 - Fax +86 10-67880566 Tel. +86 20-66356635 - Fax +86 20-86786001/86786500
Email: [email protected] Email: [email protected]

· CHINA (SHANGHAI) • CHINA (TIANJIN)


SHANGHAI KRUGER VENTILATION CO. LTD TIANJIN KRUGER VENTILATION CO. LTD
No. 500 Yuanguo Road, Anting, Jiading, No.168 Anyuan Road, Jingjin Science and Technology Park
Shanghai 201814 P.R. China Wuqing District, Tianjin, China
Tel. +86 21-69573266 - Fax +86 21-69573296 Tel. +86 22-22143480/3481 - Fax +86 22-22143482
Email: [email protected] Email: [email protected]

• CHINA (WUHAN) • DUBAI


WUHAN KRUGER VENTILATION CO. LTD KRUGER VENTILATION INDUSTRIES, GULF BRANCH
No. 805, Huian Ave, Dongxihu District, Wuhan, Hubei, P.R. China 430000 Jebel Ali Free Zone Area (JAFZA) P.O. Box No. 262949, Dubai, UAE
Tel. +86 27- 83248840/83060522/83097505 Tel. +971 4 8819188/8832017
Fax +86 27- 83261886 Fax. +971 4 8832018
Email: [email protected] Email: [email protected]

• HONG KONG • INDIA


KRUGER VENTILATION (HONG KONG) LIMITED KRUGER VENTILATION INDUSTRIES (INDIA) PVT LTD
Flat C, 9/F, Yeung Yiu Chung (No.8) Industrial Building, Kruger Centre, Mumbai-Nasik Highway,
20 Wang Hoi Road, Kowloon Bay, Kowloon, Hong Kong Kalamgaon, Shahapur, Thane 421601, Maharashtra, India
Tel. +852 22469182 - Fax +852 22469187 Tel. +91 9960558899/9975577211 - Fax +91 2527 240075
Email: [email protected] Email: [email protected]

• INDIA (NORTH) • INDONESIA


KRUGER VENTILATION INDUSTRIES (NORTH INDIA) PVT LTD P.T. KRUGER VENTILATION INDONESIA
Plot No. - 191, Sector - 59, Ballabgarh, Faridabad - 121 004, Haryana, India JL. Teuku Umar No.20,
Tel. +91-9958991660/9717449696 Karawaci - Tangerang 15115, Indonesia
Fax. +91-1294135820 Tel. +62 21-5512288/5513557 - Fax +62 21-5513502
Email: [email protected] Email: [email protected]

• KOREA • MALAYSIA
NEOMATE CO. LTD KRUVENT INDUSTRIES (M) SDN BHD
2-1010, Ace High Tech City B/D, 775 Gyeongin-ro, Lot 850, Jalan Subang 7, Taman Perindustrian Subang,
Yeongdeungpo-gu, Seoul, Korea. Postal Code 07299 47500, Subang Jaya, Selangor D.E.
Tel. +82-2-2679-2052 - Fax. +82-2-2679-2174 Tel. +603 80743399 - Fax +603 80743388
Email: [email protected] Email: [email protected]

• MYANMAR • PHILIPPINES
KRUGER VENTILATION (MYANMAR) CO.LTD KRUGER M&E INDUSTRIES CORPORATION
Room No. F21, Thiri Yadanar Whole Sale Market, (Htawunbe) FAPI Compound, E. Rodriguez Ave.
Toe Chae Ward, North Okkalapa Township, Yangon. Tunasan, Muntinlupa City 1773, Philippines
Tel. +959 763141081/2/3 Tel. +63 2-8622892/4/6/7, 5534059 - Fax +63 2-8622891
Email: [email protected] Email: [email protected]

• SINGAPORE • TAIPEI
KRUGER ENGINEERING PTE LTD KRUGER VENTILATION (TAIWAN) CO. LTD
No. 10 Buroh Street #06-06, West Connect Building, No. 157, Ping-an Rd, Hengfeng Village,
Singapore 627564 Dayuan Shiang Taoyuan County 337, Taiwan
Tel. +65 68631191 - Fax +65 68631151 Tel. +886 3-3859119 - Fax +886 3-3859118
Email: [email protected] Email: [email protected]

• THAILAND • VIETNAM
KRUGER VENTILATION IND. (THAILAND) CO. LTD KRUGER VENTILATION INDUSTRIES (VIETNAM) CO. LTD
30/105 Moo 1, Sinsakorn Industrial Estate, Lot A7. 2-4, C2 Road, Thanh Thanh Cong IZ,
Chetsadawithi Road, Khok Kham Mueng, Samuthsakorn 74000, Thailand Trang Bang Dist. Tay Ninh Province, Vietnam
Tel. +662 1050399 - Fax + 662 1050370-2 Tel. +84-276 3585200/01/02 - Fax +84-276 3585199
Email: [email protected] Email: [email protected]

You might also like