it is not anticipated that the AC grid will be replaced by a DC power grid in the future.
There are two major reasons for this:
First, the control and protection of MTDC systems is complex and the inability of
voltage transformation in dc networks imposes economic penalties.
Second, the advances in power electronics technology have resulted in the
improvement of the performance of AC transmissions using FACTS devices, for instance
through introduction of static VAR systems, static phase shifters, etc.
Types of HVDC Links
Three types of HVDC Links are considered in HVDC applications which are
Monopolar Link:
A monopolar link as shown in the above figure has one conductor and uses either
ground and/or sea return. A metallic return can also be used where concerns for harmonic
interference and/or corrosion exist. In applications with DC cables (i.e., HVDC Light), a
cable return is used. Since the corona effects in a DC line are substantially less with
negative polarity of the conductor as compared to the positive polarity, a monopolar link
is normally operated with negative polarity.
Bipolar Link:
A bipolar link as shown in the above figure has two conductors, one positive and the
other negative. Each terminal has two sets of converters of equal rating, in series on the DC
side. The junction between the two sets of converters is grounded at one or both ends by the
use of a short electrode line. Since both poles operate with equal currents under normal
operation, there is zero ground current flowing under these conditions. Monopolar operation
can also be used in the first stages of the development of a bipolar link. Alternatively, under
faulty converter conditions, one DC line may be temporarily used as a metallic return with
the use of suitable switching.
Homopolar Link:
In this type of link as shown in the above figure two conductors having the same
polarity (usually negative) can be operated with ground or metallic return.
Due to the undesirability of operating a DC link with ground return, bipolar links
are mostly used. A homopolar link has the advantage of reduced insulation costs, but the
disadvantages of earth return outweigh the advantages.
Technical Performance:
Due to its fast controllability, a DC transmission has full control over transmitted
power, an ability to enhance transient and dynamic stability in associated AC networks
and can limit fault currents in the DC lines. Furthermore, DC transmission overcomes
some of the following problems associated with AC transmission.
Stability Limits:
The power transfer in an AC line is dependent on the angle difference between the
voltage phasors at the two line ends. For a given power transfer level, this angle increases
with distance. The maximum power transfer is limited by the considerations of steady
state and transient stability. The power carrying capability of an AC line is inversely
proportional to transmission distance whereas the power carrying ability of DC lines is
unaffected by the distance of transmission.
Voltage Control:
Voltage control in ac lines is complicated by line charging and voltage drops. The
voltage profile in an AC line is relatively flat only for a fixed level of power transfer
corresponding to its Surge Impedance Loading (SIL). The voltage profile varies with the
line loading. For constant voltage at the line ends, the midpoint voltage is reduced for
line loadings higher than SIL and increased for loadings less than SIL.
The maintenance of constant voltage at the two ends requires reactive power
control as the line loading is increased. The reactive power requirements increase with
line length. Although DC converter stations require reactive power related to the power
transmitted, the DC line itself does not require any reactive power. The steady-state
charging currents in AC cables pose serious problems and make the break-even distance
for cable transmission around 50kms.
Line Compensation:
Line compensation is necessary for long distance AC transmission to overcome
the problems of line charging and stability limitations. The increase in power transfer and
voltage control is possible through the use of shunt inductors, series capacitors, Static
Var Compensators (SVCs) and, lately, the new generation Static Compensators
(STATCOMs). In the case of DC lines, such compensation is not needed.
Problems of AC Interconnection:
The interconnection of two power systems through ac ties requires the automatic
generation controllers of both systems to be coordinated using tie line power and
frequency signals. Even with coordinated control of interconnected systems, the
operation of AC ties can be problematic due to:
The presence of large power oscillations which can lead to frequent tripping,
1. Increase in fault level, and
2. Transmission of disturbances from one system to the other.
The fast controllability of power flow in DC lines eliminates all of the above
problems. Furthermore, the asynchronous interconnection of two power systems can only
be achieved with the use of DC links.
Ground Impedance:
In AC transmission, the existence of ground (zero sequence) current cannot be
permitted in steady-state due to the high magnitude of ground impedance which will not
only affect efficient power transfer, but also result in telephonic interference. The ground
impedance is negligible for DC currents and a DC link can operate using one conductor
with ground return (monopolar operation).
The ground return is objectionable only when buried metallic structures (such as
pipes) are present and are subject to corrosion with DC current flow. While operating in
the monopolar mode, the AC network feeding the DC converter station operates with
balanced voltages and currents. Hence, single pole operation of dc transmission systems
is possible for extended period, while in AC transmission, single phase operation (or any
unbalanced operation) is not feasible for more than a second.
Disadvantages of DC Transmission:
The scope of application of DC transmission is limited by
1. High cost of conversion equipment.
2. Inability to use transformers to alter voltage levels.
3. Generation of harmonics.
4. Requirement of reactive power and
5. Complexity of controls.
Over the years, there have been significant advances in DC technology, which
have tried to overcome the disadvantages listed above except for (2). These are
1. Increase in the ratings of a thyristor cell that makes up a valve.
Reliability:
The reliability of DC transmission systems is good and comparable to that of AC
systems. The reliability of DC links has also been very good.
There are two measures of overall system reliability-energy availability and
transient reliability.
Energy availability:
Energy availability = 100 (1 – equivalent outage time) %
Actual time
Where equivalent outage time is the product of the actual outage time and the
fraction of system capacity lost due to outage.
Transient reliability:
This is a factor specifying the performance of HVDC systems during recordable
faults on the associated AC systems.
Transient reliability = 100 X No. of times HVDC systems performed as designed
No. of recordable AC faults
Recordable AC system faults are those faults which cause one or more AC bus
phase voltages to drop below 90% of the voltage prior to the fault.
Both energy availability and transient reliability of existing DC systems with
thyristor valves is 95% or more.
1.1 Introduction
Electric power transmission was originally developed with direct current. The
availability of transformers and the development and improvement of induction motors
at the beginning of the 20th century, led to the use of AC transmission.
DC Transmission now became practical when long distances were to be covered
or where cables were required. Thyristors were applied to DC transmission and solid state
valves became a reality.
With the fast development of converters (rectifiers and inverters) at higher voltages
and larger currents, DC transmission has become a major factor in the planning of the
power transmission. In the beginning all HVDC schemes used mercury arc valves,
invariably single phase in construction, in contrast to the low voltage polyphase units
used for industrial application. About 1960 control electrodes were added to silicon
diodes, giving silicon-controlled-rectifiers (SCRs or Thyristors).
Today, the highest functional DC voltage for DC transmission is +/- 600kV. D.C
transmission is now an integral part of the delivery of electricity in many countries
throughout the world.
In large interconnected systems, power flow in AC ties (particularly under
disturbance conditions) can be uncontrolled and lead to overloads and stability problems
thus endangering system security. Strategically placed DC lines can overcome this
problem due to the fast controllability of DC power and provide much needed damping
and timely overload capability. The planning of DC transmission in such applications
requires detailed study to evaluate the benefits. Example is the Chandrapur-Padghe link
in India.
Presently the number of DC lines in a power grid is very small compared to the
number of AC lines. This indicates that DC transmission is justified only for specific
applications. Although advances in technology and introduction of Multi-Terminal DC
(MTDC) systems are expected to increase the scope of application of DC transmission,
it is not anticipated that the AC grid will be replaced by a DC power grid in the future.
There are two major reasons for this:
First, the control and protection of MTDC systems is complex and the inability of
voltage transformation in dc networks imposes economic penalties.
Second, the advances in power electronics technology have resulted in the improvement
of the performance of AC transmissions using FACTS devices, for instance through
introduction of static VAR systems, static phase shifters, etc.
Need for HVDC Systems
For long-distance transmission, HVDC systems may be less expensive and suffer
lower electrical losses. For underwater power cables, HVDC avoids the heavy currents
required to charge and discharge the cable capacitance each cycle. For shorter distances,
the higher cost of DC conversion equipment compared to an AC system may still be
warranted, due to other benefits of direct current links.
HVDC allows power transmission between unsynchronized AC transmission
systems. Since the power flow through an HVDC link can be controlled independently
of the phase angle between source and load, it can stabilize a network against disturbances
due to rapid changes in power. HVDC also allows transfer of power between grid systems
running at different frequencies, such as 50 Hz and 60 Hz. This improves the stability
and economy of each grid, by allowing exchange of power between incompatible
networks.
Brief History
HVDC technology first made its mark in the early under-sea cable interconnections
of Gotland (1954) and Sardinia (1967), and then in long distance transmission with the
Pacific Intertie (1970) and Nelson River (1973) schemes using mercury-arc valves. A
significant milestone occurred in 1972 with the first Back to Back (BB) asynchronous
interconnection at Eel River between Quebec and New Brunswick; this installation also
marked the introduction of thyristor valves to the technology and replaced the earlier
mercury-arc valves.
The first 25 years of HVDC transmission were sustained by converters having
mercury arc valves till the mid-1970s. The next 25 years till the year 2000 were sustained
by line-commutated converters using thyristor valves. It is predicted that the next 25 years
will be dominated by force-commutated converters . Initially, this new force-commutated
era has commenced with Capacitor Commutated Converters (CCC) eventually to be
replaced by self-commutated converters due to the economic availability of high power
switching devices with their superior characteristics.
The first commercially used HVDC link in the world was built in 1954 between
the mainland of Sweden and island of Gotland. Since the technique of power
transmission by HVDC has been continuously developed.
In India, the first HVDC line in Rihand-Delhi in 1991 i.e. I 500 KV, 800 Mkl, 1000
KM. In Maharashtra in between Chandrapur & Padaghe at 1500 KV & 1000 MV. Global
HVDC transmission capacity has increase from 20 MW in 1954 to 17.9 GW in 1984.
Now the growth of DC transmission capacity has reached an average of 2500 MW/year.
Table 1.1 List of HVDC Projects in India.
No. of
Connecting Commissioned Power AC DC Mode Of Length Of
S.No Project Name Poles/
Region On Rating Voltage Voltage Operation Line
Blocks
1. December 1500
Rihand-Dadri ER-WR 400 KV 500 KV Bipole 2 816 Km
1991 MW
2. 2000
Talcher-Kolar ER-SR June 2003 400 KV 500 KV Bipole 2 1369 Km
MW
3.
Pole1: March
Ballia- 2010 2500
ER-NR 400 KV 500 KV Bipole 2 780 Km
Bhiwadi Pole 2: March MW
2011
4. Chandrapur 1500
CR-WR 1999 400 KV 500 KV Bipole 2 752 Km
Padge MW
5. Mundra- 1500
WR-NR 2012 400 KV 500 KV Bipole 2 986 Km
Mohindergarh MW
6. Bishwanath- 6000 Multi-
NER-ER 2015 400 KV 800 KV 2 1728 Km
Agra MW Terminal
7. 2x250 Back To
Vidhyanchal WR-NR April 1989 400 KV 70 KV 2 -
MW Back
8. December 2x500 Back To
Chandrapur WR-SR 400 KV 205 KV 2 -
1997 MW Back
9. September 1x500 Back To
Sasaram ER-SR 400 KV 205 KV 2 -
2002 MW Back
Block
1: 205
2x500 KV Back To
10. Gazuwaka ER-SR March 2005 400 KV 2 -
MW Block Back
2: 177
KV
Converter Unit:
This usually consists of two three phase converter bridges connected in series to form a
12 pulse converter unit as shown in above figure. The total number of valves in such a
unit is twelve.
The main function of the VSC-HVDC is to transmit constant DC power from the
rectifier to the inverter. As shown in Figure.1, it consists of dc-link capacitors Cdc,
two converters, passive high-pass filters, phase reactors, transformers and dc cable.
2. Converters
The converters are VSCs employing IGBT power semiconductors, one operating
as a rectifier and the other as an inverter. The two converters are connected either
back-to-back or through a dc cable, depending on the application.
3. Transformers
Normally, the converters are connected to the ac system via transformers. The
most important function of the transformers is to transform the voltage of the ac
system to a value suitable to the converter. It can use simple connection (two-
winding instead of three to eight-winding transformers used for other schemes). The
leakage inductance of the transformers is usually in the range 0.1-0.2p.u.
4. Phase Reactors
The phase reactors are used for controlling both the active and the reactive power
flow by regulating currents through them. The reactors also function as ac filters to
reduce the high frequency harmonic contents of the ac currents which are caused by
the switching operation of the VSCs. The reactors are essential for both active and
reactive power flow, since these properties are determined by the power frequency
voltage across the reactors. The reactors are usually about 0.15p.u. Impedance.
5. AC Filters
The ac voltage output contains harmonic components, derived from the switching
of the IGBTs. These harmonics have to be taken care of preventing them from being
emitted into the ac system and causing malfunctioning of ac system equipment or
radio and telecommunication disturbances. High-pass filter branches are installed to
take care of these high order harmonics. With VSC converters there is no need to
compensate any reactive power consumed by the converter itself and the current
harmonics on the ac side are related directly to the PWM frequency. The amount of
low-order harmonics in the current is small.
6. Dc Capacitors
On the dc side there are two capacitor stacks of the same size. The size of these
capacitors depends on the required dc voltage. The objective for the dc capacitor is
primarily to provide a low inductive path for the turned-off current and
energy storage to be able to control the power flow. The capacitor also reduces the
voltage ripple on the dc side.
7. Dc Cables
The cable used in VSC-HVDC applications is a new developed type, where the
insulation is made of an extruded polymer that is particularly resistant to dc voltage.
Polymeric cables are the preferred choice for HVDC, mainly because of their
mechanical strength, flexibility, and low weight.
8. IGBT Valves
The insulated gate bipolar transistor (IGBT) valves used in VSC converters are
comprised of series-connected IGBT positions. The IGBT is a hybrid device
exhibiting the low forward drop of a bipolar transistor as a conducting device. A
complete IGBT position consists of an IGBT, an anti parallel diode, a gate unit, a
voltage divider, and a water-cooled heat sink. Each gate unit includes gate-driving
circuits, surveillance circuits, and optical interface. The gate-driving electronics
control the gate voltage and current at turn-on and turn-off, to achieve optimal turn-
on and turn-off processes of the IGBT. To be able to switch voltages higher than the
rated voltage of one IGBT, many positions are connected in series in each valve
similar to thyristors in conventional HVDC valves.
9. AC Grid
Usually a grid model can be developed by using the Thevenin equivalent circuit.
However, for simplicity, the grid was modeled as an ideal symmetrical three-phase
voltage source.
HVDC Circuit breakers & Operating problems
Circuit breakers will be positioned on DC grids and act when a fault occurs.
Breakers would have to fulfill some basic requirements. Current zero crossing should
be created to interrupt the current once a fault occurs. At the same time the energy
that is stored in the system’s inductance should be dissipated and the breaker should
withstand the voltage response of the network.
There are two types of HVDC circuit breakers: electromechanical and solid-state.
Electromechanical can be grouped into three categories: (1) inverse voltage generating
method, (2) divergent current oscillating method, and (3) inverse current injecting
method. Only the inverse current injecting method can be used in high voltage and
current ratings. In this type of breaker, current zero can be created by superimposing
an inverse current (of high frequency) on the input current by dis-charging a capacitor
(that was pre- charged) through an inductor. (Explained on next section) The cost of
components required for an electromechanical DC circuit breaker would not be
significantly higher than that of an AC circuit breaker. Electromechanical HVDC
circuit breakers are available up to 500 kV, 5 kA and have a fault-clearing time of the
order of 100 ms.
Solid-state circuit breakers are the second type of HVDC breakers. These
breakers can interrupt current much faster (which is required in some cases) than
electromechanical circuit breakers, having an interruption time of a few milliseconds.
They are based on Integrated Gate Commutated Thyristors (IGCT), which compared
to IGBT (bipolar thyristors) have lower on-state losses. Current flows through the
IGCT and in order to interrupt, the IGCT is turned off. Once that happens, voltage
quickly increases until a varistor (that is in parallel to the thyristor) starts to conduct.
The varistor is designed to block voltages above the voltage level of the system. The
main disadvantages of these types of circuit breakers are the high on-state losses and
the capital costs.Typical ratings of solid-state circuit breakers in operation are 4 kV, 2
kA, although in ratings of up to 150 kV, 2 kA were considered.
If the capacitor voltage exceeds a given value, which is chosen to be the voltage
capability of the circuit breaker, the energy absorption path will act causing the current
to decrease.
If SCR is less than 3, the AC system is said to be weak. The conventional constant
extinction angle control may not be suitable for weak AC systems.
Constant reactive current control or AC voltage control may overcome some of the
problems of weak AC systems. The power modulation techniques used to improve
dynamic stability of power systems will have to be modified in the presence of weak AC
systems.
Six Pulse Converters
The conversion from AC to DC and vice-versa is done in HVDC converter stations
by using three phase bridge converters. The configuration of the bridge (also called
Graetz circuit) is a six pulse converter and the 12 pulse converter is composed of two
bridges in series supplied from two different (three-phase) transformers with voltages
differing in phase by 30o.
In a series connected system, the current is set by one converter station and is
common for all the stations. The remaining stations operate at constant angle
(extinction or delay) or voltage control. In order to minimize the reactive power
requirements and the losses in valve damper circuits, the normal operating values of
firing angles may be adjusted using tap changer control. At all times, the sum of the
voltages across the rectifier stations must be larger than the sum of the voltages across
the inverter station. In case of a drop in the voltage at the current controlling rectifier
station, the inverter with the larger current reference takes over the current control.
The switching in or out of a bridge is accomplished by deblocking/block and bypass
in a manner similar to that in a two terminal system. The clearing of a fault in the DC
line is also similar. The power reversal at a station is also done as in a two terminal
system, by reversing the DC voltage by converter control.
The power control in a two terminal system is accomplished by adjusting the current
while trying to maintain a constant voltage in the system. This is done to minimize the
losses. However, in a MTDC series system, central control would be required to adjust
the current in response to changing loading conditions. The local control of power
would imply adjusting voltage at the converter station using angle and tap controls.
Using only one bridge or a 12 pulse unit for the voltage control and operating the
remaining bridges at minimum (or maximum) delay angle can reduce the reactive
power requirements.
links are capable of carrying the required power (with increased losses). Evidently, a
mesh system can be more reliable than a radial system. An example of a 4 terminal
mesh system is shown in Figure 1.7.3
The power reversal in a parallel MTDC system would involve mechanical switching
as the voltage cannot be reversed. Also, loss of a bridge in one converter station would
require either the disconnection of a bridge in all the stations or disconnection of the
affected station.
Comparison of Series and Parallel MTDC Systems
The advantages and disadvantages of series and parallel MTDC systems are given
below:
1. High speed reversal of power is possible in series systems without mechanical
switching. This is not possible in parallel systems.
2. The valve voltage rating in a series system is related to the power rating, while
the current rating in a parallel connected system is related to power. This would
imply that for small power ratings of the tap, series connection may be cheaper
even though valves have to be insulated for full voltage to ground. The parallel
connection has the advantage of staged development in the converter stations by
adding parallel converters as the power requirements increase.
3. There are increased losses in the line and valves in series systems, in comparison
to parallel systems. The system operation in series systems can be optimized by
operating current due to frequency control can be as low as 10% of the rated current. This
increases the voltage rating of the series tap. (ii) A series tap in inverter operation reduces
voltage at the main inverter terminal, requiring increased extinction angles. This is
harmful to mercury arc valves as the probability of arc-through increases.
Commutation failure at Corsica can result in overcurrents of 7 p.u. Smoothing
reactors of 2.5H are chosen to limit the overcurrents due to disturbances in the AC
system.
Quebec-New England link from Radisson in Quebec to Sandy Pond in
Massachusetts with a converter at Nicolet became operational in 1992 with two inverters
and one rectifier of capacity 2250 MW. While it was planned to integrate an existing
two terminal HVDC link (from Des Canton to Comerford) with this system to form a 5
terminal MTDC system, this plan was dropped. Other plans to introduce MTDC system
was also shelved. The setback to planning for MTDC was primarily due to the inadequate
preparation in the development of control and protection concepts required for reliable
system operation.